The CIMON line of Communication Modules allows the user to incorporate additional units into a system without having to worry about numerous communication protocols. The communication line offers RS232C, RS422/285, Ethernet, BACnet, Profibus, CDMA and CANopen which allows for the integration of a SCADA system to alert users of all facets of the production line. The RS232C and RS422/485 units are utilized for communication with production line controllers/drives via MODBUS or any other ASCII based protocol. Ether-net provides high speed up to 100Mbps so the user can forward real-time data to a Super-visory Software. The Profibus communication module enables seamless communication between different manufacturers devices. The BACnet module can be used in various ap-plications such as HVAC control systems, lighting control systems, security systems and many more.
L011065
PLC-COM-CM1 SeriesPLC-COM-CM1 Series• MultiDropConfigurationofupto32Units• BaudRatesRangefrom300to38,400bps• 1:1/1:N/N:M(RS-422)CommunicationisSupported• Full-Duplex(RS-422)andHalf-Duplex(RS-485)areSupported• EthernetModuleSupportsARP,ICMP,IP,TCPandUDP• High-SpeedDataCommunicationAmongModules• Communicationwith4StationsSimultaneously.• SupportsDNP3.0Protocol(PLC-COM-CM1-EC01DNP)
GE
NE
RA
L S
PE
CIF
ICAT
ION
S
Items Specification ReferenceOperating Temp -10 ~ 65°CStorage Temp -25 ~ 80°C
Operating Humidity 5 ~ 95% RH, (Non-condensing)Storage Humidity 5 ~ 95% RH, (Non-condensing)
Vibration
Intermittent Vibration -
IEC 61131-2
Frequency Acceleration Amplitude Sweep10 < f
< 57Hz - 0.075
X, Y, ZEach direction,
10 times
57 < f< 150Hz 9.8m/s2 {1G} -
Continuous VibrationFrequency Acceleration Pulse Width
10 < f< 57Hz - 0.035mm
57 < f< 150Hz 4.8m/s2 {0.5G} -
Shocks• Peak acceleration: 147 m/s2
• Duration: 11ms• Pulse wave type: Half-sine (3 times each X, Y, Z)
IEC61131-2
Impulse Noise
Square wave impulse noise + 2,000V KDT Standard
Electrostaticdischarge Voltage:4kV (Contact discharge) IEC 61131-2
IEC 1000-4-2Radiated electro-
magnetic field noise 27 ~ 500MHz, 10V/m IEC 61131-2IEC 1000-4-3
Fast Transient/Burst Noise
Power Digital I/O(24V or more)
Digital I/O (24V or less)
Analog I/O Comm. Interface
IEC61131-2IEC 1000-4-4
2kV 1kV 0.25kVOperation Ambience Free from corrosive gases and excessive dust
Altitude 2,000m or lessPollution Degree 2 or lessCooling Method Air cooling
910 East Orangefair Ln. Anaheim, CA 92801 Tel. (714) 992-6990 Fax. (714) 992-0471 www.anaheimautomation.com
SE
RIA
L M
OD
ULE
SP
EC
IFIC
ATIO
NS
PLC-DIO-CM1 Digital InputsPLC-DIO-CM1 Digital Inputs
Model PLC-COM-CM1-SC02A PLC-COM-CM1-SC01A PLC-COM-CM1-SC01B
Interface RS232C / 422 / 485 RS232C RS422 / 485
Communication Method
Null Model Direct communication between a PC and RS232C/422 port
Leased-Line Modem Communication using a leased-line modem
Dial-up Modem Remote communication using a dial-up modem
Operation Method
User Protocol Communication using user protocol
HMI Protocol Communication using exclusive protocol
MODBUS Protocol Communication using Modicon protocl
Graphic Loader Module Controls a PLC, using a linking function in the CICON software
Data Type
Data Bits 7 or 8
Stop Bits 1 or 2
Parity Even / Odd / None
Synchronous Type Asynchronous
Baud Rates 300 / 600 / 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 38,400 bps
Modem Link Function Long-distance communication linking modem
Serial Communication Modules
Cable SpecificationsTo minimize the noise received a twisted-pair cable for RS-232 is to be used for the following communications RS-232C/422/485. If using RS-422 communication, a ter-mination resistor is to be connected on each end of the cable. A termination resistor protects the signal from distortion in the event of long distance communication. The termination resistor should be 120Ω and rated for 1/2 a watt.
CO
MM
UN
ICAT
ION
PIN
OU
TS
Connector Pin # Name Description
1 DCD Data Carrier Detect
2 RD Receive Data
3 TD Transmit Data
4 DTR Data Terminal Ready
5 SG Signal Ground
6 DSR Data Set Ready
7 RTS Request To Send
8 CTS Clear To Send
9 RI Ring Indicator
RS232C
Connector Pin No. Name Description
1 SDA Send Data A
2 SDB Send Data B
3 RDA Receive Data A
4 RDB Receive Data B
5 SG Signal Ground
6 FG Field Ground
RS-422/485
910 East Orangefair Ln. Anaheim, CA 92801 Tel. (714) 992-6990 Fax. (714) 992-0471 www.anaheimautomation.com
PLC
-CO
M-C
M1-
SC
02A
LED Indicator - Indicates operation status
RS232C - used to connect with an outer device
RS422/485 - used to connect with an outer device
PLC-COM-CM1-SC02A
PLC
-CO
M-C
M1-
SC
01A
PLC-DIO-CM1 Digital OutputsPLC-DIO-CM1 Digital Outputs
910 East Orangefair Ln. Anaheim, CA 92801 Tel. (714) 992-6990 Fax. (714) 992-0471 www.anaheimautomation.com
LED Indicator - Indicates operation status
RS232C - used to connect with an outer device
PLC-COM-CM1-SC01A
910 East Orangefair Ln. Anaheim, CA 92801 Tel. (714) 992-6990 Fax. (714) 992-0471 www.anaheimautomation.com
PLC
-CO
M-C
M1-
SC
01B
LED Indicator - Indicates operation status
RS422/485 - used to connect with an outer device
PLC-COM-CM1-SC01B