Page 1: DSE 7310-20 Data Sheet

®DSECONTROL®

MONITORINGWITHINTELLIGENCE.

The DSE7310 and DSE7320 arecontrol modules for single gen-setapplications. The modules havebeen developed from thesuccessful DSE5310 and DSE5320Series and incorporate a numberof advanced features to meet themost demanding on-siteapplications.

The DSE7310 is an Automatic StartControl Module and the DSE7320is an Auto Mains (Utility) FailureControl Module. Both moduleshave been designed to start andstop diesel and gas generatingsets that include electronic andnon-electronic engines. TheDSE7320 includes the additionalcapability of being able to monitora mains (utility) supply.

Both modules include USB, RS232and RS485 ports as well asdedicated DSENet® terminals forexpansion device connectivity.

The modules are simple tooperate and feature a user-friendly menu layout for improvedclarity. Enhanced features includea real time clock for enhancedevent and performancemonitoring, ethernetcommunications for low costmonitoring, mutual standby(DSE7310 only) to reduce enginewear and tear and preventativemaintenance features to detectengine part faults prior to a majorproblem occurring.

FEATURES• Backed up real time clock• 132 x 64 pixel LCD display• Configurable display languages• Five-key menu navigation• Fully configurable via PC software• LED and LCD alarm indication• Engine exercise mode• Configurable start & fuel outputs• kWh monitoring• Automatic load transfer• Eight configurable digital inputs• Six configurable outputs• Configurable timers and alarms• Modbus RTU• Magnetic pick-up• Selected front panel programming• Multiple date and time exercisescheduler

• SMS messaging (additionalexternal modem required)

• Power save mode• User selectable RS232 & RS485communications

• DSENet® compatible• Ethernet communications viaDSE860/865

• Multiple date and timemaintenance scheduler

• Configurable display pages• Programmable loadshedding/acceptance

• Preventative maintenance• kW overload protection• Unbalanced load protection• Flexible sender input• Configurable SCADA output page• True dual mutual standby with loadbalancing timer (DSE7310 only)

• Fan control for additional cooling• ‘Protections Disabled’ facility• Fuel usage monitoring and lowfuel alarm

• Support for up to three remotedisplay units

• Automatic sleep mode• Easy access, configurablediagnostics page shows summaryof output states

• Improved programmable event log(250) showing date and time

• Manual fuel pump control• 3 alternative configurations• Multiple date and time scheduler• 3 Programmable Maintenancealarms with comms alert

• Customisable status screens• Low fuel level alarm delay• Charge alternator fail warning andshutdown alarms with userprogrammable delay

• Independent Earth fault trip• Sleep mode• Load switching (Load sheddingand dummy load outputs)

• Manual speed trim (on CANengines that support this feature)

• Additional display screens to helpwith modem diagnostics

• Security levels – PC software haspassword system to controlaccess to PC software features

• Operator configurable virtual LEDsvisible in SCADA

NEWFEATURES• Additional programmable logic• Improved modem diagnostics• Remote control sources (10) canbe accessed via SCADA

• Additional electrical trip options• Additional start delay functions• Oil pressure values from additionalengines

• Front panel editing of scheduler• Displays kW as % of rated kWsetting

DSE7310 &DSE7320AUTOSTART & AUTOMAINS FAILURECONTROLMODULES (COMMUNICATIONS & EXPANSION)

SPECIFICATION

DCSUPPLY

ALTERNATOR INPUT

MAINS/UTILITY INPUT (DSE7320 ONLY)

CONTINUOUS VOLTAGERATING8V to 35V Continuous

CRANKING DIP PROTECTIONAble to survive 0V for 50mS, providing supplywas at least 10V before dropout and supplyrecovers to 5V. This is achieved without the needfor internal batteries

CHARGE FAIL/ EXCITATION0V to 35V fixed power source 2.5W

MAXIMUM STANDBY CURRENT160mA at 12V 80mA at 24V

MAXIMUM OPERATING CURRENT340mA at 12V 160mA at 24V

RANGE15V - 333V (L-N) 50Hz - 60Hz(Minimum 15V AC Ph-N)

ACCURACY1% of full scale true RMS sensing

SUPPORTED TOPOLOGIES3 phase 4 wire3 phase 3 wire3 phase 4 wire DeltaSingle phase 2 wire2 phase 3 wire L1 & L22 phase 3 wire L1 & L3

RANGE15V - 333V (L-N) 50Hz - 60Hz(Minimum 15V AC Ph-N)

ACCURACY1% of full scale true RMS sensing

SUPPORTED TOPOLOGIES3 phase 4 wire3 phase 3 wire3 phase 4 wire DeltaSingle phase 2 wire2 phase 3 wire L1 & L22 phase 3 wire L1 & L3

CT’S

BURDEN0.5VA

PRIMARY RATING1A - 8000A (user selectable)

SECONDARY RATING1A or 5A secondary (user selectable)

ACCURACYOFMEASUREMENT1% of full load rating

RECOMMENDATIONSClass 1 required for instrumentationProtection class required if using for protection

Continued on page 2

Page 2: DSE 7310-20 Data Sheet

BENEFITS• 132 x 64 pixel ratio makes information easy to read• Real time clock provides accurate event logging• PC software is license free• Set maintenance periods can be configured to maintain optimum engineperformance

• Ethernet communications provides advanced remote monitoring at low cost• Modules can be integrated into building management systems• Preventative maintenance avoids expensive engine down time• Advanced PCB layout ensures high reliability• Robust design• Extensive performance monitoring

OPERATIONThe modules are operated via the START, STOP, AUTO and MANUAL softtouch membrane buttons on the front panel. The DSE7320 also has a TESTbutton. Both modules include load switch buttons. The main menu system isaccessed using the five navigation buttons to the left of the LCD display.

CONFIGURATIONThe modules can be configured using the front panel buttons or by using theDSE Configuration Suite PC software and a USB lead.

COMMUNICATIONSThe DSE7310 & DSE7320 have a number of different communicationcapabilities.

SMSMessagingWhen the module detects an alarm condition, it has the ability to send anSMS message to a dedicated mobile number (s), notifying an engineer of theexact time, date and reason why the engine failed (GSM Modem and SIMCard required).

Remote CommunicationsWhen the module detects an alarm state, it dials out to a PC notifying theuser of the condition (Modem required).

Remote ControlThe module can be controlled remotely using either a GSM Modem, Ethernet viaDSE860/865 or via RS485. Using a modem allows the module to be controlledfrom any distance. Using RS485 limits the distance to 1km (0.6 miles).

BuildingManagementThe module has been designed to be integrated into new and existingbuilding management systems, using RS485.

PC SoftwareThe module has the ability to be configured and monitored from a remotePC, using the PC software and a USB lead.

INPUTS &OUTPUTSAnalogue inputs are provided for oil pressure, coolant temperature and fuellevel. These connect to conventional engine mounted resistive sensor unitsto provide accurate monitoring and protection facilities. They can also beconfigured to interface with digital switch type inputs for low oil pressure andhigh coolant temperature shutdowns. Eight user configurable digital inputsare also included, plus one flexible sender.

Outputs are provided for fuel solenoid, start solenoid and six additionalconfigurable outputs. On these configurable outputs a range of differentfunctions, conditions or alarms can be selected.

INSTRUMENTATIONThe modules provide advanced metering facilities, displaying the information onthe LCD display. The information can be accessed using the five-key menunavigation to the left of the display.

DSENET®

DSENet® is a collection of expansionmodules that have been created towork with DSENet® compatiblecontrol modules. DSENet® allows upto 20 different expansion devices tobe used at a time. The expansionmodules available are:

• DSE2157 Relay Output ExpansionModule

• DSE2130 Input Expansion Module• DSE2548 Annunciator ModuleRemote Display Module

• DSE2510 Remote Display• DSE2520 Remote Display

EVENT LOGThe module includes acomprehensive event log that showsthe most recent 250 alarmconditions and the date and timethat they occurred. This functionassists the user when fault findingand maintaining a generating set.

ELECTRONIC ENGINECOMPATABILITY• CAT• Cummins• Deutz• John Deere• MTU• Perkins• Scania• Volvo• IVECO• Generic• Plus additional manufacturers

RELATEDMATERIALSTITLE PART NO’SDSE7xxx Manual 057-074DSE72xx/73xx PCSoftware Manual 057-077DSE2130 Data Sheet 053-060DSE2157 Data Sheet 053-061DSE2548 Data Sheet 053-062DSE860/865 DataSheet 055-071DSE2510/20 DataSheet 055-074

7310 7320

Generator InstrumentsVolts, Hz, Amps, kW, kVA, Pf, kWh, kVAr,kVArh, KVAh

Engine InstrumentsRPM, Oil Pressure, Coolant Temperature,Hours Run, Charging Voltage, Battery Volts.

Electronic EnginesEnhanced Instrumentation and Engine ECUdiagnostics via electronic engine interface.

Generator InstrumentsVolts, Hz, Amps, kW, kVA, Pf, kWh, kVAr,kVArh, KVAh

Engine InstrumentsRPM, Oil Pressure, Coolant Temperature,Hours Run, Charging Voltage, Battery Volts.

Electronic EnginesEnhanced instrumentation and Engine ECUdiagnostics via electronic engine interface.

Mains/Utility InstrumentsVolts, Frequency, Amps (optional whenCT’s are fitted load side of the line)

SPECIFICATION

MAGNETIC PICKUP

OUTPUTS

DIMENSIONS

VOLTAGERANGE+/- 0.5V minimum (during cranking) to 70V peak

FREQUENCY RANGE10,000 Hz (max)

OUTPUT A (FUEL)15 Amp DC at supply voltage

OUTPUT B (START)15 Amp DC at supply voltage

OUTPUTSC&D8 Amp 250V (Volt free)

AUXILIARYOUTPUTS E,F,G,H2 Amp DC at supply voltage

OVERALL240mm x 181.1mm x 41.7mm9.4” x 7.1” x 1.6”

PANEL CUT-OUT220mm x 160mm8.7” x 6.3”Max panel thickness 8mm ( 0.3”)

ELECTRONICENGINECAPABILITY

ENVIRONMENTAL TESTING STANDARDS

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment,including Electrical Business Equipment

ELECTROMAGNETIC COMPATIBILITYBSEN61000-6-2EMC Generic Immunity Standard for theIndustrial EnvironmentBSEN61000-6-4EMC Generic Emission Standard for theIndustrial Environment

TEMPERATURE (OPERATING)BS EN 60068Test Ab to +70oC 60068-2-2 HotTest Ab to -30oC 60068-2-1 Cold

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn

HUMIDITYBS 2011 part 2.1 60068-2-30Test Cb Ob Cyclic93% RH @ 40oC for 48 hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15gn in 11mS

Page 3: DSE 7310-20 Data Sheet

®

DSE7310 &DSE7320

BATTERY

-VE

+VE CHGALT

OIL

WATER

FUEL

(FLE

XIBLE

)

SENDERCOMMON

FLEXIBLE

8 INPUTSPLANT +VE

GENERATORLOADING RELAY

OUTPUT D

MAINSLOADING

RELAY(7320)OUTPUT C

(ALL MODELS)FLEXIBLE IFJ1939 IN USE

FLEXIBLE IFJ1939 IN USE 4 FET OUTPUTS

ENGINE ECU

MPUSCR

SCR

H L

BATTERY NEGATIVE MUST BE GROUNDED

TERMINALS SUITABLE FOR 22-16 AWG (0.6mm - 1.3mm )FIELD WIRING

TIGHTENING TORQUE = 0.8Nm (7lb-in)

NOTE 1THESE GROUND CONNECTIONS MUST BE ON THEENGINE BLOCK, AND MUST BE TO THE SENDER BODIES.THE GROUND WIRE TO TERMINAL 15 MUST NOT BEUSED TO PROVIDE A GROUND CONNECTION TO ANYOTHER DEVICE

*NOTE 2. 120 R TERMINATING RESISTORMAY BE REQUIRED EXTERNALLYSEE ENGINE MANUFACTURERS LITERATURE

*NOTE 2.

NOTE 1

CT1 CT2 CT3 N COM

51 52 53 55 54 43 44 45 46 56 57 41 42 39 40 28 29 30 47 48 49 50 7 24 22 23

1 2 3 4 5 6 16 17 18 19 15 60 61 62 63 64 65 66 67 8 9 10 11 27 25 26

U V W N

L1 L2 L3

R S T NL1 L2 L3

GEN VOLTS MAINS VOLTS

+ - SCR

DSE NETHIGH SPEED

PERIPHERAL LINKGEN CURRENT

EMERGENCYSTOP

LOW

OIL

PRESSURE

COOLA

NTTEMP

FUELLE

VELSENDER

SENDER

USERCONFIGURABLE

-VEINPUTA

USERCONFIGURABLE

-VEINPUTB

USERCONFIGURABLE

-VEINPUTC

USERCONFIGURABLE

-VEINPUTD

USERCONFIGURABLE

-VEINPUTE

USERCONFIGURABLE

-VEINPUTF

USERCONFIGURABLE

-VEINPUTG

USERCONFIGURABLE

-VEINPUTH

USERCONFIGURABLE

+VEOUTPUTE

USERCONFIGURABLE

+VEOUTPUTF

USERCONFIGURABLE

+VEOUTPUTG

USERCONFIGURABLE

+VEOUTPUTH

FUSEUPTO32

AMPS

MIN

2AMPMAX20

AMP

ANTI-SURGEFU

SE

BATTERY

FUELFUEL

WL

CRANK

CHARGEALT

2 AMPFUSES

CT’s 1 AMP OR 5 AMPSECONDARY

PROTECTION CLASS

P1 P2

S1 S2

MPU

M

2 AMPFUSES

ELECTRICAL INTERLOCK

MECHANICAL INTERLOCK

LOAD

L3

N

L2

L1

L3

N

L2

L1

FROMMAINS(UTILITY)

FROMGENERATOR

FUEL

O/P

A

CRANK

O/P

B

RS485

RS232

SCR

B

A

PROGRAMMING PORT

USB

G

DSE7320 ONLY

MODULE 7310/7320

Page 4: DSE 7310-20 Data Sheet

®

YOUR LOCAL DISTRIBUTOR.

DEEP SEA ELECTRONICS PLCmaintains a policy of continuous development and reserves the right tochange the details shown on this data sheet without prior notice. The contents are intended for guidance only.

055-051/10/09 (5)

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre from both preand post-consumer sources, together with 45% virgin ECF fibre.

DEEP SEA ELECTRONICS INC3230 Williams AvenueRockfordIL 61101-2668 USA

TELEPHONE+1 (815) 316 8706

FACSIMILE+1 (815) 316 8708

[email protected]

WEBSITEwww.deepseausa.com

DEEP SEA ELECTRONICS PLCHighfield HouseHunmanby Industrial EstateHunmanby, North YorkshireYO14 0PH England

TELEPHONE+44 (0)1723 890099

FACSIMILE+44 (0)1723 893303