effi+ dx - energie transfert thermique...• en 1886 - ventilation for buildings – air handling...

34
Double flow heat pump with extraction and recovery module ENVIRONMENTAL CLIMATE CONTROL EQUIPMENT & SOLUTIONS www.ett.fr EFFI+ DX

Upload: others

Post on 18-Mar-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

Double fl ow heat pump with extraction and recovery module

ENVIRONMENTALCLIMATE CONTROLEQUIPMENT & SOLUTIONS

www.ett.fr

EFFI+ DX

Page 2: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

2

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

■ General description ....................................................................................................................................... 03■ Operating principles ...................................................................................................................................... 04■ Description ........................................................................................................................................................... 05■ Control description ......................................................................................................................................... 07■ Main options ....................................................................................................................................................... 08

Technical features■ Type 106 – 108 – 109 – 110 – 112 ............................................................................................................. 09■ Type 213 – 215 – 217 – 218 – 220 – 222 ................................................................................................ 13■ Type 323 – 326 – 330 – 333 .......................................................................................................................... 17

Dimensions and connections■ Type 106 – 108 – 109 – 110 – 112 ............................................................................................................. 10■ Type 213 – 215 – 217 – 218 – 220 – 222 ................................................................................................ 14■ Type 323 – 326 – 330 – 333 .......................................................................................................................... 18

Arrangements■ Arrangements .................................................................................................................................................... 21

Auxiliaries■ Hot water coils ................................................................................................................................................... 22■ Electric heaters .................................................................................................................................................. 24

Options weight■ Options weight .................................................................................................................................................. 25

Sound level■ Sound level........................................................................................................................................................... 26

Installation accessories■ Roof curbs ............................................................................................................................................................. 28■ Feet ........................................................................................................................................................................... 32

Probes connection scheme■ Probes connection scheme ..................................................................................................................... 33

C O N T E N T S

E N E R G I ET R A N S F E R TT H E R M I Q U E

Page 3: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

3

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

General description

• Machinery Directive 2006/42/EC - Operator's safety• Low Voltage Directive 2006/95/EC - Electricity• EMC Directive 2004/108/EC - Electromagnetic

Compatibility• 2009/142/EC Directive - Gas Appliances

• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance

• EN 60204-1 - Safety of machinery – Electrical equipment of machines

Moreover, each unit is delivered with an EC certifi cate of conformity and complies with the standards listed below:

All units are checked and tested at the factory prior to shipment. A control certifi cate is issued for each unit.ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate 1994/2016f).

We placed ease of operation at the heart of our units design:

• The separate technical section facilitates service and control of the unit and allows measurement and adjustment during operation.

• The BEST controller is specifi cally designed for this application. It allows great fl exibility, thus optimum performance of the ETT unit through a user-friendly interface, be it local or remote (with remote display, PC or BMS).

The ETT packaged unit is delivered ready to operate. Its full aluminium structure (frame & casing) ensures an excellent corrosion protection (20-year anti-corrosion guarantee).The ETT unit can be installed either at ground level or on a roof.ECODESIGN involves DECONSTRUCTION: ETT units are 98% recyclable (re-use and recycling rates based on EFFI+ 220).

20-year guarantee against corrosion

2222222222222222222222222222222222220000000000000000000000000000000000000000000--------------------yyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaarrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrr gggggggggggggggggggggggggggggggggggggggggggggguuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaarrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrraaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaannnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnttttttttttttttttttttttttttttttttttttteeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaggggggggggggggggggggggggggggggggggggggggggggggggaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiinnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnsssssssssssssssssssssssssssssssssssssssttttttttttttttttttttttttttttttttttttt cccccccccccccccccccccccccccccccccccccccccccoooooooooooooooooooooooooooooooooooooooooooooorrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrooooooooooooooooooooooooooooooooooooooooooooosssssssssssssssssssssssssssssssssssssssiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiooooooooooooooooooooooooooooooooooooooooooooooooonnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn

Our technical choices have several impacts on the environment

• Legal and regulatory framework:- In accordance with Directive 2008/98/EC on waste, clause 26: "The polluter-pays principle is a

guiding principle at European and international levels. The waste producer and the waste holder should manage the waste in a way that guarantees a high level of protection of the environment and human health.", ETT is a member of "Eco-systèmes Pro".

- In accordance with articles 5.3, 5.4 and 11 of Regulation (EC) No. 303/2008, ETT holds a certifi cate of capability to handle refrigerants (no. 637).

• Aluminium: a good choice for the planet!- Aluminium is endlessly 100% recyclable.- Recycling covers over 30% of aluminium needs.

• Low polluting ETT manufacturing process:- Selective sorting, waste recovery, 60% of waste is recycled.- No paint on casings, no use of solvent.- ISO 14001 Certifi cation (Environmental Management System).

• Consumables: effi cient waste management:- Filtration: ETT units include "ecodesigned" air fi lters (selective sorting: frame - grille - media)

Page 4: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

4

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

The DX module can operate:> In all recycling mode during vacancy periods or

when no hygienic fresh air is required> In air conditioning/heat pump mode or in Free

Cooling mode with max. 50% fresh air compared to rated air fl ow rate

The unit operates as an air-to-air reversible heat pump coupled with a vertical double fl ow rotary heat exchanger on the fresh air/exhaust air section:> Source: outside air> Treated fl uid: inside air

Operating principles

_+ +

1

32

4

+_

1

32

4

1

32

4

1

32

4

1 Fresh air 2 Return air 3 Supply air 4 Exhaust air

Heating mode

Cooling mode

Free Cooling mode

Recycling mode

Heating mode: In winter, comfort temperature is maintained thanks to the thermodynamic system and the auxiliaries (optional), with heat recovery on exhaust air.

Cooling mode: In summer, comfort temperature is maintained thanks to the thermodynamic system with energy recovery on exhaust air.

Free Cooling mode: In mid-season, comfort temperature is maintained using in priority the difference between outside air and inside air to cool the building.

Free Cooling allows considerable savings by delaying the use of thermodynamics.

Recycling mode: Destratifi cation of the volume recycled, when return air temperature is signifi cantly higher than room temperature.

Page 5: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

5

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Description

The ETT packaged unit comprises 4 different sections:

1 The heat recovery section adjusts the hygienic fresh air fl ow rate as required, while ensuring heat transfer with the exhaust air fl ow.

2 The external section allows thermal exchanges with outside air.

3 The internal section ensures air change and air treatment.

4 The separate technical section houses the refrigeration components, the electrical board and the control components.

■ Rigid, compact and lightweight packaged unit, perfectly weather-resistant, with a 20-year anti corrosion guarantee on casing.

■ Watertight floor with drainage outlets around the unit, connected to rubber siphons.

■ Aluminium vertical panels and roof, mounted on aluminium frame.

■ Access through large “easy to remove” panels. Panels are closed with square locks. Doors tightness is ensured by a flexible gasket under compression, providing an ideal elasticity day after day (French standard NF EN 1886).

Optimised defrosting:

Defrosting principle:ü The condensation of humidity produces frost on the coil.ü The concerned refrigeration system and propeller fan stop operating

(simultaneous defrosting cycles are banned).ü The refrigeration system 4-way valve reverses: during defrosting, the

coil operates as a condenser.ü Supply air flows downwards.ü The coil is dried.ü The other refrigeration circuit continues to operate normally.

Aluminium frame and casing:

■ High performance plug fans on supply and exhaust air to avoid losses due to pulley-belt transmissions, thus improving unit energy efficiency.

■ Inner acoustic and thermal insulation on panels using 50 mm M0 glass wool, in accordance with French Public Access Buildings regulations (Article CH36).

■ Floor sound and thermal insulation using 100 mm M0 rock wool with double skin.

■ 2-damper mixing box including a motorised fresh air damper with bird proof grid and a return air damper to ensure the desired proportions and optimise Free Cooling phases. Dampers have extruded aluminium blades with low pressure drop thanks to their plane wing profile and flexible gasket which ensures excellent air tightness. The damper frame is made of tightness class 3 aluminium.

Page 6: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

6

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Description

■ Refrigeration circuits compliant with European directive on pressure equipment (PED 97/23/EC).

■ R410A refrigerant. ■ Direct expansion internal exchanger,

made with copper pipes and aluminium fins and frame, coupled with a thermostatic expansion valve in heat pump mode. These nested exchangers improve SCOP and SEER in partial load. In addition, the air flow rate can be adjusted according to the required capacity, reducing significantly ventilation energy consumption (VDP operation).

■ Direct expansion external exchanger, made with copper pipes and aluminium fins and frame, coupled with a thermostatic expansion valve in heat pump mode. External exchangers angled position and the separation by refrigerant circuit and by compressor ensure quick and efficient defrosting. Exchangers can be accessed via an access hatch for easy cleaning.

■ Optimised defrosting thanks to the new design of the external section and the integration of a Ø 800 propeller fan with supply air downwards (optimised for ecodesign).

■ Tandem hybrid circuits, operation in part load reduces significantly the number of defrost cycles and their duration.

■ 2 expansion valves per circuit and per refrigeration cycle to optimise the efficiency of each evaporator cycle and reduce energy consumption.

■ High efficiency aluminium rotary exchanger (minimum 70 % efficiency) with integrated purge sector (1).

■ Filter assembly with easy-to-remove ecodesign filters - 98 mm pleated media, efficiency 95% ASHRAE gravimetric (G4) for longer lifetime and lower pressure drops, pressure switch for fouling control.

■ Temperature and pressure probes for recovery module operation.

■ Additional controller ensuring optimum performance of the recovery module. The module controller and the ROOFTOP unit controller are wired so that the flow and capacity can be adjusted according to the room air needed.

■ Pressure relief gravity damper to isolate the exhaust section in case of exhaust fan shutdown.

■ On-floor tracer to prevent condensates from freezing on exhaust air side in case of low outside temperature.

■ Plug fans on supply air and exhaust air. This technology avoids losses due to pulley-belt transmissions.

■ Electronically commutated motors allow: ü reduced kickback during start-up when textile ducts are used (soft start mode); ü maximum rotation speed regulation according to pressure drops on site; ü reduced speed operation in Free Cooling mode to save energy (VDP operation).

■ Independent refrigeration circuit: each refrigeration circuit has a propeller fan to ventilate the exchanger. The propeller fan consists of a ferrule, a high energy performance 5-blade aluminium propeller coupled with an IP54 motor with reinforced sealing, and a zinc-plated steel fan guard, with cataphoresis protection. The fan assembly is perfectly weather resistant. Thanks to this new designed fan, exchangers air flow rate increases by up to 15% compared to standard fans, while keeping the same power input. The new blades profile results in lower compressors consumption thanks to lower HP and higher LP in the different operation modes.

■ Anti-acid filter drier. ■ HP and LP switches. ■ Cycle reversal valve.

(1) The rotary exchanger integrated to this unit is manufactured by ENVENTUS, a company which adheres to the Eurovent Certita Certifi cation Programm on Air-to-Air Regenerative Heat Exchangers. You can check the validity of certifi ed data on www.eurovent-certifi cation.com or using www.certifl ash.com.

Energy and thermodynamic assembly:

Air assembly:

Page 7: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

7

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Control description

■ Electrical board compliant with European standards EN 15-100 and EN 60204-01, including: ü ETT controller with display. ü Power switch with lockable external handle for full load cut-off. Connection using standard universal cable. Optional copper/aluminium connection boxes. ü 400-230-24 volts transformer for regulation and control circuits. ü Faults synthesis with pending dry contact on terminal. ü Numbered terminal blocks with disconnecting terminals for remote controls and transfers. ü Terminal block for compressors load shedding. ü Internal wiring with numbered ferrules at both extremities. ü Ik3 breaking capacity of basis 10 kA. ü All components protected by circuit breakers. ü LV distribution rated voltage compliant with French standards, i.e. rated voltage of 230/400V. French standards also set minimum and maximum acceptable values at the user supply point (average value for 10 lm) within a -10%/+10% range from rated values and maximum acceptable value of the voltage drop gradient to 2%. The voltage drop gradient represents the additional voltage drop created on a network point if 1 KW single-phase is added on this point.

■ CTN type temperature probes. Their accuracy and liability have been tested and validated both at the factory and on site.

■ One or more BEST type controllers (Building Energy Saving Technology) especially developed by ETT for this range of units. Programs are updated annually in order to add functions requested for some applications and to optimise units electricity consumption.

The microprocessor, memory and controllers size are adapted to the chosen applications and options by integrating a program set-up in the factory out of 160 possible confi gurations. The controller is in a plastic box which guarantees a high mechanical protection and reduces electrostatic shock threats.Among other functions, the controller includes: ü On/Off with remote contact or vacancy contact. ü On/Off according to programmed schedule (2 time slots per day). ü Fault synthesis via dry contact for transfer on customer system. ü 2 setpoints (cooling and heating) according to the European directive 2002/91/EC. ü Security management (freezestat, smoke detector, HP switch, etc.) and faults management. ü Optimisation and equalisation of compressors operating time.

ü Flash-type analogue and economical management of alternate defrostings for each refrigeration circuit using frost detection and end of defrosting through analogue probes, stop of the concerned exchanger’s ventilation, coil drying and starting of a new heating cycle in heat pump mode. External coils angled position and downward supply air flow help blowing water away from the coil, ensuring efficient defrosting. Concerning multi-circuits units, comfort and energy savings are ensured by banning simultaneous defrostings. ü Economiser management (Free Cooling) through inside temperature analysis and comparison between return air and outside air temperatures. ü Compressors stages management giving priority to the highest COP and EER in part load. ü Frost protection. ü Auxiliaries management (possibility of banning according to outside temperature). ü Night energy consumption management with compressors' use limitation (Night Cooling). ü Written faults history (no code needed) with time and outside temperature display. ü Operating hours counting (unit, compressors and auxiliaries). ü Air quality control with CO2 probe to optimise fresh air quantities to introduce, therefore limiting energy consumption.

Electrical assembly: Control assembly:

Page 8: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

8

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Main options

Frame - Casing ■ Unit with Vertical (V) or Lateral (L) supply air ■ Motorised external damper for supply air (2006/42/EC Directive) ■ Double skin in internal section, 13/10 AG, 50 mm

Acoustics ■ Technical section acoustic insulation using STOPFLAM fl exible fi re-proof polyurethane foam ■ Exhaust air box sound insulation ■ Fresh air cowl sound insulation ■ Compressors acoustic jackets

Air handling ■ Filtration pressure gauges ■ Analog air fl ow controller (AFC), air fl ow rate indication and measurement ■ Filters fouling analogue control (FFAC) ■ Self-contained smoke detector backed-up or not ■ Epoxy coating on the rotary heat exchanger + fans & vinyl coating on exchangers ■ Supply air fan available pressure 400 Pa max. ■ G4 refi llable fi lters, 98 mm thick ■ F7 or F9 opacimetric fi lters, 98 mm thick ■ G4 + F7 or F9 double fi lters (48 + 48 mm) ■ High pressure supply air fans kit available in case of high available pressure.

Thermodynamics ■ HP and LP pressure gauges ■ Electronic expansion valves ■ Cooling operation only ■ Refrigerant leak detection aid

Thermal exchangers ■ 2-stage electric heater ■ Triac ■ 2-row hot water coil with analogue freezestat ■ Progressive 3-way valve with analog freezestat mounted on hot water ■ Mounted stop valve + TA regulating valve on outlet

Electricity ■ Unit global energy metering

Laying ■ Aluminium adjustable connection roof curb ■ Aluminium adjustable adaptation roof curb ■ Aluminium adjustable ventilated roof curb ■ Aluminium ventilated adaptation roof curb ■ Aluminium plenum for return air and supply air ■ 200 or 400 mm aluminium feet

Control ■ Min. fresh air control using turret contacts (2 max.) ■ Year-round operation (compressor cooling mode authorisation with -5°C < outside temp. < +15°C) ■ Free Cooling banning based on specifi c humidity comparison ■ Hygrometry probe (for external humidifi er control)

Page 9: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

9

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Technical features Type 106 - 108 - 109110 - 112

NAME Unit 106 108 109 110 112

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 6500 8000 9000 10000 12000

Min. air fl ow rate m3/h 4500 6000 7000 8000 10000

Max. air fl ow rate m3/h 12000 12000 12000 12000 12000

COOLING MODE (1)

Net cooling capacity kW 32.2 40.6 43.5 48.8 54.9

Net absorbed electrical power kW 9.6 13.5 14.5 17.4 21.0

Net EER kW/kW 3.37 3.01 3.01 2.81 2.61

Sensible/Total capacity ratio 0.82 0.82 0.81 0.80 0.79

HEATING MODE (1)

Net heating capacity kW 32.6 41.5 44.9 51.2 58.2

Net absorbed electrical power kW 8.5 11.1 12.1 14.3 16.8

Net COP kW/kW 3.84 3.75 3.7 3.59 3.47

Power stages 2

ROTA

RY E

XCHA

NGER

EURO

VENT

CER

TIFIE

D (5

)

Recovery capacity in Cooling mode (1) 50% exhaust air kW 6.8 8.1 9.0 9.7 11.2

Thermal recovery effi ciency on fresh air % 80.8 78.1 76.5 75.1 72.4

Recovery capacity in Heating mode (1) 50% exhaust air kW 11.5 13.8 15.2 16.5 19.2

Thermal recovery effi ciency on fresh air % 77.0 74.4 72.9 71.4 68.8

Rotary exchanger rated electrical power kW 0.2

ELEC

TRIC

AL

CONN

ECTIO

N Maximum absorbed electrical power (2) kW 14.5 19.7 20.8 24.2 28.5

Total installed electrical power (2) (4) kW 21.8 26.4 27.0 29.8 33.0

Rated current (2) A 38 46 50 54 61

Starting current (2) A 92 133 135 164 178

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 1.0 1.2 1.4 1.7 2.3

SFPv (EN 13779) kW/(m3/s) 0.53 0.55 0.58 0.61 0.70

EXHAUST AIR

Absorbed electrical power (6) kW 0.60 0.80 1.00 1.30 1.56

SFPv (EN 13779) kW/(m3/s) 0.66 0.72 0.80 0.94 0.90

GEN

ERA

L

EUROVENT Energy Effi ciency class in Heating mode A A A A A

Sound power level on supply air side (EUROVENT certifi ed) (1) dB(A) 74 77 80 82 87

Outside sound power level (EUROVENT certifi ed) (1) dB(A) 79 84 86 88 91

Resulting outside sound pressure at 10 m,ref. 2x10-5 in free fi eld (1) dB(A) 51 56 58 60 63

Filters effi ciency G4

Filters dimensions & number mm (4x) 595*498*98/(2x) 595*287*98(2x) 595*595*98

Max. outside operating temperature in Cooling mode °C 45

Min. outside operating temperature in Cooling mode °C 15

Min. outside operating temperature in Heating mode °C -15

Min. internal coil inlet temperature in Heating/Cooling mode °C 12/18

Unit weight without options (3) kg 906 906 906 926 936

Connection roof curb weight kg 90

Standard ventilated roof curb weight kg 130

(1) EUROVENT conditions according to NF EN 14511 (October 2013)Cooling mode: 35°C DB - 7°C DB 47%/19°C WBHeating mode: 7°C DB - 20°C DB 60%/15°C WBExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances(3) Weight for 400 Pa available. For hot water coils and electric heaters weight, please consult "Auxiliaries". For installation accessories weight, please consult "Installation accessories".

400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection(5) The rotary exchanger integrated to this unit is manufactured by ENVENTUS, a company which adheres to the Eurovent Certita Certifi cation Programm on Air-to-Air Regenerative Heat Exchangers.You can check the validity of certifi ed data on www.eurovent-certifi cation.com or using www.certifl ash.com.(6) For 100 Pa of available static pressure: 50% exhaust air

Page 10: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

10

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Dimensions and connections

Length Width HeightCasing dimensions 4185 mm 1680 mm 1625 mm

Transport overall dimensions 4235 mm 1730 mm 1785 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota:Nota: Fresh air cowls laying shall be made by the installer.

Type 106 - 108 - 109110 - 112

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Page 11: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

11

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Length Width HeightCasing dimensions 4185 mm 1680 mm 1625 mm

Transport overall dimensions 4235 mm 1730 mm 1785 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

(propeller fan not shown) (propeller fan not shown)

Nota:Nota: Fresh air cowls laying shall be made by the installer.

Dimensions and connections Type 106 - 108 - 109110 - 112

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Page 12: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

12

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Length Width HeightCasing dimensions 4185 mm 1680 mm 1625 mm

Transport overall dimensions 4235 mm 1855 mm 1785 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

INSTALLER SUPPORT

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

Dimensions and connections Type 106 - 108 - 109110 - 112

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Page 13: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

13

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Technical features Type 213 - 215 - 217218 - 220 - 222

NAME Unit 213 215 217 218 220 222

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 13000 15000 17000 18000 20000 22000

Min. air fl ow rate m3/h 10000 12000 14000 15000 19000 19000

Max. air fl ow rate m3/h 23000 23000 23000 23000 23000 23000

COOLING MODE (1)

Net cooling capacity kW 58.9 68.9 79.2 83.7 93.6 102.2

Net absorbed electrical power kW 17.6 22.0 27.2 29.8 35.9 41.7

Net EER kW/kW 3.34 3.13 2.91 2.81 2.61 2.45

Sensible/Total capacity ratio 0.88 0.86 0.81 0.83 0.81 0.77

HEATING MODE (1)

Net heating capacity kW 61.4 72.4 85.3 91.4 104 114

Net absorbed electrical power kW 15.62 19.05 23.31 25.46 30.32 33.43

Net COP kW/kW 3.93 3.8 3.66 3.59 3.43 3.41

Power stages 4

ROTA

RY E

XCHA

NGER

EURO

VENT

CER

TIFIE

D (5

)

Recovery capacity in Cooling mode (1) 50% exhaust air kW 12.8 14.3 15.9 16.6 17.8 19.2

Thermal recovery effi ciency on fresh air % 75.7 73.7 71.8 70.9 69.2 67.5

Recovery capacity in Heating mode (1) 50% exhaust air kW 21.7 24.3 26.9 28.2 30.3 32.5

Thermal recovery effi ciency on fresh air % 72.1 70.1 68.2 67.3 65.5 63.7

Rotary exchanger rated electrical power kW 0.2

ELEC

TRIC

AL

CONN

ECTIO

N Maximum absorbed electrical power (2) kW 26.6 32.0 38.3 41.3 49.4 56.5

Total installed electrical power (2) (4) kW 40.8 45.5 50.7 53.0 61.8 67.8

Rated current (2) A 69 77 89 94 106 117

Starting current (2) A 163 192 204 238 278 289

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 2.0 2.3 2.8 3.0 3.5 4.1

SFPv (EN 13779) kW/(m3/s) 0.55 0.56 0.58 0.60 0.63 0.68

EXHAUST AIR

Absorbed electrical power (6) kW 1.20 1.40 1.70 1.90 2.30 2.70

SFPv (EN 13779) kW/(m3/s) 0.66 0.67 0.72 0.76 0.83 0.88

GEN

ERA

L

EUROVENT Energy Effi ciency class in Heating mode A A A A A A

Sound power level on supply air side (EUROVENT certifi ed) (1) dB(A) 78 80 82 83 86 88

Outside sound power level (EUROVENT certifi ed) (1) dB(A) 81 85 88 89 92 94

Resulting outside sound pressure at 10m,ref. 2x10-5 in free fi eld (1) dB(A) 53 57 60 61 64 66

Filters effi ciency G4

Filters dimensions & number mm (6x) 595*498*98/(3x) 595*287*98(3x) 595*595*98

Max. outside operating temperature in Cooling mode °C 45

Min. outside operating temperature in Cooling mode °C 15

Min. outside operating temperature in Heating mode °C -15

Min. internal coil inlet temperature in Heating/Cooling mode °C 12/18

Unit weight without options (3) kg 1455 1485 1485 1485 1515 1575

Connection roof curb weight kg 122

Standard ventilated roof curb weight kg 215

(1) EUROVENT conditions according to NF EN 14511 (October 2013)Cooling mode: 35°C DB - 7°C DB 47%/19°C WBHeating mode: 7°C DB - 20°C DB 60%/15°C WBExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances(3) Weight for 400 Pa available. For hot water coils and electric heaters weight, please consult "Auxiliaries". For installation accessories weight, please consult "Installation accessories".

400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection(5) The rotary exchanger integrated to this unit is manufactured by ENVENTUS, a company which adheres to the Eurovent Certita Certifi cation Programm on Air-to-Air Regenerative Heat Exchangers.You can check the validity of certifi ed data on www.eurovent-certifi cation.com or using www.certifl ash.com.(6) For 100 Pa of available static pressure: 50% exhaust air

Page 14: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

14

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Dimensions and connections

Length Width HeightCasing dimensions 6010 mm 2200 mm 1690 mm

Transport overall dimensions 6060 mm 2250 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota:Nota: Fresh air cowls laying shall be made by the installer.

Type 213 - 215 - 217218 - 220 - 222

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 15: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

15

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Length Width HeightCasing dimensions 6010 mm 2200 mm 1690 mm

Transport overall dimensions 6060 mm 2250 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

(propeller fan not shown)(propeller fan not shown)

Nota:Nota: Fresh air cowls laying shall be made by the installer.

Dimensions and connections Type 213 - 215 - 217218 - 220 - 222

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 16: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

16

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Length Width HeightCasing dimensions 6010 mm 2200 mm 1690 mm

Transport overall dimensions 6060 mm 2375 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

INSTALLER SUPPORT

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

Dimensions and connections Type 213 - 215 - 217218 - 220 - 222

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 17: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

17

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Technical features Type 323 - 326 - 330 - 333

NAME Unit 323 326 330 333

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 23000 26000 30000 33000

Min. air fl ow rate m3/h 18000 22000 27000 27000

Max. air fl ow rate m3/h 35000 35000 35000 35000

COOLING MODE (1)

Net cooling capacity kW 101.7 116.6 135.6 152

Net absorbed electrical power kW 32.9 40.2 51.6 62.6

Net EER kW/kW 3.09 2.9 2.63 2.43

Sensible/Total capacity ratio 0.87 0.82 0.80 0.77

HEATING MODE (1)

Net heating capacity kW 107.9 125.9 150.8 170.2

Net absorbed electrical power kW 27.81 34.03 43.33 49.91

Net COP kW/kW 3.88 3.7 3.48 3.41

Power stages 6

ROTA

RY E

XCHA

NGER

EURO

VENT

CER

TIFIE

D (5

)

Recovery capacity in Cooling mode (1) 50% exhaust air kW 21.9 23.9 26.7 28.8

Thermal recovery effi ciency on fresh air % 73.1 71.3 68.9 67.1

Recovery capacity in Heating mode (1) 50% exhaust air kW 37.2 40.7 45.4 48.2

Thermal recovery effi ciency on fresh air % 69.5 67.7 65.2 63.4

Rotary exchanger rated electrical power kW 0.4

ELEC

TRIC

AL

CONN

ECTIO

N Maximum absorbed electrical power (2) kW 48.7 56.7 69.1 84.8

Total installed electrical power (2) (4) kW 68.6 75.0 90.3 104.5

Rated current (2) A 116 130 158 177

Starting current (2) A 214 244 302 349

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 3.8 4.4 5.2 5.9

SFPv (EN 13779) kW/(m3/s) 0.60 0.60 0.62 0.65

EXHAUST AIR

Absorbed electrical power (6) kW 2.40 3.00 3.40 3.90

SFPv (EN 13779) kW/(m3/s) 0.75 0.83 0.82 0.85

GEN

ERA

L

EUROVENT Energy Effi ciency class in Heating mode A A A A

Sound power level on supply air side (EUROVENT certifi ed) (1) dB(A) 80 82 84 86

Outside sound power level (EUROVENT certifi ed) (1) dB(A) 86 90 93 95

Resulting outside sound pressure at 10m,ref. 2x10-5 in free fi eld (1) dB(A) 58 62 65 67

Filters effi ciency G4

Filters dimensions & number mm (6x) 595*595*98/(6x) 595*498*98(3x) 595*287*98

Max. outside operating temperature in Cooling mode °C 45

Min. outside operating temperature in Cooling mode °C 15

Min. outside operating temperature in Heating mode °C -15

Min. internal coil inlet temperature in Heating/Cooling mode °C 12/18

Unit weight without options (3) kg 2124 2124 2191 2281

Connection roof curb weight kg 160

Standard ventilated roof curb weight kg 230

(1) EUROVENT conditions according to NF EN 14511 (October 2013)Cooling mode: 35°C DB - 7°C DB 47%/19°C WBHeating mode: 7°C DB - 20°C DB 60%/15°C WBExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances(3) Weight for 400 Pa available. For hot water coils and electric heaters weight, please consult "Auxiliaries". For installation accessories weight, please consult "Installation accessories".

400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection(5) The rotary exchanger integrated to this unit is manufactured by ENVENTUS, a company which adheres to the Eurovent Certita Certifi cation Programm on Air-to-Air Regenerative Heat Exchangers.You can check the validity of certifi ed data on www.eurovent-certifi cation.com or using www.certifl ash.com.(6) For 100 Pa of available static pressure: 50% exhaust air

Page 18: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

18

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Dimensions and connections

Length Width HeightCasing dimensions 7970 mm 2200 mm 2130 mm

Transport overall dimensions 8020 mm 2250 mm 2180 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota:Nota: Fresh air cowls laying shall be made by the installer.

Exhaust air sec� on dimensions apply for EFFI+ 330/333 only.

Exhaust air sec� on dimensions apply for EFFI+ 330/333 only.

Type 323 - 326 - 330 - 333

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 19: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

19

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Length Width HeightCasing dimensions 7970 mm 2200 mm 2130 mm

Transport overall dimensions 8020 mm 2250 mm 2180 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

Nota:Nota: Fresh air cowls laying shall be made by the installer.

Exhaust air sec� on dimensions apply for EFFI+ 330/333 only.

Exhaust air sec� on dimensions apply for EFFI+ 330/333 only.

Dimensions and connections Type 323 - 326 - 330 - 333

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 20: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

20

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Length Width HeightCasing dimensions 7970 mm 2200 mm 1690 mm

Transport overall dimensions 8020 mm 2375 mm 2180 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

Exhaust air sec� on dimensions apply for EFFI+ 330/333 only.

Exhaust air sec� on dimensions apply for EFFI+ 330/333 only.

INSTALLER SUPPORT

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

Dimensions and connections Type 323 - 326 - 330 - 333

* Exhaust and fresh air must be separated by 8 m minimum.

1 Fresh air2 Return air3 Supply air4 Exhaust airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 21: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

21

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Arrangement 1.1

Arrangement 2.1

Arrangement 3.1

1

2

2

2

3

3

Installation on feet (400 mm minimum) or customer frame. Feet are optional. A supply air damper is necessary for units bigger than 10,000 m3/h in Public Access Buildings.

Opposite the technical section (with at least 400 mm)

4

4

4

3

Installation on roof curb or customer frame on roof.

Arrangements

1

1

SUPPLY AIR downwards

SUPPLY AIR on side

SUPPLY AIR upwards

1 Fresh air 2 Return air 3 Supply air 4 Exhaust air

Page 22: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

22

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Top view

Dimensions Unit 106 - 108 - 109110 - 112

213 - 215 - 217218 - 220 - 222 323 - 326 - 330 - 333

A mm 795 1250 1300

B mm 185 200 200C mm 95 135 135Ø mm 33/42 40/49 40/49

Auxiliary: Hot water coils

SCHEMATIC DIAGRAM

CONNECTION

Principle

Air fl ow way

Op� on

+ / -

BE

C

Ø de raccordement

A B

C

Connec� on Ø

Hot w

ater

coi

l

Page 23: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

23

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

CAPACITIES

With +10°C air inlet temperature on coils

Optional: stop valve on outlet and TA regulating valve on inlet

Unit 106 108 109 110 112 213 215 217 218 220 222

Water supply 90/70°C

Capacity kW 78 90 98 105 119 158 175 190 198 212 226

Flow rate m3/h 3.4 4 4.3 4.6 5.2 7 7.7 8.4 8.7 9.3 9.9

3WV + coilpressure drop mWC 0.7 0.95 1 1.2 1.6 4.2 5.2 6.2 6.5 7.5 8.1

Water supply 80/60°C

Capacity kW 66 76 82 88 99 134 148 162 168 180 192

Flow rate m3/h 2.9 3.3 3.6 3.9 4.4 5.9 6.5 7.1 7.4 7.9 8.4

3WV + coilpressure drop mWC 0.5 0.71 0.75 0.9 1.05 3.1 3.9 4.6 4.9 5.5 6.1

Unit 323 326 330 333

Water supply 90/70°C

Capacity kW 177 193 212 226

Flow rate m3/h 7.8 8.4 9.3 9.9

3WV + coilpressure drop mWC 5.3 6.2 7.5 8.1

Water supply 80/60°C

Capacity kW 151 164 180 192

Flow rate m3/h 6.6 7.2 7.9 8.4

3WV + coilpressure drop mWC 4 4.7 5.5 6.2

Unit 106 108 109 110 112 213 215 217 218 220 222

Water supply 90/70°C

Stop and TA valves pressure drop(opened by 3 turns)

mWC 1.4 1.9 2.1 2.5 3.1 3.1 3.8 4.5 4.8 5.6 6.2

Water supply 80/60°C

Stop and TA valves pressure drop(opened by 3 turns)

mWC 1.0 1.3 1.5 1.8 2.2 2.3 2.7 3.3 3.5 4.0 4.5

Unit 323 326 330 333

Water supply 90/70°C

Stop and TA valves pressure drop(opened by 3 turns)

mWC 3.9 4.6 5.5 6.3

Water supply 80/60°C

Stop and TA valves pressure drop(opened by 3 turns)

mWC 2.8 3.3 4.0 4.5

Auxiliary: Hot water coils

Page 24: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

24

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Total capacity

(kW)Current

(A) 1st stage 2nd stage 106 108 109 110 112 213 215 217 218 220 222 323 326 330 333 Weight (kg)

9 13.0 3 6 • • • • • • • • • • • • • • • 9 12 17.3 3 9 • • • • • • • • • • • • • • • 915 21.7 6 9 • • • • • • • • • • • • • • • 1018 26.0 6 12 • • • • • • • • • • • • • • • 1121 30.3 6 15 • • • • • • • • • • • • • • • 824 34.6 9 15 • • • • • • • • • • • • • • • 1227 39.0 9 18 • • • • • • • • • • • • • • • 1530 43.3 12 18 • • • • • • • • • • 1633 47.6 12 21 • • • • • • • • • • 1536 52.0 15 21 • • • • • • • • • • 1639 56.3 15 24 • • • • • • • • • • 1642 60.6 18 24 • • • • • • • • • • 1945 65.0 18 27 • • • • • • • • • • 2048 69.3 21 27 • • • • 1954 77.9 21 33 • • • • 2260 86.6 21 39 • • • • 2363 90.9 27 36 • • • • 26

Auxiliary: Electric heaters

AVAILABLE CAPACITIES (in kW)

SCHEMATIC DIAGRAM

+ / -

Batteries électriquesElectric heaters

An additional coil can be mounted in the supply air duct or on the fresh air inlet for higher performances.Please consult us.

Nota:

Page 25: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

25

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Options weight (kg)

Options 106 108 109 110 112 213 215 217 218 220 222 323 326 330 333

Frame - Casing

Unit with vertical (V) or lateral (L) supply air 55 75 105

Motorised external damper for supply air (2006/42/EC Directive) 10 15 20

Dampers removal -20 -42 -51

50 mm double skin 40 60 80

Fresh air cowl 9 19 23

Acoustics

Technical section soundproofi ng 2.3 3 4.5

Compressors acoustic jackets 2 4 6

Air handling

Pressure relief gravity dampers(return air below) 22 32 39

Thermal exchangers

2-row hot water coil with 3WVwith water 40 60 60

Year-round kit 1.4 2.8 4.2

Laying

Aluminium ventilated roof curb 130 215 230

Aluminium connection roof curb 90 135 160

Roof curb side insulation 7 9 11

Page 26: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

26

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Return air side: Available pressure 100 Pa 50% exhaust air

FREQUENCYBANDHz ► 63 125 250 500 1000 2000 4000 8000

FanOverall levelLw (dB(A))FLOW RATE

(m3/h) ▼

106 6500 32.9 52.1 60.0 66.3 70.5 67.8 62.4 57.9 74.0108 8000 34.5 50.8 61.8 69.5 73.3 71.1 65.7 61.7 77.0109 9000 37.0 51.7 64.3 72.5 76.1 74.3 68.8 65.3 80.0110 10000 38.9 51.4 65.6 74.6 77.8 76.7 70.9 68.7 82.0112 12000 43.5 54.1 69.7 79.5 82.2 82.2 75.7 75.2 87.0213 13000 37.5 57.6 64.4 70.3 74.5 71.7 66.3 61.7 78.0215 15000 38.4 56.6 65.6 72.4 76.5 73.9 68.5 64.2 80.0217 17000 39.5 56.2 66.9 74.4 78.3 76.1 70.7 66.6 82.0218 18000 40.2 56.0 67.6 75.5 79.3 77.2 71.9 68.0 83.0220 20000 43.0 57.0 70.1 78.6 82.0 80.4 74.9 71.8 86.0222 22000 44.8 57.5 71.6 80.5 83.8 82.6 76.8 74.5 88.0323 23000 43.1 63.9 68.2 72.9 76.3 73.2 67.9 63.5 80.0326 26000 43.2 63.6 69.2 74.6 78.5 75.5 70.1 65.6 82.0330 30000 43.2 63.2 70.3 76.3 80.6 77.8 72.4 67.8 84.0333 33000 44.6 63.3 71.8 78.3 82.5 79.9 74.4 70.0 86.0

FREQUENCYBANDHz ► 63 125 250 500 1000 2000 4000 8000

FanOverall levelLw (dB(A))FLOW RATE

(m3/h) ▼

106 6500 33.5 45.8 60.7 64.3 63.9 66.2 63.8 62.4 71.7108 8000 37.4 48.1 63.8 68.6 67.7 68.8 68.2 70.4 76.1109 9000 39.3 49.8 66.0 70.9 70.2 71.5 71.2 72.8 78.7110 10000 40.9 51.4 67.9 73.1 72.3 73.8 73.9 75.1 81.0112 12000 42.8 53.2 69.8 74.8 74.2 76.1 75.9 77.1 82.9213 13000 34.6 54.1 61.5 63.7 67.1 67.3 63.5 59.5 72.5215 15000 35.6 53.6 62.9 65.4 68.4 69.2 65.7 61.2 74.1217 17000 37.4 54.6 64.8 67.1 69.9 71.3 67.8 63.7 76.1218 18000 38.4 55.4 65.8 68.1 70.7 72.4 68.9 65.1 77.0220 20000 42.6 52.4 69.2 71.1 72.8 76.3 72.7 73.1 80.9222 22000 43.9 53.6 70.5 72.7 74.3 78.5 74.5 75.9 82.9323 23000 44.2 59.1 71.2 73.1 74.0 79.8 75.6 78.8 84.3326 26000 47.1 60.5 74.3 75.9 76.3 83.4 78.6 82.5 87.6330 30000 42.4 58.2 68.9 70.6 73.0 74.5 70.9 68.0 79.4333 33000 44.0 57.6 70.6 72.0 74.0 75.9 72.7 70.0 80.8

*Lw: sound power level (dB(A))

Sound level *

Supply air fan: Available pressure 200 Pa 50% fresh air

Page 27: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

27

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

FREQUENCYBANDHz ► 63 125 250 500 1000 2000 4000 8000

FanOverall levelLw (dB(A))FLOW RATE

(m3/h) ▼

106 6500 38.8 45.5 60.9 67.5 73.8 73.2 70.3 66.1 78.2108 8000 41.1 49.2 63.0 72.0 77.9 76.1 74.4 72.0 82.1109 9000 42.8 51.2 65.1 74.2 80.5 78.7 77.3 74.4 84.7110 10000 44.3 53.0 67.0 76.2 82.8 81.0 79.9 76.8 87.1112 12000 45.7 54.4 68.5 77.8 84.5 82.7 81.8 78.5 88.8213 13000 36.6 54.1 63.4 71.1 74.2 72.2 66.8 62.4 78.1215 15000 37.1 53.6 64.2 72.6 75.5 73.8 68.5 63.7 79.5217 17000 38.4 54.5 65.8 74.4 77.0 75.7 70.3 65.6 81.2218 18000 39.2 55.2 66.6 75.3 77.8 76.6 71.2 66.7 82.1220 20000 42.7 54.4 69.3 78.6 81.7 81.0 74.8 73.4 86.1222 22000 44.4 55.2 70.7 80.4 83.2 83.0 76.5 75.8 87.9323 23000 46.0 57.5 72.3 81.6 83.8 85.2 78.9 78.5 89.5326 26000 49.1 61.1 75.4 84.5 86.4 88.7 82.6 82.1 92.6330 30000 43.4 60.6 70.7 78.0 81.9 79.6 74.1 70.0 85.5333 33000 44.0 60.1 71.4 79.2 82.9 80.8 75.4 71.5 86.6

*Lw: sound power level (dB(A))

Sound level *

Exhaust air side: Available pressure 100 Pa 50% exhaust air

Page 28: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

28

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

RO

OF

CU

RB

S &

F

EE

T

■ Compliant with French standard NF P 84-206-1 (Grooved sheet metal roofing with waterproofing coating) and fire-safety regulations for PAB.

■ Aluminium packaged roof curb lighter than other galvanised steel constructions.

■ Adjustable angles to compensate roof slope. Other slope percentages are available on request (optional). Please confirm the roof slope percentage and direction.

■ Cap flashing allows continuous insulation and waterproofing membrane (up to 100 mm thick) on roof curb external side as required by 2002/91/EC Directive.

■ Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H = 345 mm).

■ Compliant with French standard NF P 84-206-1 (Grooved sheet metal roofing with waterproofing coating) and fire-safety regulations for PAB.

■ Aluminium packaged roof curb lighter than other galvanised steel constructions.

■ Adjustable angles to compensate roof slope. Other slope percentages are available on request (optional). Please specify the roof slope percentage and direction.

■ 200 mm ventilated air space in accordance with French fire-safety regulations for PAB. 4 (or 6) feet fixed by bolting and tightness guaranteed with foam gasket on supply air and return air ducts frames;

■ Sound insulation since the air space considerably reduces radiated noise from below the unit.

■ 200 mm double skin insulated ducts connections, with external aluminium mechanical protection, for supply and return air.

■ Cable pipes below the unit for power supply cable and hot water coils pipework.

■ Insulation below the roof curb using

25 mm glass wool with a protection veil. The insulation is secured with aluminium clips welded on the sheet metal for a better fastening than gluing methods. Insulation limits thermal losses and avoids under-surface condensation.

■ Cap flashing allows continuous insulation and waterproofing membrane (up to 100 mm thick) on roof curb external side as required by 2002/91/EC Directive.

■ Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H = 345 mm).

■ Lifting lugs to facilitate cranage.

The roof curb provides interfacing between the roof and the rooftop unit. It has been designed for easy assembly on the roof and simplifi ed unit laying.

Description

Installation accessories: Roof curbs

Packaged roof curbAdjustable connection roof curb

Packaged roof curbAdjustable ventilated roof curb

■ Bespoke roof curb to be adapted on any type of existing roof curb or header according to dimensions sent by the installer (see our particular clauses for this equipment).

Adapter interfaceon existing roof curb:

Page 29: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

29

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Max. slope (%)

106* - 108* - 109*110* - 112* 1700 2720 600 1910 2930 630 4

213 - 215 - 217 218 - 220 - 222 2220 3870 650 2430 4080 680 4

323 - 236 - 330 - 333 2220 4750 650 2430 4960 680 3.5

* Available for fi lters but not in Free Heating.

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Max. slope (%)

106 - 108 - 109 110 - 112 1700 1970 600 1910 2180 630 4

213 - 215 - 217218 - 220 - 222 2220 2770 600 2434 2978 618 4

323 - 326 - 330 - 333 2220 3550 650 2430 3760 680 4

Adjustable connection roof curb

Installation accessories: Roof curbs

For unit with "Free Heating" option or 300 mm fi lters

WARNING: for this roof curb laying, the installer is responsible for the ten-year guarantee on roofi ng. Please indicate the roof slope and directionslope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H = 345 mm). Roof curbs have to be back-drilled after mounting. Mastic application below unit frame.

H

B

A

Page 30: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

30

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Max. slope (%)

106 - 108 - 109 110 - 112 1700 1970 600 1900 2170 830 4

213 - 215 - 217 218 - 220 - 222 2220 2770 600 2420 2970 830 4

323 - 236 - 330 - 333 2220 3550 650 2420 3750 880 4

Adjustable ventilated roof curb

Installation accessories: Roof curbs

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Max. slope (%)

106 - 108 - 109 110 - 112 1700 2720 600 1900 2920 830 4

213 - 215 - 217 218 - 220 - 222 2220 3870 650 2420 4070 880 4

323 - 236 - 330 333 2220 4750 650 2420 4950 880 3.5

* Available for fi lters but not in Free Heating.

For unit with "Free Heating" option or 300 mm "box" fi lters.

WARNING: for this roof curb laying, the installer is responsible for the ten-year guarantee on roofi ng. Please indicate the roof slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H = 345 mm). Roof curbs have to be back-drilled after mounting. The unit must be bolted to the roof curb. Mastic application below unit frame.

H

200

B

A

Page 31: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

31

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm).

Installation accessories: Roof curbs

Roof curbs installation principle

One (for connection roof curb) or two (for ventilated roof curb) optional cover sheets can be added to protect the building from the weather during the time between roof curb laying and unit laying.

Nota:

50

100

Binding joist

Optional: side insulation

Connection roof curb

Unit frame

Waterproofi ng membrane

Sealant gasket between the frame and the roof curb on the periphery

Steel deck

InsulationH

150

min

.

600

(or 6

50 a

ccor

ding

to th

e un

it)

Outer insulation shall be part of the waterproofi ng package (not supplied by ETT)

Page 32: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

32

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

Unit 106 108 109 110 112 213 215 217 218 220 222 323 326 330 333

Nr. of feet 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Aluminium fi xed footUnitary weight: 1 kg

Installation accessories: Feet

Page 33: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

ETT may change equipment technical data without prior notice.Specifi cations given in this document are for information only and are not contractual.

33

2016 - 02 / EFFI+DXMARK-BRO_08.00-EN

180

1

3

2

Probes connection principle

1 Room probe: 1 shielded pair wire, 2 x 0.75 mm2 LIY-CY (max. length 100 lm)

2 CO2 probe: 2 shielded pairs wire, 4 x 0.75 mm2 LIY-CY (max. length 100 lm)

3 Humidity probe: 2 shielded pairs wire, 4 x 0.75 mm2 LIY-CY (max. length 100 lm)(optional)

- Please note that the value indicated can vary depending on probe location. For more representative results, do not install them:> Close to heat sources (spotlight, cooking appliances, glass wall, fl ues)> In draft zones (close to entrance, stockrooms, openings)> In dead zones (behind shelvings, in a corner)> Close to crowded areas (checkouts, fi tting rooms)

- For accurate measurements:> Do not install the probes in the axis of the duct used for their wiring.> Do not install control cables and power cables in the same duct (risk of electromagnetic

interference).

Nota:

Page 34: EFFI+ DX - Energie Transfert Thermique...• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance • EN 60204-1 - Safety of machinery – Electrical

Des

ign:

ETT

- D

ocum

ent p

rinte

d b

y an

env

ironm

enta

lly fr

iend

ly p

rinte

r usin

g ve

geta

ble

base

d in

k on

PEF

C p

aper

cre

ated

from

sust

aina

bly-

man

aged

fore

st.

www.ett.fr

ETT - Route de Brest - BP2629830 Ploudalmézeau - FranceTel: +33 (0)2 98 48 14 22Fax: +33 (0)2 98 48 09 12Export Contact: +33 (0)2 98 48 00 70ETT Services: +33 (0) 2 98 48 02 22

Reference: MARK-BRO_08.00-EN