Electrical distribution

Circuit protection and control devices 0.5 to 6300 ALV product characteristics2010

Page 2: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

This international site allows you to access all the Schneider Electric products in just 2 clicks via comprehensive range data-sheets, with direct links to:

complete library: technical documents, catalogs, FAQs, brochures…

selection guides from the e-catalog.

product discovery sites and their Flash animations.You will also find illustrated overviews, news to which you can subscribe, the list of country contacts…

p

p

p

These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide,the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations.For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

schneider-electric.com The technical guide

TOOLS

Page 3: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

General contents

Multi 9 A-2Multi 9 circuit breakersfrom 0.5 to 125 A A-2

NG160 A-4Characteristics of NG160circuit breakers andswitch-disconnectors A-4Incomer for modular switchboards A-4

Easypact A-6Selection table A-6EZC circuit breakers A-6

Compact NSX A-10Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A A-10

Compact NS A-12Protection of distribution systems A-12Compact NS circuit breakers up to 630 A A-�2Compact NS circuit breakers from 630 up to 3200 A A-�4

Compact NS -Direct Current A-16DC circuit breakers characteristics A-16 Compact NS�00 to NS630 A-�6

Masterpact NT and NW A-18Circuit breakers and switch-disconnectors 0 A-18NT06 to NT�6 A-�8NW08 to NW63 A-20Micrologic control units 0 A-22Overview of functions A-22

Masterpact -Direct Current A-24DC circuit breakers characteristics 0 A-24Masterpact NW�0 to NW40 A-24

Interpact INS A-26Switch-disconnector selection A-26Interpact INS250-�00 to 630 A-30Interpact INS630b to 2500 A-34

Interpact INV A-38Switch-disconnector selection A-38Interpact INV�00 to 630 A-38Interpact INV630b to 2500 A-43

Source changeover systems A-46Overview of solutions A-46Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX �00 A to 630 A A-46Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A A-47Remote-operated source-changeover systems Compact NSX�00 A to 630 A, Compact NS�00 A to �600 A A-48Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A A-49

Fupact A-50Switch-disconnector fuses selection A-50Fupact INFp32 to INFp�60 A-50Fupact INFp200 to INFp800 A-54Switch-disconnector fuses selection A-56Fupact ISFT�00N to ISFT630 A-58Fupact ISFL�60 to ISFL630 A-62

Vigirex A-66Selection guide A-66Protection and monitoring relays A-66

Page 4: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

C60N C60H C60L C120N C120H NG125N NG125H NG125L� 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4

0.5-63 0.5-63 0.5-25 32-40 50-63 63-�25 �0-�25 �0-�25 �0-80 �0-80500 500 500 500 500 500 500 690 690 6906 6 6 6 6 6 6 8 8 8440 440 440 440 440 440 440 500 500 500b b b b b b b b b bb b b b b b b b b b

6000 �0000 - - - �0000 �5000 - - -20 - 30 - 50 - 50 - 50 - 20 - 30 - 50 - 70 - �00 -�0 20 �5 30 25 50 20 40 �5 30 �0 20 �5 30 25 50 36 70 50 �003 �0 4 �5 6 25 5 20 4 �5 3 �0 4.5 �5 6 25 9 36 �2.5 50- 6 - �0 - 20 - �5 - �0 - 6 - �0 - 20 - 30 - 40- - - - - - - - - - - - - - 6 8 6 �0 6 �275 % 50 % 50 % 50 % 50 % 75 % 50 % 75 % 75 % 75 %

b b b b b b b b - bb b b b b b b b b bb b b b b b b b - b- - b b b - - - - -- - b b b - - - - -- - b y 40 A - - - - - - -

b b b b b b b b b b- - - - - - - - - -�0-�000 �0-�000 �0-�000 30-�000 30-�000 30-�000 30-�000 30-300 30-300 30-30030-�000 30-�000 30-500 30-300 30-�000 30-�000 30-�000 30-3000 30-3000 30-300030-�000 30-�000 30 30 30-�000 30-�000 30-�000 30-3000 30-3000 30-300030-�000 30-�000 30 30-300 30-�000 30-�000 30-�000 - - -

b b b b b b b b b bb b b b b b b b b bb b b b b b b b b bb b b b b b b - - -

�6 (y 25 A) 25 (> 25 A) �6 25 25 35 3525 (y 25 A) 35 (> 25 A) 25 35 35 50 50

b b b b b b y 63 A b y 63 A - - -b b b b b b b b b bb b b b b b b b b bb b b b b b b b b b�8 per pole �8 per pole �8 per pole �8 per pole �8 per pole 27 per pole 27 per pole 27 per pole 27 per pole 27 per pole8� 8� 8� 8� 8� 8� 8� �03 �03 �0373 73 73 73 73 73 73 8� 8� 8�

Multi 9 Multi 9 circuit breakers from 0.5 to 125 A

0569

84N

-47_

SE

DPN Vigi

Multi 9 circuit breaker DPN N VigiNumber of poles � + NElectrical characteristics

Rated current (A) In 4-40Rated insulation voltage (V) Ui 400Impulse withstand voltage (kV) Uimp 4Maximum operational voltage (V) Ue AC 50/60 Hz 230Fast closing bSuitability for isolation and positive contact indication b

AC breaking capacity

PB

�002

70-�

7_S

E IEC 60898 (EN 60898) Icn (A) 230/400 V 6IEC 60947-2 (EN 60947-2) Icu (kA) �30 V -

230 V -400 V -440 V -500 V -

Ics (% of Icu) -Trip units (non adjustable)

C60 Curve type B (lm = 3 to 5 ln) bC (lm = 5 to �0 ln) b

0567

38-5

4_S

E

C120

D (lm = �0 to �4 ln) -K (lm = �0 to �4 In) -Z (lm = 2.4 to 3.2) -MA (lm = �2 ln) -

Earth leakage protectionAdd-on rcd’s (Vigi module) -Integrated bSensitivity type (mA) a AC 30-300

A 30k A si 30-300

0569

08N

-46_

SE

NG125

A si E -Electrical auxiliaries

Auxiliary and alarm switches (OF-SD) bShunt trip (MX); undervoltage release (MN) bEmergency stop opening switch (MNx) bVoltage threshold release (MSU) b

ConnectionCable maxi capacity (mm2) Flexible �0

Rigid �6Installation

Plug in base -Terminal shieds -Padlocking device bRotary handle -Dimensions (mm) W 36

H 8�D 70

2

Page 5: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Multi 9 Multi 9 circuit breakers from 0.5 to 125 A

C60N C60H C60L C120N C120H NG125N NG125H NG125L� 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4 � 2-3-4

0.5-63 0.5-63 0.5-25 32-40 50-63 63-�25 �0-�25 �0-�25 �0-80 �0-80500 500 500 500 500 500 500 690 690 6906 6 6 6 6 6 6 8 8 8440 440 440 440 440 440 440 500 500 500b b b b b b b b b bb b b b b b b b b b

6000 �0000 - - - �0000 �5000 - - -20 - 30 - 50 - 50 - 50 - 20 - 30 - 50 - 70 - �00 -�0 20 �5 30 25 50 20 40 �5 30 �0 20 �5 30 25 50 36 70 50 �003 �0 4 �5 6 25 5 20 4 �5 3 �0 4.5 �5 6 25 9 36 �2.5 50- 6 - �0 - 20 - �5 - �0 - 6 - �0 - 20 - 30 - 40- - - - - - - - - - - - - - 6 8 6 �0 6 �275 % 50 % 50 % 50 % 50 % 75 % 50 % 75 % 75 % 75 %

b b b b b b b b - bb b b b b b b b b bb b b b b b b b - b- - b b b - - - - -- - b b b - - - - -- - b y 40 A - - - - - - -

b b b b b b b b b b- - - - - - - - - -�0-�000 �0-�000 �0-�000 30-�000 30-�000 30-�000 30-�000 30-300 30-300 30-30030-�000 30-�000 30-500 30-300 30-�000 30-�000 30-�000 30-3000 30-3000 30-300030-�000 30-�000 30 30 30-�000 30-�000 30-�000 30-3000 30-3000 30-300030-�000 30-�000 30 30-300 30-�000 30-�000 30-�000 - - -

b b b b b b b b b bb b b b b b b b b bb b b b b b b b b bb b b b b b b - - -

�6 (y 25 A) 25 (> 25 A) �6 25 25 35 3525 (y 25 A) 35 (> 25 A) 25 35 35 50 50

b b b b b b y 63 A b y 63 A - - -b b b b b b b b b bb b b b b b b b b bb b b b b b b b b b�8 per pole �8 per pole �8 per pole �8 per pole �8 per pole 27 per pole 27 per pole 27 per pole 27 per pole 27 per pole8� 8� 8� 8� 8� 8� 8� �03 �03 �0373 73 73 73 73 73 73 8� 8� 8�

0569

84N

-47_

SE

DPN Vigi

Multi 9 circuit breaker DPN N VigiNumber of poles � + NElectrical characteristics

Rated current (A) In 4-40Rated insulation voltage (V) Ui 400Impulse withstand voltage (kV) Uimp 4Maximum operational voltage (V) Ue AC 50/60 Hz 230Fast closing bSuitability for isolation and positive contact indication b

AC breaking capacity

PB

�002

70-�

7_S

E IEC 60898 (EN 60898) Icn (A) 230/400 V 6IEC 60947-2 (EN 60947-2) Icu (kA) �30 V -

230 V -400 V -440 V -500 V -

Ics (% of Icu) -Trip units (non adjustable)

C60 Curve type B (lm = 3 to 5 ln) bC (lm = 5 to �0 ln) b

0567

38-5

4_S

E

C120

D (lm = �0 to �4 ln) -K (lm = �0 to �4 In) -Z (lm = 2.4 to 3.2) -MA (lm = �2 ln) -

Earth leakage protectionAdd-on rcd’s (Vigi module) -Integrated bSensitivity type (mA) a AC 30-300

A 30k A si 30-300

0569

08N

-46_

SE

NG125

A si E -Electrical auxiliaries

Auxiliary and alarm switches (OF-SD) bShunt trip (MX); undervoltage release (MN) bEmergency stop opening switch (MNx) bVoltage threshold release (MSU) b

ConnectionCable maxi capacity (mm2) Flexible �0

Rigid �6Installation

Plug in base -Terminal shieds -Padlocking device bRotary handle -Dimensions (mm) W 36

H 8�D 70

3

Page 6: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

3 and 4 pole circuit breakers and switch-disconnectors specially designed for use upstream of Multi 9 modular devices:b reinforcement of breaking capacities of downstream devices by cascading up to 25 kAb easy installation in Pragma or Prisma Plus type G enclosures:v standard 45 mm front cut-outv clip-on installation on a DIN railv reduced depth (82.5 mm).

NG160 circuit breakerElectrical characteristics as per IEC 60947-2

Rated current (A) In 40 °C �60Rated insulation voltage (V) Ui 800Rated impulse withstand voltage (kV)

Uimp 8

Rated operational voltage (V) Ue AC 50/60 Hz 500Type of circuit breaker E N H

Ultimate breaking capacity Icu AC 220/240 V 25 40 50(kA rms) 50/60 380/4�5 V �6 25 36

Hz 440 V �0 �6 22500 V 8 �0 �5

Service breaking capacity Ics % Icu 75 %Suitability for isolation bDurability (C-O cycles) mechanical �0000

electrical (In -440 V) 5000

PB

�035

�2-S

E-4

0

ProtectionBuilt-in thermal-magnetic trip unitRatings In �6 25 32 40 50 63 80 �00 �25 �60Thermal protection Ir fixed threshold

Magnetic protection lm 600 600 600 600 600 800 800 �000 �250 �250

NG160NA switch-disconnectorElectrical characteristics as per IEC 60947-3

Conventional thermal current (A) Ith 40 °C �60 Rated insulation voltage (V) Ui 800Rated impulse withstand voltage (kV)

Uimp 8

Rated operational voltage (V) Ue AC 50/60 Hz 500Rated operational current Ie AC 50/60 Hz AC22A AC23A

220/240 V �60 �60380/4�5 V �60 �60440/480 V �60 �60500 V �60 �25

NG160 circuit breaker. Short-circuit making capacity

lcm (kA peak)min. for switch-disconnector alone

2.�

max. with protection by upstream circuit breaker

330

Short-time withstand current Icw (A rms) � s �5003 s �500

Suitability for isolation b

Coordination between circuit breakers and switch-disconnectorsThe switch-disconnector must be protected against downstream short-circuits. The choice of the right switch-disconnector therefore depends on coordination with the protective device installed upstream. The table below indicates the maximum short-circuit current in kArms for which the switch-disconnector is protected by coordination with the circuit breaker located upstream.Important: the switch-disconnector must be protected against overloads. The rating of the switch-disconnector must be greater than or equal to that of the upstream circuit breaker.

Upstream protection NR100F NS100 - NS160NR160F N SX H

NG160NA downstream380 - 4�5 V

Isc max kA rms 25 36 50 70Making capacity kA peak 52 75 �05 �54

440 V

Isc max kA rms 20 35 50 65Making capacity kA peak 42 73 �05 �43

NG160 Characteristics of NG160 circuit breakers and switch-disconnectorsIncomer for modular switchboards

4

Page 7: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

NG160 Characteristics of NG160 circuit breakers and switch-disconnectorsIncomer for modular switchboards

PB

�035

30-S

E-5

8 Installation and connectionsConnections

Connectors Bare cables from �.5 to 70 mm² cablesDimensions (mm) W x H x D Width in

9 mm modulesNG�60 3P 90 x �20 x 82.5 �0

4P �20 x �20 x 82.5 �4NG�60 with Vigi

3P 2�0 x �20 x 82.5 244P 240 x �20 x 82.5 27

Weight (kg)Device 3P �.�

4P �.4Device + Vigi module

3P 2.64P 2.9

NG160 in modular enclosure.

5

Page 8: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H3 3 � 3-4 � 2-3-4 3 3 2-3�5, �6, 20, 25, 30, 32, 40, 45, 50, 60

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�00, �25, �50, �60, �75, 200, 225, 250

�00, �25, �50, �60, �75, 200, 225, 250

�00, �25, �50, �60, �75, 200, 225, 250

690 690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6 6550 550 4�5 550 4�5 550 550 550 550- 250 �25 250 �25 250 250 250 250

�0 25 25 25 50 �00 25 50 85�0 25 �8 25 25 �00 (�) 25 50 857.5 �0 2.5 �8 5 30 �8 25 367.5 10 2.5 15 5 30 18 25 365 7.5 - �0 - 20 �5 20 252.5 5 - 5 - �0 5 8 �0- 5 5 5 �0 �0 5 20 30- 5 - 5 - �0 5 20 30

25 % 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %25 % 50 % 50 % 50 % 50 % 25 % 50 % 50 % 50 %b b b b b b b b b

A A A A A A A A A3 3 3 3 3 3 3 3 38 500 8 500 8 500 8 500 8 500 8 500 �0 000 �0 000 �0 000� 500 � 500 � 500 � 500 � 500 � 500 5 000 5 000 5 000

- - �0 25 �8 �00 25 50 85- - �0 (2) �0 �8 (2) �8 (3) �5 �8 25 (3)

fixed fixed fixed fixed fixed fixed fixed fixed fixedfixed fixed fixed fixed fixed fixed �0 In �0 In �0 In

b b - b - b b b b

b b - b - b b b b

b b - b - b b b b

b b - b - b b b b

b b - b - b b b b

b b b b b b b b b

b b b b b b b b b

b b - b - b (3) b b b

b b - b - b (3) b b b

- - - - - - b b b

b b - b - b b b b

b b b b b b b b b

b b - b - b (3) b b b

b b b b b b b b b

b b b b b b - - -

60 x �30 60 x �30 60 x �30 60 x �30 60 x �30 60 x �30 60 x �65 60 x �65 60 x �6575 75 25 75 (3P)

�00 (4P)25 50 (2P)

75 (3P)�00 (4P)

�05 �05 �05

0.78 0.78 0.28 0.78 (3P)�.0 (4P)

0.28 0.6 (2P) 0.78 (3P)�.0 (4P)

�.3 �.3 �.� (2P) �.3 (3P)

(1) 50 kA for 2 poles.(2) For 277 V only.(3) For 3 and 4 poles only.

Selection tableEZC circuit breakers

EasypactP

B�0

�838

-SE

-�0

EasyPact circuit breakersNumber of polesRated current (A) In at 40 °C

Rated insulation voltage (V) UiRated impulse withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz

DCEZC100-1P. Electrical characteristics as per IEC 60947-2, EN 60947-2, JIS C8201-2-1

Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz ��0/�30 V220/230/240 V

PB

�0�8

40-S

E-�

5

380 V400/415 V

440 V550 V

DC �25 V (�P)250 V (2P in series)

Rated service breaking capacity (kA rms) Ics % Icu ��0-400 V4�5-550 V

Suitability for isolationEZC100-2P. Utilisation category

Pollution degreeEndurance (C-O cycles) Mechanical

PB

�0�8

43-S

E-2

2

Electrical In/4�5 VElectrical characteristics as per NEMA-AB1

Breaking capacity (kA rms) HIC AC 50/60 Hz 240 V277/480 V

ProtectionOverload protection BimetalInstantaneous protection Magnetic Fixed (±20 %)Auxiliaries

Indication contacts Auxiliary switch AXAlarm switch AL

EZC100-3P. Combined AX + AL AXALVoltage releases Shunt trip release SHT

Undervoltage release UVR

PB

�02�

72-S

E-2

7

InstallationConnection Crimp lugs/barsAccessories Box lugs for bare cables

Rotary handles DirectExtended

Terminal extensionsSpreadersPhase barriersTerminal shieldsPadlocking system

EZC100-4P. DIN rail adaptorDimension and weight

Dimensions (mm) D x H

PB

�0�8

45-S

E-2

9

W

Weight (kg)

EZC250-3P.

6

Page 9: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Selection tableEZC circuit breakers

Easypact

EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H3 3 � 3-4 � 2-3-4 3 3 2-3�5, �6, 20, 25, 30, 32, 40, 45, 50, 60

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�5, �6, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, �00

�00, �25, �50, �60, �75, 200, 225, 250

�00, �25, �50, �60, �75, 200, 225, 250

�00, �25, �50, �60, �75, 200, 225, 250

690 690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6 6550 550 4�5 550 4�5 550 550 550 550- 250 �25 250 �25 250 250 250 250

�0 25 25 25 50 �00 25 50 85�0 25 �8 25 25 �00 (�) 25 50 857.5 �0 2.5 �8 5 30 �8 25 367.5 10 2.5 15 5 30 18 25 365 7.5 - �0 - 20 �5 20 252.5 5 - 5 - �0 5 8 �0- 5 5 5 �0 �0 5 20 30- 5 - 5 - �0 5 20 30

25 % 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %25 % 50 % 50 % 50 % 50 % 25 % 50 % 50 % 50 %b b b b b b b b b

A A A A A A A A A3 3 3 3 3 3 3 3 38 500 8 500 8 500 8 500 8 500 8 500 �0 000 �0 000 �0 000� 500 � 500 � 500 � 500 � 500 � 500 5 000 5 000 5 000

- - �0 25 �8 �00 25 50 85- - �0 (2) �0 �8 (2) �8 (3) �5 �8 25 (3)

fixed fixed fixed fixed fixed fixed fixed fixed fixedfixed fixed fixed fixed fixed fixed �0 In �0 In �0 In

b b - b - b b b b

b b - b - b b b b

b b - b - b b b b

b b - b - b b b b

b b - b - b b b b

b b b b b b b b b

b b b b b b b b b

b b - b - b (3) b b b

b b - b - b (3) b b b

- - - - - - b b b

b b - b - b b b b

b b b b b b b b b

b b - b - b (3) b b b

b b b b b b b b b

b b b b b b - - -

60 x �30 60 x �30 60 x �30 60 x �30 60 x �30 60 x �30 60 x �65 60 x �65 60 x �6575 75 25 75 (3P)

�00 (4P)25 50 (2P)

75 (3P)�00 (4P)

�05 �05 �05

0.78 0.78 0.28 0.78 (3P)�.0 (4P)

0.28 0.6 (2P) 0.78 (3P)�.0 (4P)

�.3 �.3 �.� (2P) �.3 (3P)

(1) 50 kA for 2 poles.(2) For 277 V only.(3) For 3 and 4 poles only.

PB

�0�8

38-S

E-�

0

EasyPact circuit breakersNumber of polesRated current (A) In at 40 °C

Rated insulation voltage (V) UiRated impulse withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz

DCEZC100-1P. Electrical characteristics as per IEC 60947-2, EN 60947-2, JIS C8201-2-1

Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz ��0/�30 V220/230/240 V

PB

�0�8

40-S

E-�

5

380 V400/415 V

440 V550 V

DC �25 V (�P)250 V (2P in series)

Rated service breaking capacity (kA rms) Ics % Icu ��0-400 V4�5-550 V

Suitability for isolationEZC100-2P. Utilisation category

Pollution degreeEndurance (C-O cycles) Mechanical

PB

�0�8

43-S

E-2

2

Electrical In/4�5 VElectrical characteristics as per NEMA-AB1

Breaking capacity (kA rms) HIC AC 50/60 Hz 240 V277/480 V

ProtectionOverload protection BimetalInstantaneous protection Magnetic Fixed (±20 %)Auxiliaries

Indication contacts Auxiliary switch AXAlarm switch AL

EZC100-3P. Combined AX + AL AXALVoltage releases Shunt trip release SHT

Undervoltage release UVR

PB

�02�

72-S

E-2

7

InstallationConnection Crimp lugs/barsAccessories Box lugs for bare cables

Rotary handles DirectExtended

Terminal extensionsSpreadersPhase barriersTerminal shieldsPadlocking system

EZC100-4P. DIN rail adaptorDimension and weight

Dimensions (mm) D x H

PB

�0�8

45-S

E-2

9

W

Weight (kg)

EZC250-3P.

7

Page 10: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

EZC250N EZC250H EZCV250N EZCV250H EZC400N EZC400H4 4 3-4 3-4 3-4 3-463, 80, �00, �25,�50, �60, �75, 200, 225, 250

63, 80, �00, �25,�50, �60, �75, 200, 225, 250

63, 80, �00, �25,�50, �60, �75, 200, 225, 250

63, 80, �00, �25,�50, �60, �75, 200, 225, 250

250, 300, 320, 350, 400

250, 300, 320, 350, 400

690 690 440 440 690 6906 6 6 6 8 8550 550 440 440 550 550250 250 - - 250 250

50 85 85 �00 85 �0025 36 25 36 36 5025 36 25 36 36 5020 25 20 25 36 508 �0 - - �5 2020 30 - - - -20 30 - - 20 40

50 % 50 % 50 % 50 % 50 % 50 %

b b b b b b

A A A A A A3 3 3 3 3 3�0 000 �0 000 �0 000 �0 000 4 000 4 0005 000 5 000 5 000 5 000 � 000 � 000

50 85 50 85 50 85�8 25 - - 25 35 fixed fixed fixed fixed fixed fixed�0 In �0 In �0 In �0 In �0 In �0 In - - 0.�/0.3/0.5/� 0.�/0.3/0.5/� - -- - 0/200/500/�000 0/200/500/�000 - -- - 0.�5/0.4/�/2 0.�5/0.4/�/2 - - b b b b b b

b b b b b b

b b b b b b

- - b b - -b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

68 x �65 68 x �65 68 x �65 68 x �65 �03 x 257 �03 x 257�40 �40 �05 (3P)

�40 (4P)�05 (3P)�40 (4P)

�40 (3P)�85 (4P)

�40 (3P)�85 (4P)

�.8 �.8 �.6 (3P)2.� (4P)

�.6 (3P)2.� (4P)

5 (3P)7.5 (4P)

5 (3P)7.5 (4P)

Easypact Selection tableEZC circuit breakers

PB

�0�8

52-S

E-3

2

EasyPact circuit breakersNumber of poles Rated current (A) In at 40°C

Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz

DCElectrical characteristics as per IEC 60947-2, EN 60947-2 and JIS C8201-2-1/C8201-2-2

Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 220/230/240 VEZC250. 380 V

400/415 V440 V

PB

�0�8

54-S

E-3

4

550 VDC �25 V (�P)

250 V (2P in series)

Rated service breaking capacity (kA rms)

Ics % Icu

Suitability for isolation

Utilisation category Pollution degree Endurance (C-O cycles) Mechanical

Electrical In/4�5 V Electrical characteristics as per NEMA-AB1

EZCV250-4P. Breaking capacity (kA rms) HIC AC 50/60 Hz 240 V277/480 V

Protection

PB

�02�

�4-S

E-2

8

Overload protection Bimetal Instantaneous protection Magnetic fixed (± 20 %)Earth-leakage protection

Sensitivity (A) IDn adjustableTime-delay (ms) Dt adjustableMax. breaking time (s) at 2 IDnAuxiliaries

Indication contacts Auxiliary switch AXAlarm switch ALCombined AX + AL AXALEarth-alarm switch ALV

Voltage releases Shunt trip release SHTUndervoltage release UVR

Installation EZC400-3P. Connection Crimp lugs / bars

Accessories Box lugs for bare cables Rotary handles Direct

PB

�02�

�5-S

E-

36

ExtendedTerminal extensions Spreaders Phase barriers Terminal shields Padlocking system

Dimension and weight Dimensions (mm) D x H

W

Weight (kg)

EZC400-4P.

8

Page 11: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Easypact Selection table0 EZC circuit breakers

EZC250N EZC250H EZCV250N EZCV250H EZC400N EZC400H4 4 3-4 3-4 3-4 3-463, 80, �00, �25,�50, �60, �75, 200, 225, 250

63, 80, �00, �25,�50, �60, �75, 200, 225, 250

63, 80, �00, �25,�50, �60, �75, 200, 225, 250

63, 80, �00, �25,�50, �60, �75, 200, 225, 250

250, 300, 320, 350, 400

250, 300, 320, 350, 400

690 690 440 440 690 6906 6 6 6 8 8550 550 440 440 550 550250 250 - - 250 250

50 85 85 �00 85 �0025 36 25 36 36 5025 36 25 36 36 5020 25 20 25 36 508 �0 - - �5 2020 30 - - - -20 30 - - 20 40

50 % 50 % 50 % 50 % 50 % 50 %

b b b b b b

A A A A A A3 3 3 3 3 3�0 000 �0 000 �0 000 �0 000 4 000 4 0005 000 5 000 5 000 5 000 � 000 � 000

50 85 50 85 50 85�8 25 - - 25 35 fixed fixed fixed fixed fixed fixed�0 In �0 In �0 In �0 In �0 In �0 In - - 0.�/0.3/0.5/� 0.�/0.3/0.5/� - -- - 0/200/500/�000 0/200/500/�000 - -- - 0.�5/0.4/�/2 0.�5/0.4/�/2 - - b b b b b b

b b b b b b

b b b b b b

- - b b - -b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

b b b b b b

68 x �65 68 x �65 68 x �65 68 x �65 �03 x 257 �03 x 257�40 �40 �05 (3P)

�40 (4P)�05 (3P)�40 (4P)

�40 (3P)�85 (4P)

�40 (3P)�85 (4P)

�.8 �.8 �.6 (3P)2.� (4P)

�.6 (3P)2.� (4P)

5 (3P)7.5 (4P)

5 (3P)7.5 (4P)

PB

�0�8

52-S

E-3

2

EasyPact circuit breakersNumber of poles Rated current (A) In at 40°C

Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz

DCElectrical characteristics as per IEC 60947-2, EN 60947-2 and JIS C8201-2-1/C8201-2-2

Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 220/230/240 VEZC250. 380 V

400/415 V440 V

PB

�0�8

54-S

E-3

4

550 VDC �25 V (�P)

250 V (2P in series)

Rated service breaking capacity (kA rms)

Ics % Icu

Suitability for isolation

Utilisation category Pollution degree Endurance (C-O cycles) Mechanical

Electrical In/4�5 V Electrical characteristics as per NEMA-AB1

EZCV250-4P. Breaking capacity (kA rms) HIC AC 50/60 Hz 240 V277/480 V

Protection

PB

�02�

�4-S

E-2

8

Overload protection Bimetal Instantaneous protection Magnetic fixed (± 20 %)Earth-leakage protection

Sensitivity (A) IDn adjustableTime-delay (ms) Dt adjustableMax. breaking time (s) at 2 IDnAuxiliaries

Indication contacts Auxiliary switch AXAlarm switch ALCombined AX + AL AXALEarth-alarm switch ALV

Voltage releases Shunt trip release SHTUndervoltage release UVR

Installation EZC400-3P. Connection Crimp lugs / bars

Accessories Box lugs for bare cables Rotary handles Direct

PB

�02�

�5-S

E-

36

ExtendedTerminal extensions Spreaders Phase barriers Terminal shields Padlocking system

Dimension and weight Dimensions (mm) D x H

W

Weight (kg)

EZC400-4P.

9

Page 12: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Circuit breakers NSX100 NSX160 NSX250 NSX400 NSX630Breaking capacity levels B F N H S L B F N H S L B F N H S L F N H S L F N H S LElectrical characteristics as per IEC 60947-2

Rated current (A) In 40 °C 100 160 250 400 630Number of poles 2 (3), 3, 4 2 (3), 3, 4 2 (3), 3, 4 3, 4 3, 4

Breaking capacity (kA rms)lcu AC 50/60 Hz 220/240 V 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 �00 �20 �50 40 85 �00 �20 �50

380/4�5 V 25 36 50 70 �00 �50 25 36 50 70 �00 �50 25 36 50 70 �00 �50 36 50 70 �00 �50 36 50 70 �00 �50440 V 20 35 50 65 90 �30 20 35 50 65 90 �30 20 35 50 65 90 �30 30 42 65 90 �30 30 42 65 90 �30500 V �5 25 36 50 65 70 �5 30 36 50 65 70 �5 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70525 V - 22 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 20 22 35 40 50 20 22 35 40 50660/690 V - 8 �0 �0 �5 20 - 8 �0 �0 �5 20 - 8 �0 �0 �5 20 �0 �0 20 25 35 �0 �0 20 25 35

Service breaking capacity (kA rms)lcs AC 50/60 Hz 220/240 V 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 �00 �20 �50 40 85 �00 �20 �50

380/4�5 V 25 36 50 70 �00 �50 25 36 50 70 �00 �50 25 36 50 70 �00 �50 36 50 70 �00 �50 36 50 70 �00 �50440 V 20 35 50 65 90 �30 20 35 50 65 90 �30 20 35 50 65 90 �30 30 42 65 90 �30 30 42 65 90 �30500 V 7.5 �2.5 36 50 65 70 �5 30 36 50 65 70 �5 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70525 V - �� 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 �0 �� �� �2 �2 �0 �� �� �2 �2660/690 V - 4 �0 �0 �5 20 - 8 �0 �0 �5 20 - 8 �0 �0 �5 20 �0 �0 �0 �2 �2 �0 �0 �0 �2 �2

Durability (C-O cycles) Mechanical 50000 40000 20000 �5000 �5000Electrical 440 V In/2 50000 40000 20000 �2000 8000

In 30000 20000 �0000 6000 4000690 V In/2 20000 �5000 �0000 6000 6000

In �0000 7500 5000 3000 2000Characteristics as per Nema AB1

Breaking capacity (kA rms) AC 50/60 Hz 240 V 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 �00 �20 �50 40 85 �00 �20 �50480 V 20 35 50 65 90 �30 20 35 50 65 90 �30 20 35 50 65 90 �30 30 42 65 90 �30 30 42 65 90 �30600 V - 8 20 35 40 50 - 20 20 35 40 50 - 20 20 35 40 50 - 20 35 40 50 - 20 35 40 50

Characteristics as per UL 508Breaking capacity (kA rms) AC 50/60 Hz 240 V - 85 85 85 - - - 85 85 85 - - - 85 85 85 - - 85 85 85 - - 85 85 85 - -

480 V - 25 50 65 - - - 35 50 65 - - - 35 50 65 - - 35 50 65 - - 35 50 65 - -600 V - �0 �0 �0 - - - �0 �0 �0 - - - �5 �5 �5 - - 20 20 20 - - 20 20 20 - -

Protection and measurementsShort-circuit protection Magnetic only b b b b bOverload / short-circuit protection Thermal magnetic b b b - -

Electronic b b b b bwith neutral protection (Off-0.5-�-OSN) (1) b b b b bwith ground-fault protection b b b b bwith zone selective interlocking (ZSI) (2)

b b b b b

Display / I, U, f, P, E, THD measurements / interrupted-current measurement b b b b bOptions Power Meter display on door b b b b b

Operating assistance b b b b bCounters b b b b bHistories and alarms b b b b bMetering Com b b b b bDevice status/control Com b b b b b

Earth-leakage protection By Vigi module b b b b bBy Vigirex relay b b b b b

Installation / connectionsDimensions and weights

Dimensions (mm) W x H x D

Fixed, front connections 2/3P �05 x �6� x 86 �05 x �6� x 86 �05 x �6� x 86 �40 x 255 x ��0 �40 x 255 x ��04P �40 x �6� x 86 �40 x �6� x 86 �40 x �6� x 86 �85 x 255 x ��0 �85 x 255 x ��0

Weight (kg) Fixed, front connections 2/3P 2.05 2.2 2.4 6.05 6.24P 2.4 2.6 2.8 7.90 8.�3

ConnectionsConnection terminals Pitch With/without spreaders 35/45 mm 35/45 mm 35/45 mm 45/52.5 mm

45/70 mm 45/52.5 mm45/70 mm

Large Cu or Al cables Cross-section mm² 300 300 300 4 x 240 4 x 240

Compact NSX Characteristics and performance of Compact NSX circuit breakers from 100 to 630 ACommon characteristicsRated voltages

Insulation voltage (V) Ui 800Impulse withstand voltage (kV)

Uimp 8

Operational voltage (V) Ue AC 50/60 Hz 690Suitability for isolation IEC/EN 60947-2 yes

Utilisation category APollution degree IEC 60664-� 3

PB

�033

54-4

0

Compact NSX100/160/250.

PB

�032

79-4

4

Compact NSX400/630.

(1) OSN: Over Sized Neutral protection for neutrals carrying high currents (e.g. 3rd harmonics). (2) ZSI: Zone Selective Interlocking using pilot wires.(3) 2P circuit breaker in 3P case for B and F types, only with thermal-magnetic trip unit.

�0

Page 13: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Compact NSX Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A

Common characteristicsControl

Manual With toggle b

With direct or extended rotary handle b

Electrical With remote control b

VersionsFixed b

Withdrawable Plug-in base b

Chassis b

Circuit breakers NSX100 NSX160 NSX250 NSX400 NSX630Breaking capacity levels B F N H S L B F N H S L B F N H S L F N H S L F N H S LElectrical characteristics as per IEC 60947-2

Rated current (A) In 40 °C 100 160 250 400 630Number of poles 2 (3), 3, 4 2 (3), 3, 4 2 (3), 3, 4 3, 4 3, 4

Breaking capacity (kA rms)lcu AC 50/60 Hz 220/240 V 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 �00 �20 �50 40 85 �00 �20 �50

380/4�5 V 25 36 50 70 �00 �50 25 36 50 70 �00 �50 25 36 50 70 �00 �50 36 50 70 �00 �50 36 50 70 �00 �50440 V 20 35 50 65 90 �30 20 35 50 65 90 �30 20 35 50 65 90 �30 30 42 65 90 �30 30 42 65 90 �30500 V �5 25 36 50 65 70 �5 30 36 50 65 70 �5 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70525 V - 22 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 20 22 35 40 50 20 22 35 40 50660/690 V - 8 �0 �0 �5 20 - 8 �0 �0 �5 20 - 8 �0 �0 �5 20 �0 �0 20 25 35 �0 �0 20 25 35

Service breaking capacity (kA rms)lcs AC 50/60 Hz 220/240 V 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 �00 �20 �50 40 85 �00 �20 �50

380/4�5 V 25 36 50 70 �00 �50 25 36 50 70 �00 �50 25 36 50 70 �00 �50 36 50 70 �00 �50 36 50 70 �00 �50440 V 20 35 50 65 90 �30 20 35 50 65 90 �30 20 35 50 65 90 �30 30 42 65 90 �30 30 42 65 90 �30500 V 7.5 �2.5 36 50 65 70 �5 30 36 50 65 70 �5 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70525 V - �� 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 �0 �� �� �2 �2 �0 �� �� �2 �2660/690 V - 4 �0 �0 �5 20 - 8 �0 �0 �5 20 - 8 �0 �0 �5 20 �0 �0 �0 �2 �2 �0 �0 �0 �2 �2

Durability (C-O cycles) Mechanical 50000 40000 20000 �5000 �5000Electrical 440 V In/2 50000 40000 20000 �2000 8000

In 30000 20000 �0000 6000 4000690 V In/2 20000 �5000 �0000 6000 6000

In �0000 7500 5000 3000 2000Characteristics as per Nema AB1

Breaking capacity (kA rms) AC 50/60 Hz 240 V 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 90 �00 �20 �50 40 85 �00 �20 �50 40 85 �00 �20 �50480 V 20 35 50 65 90 �30 20 35 50 65 90 �30 20 35 50 65 90 �30 30 42 65 90 �30 30 42 65 90 �30600 V - 8 20 35 40 50 - 20 20 35 40 50 - 20 20 35 40 50 - 20 35 40 50 - 20 35 40 50

Characteristics as per UL 508Breaking capacity (kA rms) AC 50/60 Hz 240 V - 85 85 85 - - - 85 85 85 - - - 85 85 85 - - 85 85 85 - - 85 85 85 - -

480 V - 25 50 65 - - - 35 50 65 - - - 35 50 65 - - 35 50 65 - - 35 50 65 - -600 V - �0 �0 �0 - - - �0 �0 �0 - - - �5 �5 �5 - - 20 20 20 - - 20 20 20 - -

Protection and measurementsShort-circuit protection Magnetic only b b b b bOverload / short-circuit protection Thermal magnetic b b b - -

Electronic b b b b bwith neutral protection (Off-0.5-�-OSN) (1) b b b b bwith ground-fault protection b b b b bwith zone selective interlocking (ZSI) (2)

b b b b b

Display / I, U, f, P, E, THD measurements / interrupted-current measurement b b b b bOptions Power Meter display on door b b b b b

Operating assistance b b b b bCounters b b b b bHistories and alarms b b b b bMetering Com b b b b bDevice status/control Com b b b b b

Earth-leakage protection By Vigi module b b b b bBy Vigirex relay b b b b b

Installation / connectionsDimensions and weights

Dimensions (mm) W x H x D

Fixed, front connections 2/3P �05 x �6� x 86 �05 x �6� x 86 �05 x �6� x 86 �40 x 255 x ��0 �40 x 255 x ��04P �40 x �6� x 86 �40 x �6� x 86 �40 x �6� x 86 �85 x 255 x ��0 �85 x 255 x ��0

Weight (kg) Fixed, front connections 2/3P 2.05 2.2 2.4 6.05 6.24P 2.4 2.6 2.8 7.90 8.�3

ConnectionsConnection terminals Pitch With/without spreaders 35/45 mm 35/45 mm 35/45 mm 45/52.5 mm

45/70 mm 45/52.5 mm45/70 mm

Large Cu or Al cables Cross-section mm² 300 300 300 4 x 240 4 x 240

��

Page 14: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

�2

Compact circuit breakers NS125E NS100 NS160 NS250 NS400 NS630Number of poles 3, 4 2 (1), 3, 4 2 (1), 3, 4 2 (1), 3, 4 3, 4 3, 4Control manual toggle b b b b b b

direct or extended rotary handle - b b b b belectric - b b b b b

Connections fixed front connection b b b b b brear connection b b b b b b

plug-in (on base) front connection - b b b b brear connection - b b b b b

withdrawable (on chassis) front connection - b b b b brear connection - b b b b b

Electrical characteristics as per IEC 60947-2 and EN 60947-2Rated current (A) In 40 °C �25 �00 �60 250 400 630

65 °C - �00 �50 220 320 500Rated insulation voltage (V) Ui 750 750 750 750 750 750Rated impulse withstand voltage (kV) Uimp 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 500 690 690 690 690 690

DC - 750 750 750 750 750Type of circuit breaker E N SX H L N SX H L N SX H L N H L N H LUltimate breaking capacity (kA rms) lcu AC 220/240 V 25 85 90 �00 �50 85 90 �00 �50 85 90 �00 �50 85 �00 �50 85 �00 �50

50/60 Hz 380/4�5 V �6/�0 36 50 70 �50 36 50 70 �50 36 50 70 �50 50 70 �50 50 70 �50440 V �0 35 50 65 �30 35 50 65 �30 35 50 65 �30 42 65 �30 42 65 �30500 V 6 25 36 50 �00 30 36 50 70 30 36 50 70 30 50 �00 30 50 70525 V - 22 35 35 �00 22 35 35 50 22 35 35 50 22 35 �00 22 35 50660/690 V - 8 �0 �0 75 8 �0 �0 20 8 �0 �0 20 �0 (2) 20 (2) 75 (2) �0 (2) 20 (2) 35 (2)

Service breaking capacity (kA rms) lcs % Icu 50 % �00 % (3) �00 % �00 % �00 % �00 % (4)

Suitability for isolation b b b b b bUtilisation category A A A A A ADurability (C-O cycles) mechanical �0000 50000 40000 20000 �5000 �5000

electrical 440 V In/2 6000 50000 40000 20000 �2000 8000In 6000 30000 20000 �0000 6000 4000

Electrical characteristics as per NEMA AB1 (H.I.C.) E N SX H L N SX H L N SX H L N H L N H LBreaking capacity (kA) 240 V 5 85 90 �00 200 85 90 �00 200 85 90 �00 200 85 �00 200 85 �00 200

480 V 5 35 50 65 �30 35 50 65 �30 35 50 65 �30 42 65 �30 42 65 �30600 V - 8 20 35 50 20 20 35 50 20 20 35 50 20 35 50 20 35 50

Electrical characteristics as per UL508 E N SX H L N SX H L N SX H L N H L N H LBreaking capacity (kA) 240 V - 85 85 85 - 85 85 85 - 85 85 85 - - - - - - -

480 V - 25 50 65 - 35 50 65 - 35 50 65 - - - - - - -600 V - �0 �0 �0 - �0 �0 �0 - �8 �8 �8 - - - - - - -

ProtectionTrip units non interchangeable TM (thermal-magnetic) STR22 (electronic) STR23 (electronic) STR53 (electronic)Overload protection long time Ir (In x …) �2.5… �25 (A) b b b bShort-circuit protection short time lsd (Ir x …) - - b b b

instantaneous Ii (In x …) - b b b bEarth-fault protection lg (In x …) - - - - bZone selective interlocking ZSI - - - - bAdd-on earth-leakage protection add-on Vigi module b b b b b

combination with Vigirex relay b b b b bCurrent measurements - - - - bAdditional measurement, indication and control auxiliaries

Indication contacts b b bMX shunt and MN undervoltage releases b b b Voltage-presence indicator - b bCurrent-transformer module and ammeter module - b bInsulation-monitoring module - b bRemote communication by bus

Device-status indication - b b b bDevice remote operation - b b b bTransmission of settings - - - - bIndication and identification of protection devices and alarms - - - - bTransmission of measured current values - - - - bInstallation

Accessories terminal extensions and spreaders b b bterminal shields and interphase barriers b b bescutcheons b b b

Dimensions (mm) W x H x D fixed, front connections 2-3P / 4P �05 x �6� x 86 / �40 x �6� x 86 �40 x 255 x ��0 / �85 x 255 x ��0Weight (kg) fixed, front connections 3P / 4P 2.0 to 2.2 / 2.6 to 2.8 6.2 to 8.�Source changeover system (see section on source changeover systems)

Manual, remote-operated and automatic source changeover systems - b b

Protection of distribution systemsCompact NS circuit breakers up to 630 A

Compact NSP

B�0

�050

_33

Compact NS250H

PB

�0�0

44_4

2

Compact NS630N

(1) 2P in 3P case for type N only(2) specific trip units are available for operational voltages > 525 V(3) NS100N et U u 500 V: Ics = 50 % Icu(4) operational voltage y 500 V

Page 15: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

�3

Protection of distribution systemsCompact NS circuit breakers up to 630 A

Compact NS

Compact circuit breakers NS125E NS100 NS160 NS250 NS400 NS630Number of poles 3, 4 2 (1), 3, 4 2 (1), 3, 4 2 (1), 3, 4 3, 4 3, 4Control manual toggle b b b b b b

direct or extended rotary handle - b b b b belectric - b b b b b

Connections fixed front connection b b b b b brear connection b b b b b b

plug-in (on base) front connection - b b b b brear connection - b b b b b

withdrawable (on chassis) front connection - b b b b brear connection - b b b b b

Electrical characteristics as per IEC 60947-2 and EN 60947-2Rated current (A) In 40 °C �25 �00 �60 250 400 630

65 °C - �00 �50 220 320 500Rated insulation voltage (V) Ui 750 750 750 750 750 750Rated impulse withstand voltage (kV) Uimp 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 500 690 690 690 690 690

DC - 750 750 750 750 750Type of circuit breaker E N SX H L N SX H L N SX H L N H L N H LUltimate breaking capacity (kA rms) lcu AC 220/240 V 25 85 90 �00 �50 85 90 �00 �50 85 90 �00 �50 85 �00 �50 85 �00 �50

50/60 Hz 380/4�5 V �6/�0 36 50 70 �50 36 50 70 �50 36 50 70 �50 50 70 �50 50 70 �50440 V �0 35 50 65 �30 35 50 65 �30 35 50 65 �30 42 65 �30 42 65 �30500 V 6 25 36 50 �00 30 36 50 70 30 36 50 70 30 50 �00 30 50 70525 V - 22 35 35 �00 22 35 35 50 22 35 35 50 22 35 �00 22 35 50660/690 V - 8 �0 �0 75 8 �0 �0 20 8 �0 �0 20 �0 (2) 20 (2) 75 (2) �0 (2) 20 (2) 35 (2)

Service breaking capacity (kA rms) lcs % Icu 50 % �00 % (3) �00 % �00 % �00 % �00 % (4)

Suitability for isolation b b b b b bUtilisation category A A A A A ADurability (C-O cycles) mechanical �0000 50000 40000 20000 �5000 �5000

electrical 440 V In/2 6000 50000 40000 20000 �2000 8000In 6000 30000 20000 �0000 6000 4000

Electrical characteristics as per NEMA AB1 (H.I.C.) E N SX H L N SX H L N SX H L N H L N H LBreaking capacity (kA) 240 V 5 85 90 �00 200 85 90 �00 200 85 90 �00 200 85 �00 200 85 �00 200

480 V 5 35 50 65 �30 35 50 65 �30 35 50 65 �30 42 65 �30 42 65 �30600 V - 8 20 35 50 20 20 35 50 20 20 35 50 20 35 50 20 35 50

Electrical characteristics as per UL508 E N SX H L N SX H L N SX H L N H L N H LBreaking capacity (kA) 240 V - 85 85 85 - 85 85 85 - 85 85 85 - - - - - - -

480 V - 25 50 65 - 35 50 65 - 35 50 65 - - - - - - -600 V - �0 �0 �0 - �0 �0 �0 - �8 �8 �8 - - - - - - -

ProtectionTrip units non interchangeable TM (thermal-magnetic) STR22 (electronic) STR23 (electronic) STR53 (electronic)Overload protection long time Ir (In x …) �2.5… �25 (A) b b b bShort-circuit protection short time lsd (Ir x …) - - b b b

instantaneous Ii (In x …) - b b b bEarth-fault protection lg (In x …) - - - - bZone selective interlocking ZSI - - - - bAdd-on earth-leakage protection add-on Vigi module b b b b b

combination with Vigirex relay b b b b bCurrent measurements - - - - bAdditional measurement, indication and control auxiliaries

Indication contacts b b bMX shunt and MN undervoltage releases b b b Voltage-presence indicator - b bCurrent-transformer module and ammeter module - b bInsulation-monitoring module - b bRemote communication by bus

Device-status indication - b b b bDevice remote operation - b b b bTransmission of settings - - - - bIndication and identification of protection devices and alarms - - - - bTransmission of measured current values - - - - bInstallation

Accessories terminal extensions and spreaders b b bterminal shields and interphase barriers b b bescutcheons b b b

Dimensions (mm) W x H x D fixed, front connections 2-3P / 4P �05 x �6� x 86 / �40 x �6� x 86 �40 x 255 x ��0 / �85 x 255 x ��0Weight (kg) fixed, front connections 3P / 4P 2.0 to 2.2 / 2.6 to 2.8 6.2 to 8.�Source changeover system (see section on source changeover systems)

Manual, remote-operated and automatic source changeover systems - b b

Page 16: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

�4

Compact circuit breakers NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS3200Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4Control manual toggle b b b b b

direct or extended rotary handle b b b b -electric b (except LB) b b b -

Type of circuit breaker N H L LB N H L N H N H N HConnections fixed front connection b b b - b b b b b b b b b

rear connection b b b b b b b b b b b - -front connection with bare cables b b - - b b - b b - - - -

withdrawable (on chassis) front connection b b b b b b b b b b b - -rear connection b b b b b b b b b b b - -

Electrical characteristics as per IEC 60947-2 and EN 60947-2Rated current (A) In 50 °C 630 800 �000 �250 �600 �600 2000 2500 3200

65 °C (1) 630 800 �000 �250 �5�0 �550 �900 2500 2970Rated insulation voltage (V) Ui 800 800 800 800 800Rated impulse withstand voltage (kV) Uimp 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690Type of circuit breaker N H L LB N H L N H N H N HUltimate breaking capacity (kA rms) lcu AC 220/240 V 50 70 �50 200 50 70 �50 50 70 50 70 85 �25

50/60 Hz 380/4�5 V 50 70 �50 200 50 70 �50 50 70 50 70 70 85440 V 50 65 �30 200 50 65 �30 50 65 50 65 65 85500/525 V 40 50 �00 �00 40 50 �00 40 50 40 50 65 -660/690 V 30 42 - 75 30 42 - 30 42 30 42 65 -

Service breaking capacity (kA rms) lcs Value or % Icu manual operation �00 % 75 % �00 % �00 % �00 % 75 % �00 % �00 % 75 % 75 % 50 % �00 % (2) 75 % electrical operation 75 % 50 % �00 % - 75 % 50 % �00 % 75 % 50 % 75 % 50 % �00 % (2) 75 %

Short-time withstand current (kA rms) lcw AC 50/60 Hz � s �9.2 �9.2 - - �9.2 �9.2 - �9.2 �9.2 �9.2 �9.2 - -3 s - - - - - - - - - - - 32 32

Integrated instantaneous protection kA peak ±�0 % 40 40 - - 40 40 - 40 40 40 40 �30 �30Suitability for isolation b b b b bUtilisation category B B A A B B A B B B B B BDurability (C-O cycles) mechanical �0000 �0000 �0000 �0000 5000

electrical 440 V In/2 6000 6000 4000 4000 6000 6000 4000 5000 5000 3000In 5000 5000 3000 3000 5000 5000 3000 4000 2000 2000

690 V In/2 4000 4000 3000 3000 4000 4000 3000 3000 2000 2000In 2000 2000 2000 2000 2000 2000 2000 2000 �000 �000

Pollution degree 3 3 3 3 3Electrical characteristics as per Nema AB1 N H L LB N H L N H N H N H

Breaking capacity at 60 Hz (kA) 240 V 50 65 �25 200 50 65 �25 50 65 50 65 85 �25480 V 35 50 �00 200 35 50 �00 35 50 35 50 65 85600 V 25 50 - �00 25 50 - 25 50 25 50 50 -

Protection and measurementsInterchangeable control units Micrologic 2.0 Micrologic 5.0 Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A Micrologic 5.0 P (3) Micrologic 6.0 P (3) Micrologic 7.0 P (3)

Overload protection long time Ir (In x …) b b b b b b b b bShort-circuit protection short time Isd (Ir x …) - b - b b b b b b

instantaneous Ii (In x …) b b b b b b b b bEarth-fault protection lg (In x …) - - - - b - - b -Residual earth-leakage protection I∆n - - - - - b b b bZone selective interlocking ZSI - - b b b b b b bProtection of the fourth pole b b b b b b b b bCurrent measurements - - b b b b b b bPower measurements - - - b b b b b bAdvanced protection - - - b b b b b bRemote communication by bus

Device-status indication b b b b b b b b bDevice remote operation b b b b - - b b bTransmission of settings - - b b b b b b bIndication and identification of protection devices and alarms - - b b b b - - -Transmission of measured current values - - b b b b b b bAdditional indication and control auxiliaries

Indication contacts b bVoltage releases MX shunt release/MN undervoltage release b bInstallation

Accessories terminal extensions and spreaders b -terminal shields and interphase barriers b bescutcheons b b

Dimensions fixed devices, front connections (mm) 3P 327 x 2�0 x �47 350 x 420 x �60H x W x D 4P 327 x 280 x �47 350 x 535 x �60Weight fixed devices, front connections (kg) 3P �4 24

4P �8 36Source changeover system (see section on "source changeover systems")

Manual, remote-operated and automatic source changeover systems

b -

Protection of distribution systemsCompact NS circuit breakers from 630 up to 3200 A

Compact NSP

B�0

339�

_SE

_43

Compact NS800L

PB

�047

99

Compact NS2000H

(1) 65 °C with vertical connections. See the temperature derating tables for other types of connections.(2) Ics: 100 % Icu for breaking capacity 440V/500V/660VIcs: 75 % Icu for breaking capacity 220V/380V.(3) Except 1600b-3200.

Page 17: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

�5

Protection of distribution systemsCompact NS circuit breakers from 630 up to 3200 A

Compact NS

Compact circuit breakers NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS3200Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4Control manual toggle b b b b b

direct or extended rotary handle b b b b -electric b (except LB) b b b -

Type of circuit breaker N H L LB N H L N H N H N HConnections fixed front connection b b b - b b b b b b b b b

rear connection b b b b b b b b b b b - -front connection with bare cables b b - - b b - b b - - - -

withdrawable (on chassis) front connection b b b b b b b b b b b - -rear connection b b b b b b b b b b b - -

Electrical characteristics as per IEC 60947-2 and EN 60947-2Rated current (A) In 50 °C 630 800 �000 �250 �600 �600 2000 2500 3200

65 °C (1) 630 800 �000 �250 �5�0 �550 �900 2500 2970Rated insulation voltage (V) Ui 800 800 800 800 800Rated impulse withstand voltage (kV) Uimp 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690Type of circuit breaker N H L LB N H L N H N H N HUltimate breaking capacity (kA rms) lcu AC 220/240 V 50 70 �50 200 50 70 �50 50 70 50 70 85 �25

50/60 Hz 380/4�5 V 50 70 �50 200 50 70 �50 50 70 50 70 70 85440 V 50 65 �30 200 50 65 �30 50 65 50 65 65 85500/525 V 40 50 �00 �00 40 50 �00 40 50 40 50 65 -660/690 V 30 42 - 75 30 42 - 30 42 30 42 65 -

Service breaking capacity (kA rms) lcs Value or % Icu manual operation �00 % 75 % �00 % �00 % �00 % 75 % �00 % �00 % 75 % 75 % 50 % �00 % (2) 75 % electrical operation 75 % 50 % �00 % - 75 % 50 % �00 % 75 % 50 % 75 % 50 % �00 % (2) 75 %

Short-time withstand current (kA rms) lcw AC 50/60 Hz � s �9.2 �9.2 - - �9.2 �9.2 - �9.2 �9.2 �9.2 �9.2 - -3 s - - - - - - - - - - - 32 32

Integrated instantaneous protection kA peak ±�0 % 40 40 - - 40 40 - 40 40 40 40 �30 �30Suitability for isolation b b b b bUtilisation category B B A A B B A B B B B B BDurability (C-O cycles) mechanical �0000 �0000 �0000 �0000 5000

electrical 440 V In/2 6000 6000 4000 4000 6000 6000 4000 5000 5000 3000In 5000 5000 3000 3000 5000 5000 3000 4000 2000 2000

690 V In/2 4000 4000 3000 3000 4000 4000 3000 3000 2000 2000In 2000 2000 2000 2000 2000 2000 2000 2000 �000 �000

Pollution degree 3 3 3 3 3Electrical characteristics as per Nema AB1 N H L LB N H L N H N H N H

Breaking capacity at 60 Hz (kA) 240 V 50 65 �25 200 50 65 �25 50 65 50 65 85 �25480 V 35 50 �00 200 35 50 �00 35 50 35 50 65 85600 V 25 50 - �00 25 50 - 25 50 25 50 50 -

Protection and measurementsInterchangeable control units Micrologic 2.0 Micrologic 5.0 Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A Micrologic 5.0 P (3) Micrologic 6.0 P (3) Micrologic 7.0 P (3)

Overload protection long time Ir (In x …) b b b b b b b b bShort-circuit protection short time Isd (Ir x …) - b - b b b b b b

instantaneous Ii (In x …) b b b b b b b b bEarth-fault protection lg (In x …) - - - - b - - b -Residual earth-leakage protection I∆n - - - - - b b b bZone selective interlocking ZSI - - b b b b b b bProtection of the fourth pole b b b b b b b b bCurrent measurements - - b b b b b b bPower measurements - - - b b b b b bAdvanced protection - - - b b b b b bRemote communication by bus

Device-status indication b b b b b b b b bDevice remote operation b b b b - - b b bTransmission of settings - - b b b b b b bIndication and identification of protection devices and alarms - - b b b b - - -Transmission of measured current values - - b b b b b b bAdditional indication and control auxiliaries

Indication contacts b bVoltage releases MX shunt release/MN undervoltage release b bInstallation

Accessories terminal extensions and spreaders b -terminal shields and interphase barriers b bescutcheons b b

Dimensions fixed devices, front connections (mm) 3P 327 x 2�0 x �47 350 x 420 x �60H x W x D 4P 327 x 280 x �47 350 x 535 x �60Weight fixed devices, front connections (kg) 3P �4 24

4P �8 36Source changeover system (see section on "source changeover systems")

Manual, remote-operated and automatic source changeover systems

b -

Page 18: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Compact NS - Direct Current

DC circuit breakers characteristics 0 Compact NS100 to NS630

PB

�0�0

47-�

4

Compact circuit breaker NS100 NS160 NS250 NS400 NS630Number of poles � 2 3/4 � 2 3/4 3/4 3/4 3/4Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2

Rated current at 40 °C In (A) �00 �60 250 400 550Rated insulation voltage Ui (V) 750 750 750 750 750Rated impulse withstand voltage Uimp (kV peak) 8 8 8 8 8Rated operational voltage Ue (V DC) 250 500 750 250 500 750 750 750 750Type of circuit breaker N H N H DC N H N H DC DC DC DC

Ultimate breaking capacity (L/R = 5 ms and L/R = �5 ms)

Icu (kA rms) V DC 48-�25 V (�P) (1) 50 85 85 �00 �00 50 85 85 �00 �00 �00 �00 �00250 V (�P) (1) 50 85 85 �00 �00 50 85 85 �00 �00 �00 �00 �00500 V (2P) (1) - - 85 �00 �00 - - 85 �00 �00 �00 �00 �00750 V (3P) (1) - - - - �00 - - - - �00 �00 �00 �00

PB

�0�0

48-2

0

Service breaking capacity Ics % Icu �00 %Rated making capacity Icm % Icu �00 %Utilisation category ABreaking time (ms) < �0 msSuitability for isolation b

Pollution degree (as per IEC 60664-�) 3Protection against overcurrents (see on catalogue LVPED208006EN)

Trip units Built-in b b b b - b b b b - - b b

Interchangeable - - - - b - - - - b b - -Protection Overloads b b b b b b b b b b - - -

Short-circuits b b b b b b b b b b b b b

Durability

PB

�0�0

55-2

7

(O/C cycles) Mechanical �0000 5000Electrical 250 V In 5000 �000

250 V In/2 �0000 2000500 V In 5000 �000500 V In/2 �0000 2000750 V In 5000 �000750 V In/2 �0000 2000

Indication and control auxiliariesAuxiliary contacts b

Voltage release MX shunt release b

MN undervoltage release b

Installation and connectionsFixed Front connection b

PB

�009

05-3

6

Rear connection b

Plug-in (base) Front connection - - - - b - - - - b b b b

Rear connection - - - - b - - - - b b b b

Withdrawable (chassis) Front connection - - - - b - - - - b b b b

Rear connection - - - - b - - - - b b b b

Dimensions and weightDimensions H x W x D (mm) connected in series

Fixed �P �6� x 35 x 86 - - �6� x 35 x 86 - - -2P - �6� x 70 x 86 - - �6� x 70 x 86 - -3P - - �6� x �05 x 86 - - �6� x �05 x 86 255 x �40 x ��04P - - �6� x �40 x 86 - - �6� x �40 x 86 225 x �85 x ��0

Weight (kg) connected in series

Fixed �P 0.7 - - 0.7 - - -2P - �.2 - - �.2 - -3P - - �.6 to �.9 - - �.6 to �.9 6.04P - - 2.� to 2.3 - - 2.� to 2.3 7.8

(1) Number of poles taking part in current interruption.Example. The NS100N circuit breaker exists in the following versions:- 1 pole with an Icu of 50 kA, for systems y 250 V- 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.

�6

Page 19: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Compact NS - Direct Current

DC circuit breaker characteristics 0 Compact NS100 to NS630

PB

�0�0

47-�

4

Compact circuit breaker NS100 NS160 NS250 NS400 NS630Number of poles � 2 3/4 � 2 3/4 3/4 3/4 3/4Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2

Rated current at 40 °C In (A) �00 �60 250 400 550Rated insulation voltage Ui (V) 750 750 750 750 750Rated impulse withstand voltage Uimp (kV peak) 8 8 8 8 8Rated operational voltage Ue (V DC) 250 500 750 250 500 750 750 750 750Type of circuit breaker N H N H DC N H N H DC DC DC DC

Ultimate breaking capacity (L/R = 5 ms and L/R = �5 ms)

Icu (kA rms) V DC 48-�25 V (�P) (1) 50 85 85 �00 �00 50 85 85 �00 �00 �00 �00 �00250 V (�P) (1) 50 85 85 �00 �00 50 85 85 �00 �00 �00 �00 �00500 V (2P) (1) - - 85 �00 �00 - - 85 �00 �00 �00 �00 �00750 V (3P) (1) - - - - �00 - - - - �00 �00 �00 �00

PB

�0�0

48-2

0

Service breaking capacity Ics % Icu �00 %Rated making capacity Icm % Icu �00 %Utilisation category ABreaking time (ms) < �0 msSuitability for isolation b

Pollution degree (as per IEC 60664-�) 3Protection against overcurrents (see on catalogue LVPED208006EN)

Trip units Built-in b b b b - b b b b - - b b

Interchangeable - - - - b - - - - b b - -Protection Overloads b b b b b b b b b b - - -

Short-circuits b b b b b b b b b b b b b

Durability

PB

�0�0

55-2

7

(O/C cycles) Mechanical �0000 5000Electrical 250 V In 5000 �000

250 V In/2 �0000 2000500 V In 5000 �000500 V In/2 �0000 2000750 V In 5000 �000750 V In/2 �0000 2000

Indication and control auxiliariesAuxiliary contacts b

Voltage release MX shunt release b

MN undervoltage release b

Installation and connectionsFixed Front connection b

PB

�009

05-3

6

Rear connection b

Plug-in (base) Front connection - - - - b - - - - b b b b

Rear connection - - - - b - - - - b b b b

Withdrawable (chassis) Front connection - - - - b - - - - b b b b

Rear connection - - - - b - - - - b b b b

Dimensions and weightDimensions H x W x D (mm) connected in series

Fixed �P �6� x 35 x 86 - - �6� x 35 x 86 - - -2P - �6� x 70 x 86 - - �6� x 70 x 86 - -3P - - �6� x �05 x 86 - - �6� x �05 x 86 255 x �40 x ��04P - - �6� x �40 x 86 - - �6� x �40 x 86 225 x �85 x ��0

Weight (kg) connected in series

Fixed �P 0.7 - - 0.7 - - -2P - �.2 - - �.2 - -3P - - �.6 to �.9 - - �.6 to �.9 6.04P - - 2.� to 2.3 - - 2.� to 2.3 7.8

(1) Number of poles taking part in current interruption.Example. The NS100N circuit breaker exists in the following versions:- 1 pole with an Icu of 50 kA, for systems y 250 V- 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.

�7

Page 20: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

PB

�043

78A

48 Common characteristics Sensor selectionSensor rating (A) 250 (1) 400 630 800 �000 �250 �600Ir threshold setting(A) �00 to 250 �60 to 400 250 to 630 320 to 800 400 to �000 500 to �250 640 to �600(1) For circuit-breaker NT02, please consult us.

Number of poles 3/4Rated insulation voltage (V) Ui �000Impulse withstand voltage (kV) Uimp �2Rated operational voltage (V AC 50/60 Hz) Ue 690Suitability for isolation IEC 60947-2 Degree of pollution IEC 60664-� 3

Basic sweatchgear NT06 NT08 NT10 NT12 NT16Circuit-breaker as per IEC 60947-2

Rated current (A) In at 40 °C/50 °C (1) 630 800 �000 �250 �600Rating of 4th pole (A) 630 800 �000 �250 �600Sensor ratings (A) 400 to 630 400 to 800 400 to �000 630 to �250 800 to �600Type of circuit breaker H1 H2 L1 (2) H1 H2

Ultimate breaking capacity (kA rms) Icu 220/4�5 V 42 50 �50 42 50V AC 50/60 Hz 440 V 42 50 �30 42 50

525 V 42 42 �00 42 42690 V 42 42 25 42 42

Rated service breaking capacity (kA rms) Ics % Icu �00 % �00 %Utilisation category B B A B BRated short-time withstand current (kA rms)V AC 50/60 Hz

Icw 0.5 s 42 36 �0 42 36� s 42 36 - 42 363 s 24 20 - 24 20

Integrated instantaneous protection (kA peak ±�0 %) - 90 �0 x In (3) - 90Rated making capacity (kA peak) Icm 220/4�5 V 88 �05 330 88 �05V AC 50/60 Hz 440 V 88 �05 286 88 �05

525 V 88 88 220 88 88690 V 88 88 52 88 88

Break time (ms) between tripping order and arc extinction 25 25 9 25 25Closing time (ms) < 50 < 50Circuit-breaker as per NEMA AB1

Breaking capacity (kA)V AC 50/60 Hz

240 V 42 50 �50 42 50480 V 42 50 �00 42 50600 V 42 42 25 42 42

(1) 50 °C: rear vertical connected. Refer to temperature derating tables for other connection types.(2) See the current-limiting curves in the “additional characteristics” section.(3) SELLIM system.(4) Available for 480 V NEMA.(5) Suitable for motor control (direct-on-line starting).

Switch-disconnector as per IEC 60947-3 and Annex AType of switch-disconnector HA HA

Rated making capacity (kA peak) Icm 220 V 75 75AC23A/AC3 category V AC 50/60 Hz 440 V 75 75

525/690 V 75 75Rated short-time withstand current (kA rms) Icw 0.5 s 36 36AC23A/AC3 category V AC 50/60 Hz � s 36 36

3 s 20 20Ultimate breaking capacity Icu (kA rms) with an external protection relay Maximum time delay: 350 ms

690 V 36 36

Mechanical and electrical durability as per IEC 60947-2/3 at In/IeService life Mechanical without maintenance �2.5C/O cycles x �000Type of circuit breaker H1 H2 L1 H1 H2 L1 H1 H2 L1 H1 H2 H1 H2Rated current In (A) 630 800 1000 1250

C/O cycles x �000 Electrical without maintenance 440 V (4) 6 6 3 6 6 3 6 6 3 6 6 3 3IEC 60947-2 690 V 3 3 2 3 3 2 3 3 2 3 3 � �Type of circuit breaker or switch-disconnector H1/H2/HARated operationnal current Ie (A) AC23A 630 800 1000 1250 1600

C/O cycles x �000 Electrical without maintenance 440 V (4) 6 6 6 6 3IEC 60947-3 690V 3 3 3 3 �Type of circuit breaker or switch-disconnector H1/H2/HARated operationnal current Ie (A) AC3 (5) 500 630 800 1000 1000

Motor power 380/4�5 V (kW) y 250 250 to 335 335 to 450 450 to 560 450 to 560440 V (kW) y 300 300 to 400 400 to 500 500 to 630 500 to 630

C/O cycles x �000 Electrical without maintenance 440 V (4) 6IEC 60947-3 Annex M/IEC 60947-4-� 690 V -

Masterpact NT and NW Circuit breakers and switch-disconnectors 0 NT06 to NT16

�8

Page 21: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact NT and NW Circuit breakers and switch-disconnectors 0 NT06 to NT16

PB

�043

78A

48 Common characteristics Sensor selectionSensor rating (A) 250 (1) 400 630 800 �000 �250 �600Ir threshold setting(A) �00 to 250 �60 to 400 250 to 630 320 to 800 400 to �000 500 to �250 640 to �600(1) For circuit-breaker NT02, please consult us.

Number of poles 3/4Rated insulation voltage (V) Ui �000Impulse withstand voltage (kV) Uimp �2Rated operational voltage (V AC 50/60 Hz) Ue 690Suitability for isolation IEC 60947-2 Degree of pollution IEC 60664-� 3

Basic sweatchgear NT06 NT08 NT10 NT12 NT16Circuit-breaker as per IEC 60947-2

Rated current (A) In at 40 °C/50 °C (1) 630 800 �000 �250 �600Rating of 4th pole (A) 630 800 �000 �250 �600Sensor ratings (A) 400 to 630 400 to 800 400 to �000 630 to �250 800 to �600Type of circuit breaker H1 H2 L1 (2) H1 H2

Ultimate breaking capacity (kA rms) Icu 220/4�5 V 42 50 �50 42 50V AC 50/60 Hz 440 V 42 50 �30 42 50

525 V 42 42 �00 42 42690 V 42 42 25 42 42

Rated service breaking capacity (kA rms) Ics % Icu �00 % �00 %Utilisation category B B A B BRated short-time withstand current (kA rms)V AC 50/60 Hz

Icw 0.5 s 42 36 �0 42 36� s 42 36 - 42 363 s 24 20 - 24 20

Integrated instantaneous protection (kA peak ±�0 %) - 90 �0 x In (3) - 90Rated making capacity (kA peak) Icm 220/4�5 V 88 �05 330 88 �05V AC 50/60 Hz 440 V 88 �05 286 88 �05

525 V 88 88 220 88 88690 V 88 88 52 88 88

Break time (ms) between tripping order and arc extinction 25 25 9 25 25Closing time (ms) < 50 < 50Circuit-breaker as per NEMA AB1

Breaking capacity (kA)V AC 50/60 Hz

240 V 42 50 �50 42 50480 V 42 50 �00 42 50600 V 42 42 25 42 42

(1) 50 °C: rear vertical connected. Refer to temperature derating tables for other connection types.(2) See the current-limiting curves in the “additional characteristics” section.(3) SELLIM system.(4) Available for 480 V NEMA.(5) Suitable for motor control (direct-on-line starting).

Switch-disconnector as per IEC 60947-3 and Annex AType of switch-disconnector HA HA

Rated making capacity (kA peak) Icm 220 V 75 75AC23A/AC3 category V AC 50/60 Hz 440 V 75 75

525/690 V 75 75Rated short-time withstand current (kA rms) Icw 0.5 s 36 36AC23A/AC3 category V AC 50/60 Hz � s 36 36

3 s 20 20Ultimate breaking capacity Icu (kA rms) with an external protection relay Maximum time delay: 350 ms

690 V 36 36

Mechanical and electrical durability as per IEC 60947-2/3 at In/IeService life Mechanical without maintenance �2.5C/O cycles x �000Type of circuit breaker H1 H2 L1 H1 H2 L1 H1 H2 L1 H1 H2 H1 H2Rated current In (A) 630 800 1000 1250

C/O cycles x �000 Electrical without maintenance 440 V (4) 6 6 3 6 6 3 6 6 3 6 6 3 3IEC 60947-2 690 V 3 3 2 3 3 2 3 3 2 3 3 � �Type of circuit breaker or switch-disconnector H1/H2/HARated operationnal current Ie (A) AC23A 630 800 1000 1250 1600

C/O cycles x �000 Electrical without maintenance 440 V (4) 6 6 6 6 3IEC 60947-3 690V 3 3 3 3 �Type of circuit breaker or switch-disconnector H1/H2/HARated operationnal current Ie (A) AC3 (5) 500 630 800 1000 1000

Motor power 380/4�5 V (kW) y 250 250 to 335 335 to 450 450 to 560 450 to 560440 V (kW) y 300 300 to 400 400 to 500 500 to 630 500 to 630

C/O cycles x �000 Electrical without maintenance 440 V (4) 6IEC 60947-3 Annex M/IEC 60947-4-� 690 V -

�9

Page 22: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact NT and NW Circuit breakers and switch-disconnectors 0 NW08 to NW63

PB

�044

23A

35 Common characteristics Sensor selectionNumber of poles 3/4 Sensor rating (A) 250 (1) 400 630 800 �000 �250 �600 2000 2500 3200 4000 5000 6300Rated insulation voltage (V) Ui �000/�250 Ir threshold setting(A) �00 �60 250 320 400 500 630 800 �000 �250 �600 2000 2500Impulse withstand voltage (kV) Uimp �2 to 250 to 400 to 630 to 800 to �000 to �250 to �600 to 2000 to 2500 to 3200 to 4000 to 5000 to 6300Rated operational voltage (V AC 50/60 Hz) Ue 690/��50 (1) For circuit-breaker NW02 , please consult us.Suitability for isolation IEC 60947-2 Degree of pollution IEC 60664-� 4 (�000 V) / 3 (�250 V)

PB

�044

33A

65

Basic circuit-breaker NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63Circuit-breaker as per IEC 60947-2

Rated current (A) at 40 °C / 50 °C (1) 800 �000 �250 �600 2000 2500 3200 4000 4000 5000 6300Rating of 4th pole (A) 800 �000 �250 �600 2000 2500 3200 4000 4000 5000 6300Sensor ratings (A) 400

to 800400to �000

630to �250

800 to �600 �000 to 2000 �250to 2500

�600to 3200

2000 to 4000 2000to 4000

2500to 5000

3200to 6300

Type of circuit breaker N1 H1 H2 L1 (2) H10 H1 H2 H3 L1 (2) H10 H1 H2 H3 H10 H1 H2Ultimate breaking capacity (kA rms)V AC 50/60 Hz

Icu 220/4�5/440 V 42 65 �00 �50 - 65 �00 �50 �50 - 65 �00 �50 - �00 �50525 V 42 65 85 �30 - 65 85 �30 �30 - 65 85 �30 - �00 �30690 V 42 65 85 �00 - 65 85 �00 �00 - 65 85 �00 - �00 �00��50 V - - - - 50 - - - - 50 - - - 50 - -

Rated service breaking capacity (kA rms) Ics % Icu �00 % �00 % �00 % �00 %Utilisation category B B B BRated short-time withstand current (kA rms)V AC 50/60 Hz

Icw � s 42 65 85 30 50 65 85 65 30 50 65 85 65 50 �00 �003 s 22 36 50 30 50 36 75 65 30 50 65 75 65 50 �00 �00

Integrated instantaneous protection (kA peak ±�0 %) - - �90 80 - - �90 �50 80 - - �90 �50 - - 270Rated making capacity (kA peak)V AC 50/60 Hz

Icm 220/4�5/440 V 88 �43 220 330 - �43 220 330 330 - �43 220 330 - 220 330525 V 88 �43 �87 286 - �43 �87 286 286 - �43 �87 286 - 220 286690 V 88 �43 �87 220 - �43 �87 220 220 - �43 �87 220 - 220 220��50 V - - - - �05 - - - - �05 - - - �05 - -

Break time (ms) between tripping order and arc extinction 25 25 25 �0 25 25 25 25 �0 25 25 25 25 25 25 25Closing time (ms) < 70 < 70 < 70 < 80Circuit-breaker as per NEMA AB1

Breaking capacity (kA)V AC 50/60 Hz

240/480 V 42 65 �00 �50 - 65 �00 �50 �50 - 65 �00 �50 - �00 �50600 V 42 65 85 �00 - 65 85 �00 �00 - 65 85 �00 - �00 �00

Unprotected circuit-breakerTripping by shunt trip as per IEC 60947-2Type of circuit breaker HA HF (3) HA HF (3) HA HF (3) HA

Ultimate breaking capacity (kA rms) V AC 50/60 Hz Icu 220...690 V 50 85 50 85 55 85 85Rated service breaking capacity (kA rms) Ics % Icu �00 % �00 % �00 % �00 %Rated short-time withstand current (kA rms) Icw � s 50 85 50 85 55 85 85

3 s 36 50 36 75 55 75 85Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4)

- - - - - - -

Rated making capacity (kA peak) V AC 50/60 Hz Icm 220...690 V �05 �87 �05 �87 �2� �87 �87

(1) 50 °C: rear vertical connected. Refer to temperature derating tables for other connection types.(2) See the current-limiting curves in the “additional characteristics” section.(3) Equipped with a trip unit with a making current of 90 kA peak.(4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us). No fault-trip indication by the SDE or the reset button.(5) Available for 480 V NEMA.(6) Suitable for motor control (direct-on-line starting).

Switch-disconnector as per IEC 60947-3 and Annex A NW08/NW10/NW12 NW16 NW20 NW25/NW32/NW40 NW40b/NW50/NW63Type of switch-disconnector NA HA HF HA10 HA HF HA10 HA HF HA10 HA HF HA10 HA

Rated making capacity (kA peak)AC23A/AC3 category V AC 50/60 Hz

Icm 220...690 V 88 �05 �87 - �05 �87 - �05 �87 - �2� �87 - �87��50 V - - - �05 - - �05 - - �05 - - �05 -

Rated short-time withstand current (kA rms)AC23A/AC3 category V AC 50/60 Hz

Icw � s 42 50 85 50 50 85 50 50 85 50 55 85 50 853 s - 36 50 50 36 50 50 36 75 50 55 75 50 85

Earthing switchLatching capacity (kA peak) �35Rating short time withstand (kA rms) Icw � s 60 Hz

3 s 50 Hz

Mechanical and electrical durability as per IEC 60947-2/3 at In/IeService life Mechanical with maintenance 25 20 �0C/O cycles x �000 without maintenance �2.5 �0 5Type of circuit breaker N1/H1/H2 L1 H10 H1/H2 H3 L1 H10 H1/H2 H3 H10 H1 H2Rated current In (A) 800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/6300

C/O cycles x �000 Electrical without maintenance 440 V (5) �0 3 - 8 2 3 - 5 �.25 - �.5 �.5IEC 60947-2 690 V �0 3 - 6 2 3 - 2.5 �.25 - �.5 �.5

��50 V - - 0.5 - - - 0.5 - - 0.5 - -Type of circuit breaker or switch-disconnector H1/H2/HA/HF H1/H2/H3/HA/HF H1/H2/H3/HA/HF H1/H2/HARated operational current Ie (A) AC23A 800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/6300

C/O cycles x �000 Electrical without maintenance 440 V (5) �0 8 5 �.5IEC 60947-3 690 V �0 6 2.5 �.5Type of circuit breaker or switch-disconnector H1/H2/HA/HF H1/H2/H3/HA/HFRated operational current Ie (A) AC3 (6) 800 1000 1250 1600 2000

Motor power 380/4�5 V (kW) 335 to 450 450 to 560 560 to 670 670 to 900 900 to ��50440 V (5) (kW) 400 to 500 500 to 630 500 to 800 800 to �000 �000 to �300690 V (kW) y 800 800 to �000 �000 to �250 �250 to �600 �600 to 2000

C/O cycles x �000 Electrical without maintenance 440/690 V (5) 6IEC 60947-3 Annex M/IEC 60947-4-�

20

Page 23: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact NT and NW Circuit breakers and switch-disconnectors 0 NW08 to NW63

PB

�044

23A

35 Common characteristics Sensor selectionNumber of poles 3/4 Sensor rating (A) 250 (1) 400 630 800 �000 �250 �600 2000 2500 3200 4000 5000 6300Rated insulation voltage (V) Ui �000/�250 Ir threshold setting(A) �00 �60 250 320 400 500 630 800 �000 �250 �600 2000 2500Impulse withstand voltage (kV) Uimp �2 to 250 to 400 to 630 to 800 to �000 to �250 to �600 to 2000 to 2500 to 3200 to 4000 to 5000 to 6300Rated operational voltage (V AC 50/60 Hz) Ue 690/��50 (1) For circuit-breaker NW02 , please consult us.Suitability for isolation IEC 60947-2 Degree of pollution IEC 60664-� 4 (�000 V) / 3 (�250 V)

PB

�044

33A

65

Basic circuit-breaker NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63Circuit-breaker as per IEC 60947-2

Rated current (A) at 40 °C / 50 °C (1) 800 �000 �250 �600 2000 2500 3200 4000 4000 5000 6300Rating of 4th pole (A) 800 �000 �250 �600 2000 2500 3200 4000 4000 5000 6300Sensor ratings (A) 400

to 800400to �000

630to �250

800 to �600 �000 to 2000 �250to 2500

�600to 3200

2000 to 4000 2000to 4000

2500to 5000

3200to 6300

Type of circuit breaker N1 H1 H2 L1 (2) H10 H1 H2 H3 L1 (2) H10 H1 H2 H3 H10 H1 H2Ultimate breaking capacity (kA rms)V AC 50/60 Hz

Icu 220/4�5/440 V 42 65 �00 �50 - 65 �00 �50 �50 - 65 �00 �50 - �00 �50525 V 42 65 85 �30 - 65 85 �30 �30 - 65 85 �30 - �00 �30690 V 42 65 85 �00 - 65 85 �00 �00 - 65 85 �00 - �00 �00��50 V - - - - 50 - - - - 50 - - - 50 - -

Rated service breaking capacity (kA rms) Ics % Icu �00 % �00 % �00 % �00 %Utilisation category B B B BRated short-time withstand current (kA rms)V AC 50/60 Hz

Icw � s 42 65 85 30 50 65 85 65 30 50 65 85 65 50 �00 �003 s 22 36 50 30 50 36 75 65 30 50 65 75 65 50 �00 �00

Integrated instantaneous protection (kA peak ±�0 %) - - �90 80 - - �90 �50 80 - - �90 �50 - - 270Rated making capacity (kA peak)V AC 50/60 Hz

Icm 220/4�5/440 V 88 �43 220 330 - �43 220 330 330 - �43 220 330 - 220 330525 V 88 �43 �87 286 - �43 �87 286 286 - �43 �87 286 - 220 286690 V 88 �43 �87 220 - �43 �87 220 220 - �43 �87 220 - 220 220��50 V - - - - �05 - - - - �05 - - - �05 - -

Break time (ms) between tripping order and arc extinction 25 25 25 �0 25 25 25 25 �0 25 25 25 25 25 25 25Closing time (ms) < 70 < 70 < 70 < 80Circuit-breaker as per NEMA AB1

Breaking capacity (kA)V AC 50/60 Hz

240/480 V 42 65 �00 �50 - 65 �00 �50 �50 - 65 �00 �50 - �00 �50600 V 42 65 85 �00 - 65 85 �00 �00 - 65 85 �00 - �00 �00

Unprotected circuit-breakerTripping by shunt trip as per IEC 60947-2Type of circuit breaker HA HF (3) HA HF (3) HA HF (3) HA

Ultimate breaking capacity (kA rms) V AC 50/60 Hz Icu 220...690 V 50 85 50 85 55 85 85Rated service breaking capacity (kA rms) Ics % Icu �00 % �00 % �00 % �00 %Rated short-time withstand current (kA rms) Icw � s 50 85 50 85 55 85 85

3 s 36 50 36 75 55 75 85Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4)

- - - - - - -

Rated making capacity (kA peak) V AC 50/60 Hz Icm 220...690 V �05 �87 �05 �87 �2� �87 �87

(1) 50 °C: rear vertical connected. Refer to temperature derating tables for other connection types.(2) See the current-limiting curves in the “additional characteristics” section.(3) Equipped with a trip unit with a making current of 90 kA peak.(4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us). No fault-trip indication by the SDE or the reset button.(5) Available for 480 V NEMA.(6) Suitable for motor control (direct-on-line starting).

Switch-disconnector as per IEC 60947-3 and Annex A NW08/NW10/NW12 NW16 NW20 NW25/NW32/NW40 NW40b/NW50/NW63Type of switch-disconnector NA HA HF HA10 HA HF HA10 HA HF HA10 HA HF HA10 HA

Rated making capacity (kA peak)AC23A/AC3 category V AC 50/60 Hz

Icm 220...690 V 88 �05 �87 - �05 �87 - �05 �87 - �2� �87 - �87��50 V - - - �05 - - �05 - - �05 - - �05 -

Rated short-time withstand current (kA rms)AC23A/AC3 category V AC 50/60 Hz

Icw � s 42 50 85 50 50 85 50 50 85 50 55 85 50 853 s - 36 50 50 36 50 50 36 75 50 55 75 50 85

Earthing switchLatching capacity (kA peak) �35Rating short time withstand (kA rms) Icw � s 60 Hz

3 s 50 Hz

Mechanical and electrical durability as per IEC 60947-2/3 at In/IeService life Mechanical with maintenance 25 20 �0C/O cycles x �000 without maintenance �2.5 �0 5Type of circuit breaker N1/H1/H2 L1 H10 H1/H2 H3 L1 H10 H1/H2 H3 H10 H1 H2Rated current In (A) 800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/6300

C/O cycles x �000 Electrical without maintenance 440 V (5) �0 3 - 8 2 3 - 5 �.25 - �.5 �.5IEC 60947-2 690 V �0 3 - 6 2 3 - 2.5 �.25 - �.5 �.5

��50 V - - 0.5 - - - 0.5 - - 0.5 - -Type of circuit breaker or switch-disconnector H1/H2/HA/HF H1/H2/H3/HA/HF H1/H2/H3/HA/HF H1/H2/HARated operational current Ie (A) AC23A 800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/6300

C/O cycles x �000 Electrical without maintenance 440 V (5) �0 8 5 �.5IEC 60947-3 690 V �0 6 2.5 �.5Type of circuit breaker or switch-disconnector H1/H2/HA/HF H1/H2/H3/HA/HFRated operational current Ie (A) AC3 (6) 800 1000 1250 1600 2000

Motor power 380/4�5 V (kW) 335 to 450 450 to 560 560 to 670 670 to 900 900 to ��50440 V (5) (kW) 400 to 500 500 to 630 500 to 800 800 to �000 �000 to �300690 V (kW) y 800 800 to �000 �000 to �250 �250 to �600 �600 to 2000

C/O cycles x �000 Electrical without maintenance 440/690 V (5) 6IEC 60947-3 Annex M/IEC 60947-4-�

2�

Page 24: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact NT and NW Micrologic control units 0 Overview of functions

All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site.Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications.Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.

DependabilityIntegration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances.On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.

AccessoriesCertain functions require the addition of Micrologic control unit accessories, described on catalogue LVPED208008EN.The rules governing the various possible combinations can be found in the documentation accessible via the Products and services menu of the www.schneider-electric.com web site.

Measurements and programmable protectionA: ammeter

I�, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurementsfault indicationssettings in amperes and in seconds.

bbb

P: A + power meter + programmable protectionmeasurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and maximeters and minimetersIDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imbalance,

phase sequence, reverse powerload shedding and reconnection depending on power or currentmeasurements of interrupted currents, differentiated fault indications, maintenance indications, event histories

and time-stamping, etc.

bb

bb

H: P + harmonicspower quality: fundamentals, distortion, amplitude and phase of harmonics up to the

3�st orderwaveform capture after fault, alarm or on requestenhanced alarm programming: thresholds and actions.

b

bb

Micrologic name codes Current protection

X: type of protection2 for basic protection5 for selective protection6 for selective + earth-fault protection7 for selective + earth-leakage protection.

Y: control-unit generationIdentification of the control-unit generation.“0” signifies the first generation.Z: type of measurement

A for “ammeter”P for “power meter”H for “harmonic meter”.

bbbb

bbb

Micrologic 2: basic protection

DB

�0��

�6 Protection:long time + instantaneous

2.0 A

DB

�0��

20

Micrologic 5: basic protection

DB

�0��

�7 Protection: long time + short time + instantaneous

5.0 A

DB

�0��

2� 5.0 P

DB

�0��

22 5.0 H

DB

�0��

22

PB

�007

72-3

2 Micrologic 6: selective + earth-fault protection

DB

�0��

�7

DB

�0��

�8 Protection: long time + short time + instantaneous + earth fault

6.0 A

DB

�0��

23 6.0 P

DB

�0��

24 6.0 H

DB

�0��

24

Micrologic 7: selective + earth-leakage protection

DB

�0��

�7

DB

�0��

�9 Protection: long time + short time + instantaneous + earth leakage up to 3200A

7.0 AD

B�0

��23 7.0 P

DB

�0��

24 7.0 H

DB

�0��

24

2.0 AX Y Z

2.0 AX Y Z

22

Page 25: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact NT and NW Micrologic control units 0 Overview of functions

All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site.Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications.Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.

DependabilityIntegration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances.On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.

AccessoriesCertain functions require the addition of Micrologic control unit accessories, described on catalogue LVPED208008EN.The rules governing the various possible combinations can be found in the documentation accessible via the Products and services menu of the www.schneider-electric.com web site.

Measurements and programmable protectionA: ammeter

I�, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurementsfault indicationssettings in amperes and in seconds.

bbb

P: A + power meter + programmable protectionmeasurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and maximeters and minimetersIDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imbalance,

phase sequence, reverse powerload shedding and reconnection depending on power or currentmeasurements of interrupted currents, differentiated fault indications, maintenance indications, event histories

and time-stamping, etc.

bb

bb

H: P + harmonicspower quality: fundamentals, distortion, amplitude and phase of harmonics up to the

3�st orderwaveform capture after fault, alarm or on requestenhanced alarm programming: thresholds and actions.

b

bb

Micrologic name codes Current protection

X: type of protection2 for basic protection5 for selective protection6 for selective + earth-fault protection7 for selective + earth-leakage protection.

Y: control-unit generationIdentification of the control-unit generation.“0” signifies the first generation.Z: type of measurement

A for “ammeter”P for “power meter”H for “harmonic meter”.

bbbb

bbb

Micrologic 2: basic protection

DB

�0��

�6 Protection:long time + instantaneous

2.0 A

DB

�0��

20

Micrologic 5: basic protection

DB

�0��

�7 Protection: long time + short time + instantaneous

5.0 A

DB

�0��

2� 5.0 P

DB

�0��

22 5.0 H

DB

�0��

22

PB

�007

72-3

2 Micrologic 6: selective + earth-fault protection

DB

�0��

�7

DB

�0��

�8 Protection: long time + short time + instantaneous + earth fault

6.0 A

DB

�0��

23 6.0 P

DB

�0��

24 6.0 H

DB

�0��

24

Micrologic 7: selective + earth-leakage protection

DB

�0��

�7

DB

�0��

�9 Protection: long time + short time + instantaneous + earth leakage up to 3200A

7.0 A

DB

�0��

23 7.0 P

DB

�0��

24 7.0 H

DB

�0��

24

2.0 AX Y Z

2.0 AX Y Z

23

Page 26: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact - Direct Current

DC circuit breakers characteristics 0 Masterpact NW10 to NW40

E88

�93-

34A

R_S

E

Masterpact circuit breaker NW10 NW20 NW40Poles coupling version C or D (3 poles) b b b

E (4 poles) b b b

Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2Rated current at 40 °C / 50 °C (1) In (A) �000 2000 4000Rated insulation voltage Ui (V) �000 �000 �000Rated impulse withstand voltage Uimp (kV peak) �2 �2 �2Rated operational voltage Ue (V DC) 500/900 500/900 500/900Type of circuit breaker N H N H N H

Ultimate breaking capacity L/R = 5 ms Icu (kA) V DC 500 85 �00 85 �00 85 �00750 - 85 - 85 - 85

PB

�044

28-4

2SE

900 - 85 - 85 - 85

NW10DC 4P.

L/R = �5 ms Icu 500 35 85 35 85 35 85750 - 50 - 50 - 50900 - 35 - 35 - 35

L/R = 30 ms Icu 500 25 50 25 50 25 50750 - 50 - 50 - 50900 - 25 - 25 - 25

Service breaking capacity Ics % Icu �00 %Rated making capacity Icm % Icu �00 %Short-time withstand current Icw � s 50 85 50 85 50 85Utilisation category BBreaking time (ms) 30 to 75Making time (ms) < 70Suitability for isolation b b b b b b

Pollution degree (as per IEC 60664-�) 4Protection against overcurrents (see on catalogue LVPED208006EN)

Trip units Built-in b b b b b b

Protection Overloads - - - - - -Short-circuits b b b b b b

Durability(O/C cycles) Mechanical With maintenance 20000

Without maintenance �0000Electrical Without maintenance 500 V DC 8500 5000 2000

900 V DC - 2000 - 2000 - �000Indication and control auxiliaries

Auxiliary contacts b b b b b b

Voltage release MX shunt release b b b b b b

MN undervoltage release b b b b b b

Characteristics of switch-disconnectors as per IEC 60947-3 and EN 60947-3Type of switch-disconnector HA HA HA

Rated making capacity Icm (kA) - 85 - 85 - 85Rated short-time withstand current Icw (kA) � s - 85 - 85 - 85Installation and connections

Connection Drawout 3P RC Horizontal b b b b - -4P Vertical b b b b b b

Fixed 3P RC Horizontal b b b b - -4P Vertical b b b b b b

Dimensions and weightDimensions H x W x D (mm) connected in series

Drawout 3P 439 x 44� x 494 439 x 44� x 5944P 439 x 556 x 494 439 x 556 x 594

Fixed 3P 352 x 422 x 427 352 x 422 x 5274P 352 x 537 x 427 352 x 537 x 527

Weight (kg)connected in series (approximate values)

Drawout 3P 90 to ��64P �25 to �46

Fixed 3P 60 to 864P 85 to �06

(1) 50 °C - see the derating table for the NW40.

24

Page 27: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Masterpact - Direct Current

DC circuit breakers characteristics 0 Masterpact NW10 to NW40

E88

�93-

34A

R_S

E

Masterpact circuit breaker NW10 NW20 NW40Poles coupling version C or D (3 poles) b b b

E (4 poles) b b b

Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2Rated current at 40 °C / 50 °C (1) In (A) �000 2000 4000Rated insulation voltage Ui (V) �000 �000 �000Rated impulse withstand voltage Uimp (kV peak) �2 �2 �2Rated operational voltage Ue (V DC) 500/900 500/900 500/900Type of circuit breaker N H N H N H

Ultimate breaking capacity L/R = 5 ms Icu (kA) V DC 500 85 �00 85 �00 85 �00750 - 85 - 85 - 85

PB

�044

28-4

2SE

900 - 85 - 85 - 85

NW10DC 4P.

L/R = �5 ms Icu 500 35 85 35 85 35 85750 - 50 - 50 - 50900 - 35 - 35 - 35

L/R = 30 ms Icu 500 25 50 25 50 25 50750 - 50 - 50 - 50900 - 25 - 25 - 25

Service breaking capacity Ics % Icu �00 %Rated making capacity Icm % Icu �00 %Short-time withstand current Icw � s 50 85 50 85 50 85Utilisation category BBreaking time (ms) 30 to 75Making time (ms) < 70Suitability for isolation b b b b b b

Pollution degree (as per IEC 60664-�) 4Protection against overcurrents (see on catalogue LVPED208006EN)

Trip units Built-in b b b b b b

Protection Overloads - - - - - -Short-circuits b b b b b b

Durability(O/C cycles) Mechanical With maintenance 20000

Without maintenance �0000Electrical Without maintenance 500 V DC 8500 5000 2000

900 V DC - 2000 - 2000 - �000Indication and control auxiliaries

Auxiliary contacts b b b b b b

Voltage release MX shunt release b b b b b b

MN undervoltage release b b b b b b

Characteristics of switch-disconnectors as per IEC 60947-3 and EN 60947-3Type of switch-disconnector HA HA HA

Rated making capacity Icm (kA) - 85 - 85 - 85Rated short-time withstand current Icw (kA) � s - 85 - 85 - 85Installation and connections

Connection Drawout 3P RC Horizontal b b b b - -4P Vertical b b b b b b

Fixed 3P RC Horizontal b b b b - -4P Vertical b b b b b b

Dimensions and weightDimensions H x W x D (mm) connected in series

Drawout 3P 439 x 44� x 494 439 x 44� x 5944P 439 x 556 x 494 439 x 556 x 594

Fixed 3P 352 x 422 x 427 352 x 422 x 5274P 352 x 537 x 427 352 x 537 x 527

Weight (kg)connected in series (approximate values)

Drawout 3P 90 to ��64P �25 to �46

Fixed 3P 60 to 864P 85 to �06

(1) 50 °C - see the derating table for the NW40.

25

Page 28: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS switch-disconnectors INS40 INS63 INS80 INS100 INS125 INS160Number of poles 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C 40 63 80 �00 �25 �60Conventional thermal current in enclosure Ithe at 60 °C 40 63 80 �00 �25 �60Rated insulation level (V) Ui AC 50/60 Hz 690 690 690 750 750 750Impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 500 500 500 690 690 690

DC 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 690 690 690 750 750 750Rated operational current (A) Ie Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220-240 V 40 40 63 63 80 80 �00 �00 �25 �25 �60 �60380-4�5 V 40 40 63 63 80 72 �00 �00 �25 �25 �60 �60440-480 V (1) 40 40 63 63 80 63 �00 �00 �25 �25 �60 �60500 V 40 32 63 40 80 40 �00 �00 �25 �25 �60 �60660-690 V - - - - - - �00 63 �25 80 �60 �00

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A�25 V (2P in series) 40 40 63 63 80 80 �00 �00 �25 �25 �60 �60250 V (4P in series) 40 40 63 63 80 80 �00 �00 �25 �25 �60 �60

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V �� �5 22 22 37 45230 V (NEMA) 7,5 �5 �5 22 37 45380-4�5 V 20 30 37 45 55 75440 V 22 30 37 55 55 90480 V (NEMA) 22 30 30 55 75 90500-525 V �8,5 22 22 55 75 ��0660-690 V - - - 55 75 90

Rated duties Uninterrupted duty b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) �5 �5 �5 20 20 20Max. (with upstream protection circuit breaker)

75 75 75 �54 �54 �54

Short-time withstand current (A rms) Icw � s 3000 3000 3000 5500 5500 55003 s �730 �730 �730 3�75 3�75 3�7520 s 670 670 670 �230 �230 �23030 s 550 550 550 �000 �000 �000

Suitability for isolation b b b b b bDurability (O-C cycles) Mechanical 20000 20000 20000 �5000 �5000 �5000

Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A220-240 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500380-4�5 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500440 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500500 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500690 V - - - - - - �500 �500 �500 �500 �500 �500

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A250 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500

Positive contact indication b b b b b bVisible break - - - - - -Emergency-off switch disconnector b b b b b bDegree of pollution 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - -(1) Suitable for 480 V NEMA.

Interpact INS Switch-disconnector selectionInterpact INS40 to 160

052�

64a-

38

Interpact INS80 switch-disconnector.

0592

03a-

38

Interpact INS40 emergency-off switch-disconnector.

052�

68a-

50

Interpact INS160 switch-disconnector.

0592

02a-

50

Interpact INS160 emergency-off switch-disconnector.

26

Page 29: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS Switch-disconnector selectionInterpact INS40 to 160

Interpact INS switch-disconnectors INS40 INS63 INS80 INS100 INS125 INS160Number of poles 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C 40 63 80 �00 �25 �60Conventional thermal current in enclosure Ithe at 60 °C 40 63 80 �00 �25 �60Rated insulation level (V) Ui AC 50/60 Hz 690 690 690 750 750 750Impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 500 500 500 690 690 690

DC 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 690 690 690 750 750 750Rated operational current (A) Ie Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220-240 V 40 40 63 63 80 80 �00 �00 �25 �25 �60 �60380-4�5 V 40 40 63 63 80 72 �00 �00 �25 �25 �60 �60440-480 V (1) 40 40 63 63 80 63 �00 �00 �25 �25 �60 �60500 V 40 32 63 40 80 40 �00 �00 �25 �25 �60 �60660-690 V - - - - - - �00 63 �25 80 �60 �00

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A�25 V (2P in series) 40 40 63 63 80 80 �00 �00 �25 �25 �60 �60250 V (4P in series) 40 40 63 63 80 80 �00 �00 �25 �25 �60 �60

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V �� �5 22 22 37 45230 V (NEMA) 7,5 �5 �5 22 37 45380-4�5 V 20 30 37 45 55 75440 V 22 30 37 55 55 90480 V (NEMA) 22 30 30 55 75 90500-525 V �8,5 22 22 55 75 ��0660-690 V - - - 55 75 90

Rated duties Uninterrupted duty b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) �5 �5 �5 20 20 20Max. (with upstream protection circuit breaker)

75 75 75 �54 �54 �54

Short-time withstand current (A rms) Icw � s 3000 3000 3000 5500 5500 55003 s �730 �730 �730 3�75 3�75 3�7520 s 670 670 670 �230 �230 �23030 s 550 550 550 �000 �000 �000

Suitability for isolation b b b b b bDurability (O-C cycles) Mechanical 20000 20000 20000 �5000 �5000 �5000

Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A220-240 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500380-4�5 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500440 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500500 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500690 V - - - - - - �500 �500 �500 �500 �500 �500

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A250 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500

Positive contact indication b b b b b bVisible break - - - - - -Emergency-off switch disconnector b b b b b bDegree of pollution 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - -(1) Suitable for 480 V NEMA.

27

Page 30: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS switch-disconnectors INS40 INS63 INS80 INS100 INS125 INS160Installation

Fixed, front connection b b b b b bFixed, rear connection - - - b b bOn symmetrical rails b b b - - -On a backplate b b b b b bConnection

By cables To bare cable connectors b b b b b bBy cables with lugs Directly to terminals - - - b b b

To spreaders - - - - - -To vertical-connection adapters via cable-lug adapters - - - - - -

Flat-facing bars Directly to terminals b b b b b bTo spreaders - - - - - -

Edgewise bars To vertical-connection adapters - - - - - -Indication and measurement auxiliaries

Auxiliary contacts b b b b b bVoltage-presence indicator - - - - - -Current-transformer module - - - - - -Ammeter module - - - - - -Control, locking and interlocking

Control Direct front rotary handle b b b b b bExtended front rotary handle b b b b b bDirect lateral rotary handle b b b b b bExtended lateral rotary handle b b b b b b

Locking By keylock - - - - - -By padlocks b b b b b b

Interlocking By keylock - - - - - -Mechanical b b b b b b

Complete source-changeover assembly - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 0.7 < Nm < �.3 0.7 < Nm < �.3 0.7 < Nm < �.3 �.4 < Nm < 2 �.4 < Nm < 2 �.4 < Nm < 2Installation and connection accessories

Bare cable connectors b b b b b bRear connectors - - - - - -Terminal extensions - - - - - -Spreaders - - - - - -One-piece spreader - - - - - -Terminal shrouds b b b b b bTerminal shields b b b b b bInterphase-barrier b b b b b bFront panel escutcheons - - - - - -Coupling accessories - - - - - -Tightening torque for electrical connections (Nm) 5 5 5 8 8 8Dimensions and weights

Overall dimensions H x W x D (mm) 3 poles 85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.54 poles 85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.5

Approximate weight (kg) 3 poles 0.5 0.5 0.5 0.8 0.8 0.84 poles 0.6 0.6 0.6 0.9 0.9 0.9

Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) �90 x ��5 x 55 �90 x ��5 x 55 �90 x ��5 x 55 260 x �60 x 55 260 x �60 x 55 260 x �60 x 55

Interpact INS Switch-disconnector selectionInterpact INS40 to 160

28

Page 31: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector selectionInterpact INS40 to 160

Interpact INS

Interpact INS switch-disconnectors INS40 INS63 INS80 INS100 INS125 INS160Installation

Fixed, front connection b b b b b bFixed, rear connection - - - b b bOn symmetrical rails b b b - - -On a backplate b b b b b bConnection

By cables To bare cable connectors b b b b b bBy cables with lugs Directly to terminals - - - b b b

To spreaders - - - - - -To vertical-connection adapters via cable-lug adapters - - - - - -

Flat-facing bars Directly to terminals b b b b b bTo spreaders - - - - - -

Edgewise bars To vertical-connection adapters - - - - - -Indication and measurement auxiliaries

Auxiliary contacts b b b b b bVoltage-presence indicator - - - - - -Current-transformer module - - - - - -Ammeter module - - - - - -Control, locking and interlocking

Control Direct front rotary handle b b b b b bExtended front rotary handle b b b b b bDirect lateral rotary handle b b b b b bExtended lateral rotary handle b b b b b b

Locking By keylock - - - - - -By padlocks b b b b b b

Interlocking By keylock - - - - - -Mechanical b b b b b b

Complete source-changeover assembly - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 0.7 < Nm < �.3 0.7 < Nm < �.3 0.7 < Nm < �.3 �.4 < Nm < 2 �.4 < Nm < 2 �.4 < Nm < 2Installation and connection accessories

Bare cable connectors b b b b b bRear connectors - - - - - -Terminal extensions - - - - - -Spreaders - - - - - -One-piece spreader - - - - - -Terminal shrouds b b b b b bTerminal shields b b b b b bInterphase-barrier b b b b b bFront panel escutcheons - - - - - -Coupling accessories - - - - - -Tightening torque for electrical connections (Nm) 5 5 5 8 8 8Dimensions and weights

Overall dimensions H x W x D (mm) 3 poles 85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.54 poles 85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.5 �00 x �35 x 62.5

Approximate weight (kg) 3 poles 0.5 0.5 0.5 0.8 0.8 0.84 poles 0.6 0.6 0.6 0.9 0.9 0.9

Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) �90 x ��5 x 55 �90 x ��5 x 55 �90 x ��5 x 55 260 x �60 x 55 260 x �60 x 55 260 x �60 x 55

29

Page 32: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS switch-disconnectors INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C �00 �60 200 250 320 400 500 630Conventional thermal current in enclosure Ithe at 60 °C �00 �60 200 250 320 400 500 630 (2)

Rated insulation level (V) Ui AC 50/60 Hz 750 750 750 750 750 750 750 750Impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 750 750 750 750 750 750 750 750Rated operational current (A) Ie Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220-240 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630380-4�5 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630440-480 V (1) �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630500-525 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630660-690 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23B�25 V (2P in series) �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 550 550 630250 V (4P in series) �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 550 550 630

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 22 45 55 75 90 ��0 �32 200230 V (NEMA) 22 45 55 75 90 ��0 �50 200380-4�5 V 45 75 90 �32 �60 200 250 3�5440 V 55 90 ��0 �50 �85 220 250 400480 V (NEMA) 55 90 ��0 �50 �85 220 250 375500-525 V 55 ��0 �32 �60 220 250 355 400660-690 V 55 90 �60 2�0 250 400 500 560

Rated duties Uninterrupted duty b b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 30 30 30 30 50 50 50 50Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330 330

Short-time withstand current (A rms) Icw � s 8500 8500 8500 8500 20000 20000 20000 200003 s 4900 4900 4900 4900 ��500 ��500 ��500 ��50020 s 2200 2200 2200 2200 4900 4900 4900 490030 s �800 �800 �800 �800 4000 4000 4000 4000

Suitability for isolation b b b b b b b bDurability (O-C cycles) Mechanical �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000

Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A440 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500500 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500690 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A DC23B DC23A DC23B DC23A DC23B DC23A DC23B250 V �500 �500 �500 �500 �500 �500 �500 �500 �000 - �000 - �000 - �000 200

Positive contact indication b b b b b b b bVisible break - - - - - - - -Emergency-off switch disconnector b b b b b b b bDegree of pollution 3 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - - -(1) Suitable for 480 V NEMA.(2) 550 A (DC).

Interpact INS Switch-disconnector selectionInterpact INS250-100 to 630

0566

48c-

4�

Interpact INS250 switch-disconnector.

0566

52c-

4�

Interpact INS250 emergency-off switch-disconnector.

0594

87c-

54

Interpact INS400 switch-disconnector.

0594

88c-

54

Interpact INS400 emergency-off switch-disconnector.

30

Page 33: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector selectionInterpact INS250-100 to 630

Interpact INS

Interpact INS switch-disconnectors INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C �00 �60 200 250 320 400 500 630Conventional thermal current in enclosure Ithe at 60 °C �00 �60 200 250 320 400 500 630 (2)

Rated insulation level (V) Ui AC 50/60 Hz 750 750 750 750 750 750 750 750Impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 750 750 750 750 750 750 750 750Rated operational current (A) Ie Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220-240 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630380-4�5 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630440-480 V (1) �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630500-525 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630660-690 V �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 630 630

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23B�25 V (2P in series) �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 550 550 630250 V (4P in series) �00 �00 �60 �60 200 200 250 250 320 320 400 400 500 500 550 550 630

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 22 45 55 75 90 ��0 �32 200230 V (NEMA) 22 45 55 75 90 ��0 �50 200380-4�5 V 45 75 90 �32 �60 200 250 3�5440 V 55 90 ��0 �50 �85 220 250 400480 V (NEMA) 55 90 ��0 �50 �85 220 250 375500-525 V 55 ��0 �32 �60 220 250 355 400660-690 V 55 90 �60 2�0 250 400 500 560

Rated duties Uninterrupted duty b b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 30 30 30 30 50 50 50 50Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330 330

Short-time withstand current (A rms) Icw � s 8500 8500 8500 8500 20000 20000 20000 200003 s 4900 4900 4900 4900 ��500 ��500 ��500 ��50020 s 2200 2200 2200 2200 4900 4900 4900 490030 s �800 �800 �800 �800 4000 4000 4000 4000

Suitability for isolation b b b b b b b bDurability (O-C cycles) Mechanical �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000

Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A440 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500500 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500690 V �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500 �500

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A DC23B DC23A DC23B DC23A DC23B DC23A DC23B250 V �500 �500 �500 �500 �500 �500 �500 �500 �000 - �000 - �000 - �000 200

Positive contact indication b b b b b b b bVisible break - - - - - - - -Emergency-off switch disconnector b b b b b b b bDegree of pollution 3 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - - -(1) Suitable for 480 V NEMA.(2) 550 A (DC).

3�

Page 34: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS switch-disconnectors INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630Installation

Fixed, front connection b b b b b b b bFixed, rear connection b b b b b b b bOn symmetrical rails - - - - - - - -On a backplate b b b b b b b bConnection

By cables To bare cable connectors b b b b b b b bBy cables with lugs Directly to terminals b b b b b b b b

To spreaders b b b b b b b bTo vertical-connection adapters via cable-lug adapters - - - - - - - -

Flat-facing bars Directly to terminals b b b b b b b bTo spreaders b b b b b b b b

Edgewise bars To vertical-connection adapters - - - - b b b bIndication and measurement auxiliariesAuxiliary contacts b b b b b b b bVoltage-presence indicator b b b b b b b bCurrent-transformer module b b b b b b b bAmmeter module b b b b b b b bControl, locking and interlockingControl Direct front rotary handle b b b b b b b b

Extended front rotary handle b b b b b b b bDirect lateral rotary handle b b b b - - - -Extended lateral rotary handle b b b b - - - -

Locking By keylock b b b b b b b bBy padlocks b b b b b b b b

Interlocking By keylock b b b b b b b bMechanical b b b b b b b b

Complete source-changeover assembly b b b b b b b bOperating torque (Nm) (typical value for 3-4 poles with front handle) 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5Installation and connection accessories

Bare cable connectors b b b b b b b bRear connectors b b b b b b b bTerminal extensions b b b b b b b bSpreaders b b b b b b b bOne-piece spreader b b b b - - - -Terminal shrouds - - - - - - - -Terminal shields b b b b b b b bInterphase-barrier b b b b b b b bFront panel escutcheons b b b b b b b bCoupling accessories b b b b b b b bTightening torque for electrical connections (Nm) �5 �5 �5 �5 50 50 50 50Dimensions and weights

Overall dimensions H x W x D (mm) 3 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �304 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30

Approximate weight (kg) 3 poles 2 2 2 2 4.6 4.6 4.6 4.64 poles 2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9

Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200

Interpact INS Switch-disconnector selectionInterpact INS250-100 to 630

32

Page 35: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector selectionInterpact INS250-100 to 630

Interpact INS

Interpact INS switch-disconnectors INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630Installation

Fixed, front connection b b b b b b b bFixed, rear connection b b b b b b b bOn symmetrical rails - - - - - - - -On a backplate b b b b b b b bConnection

By cables To bare cable connectors b b b b b b b bBy cables with lugs Directly to terminals b b b b b b b b

To spreaders b b b b b b b bTo vertical-connection adapters via cable-lug adapters - - - - - - - -

Flat-facing bars Directly to terminals b b b b b b b bTo spreaders b b b b b b b b

Edgewise bars To vertical-connection adapters - - - - b b b bIndication and measurement auxiliariesAuxiliary contacts b b b b b b b bVoltage-presence indicator b b b b b b b bCurrent-transformer module b b b b b b b bAmmeter module b b b b b b b bControl, locking and interlockingControl Direct front rotary handle b b b b b b b b

Extended front rotary handle b b b b b b b bDirect lateral rotary handle b b b b - - - -Extended lateral rotary handle b b b b - - - -

Locking By keylock b b b b b b b bBy padlocks b b b b b b b b

Interlocking By keylock b b b b b b b bMechanical b b b b b b b b

Complete source-changeover assembly b b b b b b b bOperating torque (Nm) (typical value for 3-4 poles with front handle) 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5Installation and connection accessories

Bare cable connectors b b b b b b b bRear connectors b b b b b b b bTerminal extensions b b b b b b b bSpreaders b b b b b b b bOne-piece spreader b b b b - - - -Terminal shrouds - - - - - - - -Terminal shields b b b b b b b bInterphase-barrier b b b b b b b bFront panel escutcheons b b b b b b b bCoupling accessories b b b b b b b bTightening torque for electrical connections (Nm) �5 �5 �5 �5 50 50 50 50Dimensions and weights

Overall dimensions H x W x D (mm) 3 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �304 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30

Approximate weight (kg) 3 poles 2 2 2 2 4.6 4.6 4.6 4.64 poles 2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9

Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200

33

Page 36: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS switch-disconnectors INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Conventional thermal current in enclosure Ithe at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Rated insulation level (V) Ui AC 50/60 Hz �000 �000 �000 �000 �000 �000 �000Impulse-withstand voltage (kV) Uimp �2 �2 �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 800 800 800 800 800 800 800Rated operational current (A) Ie Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B

AC21A AC22A220-240 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450380-4�5 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450440-480 V (1) 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250500-525 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250660-690 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B

�25 V (2P in series) 630/2 630/2 630/2 800/2 800/2 800/2 �000/2 �000/2 �000/2 �250/2 �250/2 �250/2 �600/2 �600/2 �600/2 2000/2 2000/2 - 2500/2 2500/2 -250 V (4P in series) 630/4 630/4 630/4 800/4 800/4 800/4 �000/4 �000/4 �000/4 �250/4 �250/4 �250/4 �600/4 �600/4 �600/4 2000/4 2000/4 - 2500/4 2500/4 -

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 250 250 3�5 400 400 - -380-400 V 400 400 560 7�0 7�0 - -4�5 V 500 500 630 800 800 - -500-525 V 560 560 7�0 900 900 - -660-690 V 7�0 7�0 900 - - - -

Rated duties Uninterrupted duty b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 75 75 75 75 75 �05 �05Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330

Short-time withstand current (kA rms) Icw 0.5 s 50 50 50 50 50 50 500.8 s 42 42 42 42 42 50 50� s 35 35 35 35 35 50 503 s 20 20 20 20 20 30 3020 s �0 �0 �0 �0 �0 �3 �330 s 8 8 8 8 8 �� ��

Suitability for isolation b b b b b b bDurability (O-C cycles) Mechanical 5000 3000 3000 3000 3000 3000 3000

Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23BAC21A AC22A

220-240 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

380-4�5 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

440-480 V (1) �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

500-525 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

660-690 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B�25 V (2P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -250 V (4P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -

Positive contact indication b b b b b b bVisible break - - - - - - -Emergency-off switch disconnector b b b b b - -Degree of pollution 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - -(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see catalogue LVPED2080�5EN.

Interpact INS Switch-disconnector selectionInterpact INS630b to 2500

PB

�000

�6b-

55

Interpact INS1600 switch-disconnector.

PB

�000

�8b-

55

Interpact INS1600 emergency-off switch-disconnector.

PB

�000

20b-

65

Interpact INS2500 switch-disconnector.

34

Page 37: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector selectionInterpact INS630b to 2500

Interpact INS

Interpact INS switch-disconnectors INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Conventional thermal current in enclosure Ithe at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Rated insulation level (V) Ui AC 50/60 Hz �000 �000 �000 �000 �000 �000 �000Impulse-withstand voltage (kV) Uimp �2 �2 �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 800 800 800 800 800 800 800Rated operational current (A) Ie Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B

AC21A AC22A220-240 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450380-4�5 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450440-480 V (1) 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250500-525 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250660-690 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B

�25 V (2P in series) 630/2 630/2 630/2 800/2 800/2 800/2 �000/2 �000/2 �000/2 �250/2 �250/2 �250/2 �600/2 �600/2 �600/2 2000/2 2000/2 - 2500/2 2500/2 -250 V (4P in series) 630/4 630/4 630/4 800/4 800/4 800/4 �000/4 �000/4 �000/4 �250/4 �250/4 �250/4 �600/4 �600/4 �600/4 2000/4 2000/4 - 2500/4 2500/4 -

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 250 250 3�5 400 400 - -380-400 V 400 400 560 7�0 7�0 - -4�5 V 500 500 630 800 800 - -500-525 V 560 560 7�0 900 900 - -660-690 V 7�0 7�0 900 - - - -

Rated duties Uninterrupted duty b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 75 75 75 75 75 �05 �05Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330

Short-time withstand current (kA rms) Icw 0.5 s 50 50 50 50 50 50 500.8 s 42 42 42 42 42 50 50� s 35 35 35 35 35 50 503 s 20 20 20 20 20 30 3020 s �0 �0 �0 �0 �0 �3 �330 s 8 8 8 8 8 �� ��

Suitability for isolation b b b b b b bDurability (O-C cycles) Mechanical 5000 3000 3000 3000 3000 3000 3000

Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23BAC21A AC22A

220-240 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

380-4�5 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

440-480 V (1) �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

500-525 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

660-690 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B�25 V (2P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -250 V (4P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -

Positive contact indication b b b b b b bVisible break - - - - - - -Emergency-off switch disconnector b b b b b - -Degree of pollution 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - -(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see catalogue LVPED2080�5EN.

35

Page 38: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS switch-disconnectors INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500Installation

Fixed, front connection b b b b b b bFixed, rear connection b b b b b b bOn symmetrical rails - - - - - - -On a backplate b b b b b b bConnection

By cables To bare cable connectors - - - - - - -By cables with lugs Directly to terminals - - - - - b b

To spreaders - - - - - - -To vertical-connection adapters via cable-lug adapters b b b b b - -

Flat-facing bars Directly to terminals b b b b b b bTo spreaders b b b b b - -

Edgewise bars To vertical-connection adapters b b b b b - -Indication and measurement auxiliaries

Auxiliary contacts b b b b b b bVoltage-presence indicator - - - - - - -Current-transformer module - - - - - - -Ammeter module - - - - - - -Control, locking and interlocking

Control Direct front rotary handle b b b b b b bExtended front rotary handle b b b b b b bDirect lateral rotary handle - - - - - - -Extended lateral rotary handle - - - - - - -

Locking By keylock b b b b b b bBy padlocks b b b b b b b

Interlocking By keylock b b b b b b bMechanical - - - - - - -

Complete source-changeover assembly - - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 30 30 30 30 30 60 60Installation and connection accessories

Bare cable connectors - - - - - - -Rear connectors - - - - - - -Terminal extensions b b b b b b bSpreaders b b b b b b bOne-piece spreader - - - - - - -Terminal shrouds - - - - - - -Terminal shields b b b b b b bInterphase-barrier b b b b b b bFront panel escutcheons b b b b b b bCoupling accessories - - - - - - -Tightening torque for electrical connections (Nm)

50 50 50 50 50 50 50

Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5

4 poles 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5Approximate weight (kg) 3 poles �4 �4 �4 �4 �4 35 35

4 poles �8 �8 �8 �8 �8 45 45Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) - - - - - - -

Interpact INS Switch-disconnector selectionInterpact INS630b to 2500

36

Page 39: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INS Switch-disconnector selectionInterpact INS630b to 2500

Interpact INS switch-disconnectors INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500Installation

Fixed, front connection b b b b b b bFixed, rear connection b b b b b b bOn symmetrical rails - - - - - - -On a backplate b b b b b b bConnection

By cables To bare cable connectors - - - - - - -By cables with lugs Directly to terminals - - - - - b b

To spreaders - - - - - - -To vertical-connection adapters via cable-lug adapters b b b b b - -

Flat-facing bars Directly to terminals b b b b b b bTo spreaders b b b b b - -

Edgewise bars To vertical-connection adapters b b b b b - -Indication and measurement auxiliaries

Auxiliary contacts b b b b b b bVoltage-presence indicator - - - - - - -Current-transformer module - - - - - - -Ammeter module - - - - - - -Control, locking and interlocking

Control Direct front rotary handle b b b b b b bExtended front rotary handle b b b b b b bDirect lateral rotary handle - - - - - - -Extended lateral rotary handle - - - - - - -

Locking By keylock b b b b b b bBy padlocks b b b b b b b

Interlocking By keylock b b b b b b bMechanical - - - - - - -

Complete source-changeover assembly - - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 30 30 30 30 30 60 60Installation and connection accessories

Bare cable connectors - - - - - - -Rear connectors - - - - - - -Terminal extensions b b b b b b bSpreaders b b b b b b bOne-piece spreader - - - - - - -Terminal shrouds - - - - - - -Terminal shields b b b b b b bInterphase-barrier b b b b b b bFront panel escutcheons b b b b b b bCoupling accessories - - - - - - -Tightening torque for electrical connections (Nm)

50 50 50 50 50 50 50

Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5

4 poles 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5Approximate weight (kg) 3 poles �4 �4 �4 �4 �4 35 35

4 poles �8 �8 �8 �8 �8 45 45Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) - - - - - - -

37

Page 40: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV switch-disconnectors INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C �00 �60 200 250 320 400 500 630Conventional thermal current in enclosure Ithe at 60 °C �00 �60 200 250 320 400 500 630 (2)

Rated insulation level (V) Ui AC 50/60 Hz 750 750 750 750 750 750 750 750Impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 750 750 750 750 750 750 750 750Rated operational current (A) Ie Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/

AC23B220-240 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630380-4�5 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630440-480 V (1) �00 �00 �00 �60 �60 �60 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630500-525 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 630 500/630660-690 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 550 500/630

Electrical DC DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/DC23B

�25 V (2P in series) �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630250 V (4P in series) �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 22 45 55 75 90 ��0 �32 200230 V (NEMA) 22 45 55 75 90 ��0 �50 200380-4�5 V 45 75 90 �32 �60 200 250 3�5440 V 55 90 ��0 �50 �85 220 250 400480 V (NEMA) 55 50 ��0 �50 �85 220 250 375500-525 V 55 ��0 �32 �32 220 250 355 400660-690 V 55 90 �60 �60 250 400 500 560

Rated duties Uninterrupted duty b b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 30 30 30 30 50 50 50 50Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330 330

Short-time withstand current (A rms) Icw � s 8500 8500 8500 8500 20000 20000 20000 200003 s 4900 4900 4900 4900 ��500 ��500 ��500 ��50020 s 2200 2200 2200 2200 4900 4900 4900 490030 s �800 �800 �800 �800 4000 4000 4000 4000

Suitability for isolation b b b b b b b bDurability (O-C cycles) Mechanical �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000

Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/AC23B

440 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000500 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/200690 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/200

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/DC23B

250 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/200Positive contact indication b b b b b b b bVisible break b b b b b b b bEmergency-off switch disconnector b b b b b b b bDegree of pollution 3 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - - -(1) Suitable for 480 V NEMA.(2) 550 A (DC).

Interpact INV Switch-disconnector selectionInterpact INV100 to 630

0566

50b-

4�

Interpact INV250 switch-disconnector.

0566

54b-

4�

Interpact INV250 emergency-off switch-disconnector.

0594

9�b-

54

Interpact INV400 Std.

0594

93b-

52

Interpact INV400 emergency-off switch-disconnector.

38

Page 41: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector selectionInterpact INV100 to 630

Interpact INV

Interpact INV switch-disconnectors INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C �00 �60 200 250 320 400 500 630Conventional thermal current in enclosure Ithe at 60 °C �00 �60 200 250 320 400 500 630 (2)

Rated insulation level (V) Ui AC 50/60 Hz 750 750 750 750 750 750 750 750Impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 750 750 750 750 750 750 750 750Rated operational current (A) Ie Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/

AC23B220-240 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630380-4�5 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630440-480 V (1) �00 �00 �00 �60 �60 �60 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630500-525 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 630 500/630660-690 V �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 550 500/630

Electrical DC DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/DC23B

�25 V (2P in series) �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630250 V (4P in series) �00 �00 �00 �60 �60 �60 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 22 45 55 75 90 ��0 �32 200230 V (NEMA) 22 45 55 75 90 ��0 �50 200380-4�5 V 45 75 90 �32 �60 200 250 3�5440 V 55 90 ��0 �50 �85 220 250 400480 V (NEMA) 55 50 ��0 �50 �85 220 250 375500-525 V 55 ��0 �32 �32 220 250 355 400660-690 V 55 90 �60 �60 250 400 500 560

Rated duties Uninterrupted duty b b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 30 30 30 30 50 50 50 50Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330 330

Short-time withstand current (A rms) Icw � s 8500 8500 8500 8500 20000 20000 20000 200003 s 4900 4900 4900 4900 ��500 ��500 ��500 ��50020 s 2200 2200 2200 2200 4900 4900 4900 490030 s �800 �800 �800 �800 4000 4000 4000 4000

Suitability for isolation b b b b b b b bDurability (O-C cycles) Mechanical �5000 �5000 �5000 �5000 �0000 �0000 �0000 �0000

Electrical AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/AC23B

440 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000500 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/200690 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/200

Electrical DC DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/DC23B

250 V �500 �500 �500 �500 �500 �500 �500 �500 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000 �000/200Positive contact indication b b b b b b b bVisible break b b b b b b b bEmergency-off switch disconnector b b b b b b b bDegree of pollution 3 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - - -(1) Suitable for 480 V NEMA.(2) 550 A (DC).

39

Page 42: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV switch-disconnectors INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630Installation

Fixed, front connection b b b b b b b bFixed, rear connection b b b b b b b bOn symmetrical rails - - - - - - - -On a backplate b b b b b b b bConnection

By cables To bare cable connectors b b b b b b b bBy cables with lugs Directly to terminals b b b b b b b b

To spreaders b b b b b b b bTo vertical-connection adapters via cable-lug adapters - - - - - - - -

Flat-facing bars Directly to terminals b b b b b b b bTo spreaders b b b b b b b b

Edgewise bars To vertical-connection adapters - - - - b b b bIndication and measurement auxiliaries

Auxiliary contacts b b b b b b b bVoltage-presence indicator b b b b b b b bCurrent-transformer module b b b b b b b bAmmeter module b b b b b b b bControl, locking and interlocking

Control Direct front rotary handle b b b b b b b bExtended front rotary handle b b b b b b b bDirect lateral rotary handle b b b b - - - -Extended lateral rotary handle b b b b - - - -

Locking By keylock b b b b b b b bBy padlocks b b b b b b b b

Interlocking By keylock b b b b b b b bMechanical b b b b b b b b

Complete source-changeover assembly - - - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5Installation and connection accessories

Bare cable connectors b b b b b b b bRear connectors b b b b b b b bTerminal extensions b b b b b b b bSpreaders b b b b b b b bOne-piece spreader b b b b b b b bTerminal shrouds - - - - - - - -Terminal shields b b b b b b b bInterphase-barrier b b b b b b b bFront panel escutcheons b b b b b b b bCoupling accessories b b b b b b b bTightening torque for electrical connections (Nm) �5 �5 �5 �5 50 50 50 50Dimensions and weights

Overall dimensions H x W x D (mm) 3 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �304 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30

Approximate weight (kg) 3 poles 2 2 2 2 4.6 4.6 4.6 4.64 poles 2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9

Enclosure dimensions for Ithe

db�0

54�3 H x W x D (mm) 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200

Interpact INV Switch-disconnector selectionInterpact INV100 to 630

40

Page 43: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV Switch-disconnector selection Interpact INV100 to 630

Interpact INV switch-disconnectors INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630Installation

Fixed, front connection b b b b b b b bFixed, rear connection b b b b b b b bOn symmetrical rails - - - - - - - -On a backplate b b b b b b b bConnection

By cables To bare cable connectors b b b b b b b bBy cables with lugs Directly to terminals b b b b b b b b

To spreaders b b b b b b b bTo vertical-connection adapters via cable-lug adapters - - - - - - - -

Flat-facing bars Directly to terminals b b b b b b b bTo spreaders b b b b b b b b

Edgewise bars To vertical-connection adapters - - - - b b b bIndication and measurement auxiliaries

Auxiliary contacts b b b b b b b bVoltage-presence indicator b b b b b b b bCurrent-transformer module b b b b b b b bAmmeter module b b b b b b b bControl, locking and interlocking

Control Direct front rotary handle b b b b b b b bExtended front rotary handle b b b b b b b bDirect lateral rotary handle b b b b - - - -Extended lateral rotary handle b b b b - - - -

Locking By keylock b b b b b b b bBy padlocks b b b b b b b b

Interlocking By keylock b b b b b b b bMechanical b b b b b b b b

Complete source-changeover assembly - - - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5 �3.5 < Nm < �6.5Installation and connection accessories

Bare cable connectors b b b b b b b bRear connectors b b b b b b b bTerminal extensions b b b b b b b bSpreaders b b b b b b b bOne-piece spreader b b b b b b b bTerminal shrouds - - - - - - - -Terminal shields b b b b b b b bInterphase-barrier b b b b b b b bFront panel escutcheons b b b b b b b bCoupling accessories b b b b b b b bTightening torque for electrical connections (Nm) �5 �5 �5 �5 50 50 50 50Dimensions and weights

Overall dimensions H x W x D (mm) 3 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �304 poles �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 �36 x �40 x 96 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30 205 x �85 x �30

Approximate weight (kg) 3 poles 2 2 2 2 4.6 4.6 4.6 4.64 poles 2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9

Enclosure dimensions for Ithe

db�0

54�3 H x W x D (mm) 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200

4�

Page 44: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV switch-disconnectors INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Conventional thermal current in enclosure Ithe at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Rated insulation level (V) Ui AC 50/60 Hz �000 �000 �000 �000 �000 �000 �000Impulse-withstand voltage (kV) Uimp �2 �2 �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 800 800 800 800 800 800 800Rated operational current (A) Ie Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B

AC21A AC22A220-240 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450380-4�5 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450440-480 V (1) 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250500-525 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250660-690 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B

�25 V (2P in series) 630/2 630/2 630/2 800/2 800/2 800/2 �000/2 �000/2 �000/2 �250/2 �250/2 �250/2 �600/2 �600/2 �600/2 2000/2 2000/2 - 2500/2 2500/2 -250 V (4P in series) 630/4 630/4 630/4 800/4 800/4 800/4 �000/4 �000/4 �000/4 �250/4 �250/4 �250/4 �600/4 �600/4 �600/4 2000/4 2000/4 - 2500/4 2500/4 -

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 250 250 3�5 400 400 - -380-400 V 400 400 560 7�0 7�0 - -4�5 V 500 500 630 800 800 - -500-525 V 560 560 7�0 900 900 - -660-690 V 7�0 7�0 900 - - - -

Rated duties Uninterrupted duty b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 75 75 75 75 75 �05 �05Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330

Short-time withstand current (kA rms) Icw 0.5 s 50 50 50 50 50 50 500.8 s 42 42 42 42 42 50 50� s 35 35 35 35 35 50 503 s 20 20 20 20 20 30 3020 s �0 �0 �0 �0 �0 �3 �330 s 8 8 8 8 8 �� ��

Suitability for isolation b b b b b b bDurability (O-C cycles) Mechanical 5000 3000 3000 3000 3000 3000 3000

Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23BAC21A AC22A

220-240 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

380-4�5 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

440-480 V (1) �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

500-525 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

660-690 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B�25 V (2P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -250 V (4P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -

Positive contact indication b b b b b b bVisible break b b b b b b bEmergency-off switch disconnector b b b b b - -Degree of pollution 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - -(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see catalogue LVPED208015EN.

Switch-disconnector selectionInterpact INV630b to 2500

Interpact INV P

B�0

00�7

b-55

Interpact INV1600 switch-disconnector.

PB

�000

�9b-

55

Interpact INV1600 emergency-off switch-disconnector.

PB

�000

2�b-

65

Interpact INV2500 switch-disconnector.

42

Page 45: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV Switch-disconnector selectionInterpact INV630b to 2500

Interpact INV switch-disconnectors INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3

Conventional thermal current (A) Ith at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Conventional thermal current in enclosure Ithe at 60 °C 630 800 �000 �250 �600 (2) 2000 2500Rated insulation level (V) Ui AC 50/60 Hz �000 �000 �000 �000 �000 �000 �000Impulse-withstand voltage (kV) Uimp �2 �2 �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690 690

DC 250 250 250 250 250 250 250Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz 800 800 800 800 800 800 800Rated operational current (A) Ie Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B

AC21A AC22A220-240 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450380-4�5 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�450 �450440-480 V (1) 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250500-525 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250660-690 V 630 630 630 800 800 800 �000 �000 �000 �250 �250 �250 �600 �600 �250 2000 2000 - 2500 2500 -

�250 �250Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B

�25 V (2P in series) 630/2 630/2 630/2 800/2 800/2 800/2 �000/2 �000/2 �000/2 �250/2 �250/2 �250/2 �600/2 �600/2 �600/2 2000/2 2000/2 - 2500/2 2500/2 -250 V (4P in series) 630/4 630/4 630/4 800/4 800/4 800/4 �000/4 �000/4 �000/4 �250/4 �250/4 �250/4 �600/4 �600/4 �600/4 2000/4 2000/4 - 2500/4 2500/4 -

Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V 250 250 3�5 400 400 - -380-400 V 400 400 560 7�0 7�0 - -4�5 V 500 500 630 800 800 - -500-525 V 560 560 7�0 900 900 - -660-690 V 7�0 7�0 900 - - - -

Rated duties Uninterrupted duty b b b b b b bIntermittent duty Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 % Class �20 - 60 %

Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone) 75 75 75 75 75 �05 �05Max. (with upstream protection circuit breaker)

330 330 330 330 330 330 330

Short-time withstand current (kA rms) Icw 0.5 s 50 50 50 50 50 50 500.8 s 42 42 42 42 42 50 50� s 35 35 35 35 35 50 503 s 20 20 20 20 20 30 3020 s �0 �0 �0 �0 �0 �3 �330 s 8 8 8 8 8 �� ��

Suitability for isolation b b b b b b bDurability (O-C cycles) Mechanical 5000 3000 3000 3000 3000 3000 3000

Electrical AC 50/60 Hz AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23BAC21A AC22A

220-240 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

380-4�5 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

440-480 V (1) �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

500-525 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

660-690 V �000 �000 �000 500 500 500 500 500 500 500 500 500 �00 �00 500 �00 �00 - �00 �00 -500 500

Electrical DC DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B�25 V (2P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -250 V (4P) �000 �000 �000 500 500 500 500 500 500 500 500 500 500 500 500 �00 �00 - �00 �00 -

Positive contact indication b b b b b b bVisible break b b b b b b bEmergency-off switch disconnector b b b b b - -Degree of pollution 3 3 3 3 3 3 3Upstream protection

See catalogue LVPED2080�5EN. - - - - - - -(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only. For horizontal connection busbars, see catalogue LVPED208015EN.

43

Page 46: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV switch-disconnectors INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500Installation

Fixed, front connection b b b b b b bFixed, rear connection b b b b b b bOn symmetrical rails - - - - - - -On a backplate b b b b b b bConnection

By cables To bare cable connectors - - - - - - -By cables with lugs Directly to terminals - - - - - b b

To spreaders - - - - - - -To vertical-connection adapters via cable-lug adapters b b b b b - -

Flat-facing bars Directly to terminals b b b b b b bTo spreaders b b b b b - -

Edgewise bars To vertical-connection adapters b b b b b - -Indication and measurement auxiliaries

Auxiliary contacts b b b b b b bVoltage-presence indicator - - - - - - -Current-transformer module - - - - - - -Ammeter module - - - - - - -Control, locking and interlocking

Control Direct front rotary handle b b b b b b bExtended front rotary handle b b b b b b bDirect lateral rotary handle - - - - - - -Extended lateral rotary handle - - - - - - -

Locking By keylock b b b b b b bBy padlocks b b b b b b b

Interlocking By keylock b b b b b b bMechanical - - - - - - -

Complete source-changeover assembly - - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 30 30 30 30 30 60 60Installation and connection accessories

Bare cable connectors - - - - - - -Rear connectors - - - - - - -Terminal extensions b b b b b b bSpreaders b b b b b b bOne-piece spreader - - - - - - -Terminal shrouds - - - - - - -Terminal shields b b b b b b bInterphase-barrier b b b b b b bFront panel escutcheons b b b b b b bCoupling accessories - - - - - - -Tightening torque for electrical connections (Nm)

50 50 50 50 50 50 50

Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5

4 poles 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5Approximate weight (kg) 3 poles �4 �4 �4 �4 �4 35 35

4 poles �8 �8 �8 �8 �8 45 45Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) - - - - - - -

Interpact INV Switch-disconnector selectionInterpact INV630b to 2500

44

Page 47: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Interpact INV Switch-disconnector selectionInterpact INV630b to 2500

Interpact INV switch-disconnectors INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500Installation

Fixed, front connection b b b b b b bFixed, rear connection b b b b b b bOn symmetrical rails - - - - - - -On a backplate b b b b b b bConnection

By cables To bare cable connectors - - - - - - -By cables with lugs Directly to terminals - - - - - b b

To spreaders - - - - - - -To vertical-connection adapters via cable-lug adapters b b b b b - -

Flat-facing bars Directly to terminals b b b b b b bTo spreaders b b b b b - -

Edgewise bars To vertical-connection adapters b b b b b - -Indication and measurement auxiliaries

Auxiliary contacts b b b b b b bVoltage-presence indicator - - - - - - -Current-transformer module - - - - - - -Ammeter module - - - - - - -Control, locking and interlocking

Control Direct front rotary handle b b b b b b bExtended front rotary handle b b b b b b bDirect lateral rotary handle - - - - - - -Extended lateral rotary handle - - - - - - -

Locking By keylock b b b b b b bBy padlocks b b b b b b b

Interlocking By keylock b b b b b b bMechanical - - - - - - -

Complete source-changeover assembly - - - - - - -Operating torque (Nm) (typical value for 3-4 poles with front handle) 30 30 30 30 30 60 60Installation and connection accessories

Bare cable connectors - - - - - - -Rear connectors - - - - - - -Terminal extensions b b b b b b bSpreaders b b b b b b bOne-piece spreader - - - - - - -Terminal shrouds - - - - - - -Terminal shields b b b b b b bInterphase-barrier b b b b b b bFront panel escutcheons b b b b b b bCoupling accessories - - - - - - -Tightening torque for electrical connections (Nm)

50 50 50 50 50 50 50

Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 300 x 340 x �46.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5

4 poles 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 300 x 4�0 x �46.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5Approximate weight (kg) 3 poles �4 �4 �4 �4 �4 35 35

4 poles �8 �8 �8 �8 �8 45 45Enclosure dimensions for Ithe

DB

�054

�3 H x W x D (mm) - - - - - - -

45

Page 48: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Source changeover systems Overview of solutionsManual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 100 A to 630 A

Range Interpact CompactModels INS40 to INS80

INS�00 to INS�60INS250 to INS630INV250 to INV630

NS/NSX�00 to NS/NSX250NS/NSX400 to NS/NSX630

Rating (A) 40 to �60 �00 to 630 �00 to 630Type of device Switch-disconnectors with

extended handlesSwitch-disconnectors N/H/L circuit breakers

NA switch-disconnectors

Manual source-changeover systemsInterlocking via toggles

DB

�0�7

68

DB

�0�5

45

2 devices side-by-side 3 devices side-by-side

Interlocking via rotary handles

DB

�0�7

69

DB

�0�5

46

DB

�0�5

47

DB

�0�5

48

2 devices side-by-side

Interlocking via keylocks with captive keys

DB

�0�7

70

DB

�0�5

49

DB

�0�5

50

A number of different devices

Interlocking on a base plate

DB

�0�7

7�

DB

�0�5

5�

2 devices side-by-side

Complete source-changeover assemblies

DB

�0�7

72

DB

�0�5

52

2 devices side-by-side

N

2.4

N

2.4

ONI

OOFF

ONI

OOFF

ONI

OOFF

ONI

OOFF

46

Page 49: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Source changeover systems Overview of solutionsManual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A

Range Compact MasterpactModels NS630b to NS�600 NT06 to NT�6 NW08 to NW63Rating (A) 630 to �600 630 to �600 800 to 6300 Type of device N/H/L circuit breakers

NA switch-disconnectorsH�/L� circuit breakersHA switch-disconnectors

N�/H�/H2/H3/L� circuit breakersNA/HA/HF switch-disconnectors

Manual source-changeover systemsInterlocking via extended rotary handles

DB

�0�7

69

DB

�0�5

53

2 devices side-by-side

Interlocking via keylocks with captive keys

DB

�0�7

70

DB

�0�5

54

DB

�0�5

55

DB

�0�5

56

A number of different devices

Mechanical interlocking using connecting rods

DB

�0�7

73

DB

�0�5

57

DB

�0�5

58

DB

�0�5

59

2 devices one above the other

(1)

Mechanical interlocking using cables

DB

�0�7

74

DB

�0�5

60

DB

�0�5

6�

DB

�0�5

62

2 or 3 devices one above the other

DB

�0�7

75

(1)

(2)2 or 3 devices side-by-sideFor this case and other cases, please consult us

DB

�0�9

�6

(1) Implemented with NS630b to NS1600 electrically-operated devices only.(2) For source-changeover systems using cables, always respect the installation conditions specified on catalogue LVPED208007EN.

Opush OFF

Ipush ON

O OFF

discharged

Opush OFF

Ipush ON

O OFF

discharged

Opush OFF

Ipush ON

O OFF

discharged

Opush OFF

Ipush ON

O OFF

discharged

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

47

Page 50: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Source changeover systems Overview of solutionsRemote-operated source-changeover systems Compact NSX100 A to 630 A, Compact NS100 A to 1600 A

Range CompactModels NS/NSX�00 to NS630 NS630b to NS�600Rating (A) �00 to 630 630 to �600Type of device N/H/L circuit breakers

NA switch-disconnectorsN/H/L circuit breakersNA switch-disconnectors

Remote-operated source-changeover systemMechanical interlocking on base plate + electrical interlocking

DB

�0�7

7�

DB

�0�5

63

2 electrically-operated devices side-by-side combined with an electrical interlocking system

Mechanical interlocking using connecting rods + electrical interlocking

DB

�0�7

73

DB

�0�5

57

2 electrically-operated devices one above the other combined with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking

DB

�0�7

77

DB

�0�5

60

2 electrically-operated devices one above the other combined with an electrical interlocking system

DB

�0�7

76

2 electrically-operated devices side-by-side combined with an electrical interlocking system

(2)

Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

DB

�0�7

77 The automatic controller operates the devices depending on external parameters.

BA: Simple controller that manages the changeover function.

UA: Controller that also manages engine generator sets.

UA150: UA controller with a communication option.

DB

�259

72

BA controller

DB

�0�7

76

DB

�259

63

UA and UA150 controller

(2) For source-changeover systems using cables, always respect the installation conditions specified on catalogue LVPED208007EN.

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

48

Page 51: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Source changeover systems Overview of solutionsRemote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A

Range MasterpactModels NT06 to NT�6 NW08 to NW63Rating (A) 630 to �600 800 to 6300 Type of device H�/L� circuit breakers

HA switch-disconnectorsN�/H�/H2/H3/L� circuit breakersNA/HA/HF switch-disconnectors

Remote-operated source-changeover systemMechanical interlocking using connecting rods + electrical interlocking

DB

�0�7

73

DB

�0�5

58

DB

�0�5

59

2 electrically-operated devices side-by-side combined with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking

DB

�0�7

74

DB

�0�5

6�

DB

�0�5

62

2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1)

DB

�0�7

75

2 or 3 electrically-operated devices side-by-side combined with an electrical interlocking system (1)

(2)

Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

DB

�0�7

77 The automatic controller operates the devices depending on external parameters.

BA: Simple controller that manages the changeover function.

UA: Controller that also manages engine generator sets.

UA150: UA controller with a communication option.

DB

�259

72

BA controller

DB

�0�7

76

DB

�259

63

UA and UA150 controller

(1) Three devices with Masterpact NW only.(2) For source-changeover systems using cables, always respect the installation conditions specified on catalogue LVPED208007EN. For other cases, please consult us.

49

Page 52: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fupact Switch-disconnector fuses selection Fupact INFp32 to INFp160

0590

00 Switch-disconnector fuses INFp32 INFD40 INFp63 INFB100 INFC125 INFp160Number of poles / type of fuse-link 3 poles / 3 fuse-links NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS

4 poles / 3 fuse-links + switched neutral NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS4 poles / 4 fuse-links NFC - NFC-DIN - NFC DIN

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C 32 40 63 �00 �25 �60

Maximum fuse power dissipation (W) 3.5 4.5 7.5 �2 �2 �2In enclosure Ithe at 40 °C 32 40 63 �00 �25 �60 �35Maximum fuse power dissipation (W) 3.5 4.5 7.5 �2 �2 �0 �2

Rated insulation voltage (V) Ui AC 50/60 Hz / DC �000 �000 �000 �000 �000 �000

0565

02 Rated impulse withstand voltage (kV) Uimp �2 �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690

DC 250 250 250 500 500 500Rated operational voltage AC20 and DC20 (V) Ue 690 690 690 690 690 690Rated operational current (A) Ie AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220/240 V 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60380/4�5 V 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60440/480 V (1) 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60500/525 V 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60660/690 V 32 32 40 40 63 63 (2) �00 �00 (2) �25 �25 (2) �60 �60 (2)

DC/poles in series DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A�25 V/nbr of poles 32/2 32/2 40/2 40/2 63/3 63/3 �00/2 �00/2 �25/2 �25/2 �60/2 �60/2250 V/nbr of poles 32/4 32/4 40/4 40/4 63/3 63/3 �00/2 �00/2 �25/2 �25/2 �60/2 �60/2500 V/nbr of poles - - - - - - �00/4 �00/4 �00/4 �00/4 �00/4 �00/4

0565

03 750 V/nbr of poles - - - - - - - - - - - -Rated operational power (kW) (3)

(motor power given for direct on-line starting)AC 220/240 V 8 �� �8.5 30 37 45

380/400 V �4 �8.5 30 45 60 804�5 V �5 �8.5 30 55 60 90500/525 V �8 22 37 60 80 ��0660/690 V 25 30 60 90 ��0 �32

Rated duties Uninterrupted duty b b b b b b

Intermittent duty class �20-60 % class �20-60 % class �20-60 % class �20-60 % class �20-60 % class �20-60 %Rated short-circuit making capacity (kA peak)Switch-disconnector without fuse (refer to single-phase fuse limitation curves)

Icm 4�5 V 9 9 �7 22 22 22500 V 7.5 7.5 �7 22 22 22690 V 6 6 �3 �5 �5 �5

Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak) (4)

Icn / Icm 4�5 V (BS) 80/�76 80/�76 80/�76 80/�76 80/�76 80/�76500 V (DIN) �00/220 �00/220 �00/220 �00/220 �00/220 �00/220690 V (DIN) 50/�05 50/�05 50/�05 50/�05 50/�05 50/�05

Rated short-time withstand current (A rms) Icw � s �000 �000 2500 5000 5000 50003 s 570 570 �440 2900 2900 290020 s 220 220 560 ��50 ��50 ��5030 s �80 �80 460 950 950 950

Endurance (category A) (CO cycles) Mechanical �0000 �0000 �0000 �0000 �0000 �0000Electrical AC AC22A 500 V �500 �500 �500 �500 �500 �500

AC22A 690 V �500 �500 �500 �500 �500 �500AC23A 500 V �500 �500 �500 �500 �500 �500AC23A 690 V �500 �500 �500 �500 �500 �500

Suitability for isolation b b b b b b

Positive contact indication b b b b b b

Pollution degree 3 3 3 3 3 3Control

Direct front rotary handle b b b b b b

Extended front rotary handle b b b b b b

Extended lateral rotary handle b b b b b b

Locking by padlocks b b b b b b

Operating torque (typical for 3-pole switch-disconnector fuses) (Nm) 3 3 4 8 8 8Indication auxiliaries

Auxiliary contacts b b b b b b

Blown-fuse indicator b (5) - b (5) - b -Fuse monitor b b b b b b

Auxiliary contact test position b (standard) b (standard) b (standard) b (standard) b (standard) b (standard)(1) Suitable for 480 V NEMA.(2) AC23B.(3) Some fuse-links limit these values. Motor starting current must be considered separately.(4) Switch-disconnector combined with fuses.(5) Only for NFC fuse-links.

INFB32.

INFC63.

INFD160.

50

Page 53: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fupact Switch-disconnector fuses selection Fupact INFp32 to INFp160

0590

00 Switch-disconnector fuses INFp32 INFD40 INFp63 INFB100 INFC125 INFp160Number of poles / type of fuse-link 3 poles / 3 fuse-links NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS

4 poles / 3 fuse-links + switched neutral NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS4 poles / 4 fuse-links NFC - NFC-DIN - NFC DIN

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C 32 40 63 �00 �25 �60

Maximum fuse power dissipation (W) 3.5 4.5 7.5 �2 �2 �2In enclosure Ithe at 40 °C 32 40 63 �00 �25 �60 �35Maximum fuse power dissipation (W) 3.5 4.5 7.5 �2 �2 �0 �2

Rated insulation voltage (V) Ui AC 50/60 Hz / DC �000 �000 �000 �000 �000 �000

0565

02 Rated impulse withstand voltage (kV) Uimp �2 �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690

DC 250 250 250 500 500 500Rated operational voltage AC20 and DC20 (V) Ue 690 690 690 690 690 690Rated operational current (A) Ie AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220/240 V 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60380/4�5 V 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60440/480 V (1) 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60500/525 V 32 32 40 40 63 63 �00 �00 �25 �25 �60 �60660/690 V 32 32 40 40 63 63 (2) �00 �00 (2) �25 �25 (2) �60 �60 (2)

DC/poles in series DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A�25 V/nbr of poles 32/2 32/2 40/2 40/2 63/3 63/3 �00/2 �00/2 �25/2 �25/2 �60/2 �60/2250 V/nbr of poles 32/4 32/4 40/4 40/4 63/3 63/3 �00/2 �00/2 �25/2 �25/2 �60/2 �60/2500 V/nbr of poles - - - - - - �00/4 �00/4 �00/4 �00/4 �00/4 �00/4

0565

03 750 V/nbr of poles - - - - - - - - - - - -Rated operational power (kW) (3)

(motor power given for direct on-line starting)AC 220/240 V 8 �� �8.5 30 37 45

380/400 V �4 �8.5 30 45 60 804�5 V �5 �8.5 30 55 60 90500/525 V �8 22 37 60 80 ��0660/690 V 25 30 60 90 ��0 �32

Rated duties Uninterrupted duty b b b b b b

Intermittent duty class �20-60 % class �20-60 % class �20-60 % class �20-60 % class �20-60 % class �20-60 %Rated short-circuit making capacity (kA peak)Switch-disconnector without fuse (refer to single-phase fuse limitation curves)

Icm 4�5 V 9 9 �7 22 22 22500 V 7.5 7.5 �7 22 22 22690 V 6 6 �3 �5 �5 �5

Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak) (4)

Icn / Icm 4�5 V (BS) 80/�76 80/�76 80/�76 80/�76 80/�76 80/�76500 V (DIN) �00/220 �00/220 �00/220 �00/220 �00/220 �00/220690 V (DIN) 50/�05 50/�05 50/�05 50/�05 50/�05 50/�05

Rated short-time withstand current (A rms) Icw � s �000 �000 2500 5000 5000 50003 s 570 570 �440 2900 2900 290020 s 220 220 560 ��50 ��50 ��5030 s �80 �80 460 950 950 950

Endurance (category A) (CO cycles) Mechanical �0000 �0000 �0000 �0000 �0000 �0000Electrical AC AC22A 500 V �500 �500 �500 �500 �500 �500

AC22A 690 V �500 �500 �500 �500 �500 �500AC23A 500 V �500 �500 �500 �500 �500 �500AC23A 690 V �500 �500 �500 �500 �500 �500

Suitability for isolation b b b b b b

Positive contact indication b b b b b b

Pollution degree 3 3 3 3 3 3Control

Direct front rotary handle b b b b b b

Extended front rotary handle b b b b b b

Extended lateral rotary handle b b b b b b

Locking by padlocks b b b b b b

Operating torque (typical for 3-pole switch-disconnector fuses) (Nm) 3 3 4 8 8 8Indication auxiliaries

Auxiliary contacts b b b b b b

Blown-fuse indicator b (5) - b (5) - b -Fuse monitor b b b b b b

Auxiliary contact test position b (standard) b (standard) b (standard) b (standard) b (standard) b (standard)(1) Suitable for 480 V NEMA.(2) AC23B.(3) Some fuse-links limit these values. Motor starting current must be considered separately.(4) Switch-disconnector combined with fuses.(5) Only for NFC fuse-links.

5�

Page 54: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector fuses selection0 Fupact INFp32 to INFp160

Fupact05

9000 Switch-disconnector fuses INFp32 INFD40 INFp63 INFB100 INFC125 INFp160

Type of fuse-linkNFC �0 x 38 b - - - - -

�4 x 5� b - b - - -22 x 58 - - b - b b

DIN (NH) NH000 - b b - - b

NH00 - - b - - b

BS (fixing centres in mm) (2) A� (44.5) b - - - - -F� b - - - - -A2 (73.0) b - b b - b

0565

02 A3 (73.0) - - b b - b

A4 (93.7) - - - b (1) - b (1)

Installation and connectionFixed front connection b b b b b b

Terminal tightening torque (Nm) 2 2 3.5 M8: �5-22 M8: �5-22 M8: �5-22Fuse-link bolt tightening torque (Nm) 2 2 2 M5: 3.5 M8: 5 - M5: 3.5 M8: 5Installation and connection accessories

Bare cable connectors b (standard) b (standard) b (standard) b (optional) b (optional) b (optional)Terminals - - - b b b

Neutral link b b b b b b

Terminal shields - b b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P 97 x �06 x �05 97 x �06 x �33 �00 x �43 x �28 �40 x �80 x �30 �40 x �80 x �30 �40 x �80 x �30

4P 97 x �42 x �05 97 x �42 x �33 �00 x �88 x �28 �40 x 2�5 x �30 �40 x 2�5 x �30 �40 x 2�5 x �30

0565

03 Approximate weight without fuses (kg) 3P 0.7 0.7 �.3 �.5 �.5 �.54P 0.9 0.9 �.6 �.8 �.8 �.8

Enclosure dimensions for ItheH x W x D (mm) 300 x 350 x 200

Temperature derating (3) (4) NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C 32 40 63 �00 �25 �6045 °C 30.4 38 60 95 ��9 �5250 °C 28.8 36 56.7 90 ��3 �4455 °C 27.2 34 53.6 85 �06 �3660 °C 25.6 32 50.4 80 �00 �2865 °C 25 30 47.2 75 94 �2070 °C 24.4 28 44 70 88 ��2

“Horizontal mounting” fuse-links in horizontal position

Ith (A) 35 °C 3� 38 6� 96 �2� �5640 °C 29.5 36 58 92 ��5 �4845 °C 28 34 55 87 �09 �4050 °C 26.5 32 52.2 83 �03 �3355 °C 25 30 49.3 78 97 �2660 °C 23.5 28 46.4 74 92 ��865 °C 22 26 43 69 86 ���70 °C 20.5 24 40 65 8� �03

(1) Maximum fuse body diameter: Ø32 mm.(2) A: fuse-link with centre bolted tags.(3) Derating data is based on:- the maximum rating for fuse-links intended for the device,- maximum power dissipation.(4) For installation on a ceiling, derate an additional 10 %.

INFB32.

INFC63.

INFD160.

52

Page 55: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector fuses selection0 Fupact INFp32 to INFp160

Fupact

0590

00 Switch-disconnector fuses INFp32 INFD40 INFp63 INFB100 INFC125 INFp160Type of fuse-link

NFC �0 x 38 b - - - - -�4 x 5� b - b - - -22 x 58 - - b - b b

DIN (NH) NH000 - b b - - b

NH00 - - b - - b

BS (fixing centres in mm) (2) A� (44.5) b - - - - -F� b - - - - -A2 (73.0) b - b b - b

0565

02 A3 (73.0) - - b b - b

A4 (93.7) - - - b (1) - b (1)

Installation and connectionFixed front connection b b b b b b

Terminal tightening torque (Nm) 2 2 3.5 M8: �5-22 M8: �5-22 M8: �5-22Fuse-link bolt tightening torque (Nm) 2 2 2 M5: 3.5 M8: 5 - M5: 3.5 M8: 5Installation and connection accessories

Bare cable connectors b (standard) b (standard) b (standard) b (optional) b (optional) b (optional)Terminals - - - b b b

Neutral link b b b b b b

Terminal shields - b b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P 97 x �06 x �05 97 x �06 x �33 �00 x �43 x �28 �40 x �80 x �30 �40 x �80 x �30 �40 x �80 x �30

4P 97 x �42 x �05 97 x �42 x �33 �00 x �88 x �28 �40 x 2�5 x �30 �40 x 2�5 x �30 �40 x 2�5 x �30

0565

03 Approximate weight without fuses (kg) 3P 0.7 0.7 �.3 �.5 �.5 �.54P 0.9 0.9 �.6 �.8 �.8 �.8

Enclosure dimensions for ItheH x W x D (mm) 300 x 350 x 200

Temperature derating (3) (4) NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C 32 40 63 �00 �25 �6045 °C 30.4 38 60 95 ��9 �5250 °C 28.8 36 56.7 90 ��3 �4455 °C 27.2 34 53.6 85 �06 �3660 °C 25.6 32 50.4 80 �00 �2865 °C 25 30 47.2 75 94 �2070 °C 24.4 28 44 70 88 ��2

“Horizontal mounting” fuse-links in horizontal position

Ith (A) 35 °C 3� 38 6� 96 �2� �5640 °C 29.5 36 58 92 ��5 �4845 °C 28 34 55 87 �09 �4050 °C 26.5 32 52.2 83 �03 �3355 °C 25 30 49.3 78 97 �2660 °C 23.5 28 46.4 74 92 ��865 °C 22 26 43 69 86 ���70 °C 20.5 24 40 65 8� �03

(1) Maximum fuse body diameter: Ø32 mm.(2) A: fuse-link with centre bolted tags.(3) Derating data is based on:- the maximum rating for fuse-links intended for the device,- maximum power dissipation.(4) For installation on a ceiling, derate an additional 10 %.

53

Page 56: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector fuses selection Fupact INFp200 to INFp800

FupactP

B �

0422

4A

INFD200.

Switch-disconnector fuses INFp200 INFp250 INFp400 INFp630 INFp800Number of poles / type of fuse-link 3 poles / 3 fuse-links DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS

4 poles / 3 fuse-links + switched neutral DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS4 poles / 4 fuse-links DIN DIN DIN DIN DIN

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C 200 250 400 630 800

Maximum fuse power dissipation (W) �7 23 45 60 65In enclosure Ithe at 40 °C 200 �80 250 230 400 360 570 720Maximum fuse power dissipation (W) �5 �8 20 27 30 37 50 55

Rated insulation voltage (V) Ui AC 50/60 Hz / DC �000 �000 �000 �000 �000Rated impulse withstand voltage (kV) Uimp �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690

DC 750 750 750 750 750

PB

�04

226A

Rated operational voltage AC20 and DC20 (V) Ue �000 �000 �000 �000 �000Rated operational current (A) Ie AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220/240 V 200 200 250 250 400 400 630 630 800 800380/4�5 V 200 200 250 250 400 400 630 630 800 800440/480 V (1) 200 200 250 250 400 400 630 630 800 800500/525 V 200 200 250 250 400 400 630 630 800 800660/690 V 200 200 250 250 400 400 630 630 800 800

DC/poles in series DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A�25 V/nbr of poles 200/� 200/� 250/� 250/� 400/2 400/2 630/� 630/� 800/� 800/�250 V/nbr of poles 200/2 200/2 250/2 250/2 400/3 400/3 630/2 (4) 630/2 (4) 800/2 (4) 800/2 (4)

500 V/nbr of poles 200/3 200/3 250/3 250/3 400/4 (4) 400/4 (4) 630/3 (4) 630/3 (4) 720/3 (4) 720/3 (4)

750 V/nbr of poles �80/4 �80/4 230/4 230/4 400/4 (4) 400/4 (4) 630/4 (4) 630/4 (4) 720/4 (4) 720/4 (4)

Rated operational power (kW) (2)

(motor power given for direct on-line starting)AC 220/240 V 60 75 �32 200 250

380/400 V ��0 �40 220 355 450INFD400. 4�5 V ��0 �45 230 355 450

PB

�04

227A

500/525 V �32 �70 280 450 560660/690 V 200 250 400 630 7�0

Rated duties Uninterrupted duty b b b b b

Intermittent duty class �20-60 % class �20-60 % class �20-60 % class �20-60 % class �20-60 %Rated short-circuit making capacity (kA peak)Switch-disconnector without fuse (refer to single- phase fuse limitation curves)

Icm 4�5 V 35 40.5 59 77 77500 V 37.5 37.5 63.5 83 83690 V 28 28 48 55 55

Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak) (3)

Icn / Icm 4�5 V (BS) 80/�76 80/�76 80/�76 80/�76 80/�76500 V (DIN) �00/220 �00/220 �00/220 �00/220 �00/220690 V (DIN) 80/�76 80/�76 80/�76 80/�76 80/�76

Rated short-time withstand current (A rms) Icw � s 8000 8000 �4000 �8000 �80003 s 4620 4620 8080 �0400 �040020 s �790 �790 3�30 4000 400030 s �460 �460 2550 3300 3300

Endurance (category A) (CO cycles) Mechanical �0000 �0000 8000 5000 5000Electrical AC AC22A 500 V �000 �000 �000 �000 500

AC22A 690 V �000 �000 �000 �000 500AC23A 500 V �000 �000 �000 �000 500AC23A 690 V �000 �000 �000 �000 500

INFB800. Suitability for isolation b b b b b

Positive contact indication b b b b b

Pollution degree 3 3 3 3 3Control

Direct front rotary handle b b b b b

Extended front rotary handle b b b b b

Extended lateral rotary handle - - - - -Locking by padlocks b b b b b

Operating torque (typical for 3-pole switch-disconnector fuses) (Nm) 7 7 �9 38 38Indication auxiliaries

Auxiliary contacts b b b b b

Blown-fuse indicator b (5) b (5) b (5) b (5) b (5)

Fuse monitor b b b b b

Auxiliary contact test position b b b b b (1) Suitable for 480 V NEMA.(2) Some fuse-links limit these values. Motor starting current must be considered separately.(3) Switch-disconnector combined with fuses.(4) Category B.(5) Only for DIN fuse-links.

54

Page 57: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector fuses selection Fupact INFp200 to INFp800

Fupact

PB

�04

224A

INFD200.

Switch-disconnector fuses INFp200 INFp250 INFp400 INFp630 INFp800Number of poles / type of fuse-link 3 poles / 3 fuse-links DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS

4 poles / 3 fuse-links + switched neutral DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS4 poles / 4 fuse-links DIN DIN DIN DIN DIN

Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3Conventional thermal current (A) In free air Ith at 40 °C 200 250 400 630 800

Maximum fuse power dissipation (W) �7 23 45 60 65In enclosure Ithe at 40 °C 200 �80 250 230 400 360 570 720Maximum fuse power dissipation (W) �5 �8 20 27 30 37 50 55

Rated insulation voltage (V) Ui AC 50/60 Hz / DC �000 �000 �000 �000 �000Rated impulse withstand voltage (kV) Uimp �2 �2 �2 �2 �2Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690

DC 750 750 750 750 750

PB

�04

226A

Rated operational voltage AC20 and DC20 (V) Ue �000 �000 �000 �000 �000Rated operational current (A) Ie AC 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

220/240 V 200 200 250 250 400 400 630 630 800 800380/4�5 V 200 200 250 250 400 400 630 630 800 800440/480 V (1) 200 200 250 250 400 400 630 630 800 800500/525 V 200 200 250 250 400 400 630 630 800 800660/690 V 200 200 250 250 400 400 630 630 800 800

DC/poles in series DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A�25 V/nbr of poles 200/� 200/� 250/� 250/� 400/2 400/2 630/� 630/� 800/� 800/�250 V/nbr of poles 200/2 200/2 250/2 250/2 400/3 400/3 630/2 (4) 630/2 (4) 800/2 (4) 800/2 (4)

500 V/nbr of poles 200/3 200/3 250/3 250/3 400/4 (4) 400/4 (4) 630/3 (4) 630/3 (4) 720/3 (4) 720/3 (4)

750 V/nbr of poles �80/4 �80/4 230/4 230/4 400/4 (4) 400/4 (4) 630/4 (4) 630/4 (4) 720/4 (4) 720/4 (4)

Rated operational power (kW) (2)

(motor power given for direct on-line starting)AC 220/240 V 60 75 �32 200 250

380/400 V ��0 �40 220 355 450INFD400. 4�5 V ��0 �45 230 355 450

PB

�04

227A

500/525 V �32 �70 280 450 560660/690 V 200 250 400 630 7�0

Rated duties Uninterrupted duty b b b b b

Intermittent duty class �20-60 % class �20-60 % class �20-60 % class �20-60 % class �20-60 %Rated short-circuit making capacity (kA peak)Switch-disconnector without fuse (refer to single- phase fuse limitation curves)

Icm 4�5 V 35 40.5 59 77 77500 V 37.5 37.5 63.5 83 83690 V 28 28 48 55 55

Rated short-circuit breaking capacity (kA rms) / Rated short-circuit making capacity (kA peak) (3)

Icn / Icm 4�5 V (BS) 80/�76 80/�76 80/�76 80/�76 80/�76500 V (DIN) �00/220 �00/220 �00/220 �00/220 �00/220690 V (DIN) 80/�76 80/�76 80/�76 80/�76 80/�76

Rated short-time withstand current (A rms) Icw � s 8000 8000 �4000 �8000 �80003 s 4620 4620 8080 �0400 �040020 s �790 �790 3�30 4000 400030 s �460 �460 2550 3300 3300

Endurance (category A) (CO cycles) Mechanical �0000 �0000 8000 5000 5000Electrical AC AC22A 500 V �000 �000 �000 �000 500

AC22A 690 V �000 �000 �000 �000 500AC23A 500 V �000 �000 �000 �000 500AC23A 690 V �000 �000 �000 �000 500

INFB800. Suitability for isolation b b b b b

Positive contact indication b b b b b

Pollution degree 3 3 3 3 3Control

Direct front rotary handle b b b b b

Extended front rotary handle b b b b b

Extended lateral rotary handle - - - - -Locking by padlocks b b b b b

Operating torque (typical for 3-pole switch-disconnector fuses) (Nm) 7 7 �9 38 38Indication auxiliaries

Auxiliary contacts b b b b b

Blown-fuse indicator b (5) b (5) b (5) b (5) b (5)

Fuse monitor b b b b b

Auxiliary contact test position b b b b b (1) Suitable for 480 V NEMA.(2) Some fuse-links limit these values. Motor starting current must be considered separately.(3) Switch-disconnector combined with fuses.(4) Category B.(5) Only for DIN fuse-links.

55

Page 58: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector fuses selection Fupact INFp200 to INFp800

FupactP

B�0

4224

A

INFD200.

Switch-disconnector fuses INFp200 INFp250 INFp400 INFp630 INFp800Type of fuse-link

DIN (NH) NH (0) b - - - -NH (0, �) - b - - -NH (0, �, 2) - - b - -NH (3) - - - b b

BS (fixing centres in mm) (1) B� (���) b b b - -B2 (���) b b b - -B3 (���) - b (4) b - -B4 (���) - - b (5) - -C� (�33) - - - b b

C2 (�33) - - - b b

PB

�04

226A

INFD400.

C3 (�33) - - - - b

Installation and connectionFixed front connection b b b b b

Terminal tightening torque (Nm) �5-22 30-44 30-44 50-75 50-75Fuse-link bolt tightening torque (Nm) 4 5 20 M�0 : 30 M�2 : 40 M�0 : 30 M�2 : 40Installation and connection accessories

Bare cable connectors b (optional) b (optional) b (optional) b (optional) b (optional)Terminals b b b b b

Neutral link b b b b b

Terminal shields b b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P (DIN) �99 x �75.5 x �49 �93 x 206 x �54 230 x 254 x �93 306 x 34� x 233 306 x 34� x 233

3P (BS) �99 x �75.5 x �30 230 x 254 x �764P (DIN) �99 x 2�9 x �49 �93 x 260 x �54 230 x 3�8 x �93 306 x 429 x 233 306 x 429 x 2334P (BS) �99 x 2�9 x �30 230 x 3�8 x �76

Approximate weight without fuses (kg) 3P 2.6 3.� 5.7 ��.5 ��.5

PB

�04

227A 4P 3.6 4.� 7.7 �4.4 �4.4

Enclosure dimensions for ItheH x W x D (mm) 600 x 350 x 300 800 x 400 x 330 6�0 x 508 x 254 800 x �000 x 330 800 x �000 x 330

Temperature derating (2) (3) DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C 200 250 400 630 80045 °C �85 232 370 583 74�50 °C �77 222 355 558 70955 °C �69 2�� 338 532 67660 °C �60 200 32� 505 64�65 °C �5� �89 302 476 60570 °C �4� �77 283 446 566

“Horizontal mounting” fuse-links in horizontal position

Ith (A) 35 °C 200 250 400 570 72040 °C �93 24� 385 549 69445 °C �85 23� 370 528 66750 °C �77 222 355 505 63855 °C �69 2�� 338 482 60960 °C �60 200 32� 457 57765 °C �5� �89 302 43� 544

INFB800. 70 °C �4� �77 283 403 509(1) B: fuse-link with offset bolted tags.(2) Derating data is based on:- the maximum rating for fuse-links intended for the device,- maximum power dissipation.(3) For installation on a ceiling, derate an additional 10 %.(4) Maximum fuse body diameter: Ø52 mm.(5) Maximum fuse body diameter: Ø62 mm.

56

Page 59: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Switch-disconnector fuses selection Fupact INFp200 to INFp800

Fupact

PB

�042

24A

INFD200.

Switch-disconnector fuses INFp200 INFp250 INFp400 INFp630 INFp800Type of fuse-link

DIN (NH) NH (0) b - - - -NH (0, �) - b - - -NH (0, �, 2) - - b - -NH (3) - - - b b

BS (fixing centres in mm) (1) B� (���) b b b - -B2 (���) b b b - -B3 (���) - b (4) b - -B4 (���) - - b (5) - -C� (�33) - - - b b

C2 (�33) - - - b b

PB

�04

226A

INFD400.

C3 (�33) - - - - b

Installation and connectionFixed front connection b b b b b

Terminal tightening torque (Nm) �5-22 30-44 30-44 50-75 50-75Fuse-link bolt tightening torque (Nm) 4 5 20 M�0 : 30 M�2 : 40 M�0 : 30 M�2 : 40Installation and connection accessories

Bare cable connectors b (optional) b (optional) b (optional) b (optional) b (optional)Terminals b b b b b

Neutral link b b b b b

Terminal shields b b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P (DIN) �99 x �75.5 x �49 �93 x 206 x �54 230 x 254 x �93 306 x 34� x 233 306 x 34� x 233

3P (BS) �99 x �75.5 x �30 230 x 254 x �764P (DIN) �99 x 2�9 x �49 �93 x 260 x �54 230 x 3�8 x �93 306 x 429 x 233 306 x 429 x 2334P (BS) �99 x 2�9 x �30 230 x 3�8 x �76

Approximate weight without fuses (kg) 3P 2.6 3.� 5.7 ��.5 ��.5

PB

�04

227A 4P 3.6 4.� 7.7 �4.4 �4.4

Enclosure dimensions for ItheH x W x D (mm) 600 x 350 x 300 800 x 400 x 330 6�0 x 508 x 254 800 x �000 x 330 800 x �000 x 330

Temperature derating (2) (3) DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C 200 250 400 630 80045 °C �85 232 370 583 74�50 °C �77 222 355 558 70955 °C �69 2�� 338 532 67660 °C �60 200 32� 505 64�65 °C �5� �89 302 476 60570 °C �4� �77 283 446 566

“Horizontal mounting” fuse-links in horizontal position

Ith (A) 35 °C 200 250 400 570 72040 °C �93 24� 385 549 69445 °C �85 23� 370 528 66750 °C �77 222 355 505 63855 °C �69 2�� 338 482 60960 °C �60 200 32� 457 57765 °C �5� �89 302 43� 544

INFB800. 70 °C �4� �77 283 403 509(1) B: fuse-link with offset bolted tags.(2) Derating data is based on:- the maximum rating for fuse-links intended for the device,- maximum power dissipation.(3) For installation on a ceiling, derate an additional 10 %.(4) Maximum fuse body diameter: Ø52 mm.(5) Maximum fuse body diameter: Ø62 mm.

57

Page 60: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fuse-switch disconnectors0

selection Fupact ISFT100N to ISFT630

FupactP

B�0

43��

ISFT100N.

ISFT100.

ISFT160.

ISFT630.

Fuse-switch disconnectors ISFT100N ISFT100 ISFT160 ISFT250 ISFT400 ISFT630Number of poles / type of fuse-link IEC60 269-2-� Section � 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH)Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3

Conventional thermal current (A) In free air Ith at 40 °C �00 �00/�60 (1) �60 250 400 630Maximum fuse power dissipation (W) 7.5 9 �2 23 34 48In enclosure Ithe at 40 °C �00 �00/�60 (1) �60 250 400 630Maximum fuse power dissipation (W) 7.5 9 �2 23 34 48

Rated insulation voltage (V) Ui AC 50/60 Hz / DC 800 690 800 800 800 800Rated impulse withstand voltage (kV) Uimp 8 6 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690

DC 440 440 440 440 440 440Rated operational voltage AC20 and DC20 (V) Ue 690 690 800 800 800 800Rated operational current (A) Ie AC 50/60 Hz AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B

220/240 V �00 �00 (4) �60 �60 �60 �60 250 250 400 400 630 630380/4�5 V �00 �00 (4) �60 �60 �60 �60 250 250 400 400 630 630

62�9

3A_S

E

440/480 V (2) �00 �00 �00 - �60 - 250 - 400 - 630 -500 V �00 �00 �00 - �60 - 250 - 400 - 630 -660/690 V �00 - �00 - �00 - 250 - 400 - 630 -

DC/poles in series DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B�25 V /nbr of poles �00/3 �00/3 �00/� - �60/� - 250/� - 400/� - 630/� -220 V /nbr of poles �00/3 �00/3 �00/� - �60/� - 250/� - 400/� - 630/� -440 V /nbr of poles �00/3 �00/3 �00/� - �60/2 - 250/2 - 400/2 - 630/2 -

Rated duties Uninterrupted duty b b b b b b

Rated short-circuit breaking capacity (kA rms)/Rated short-circuit making capacity (kA peak)/Fuse-link In (A) (3)

Icn/Icm/In 4�5 V 80 / �76 / �00 80 / �76 / �00 50 / �05 / �60 50 / �05 / 250 50 / �05 / 400 50 / �05 / 630500 V 50 / �05 / �00 50 / �05 / �00 50 / �05 / �60 50 / �05 / 250 50 / �05 / 400 50 / �05 / 630690 V 50 / �05 / �00 50 / �05 / �00 50 / �05 / �00 50 / �05 / 200 50 / �05 / 3�5 50 / �05 / 500

Endurance (category B) (CO cycles) Mechanical 2000 2000 �600 �600 �000 �000Electrical AC AC22B 4�5 V 300 300 200 200 200 200

AC23B 4�5 V 300 - - - - -AC2�B 690 V 300 300 200 200 200 200

Suitability for isolation b b b b b b

62�9

4A_S

E Positive contact indication b b b b b b

Pollution degree 3 3 3 3 3 3Control

Direct front rotary handle (operator-dependent opening and closing) b b b b b b

Locking Padlocks - - - - - -Lead seal b b b b b b

Indication auxiliariesAuxiliary contacts b b b b b b

Fuse monitor - - b b b b

Blown-fuse indicator - - b - - -Installation and connection accessories

Possible mounting positions Horizontal b b b b b b

Vertical b b b b b b

Bare cable connectors b b b - - -Other connectors For bare Cu/Al cables - - b b b b

62�9

5A_S

E

For flexible bars - - b b b b

Distribution connectors - b b - - -Lugs for copper cables - - b b b b

Insulated comb busbar covers - b - - - -Insulated comb covers - b - - - -Incoming connector for comb busbars - b - - - -Terminal shields - - b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P 2�6 x 53 x 82 �4� x 89 x 7� �63 x �07 x 80 246 x �86 x ��0 27� x 2�0 x �27 27� x 250 x �32Approximate weight without fuse-links (kg) 3P 0.54 0.46 0.64 2.06 2.96 4.00(1) With 95 mm2 connector.(2) Suitable for 480 V NEMA.(3) Fuse-switch disconnectors with fuse-links.(4) AC23B: 100 A.

58

Page 61: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fuse-switch disconnectors0

selection Fupact ISFT100N to ISFT630

Fupact

PB

�043

��

ISFT100N.

ISFT100.

ISFT160.

ISFT630.

Fuse-switch disconnectors ISFT100N ISFT100 ISFT160 ISFT250 ISFT400 ISFT630Number of poles / type of fuse-link IEC60 269-2-� Section � 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH)Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3

Conventional thermal current (A) In free air Ith at 40 °C �00 �00/�60 (1) �60 250 400 630Maximum fuse power dissipation (W) 7.5 9 �2 23 34 48In enclosure Ithe at 40 °C �00 �00/�60 (1) �60 250 400 630Maximum fuse power dissipation (W) 7.5 9 �2 23 34 48

Rated insulation voltage (V) Ui AC 50/60 Hz / DC 800 690 800 800 800 800Rated impulse withstand voltage (kV) Uimp 8 6 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690 690

DC 440 440 440 440 440 440Rated operational voltage AC20 and DC20 (V) Ue 690 690 800 800 800 800Rated operational current (A) Ie AC 50/60 Hz AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B

220/240 V �00 �00 (4) �60 �60 �60 �60 250 250 400 400 630 630380/4�5 V �00 �00 (4) �60 �60 �60 �60 250 250 400 400 630 630

62�9

3A_S

E

440/480 V (2) �00 �00 �00 - �60 - 250 - 400 - 630 -500 V �00 �00 �00 - �60 - 250 - 400 - 630 -660/690 V �00 - �00 - �00 - 250 - 400 - 630 -

DC/poles in series DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B DC21B DC22B�25 V /nbr of poles �00/3 �00/3 �00/� - �60/� - 250/� - 400/� - 630/� -220 V /nbr of poles �00/3 �00/3 �00/� - �60/� - 250/� - 400/� - 630/� -440 V /nbr of poles �00/3 �00/3 �00/� - �60/2 - 250/2 - 400/2 - 630/2 -

Rated duties Uninterrupted duty b b b b b b

Rated short-circuit breaking capacity (kA rms)/Rated short-circuit making capacity (kA peak)/Fuse-link In (A) (3)

Icn/Icm/In 4�5 V 80 / �76 / �00 80 / �76 / �00 50 / �05 / �60 50 / �05 / 250 50 / �05 / 400 50 / �05 / 630500 V 50 / �05 / �00 50 / �05 / �00 50 / �05 / �60 50 / �05 / 250 50 / �05 / 400 50 / �05 / 630690 V 50 / �05 / �00 50 / �05 / �00 50 / �05 / �00 50 / �05 / 200 50 / �05 / 3�5 50 / �05 / 500

Endurance (category B) (CO cycles) Mechanical 2000 2000 �600 �600 �000 �000Electrical AC AC22B 4�5 V 300 300 200 200 200 200

AC23B 4�5 V 300 - - - - -AC2�B 690 V 300 300 200 200 200 200

Suitability for isolation b b b b b b

62�9

4A_S

E Positive contact indication b b b b b b

Pollution degree 3 3 3 3 3 3Control

Direct front rotary handle (operator-dependent opening and closing) b b b b b b

Locking Padlocks - - - - - -Lead seal b b b b b b

Indication auxiliariesAuxiliary contacts b b b b b b

Fuse monitor - - b b b b

Blown-fuse indicator - - b - - -Installation and connection accessories

Possible mounting positions Horizontal b b b b b b

Vertical b b b b b b

Bare cable connectors b b b - - -Other connectors For bare Cu/Al cables - - b b b b

62�9

5A_S

E

For flexible bars - - b b b b

Distribution connectors - b b - - -Lugs for copper cables - - b b b b

Insulated comb busbar covers - b - - - -Insulated comb covers - b - - - -Incoming connector for comb busbars - b - - - -Terminal shields - - b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P 2�6 x 53 x 82 �4� x 89 x 7� �63 x �07 x 80 246 x �86 x ��0 27� x 2�0 x �27 27� x 250 x �32Approximate weight without fuse-links (kg) 3P 0.54 0.46 0.64 2.06 2.96 4.00(1) With 95 mm2 connector.(2) Suitable for 480 V NEMA.(3) Fuse-switch disconnectors with fuse-links.(4) AC23B: 100 A.

59

Page 62: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fupact Fuse-switch disconnectors selectionFupact ISFT100N to ISFT630

PB

�043

��

ISFT100N.

ISFT100.

ISFT160.

ISFT630.

Fuse-switch disconnectors ISFT100N ISFT100 ISFT160 ISFT250 ISFT400 ISFT630Type of fuse-link

DIN NH000 b b b - - -DIN NH00 - - b - - -DIN NH� - - - b - -DIN NH2 - - - - b -DIN NH3 - - - - - b

Installation and connectionSymmetrical rail b b - - -Direct connection on backplate b b b b b b

Push-on connection to 60 mm busbars - - b b - -Hook-on connection to 60 mm busbars b - b b b b

Hook-on connection to �00 mm busbars - - - b b b

Tightening torque (Nm) see catalogue LVPED2080�4ENTemperature derating (with gG fuse-link) (1) (2)

62�9

3A_S

E

“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C �00 �00/�60 (3) �60 250 400 63045 °C 95 95/�52 �52 238 380 59950 °C 90 90/�44 �44 225 360 56755 °C 85 85/�36 �36 2�3 340 53660 °C 80 80/�28 �28 200 320 50465 °C 75 75/�20 �20 �88 300 47370 °C 70 70/��2 ��2 �75 280 44�

“Horizontal mounting”fuse-links in horizontal position

Ith (A) 40 °C �00 �00/�60 (3) �60 250 400 63045 °C 95 95/�52 �52 238 380 59950 °C 90 90/�44 �44 225 360 56755 °C 85 85/�36 �36 2�3 340 53660 °C 80 80/�28 �28 200 320 50465 °C 75 75/�20 �20 �88 300 47370 °C 70 70/��2 ��2 �75 280 44�

62�9

4A_S

E

(1) Derating data is based on: - the maximum rating for fuse-links intended for the device,- maximum power dissipation.(2) For installation on a ceiling, derate an additional 10 %.(3) With 100/160 A fuse-link.

62�9

5A_S

E

60

Page 63: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fupact Fuse-switch disconnectors selectionFupact ISFT100N to ISFT630

PB

�043

��

ISFT100N.

ISFT100.

ISFT160.

ISFT630.

Fuse-switch disconnectors ISFT100N ISFT100 ISFT160 ISFT250 ISFT400 ISFT630Type of fuse-link

DIN NH000 b b b - - -DIN NH00 - - b - - -DIN NH� - - - b - -DIN NH2 - - - - b -DIN NH3 - - - - - b

Installation and connectionSymmetrical rail b b - - -Direct connection on backplate b b b b b b

Push-on connection to 60 mm busbars - - b b - -Hook-on connection to 60 mm busbars b - b b b b

Hook-on connection to �00 mm busbars - - - b b b

Tightening torque (Nm) see catalogue LVPED2080�4ENTemperature derating (with gG fuse-link) (1) (2)

62�9

3A_S

E

“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C �00 �00/�60 (3) �60 250 400 63045 °C 95 95/�52 �52 238 380 59950 °C 90 90/�44 �44 225 360 56755 °C 85 85/�36 �36 2�3 340 53660 °C 80 80/�28 �28 200 320 50465 °C 75 75/�20 �20 �88 300 47370 °C 70 70/��2 ��2 �75 280 44�

“Horizontal mounting”fuse-links in horizontal position

Ith (A) 40 °C �00 �00/�60 (3) �60 250 400 63045 °C 95 95/�52 �52 238 380 59950 °C 90 90/�44 �44 225 360 56755 °C 85 85/�36 �36 2�3 340 53660 °C 80 80/�28 �28 200 320 50465 °C 75 75/�20 �20 �88 300 47370 °C 70 70/��2 ��2 �75 280 44�

62�9

4A_S

E

(1) Derating data is based on: - the maximum rating for fuse-links intended for the device,- maximum power dissipation.(2) For installation on a ceiling, derate an additional 10 %.(3) With 100/160 A fuse-link.

62�9

5A_S

E

6�

Page 64: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fuse-switch disconnectors selectionFupact ISFL160 to ISFL630

Fupact

62�9

6

ISFL160.

ISFL250.

Fuse-switch disconnectors ISFL160 ISFL250 ISFL400 ISFL630Number of poles / type of fuse-link IEC60 269-2-� Section � 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH)Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3

Conventional thermal current (A) In free air Ith at 40 °C �60 250 400 630Maximum fuse power dissipation (W) �2 23 34 48In enclosure Ithe at 40 °C �60 250 400 630Maximum fuse power dissipation (W) �2 23 34 48

Rated insulation voltage (V) Ui AC 50/60 Hz / DC 800 800 800 800Rated impulse withstand voltage (kV) Uimp 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690

DC 440 440 440 440Rated operational voltage AC20 and DC20 (V) Ue 800 800 800 800Rated operational current (A) Ie AC 50/60 Hz AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B

220/240 V �60 �60 250 250 400 400 630 630380/4�5 V �60 �60 250 250 400 400 630 630440/480 V (1) �60 - 250 - 400 - 630 -500 V �60 - 250 - 400 - 630 -660/690 V �00 - 250 - 400 - 630 -

DC/poles in series DC21B DC22B DC21B DC22B DC22B DC21B DC22B DC21B�25 V /nbr of poles - - - - - - - -

62�9

7

220 V /nbr of poles - - - - - - - -440 V /nbr of poles - - - - - - - -

Rated duties Uninterrupted duty b b b b

Rated short-circuit breaking capacity (kA rms)/Rated short-circuit making capacity (kA peak)/Fuse-link In (A) (2)

Icn/Icm/In 4�5 V 50 / �05 / �60 �00 / 220 / 250 �00 / 220 / 400 �00 / 220 / 630500 V 50 / �05 / �60 50 / �05 / 250 50 / �05 / 400 50 / �05 / 630690 V 50 / �05 / �00 50 / �05 / 200 50 / �05 / 3�5 50 / �05 / 500

Endurance (category B) (CO cycles) Mechanical �600 �600 �000 �000Electrical AC AC22B 4�5 V 200 200 200 200

AC2�B 690 V 200 200 200 200Suitability for isolation b b b b

Positive contact indication b b b b

Pollution degree 3 3 3 3Control

Direct front rotary handle (operator-dependent opening and closing) b b b b

Locking Padlocks b b b b

Lead seal - - - -Indication auxiliaries

Auxiliary contacts b b b b

Blown-fuse indicator - - - -Current transformer b (3) b b b

Installation and connection accessoriesPossible mounting position Horizontal b - - -

Vertical b b b b

Connector For bare Cu/Al cables b b b b

For flexible bars b - - -Lugs for Cu/Al cables b - - -Terminal shields b b b b

Coupling accessories b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P 456 x 50 x �59 755 x �00 x �92 755 x �00 x �92 755 x �00 x �92Approximate weight without fuse-links (kg) 3P �.35 6.35 6.35 6.35(1) Suitable for 480 V NEMA.(2) Fuse-switch disconnectors with fuse-links.(3) Only for ISF160 with direct connection to the busbars.

62

Page 65: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fuse-switch disconnectors selectionFupact ISFL160 to ISFL630

Fupact

62

�96

ISFL160.

ISFL250.

Fuse-switch disconnectors ISFL160 ISFL250 ISFL400 ISFL630Number of poles / type of fuse-link IEC60 269-2-� Section � 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH) 3P/DIN (NH)Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3

Conventional thermal current (A) In free air Ith at 40 °C �60 250 400 630Maximum fuse power dissipation (W) �2 23 34 48In enclosure Ithe at 40 °C �60 250 400 630Maximum fuse power dissipation (W) �2 23 34 48

Rated insulation voltage (V) Ui AC 50/60 Hz / DC 800 800 800 800Rated impulse withstand voltage (kV) Uimp 8 8 8 8Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690

DC 440 440 440 440Rated operational voltage AC20 and DC20 (V) Ue 800 800 800 800Rated operational current (A) Ie AC 50/60 Hz AC21B AC22B AC21B AC22B AC21B AC22B AC21B AC22B

220/240 V �60 �60 250 250 400 400 630 630380/4�5 V �60 �60 250 250 400 400 630 630440/480 V (1) �60 - 250 - 400 - 630 -500 V �60 - 250 - 400 - 630 -660/690 V �00 - 250 - 400 - 630 -

DC/poles in series DC21B DC22B DC21B DC22B DC22B DC21B DC22B DC21B�25 V /nbr of poles - - - - - - - -

62�9

7

220 V /nbr of poles - - - - - - - -440 V /nbr of poles - - - - - - - -

Rated duties Uninterrupted duty b b b b

Rated short-circuit breaking capacity (kA rms)/Rated short-circuit making capacity (kA peak)/Fuse-link In (A) (2)

Icn/Icm/In 4�5 V 50 / �05 / �60 �00 / 220 / 250 �00 / 220 / 400 �00 / 220 / 630500 V 50 / �05 / �60 50 / �05 / 250 50 / �05 / 400 50 / �05 / 630690 V 50 / �05 / �00 50 / �05 / 200 50 / �05 / 3�5 50 / �05 / 500

Endurance (category B) (CO cycles) Mechanical �600 �600 �000 �000Electrical AC AC22B 4�5 V 200 200 200 200

AC2�B 690 V 200 200 200 200Suitability for isolation b b b b

Positive contact indication b b b b

Pollution degree 3 3 3 3Control

Direct front rotary handle (operator-dependent opening and closing) b b b b

Locking Padlocks b b b b

Lead seal - - - -Indication auxiliaries

Auxiliary contacts b b b b

Blown-fuse indicator - - - -Current transformer b (3) b b b

Installation and connection accessoriesPossible mounting position Horizontal b - - -

Vertical b b b b

Connector For bare Cu/Al cables b b b b

For flexible bars b - - -Lugs for Cu/Al cables b - - -Terminal shields b b b b

Coupling accessories b b b b

Dimensions and weightOverall dimensions H x W x D (mm) 3P 456 x 50 x �59 755 x �00 x �92 755 x �00 x �92 755 x �00 x �92Approximate weight without fuse-links (kg) 3P �.35 6.35 6.35 6.35(1) Suitable for 480 V NEMA.(2) Fuse-switch disconnectors with fuse-links.(3) Only for ISF160 with direct connection to the busbars.

63

Page 66: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fuse-switch disconnectors selectionFupact ISFL160 to ISFL630

Fupact

ISFL160.

ISFL250.

Fuse-switch disconnectors ISFL160 ISFL250 ISFL400 ISFL630Type of fuse-link

DIN NH000 b - - -DIN NH00 b - - -DIN NH� - b - -DIN NH2 - - b -DIN NH3 - - - b

Installation and connectionHook-on connection to 60 mm busbars b - - -Direct connection to �00 mm busbars b - - -Direct connection to �85 mm busbars - b b b

To 60 mm busbars using a single-device conversion kit b - - -To �85 mm busbars using a single- or double-device conversion kit b - - -Tightening torque (Nm) see catalogue LVPED2080�4ENTemperature derating (with gG fuse-link) (1)

“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C �60 250 400 63045 °C �52 238 380 59950 °C �44 225 360 56755 °C �36 2�3 340 53660 °C �28 200 320 50465 °C �20 �88 300 47370 °C ��2 �75 280 44�

“Horizontal mounting”fuse-links in horizontal position

Ith (A) 40 °C �60 - - -45 °C �52 - - -50 °C �44 - - -55 °C �36 - - -60 °C �28 - - -65 °C �20 - - -70 °C ��2 - - -

(1) Derating data is based on:- the maximum rating for fuse-links intended for the device- maximum power dissipation.

64

Page 67: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Fuse-switch disconnectors selectionFupact ISFL160 to ISFL630

Fupact

ISFL160.

ISFL250.

Fuse-switch disconnectors ISFL160 ISFL250 ISFL400 ISFL630Type of fuse-link

DIN NH000 b - - -DIN NH00 b - - -DIN NH� - b - -DIN NH2 - - b -DIN NH3 - - - b

Installation and connectionHook-on connection to 60 mm busbars b - - -Direct connection to �00 mm busbars b - - -Direct connection to �85 mm busbars - b b b

To 60 mm busbars using a single-device conversion kit b - - -To �85 mm busbars using a single- or double-device conversion kit b - - -Tightening torque (Nm) see catalogue LVPED2080�4ENTemperature derating (with gG fuse-link) (1)

“Vertical mounting” fuse-links in vertical position

Ith (A) 40 °C �60 250 400 63045 °C �52 238 380 59950 °C �44 225 360 56755 °C �36 2�3 340 53660 °C �28 200 320 50465 °C �20 �88 300 47370 °C ��2 �75 280 44�

“Horizontal mounting”fuse-links in horizontal position

Ith (A) 40 °C �60 - - -45 °C �52 - - -50 °C �44 - - -55 °C �36 - - -60 °C �28 - - -65 °C �20 - - -70 °C ��2 - - -

(1) Derating data is based on:- the maximum rating for fuse-links intended for the device- maximum power dissipation.

65

Page 68: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Monitoring relays (3)

RH99 RH197P RHUs or RHU RH99 RMH

PB

�004

34-�

8_S

E

PB

�004

32-�

9_S

E

PB

�007

�5-�

9_S

E

0594

83-�

9_S

E

PB

�004

29-�

8_S

E

PB

�004

32-�

9_S

E

(4)

0594

85-�

4_S

E

b b b - -b b b b b

- b b b b

- - b except RHUs - b

- b (8) b - b �2 measurement channels (5)

b b b - -b b b - -

b - - b -b b b b b

b - - b -- b - - -b - - b - - b b - 220 to 240 V AC

9 user-selectable thresholds from 0.03 A to 30 A

19 user-selectable thresholds from 0.03 A to 30 A

1 adjustable threshold from 0.03 A to 30 A

- -

- Fixed: 50 % IDnor �00 % IDn

1 adjustable thresholdfrom 0.0�5 A to 30 A

9 user-selectable thresholds from 0.03 A to 30 A

1 adjustable threshold/channelfrom 0.03 A to 30 A

- - - - 1 adjustable threshold/channelfrom 0.0�5 A to 30 A

Instantaneous for IDn = 0.03 A 9 user-selectable time delays instantaneous to 4.5 s

7 user-selectable time delaysinstantaneous to 4.5 s

1 adjustable threshold instantaneous to 4.5 s

- -

- instantaneous 1 adjustable threshold instantaneous to 4.5 s

9 user-selectable time delays instantaneous to 4.5 s

1 adjustable threshold/channel instantaneous to 5 s

- - - - 1 adjustable threshold/channel instantaneous to 5 s

b b (9) b b b

b b b - -- b b b b

- - - - b

- on bargraph b - b

- - b - b(10)

b b b b b

b b b b -b b b b -- - b except RHUs - b

- - b except RHUs - b

See catalogue LVPED208009EN See catalogue LVPED208009EN

See catalogue LVPED208009EN

See catalogue LVPED208009EN See catalogue LVPED208009EN

b b b b b

b b b b b

(6) Depending on the type of wiring (optimum continuity of service or optimum safety).(7) See catalogue LVPED208009EN.

(8) On a bargraph(9) No voltage presence relay.(10) With actuation of contacts only.

Vigirex Selection guideProtection and monitoring relays

Protection relays (2)

RH10 RH21All Vigirex products are type A (1) devices, also covering the requirements of type AC devices.

PB

�004

35-�

8_S

E

PB

�004

30-�

9_S

E

PB

�004

33-�

8_S

E

PB

�004

3�-�

9_S

E

FunctionsProtection b b

Local indications b b

Remote indications (hard-wired) - -Remote indications (via communication) - -Display of measurements - -WiringOptimum continuity of service b b

Optimum safety (failsafe) b b

MountingDIN rail b b

Front-panel mount b b

Rated operational voltage� DC voltage range from �2 to 48 V b b

� DC voltage range from 24 to �30 V and AC 48 V - -6 AC voltage ranges from �2 to 525 V b b

4 AC voltage ranges from 48 to 4�5 V - -ThresholdsFault (IDn) 1 fixed instantaneous threshold

choose from 0.03 A to � A2 user-selectable thresholds 0.03 A or 0.3 A

Alarm - -

Pre-alarm - -

Time delaysFault Instantaneous 1 user-selectable time delay

instantaneous or 0.06 s for IDn = 0.3 A

Alarm - -

Pre-alarm - -

Display and indicationsVoltage presence (LED and/or relay) (6) b b

Threshold overrun fault (LED) b b

alarm (LED and relay) - -pre-alarm (LED and relay) - -

Leakage current (digital) - -Settings (digital) - -Test with or without actuation of output contactsLocal b b

Remote (hard-wired) b b

Remote (hard-wired for several relays) b b

Remote (via communication) - -CommunicationSuitable for supervision (internal bus) - -Characteristics

See catalogue LVPED208009EN See catalogue LVPED208009EN

SensorsMerlin Gerin A, OA, E toroids (7) up to 630 A b b

Merlin Gerin rectangular sensors up to 3200 A b b

(1) Type A relay up to IDn = 5 A.(2) Relay with output contact requiring local, manual reset after fault clearance.(3) Relay with output contact that automatically resets after fault clearance.

(4) Mandatory with an RMH (multiplexing for the 12 toroids).(5) Mandatory with an RM12T (multiplexing for the 12 toroids).

66

Page 69: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Selection guideProtection and monitoring relays

Vigirex

Monitoring relays (3)

RH99 RH197P RHUs or RHU RH99 RMH

PB

�004

34-�

8_S

E

PB

�004

32-�

9_S

E

PB

�007

�5-�

9_S

E

0594

83-�

9_S

E

PB

�004

29-�

8_S

E

PB

�004

32-�

9_S

E

(4)

0594

85-�

4_S

E

b b b - -b b b b b

- b b b b

- - b except RHUs - b

- b (8) b - b �2 measurement channels (5)

b b b - -b b b - -

b - - b -b b b b b

b - - b -- b - - -b - - b - - b b - 220 to 240 V AC

9 user-selectable thresholds from 0.03 A to 30 A

19 user-selectable thresholds from 0.03 A to 30 A

1 adjustable threshold from 0.03 A to 30 A

- -

- Fixed: 50 % IDnor �00 % IDn

1 adjustable thresholdfrom 0.0�5 A to 30 A

9 user-selectable thresholds from 0.03 A to 30 A

1 adjustable threshold/channelfrom 0.03 A to 30 A

- - - - 1 adjustable threshold/channelfrom 0.0�5 A to 30 A

Instantaneous for IDn = 0.03 A 9 user-selectable time delays instantaneous to 4.5 s

7 user-selectable time delaysinstantaneous to 4.5 s

1 adjustable threshold instantaneous to 4.5 s

- -

- instantaneous 1 adjustable threshold instantaneous to 4.5 s

9 user-selectable time delays instantaneous to 4.5 s

1 adjustable threshold/channel instantaneous to 5 s

- - - - 1 adjustable threshold/channel instantaneous to 5 s

b b (9) b b b

b b b - -- b b b b

- - - - b

- on bargraph b - b

- - b - b(10)

b b b b b

b b b b -b b b b -- - b except RHUs - b

- - b except RHUs - b

See catalogue LVPED208009EN See catalogue LVPED208009EN

See catalogue LVPED208009EN

See catalogue LVPED208009EN See catalogue LVPED208009EN

b b b b b

b b b b b

(6) Depending on the type of wiring (optimum continuity of service or optimum safety).(7) See catalogue LVPED208009EN.

(8) On a bargraph(9) No voltage presence relay.(10) With actuation of contacts only.

+

0594

84-�

9_SE

Protection relays (2)

RH10 RH21All Vigirex products are type A (1) devices, also covering the requirements of type AC devices.

PB

�004

35-�

8_S

E

PB

�004

30-�

9_S

E

PB

�004

33-�

8_S

E

PB

�004

3�-�

9_S

E

FunctionsProtection b b

Local indications b b

Remote indications (hard-wired) - -Remote indications (via communication) - -Display of measurements - -WiringOptimum continuity of service b b

Optimum safety (failsafe) b b

MountingDIN rail b b

Front-panel mount b b

Rated operational voltage� DC voltage range from �2 to 48 V b b

� DC voltage range from 24 to �30 V and AC 48 V - -6 AC voltage ranges from �2 to 525 V b b

4 AC voltage ranges from 48 to 4�5 V - -ThresholdsFault (IDn) 1 fixed instantaneous threshold

choose from 0.03 A to � A2 user-selectable thresholds 0.03 A or 0.3 A

Alarm - -

Pre-alarm - -

Time delaysFault Instantaneous 1 user-selectable time delay

instantaneous or 0.06 s for IDn = 0.3 A

Alarm - -

Pre-alarm - -

Display and indicationsVoltage presence (LED and/or relay) (6) b b

Threshold overrun fault (LED) b b

alarm (LED and relay) - -pre-alarm (LED and relay) - -

Leakage current (digital) - -Settings (digital) - -Test with or without actuation of output contactsLocal b b

Remote (hard-wired) b b

Remote (hard-wired for several relays) b b

Remote (via communication) - -CommunicationSuitable for supervision (internal bus) - -Characteristics

See catalogue LVPED208009EN See catalogue LVPED208009EN

SensorsMerlin Gerin A, OA, E toroids (7) up to 630 A b b

Merlin Gerin rectangular sensors up to 3200 A b b

(1) Type A relay up to IDn = 5 A.(2) Relay with output contact requiring local, manual reset after fault clearance.(3) Relay with output contact that automatically resets after fault clearance.

(4) Mandatory with an RMH (multiplexing for the 12 toroids).(5) Mandatory with an RM12T (multiplexing for the 12 toroids).

67

Page 70: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

Notes

68

Page 71: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover
Page 72: Electrical distribution Circuit protection and control ... · Manual source-changeover systems Interpact INS/INV40 A to 630 A Compact NS/NSX 00 A to 630 A A-46 Manual source-changeover

03-20�0LVPED2080�3EN

AR

T834

5�9

© 2

0�0

- Sch

neid

er E

lect

ric -

All

right

s re

serv

ed.

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.