drainable blade louver in 4” thick frame design - model lec-04 s… · 1855 s. 54th avenue,...

4
STANDARD CONSTRUCTION ALL MATERIAL – EXTRUDED ALUMINUM Alloy (6063-T5), (6063-T6) or (6061-T6) FRAME LEC – 04” (102) thick, is .081 (2.1) extruded aluminum in style #3. BLADES LEC – 04” (102) are .081” (2.1) extruded aluminum, approx. spacing is 4-1/2” (114) @ 45 MAXIMUM SIZE Unlimited, with mullions, structural bracing supplied by others MAXIMUM FACTORY ASSEMBLY SIZE 120” w x 84 H” or 84” w x 120” H (3048 x 2124) or (2134 x 3048) (allows for best handling) (Type of finish may limit maximum single section) MULLION Invisible MINIMUM SIZE 12” w x 12” H (305 x 305) UNDERSIZED 1/4” (6) under ordered size unless specified Exact or Actual SCREEN 3/4” .051” (19 x 1.3) flattened expanded aluminum bird screen no frame FINISH Mill OPTIONAL CONSTRUCTION FRAME – Available in a heavier extrusion of .125” (3.2) BLADES – Available in a heavier extrusion of .125” (3.2) SCREEN - Many styles available please consult screen listing FINISH – Air-dry primer, polyurethane, epoxy, or enamel. Baked epoxy, powder coat Anodize or Kynar 500 MULLION – Visible for architectural preference SPECIAL PURPOSE CONSTRUCTION Special Shapes; Triangle, Trapezoid, etc. Fully welded construction Security bars Filter racks Hinged as walk through door or for swing out access Sleeved for ductwork connection DATE ARCHITECT/ENGINEER CUSTOMER PROJECT ITEM QTY W H Products Group A division of Safe Air of Illinois EXTRUDED ALUMINUM LOUVER Drainable Blade Louver in 4” thick frame design - Model LEC-04 Design Features – High Performance patented design allowing maximum airflow with minimum outside element or water penetration. www.elouver.com LEC-04 4/06 TYPICAL SCREEN STYLES Expanded Aluminum Wire Mesh Standard FRAME STYLE MULLION STYLES Visible Invisible Point of water penetration 879 fpm (268) Free area a 48 x 48 section 50% DEPENDABLE PRODUCTS SINCE 1955 DOWCO PRODUCTS GROUP Engineering and General Offices 1855 South 54 th Avenue, Cicero, Illinois 60804 Phone 708-652-9100 FAX 708-652-9158 1- Flange (1.5”) 3 – Box 4 - Glazing 8- Box with 9 - Flange Adapter Sill Extension w/ Sub Frame PERFORMANCE Products Group A division of Safe Air of Illinois DOWCO PRODUCTS GROUP Certifies that the LEC-04 louver shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publications 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and ratings and water penetration ratings.

Upload: others

Post on 22-Aug-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Drainable Blade Louver in 4” thick frame design - Model LEC-04 S… · 1855 S. 54th Avenue, Cicero, Il. 60804 Tel. 708-652-9100 / Fax 708-652-9158 August 2000 METAL PANEL WALL FLANGE

STANDARD CONSTRUCTIONALL MATERIAL – EXTRUDED ALUMINUM Alloy (6063-T5), (6063-T6) or (6061-T6)FRAME

LEC – 04” (102) thick, is .081 (2.1) extruded aluminum in style #3.BLADES

LEC – 04” (102) are .081” (2.1) extruded aluminum, approx. spacing is 4-1/2” (114) @ 45MAXIMUM SIZE

Unlimited, with mullions, structural bracing supplied by othersMAXIMUM FACTORY ASSEMBLY SIZE

120” w x 84 H” or 84” w x 120” H (3048 x 2124) or (2134 x 3048) (allows for best handling)

(Type of finish may limit maximum single section)MULLION

InvisibleMINIMUM SIZE

12” w x 12” H (305 x 305)UNDERSIZED

1/4” (6) under ordered size unless specified Exact or ActualSCREEN

3/4” .051” (19 x 1.3) flattened expanded aluminum bird screen no frameFINISH

Mill

OPTIONAL CONSTRUCTIONFRAME – Available in a heavier extrusion of .125” (3.2)BLADES – Available in a heavier extrusion of .125” (3.2)SCREEN - Many styles available please consult screen listingFINISH – Air-dry primer, polyurethane, epoxy, or enamel. Baked epoxy,powder coat Anodize or Kynar 500

MULLION – Visible for architectural preference

SPECIAL PURPOSE CONSTRUCTIONSpecial Shapes; Triangle, Trapezoid, etc.Fully welded constructionSecurity barsFilter racksHinged as walk through door or for swing out accessSleeved for ductwork connection

DATE ARCHITECT/ENGINEER CUSTOMER

PROJECT

ITEM QTY W H

Products GroupA division of Safe Air of Illinois EXTRUDED ALUMINUM LOUVER

Drainable Blade Louver in 4” thick frame design - Model LEC-04Design Features – High Performance patented design allowing maximum airflow with minimum outside element or water penetration.

www.elouver.com LEC-04 4/06

TYPICAL SCREEN STYLES

Expanded Aluminum Wire Mesh Standard

FRAME STYLE

MULLION STYLES

Visible Invisible

Point ofwater penetration

879 fpm (268)Free area a48 x 48 section

50%

DEPENDABLE PRODUCTS SINCE 1955DOWCO PRODUCTS GROUP

Engineering and General Offices

1855 South 54th Avenue, Cicero, Illinois 60804 Phone 708-652-9100 FAX 708-652-9158

1- Flange (1.5”) 3 – Box 4 - Glazing 8- Box with 9 - FlangeAdapter Sill Extension w/ Sub Frame

PERFORMANCE

Products GroupA division of Safe Air of Illinois

DOWCO PRODUCTS GROUPCertifies that the LEC-04 louvershown herein is licensed to bear theAMCA Seal. The ratings shown arebased on tests and proceduresperformed in accordance with AMCAPublications 511 and comply with therequirements of the AMCA CertifiedRatings Program. The AMCACertified Ratings Seal applies to airperformance and ratings and waterpenetration ratings.

Page 2: Drainable Blade Louver in 4” thick frame design - Model LEC-04 S… · 1855 S. 54th Avenue, Cicero, Il. 60804 Tel. 708-652-9100 / Fax 708-652-9158 August 2000 METAL PANEL WALL FLANGE

1.00.90.80.70.6

0.5

0.4

0.3

0.2

0.10.090.080.070.060.05

0.04

0.03

0.02

0.01

200 500 1000 2000 3000

CALCULATING PRESSURE LOSSBased upon a given flow rate (in CFM), the flowing pressure loss maybe determined from the “air performance” graph, knowing the sq. ft. offree area of the louver. Alternately, the free area may be determinedbased upon a volumetric flow rate and a maximum pressure loss.Utilizing the “air performance” graph.

_________in. W.C. Max. Pressure Loss Intake or Exhaust

_________FPM (Free Area Velocity From “Air Performance” Graph)

_____CFM / ____ FPM Free Area Velocity = _____Sq. Ft. Free Area

CALCULATING MAXIMUM AIRFLOW BEFORE WATER PENETRATION

The “free area flow rate” at which water penetration commences (.01 oz. ofwater) is established at, 879 fpm (268), and will vary depending upon actualweather conditions. The “water penetration” graph illustrates the results ofactual laboratory test on a 48” x 48” (1219 x 1219) test sample subjected tohypothetical rainfall conditions. To determined the free area (in sq. ft.) basedon upon a known volumetric flow rate in CFM;_____________CFM/_____________FPM=_________SQ. FT. FREE AREA(System Requirements)

INTAKE FREE AREA VELOCITY (fpm)

DBE-04 PERFORMANCE SPECIFICATIONS

FREE AREA VELOCITY (fpm)879 fpm (268) beginning of water penetration

W I D T HH

E I

G H

T

Water Penetration Graphin oz. of water per sq. ft. of

free area over a 15 min. test period

www.elouver.com LEC-04 4/06

AIR PERFORMANCE

All tests performed at an independent laboratory and based on AMCA standard 511 – 91 for air performance and water penetration.

PRES

SUR

E LO

SS IN

CH

ES W

.C.

900 1000 1100 1200

.30

.20

.10

0

Oun

ces

of w

ater

per

sq.

ft. o

f fre

e ar

ea

FREE AREA CALCULATIONS IN SQ. FT .

Beginningpoint of waterpenetration

.01 .02 .05 .1 .2 . 3 (H20)

Intake Mode

Products GroupA division of Safe Air of Illinois

879 900 929 951 972 985 (fpm)

INCHES 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 12012 .28 .44 .61 .77 .94 1.10 1.27 1.43 1.60 1.76 1.93 2.10 2.26 2.43 2.59 2.76 2.92 3.09 3.2518 .54 .87 1.19 1.52 1.84 2.17 2.49 2.82 3.15 3.47 3.80 4.12 4.45 4.77 5.10 5.42 5.75 6.07 6.4024 .72 1.16 1.59 2.02 2.46 2.89 3.33 3.76 4.19 4.63 5.06 5.50 5.93 6.36 6.80 7.23 7.66 8.10 8.5330 1.00 1.60 2.20 2.80 3.40 4.00 4.59 5.19 5.79 6.39 6.99 7.59 8.19 8.79 9.39 9.99 10.5

911.19

11.7936 1.27 2.02 2.78 3.54 4.30 5.06 5.82 6.58 7.34 8.10 8.86 9.62 10.3

811.13

11.89 12.65 13.41 14.17 14.9342 1.45 2.31 3.18 4.05 4.92 5.78 6.65 7.52 8.39 9.25 10.1

210.99

11.86 12.73 13.59 14.46 15.33 16.20 17.0648 1.72 2.75 3.79 4.82 5.85 6.89 7.92 8.95 9.99 11.0

2 12.05 13.09 14.12 15.15 16.19 17.22 18.25 19.28 20.32

54 1.99 3.18 4.37 5.57 6.76 7.95 9.15 10.34

11.53 12.73 13.92 15.11 16.30 17.50 18.69 19.88 21.08 22.27 23.4660 2.17 3.47 4.77 6.07 7.38 8.68 9.98 11.28 12.58 13.88 15.18 16.49 17.79 19.09 20.39 21.69 22.99 24.29 25.60

66 2.44 3.91 5.38 6.85 8.31 9.78 11.25 12.71 14.18 15.65 17.11 18.58 20.05 21.52 22.98 24.45 25.92 27.38 28.8572 2.71 4.34 5.97 7.59 9.22 10.85 12.47 14.10 15.73 17.35 18.98 20.61 22.23 23.86 25.49 27.11 28.74 30.37 31.9978 2.89 4.63 6.36 8.10 9.83 11.57 13.30 15.04 16.77 18.51 20.25 21.98 23.72 25.45 27.19 28.92 30.66 32.39 34.1384 3.17 5.07 6.97 8.87 10.77 12.67 14.57 16.47 18.37 20.27 22.18 24.08 25.98 27.88 29.78 31.68 33.58 35.48 37.3890 3.43 5.50 7.56 9.62 11.68 13.74 15.80 17.86 19.92 21.98 24.04 26.10 28.16 30.22 32.28 34.34 36.41 38.47 40.5396 3.62 5.78 7.95 10.1

2 12.29 14.46 16.63 18.80 20.97 23.14 25.31 27.48 29.64 31.81 33.98 36.15 38.32 40.49 42.66

Page 3: Drainable Blade Louver in 4” thick frame design - Model LEC-04 S… · 1855 S. 54th Avenue, Cicero, Il. 60804 Tel. 708-652-9100 / Fax 708-652-9158 August 2000 METAL PANEL WALL FLANGE

www.elouver.com 1855 S. 54th Avenue, Cicero, Il. 60804 Tel. 708-652-9100 / Fax 708-652-9158 August 2000

METAL PANEL WALL FLANGE FLANGE W/ SUBFRAME

TYPICAL INSTALLATIONS

WOOD CONCRETE GLAZING ADAPTER (FLUSHED)

Products GroupA division of Safe Air of Illinois

GLAZING ADAPTER (RECESSED)

Page 4: Drainable Blade Louver in 4” thick frame design - Model LEC-04 S… · 1855 S. 54th Avenue, Cicero, Il. 60804 Tel. 708-652-9100 / Fax 708-652-9158 August 2000 METAL PANEL WALL FLANGE

Dependable Product Since 1955

SUGGESTED SPECIFICATIONS LOUVER MODEL: LEC-04/ SERIES GENERAL:

Furnish and install at locations where indicated on the drawings or as described in schedules with high performance weather-resistant drainable louver Model LEC-04/series as manufactured by DOWCO Products Group, 1855 South 54th Ave., Cicero, IL. 60804. Tel. 708-652-9100, Fax 708-652-9158 (www.safeair-dowco.com/contact.asp). All louvers shall manufactured under ARRA – American Recovery Reinvestment Act, “Buy American Stimulus Provision” and shall have a factory certified Union Label. Submit complete submittals or shop drawings to the architect/engineer for approval. All opening sizes shall be field verified prior to fabrication. MATERIAL:

Frames and blades thickness shall be .081" (2.96mm) extruded aluminum alloy 6063-T5, T52 or T6. Sill and jamb frames shall be caulked to prevent water penetration to interior wall construction. Blades are attached to jamb frames by means of plated steel screws. All fasteners to be aluminum, plated carbon steel, or stainless steel. Frames shall have integral caulking slot and retaining beads. Stationary louvers shall be furnished with bird and / or insect screens, supports and finishes as specified and as required for a complete installation. PERFORMANCE:

Louvers shall be tested in accordance with AMCA Standard 500-L and licensed under the AMCA Certified Ratings Seal for both air performance and water penetration. The louvers shall have a minimum of 7.92 ft2. (0.736 m2) (50%) free area on a 48 inch x 48 inch (1219 x 1219) louver. The rating shall show a maximum water penetration of .01 oz. at an air flow of 879 FPM (4.47 m/s) free area velocity based on a 15 minute test duration. The Static Pressure Loss shall not be more than 0.18 in. H2O of water gauge (0.04 kPa) at an air flow of 1000 FPM (5.08 m/s) free area velocity. STRUCTURAL DESIGN CRITERIA:

Louvers shall be designed and furnished with all the supports required to withstand a negative and positive wind load of 25 psf (1.20 kPa) @ delta L/180 deflection based on the maximum single section of 120 x 84 (3048 x 2135) or 84 x 120 (2135 x 3048). Larger sizes and higher wind loads require additional structural supports. Due to the variation of job requirements and local building codes, structural supports shall be analyzed on a job to job basis. FINISH:

All louvers shall be finished with DOWCO’s Kynar 500 with 100% resin Fluoropolymer coating. Finish to adhere to a 4H hardness rating. All finishing procedures shall be one continuous operation and the coating shall meet or exceed all requirements of AAMA Specification 2605-05 “Voluntary Specification for High Performance Organic Coatings on Architectural Extrusions and Panels.” Manufacturer shall supply a standard 5-year limited warranty against failure and excessive fading or upon request a 20-year limited warranty against failure and excessive fading.

Products Group A division of Safe Air of Illinois

www.elouver.com 1855 S. 54th Avenue, Cicero, Il. 60804 Tel. 708-652-9100 / Fax 708-652-9158 August 2000