emprical and rational design

Upload: calvin-copeling

Post on 08-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/6/2019 Emprical and Rational Design

    1/6

    Foundations

    Empirical rulesWalls forming the structural system must be placed centrally on foundation, and soils

    should be not heaving, clay or collapsing.

    Concrete use must have a compressive of not less than 10MPa at 28 days, which is mixed1 part cement, 4 parts sand and 5 parts aggregate

    With continuous Strip foundation the diameter must not be less than 200 mm, and the

    width is to be not less than 600 mm with masonry walls, and 400 mm with timber framedstructures

    When strip foundations are at more than one level, the upper portion and must extend

    over the lower portion to at least the thickness of the foundation, using the same strength

    of concreteWhere the floor slab is thickened to form the foundation, the thickness must be not be les

    than the thickness required for a strip foundation, width of the thickened portion must not

    be less than required thickness of a strip foundation

    PiersWhere piers are used built into the wall, the thickness of the foundation must be the same

    for the wall. The foundation must project at least 200 mm beyond the pier

    Rational rules

    When foundations are required for heaving, heaving clay or collapsing soils aprofessional engineer

    To determine the compressive strength, test must be carried out

    Floors

    The floor must be supported by well compacted ground or on suitable filling and to be

    constructed from an imperious layer not more than 40 mm thick composed of slate, rock

    or brick or concrete slab with a compressive strength of not less 10mPA at 28 days,composed of 1 part concrete, 5 parts arrogate and 4 parts sand

    concrete must be used in the construction of water resistant floors

    in the construction of Timber Suspended floor, the boards must be places at least no less

    than 550 mm from the ground, providing an area for ventilation.

    under floor membrane

    should not be less than 0.25 mm thick and paved on a surface free from sharp objectsIt must be turned up on the at least the thickness of the slab on the perimeter

    Joints must be sealed by overlapping sheets by at least 150 mm

    Walls

  • 8/6/2019 Emprical and Rational Design

    2/6

    empirical

    Empirical rules for walls

    Complies to walls that are internal, external , structural, non structural, parapet, free

    standing or retaining

    Masonry walls, that are load bearing must transfer resist loads and transfer these to the

    ground, via the foundations

    A non structural wall is where the masonry is used a sinfill or classing and does notexceed 25 m in height. In the case of a parapert wall, its thickness should not be less than

    one fifth its height. . Non structural walls may be exposed to forces other than their own

    weight, such as wind impact on a parapet wall. , its its strength is still of importance.

    Materials

    Minimum

    average

    compressivestrength (MPa)

    Wall type position Solid units Hollow units Class of mortar

    required

    Structural

    (other than

    foundation or

    retaining)

    Single storey

    (internal or

    external)

    7 3.5 II

    Double storey

    (Internal or

    exctrenal0

    10.5 or 14 ** 7 II

    Non structural

    (other than

    parapet,

    balustrade andfree-standing

    wall)

    External 7 3.5 II

    Internal 7 3.5 II

    Free-standing External or

    internal

    10.5 7 II

    Foundation Supporting a

    single storey

    7 3.5 II

    Foundation Supporting a

  • 8/6/2019 Emprical and Rational Design

    3/6

  • 8/6/2019 Emprical and Rational Design

    4/6

    Concrete roofs must not exceed 175mm in thickness when soild, or equivalent mass when

    voided

    wall dimensions

    In regards intersecting walls form the lateral support,

    must be constructed from masonry units and mortar of the same quality and

    strength. Its height must not be less than 80% of the height of the wall it supports,

    its width must not be less than 45% (or 90 mm, whichever is greater) of the wall it

    supports

    Its length must at least one fifth the length of the wall it supports, or one eighththe distance between intersecting walls

    Walls must intersect supporting walls between 60 and 120 degrees

    RationalWhere a masonry pier is used for lateral support

    its perpendicular length must be 3 times the thickness of the wall its width along the length of the wall must at least twice the thickness of the wall

    must be at least 80% the length of the wall it is supporting

    Cavity walls

    An external masonry cavity will be between 50 and 110 mm wide

    Wall ties must be evenly spaces at a 2.5 ties per meter sqaured, if the cavity is not morethan 75 mm, if the cavity is more than 75 mm, 3 ties are required per meter square

    foundation wallsfunctions as a retaining wall, must not exceed 1.5m

    The level between the ground and the backfill should not be more than 1m

    The thickness of the walls cant be less than the they carry

    ballustarde walls

    Solid masonry ballustrade wall, must be

    tied to reinforced concrete, brick columns or bonded into return walls or reinforced

    brick piers expansion joints are to be used when neccesary, no further than 8 m apartwhere a wall

    is supportred by comulum and pier (both reinforced)

    Where the structural beams are bonded to the return walls. The return walls must not bespaced more than 6m part when 230 thickness wall, 5m for 190 mm walls and 4m for 110

    Brick ballustrade walls

    Reinforced, consisting od galvanised steel wire not less than 3.5 mm in diameter, in thehighest 4 bed joints. these must overlap at least 150 mm with the supporting column

  • 8/6/2019 Emprical and Rational Design

    5/6

    Except for buildings containing more than 2 dwelligs (H3 classified), but no empirical

    rules govern ballustrades except for materials

    Ballustrade walls must be designed by an engineer or comptetnt person

    Free standing walls

    wall thickness(mm)

    Max height of wall above groudlevel

    Pier

    Without piers with piers Min dimensions max spacing

    (centre tocentre) m

    90 0.8 1.2 290 x 290 1.9

    110 1.0 1.5 350 x 350 2.1

    140 1.3 1.8 340 x 340 2.5

    190 1.5 2.2 390 x 390 2.7

    230 1.8 2.4 470 x 470 3.7230 1.8 2.6 470 x 470

    290 2.2 2.6 490 x 490

    340 2.4

    Roofs

    Empirical rules

    Where the roof is supported by a wall the following apply:

    Miniun height requirements

    In regards to a double pitched roof (Howe, single or douyble pitch span not exceeding10m, and bays no more than 1.5m apart)

    roof

    covering

    truss

    member

    nominal

    timber size(mm)

    max span (m)

    metal and

    fiber-cementsheets

    rafter 38 x 114 3.1 4.6 5.8

    38 x 152 4.0 5.8 7.238 x 228 6.1 8.5 10.0

    tie beam 38 x 114 3.1 4.5 6.2

    38 x 152 4.5 6.4 8.3

    38 x 228 7.1 10.0 10.0

    Concrete

    tiles, clay

    tiles and

    rafter 38 x 114 6.0 9.0 10.0

    38 x 152 8.2 10.0 10.0

    38 x 228 10.0 10.0 10.0

  • 8/6/2019 Emprical and Rational Design

    6/6

    thatch tie beam 38 x 114 4.7 6.7 9.4

    38 x 152 5.9 8.5 10.0

    38 x 228 7.2 10.0 10.0

    metal roof

    tiles

    rafter 38 x 114 6.2 9.0 10.0

    38 x 152 8.0 10.0 10.0

    38 x 228 10.0 10.0 10.0tie beam 38 x 114 4.5 6.7 9.0

    38 x 152 5.9 8.7 10.0

    38 x 228 8.7 10.0 10.0

    all web members need to be at leat 38 x 114