ElectroMagnetic Compatibility in Cable Tray Systems

Ed Cronin, RCDD, President, Cronin Consulting

Claes Rosenberg, Export Manager, Defem System/Schneider Electric

Page 2: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

EMC Research Consortium

Page 3: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Definition of ElectoMagnetic Compatibility

”The ability of a device, equipment or system to function satisfactorily in its electromagnetic environment without introducing intolerable electromagnetical disturbances to anything in that environment”

Source: 2008 International Electrical Committee (IEC)

Page 4: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

EMC in the Data Room

• The metal cable tray is part of the electrical structure

• The metal cable tray is part of the metallic structure

• Any metallic structure is known as a “generalized shield”

Page 5: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Definition of generalized shield

• To function as a generalized shield, the metal does not have to be enclosing the cable. Any continous metal along the cable is a shield.

• A shield is any metal structure that is continous and parallel along the cable path

Page 6: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Metal Cable TrayQuick Facts

• Properly bonded and grounded = ”earth”

• Poorly bonded and grounded = ”antenna”

Page 7: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Background

• July 2007 - EU introduces new EMC directive

• It states that any electrical installation shall be made according to ”good engineering EMC practice”

Page 8: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

EU Directive

...”installer must document that the EMC

performance of complete installation is made

according to ”good engineering practice” ...

Source: EMC Directive 2004/108/EC

Page 9: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Common EMC Problems

• “Come and go problems” – Lightning strike– on/off transients– radio transmission

• “Slow down problems”– Disturbances may force packaged signals to be

re-packaged and re-sent

Page 10: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Metal structure

Equipment

Cables Differential mode

Principles of Generalized Shield

Page 11: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Various Shield Structures

Page 12: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Principles of Earth Loop Area Reduction

Page 13: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Principles of Earth Loop Area Reduction

Page 14: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Principals of Earth Loop Area Reduction

Page 15: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Principles of Earth Loop Area Reduction

Page 16: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Tray Design

• Minor Importance– wire mesh – solid metal tray – perforated metal tray– cable ladder

…are all “shield” when properly installed

Page 17: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Schneider Electric tests performed with Defem cable tray

Page 18: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Ultimate installationTray directly connected to top of cabinets

Floor is Ground Reference Plane.

Page 19: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Realistic installationTray connected with short ground wire to top of both cabinets

Page 20: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Possible installationTray connected with long ground wire to low point of both cabinets

Page 21: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Poor installationTray connected once with a single ground wire to one cabinet

Page 22: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Schneider Electric Results

Page 23: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Test Conclusions

• Single ground connection – Tray connected to one cabinet only – worse than no metal tray at all – creates a disturbance

• Continous tray installation – Tray from cabinet to cabinet– best option– not realistic for practical reasons

Page 24: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Test Conclusions

• Realistic installation – Sort ground wire between tray and all cabinets – clear improvement

• Critical Parameter – connection between cable trays and cabinets

• continuity of generalized shield

Page 25: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Other Conclusions

• Source and victim cables at bigger separation distance does not compensate for a badly connected cable tray. It is still contagious…

Page 26: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Good Engineering Practices

• IEC Standards– To use gasfree and vibration safe joinings of tray,

ensuring max 50mΩ– To mark tray joints with a bonding sign

• To connect metal cable trays to all cabinets with ground wire, preferrably at cable entrance

Page 27: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Good Engineering Practices

Place cables as close as possible to parallel earth conductor

Page 28: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Good Engineering Practices

Additional cables will enhance external shielding effect

Page 29: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Good Engineering Practice

With multi level cabling, ground wire connection between tray levels

Page 30: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Take Away

• Properly bonded and grounded = ”earth”

• Poorly bonded and grounded = ”antenna”

Page 31: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Thank You

• Claes Rosenberg – Defem

• Ed Cronin RCDD – Cronin Consulting

Page 32: ElectroMagnetic Compatibility in Cable Tray Systems Ed Cronin, RCDD, President, Cronin Consulting Claes Rosenberg, Export Manager, Defem System/Schneider

Thank You