em6438 em6436 dual qsg v01 - max · pdf filetable 1: dual source energy meter models and...

4
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH ? Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. In the USA, see NFPA 70E. ? Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions. ? provided by the equipment may be impaired. ? NEVER work alone. ? Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de- energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding. ? Turn off all power supplying the dual energy meter and the equipment in which it is installed before working on it. ? Always use a properly rated voltage sensing device to confirm that all power is off. ? Before closing all covers and doors, carefully inspect the work area for tools and objects that may have been left inside the equipment. ? Use caution while removing or installing panels so that they do not extend into the energized bus; avoid handling the panels, which could cause personal injury. ? The successful operation of this equipment depends upon proper handling, installation, and operation. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property. ? NEVER bypass external fusing. ? NEVER short the secondary of a PT. ? NEVER open circuit a CT; use the shorting block to short circuit the leads of the CT before removing the connection from the dual energy meter. ? Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the dual energy meter is installed, disconnect all input and output wires to the dual energy meter. High voltage testing may damage electronic components contained in the dual energy meter. ? The dual energy meter should be installed in a suitable electrical enclosure. Failure to follow these instructions will result in death or serious injury If the equipment is not used in the manner specified by the manufacturer, the protection Quick Start Guide English CTD7304 01/2011 Safety Precautions Models and Parameters Box Contents Installation Introduction EM6438_EM6436 Dual—Dual Source Energy Meters Read and follow all the safety precautions and instructions before installing and working with this equipment. The dual energy meter ships in two different configurations as given below. 1. EM6438 2. EM6436 dual Connecting Cable Requirements Additional Resources Go to http://www.schneider-electric.co.in > in the search window enter EM6438_EM6436 dual > On the EM6438_EM6436 dual screen, click Downloads tab, then click on tech publications tab > click on the document name to download or read the document file. Table 1: Dual source energy meter models and parameters Parameter EM6438 EM6436 dual RMS DM V12 V23 V31 VLL V1 V2 V3 VLN Demand VA/W/A (selectable through setup) Rising demand Time remaining Maximum demand (MD) U and G Hour MD occurred A1 A2 A3 A PF1 PF2 PF3 PF Frequency W1 W2 W3 W INTG and OLD U Wh.U Run.U On.U INTG and OLD G Wh.G Run.G On.G INTG and OLD TOT t.Wh t.Run t.On.h Dual Source Meter Physical Description Front Panel Rear Panel Figure 1: Front panel Figure 2: Rear panel ? One (1) EM6438 or EM6436 dual, dual energy meter. ? One (1) quick start guide (QSG). ? One (1) test and calibration certificate for the dual energy meter. ? One (1) connector. Tools and Equipments Requirements Insulation rating Current rating Voltage circuit > 600 VAC > 0.1 A > 7.5 A 2 or 2.5 mm /14 AWG minimum > 600 VAC Current circuit Table 2: Connecting cable requirements Table 3: Tools and equipments Torque driver preferred; may use hand screwdriver. Philips tip preferred, but you can also use flat. 3.5 mm < 5 mm. Diameter 5 mm will get stuck in the cover. Driver Tip Screw head Diameter Shaft diameter Torque Screw Travel Do not use Pozidriv tip. Tightening Torque: 0.25 to 1 N.m 6 mm less wire thickness Loosening Torque: 1.2 N.m Torque > 1 N.m may strip the screw or break the cover. NOTE: Installation should include a disconnecting device, like a switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary supply (control power). The disconnecting device should be within the reach of the equipment and the operator. Input voltage terminals V1, V2, V3, VN Auxiliary supply (control power) terminals RS 485 communication terminals Input current terminals A1, A2, A3 90° 90° Dimensions and Mounting Terminal Connections using Lugs Figure 4: Dual energy meter dimensions Figure 6: Dual energy meter mounting steps Figure 5: Dual energy meter mounting angle Dual Energy Meter Mounting 1 2 3 1. Remove the mounting clamps from the dual energy meter. 2. Gently slide the dual energy meter through the cut-out. 3. Put the mounting clamps back in the dual energy meter and tighten the mounting clamp screws. EM6438 Conzerv L3 L2 L1 Giga Giga Giga ^ 120 110 100 90 80 70 60 50 40 30 20 10 %A FS G.Sense Color-coded analog load bar GEN Indicators Eight-segment LED display Keys Terminal Connections using U Lugs Lug: Insulated sleeved U lug 2 Cross-section: 2.5 mm /14 AWG Figure 7: Terminal connections using U lugs 1. Loosen the terminal screw. 2. Connect the wire with the U lug to the dual energy meter terminal. 3. Tighten the terminal screw. 1 2 3 NOTE: - Standard. - Option specified while ordering. 90.0 96.0 3.54 3.78 83.0 8.0 0.31 3.26 Quick Setup, While Powering ON It is much easier to set up the dual energy meter before you mount the dual energy meter into the panel. This section explains how to set up the dual energy meter before mounting. Figure 3: Quick setup RS 485 communication Aux supply (control power) 44 to 300 VAC/DC Use CT1 Use PT1 Use CT2 Use PT2 Use CT3 Use PT3 1 2 3 4 1. Connect the auxiliary supply (control power) 44 to 300 VAC/DC to terminals 12 and 13. Press and hold for two seconds, while powering up the dual energy meter. The display enters PROG menu setup and displays EDIT A.PRI 100.0. Refer to “Edit set parameters” for programming. Program the following readings for accurate readings: A.PRI, A.SEC: Set these values to match your CT primary and secondary values. For example, if your CT ratio is 200:5, set A.PRI =200.0 and A.SEC = 5.000. V.PRI, V.SEC: Set these values to your input voltage VLL of circuit, if your input voltage is < 600 VACLL. For example, if the input voltage is 300 VACLL, set V.PRI = 300.0 and V.SEC = 300.0. Use potential transformer (PT/VT), if the input voltage > 600 VACLL. Set the V.pri and V.sec values to match the primary and secondary of the PT(VT) respectively. For example, if PT(VT) ratio is 11 kV: 110, set V.pri = 11.00 k and V.sec = 110.0. Select one of the following systems according to your wiring configuration. SYS = Star for 4-phase 3-wire system. See “Figure 9” for more information. SYS = Delta for 3-phase 3-wire system. See “Figures 10,11” for more information. SYS = 2-phase for 2-phase 3-wire system. See “Figure 12” for more information. SYS = Single-phase for single-phase 2-wire system. See “Figure 13” for more information. 2. Connect the current transformers (CTs). 3. Connect the voltage inputs. Use PT(VT) if input voltage exceeds 600 VLL. 4. Connect the RS 485 communication terminals. CT1 CT2 CT3 1, 2 3, 4 5, 6 PT1 PT2 PT3 Neutral 8 9 10 11 +ve -ve 7 14

Upload: ngothien

Post on 06-Mar-2018

240 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: EM6438 EM6436 dual QSG V01 - Max · PDF fileTable 1: Dual source energy meter models and parameters Parameter EM6438 EM6436 dual RMS DM ... test and calibration certificate for the

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH? Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. In the USA, see NFPA 70E.? Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.?

provided by the equipment may be impaired.? NEVER work alone.? Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de- energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding. ? Turn off all power supplying the dual energy meter and the equipment in which it is installed before working on it.? Always use a properly rated voltage sensing device to confirm that all power is off.? Before closing all covers and doors, carefully inspect the work area for tools and objects that may have been left inside the equipment. ? Use caution while removing or installing panels so that they do not extend into the energized bus; avoid handling the panels, which could cause personal injury.? The successful operation of this equipment depends upon proper handling, installation, and operation. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property.? NEVER bypass external fusing.? NEVER short the secondary of a PT.? NEVER open circuit a CT; use the shorting block to short circuit the leads of the CT before removing the connection from the dual energy meter.? Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the dual energy meter is installed, disconnect all input and output wires to the dual energy meter. High voltage testing may damage electronic components contained in the dual energy meter.? The dual energy meter should be installed in a suitable electrical enclosure.

Failure to follow these instructions will result in death or serious injury

If the equipment is not used in the manner specified by the manufacturer, the protection

Quick Start Guide EnglishCTD7304 01/2011

Safety Precautions

Models and Parameters

Box Contents

Installation

Introduction EM6438_EM6436 Dual—Dual Source Energy MetersRead and follow all the safety precautions and instructions before installing and working with this equipment.

The dual energy meter ships in two different configurations as given below.1. EM64382. EM6436 dual

Connecting Cable Requirements

Additional Resources

Go to http://www.schneider-electric.co.in > in the search window enter EM6438_EM6436dual > On the EM6438_EM6436 dual screen, click Downloads tab, then click on tech publications tab > click on the document name to download or read the document file.

Table 1: Dual source energy meter models and parameters

Parameter EM6438 EM6436 dual

RMS

DM

V12 V23 V31 VLLV1 V2 V3 VLN

Demand VA/W/A (selectable through setup)

Rising demand

Time remaining

Maximum demand (MD) U and G

Hour MD occurred

A1 A2 A3 A

PF1 PF2 PF3 PF

Frequency

W1 W2 W3 W

INTGandOLDU

Wh.U

Run.U

On.U

INTGandOLDG

Wh.G

Run.G

On.G

INTGandOLDTOT

t.Wh

t.Run

t.On.h

Dual Source Meter Physical DescriptionFront Panel

Rear Panel

Figure 1: Front panel

Figure 2: Rear panel

? One (1) EM6438 or EM6436 dual, dual energy meter.

? One (1) quick start guide (QSG).

? One (1) test and calibration certificate for the dual energy meter.

? One (1) connector.

Tools and Equipments Requirements

Insulation rating Current rating

Voltage circuit > 600 VAC > 0.1 A

> 7.5 A2or 2.5 mm /14 AWG minimum

> 600 VACCurrent circuit

Table 2: Connecting cable requirements

Table 3: Tools and equipments

Torque driver preferred; may use hand screwdriver.Philips tip preferred, but you can also use flat.

3.5 mm < 5 mm. Diameter ³ 5 mm will get stuck in the cover.

Driver Tip

Screw head Diameter

Shaft diameter

Torque

Screw Travel

Do not use Pozidriv tip.

Tightening Torque: 0.25 to 1 N.m

6 mm less wire thickness

Loosening Torque: 1.2 N.m

Torque > 1 N.m may strip the screw or break the cover.

NOTE: Installation should include a disconnecting device, like a switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary supply (control power). The disconnecting device should be within the reach of the equipment and the operator.

Input voltage terminalsV1, V2, V3, VN

Auxiliary supply (control power) terminals

RS 485 communication terminals

Input current terminalsA1, A2, A3

90° 90°

Dimensions and Mounting Terminal Connections using LugsFigure 4: Dual energy meter dimensions

Figure 6: Dual energy meter mounting steps

Figure 5: Dual energy meter mounting angle

Dual Energy Meter Mounting

1 2 3

1. Remove the mounting clamps from the dual energy meter.2. Gently slide the dual energy meter through the cut-out.3. Put the mounting clamps back in the dual energy meter and tighten the mounting clamp screws.

EM6438Conzerv

L3

L2

L1

Gig

aG

iga

Gig

a

^

120

110

100

90

80

70

60

50

40

30

20

10

%A FSG.Sense

Color-coded analog load bar

GEN

IndicatorsEight-segment LED display

Keys

Terminal Connections using U LugsLug: Insulated sleeved U lug

2Cross-section: 2.5 mm /14 AWG

Figure 7: Terminal connections using U lugs

1. Loosen the terminal screw.2. Connect the wire with the U lug to the dual energy meter terminal.3. Tighten the terminal screw.

1 2

3

NOTE: - Standard. - Option specified while ordering.

90.0

96.0

3.54

3.78

83.0 8.00.313.26

Quick Setup, While Powering ONIt is much easier to set up the dual energy meter before you mount the dual energy meter into the panel. This section explains how to set up the dual energy meter before mounting.

Figure 3: Quick setup

RS 485 communication Aux supply

(control power)44 to 300 VAC/DC

Use CT1Use PT1Use CT2Use PT2

Use CT3 Use PT3

1

23

4

1. Connect the auxiliary supply (control power) 44 to 300 VAC/DC to terminals 12 and 13. Press and hold for two seconds, while powering up the dual energy meter. The display enters PROG menu setup and displays EDIT A.PRI 100.0. Refer to “Edit set parameters” for programming.

Program the following readings for accurate readings: A.PRI, A.SEC: Set these values to match your CT primary and secondary values. For example, if your CT ratio is 200:5, set A.PRI =200.0 and A.SEC = 5.000. V.PRI, V.SEC: Set these values to your input voltage VLL of circuit, if your input voltage is < 600 VACLL. For example, if the input voltage is 300 VACLL, set V.PRI = 300.0 and V.SEC = 300.0. Use potential transformer (PT/VT), if the input voltage > 600 VACLL. Set the V.pri and V.sec values to match the primary and secondary of the PT(VT) respectively. For example, if PT(VT) ratio is 11 kV: 110, set V.pri = 11.00 k and V.sec = 110.0. Select one of the following systems according to your wiring configuration. SYS = Star for 4-phase 3-wire system. See “Figure 9” for more information. SYS = Delta for 3-phase 3-wire system. See “Figures 10,11” for more information. SYS = 2-phase for 2-phase 3-wire system. See “Figure 12” for more information. SYS = Single-phase for single-phase 2-wire system. See “Figure 13” for more information.2. Connect the current transformers (CTs).

3. Connect the voltage inputs. Use PT(VT) if input voltage exceeds 600 VLL.

4. Connect the RS 485 communication terminals.

CT1 CT2 CT3

1, 2 3, 4 5, 6

PT1 PT2 PT3 Neutral

8 9 10 11

+ve -ve

7 14

Page 2: EM6438 EM6436 dual QSG V01 - Max · PDF fileTable 1: Dual source energy meter models and parameters Parameter EM6438 EM6436 dual RMS DM ... test and calibration certificate for the

Keypad SetupKeys DescriptionTable 6: Keys description

Keys OperationThe following example explains, how the different keys in the dual energy meter operates. The example explains, how to navigate from the RMS page to VLN A F page and back to RMS page, in EM6436 dual, dual energy meter.

NOTE: The following symbols are used to explain the different operations of the keys. for right key operation. for left key operation. for up key operation. for down key operation.

Right key:Go forward to sub-parameter pages. When changing parameters, moves one position to the right. Left key:Go backward to main parameter pages. When changing parameters, moves one position to the left.Up key:Scroll up through the display pages at the level, within the same function. When changing parameters, increases value by one.

Down key:Scroll down through the display pages at the same level through all the functions. When changing parameters, decreases value by one.

TURBO key:The TURBO key is the one-touch access to the most commonly used parameters (factory-set). The TURBO key scrolls through Wh.U, Wh.G or VAh.U, VAh.G. If you are lost, use the TURBO key to quickly return the RMS page.

RMS

VLLAPF

VLNAF

1. Press , from RMS page. The display shows VLL A PF.2. Press . The display shows VLN A F. 3. Press , to return to RMS page.

NOTE: Use to go forward to sub-parameter pages. Use to go back to main parameter pages. Use and to scroll up and down through the display pages.

PROG Menu - Setup

Enter Setup Menu in View (Read-only) Mode

The PROG menu setup gives the complete list of user-programmable parameters.? You must set up the dual energy meter to match the application settings before use. Otherwise, readings will be wrong.? All the setup parameters can be re-programmed, using SET. However, the following settings critically determine the scaling of the measured readings: SYS (star or delta), Vpri, Vsec, Apri, Asec.? The scaling may be used to minimize the errors in reading due to instrument transformer errors. However, wrong settings will introduce errors in readings on other running systems.

You can enter PROG menu setup in ? View mode: To view the set parameters.

? Edit mode: To view or edit the set parameters.

HAZARD OF UNINTENDED OPERATIONOnly qualified personnel are authorized to set up the dual energy meter.

Failure to follow these instructions can result in injury or equipment damage.

1. Press from RMS page. The display shows SET.2. Press . The display shows VIEW. 3. Press . The display shows VIEW A.PRI 100.0. Use and to view the setup parameters and their default values.

Setup Parameters in View and Edit Modes

Figure 10: 3-phase 3-wire delta connection

Figure 11: 3-phase 3-wire open delta connection

Figure 12: 2-phase 3-wire connection

Figure 13: Single-phase connection

Wirings

Wiring Diagram Symbols

Supported System Types

Fuse

StAr 9Star/Wye

dLtA 10, 11Delta, open delta

2-phase 122-phase

Single-phase 13Single-phase

Current transformer (CT)

S2

S1

Table 5: Wiring diagram symbols

Table 4: Supported system types

Symbol

System type

Description

Meter configuration Figure number

Wiring Diagrams

Figure 9: 3-phase 4-wire star/wye connection

Terminal Connections using Lugs (Continued)Terminal Connections using Ring LugsLug: Ring lug

2Cross-section: 2.5 mm /14 AWG

Figure 8: Terminal connections using ring lugs

1. Remove the protective cover from the dual energy meter.2. Remove the terminal screw from the dual energy meter.3. Connect the wire with the ring lug to the dual energy meter terminal.4. Place the terminal screw back and tighten the terminal screw.5. Place the protective cover back and tighten the protective cover.

Enter Setup Menu in Edit Mode

1. Press from RMS page. The display shows SET.2. Press . The display shows VIEW.3. Press . The display shows EDIT. CODE entry is required to edit the parameters.4. Press for two seconds. The display shows CODE 2000 with blinking 2. The factory set CODE is 1000.5. Press . The display shows CODE 1000 with blinking 1. 6. Press once or four times to accept the new CODE value. The display flashes PASS and shows EDIT A.PRI 100.0. This indicates that you have successfully entered the setup menu in edit mode.

NOTE: If you enter a wrong CODE, the display flashes FAIL and shows EDIT. Repeat thesteps and make sure that you enter the correct CODE.

- Means blinking

1 - Means blinking 1A.PRI = Current primary winding (CT)*; Input range 1 A to 99 kA. Default value is 100.0

A.SEC = Current secondary winding (CT); Default value is 5.000

V.PRI = Voltage primary winding (PT), line to line*; Input range 100 V to 999 kV; Default value is 415.0

V.SEC = Voltage secondary winding (PT), line to line*; Input range 80 V to 600 V; Default value is 415.0

SYS = System configuration; Select from StAR, dLtA, 2 ph, 1 ph; Default value is StAR.

LAbL = Phase labeling; Select from 123, RYB, RST, PQR, ABC; Default value is 123.

VA.Fn = VA function selection; Select between 3D, ARTH; Default value is 3D.

d.SEL = Demand selection*; Select from AUTO, User; Default value is AUTO.

1

2

L1 L2 L3 N

*

*

*

* Other Meters (In Series)

LOAD

LINE

Communication

Other Meters

0.25 A

CT

CT

CT

PT if VAC LL 601 VS1

S1

S1

S2

S2

S2

44 to 300 VAC/DCAux Supply(Control power)

D0D1

50

mA

to

6A

44

to

30

0 V

50

/60

Hz <

5 V

A

80 t

o 6

00 V

ac L

L

S/N

:CO

YW

WD

XX

XX

Acc

CI:

X.X

N9

98

RS 485

CT

S1

S2

L1 L2 L3

*

*

Communication

Other Meters

0.25 A

CT

LOAD

LINE

PT if VAC LL 601 V

S1

S2

* Other Meters (In series)

44 to 300 VAC/DCAux Supply(Control power)

D0D1

50m

A t

o 6

A

44 t

o 3

00 V

50

/60

Hz

<5 V

A

80 t

o 6

00 V

ac L

L

S/N

:CO

YW

WD

XX

XX

Acc

CI:

X.X

N9

98

RS 485

CT

S1

S2

L1 L2 L3

*

*

Communication

Other Meters

0.25 A

CT

LOAD

LINE

PT if VAC LL 601 V

S1

S2

* Other Meters (In Series)

44 to 300 VAC/DC

44 to 300 VAC/DC

Aux Supply(Control power)

D0D1

50

mA

to

6A

44

to

30

0 V

50

/60

Hz

<5

VA

80 t

o 6

00 V

ac L

L

S/N

:CO

YW

WD

XX

XX

Acc

CI:

X.X

N9

98

RS 485

D0D1

50

mA

to

6A

44

to

30

0 V

50

/60

Hz

<5

VA

80 t

o 6

00 V

ac L

L

S/N

:CO

YW

WD

XX

XX

Acc

CI:

X.X

N998

RS 485

CT

Communication

S1

S2

L1 N

*

* Other meters(in series)

* Other meters(in series)

Other Meters

0.25 A

LINE

LOAD

44 to 300 VAC/DCAux Supply(Control power)

D0D1

50

mA

to

6A

44

to

30

0 V

50

/60

Hz

<5

VA

80 t

o 6

00 V

ac L

L

S/N

:CO

YW

WD

XX

XX

Acc

CI:

X.X

N9

98

RS 485

AC

Page 3: EM6438 EM6436 dual QSG V01 - Max · PDF fileTable 1: Dual source energy meter models and parameters Parameter EM6438 EM6436 dual RMS DM ... test and calibration certificate for the

Default Display Page

The default display page feature enables you to select any display page as user-set display page. You can scroll to other pages, when the default display page is active. The default display page will be displayed two minutes after you stop the manual key operation.

To LOCK default display page:Go to the desired page you want to set as default display page. Press and together. The display shows LOCK and the display page is locked.

To unlock default display page:Once the default display page is active, press and together.The display shows ULOC and the default display page is unlocked.

NOTE:Entry to PROG menu setup is possible only when the default display page is unlocked.

Default display page through communication:? You can lock and unlock the default display page through communication (ConPAD).? If an operator locks the default display page through communication, any user can unlock it from the front panel.? If a supervisor locks the default display page through communication, an operator cannot unlock it. Only a supervisor can unlock it through communication.

FeaturesAuto-scroll

Indicators

Auto-scroll within the Page Group

Auto-scroll Down the Entire Column of Pages

TURBO Auto-scroll

? Auto-scroll allows you to view a group of display pages sequentially every five seconds without manual key operation. ? During auto-scroll, the dual energy meter displays parameter name for one second and value for four seconds.? The dual energy meter has three different types of auto-scroll explained in the following examples.

1. Go to a particular page in the desired page group.2. Press continuously for three seconds and release. The display flashes AUTO and starts auto-scroll within the page group.

1. Go to the desired page.2. Press continuously for three seconds and release. The display flashes AUTO and starts auto-scroll down the column of pages.

Press continuously for three seconds and release. The display flashes AUTO and starts auto-scroll down the TURBO pages.

NOTE:Press any key to revert to manual scrolling.Auto scrolling is not possible in setup parameters.

Kilo: When lit, indicates that the reading is in Kilo (10^3). 10,000 is displayed as 10.00 K and 1.0 K is displayed as 1000.

Mega: When lit, indicates that the reading is in Mega (10^6). 10,000 K is displayed as 10.00 M and 1.0 M is displayed as 1000 K.

Giga: When both K and M are lit, indicates that the reading is in Giga (10^9). 10,000 M is displayed as 10.00 G and 1.0 G is displayed as 1000 M.

Negative: When lit, indicates that the reading is in negative as per IEEE 100 and industry standard.

GEN: Indicates generator running, if used for generator applicationIndicates gated load (ON load), if used for industrial applicationIndicates greater load (peak load), if used for dual tariff application

Table 8: Indicators

G Sense WiringINTG Overflow

OLD Data Register

? The energy values stored in INTG are based on V.Pri x A.Pri; they are independent of secondary values of V and A.? The energy value readings will overflow based on V.Pri x A.Pri of the primary settings in setup, when Wh/VAh reaches 9999 K or 9999 M or 9999 G or when 9999 run hours is reached.? The energy parameter for overflow is user selectable (Wh or Vah) through setup. By default it is Wh or by the Run hours which is fixed 9999 Run hours (almost 13.88 months).? For power systems ranging from 1 VA to 1000 MVA, the integrator will overflow at 9999 run hours. The duration required for the integrator to overflow will be 13.88 months if the dual energy meter is constantly running at full scale.? However, in case of power systems greater than 1000 MVA, the integrator will overflow at a value less than 9999 run hours. The duration required for the integrator to overflow will be less than a year if the dual energy meter is constantly running at full scale.

When the integrator is cleared (through ConPAD or due to overflow), the energy values stored in the integrator will be transferred to the OLD register. Thus the old energy values are not lost even after the integrator is cleared and can be viewed with the OLD parameter.

NOTE: For energy studies clear the Integrator at the end of each observation. This transfers all the stored energy values to the OLD register, where they are held while the Integrator begins accumulating data for the next observation. Remember that the next time the Integrator is cleared, the OLD values will be overwritten.

Energy Integrator, OLD Data Register, OverflowEnergy Integrator INTG

User Programmable Integrator names

? Your dual energy meter is equipped with an energy integrator function which provides several parameters for energy management: Wh.U, ON.U, Wh.G, ON.G, t.Wh, t.On.h and OLD registers. ? The integrator parameters are always accumulated irrespective of the parameter selected in the setup. ? All the values stored in INTG are direct readings and have high resolution.

? The Integrator parameters can be viewed by changing the PAR in the PROG menu setup.

NOTE: CT Reversal: Auto - correction for energy integration in star (wye). In star (wye) mode energy integration will always be in forward direction irrespective of the direction of current flow or sign of the per phase power reading.

? The dual source energy meter has two integrators with user programmable names.

? You can program the alpha-numeric source names for these integrators from A to Y (except X) and 0 to 9.? The factory-set names for these integrators are U and G.

Table 7: Integrator and applications

U Utility Usual (off peak load) Ungated (idle load)

G Generator Greater (peak load) Gated (on load)

GEN TARIFF INDUSTRIAL

In all the above mentioned applications (GEN, TARIFF, INDUSTRIAL), the dual energy meter integrates the energy values normally in U register. It integrates the value in G register, whencontrol input signal (18 to 60 VDC/80 to 300 VAC) for the generator is ON. The G sense LED in the front panel lights up when the generator is ON.

Clear MD

- Means blinking

1 - Means blinking 1

1. From RMS, Press . The display shows CLR. CODE entry is required to clear the MD values.

After the successful CODE entry, the display shows CLR INTG.

6 To clear MD, press . The display shows CLR MD y with blinking y.

7. Press or to clear MD. The display flashes PASS and then CLR MD.

8. Press . The display shows CLR.

9. Press to return to RMS page.

2. Press for two seconds. The display shows CODE 2000 with blinking 2.

The factory set CODE is 1000.

3. Press . The display shows CODE 1000 with blinking 1.

5. Press . The display shows CLR MD.

4. Press once or four times to accept the new value.

NOTE: If you do not want to clear the integrators, press to change the value from CLR MD y to CLR MD n in step 6. Then press or . The display flashes FAIL and then shows CLR MD. Proceed to step 8.

This section is applicable only for EM648 or EM6436 dual model with demand option.

PROG Menu - Setup (Continued)Setup Parameters in View and Edit Modes (Continued)

Edit Set Parameter

- Means blinking

- Means blinking

1 - Means blinking 1

y - Means blinking y

This section explains how you can edit the setup parameter A.PRI from 100.0 to 5000 in the dual energy meter.For better understanding, the editing is explained in two parts: Edit and accept setup, save new value to the setup.

Edit and Accept Setup

Save New Value to Setup

1. After you have successfully entered into setup menu in edit mode (Refer to “Enter Setup Menu in Edit mode” for more information), press . The display shows EDIT A.PRI 100.0 with blinking 1.2. Press four times. The display shows EDIT A.PRI 500.0 with blinking 5. 3. Press for four times. The display shows EDIT A.PRI 500.0 with blinking “.”.4. Press . The display shows EDIT A.PRI 5000. with blinking “.”.5. Press to accept the new value. To edit the next parameter, press and repeat the above steps.

1. After you edit the parameter as described above, press . The display shows SAVE y with blinking y.2. Press . The display flashes PASS and shows EDIT.3. Press . The display shows SET.

NOTE; If you do not want to save the new value, press to change SAVE y to SAVE n. Press . The display flashes FAIL and shows EDIT. Then proceed to step 3.

Press four times

Press four times

d.PAR = Demand parameter selection*; Select from VA, W, A; Default value is VA.

d.PRD = Demand period; Select from 5, 10, 15, 20, 25, 30; Default value is 15.

Baud = Baud rate; Select from 1200, 2400, 4800, 9600, 19200; Default value is 9600.

PRTY = Parity and stop bit settings; Select from EVN.1, EVN.2, OD.1,ODD.2, no.1, no.2; Default value is EVN.1.

ID = RS 485 device ID number; Select from 1.000 to 247.0; Default value is 1.000.

F.S% = Full scale percentage; Set the full scale between 1.000 to 100.0; Default value is 100.0

OFLO = Overflow parameter selection; Select from Wh, VAh;

PAR = Parameter selection; Select from Wh, VAh

R1.R2 = User-programmable dual source names (U G);Select any alpha-numeric from A-Y (except X) and 0 to 9

2

1

NOTE: * Changing these values is not recommended, while the device is in use.Demand parameters are available only for EM6438 or EM6436 dual models with demand option.

Page 4: EM6438 EM6436 dual QSG V01 - Max · PDF fileTable 1: Dual source energy meter models and parameters Parameter EM6438 EM6436 dual RMS DM ... test and calibration certificate for the

Schneider Electric India Pvt Ltd44 P, Electronics City East Phase,Hosur Road,Bangalore - 560 100 , IndiaE:[email protected] Toll Free Help desk Numbers:1800 180 1707, 1800 103 0011www.schneider-electric.co.in

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

SEI/EM6438_EM6436Dual/0111/V01.d15© 2011 Schneider Electric All Rights Reserved

OLDG

Wh.G

RUN.G

ON.G

OLDTOT

t.Wh

t.RUN

t.ON.h

DIAG Dia 1

Dia 7

SET

CLR

VIEW

EDIT

OLD G = OLD integrator G

Wh.G = OLD Watts hours G

RUN.G = OLD Run hours G

ON.G = OLD On hours G

OLD TOT = OLD integrator total, U + G

t.Wh = OLD total Watts hours U + G

t.RUN = OLD total Run hours U + G

t.ON = OLD total On hours U + G

DIAG = Represents diagnostic pages.The values in these pages are for factory testing only.

Dia 1 = Communication settings.

Dia 2 = Product model and version.

Dia 3 = Display scanning to check LED.

SET = Has two modes; View and edit modes.

CLR = Clears MD values

View = Enter setup in read-only mode

Edit = Enter setup in editable mode

3

2

EM6436 Dual: Menu Hierarchy (Continued) EM6436 Dual: Menu Hierarchy

INTG U = Integrator U

Wh.U = Watts hours U

RUN.U = Run hours U

ON.U = On hours U

INTG G = Integrator G

Wh.G = Watts hours G

RUN.G = Run hours G

ON.G = On hours G

INTGU

Wh.U

RUN.U

ON.U

INTGG

Wh.G

RUN.G

ON.G

OLDU

Wh.U

RUN.U

ON.U

INTGTOT

t.Wh

t.RUN

t.ON.h

OLD U = OLD integrator U

Wh.U = OLD Watts hours U

RUN.U = OLD Run hours U

ON.U = OLD On hours U

INTG TOT = Integrator total, U + G

t.Wh = Total Watts hours U + G

t.RUN = Total Run hours U + G

t.ON = Total On hours U + G

2

1

NOTE: DMD W, CLR pages are only for EM6436 Dual with demand option.

3

OLDU

Wh.U

RUN.U

ON.U

OLDG

Wh.G

RUN.G

ON.G

OLDTOT

t.Wh

t.RUN

t.ON.h

DIAG Dia 1

Dia 7

SET

CLR

VIEW

EDIT

1

2

OLD U = OLD integrator U

Wh.U = OLD Watts hours U

RUN.U = OLD Run hours U

ON.U = OLD On hours U

OLD G = OLD integrator G

Wh.G = OLD Watts hours G

RUN.G = OLD Run hours G

ON.G = OLD On hours G

OLD TOT = OLD integrator total, U + G

t.Wh = OLD total Watts hours U + G

t.RUN = OLD total Run hours U + G

t.ON = OLD total On hours U + G

DIAG = Represents diagnostic pages.The values in these pages are for factory testing only.

Dia 1 = Communication settings.

Dia 2 = Product model and version.

Dia 3 = Display scanning to check LED.

SET = Has two modes; View and edit modes.

CLR = Clear MD values.

View = Enter setup in read-only mode

Edit = Enter setup in editable mode

NOTE: DMD W, CLR pages are only for EM6438 with demand option.

EM6438: Menu Hierarchy (Continued)

EM6436 Dual: Menu hierarchy (Continued)

Menu HierarchiesEM6438: Menu Hierarchy

RMS W W1 2 3

INTGU

Wh.U

RUN.U

ON.U

INTGG

Wh.G

RUN.G

ON.G

INTGTOT

t.Wh

t.RUN

t.ON.h

DMDW

W.DRDT.R

MD.UHr

MD.GHr

1

23 RMS = RMS value display pages are in sub-level

DMD W = W Demand; This can be DM A or DM VA depending on the parameter selected in the PROG menu setup.

W = Watts, total

W.D = W demandRd = Rising demandT.R = Time remaining

MD.U = Maximum demand UHr = On hours at which maximum demand has occurred.

MD.G = Maximum demand GHr = On hours at which maximum demand has occurred.

INTG U = Integrator U

Wh.U = Watts hours U

RUN.U = Run hours U

ON.U = On hours U

INTG G = Integrator G

Wh.G = Watts hours G

RUN.G = Run hours G

ON.G = On hours G

INTG TOT = Integrator total, U + G

t.Wh = Total Watts hours U + G

t.RUN = Total Run hours U + G

t.ON = Total On hours U + G

W1 = Watts, phase 1W2 = Watts, phase 2W3 = Watts, phase 3

4

Technical Specifications

Description Specification

Sensing/measurement True RMS, one second update time, four quadrant power and two quadrant energy

Auxiliary supply (control power) 44 to 300 VAC/DC

Input voltage Four voltage inputs (V1, V2, V3, VN)110 or 415 VACLL nominal (80 to 600 VACLL)

Input current(energy measurement)

Current inputs (A1, A2, A3); 5 mA (starting) to 6 A*; 5 A Class 0.2S: 5 mA (starting) to 6 A1 A Class 0.2S: 1 mA (starting) to 1.2 A

Frequency 45 to 65 Hz

Burden Voltage and current input < 0.2 VA per phaseAuxiliary supply (control power) < 3 VA

Overload 5 A: 10 A max continuous 1 A: 2 A max continuous

Display and resolution Alphanumeric LED display; RMS: Four digits; INTG: Eight digits

Communication (optional) RS 485 serial channel connection industry standard Modbus RTU protocol

Isolation 2 k VAC isolation for one min between all isolated circuits includingcommunication port.

Environmental Operating temperature: -10 °C to 60 Storage temperature: -25 °C to 70 °C (-13 °F to 158 °F)Humidity 5 % to 95 % non-condensing

°C (14 °F to 140 °F)

Weight 400 gms approx, unpacked500 gms approx, shipping

Protection against dust and water Front panel: IP 51Rear panel: IP 40

Accuracy Class 1 .0 as per IEC 62052-11 and IEC 62053-21; Class 0.5S (optional) as per IEC 62052-11, 62053-22 and ANSIC12. 20Class 0.2S (optional) as per IEC 62052-11 and IEC 62053-22

Standards - Measurement category III, Pollution degree 2 - Double insulation at user-accessible area

Table 9: Technical specifications

NOTE: * Additional error of 0.05% of full scale, for dual energy meter input current below 100 mA.

RMS = RMS value display pages are in sub-level

VLL = Phase to phase voltage averageA = Current averagePF = Power factor average

VLN = Phase to neutral voltage averageA = Current averageF = Frequency in Hz

A = Current averageW = Watts totalPF = Power factor average

W1 = Watts, phase 1W2 = Watts, phase 2W3 = Watts, phase 3

V12 = RMS voltage, phase 12V23 = RMS voltage, phase 23V31 = RMS voltage, phase 31

V1 = RMS voltage, phase 1 to neutralV2 = RMS voltage, phase 2 to neutralV3 = RMS voltage, phase 3 to neutral

W1 = Watts, phase 1W2 = Watts, phase 2W3 = Watts, phase 3

PF1 = Power factor, phase 1PF2 = Power factor, phase 2PF3 = Power factor, phase 3

RMS VLLAPF

VLNAF

AWPF

V12 23 31

V 1 2 3

A 1 2 3

W 1 2 3

PF 1 2 3

34

DMDW

W.DRDT.R

MD.UHr

MD.GHr

DMD W = W Demand; This can be DM A or DM VA depending on the parameter selected in the PROG menu setup.

W.D = W demandRd = Rising demandT.R = Time remaining

MD.U = Maximum demand UHr = On hours at which maximum demand has occurred.

MD.G = Maximum demand GHr = On hours at which maximum demand has occurred.

1