ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED PLATE HEAT EXCHANGER INSTALLATION, OPERATION & MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050 / 08707 707 747 FAX: 020 87833051 / 08707 707 767 E-MAIL: [email protected] WEBSITE: www.stokvisboilers.com E4A O&M 2004

Upload: vandan

Post on 12-Dec-2018

227 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ECONOPLATE

E SERIES HOT WATER SERVICE

PACKAGED PLATE HEAT EXCHANGER

INSTALLATION, OPERATION & MAINTENANCE DOCUMENTATION

STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050 / 08707 707 747 FAX: 020 87833051 / 08707 707 767 E-MAIL: [email protected] WEBSITE: www.stokvisboilers.com

E4A O&M 2004

Page 2: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis
Page 3: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

STOKVIS ECONOPLATE ‘E’ SERIES INSTALLATION PRIMARY ON 4 PORT VALVE MODELS: The flow from the primary heat source is connected to the vertical connection of the 4 port valve, the return to the horizontal connection. Connections must be made using appropriate flanges and isolating valves to enable servicing of the valve after installation. PRIMARY ON 3 PORT VALVE MODELS: The flow from the primary heat source is connected to the flange of the 3 port valve, the return is from the lower, yellow, epoxy coated threaded pipe connection. SECONDARY: The cold water feed is connected to the bottom horizontal bronze connection, the hot water service flow to the top bronze connection. The flow connection can be recognised because of the electrical temperature probe fitted to it. Secondary re-circulation must be maintained at all times either around the installation or locally to the Econoplate. A connection is provided in the bronze cold feed casting for this purpose, or alternatively into the re-circulation pump if supplied. Suitable isolating valves should be included in all circuits.

Typical Installation of Econoplate Heat Exchanger on a combined heating and hot water system

BOILER

LOW VELOCITY MANIFOLD

ECONOPLATE PACKAGE

HEATING CIRCUIT

HWS CIRCUIT

COLD WATERFEED

SHUNT PUMP

ISOLATION , SAFETY & REGULATION VALVES NOT SHOWN FOR CLARITY

1

Page 4: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ASSEMBLY DETAILS : ECONOPLATE E4A--+1R.

PRIMARY INLETDN40 PN6

PRIMARY OUTLETDN40 PN6

SECONDARY OUTLET1½BSPF

SECONDARY RECIRC3/ 4" BSPF

SECONDARY INLET1½BSPF

87 mm

151 mm

555

mm

184

mm

101 mm

1110

mm

500 mm

300 mm

542 mm

39 mm

255 mm

10 mm

100 mm 75 mm250 mm

305 mm

383 mm

140

mm

75 mm

ASSEMBLY DETAILS : ECONOPLATE E4A--+1T.

PRIMARY INLETDN40 PN6

PRIMARY OUTLETDN40 PN6

SECONDARY OUTLET1½BSPF

SECONDARY INLETSEE TEXT

555

mm

101 mm

1110

mm

500 mm

300 mm

542 mm

255 mm

10 mm

100 mm 75 mm250 mm

305 mm

383 mm

140

mm

75 mm

SECONDARY INLET

DEPENDANT ON PUMP

UP20-45N = 3/4" BSP(F)

UPS25-55B = 1" BSP(F)

UPS32-55B = 11/4" BSP(F)

UPS32-80B = 11/4" BSP(F)

2

Page 5: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ASSEMBLY DETAILS : ECONOPLATE E4B--+1R.

SECONDARY INLET50mm BSP(F)

PRIMARY OUTLETDN50 PN6

PRIMARY INLETDN50 PN6

SECONDARY OUTLET2" BSP(F)

1130m

m

397mm

300mm

300mm

500mm394mm

555m

m

250mm

100mm 75mm

75mm

101mm

SECONDARY RECIRC11/4" BSP(F)

151mm

674mm

245m

m

10mm

ASSEMBLY DETAILS : ECONOPLATE E4B--+1T.

PRIMARY INLETDN50 PN6

GRUNDFOS

GRUNDFOS

GRUN

DFOS

PRIMARY OUTLETDN50 PN6

SECONDARY INLETDN40 PN6/10 (STANDARD PUMPS)

OPTIONAL DN50 PN6/10 PUMP FOR REMOTE FITTING BY CUSTOMER

SECONDARY OUTLET2" BSPF

101mm

300mm

397mm11

30m

m

555m

m

300mm

500mm

100mm 75mm

394mm

250mm

290mm

75mm

3

Page 6: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ASSEMBLY DETAILS : ECONOPLATE E3C--+1R.

SECONDARYRECIRC

SECONDARY INLET2" BSPF

" BSPF1 41/

PRIMARY OUTLET2" BSPF

PRIMARY INLETDN50 PN10

SECONDARY OUTLET2" BSPF

135mm

475mm

330mm

140m

m

105m

m

75mm

500mm865mm

151mm

275mm

1165

mm

590m

m

325mm

ASSEMBLY DETAILS : ECONOPLATE E3C--+1T.

PRIMARY OUTLET2" BSPM

PRIMARY INLETDN50 PN10

SECONDARY OUTLET2" BSPF

135mm

475mm

330mm

140m

m

75mm

500mm

865mm

151mm

275mm

1165

mm

590m

m

325mm

GRUNDFOS

SECONDARY INLETDN40 PN6/10 (STANDARD PUMPS)

OPTIONAL DN50 PN6/10 PUMP FOR REMOTE FITTING BY CUSTOMER

COMPLETE WITH OPTIONAL DUPLEX PRIMARY PUMP

4

Page 7: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ELECTRICAL DETAILS E4A Range: 240V - Single phase - 375 Watt E4B & E3C Range: 240V - Single phase - 915 Watt or 415V - Three phase - 915 Watt An external electrical supply isolator should always be fitted adjacent to the unit. The supply itself should be provided with suitable protection in accordance with current IEE regulations and codes of practice. EXTERNAL CONNECTIONS Common Temperature Alarm. A rise of 10oC above the set point or a fall of 20oC below the set point causes an alarm relay to be energised. A pair of volt free terminals, which close on a fault, are available for external indication. External Interlock. An external safety device can be connected to the Econoplate which will shut the unit down in case of a fault, it is a safety extra low voltage circuit, an open circuit should be used as a fault signal. External “Clock”. An external device can be connected to switch between 2 temperatures, or to switch between a single set point and off. A closed contact across this safety extra low voltage circuit gives the day setting and an open circuit the night. External Temperature indication. A 4-20mA output gives an indication of the secondary flow temperature, it is a linear scale, 4mA = 0OC, 20mA = 99OC. Fuse Protection. The electronic controller is protected by a 500mA fuse and the main p.c.b. output side is protected by a 10A fuse, both are located on the p.c.b.

WARNING NEVER RUN CONTROL CABLES USING LOW VOLTAGES WITH POWER CABLES, INDUCED VOLTAGES CAN AFFECT THE OPERATION OF THE CONTROLLER.

5

Page 8: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

SECONDARY CONNECTIONS, INSTANTANEOUS SYSTEM WITH MAINS COLD FEED CONNECTION.

LEGEND

SAFETY VALVE

DOUBLE NRV

SINGLE NRV

ISOLATION VALVE

AUTO AIR VALVE

DRAIN VALVE

HWS DRAW OFF

EXPANSION VESSEL

RECIRC PUMP

COLD WATERSERVICE

PLATE HEATEXCHANGER

PRESSUREREG VALVE

N.B. COMPLIANCE WITH WATER BY-LAWS, BUILDING REGULATIONS & ANY OTHER APPLICABLE STANDARDS SHOULD BE CHECKED PRIOR TO INSTALLATION

MAINTENANCE LOCKSHIELD VALVE (PROHIBITED BYU.K. REGULATIONS)

SECONDARY CONNECTION, SEMI INSTANTANEOUS WITH STORAGE AND MAINS COLD FEED CONNECTION.

LEGEND

T&P VALVE

SAFETY VALVE

SETTER VALVE

DOUBLE NRV

SINGLE NRV

LOCKSHIELDISOLATION VALVE

ISOLATION VALVE

AUTO AIR VALVE

ANTI VAC VALVE

DRAIN VALVE

ALTERNATIVEPOSITION FORT&P VALVE

HWS DRAW OFF

EXPANSION VESSEL

HWS RETURN

RECIRC PUMP

PHE TRANSFERPUMP

HWS FLOW

COLD WATERSERVICE

HWS BUFFERVESSEL

PLATE HEATEXCHANGER

PRESSUREREG VALVE

N.B. COMPLIANCE WITH WATER BY-LAWS, BUILDING REGULATIONS & ANY OTHERAPPLICABLE STANDARDS SHOULD BE CHECKED PRIOR TO INSTALLATION

MAINTENANCE LOCKSHIELD VALVE (PROHIBITED BYU.K. REGULATIONS)

6

Page 9: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

OPERATION.

Prior to switching the Econoplate on it must be ensured that the unit is filled with water and that all pipework and pumps are vented. Once this is complete and the unit is on, the Econoplate Controller should be set as described under Econoplate Controller Adjustment to suit the particular requirements of the client. The pump(s) should be vented, on the E4B and E3C Ranges a three phase pump may be fitted, therefore the direction of rotation must also be checked. In all cases the pump run current should be measured and on the E4B and E3C Ranges the overloads set accordingly. Overload trip on the E4B and E3C is indicated on the LCD display and on duplex units auto changeover is also included, these functions should be checked. On all units the travel of the motorised valve should be checked by simulating a load / no load situation and the limit switched adjusted if necessary to prevent the motor driving up against the mechanical stops.

7

Page 10: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

MAINTENANCE.

If the installation is set up as per the above instructions, and if the pre-set factory values are unchanged, the Stokvis Econoplate Unit should not need dismantling for service for many years. Any clogging, may be detected as follows: - A high pressure drop between inlet and outlet of the secondary hot water

circuit. - A small temperature drop between inlet and outlet of the primary circuit (under 30°C at full load the exchanger is clogged). If it is required to clean the Plate Heat Exchanger the following instructions should be followed: - Isolate the exchanger, primary first, then allow the temperature to fall below 40o C, then isolate the secondary. - Reduce the pressure by opening the vents and drain both primary and secondary. - Carefully release the securing bolts between the frame and front plate. Slacken the bolts in sequence to reduce stress on individual bolts. - Remove the plates one at a time from the unit. If possible keep the plates in order ready for re-assembly, otherwise refer to the following notes. - Plates can be identified in the following way.

G30, G50, VU8, VU12 all have gaskets on one side of each plate facing the fixed chassis. G30 and G50 have octagonal gaskets around the ports and the corner of the plate is cropped at 45o. VU8 and VU12 have round gaskets around the ports the corner of the plate is also rounded. GX12 have round gaskets around the ports and have the corner of the plate is cropped at 45o (2 gasketing styles exist) letters C,G,B,E are stamped into the top/bottom of each plate. GL13 have round gaskets around the ports and have the corner of the plate is cropped at 45o letter O is stamped into the one side at the top/bottom of each plate.

- A plate pack always has a 4 hole first plate which has a gasket around all

4 ports. This plate sits against the fixed chassis plate. Next are a number of intermediate plates and finally a blank plate with no ports.

8

Page 11: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

G30, and VU8 plates, have one type of intermediate plate (they cannot however be mixed), G50, VU8, GX12 and GL13 plates have 2 types of intermediate plate, which alternate, these are left hand and right hand gasketed plates. On G50 and VU12 the direction of the chevron pattern, on the face of the plate, alternates across the whole assembly and alternate left and right top ports have a gasket around their circumference. There are 2 styles of gasketing on the GX12 plates, one style has gaskets on both sides of one plate and then no gasket on the next. These alternate and the correct orientation is given by the letter stamped at the top of each plate. This sequence must be noted prior to dismantling as it will ensure the correct re-assembly. The other style has a gasket on one face of each intermediate plate and the correct orientation is again given by the letter stamped at the top of each plate. Alternate left and right top ports will have a gasket around their circumference. These sequences must be noted prior to dismantling as it will ensure the correct re-assembly. On GL13 plates the letter O is stamped into either the top or bottom of each plate and alternate left and right top ports have a gasket around their circumference. These sequences must be noted prior to dismantling as it will ensure the correct re-assembly.

- Carefully clean the plates. (Do not use a metallic device). Use a nylon brush with water. A proprietary de-scaling agent may be used if necessary, always rinse thoroughly with clean fresh water. Always follow the correct safety procedures when handling chemicals. - Re-assemble the plates in the same order that they were removed. Replace front plate and tighten the bolts in a similar manner to that used on an automobile cylinder head to ensure an even distribution of force over the surface of the plate. The distance between the front plate and the rear chassis plate should be between 3 and 3.1 mm per plate for G30 and G50 plates or 3.6 mm per plate for VU8 & VU12 plates or

3.4mm for GX12 and GL13 plates and should be measured next to each bolt to ensure even tightening of the bolts.

- If the plates are dirty it is important to also clean the temperature sensor. - A visual check on the correct assembly can be made by looking at the edge of the plates. A pattern resembling a honeycomb should always be seen.

9

Page 12: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

FAULT FINDING.

E SERIES PLATE HEAT EXCHANGER FLUCTUATING TEMPERATURES AT OUTLET. 1. Check that the secondary pump is operating correctly and that good circulation exists - feel the temperature of the return pipe, if it is cool then there is no circulation. 2. Check that a non-return valve is fitted on the HWS return and that it is not letting by and so allowing the cold feed to pass up the HWS return - feel for a cool return pipe. 3. Check that the motorised valve is opening and closing in response to changes in demand - raise and lower the set point on the controller or open and close some hot water taps and observe the valve. Also check that the linkages between the valve and motor are secured. 4. Check that the motorised valve is responding by moving in the correct direction - test as above. If incorrect electrically isolate the Econoplate and reverse the + and - valve motor connections on the p.c.b. reinstate the electrical supply and check again. 5. Check that the temperature sensor is not scaled - isolate the secondary side of the unit and remove the sensor, clean as appropriate. If heavily scaled the Plate Heat Exchanger will probably be similarly affected strip and clean as necessary. (see maintenance procedure). NO HOT WATER AT OUTLETS 1. Check the electrical supply to the unit-reinstate if necessary. 2. Check for the LCD display on the control panel - if not on check/replace 500mA control fuse - check control panel isolator switch is in the ON position.

10

Page 13: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

3. If the 500mA fuse blows again, set the Econoplate to give temporary hot water as detailed below and replace the printed circuit board as soon as possible. TEMPORARY OPERATION TO PROVIDE HOT WATER IN THE EVENT OF COMPONENT FAILURE IS ACHIEVED AS FOLLOWS:

a. Open the motorised valve fully by hand. b. Ensure that there is an electrical supply to a primary pump and link the start/stop terminals for that pump if not already made. c. Reduce the boiler flow temperature to a maximum of 65°C to prevent excess secondary temperatures. d. Set the high temperature alarm to automatic - refer to “Controller Adjustments” for procedure.

4. If there is an LCD display but no apparent outputs to pumps etc. check the 10A output fuse on the p.c.b. If it is blown, make electrical checks on all pumps and valves fitted to the unit, repair, replace or isolate faulty item and replace 10A fuse 5. Check that the motorised valve is operating - place in manual operation and move the valve through its travel to check for seizure, strip and clean or replace as required. 6. Check that all linkage arms are secure and not slipping on their shafts-tighten with the motor at the end of its travel and check limits. 7. Check that the valve motor is operating - raise and lower the set point on the controller and observe. - If the motor does not work, perform the procedure above for the temporary hot water supply. 8. Check that the primary pump is operating - check the pump overload (E4B/EJB & E3C) - check the pump rotation by removing the pump end cap - check that there is a start signal to the pump, replace pump head or switch permanently to standby pump if available.

11

Page 14: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

NO WATER FROM HIGHEST OUTLET 1. The resistance through the heat exchanger exceeds the static head/pressure of the cold feed. If water flow has deteriorated from when originally installed strip and clean the Heat Exchanger as per the maintenance procedure, if scaled up also clean the temperature probe. If new, investigate the effect of turning off HWS recirculation pumps, where they are installed on the HWS return. If it improves water flow try operating the pump on a lower speed or reinstall it on the HWS flow, perhaps with a bypass and non- return valve if the Econoplate flow exceeds the LEAKING maximum flow of the pump. FROM THE PLATE HEAT EXCHANGER 1. Check that the Heat Exchanger is bolted up fully - measure the space occupied by the plates, next to each bolt. The gap between the chassis and clamping plate should be between 3 and 3.1mm per plate for G30 and G50 plates and 3.6mm for

VU8 and VU12 plates and 3.4mm for GX12 and GL13 and it should be evenly spaced across the whole assembly. - Relieve the pressure on primary and secondary side and tightened down to the correct figure. If the unit still leaks the affected plates should be replace.

2. Check that the maximum operating pressure has not been exceeded at any time.

12

Page 15: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

PARTS LIST.

Part No Description ESS8133 Econotrol 2100 controller exc. Enclosure ESS8122 Integral ‘E’ series controller complete(yellow facia red display) ESS8100/1 ‘E’ Series Temp Regulator (Square Type p.c.b.) from Oct’93 ESS7001 ‘E’ Series Temp Regulator (Rectangular type p.c.b.) pre Oct’93 ESS7014 Klockner Moeller overload 1 phase PKZM 1-4 EJB/ESC ESS7013 Klockner Moeller overload 3 phase PKZM 1-2.4 EJB/ESC ESS7015 Klockner Moeller auxiliary relay DIL ER 22 240V ESS8123 Telemecanique overload 1 phase LR2-K 0310 EJB/E4B/E3C ESS8124 Telemecanique overload 3 phase LR2-K 0307 EJB/E4B/E3C ESS8125 Telemecanique contactor LC1K-0610-U7 EJB/E4B/E3C ESS8106 ‘E’ Series 24 Hour Clock (Flash Type) for ESS8101 ESS7010 ‘E’ Series 24 Hour Clock (Grasslin Type) for ESS7001 ESS6600 ‘E’ Series Temperature Sensor 1/8” BSP 39mm ESS6601 ‘E’ Series Temperature Sensor 1/8” BSP 65mm ESS7012 ‘E’ Series Temperature Sensor 1/4” BSP ESS4817 UJ & US Series Temperature Sensor 1/2” BSP ESS7020 4 Port Valve Sauter MH42F32 EJA Only ESS7024 4 Port Valve Sauter MH42F40 E4A/EJA/EJB ESS7022 4 Port Valve Sauter MH42F50 E4B/EJB/ESC ESS7027 Sauter MH42 Seal kit ESS8104 4 Port Valve ESBE TYPE G438 1 1/2” screwed EJA only ESS8105 4 Port Valve ESBE TYPE G451 2” screwed EJB/ESC only ESS8108 4 Port Valve ESBE TYPE F440 40mm Flanged EJA only ESS8109 4 Port Valve ESBE TYPE F450 50mm Flanged EJB/ESC ESS8102 ‘E’ Series valve actuator Neptronic BBT HV1200 (Use ESS7025 and ESS7026) ESS7025 ‘E’ Series valve actuator Sauter AR30W21-F001 (alternative to AR30W11-F001) ESS7026 Sauter actuator mounting kit Z361775 for AR30W21/11 ESS6603 3 port valve Sauter type B16E50F300 for E3C only ESS7052 Sauter actuator type AVR32W30-F001 for B16E valve ESS7805 E4A/EJA Primary Pump Motor UPS40-80 1 Phase ESS7804 E4B/EJB/ESC Primary Pump Motor UPC50-120 1 Phase- 96406328 ESS7803 E4B/EJB/ESC Primary Pump Motor UPC50-120 3 Phase- 96406329 ESS7800 Terminal Box 96405868 with internal speed control & indicator lights for UPC50-120 1 Phase-excluding start stop relay ESS7798 ESS7826 Terminal Box 96405869 with internal speed control & indicator lights for UPS50-120/2 1 Phase-excluding start stop relay ESS7798 ESS7798 Start stop relay 96404518 for 1 phase terminal box ESS7800 ESS7826(required for pumps controlled with PKZM1 panel mounted starters)

13

Page 16: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ESS7801 Terminal Box (Type 200) 00546092 for UPC50-120 3 Phase - excludes start stop relay ESS7799 (alternative terminal box ESS7827) ESS7799 Start stop relay for 3 phase terminal box ESS7801(required for pumps controlled with PKZM1 panel mounted starters) ESS7827 Terminal Box 96404874 with internal speed control & indicator lights for UPS50-120/2 & UPC50- 120 3 Phase-excludes start stop relay ESS7797 ESS7797 Start stop relay 96404520 for 3 phase terminal box ESS7827(required for pumps controlled with PKZM1 panel mounted starters) ESS7824 E4B/E3C Primary Pump Motor UPS50-120 1 Phase-96406015 ESS7825 E4B/E3C Primary Pump Motor UPS50-120 3 Phase-96406017 ESS4904 E4A/EJA Secondary Recirculating Pump UP20-45N 1 Phase ESS7805 EJB/ESC Secondary Recirculating Pump Motor UPS40-80 1 Phase for UPS32-80B ESS7049 E4B/EJB/E3C Secondary Recirculating Pump UPS32-55B 1 Phase

HEAT EXCHANGER PLATES ESS4625 E4A/E4B/EJA/EJB G30H End Blanking Plate ESS4626 E4A/E4B/EJA/EJB G30H Intermediate Plate ESS4627 E4A/E4B/EJA/EJB G30H 4 Hole First Plate ESS4611 EJA/EJB VU8 End Blanking Plate ESS4612 EJA/EJB VU8 Intermediate Plate ESS4613 EJA/EJB VU8 4 Hole First Plate ESS4703 ESC G50H End Blanking Plate ESS4704 ESC G50H Left Hand Intermediate Plate ESS4705 ESC G50H Right Hand Intermediate Plate ESS4706 ESC G50H 4 Hole First Plate ESS4699 ESC VU12 End Blanking Plate ESS4700 ESC VU12 Left Hand Intermediate Plate ESS4701 ESC VU12 Right Hand Intermediate Plate ESS4702 ESC VU12 4 Hole First Plate ESS6610 E3C GX12H Half Gasket Front 4 Hole Plate ESS6611 E3C GX12H Gaskets Both Sides Intermediate Plate ESS6612 E3C GX12H No Gasket Intermediate Plate ESS6613 E3C GX12H Half Gasket Back Blank Plate ESS6618 E3C GX12H Half +1 Gasket First 4 Hole Plate ESS6619 E3C GX12H 1 Gaskets LH Intermediate Plate ESS6620 E3C GX12H 1 Gasket RH Intermediate Plate ESS6621 E3C GX12H Half Gasket Back Blank Plate GL13H FIRST E3C GL13H First 4 Hole Plate GL13H LH E3C GL13H LH Intermediate Plate GL13H RH E3C GL13H RH Intermediate Plate GL13H LAST E3C GL13H Blank Plate

14

Page 17: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ECONOTROL 2100 CONTROLLER INSTRUCTIONS.

STOKVIS ENERGY SYSTEMS 96R WALTON ROAD

EAST MOLESEY SURREY KT8 ODL

TEL: 08707 707 747 FAX: 08707 707 767

MARCH2001 ECT32001

Page 18: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis
Page 19: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ECONOTROL 2100 GENERAL SPECIFICATION. The Econotrol 2100 is a purpose designed PID regulator which controls temperature via a motorised modulating valve as well as operating a number of primary and secondary pumps, as can be fitted to the various Econoplate units. In addition to the PID control it also contains all functional indicator lamps, a control fuse, an output fuse, duplex pump duty share (if fitted), high and low temperature alarm indication, common volt free temperature alarm terminals, and high temperature lockout, extra low voltage external interlock circuit with indication, 4-20 mA flow temperature indication, a 7 day time clock for either 2 temperatures of operation or a single temperature and night off, per day. Alternatively the extra low voltage “external time clock” circuit can be used for operation at 2 temperatures or for single temperature and off. If primary pump overloads are included, overload trip indication is available on the panel. On duplex units with overloads, auto changeover on primary pump fault is also possible. ECONOTROL 2100 - FACIA LAYOUT.

1

Page 20: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ECONOTROL 2100 - DISPLAY. The current SET POINT is always displayed, to view any one of the other display options press either the t or u key to move from one to the other DISPLAY options: -DAY of the week & TIME, (24 hour clock). -Secondary water flow TEMPERATURE, in OC -EXTERNAL INTERLOCK, shown only if an external interlock has been connected and activated. -HIGH TEMPERATURE ALARM, shown only if the alarm temperature has been exceeded (factory set at 10OC above the higher set point). -LOW TEMPERATURE ALARM, shown only if the alarm temperature has been exceeded(factory set at 20 OC below the current set point). -PUMP OVERLOAD TRIP, shown only if a primary pump, P1 or P2, overload has tripped, only available on units fitted with contactor overloads, with auxiliary contacts. ECONOTROL 2100 - FUNCTION. The FUNCTION options are accessed by pressing either the 3or 8 key. To move from one option to the next press either the t or u key. To view the current status of an option press the h key. To change the current status press either the t or u key. To enter/select this change press the h key. To return to the DISPLAY press 3 or 4 key. -The DAY<FROM>NIGHT function is used to change from one mode of operation to the other, e.g. if you were running in night mode and the unit was off, if you wanted hot water as you had during the day, by using this function you can swap over from the night setting to the day setting. When the unit next operates in the day mode the unit will revert back to normal operation. -The HIGH TEMPERATURE RESET only operates if a high temperature lockout has occurred, using it restarts the unit and resets the external volt free temperature alarm. -The RESTORE DEFAULTS option is used to return to the factory values for all settings. A further “Are You Sure” prompt appears on the display prior to this function being actioned.

2

Page 21: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ECONOTROL 2100 - SETTINGS. The SETTINGS are used to set all of the parameters which have an influence on the way in which the controller will work, there are default values for all of these parameters, which are given in SUMMARY OF OPERATION. The SETTINGS options are accessed from FUNCTION by pressing and holding either the 3 or 4 key for 5 seconds then releasing. To view the current status of a setting press the h key. To select a particular parameter within a particular setting press the h key (the parameter will now flash) To change the current value of a parameter press the t key. To move to the next parameter press the 4 key. To enter this change press the h key (the parameter stops flashing). To move to the next setting press the tor u key. To return to FUNCTION then DISPLAY press the 3 or 4 key twice. -TIME, this includes the current day of the week, time, in hours, minutes and seconds, based on a 24 hour clock. -CLOCK, the unit can run on its internal clock or it can be controlled from an external source, (default setting is internal clock). -DAILY DAY, TIME & TEMPERATURE, this is used , for each day of the week to set the start time for the day operation and the temperature. The temperature range is from 01OC to 99OC, alternatively OFF can be selected. -DAILY NIGHT, TIME & TEMPERATURE, this is used for each day of the week, to set the start time for the night operation and the temperature. The temperature range is from 01OC to 99OC, alternatively OFF can be selected. -EXTERNAL CLOCK DAY, TEMPERATURE, this is used to set the temperature for the day operation when controlled by an external source. The temperature range is from 01OC to 99OC, alternatively OFF can be selected. -EXTERNAL CLOCK NIGHT, TEMPERATURE, this is used to set the temperature for the night operation when controlled by an external source. The temperature range is from 01OC to 99OC, alternatively OFF can be selected. HIGH TEMPERATURE ALARM, this is used to set the temperature difference above the higher set point at which an alarm mode occurs. The temperature difference is from 01OC to 99OC, alternatively OFF can be selected. LOW TEMPERATURE ALARM, this is used to set the temperature difference below the current set point at which an alarm mode occurs. The temperature difference is from 01OC to 99OC, alternatively OFF can be selected.

3

Page 22: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

PROPORTIONAL BAND, a high proportional band will produce slow response but no overshoot, the set point may never be reached, a low proportional band will produce a fast response but a big temperature overshoot and prolonged oscillations in temperature may occur DIFFERENTIAL, this term helps the controller approach the set point more rapidly with less overshoot. The higher the value the more the differential term works, and in theory the better the response, however there is a limit above which the system will respond too quickly to small errors and become unstable. -PUMP MODE, this is used to determine which pump output is used. If a single primary pump is connected to the P1 terminals then P1 ON should be selected. If a single primary pump is connected to the P2 terminals then P2 ON should be selected. If a twin headed(duplex) pump is fitted, one will be connected to P1 the other to P2, P1/P2 should be selected which will then perform duty share on the 2 pumps -ALARM MODE, there are 3 automatic and 1 manual reset high temperature alarm modes. AUT1 - If the secondary temperature measured is greater than the high temperature alarm value, the LCD indicates this. If this persists, the unit is shut down, all pumps are turned off, and the modulating valve is closed. The common temperature alarm lamp is lit and the common temperature alarm volt free terminals are closed. Auto reset occurs once the temperature has fallen below the alarm temperature. AUT2 - If the secondary temperature measured is greater than the high temperature alarm value, the LCD indicates this. If this persists, the unit is shut down, all pumps are turned off, and the modulating valve is closed. The common temperature alarm lamp is lit and the common temperature alarm volt free terminals are closed. Subsequent high temperatures cause an almost immediate shut down. Auto reset occurs once the temperature has fallen below the alarm temperature. AUT3 - If the secondary temperature measured is greater than the high temperature alarm value, the LCD indicates this. If this persists the common temperature alarm lamp is lit and the common temperature alarm volt free terminals are closed, the unit is not shut down. Auto reset occurs once the temperature has fallen below the alarm temperature. MAN - If the secondary temperature measured is greater than the high temperature alarm value, the LCD indicates this. If this persists, the unit is shut down, all pumps are turned off, and the modulating valve is closed. The common temperature alarm lamp is lit and the common temperature alarm volt free terminals are closed. To reset the alarm, go into FUNCTION and select HIGH TEMP. RESET.

4

Page 23: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

EXTERNAL CONNECTIONS Electrical Supply. The controller operates with a 240V supply. An external electrical supply isolator should always be fitted adjacent to the unit. The supply itself should be provided with suitable protection in accordance with current IEE regulations and codes of practice. Internal Fuse Protection. The electronic controller is protected by a 500mA fuse and the main p.c.b. output side is protected by a 10A fuse, both are located on the p.c.b. Common Temperature Alarm. If either the high or low temperature alarm value is exceeded a relay is energised ,closing a pair of volt free terminals for external indication. External Interlock. An external safety device can be connected to the Econoplate which will shut the unit down in case of a fault, it is a safety extra low voltage circuit, an open circuit should be used as a fault signal. External “Clock”. An external device can be connected to switch between 2 temperatures, or to switch between a single set point and off. A closed contact across this safety extra low voltage circuit gives the day setting and an open circuit the night setting. External Temperature indication. A 4-20mA output gives an indication of the secondary flow temperature, it is a linear scale, 4mA = 0OC, 20mA = 99OC. (24v @470 ohm) WARNING NEVER RUN CONTROL CABLES USING LOW VOLTAGES WITH POWER CABLES, INDUCED VOLTAGES CAN AFFECT THE OPERATION OF THE CONTROLLER.

5

Page 24: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

SUMMARY OF DISPLAY & FUNCTION.

SUMMARY OF SETTINGS

6

Page 25: ECONOPLATE E SERIES HOT WATER SERVICE PACKAGED … · econoplate e series hot water service packaged plate heat exchanger installation, operation & maintenance documentation stokvis

ECONOTROL BASIC WIRING.

L N EN - M +

ALARM

1 PHASESUPPLY

P2P1

(OPTIONAL)SECONDARY PUMP

P1/ P2 F.L.C. 1.0A

P3 F.L.C. 0.5A(20- 45/ 25- 55) OR0.58A(32- 55) OR0.62A(40- 50) OR1.0A(32- 80/ 40- 80)

EXTERNAL CLOCKN/ C = DAY SET POINT

EXTERNAL INTERLOCK

N/ O = NIGHT SET POINT

BA

SENSORCLOCKI/ LOCKEXTEXT

- +EE ENN

P2

P3

P1

PUMP 1PRIMARY

PUMP 2PRIMARY

(OPTIONAL)

AMMETER

470NIGHT

P1 O/ LP2 O/ LN/ C = NORMAL OPERATIONN/ O = EXT SAFETY TRIPPED

24V

STOKVIS ENERGY SYSTEMS, 96R WALTON ROAD, EAST MOLESEY, SURREY, KT8 0DL. Tel. 44 (0)870 770 7747

E4A BASIC WIRING DETAIL - 240V ECONOTROL 2100 Title

TIL/ E/ 030/ A

STK- WIR- E- E4A- 044/ AOCT 00 Date

CAD refCode No

R.S.Drawn Drawing NoDATEISSUE MODIFICATION

4- 20mA

DAY

W- E- 044/ A

P1

(OPTIONAL)SECONDARY PUMP

P3

P1

PUMP 1PRIMARY

N

P1/ P3 CONNECTION SIMPLEX MODELS

4- 20mA EXTERNAL TEMPERATURE INDICATION4mA = 0.C20mA= 99.C@ 470 OHM

M

ACTUATORTERMINALS

2 1 3