ecen 615 methods of electric power systems analysis...

29
Lecture 9: Advanced Power Flow, Gaussian Elimination, Sparse Systems ECEN 615 Methods of Electric Power Systems Analysis Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University [email protected]

Upload: others

Post on 18-Mar-2020

20 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Lecture 9: Advanced Power Flow, Gaussian

Elimination, Sparse Systems

ECEN 615Methods of Electric Power Systems Analysis

Prof. Tom Overbye

Dept. of Electrical and Computer Engineering

Texas A&M University

[email protected]

Page 2: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Announcements

• Read Chapter 6

• Homework 2 is due on Sept 27

2

Page 3: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Area Interchange Example: Seven Bus, Three Area System

3PowerWorld Case: B7Flat

Page 4: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Example Large System Areas

4

1

101

102

103

104105

106

107

201

202

205

206

207

208

209

210

212

215

216

217

218

219

222

225

226

227

228229

230

231

232

233

234

235

236 237

295

296

314

320

327

330

332

333

340

341

342

343

344

345

346

347

349

350

351

352

353

354

355

356

357

360

361

362

363364

365

366

401

402

403

404

405

406

407

409

410

411

412

415

416

417

418

419

421

426

427

428

433

436

438

502

503

504

515

520

523

524

525

526

527

531

534

536

540541

542

544

545

546

600

608

613

615

620

627

633

635

640

645

650

652

661

667

672

680

694

696

697

698

998

999

Each oval

corresponds to a

power flow area

with the size

proportional to

the area’s

generation

Page 5: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Generator Volt/Reactive Control

• Simplest situation is a single generator at a bus

regulating its own terminal

• Either PV, modeled as a voltage magnitude constraint, or as a

PQ with reactive power fixed at a limit value. If PQ the

reactive power limits can vary with the generator MW output

• Next simplest is multiple generators at a bus. Obviously

they need to be regulating the bus to the same voltage

magnitude

• From a power flow solution perspective, it is similar to a single

generator, with limits being the total of the individual units

• Options for allocation of vars among generators; this can affect

the transient stability results

5

Page 6: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Generator Volt/Reactive Control

6

Case is Aggieland37_

Gen_VoltVar

Page 7: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Generator Volt/Reactive Control

• Next complication is generators at a single bus

regulating a remote bus; usually this is the high side of

their generator step-up (GSU) transformer

• When multiple generators regulate a single point their exciters

need to have a dual input

• This can be implemented in the power flow for the generators

at bus j regulating the voltage at bus k by changing the bus j

voltage constraint equation to be

(however, this does create a zero on the diagonal of the

Jacobian)

• Helps with power system voltage stability 7

, 0k k setV V

Page 8: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Generator Volt/Reactive Control

• The next complication is to have the generators at

multiple buses doing coordinated voltage control

• Controlled bus may or may not be one of the terminal buses

• There must be an a priori decision about how much

reactive power is supplied by each bus; example

allocations are a fixed percentage or placing all

generators at the same place in their regulation range

• Implemented by designating one bus as the master; this

bus models the voltage constraint

• All other buses are treated as PQ, with the equation

including a percent of the total reactive power output of

all the controlling bus generators 8

Page 9: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Remote and Coordinated Var Control Example

9

GIGEM69

KYLE69

KYLE138

WEB138

WEB69

BONFIRE69

FISH69

RING69

TREE69

CENTURY69

REVEILLE69MAROON69

SPIRIT69

YELL69

RELLIS69

WHITE138

RELLIS138

BUSH69

MSC69

RUDDER69

HULLABALOO138

REED69

REED138

AGGIE138 AGGIE345

16%A

MVA

33%A

MVA

78%A

MVA

78%A

MVA

18%A

MVA

55%A

MVA

14%A

MVA

54%A

MVA

60%A

MVA

16%A

MVA

49%A

MVA

49%A

MVA

45%A

MVA

50%A

MVA

49%A

MVA

49%A

MVA

35%A

MVA

A

MVA

57%A

MVA

45%A

MVA

A

MVA

72%A

MVA

75%A

MVA

33%A

MVA

68%A

MVA

33%A

MVA

39%A

MVA

68%A

MVA

68%A

MVA

22%A

MVA

A

MVA

19%A

MVA

52%A

MVA

57%A

MVA

39%A

MVA

63%A

MVA

70%A

MVA

70%A

MVA

0.97 pu

0.945 pu0.98 pu

0.96 pu

0.982 pu

0.97 pu

0.950 pu

0.972 pu0.97 pu

0.98 pu

1.000 pu

1.01 pu

0.993 pu

0.992 pu

0.975 pu0.98 pu

0.96 pu

0.96 pu 0.95 pu

0.981 pu

0.976 pu0.96 pu

1.01 pu1.03 pu

PLUM138

1.01 pu

14%A

MVA

0.97 pu

61%A

MVA

34 MW

0 Mvar

59 MW

17 Mvar

20 MW

8 Mvar

100 MW

30 Mvar

61 MW 17 Mvar

59 MW

6 Mvar

69 MW

0 Mvar

93 MW

58 Mvar

58 MW

17 Mvar

36 MW

24 Mvar

96 MW

20 Mvar

93 MW

65 Mvar 82 MW

27 Mvar

0.0 Mvar

35 MW

11 Mvar

25 MW

10 Mvar

38 MW 10 Mvar

22 MW

0 Mvar

0.0 Mvar

0.0 Mvar

0.0 Mvar

0.0 Mvar

0.0 Mvar

0.0 Mvar

31 MW

13 Mvar

49 MW

17 Mvar

deg 0

tap1.0875

tap1.0000

tap1.0213tap1.0213

3.4 Mvar

52.8 Mvar

pu 1.031

pu 0.993 10.0 Mvar

20.4 Mvar

39.2 Mvar

95%A

MVA

Each oval

corresponds to a

power flow area

with the size

proportional to

the area’s

generation

Page 10: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Model Complexity Examples

• A recent 76,000 bus Eastern Interconnect (EI) power

flow model has voltage magnitudes controlled at about

19,000 buses (by Gens, LTCs, switched shunts) 94%

regulate their own terminals with about 1100 doing

remote regulation. Of this group 572 are regulated by

two or more devices, 277 by three or more, 12 by eight

or more, and three by 12 devices!

• It also has 27,622 transformers with 98 phase shifters

• Impedance correction tables are used for 351, including about

2/3 of the phase shifters; tables can change the impedance by

more than two times

10

Page 11: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

PV Bus Voltage Droop

• Traditionally the PV bus approach considered either 1)

on control at setpoint or 2) at a limit

• Increasingly this is no longer the case, particularly for

wind and solar. Rather regulation has a droop

11

Page 12: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

PV Bus Voltage Droop

• This actually allows for multiple generators to regulate

a single remote bus using different characteristics

12

B2

RegBus

Generators are

all configured to

regulate the

RegBus

B3

B1

A2

A3

A1

“Arriving

Branches”

Page 13: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

PV Droop Implementation

• PowerWorld just implemented this using a voltage

droop control object

13

Page 14: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

B7Flat Example with PV Deadband

14

Case is B7Flat_PVDroop

Research opportunity with the synthetic models to discuss

the impact of deadbands on, say, voltage stability

Page 15: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Example of Hourly Voltage Variation Over Time

15

Page 16: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Power Flow Topology Processing

• Commercial power flow software must have

algorithms to determine the number of asynchronous,

interconnected systems in the model

• These separate systems are known as Islands

• In large system models such as the Eastern Interconnect it is

common to have multiple islands in the base case (one recent

EI model had nine islands)

• Islands can also form unexpectedly as a result of

contingencies

• Power can be transferred between islands using dc lines

• Each island must have a slack bus

16

Page 17: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Power Flow Topology Processing

• Anytime a status change occurs the power flow

must perform topology processing to determine

whether there are either 1) new islands or 2) islands

have merged

• Determination is needed to determine whether the

island is “viable.” That is, could it truly function as

an independent system, or should the buses just be

marked as dead

• A quite common occurrence is when a single load or

generator is isolated; in the case of a load it can be

immediately killed; generators are more tricky

17

Page 18: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Topology Processing Algorithm

• Since topology processing is performed often, it must

be quick (order n ln(n))!

• Simple, yet quick topology processing algoritm

• Set all buses as being in their own island (equal to bus

number)

• Set ChangeInIslandStatus true

• While ChangeInIslandStatus Do

• Go through all the in-service lines, setting the islands for each of the

buses to be the smaller island number; if the island numbers are

different set ChangeInIslandStatus true

• Determine which islands are viable, assigning a slack bus as

necessary

18

Page 19: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Example of Island Formation

19

Top Area Cost

Left Area Cost Right Area Cost slack

1.00 pu

1.01 pu

1.04 pu1.04 pu

1.04 pu

0.99 pu1.05 pu

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

62 MW

61 MW

44 MW 42 MW 31 MW 31 MW

38 MW

37 MW

80 MW 78 MW

32 MW

33 MW

14 MW

38 MW

39 MW 20 MW 21 MW

42 MW

41 MW

A

MVA

21 MW 20 MW

8078 $/h

4652 $/h 4189 $/h

Case Hourly Cost 16919 $/h

Bus 1 Bus 3 Bus 4

Bus 2 Bus 5

Bus 6 Bus 7

MW106

MW171

MW200 MW198

110 MW

40 Mvar

80 MW 30 Mvar

130 MW 40 Mvar

40 MW

20 Mvar

MW 94

200 MW

0 Mvar200 MW

0 Mvar

AGC ON

AGC ON

AGC ON

AGC ON

AGC ON

80%A

MVA

Splitting large systems requires a careful consideration

of the flow on the island tie-lines as they are opened

Page 20: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Bus Branch versus Node Breaker

• Due to a variety of issues during the 1970’s and 1980’s

the real-time operations and planning stages of power

systems adopted different modeling approaches

20

PlanningUse simplified bus/branch model

PC approach

Use of files

Stand-alone applications

Real-Time OperationsUse detailed node/breaker model

EMS system as a set of integrated applications and processes

Real-time operating system

Real-time databases

Entire data sets and software tools developed around

these two distinct power system models

Page 21: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Circuit Breakers and Disconnects

• Circuit breakers are devices that are designed to clear

fault current, which can be many times normal

operating current

• AC circuit breakers take advantage of the current going

through zero twice per cycle

• Transmission faults can usually be cleared in less than three

cycles

• Disconnects cannot clear fault current, and usually not

normal current. They provide a visual indication the

line is open. Can be manual or motorized.

• In the power flow they have essentially no impedance;

concept of a zero branch reactance (ZBR)21

Page 22: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Google View of a 345 kV Substation

22

Page 23: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Substation Configurations

• Several different substation breaker/disconnect

configurations are common:

• Single bus: simple but a fault

any where requires taking out the

entire substation; also doing breaker

or disconnect maintenance requires

taking out the associated line

23Source: http://www.skm-eleksys.com/2011/09/substation-bus-schemes.html

Page 24: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Substation Configurations, cont.

• Main and Transfer Bus:

Now the breakers can be taken

out for maintenance without

taking out a line, but protection

is more difficult, and a fault

on one line will take out at least two

• Double Bus Breaker:

Now each line is fully protected

when a breaker is out, so high

reliability, but more costly

24Source: http://www.skm-eleksys.com/2011/09/substation-bus-schemes.html

Page 25: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Ring Bus, Breaker and Half

• As the name implies with a ring

bus the breakers form a ring;

number of breakers is same as

number of devices; any breaker can

be removed for maintenance

• The breaker and half has two buses

and uses three breakers for two

devices; both breakers and buses

can be removed for maintenance

25Source: http://www.skm-eleksys.com/2011/09/substation-bus-schemes.html

Page 26: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

• EMS Model

– Used for real-time operations

– Called full topology model

– Has node-breaker detail

• Planning Model

– Used for off-line analysis

– Called consolidated model

by PowerWorld

– Has bus/branch detail

EMS and Planning Models

50 MW

20 Mvar

-30 MW

-18 Mvar

-40 MW

-10 Mvar

10 MW

3 Mvar10 MW

5 Mvar

-30 MW

-18 Mvar

-40 MW

-10 Mvar

10 MW

3 Mvar

10 MW

5 Mvar

26

Page 27: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Node-Breaker Consolidation

• One approach to modeling systems with large numbers

of ZBRs (zero branch reactances, such as from circuit

breakers) is to just assume a small reactance and solve

– This results in lots of buses and branches, resulting in a much

larger problem

– This can cause numerical problems in the solution

• The alterative is to consolidate the nodes that are

connected by ZBRs into a smaller number of buses

– After solution all nodes have the same voltage; use logic to

determine the device flows

27

Page 28: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Node-Breaker Example

28

Case name is FT_11Node. PowerWorld consolidates

nodes (buses) into super buses; available in the Model

Explorer: Solution, Details, Superbuses

Page 29: ECEN 615 Methods of Electric Power Systems Analysis ...overbye.engr.tamu.edu/wp-content/uploads/sites/146/2018/09/ECE615Fall2018_Lect9.pdfLecture 9: Advanced Power Flow, Gaussian Elimination,

Node-Breaker Example

Note there is ambiguity on how much power is flowing

in each device in the ring bus (assuming each device

really has essentially no impedance)29