emprical and rational design
TRANSCRIPT
-
8/6/2019 Emprical and Rational Design
1/6
Foundations
Empirical rulesWalls forming the structural system must be placed centrally on foundation, and soils
should be not heaving, clay or collapsing.
Concrete use must have a compressive of not less than 10MPa at 28 days, which is mixed1 part cement, 4 parts sand and 5 parts aggregate
With continuous Strip foundation the diameter must not be less than 200 mm, and the
width is to be not less than 600 mm with masonry walls, and 400 mm with timber framedstructures
When strip foundations are at more than one level, the upper portion and must extend
over the lower portion to at least the thickness of the foundation, using the same strength
of concreteWhere the floor slab is thickened to form the foundation, the thickness must be not be les
than the thickness required for a strip foundation, width of the thickened portion must not
be less than required thickness of a strip foundation
PiersWhere piers are used built into the wall, the thickness of the foundation must be the same
for the wall. The foundation must project at least 200 mm beyond the pier
Rational rules
When foundations are required for heaving, heaving clay or collapsing soils aprofessional engineer
To determine the compressive strength, test must be carried out
Floors
The floor must be supported by well compacted ground or on suitable filling and to be
constructed from an imperious layer not more than 40 mm thick composed of slate, rock
or brick or concrete slab with a compressive strength of not less 10mPA at 28 days,composed of 1 part concrete, 5 parts arrogate and 4 parts sand
concrete must be used in the construction of water resistant floors
in the construction of Timber Suspended floor, the boards must be places at least no less
than 550 mm from the ground, providing an area for ventilation.
under floor membrane
should not be less than 0.25 mm thick and paved on a surface free from sharp objectsIt must be turned up on the at least the thickness of the slab on the perimeter
Joints must be sealed by overlapping sheets by at least 150 mm
Walls
-
8/6/2019 Emprical and Rational Design
2/6
empirical
Empirical rules for walls
Complies to walls that are internal, external , structural, non structural, parapet, free
standing or retaining
Masonry walls, that are load bearing must transfer resist loads and transfer these to the
ground, via the foundations
A non structural wall is where the masonry is used a sinfill or classing and does notexceed 25 m in height. In the case of a parapert wall, its thickness should not be less than
one fifth its height. . Non structural walls may be exposed to forces other than their own
weight, such as wind impact on a parapet wall. , its its strength is still of importance.
Materials
Minimum
average
compressivestrength (MPa)
Wall type position Solid units Hollow units Class of mortar
required
Structural
(other than
foundation or
retaining)
Single storey
(internal or
external)
7 3.5 II
Double storey
(Internal or
exctrenal0
10.5 or 14 ** 7 II
Non structural
(other than
parapet,
balustrade andfree-standing
wall)
External 7 3.5 II
Internal 7 3.5 II
Free-standing External or
internal
10.5 7 II
Foundation Supporting a
single storey
7 3.5 II
Foundation Supporting a
-
8/6/2019 Emprical and Rational Design
3/6
-
8/6/2019 Emprical and Rational Design
4/6
Concrete roofs must not exceed 175mm in thickness when soild, or equivalent mass when
voided
wall dimensions
In regards intersecting walls form the lateral support,
must be constructed from masonry units and mortar of the same quality and
strength. Its height must not be less than 80% of the height of the wall it supports,
its width must not be less than 45% (or 90 mm, whichever is greater) of the wall it
supports
Its length must at least one fifth the length of the wall it supports, or one eighththe distance between intersecting walls
Walls must intersect supporting walls between 60 and 120 degrees
RationalWhere a masonry pier is used for lateral support
its perpendicular length must be 3 times the thickness of the wall its width along the length of the wall must at least twice the thickness of the wall
must be at least 80% the length of the wall it is supporting
Cavity walls
An external masonry cavity will be between 50 and 110 mm wide
Wall ties must be evenly spaces at a 2.5 ties per meter sqaured, if the cavity is not morethan 75 mm, if the cavity is more than 75 mm, 3 ties are required per meter square
foundation wallsfunctions as a retaining wall, must not exceed 1.5m
The level between the ground and the backfill should not be more than 1m
The thickness of the walls cant be less than the they carry
ballustarde walls
Solid masonry ballustrade wall, must be
tied to reinforced concrete, brick columns or bonded into return walls or reinforced
brick piers expansion joints are to be used when neccesary, no further than 8 m apartwhere a wall
is supportred by comulum and pier (both reinforced)
Where the structural beams are bonded to the return walls. The return walls must not bespaced more than 6m part when 230 thickness wall, 5m for 190 mm walls and 4m for 110
Brick ballustrade walls
Reinforced, consisting od galvanised steel wire not less than 3.5 mm in diameter, in thehighest 4 bed joints. these must overlap at least 150 mm with the supporting column
-
8/6/2019 Emprical and Rational Design
5/6
Except for buildings containing more than 2 dwelligs (H3 classified), but no empirical
rules govern ballustrades except for materials
Ballustrade walls must be designed by an engineer or comptetnt person
Free standing walls
wall thickness(mm)
Max height of wall above groudlevel
Pier
Without piers with piers Min dimensions max spacing
(centre tocentre) m
90 0.8 1.2 290 x 290 1.9
110 1.0 1.5 350 x 350 2.1
140 1.3 1.8 340 x 340 2.5
190 1.5 2.2 390 x 390 2.7
230 1.8 2.4 470 x 470 3.7230 1.8 2.6 470 x 470
290 2.2 2.6 490 x 490
340 2.4
Roofs
Empirical rules
Where the roof is supported by a wall the following apply:
Miniun height requirements
In regards to a double pitched roof (Howe, single or douyble pitch span not exceeding10m, and bays no more than 1.5m apart)
roof
covering
truss
member
nominal
timber size(mm)
max span (m)
metal and
fiber-cementsheets
rafter 38 x 114 3.1 4.6 5.8
38 x 152 4.0 5.8 7.238 x 228 6.1 8.5 10.0
tie beam 38 x 114 3.1 4.5 6.2
38 x 152 4.5 6.4 8.3
38 x 228 7.1 10.0 10.0
Concrete
tiles, clay
tiles and
rafter 38 x 114 6.0 9.0 10.0
38 x 152 8.2 10.0 10.0
38 x 228 10.0 10.0 10.0
-
8/6/2019 Emprical and Rational Design
6/6
thatch tie beam 38 x 114 4.7 6.7 9.4
38 x 152 5.9 8.5 10.0
38 x 228 7.2 10.0 10.0
metal roof
tiles
rafter 38 x 114 6.2 9.0 10.0
38 x 152 8.0 10.0 10.0
38 x 228 10.0 10.0 10.0tie beam 38 x 114 4.5 6.7 9.0
38 x 152 5.9 8.7 10.0
38 x 228 8.7 10.0 10.0
all web members need to be at leat 38 x 114