FM Global
PUBLIC
Fire Protection to
FM Global Standards
FG-Sprinklerkonferansen 2016
Steve Plummer, Group Manager Field Engineering
Nordic Region
![Page 2: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/2.jpg)
FM Global
PUBLIC
Overview
FM Global
Fire protection
– Today’s challenges
– Project handling
– Nonstorage and storage applications
New protection options
![Page 3: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/3.jpg)
FM Global
PUBLIC
Speciality focus
Mutuality
Engineering
Business risk consulting
Global delivery
FM Approvals
![Page 4: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/4.jpg)
FM Global
PUBLIC
Today's Challenges
Business is global
Supply chain risks are growing
Business is changing
– Building design, larger and higher
– New storage solutions
– Increasing amounts of plastics
– Integration of operations
Understanding the client’s
operations and innovation in
insurance coverage and
engineering solutions are critical
![Page 5: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/5.jpg)
FM Global
PUBLIC
![Page 6: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/6.jpg)
FM Global
PUBLIC
![Page 7: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/7.jpg)
FM Global
PUBLIC
The Full Impact of Fires – Iceberg
Property & Business Interruption
Supply Chain
Community
Environment
Life Safety
Macro Economic
Customers
Market
Share
Reputation
![Page 8: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/8.jpg)
FM Global
PUBLIC
Project Handling
What design and installation standard does the client (or
other stakeholders) want to work to?
Nonstorage or Storage application?
– Storage >20m2 or >1.5m high plastics or >3m ordinary
combustibles, protect according to Data Sheet 8-9
Occupancy specific data sheets; hydraulic or cutting oil,
paper mills, woodworking, chemical plants, ignitable liquids
etc
![Page 9: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/9.jpg)
FM Global
PUBLIC
Nonstorage Protection
FM Global Data Sheet 3-26 & 2-0
K80 sprinklers or water-mist is acceptable for HC-1
occupancy
Minimum K115 sprinklers in manufacturing areas (HC-2)
– HC-3 occuancy, minimum K160 sprinklers
– Ceiling heights >18 m, use K360 sprinklers
Extended coverage (EC) heads allow sprinkler spacings
up to 36 m2, but beware:
– Ceiling slopes >10°and
– Obstructed ceiling construction
![Page 10: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/10.jpg)
FM Global
PUBLIC
![Page 11: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/11.jpg)
FM Global
PUBLIC
Obstructions - Nonstorage
Obstructions to sprinkler discharge
“Individual obstructions” ≥1.2m wide
Obstructions can only be considered
an “individual obstruction” if less
than 3 diameters apart
Spacing of sprinklers under non-flat
obstructions should be 1.2m or
install a flat barrier
![Page 12: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/12.jpg)
FM Global
PUBLIC
Storage Protection
Ceiling only or ceiling and in-rack sprinklers?
Ceiling Only
– FM Global Data Sheets 8-9 & 2-0
– Storage sprinklers (“ESFR” or “large-drop”), large
orifice quick response storage heads
– Flexible and economic
– FM Global standards require minimum K160
sprinklers for storage applications
![Page 13: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/13.jpg)
FM Global
PUBLIC
![Page 14: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/14.jpg)
FM Global
PUBLIC
Storage Protection
Constraints of ceiling only
protection– Limited to 12 – 13.5m buildings
– Obstructions
– Lack of flue spaces
– Solid shelves
– Open top containers
Must not stop water getting
to seat of fire
![Page 15: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/15.jpg)
FM Global
PUBLIC
Storage Protection
Ceiling and in-rack automatic sprinklers (IRAS)
– Can be used for any storage height
– Very effective protection – suppression usually achieved
– New options can keep water supply to the same size as
for ceiling only
![Page 16: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/16.jpg)
FM Global
PUBLIC
Storage Protection
In-rack sprinkler protection
– Minimum K115 orifice heads, quick-response
– Constraints
• Heads need to be located in the correct position in the
racks
• Face sprinklers needed for some solutions
• Need to be removed and reinstalled if racks are
moved
![Page 17: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/17.jpg)
FM Global
PUBLIC
![Page 18: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/18.jpg)
FM Global
PUBLIC
![Page 19: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/19.jpg)
FM Global
PUBLIC
New storage protection options
Factory Mutual began testing sprinklers in 1884
In the past 30 years, the focus has been on developing
ceiling sprinkler protection
– FM Global began research into “large drop” sprinklers in
the 1970s and “ESFR” sprinklers in the 1980s
![Page 20: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/20.jpg)
FM Global
PUBLIC
New storage protection options
Most testing of in-rack sprinkler designs was done in the
1960s and 1970s using K80 and K115 heads
Research into “ESFR” in-racks began in the late 2000s
New protection options published in FM Global Data Sheet
8-9 in May 2015
Alternative in-rack sprinkler designs can be used for all
commodities covered by Data Sheet 8-9 but must be open
frame racks with adequate flue spaces (no solid shelves
and no open top containers)
![Page 21: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/21.jpg)
FM Global
PUBLIC
K200 to K320 pendent sprinklers in the flue and face in
every transverse flue (at uprights only for face sprinklers if
no more than 2.6m apart)
![Page 22: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/22.jpg)
FM Global
PUBLIC
New storage protection options
Vertical intervals of 9 m or 12 m
5 to 10 heads (5 in two adjacent rack) at 250 to 455
LPM/head
Treat top level of in-racks as the “floor” for the purposes of
designing the ceiling system
Do not need to balance in-rack sprinklers with ceiling, nor
account for them flowing simultaneously
150 mm clearance needed from top of storage to sprinkler
deflector
![Page 23: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/23.jpg)
FM Global
PUBLIC
Typical Layout for Uncartoned Plastics and Cartoned
Expanded Plastics
![Page 24: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/24.jpg)
FM Global
PUBLIC
Typical Layout for Cartoned Unexpanded Plastics and
Lower Hazard Commodities
![Page 25: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/25.jpg)
FM Global
PUBLIC
![Page 26: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/26.jpg)
FM Global
PUBLIC
New storage protection options
Protection for unlimited building heights
Lower cost with far fewer levels of in-rack sprinklers
(every 9m or 12m)
Reduced vulnerability to damage
Efficient fire control
Lower water demands
Reduced water usage and environmental impact
![Page 27: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/27.jpg)
FM Global
PUBLIC
Summary
FM Global
Fire protection
– Today’s challenges
– Project handling
– Nonstorage and storage applications
New protection options
![Page 28: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/28.jpg)
FM Global
PUBLIC
Resources
www.fmglobaldatasheets.com
www.approvalguide.com
www.fmglobal.com
![Page 29: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/29.jpg)
FM Global
PUBLIC
![Page 30: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/30.jpg)
FM Global
PUBLIC
FM Global Seminar
Teknologisk Institutt Haugesund
1st – 2nd June – Ensuring Effective Sprinkler
Installations: Designing and Installing Automatic
Sprinkler Systems to FM Global Standards
![Page 31: Working to FM Global Standards - fgsikring.no · Most testing of in-rack sprinkler designs was done in the 1960s and 1970s using K80 and K115 heads Research into “ESFR” in-racks](https://reader034.vdocuments.mx/reader034/viewer/2022042023/5e7bc911c8494b07f513e02d/html5/thumbnails/31.jpg)
FM Global
PUBLIC
Questions?