Seal for Civil Drawings
Seal for Architectural Drawings
Seal for Electrical Drawings
Seal for Mechanical Drawings
Seal for Plumbing Drawings
Seal for Structural Drawings
46 Harriman DriveAuburn, ME 04210
207.784.5100
123 Middle StreetPortland, ME 04101
207.775.0053
LIST OF DRAWINGS
Seal for Fire Protection Drawings
NOT USED
NOT USED
NOT USED
NOT USED
Harriman Project No.
Harriman Associatesc
33 Jewell Court, Suite 101Portsmouth, NH 03801
603.626.1242
170 Milk Street, Suite 5Boston, MA 02109‐3438
617.426.5050
PRELIMINARY NOT FOR CONSTRUCTION
FINAL REVIEW05-31-18
DURHAM, NEW HAMPSHIRE
16642
G00.1
2018
COVER SHEET
UNH NECBOILER UPGRADESPROJECT ID: 2016-0402
G00.1 COVER SHEET
PLUMBING DRAWINGSP00.1 LEGEND, SCHEDULES, DETAIL & GENERAL NOTESP20.1 SUPPLY PLANS
MECHANICAL DRAWINGSM00.1 LEGEND & GENERAL NOTESM05.1 MECHANICAL DEMOLITIONM10.1 MECHANICALM30.1 DETAILSM30.2 DETAILSM40.1 SCHEDULES
ELECTRICAL DRAWINGSE00.1 ELECTRICAL LEGEND, NOTES AND SCHEDULESE05.1 BASEMENT FLOOR PART PLAN EXISTING CONDITIONSE20.1 BASEMENT FLOOR PART PLAN POWER AND SYSTEMS
RFX# 100299NEC Drawings
LEGEND
CHECK VALVE
SHUT-OFF VALVE
CAP
DN DOWN
AFF ABOVE FINISHED FLOOR
BFF BELOW FINISHED FLOOR
TYP. TYPICAL
TRANSITION
CIRCULATING PUMP
THERMOMETER
DCP-X DOMESTIC CIRCULATING PUMP
ET-X EXPANSION TANK
FD-X FLOOR DRAIN
COLD WATER PIPING ABOVE FINISHED FLOORCW
EXISTING COLD WATER PIPING ABOVE FINISHED FLOORXCW
EXISTING HOT WATER PIPING ABOVE FINISHED FLOORXHW
HOT WATER PIPING ABOVE FINISHED FLOORHW
EXISTING HOT WATER RETURN PIPING ABOVE FINISHED FLOORXHWR
HOT WATER RETURN PIPING ABOVE FINISHED FLOORHWR
HOT WATER HOSE BIBB
FREEZE PROOF WALL HYDRANT
PIPE DROP
PIPE RISE
EXISTING ABOVE FINISHED FLOOR PIPING TO BE DEMOLISHED
NATURAL GAS PIPING ABOVE FINISHED FLOORG
FINISHED FLOOR
3/4" CW
WHTR-1 MOUNTED IN CABINET. SET TO DELIVER 120°F
3/4" HW
HW TO SERVE EXISTING UTILITY SINK SEE P20.1
FOR ROUTING
TV-1 SET TO DELIVER 110°F
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:5/
31/2
018
8:30
:33
AM
DURHAM, NEW HAMPSHIRE
16642
P00.1
CG
MAM
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
LEGEND, SCHEDULES,DETAIL & GENERAL
NOTES
2018
WATER HEATER SCHEDULEBASIS OF DESIGN WATER HEATER SPECIFICATIONS REFER TO THE SPECIFICATIONS FOR APPROVED EQUALS AND DETAILED DESCRIPTIONS
TAG MANUFACTURER MODEL FUEL TYPERECOVERY
(GPH)BRANCH SIZE ELECTRICAL
NOTESCW HW VOLTS PHASEWHTR-3 BOSCH TRONIC
MODEL ES4ELECTRIC 6.8 @ 90°F RISE 1/2" 1/2" 120 V 1
TEMPERING VALVE SCHEDULEBASIS OF DESIGN TEMPERING VALVE SPECIFICATIONS REFER TO THE SPECIFICATIONS FOR APPROVED
EQUALS AND DETAILED DESCRIPTIONSTAG MANUFACTURER MODEL CW HW TW NOTESTV-1 APOLLO 34ALF213PR 1/2" 1/2" 1/2" SET TO DELIVER 110 °F HW
GENERAL NOTES
1 DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF THE WORK.REVIEW THE GENERAL NOTES, SPECIFICATIONS AND PLANS FOR ADDITIONAL REQUIREMENTSTHAT MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTIONDOCUMENTS. NOTIFY THE ARCHITECT OF ANY CONFLICTS ORDISCREPANCIES PRIOR TO SUBMISSION OF BID.
2 VERIFY LOCATION AND DEPTH OF UTILITIES AT ALL POINTS OF CONNECTION INDICATED ONDRAWINGS BEFORE START OF PROJECT.
3 COORDINATE ALL WORK WITH OTHER TRADES AND CONTRACTORS. COORDINATE PIPINGINSTALLATION WITH STRUCTURAL GRADE BEAMS, FOOTINGS, COLUMN PIERS, ETC. SLEEVEPIPING THROUGH GRADE BEAMS, FOOTING, ETC. WHERE REQUIRED AND AS NOTED ONPLANS. COORDINATE SLEEVE INSTALLATIONS WITH THE ARCHITECT, STRUCTURAL ENGINEER,STRUCTURAL CONTRACTOR AND GENERAL CONTRACTOR BEFORE CONCRETE IS INSTALLED.PIPING INVERTS AND SLOPE SHALL BE CLOSELY COORDINATED TO AVOID CONFLICTS WITHALL OTHER TRADES BELOW SLAB WORK.
4 COORDINATE PIPE ROUTING AWAY FROM ELECTRICAL PANELS. DO NOT ROUTE PIPING OVERELECTRICAL PANELS.
5 PIPING IN FINISHED AREAS SHALL BE ROUTED CONCEALED; EXPOSED PIPING, WHERENECESSARY, SHALL BE ROUTED AS HIGH AS POSSIBLE AND TIGHT TO WALLS.
6 REFER TO INSTALLATION SCHEDULE DATA FOR THE SIZE OF PIPING CONNECTIONS ANDMOUNTING HEIGHTS OF EACH FIXTURE.
7 ALL PLUMBING FIXTURE SHUT-OFF AND/OR BALANCING VALVES INSTALLED IN PIPE CHASESSHALL BE ACCESSIBLE FROM JUST ABOVE THE CEILING LINE OR ACCESS DOORS PROVIDEDLOW IN CHASE WALL.
8 VENT AND WATER PIPING SHALL PITCH TO DRAIN.9 CLEAN FAUCET AERATORS AND PIPE STRAINERS PRIOR TO TURNING BUILDING OVER TO THE
OWNER.10 VALVES SHALL BE LINE SIZE UNLESS OTHERWISE NOTED.11 THE TERM "PROVIDE" SHALL MEAN "TO FURNISH, INSTALL AND CONNECT COMPLETELY".12 ENTIRE PLUMBING INSTALLATION SHALL BE IN COMPLIANCE WITH ALL CURRENT LOCAL, STATE
AND FEDERALCODES AND STANDARDS.
13 OSHA RULES, REGULATIONS AND REQUIREMENTS, AND ANY STATE AND LOCALREQUIREMENTS FOR SAFETY SHALL BE FOLLOWED BY THE CONTRACTOR
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
NO SCALE1 WATER HEATER PIPING DETAIL
87 9 10 11
12
13
E
D
C
B
F
G
654
REMOVE 4" HW& 2" HWR DOMESTIC
PIPING TO ADAMS TOWER
EXISTING 4" CW TO ADAMS TOWER SHALL REMAIN
REMOVE EXISTINGHW DN TO SINK. SINK
SHALL REMAIN
REMOVE EXISTINGAJAX SEMI-INSTANTANEOUS WATER HEATER WITH ASSOCIATED PUMPS, PIPING & ACCESSORIES.(TYP OF 2)
REMOVE EXISTINGHW PIPING & ASSOCIATED ACCESSORIES
EXISTING HW & HWR PIPING& ASSOCIATED ACCESSORIES
REMOVE EXISTINGHW PIPING UP TO DECK& CAP. PROVIDE LOW POINT DRAIN VALVE AT DECK
EXISTING DOMESTIC CW TO REMAIN
REMOVE EXISTINGCW BACK TO VALVE
REMOVE EXISTINGCIRCULATING PUMP& ASSOCIATED ACCESSORIES
87 9 10 11
12
13
E
D
C
B
F
G
654XC
W- 4
"
XCW- 1/2"
WHTR-3
MAKE FINAL CONNECTIONS TO SINK FROM WATER HEATER
CONNECT 1/2" CW TO EXISTING CWTV-1
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic Scale
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:5/
31/2
018
8:30
:41
AM
DURHAM, NEW HAMPSHIRE
16642
P20.1
CG
MAM
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
SUPPLY PLANS
2018
SCALE: 1/8" = 1'-0"1 DEMOLITION SUPPLY PLANSCALE: 1/8" = 1'-0"2 SUPPLY PLAN
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
AMS
TIGHT SHUT-OFF VALVE
FD (3 HR) FIRE DAMPER (3 HOUR RATED)
S2 4400
SUPPLY DIFFUSER ( TYPE 2 )
400 CFM EA
DIFFUSER DESCRIPTION
QUANTITY
FIRE DAMPER (1 1/2 HOUR RATED)
( SEE REG., GRILLES & DIFF SCHEDULE )
BDD
H
HS
V
DN
10'-0" FL10.0 gpm
T
VD
ACOUSTICALLY LINED DUCT
LENGTH, 10,000 BTU/HR) WITHOUT DAMPER
RADIATION I.D. ( TYPE A, 10'-0" FINNED110'-0" FL/D10.0 GPM LENGTH, 10,000 BTU/HR) WITH DAMPER
AM10.1
ACV 2 - WAY
ACV 3 - WAY
BALANCE VALVE
BACKDRAFT DAMPER
CAP - PIPE
CHECK VALVE
COMBINATION BALANCING, FLOW MEASURING &
DUCT SECTION - SUPPLY/OUTDOOR AIR
DUCT SECTION - RETURN AIR
DUCT TURNING VANES
FLEXIBLE DUCT
FLOAT & THERMOSTATIC TRAP
ISOLATION VALVE
GLOBE VALVE
HUMIDISTAT
HUMIDITY SENSOR
LOCKSHIELD GATE VALVE
LOUVER
MANUAL AIR VENT
MOTORIZED DAMPER
OS&Y GATE VALVE
PETCOCK FOR GAUGE CONNECTION
PIPE ANCHOR
PIPE GUIDE
PITCH DOWN
PLUG VALVE
PRESSURE GAUGE
PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
PRESSURE RELIEF DAMPER
RADIATION I.D. ( TYPE A, 10'-0" FINNED
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
RETURN AIR
SECTION I.D. ( SECTION A SHOWN ON DWG. M10.1)
SMOKE DAMPER
STRAINER
SUPPLY AIR
TAKE - OFF FROM BOTTOM OF PIPE
TAKE - OFF FROM TOP OF PIPE
TEMPERATURE SENSOR
THERMOMETER
THERMOMETER WELL
THERMOSTAT
THERMOSTAT COOLING
THERMOSTAT HEATING
THERMOSTAT - NIGHT
THERMOSTAT - HEATING/COOLING
THERMOSTATIC TRAP
UNION
VOLUME DAMPER
DUCT DIAMETER
CBD COUNTERBALANCED DAMPER
1
S (SUPPLY) R (RETURN)E (EXHAUST) T (TRANSFER)
DESCRIPTIONSYMBOL
SD
PRD
MD
FD
AIRFLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR
T
TS
TC
H
N
H/C
T
T
T
DESCRIPTIONSYMBOL
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
SD
EXISTING SUPPLY PIPING TO REMAIN
EXISTING RETURN PIPING TO REMAIN
NEW SUPPLY PIPING
NEW RETURN PIPING
EXISTING DUCTWORK TO REMAIN
NEW DUCTWORK
PIPE DOWN
PIPE UP
DUCT SECTION - EXHAUST AIR
DIFFERENTIAL PRESSURE SENSORDPS
INVERTED BUCKET TRAPIB
STATIC PRESSURE SENSORSPS
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
6/18
/201
8 11
:10:
07 A
M
DURHAM, NEW HAMPSHIRE
16642
M00.1
CG
BPH
LEGEND & GENERALNOTES
2018
ABBREV DESCRIPTIONLAT LEAVING AIR TEMPERATURELPCR LOW PRESSURE CONDENSATE
RETURN (LESS THAN 15 PSI)LPS LOW PRESSURE STEAM(LESS THAN
15 PSI)LRA LOCKED ROTOR AMPSLSGV LOCK & SHIELD GATE VALVELWT LEAVING WATER TEMPERATURE
MAX MAXIMUMMBH 1000 BRITISH THERMAL UNITSMCA MINIMUM CIRCUIT AMPSMD MOTORIZED DAMPERMIN MINIMUMMOPD MAXIMUM OVERCURRENT
PROTECTIVE DEVICEMPCR MEDIUM PRESSURE CONDENSATE
RETURN(16-30 PSIG)MPS MEDIUM PRESSURE STEAM (16-30
PSIG)
NA NOT APPLICABLENC NOISE CRITERIANIC NOT IN CONTRACTNO NORMALLY OPENNTS NOT TO SCALE
OA OUTSIDE AIROC ON CENTEROED OPEN END DUCTOS&Y OUTSIDE SCREW & YOKE GATE
VALVE
PD PRESSURE DROPPRD PRESSURE RELIEF DAMPERPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH
RET RETURNRET RETURNRL REFRIGERANT LIQUIDRLA RATED LOAD AMPERESRPM REVOLUTIONS PER MINUTERS REFRIGERANT SUCTION
SD SMOKE DAMPERSD/FD SMOKE AND FIRE COMBINATION
DAMPERSP STATIC PRESSURESS STAINLESS STEELSUP SUPPLY
TEMP TEMPERATURETT THERMOSTATIC TRAPTYP TYPICAL
VD VOLUME DAMPERVFD VARIABLE FREQUENCY DRIVE
W/ WITHW/O WITHOUTWC WATER COLUMNWG WATER GAUGEWPD WATER PRESSURE DROPWWMS WELDED WIRE MESH SCREEN
ZD ZONE DAMPER
PREFIX OF X EXISTING
ABBREV DESCRIPTIONACV AUTOMATIC CONTROL VALVEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEALD ACOUSTICAL LINED DUCTAMS AIRFLOW MEASURING STATIONAPD AIR PRESSURE DROPATC AUTOMATIC TEMPERATURE
CONTROL
BD BAROMETRIC DAMPERBDD BACKDRAFT DAMPERBHP BRAKE HORSEPOWERBPD BYPASS DAMPERBTU BRITISH THERMAL UNITS
CBD COUNTERBALANCED BACKDRAFTDAMPER
CFM CUBIC FEET PER MINUTECHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCO CLEANOUTCTE CONNECT TO EXISTINGCWR CONDENSER WATER RETURNCWS CONDENSER WATER SUPPLY
DCW DOMESTIC COLD WATERDEG.F DEGREES FAHRENHEITDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWN
EAT ENTERING AIR TEMPERATUREESP EXTERNAL STATIC PRESSUREEWT ENTERING WATER TEMPERATUREEXG EXISTINGEXH EXHAUST
F&T FLOAT & THERMOSTATIC TRAPFD FIRE DAMPERFL FINNED LENGTH OF RADIATIONFM FLOW METERFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFPF FINS PER FOOTFPI FINS PER/INCHFPM FEET PER MINUTEFT FEETFT-HD FEET OF HEADFT-WG FEET WATER GAUGEFTR FIN TUBE RADIATOR
GAL GALLONSGPM GALLONS PER MINUTE
HP HORSEPOWERHPCR HIGH PRESSURE CONDENSATE
RETURN (OVER 30 PSIG)HPS HIGH PRESSURE STEAM (OVER
30PSIG)HRR HEAT RECOVERY RETURNHRS HEAT RECOVERY SUPPLYHWR HOT WATER RETURNHWS HOT WATER SUPPLY
IN INCHES
GENERAL NOTES1 VISIT THE BUILDING SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH EXISTING CONDITIONS, AND TO
TAKE MEASUREMENTS AS NECESSARY FOR COMPLETION OF THE WORK ASSOCIATED WITH THE DESIGNINTENT OF THE CONTRACT DOCUMENTS.
2 COORDINATE WORK OF MECHANICAL SUBCONTRACTOR WITH WORK OF OTHER TRADES.3 DUCTWORK, PIPING AND EQUIPMENT ARE INDICATED DIAGRAMMATICALLY. FIELD-VERIFY LOCATIONS.4 PRIOR TO FABRICATING DUCTWORK, COORDINATE WITH OTHER TRADES TO ENSURE THAT THE DUCTWORK
CAN BE INSTALLED WITH THE INDICATED SIZES AND LOCATIONS.FIELD-VERIFY EXISTING DUCT SIZES ANDCONDITIONS.SUBMIT ANY DISCREPANCIES OR PROPOSED CHANGES.
5 REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS OF CEILING DIFFUSERS ANDREGISTERS.PROVIDE VOLUME DAMPERS SO THAT EVERY REGISTER, GRILLE AND DIFFUSER (SUPPLY,RETURN, AND EXHAUST) CAN BE INDIVIDUALLY BALANCED.
6 VERIFY INSTALLATION OF EXISTING VOLUME DAMPERS AT EACH BRANCH IN EXISTING SUPPLY DUCT.PROVIDE ADDITIONAL VOLUME DAMPERS WHERE REQUIRED.
7 LOCATE VOLUME DAMPERS AS FAR AWAY FROM REGISTERS, GRILLES AND DIFFUSERS AS POSSIBLE TOMINIMIZE NOISE. LOCATE TO BE UNOBSTRUCTED AND EASILY ACCESSIBLE FOR TESTING AND BALANCING.LOCATE POSSIBLE. WHERE VOLUME DAMPERS MUST BE LOCATED ABOVE HARD CEILINGS SUCH ASGYPSUM WALLBOARD, PROVIDE ACCESS PANELS AS SPECIFIED, AND NOTIFY THE ARCHITECT OF SUCHLOCATIONS VERBALLY AND IN WRITING. OBTAIN PERMISSION FROM THE ARCHITECT BEFORE INSTALLINGACCESS PANELS.
8 DUCT ELBOWS SHALL BE LONG-RADIUS TYPE (THROAT RADIUS EQUAL TO OR GREATER THAN DUCT WIDTHIN THE PLANE OF THE TURN) WHEREVER SPACE ALLOWS. IF SPACE IS NOT ADEQUATE, PROVIDE MITEREDELBOWS WITH TURNING VANES.
9 PROVIDE 16 GAUGE SINGLE-THICKNESS TURNING VANES AT MITERED DUCT ELBOWS. VANE EDGES(LEADING AND TRAILING) SHALL BE TANGENTIAL TO AIRFLOW.
10 FLEXIBLE DUCT LENGTHS SHALL NOT EXCEED 5'-0"11 PAINT DUCTWORK VISIBLE THRU CEILING OPENINGS, DUCT OPENINGS, AND REGISTERS, GRILLES, AND
DIFFUSERS WITH BLACK PAINT IN ACCORDANCE WITH DIVISION 09 SECTION "PAINTING."12 MOUNT THERMOSTATS AND TEMPERATURE AND HUMIDITY SENSORS AT 48 INCHES AFF TO TOP OF ITEM.
PROVIDE ELECTRICAL WALL BOX ATTACHED TO FRAMING.13 WHERE THERMOSTATS/TEMPERATURE SENSORS ARE LOCATED NEAR LIGHT SWITCHES, INSTALL SO THAT
LIGHT SWITCHES ARE NEARER TO THE DOOR JAMBS. THE INTENT IS TO LOCATE THERMOSTATS/TEMPERATURE SENSORS SO THEY WILL NOT INTERFERE WITH ACCESSIBILITY OF LIGHT SWITCHES.
14 PIPING INDICATED IN OUTSIDE WALLS SHALL BE RUN ON THE WARM SIDE OF BUILDING INSULATION ANDVAPOR BARRIER. BUILDING INSULATION BEHIND SUCH PIPING SHALL BE CONTINUOUS, WITHOUT JOINTS ORGAPS.
15 PIPING SHALL BE CONCEALED EXCEPT IN MECHANICAL ROOMS AND AS INDICATED. WHERE PIPES DROP INBLOCK WALLS, PROVIDE 1/2" THICK INSULATION MINIMUM.
16 SEAL DUCTWORK AND PIPING THRU MECHANICAL ROOM FLOORS AND PARTITIONS, AND THRU FIRE-RATEDASSEMBLIES, WITH FIRESTOP MATERIAL AS SPECIFIED.
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
COMPLETELY REMOVE AIR SEPERATOR AND ASSOCIATED PIPING
COMPLETELY REMOVE EXPANSION TANK AND ASSOCIATED PIPING
COMPLETELY REMOVE HEAT EXCHANGER AND ASSOCIATED PIPING
COMPLETELY REMOVE BOILER 1 AND ASSOCIATED PIPING
COMPLETELY REMOVE CHEMICAL FEED STATION FOR STEAMAND ASSOCIATED PIPING
COMPLETELY REMOVE CHEMICAL FEED FOR CONDENSATE AND ASSOCIATED PIPING
COMPLETELY REMOVE FLASH TANK AND ASSOCIATED PIPING
COMPLETELY REMOVE FEEDWATER TANK AND ASSOCIATED PIPING
COMPLETELY REMOVE BOILER 2 AND ASSOCIATED PIPING
COMPLETELY REMOVE PUMP & POWER SET AND ASSOCIATED PIPING
COMPLETELY REMOVE PUMP SET AND ASSOCIATED PIPING
COMPLETELY REMOVE HEAT EXCHANGER AND ASSOCIATED PIPING
HWR- 6"HWS- 6"
COMPLETELY REMOVE CONDENSATE PUMPS, ASSOCIATED PIPING, POWER AND CONTROLS
PREPARE FOR NEW HWS&R 4" CONNECTION
PREPARE TO BE CAPPED(TYP)
COMPLETELY REMOVE PUMP SET AND ASSOCIATED PIPING
TO ADAMS TOWERS
PREPARE FOR NEW HWS&R 4" CONNECTION
UP TO NEC CONFERENCE CENTER
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic Scale
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
6/18
/201
8 11
:10:
17 A
M
DURHAM, NEW HAMPSHIRE
16642
M05.1
CG
BPH
MECHANICALDEMOLITION
2018
SCALE: 1/8" = 1'-0"1 DEMOLITION N.E.C. CONFERENCE CENTER
COMPLETELY REMOVE BLOWDOWN TANK AND ASSOCIATED PIPING
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
CONNECT TO EXISITNG HWS&R 4" PIPES TO SERVE THE NEW ENGLAND CENTER
CONNECT TO EXISITNG 4" HWS&R TO SERVE THE LEARNING CENTER
CAP PIPES AT WALL
AS-1
P-4
P-3
P-6
P-5
12"ø 2M10.1
HWR 4"
HWS 4"
HWS- 5"
HWS- 5"
HWS- 5"
HWS- 4"
HWR- 4"
HWS- 4"
HWR- 4"
HWS- 5"
ET-1
P-1
P-2
12"ø
TERMINATE FLUE'S 6'-0"ABOVE ROOF. PROVIDE RAIN CAP.
8"ø
8"ø
B-2
B-1
8"ø
PROVIDE WIRE MESH
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
0 2' 4' 6'
1/4" = 1'-0"
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
6/18
/201
8 11
:10:
28 A
M
DURHAM, NEW HAMPSHIRE
16642
M10.1
CG
BPH
MECHANICAL
2018
SCALE: 1/8" = 1'-0"1 N.E.C. CONFERENCE CENTERSCALE: 1/4" = 1'-0"2 COMBUSTION AIR INLET
WALL
AIR INLET
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
PATCH WALL AS NEEDEDMATCH EXISITNG
PROBE-TYPE LWCO
CHECK VALVE
BALL VALVE
LINE SIZE ACV
FLOW MEASURING
BOILER B-1BOILER B-2
AIR VENT
THERMOMETER
PRV
EXPANSION TANK
LOCKABLE VALVE
HOT WATER SUPPLY
COLD WATER MAKEUP (SEE
PLUMBING)
1" FAST FILL
VIBRATION ISOLATOR
AUTOMATIC AIR VENT. PIPE 3/8" TO FLOOR
DRAIN WITH AIR GAP.
AIR/DIRT SEPARATOR
3/4"
PRESSURE GAUGE
THERMOMETER
THE NEW ENGLAND CENTERTHE LEARNING CENTER
3/4" DRAIN
CH
EMIC
AL
FEED
ER
TSTS
DPS DPS
CLOSELY SPACED TEES
CONDENSATE DRAIN
HOUSE KEEPING PAD (TYP)
CLOSELY SPACED TEES
TS TS
PROVIDE ACID NEUTRILIZATION TANK
FROM MANUFACTURER
V V
DPS
SEE DETAIL M30.2.3
SEE DETAIL M30.2.3 SEE DETAIL M30.2.3
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
6/18
/201
8 11
:10:
38 A
M
DURHAM, NEW HAMPSHIRE
16642
M30.1
CG
BPH
DETAILS
2018
NO SCALE1 NEW ENGLAND CENTER PIPING DETAIL
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
ONE SHOTFEEDER
3/4" DRAIN
AIR VENTVALVE
PIPING MAIN
QUICK-CLOSINGWIDEMOUTH CAP
SUPPORT LEGS,TYPICAL
BRANCH SIZE,TYP. OF 2
MAIN SIZE
NOTES:BRANCH PIPING SHALL BE THE LARGER OFFEEDER CONNECTION SIZE OR 1-1/4"MOUNT FEEDER TO BE REACHABLE FROM FLOOR.INSTALL UPSTREAM OF PUMPS.SUPPORT FEEDER INDEPENDENT OF PIPING.INSULATE BRANCH PIPING. HOT WATER FEEDERMAY BE UNINSULATED.
1.
2.3.4.5.
NEOPRENE ISOLATION PAD
PIPE SUPPORT
SUCTION DIFFUSER
STRAINERSEE SPECIFICATIONS
FOR TYPE
ISOLATION VALVESEE SPECIFICATIONS
FOR TYPE (TYP)
SPLIT COUPLER
DRAIN CONNECTION
FLUSH LINE
PET COCK(TYP)
24" T
O 3
6" A
FF
HANGERS SHALL BE SIZED TO SUPPORT WEIGHT OF FILLED PIPING, PUMPS &
FITTINGS
HANGERS SHALL BE SIZED TO SUPPORT WEIGHT OF FILLED PIPING, PUMPS &
FITTINGS
SILENT CHECKVALVE
FOR FLOW MEASURING ONLY,DO NOT USE FOR THROTTLINGFLOW. SIZE TO ALLOW 2 TO 5FT WG PRESSURE DROP READING."TRIPLE-DUTY" VALVES NOTALLOWED
PUMP
PRESSURE GAGE & PIPING
4" HOUSE KEEPING PAD WITH 1" CHAMFERED
EDGES
PROVIDE STRAIGHT LENGTH OF PIPE AT BALANCE VALVE
INLET AS REQUIRED BY VALVE MANUFACTURER
DPS
1/2" TYPICAL
HWS OR CHWSSUPPLY MAIN
HWS OR CHWSRETURN MAIN
SHUNT VALVE, CLOSED DURINGNORMAL OPERATION, OPEN DURINGAIR BLEEDING AT STARTUP ANDFOR EQUALIZING PRESSURE BEFOREREMOVING THE DPS FOR SERVICE
SHUTOFF VALVE, OPEN DURINGNORMAL OPERATION, TYP OF 2
NORMAL OPERATION, TYP. OF 2
SETRA MODEL 230 WET-TO-WETPRESSURE TRANSDUCER. SELECTRANGE BASED ON ANTICIPATED ORMEASURED DIFFERENTIAL PRESSURESMALLER RANGE INCREASES ACCURACY
1/2" TYPICAL
SEE PLAN DRAWINGSFOR MAIN SIZES
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
6/18
/201
8 11
:10:
45 A
M
DURHAM, NEW HAMPSHIRE
16642
M30.2
CG
BPH
DETAILS
2018
NO SCALE1 ONE SHOT CHEMICAL FEEDER
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
NO SCALE3 IN LINE PUMP
NO SCALE2 CONDENSATE RECIEVER/PUMPSET PIPING
Graphic Scale
PRELIMINARYNOT FOR
CONSTRUCTION
AUBURN PORTLAND PORTSMOUTH BOSTON
Graphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By: Harriman Associatesc
Proj North
Issues and Revisions
DescriptionDate
Plo
t Dat
e:
UNH NECBOILER UPGRADES
PROJECT ID: 2016-0402
6/18
/201
8 11
:10:
51 A
M
DURHAM, NEW HAMPSHIRE
16642
M40.1
CG
BPH
SCHEDULES
2018
BOILER SCHEDULETAG MANUFACTURER MODEL
FUELTYPE
INPUT(MBH)
OUTPUT(MBH)
FLOW(GPM) EWT LWT VOLTS PHASE
WEIGHT(LBS) NOTES
B-1 CLEAVER BROOKS CFC-2500-125 NG 2500 2200 250 200 180 115 1 4685B-2 CLEAVER BROOKS CFC-2500-125 NG 2500 2200 250 200 180 115 1 4685
AIR SEPARATOR SCHEDULETAG MANUFACTURER MODEL SERVICE PIPE SIZE
FLOW(GPM)
WPD(FT WG)
DIAMETER(IN)
HEIGHT(IN) NOTES
AS-1 SPIROTHERM VDT600 B1&B2 5" 500 3 13 19
EXPANSION TANK SCHEDULE
TAG MANUFACTURER MODEL SERVICEVOLUME
(GAL.)
ESTIMATEDSYSTEM VOL.
(GAL)MIN TEMP.
(DEG. F)MAX TEMP
(DEG .F)DIAMETER
(IN)HEIGHT
(IN)WEIGHT
(LBS) NOTESET-1 TACO CA1000-125 HOT WATER 264.0 4714.0 40 240 30 79 2260
PUMP SCHEDULETAG MANUFACTURER MODEL SERVICE
FLOW(GPM)
HEAD(FT.WG)
EFF'Y(%)
SPEED(RPM)
ELECTRIC MOTORCONTROL NOTESHP PHASE VOLTS
P-1 GRUNDFOS VLSE NEC LEARNING CENTER 500 GPM 25 72.6 1780 10 3 460 VFDP-2 GRUNDFOS VLSE NEC LEARNING CENTER 500 GPM 25 72.6 1780 10 3 460 VFDP-3 GRUNDFOS VLSE NEC CONFERENCE CENTER 330 GPM 50 76 1775 7.5 3 460 VFDP-4 GRUNDFOS VLSE NEC CONFERENCE CENTER 330 GPM 50 76 1775 7.5 3 460 VFDP-5 GRUNDFOS CRE-DP NEC LEARNING CENTER 55 GPM 95 71 3599 7.5 3 460 VFDP-6 GRUNDFOS CRE-DP NEC LEARNING CENTER 55 GPM 95 71 3599 7.5 3 460 VFD
05-26-17 DESIGN DEVELOPMENT08-18-17 50% REVIEW05-31-18 FINAL REVIEW
REF:A1
--
1.
2.
3.
4.
5.
6.
7.
8.
UNLESS OTHERWISE NOTED, WIRING SHALL BE 2#12 AWG
CONDUCTORS & #12 GND. HOMERUNS FED FROM 20A, SINGLE
POLE CIRCUITS IN EXCESS OF 100 FEET SHALL BE #10 AWG
UNLESS INDICATED OTHERWISE. INSULATION TYPE SHALL BE
THHN/TWHN, 75 DEG. C, AND 600V CLASS UNLESS SPECIFIED
OTHERWISE.
FLEXIBLE CONNECTIONS TO MOTORS SHALL BE
FLEXIBLE LIQUID TIGHT CONDUIT.
9.
10.
11.
12.
13.
14.
15.
16.
17.
UNLESS OTHERWISE NOTED, ALL WIRING SHALL
BE 600V, COPPER WITH THHN-THWN INSULATION.
WHERE A DISCREPANCY OCCURS BETWEEN THE
DRAWINGS AND THE SPECIFICATIONS, THE
SPECIFICATIONS SHALL PREVAIL. CONTACT THE
ENGINEER FOR CLARIFICAION WHEN SUCH A
SITUATION OCCURS.
WHERE IT IS INDICATED THAT EXISTING WIRING
IS TO BE REUSED, THE ELECTRICAL SUBCONTRACTOR
SHALL VERIFY THAT THE INTEGRITY OF THE INSULATION
IS ADEQUATE FOR REUSE. ALL SUSPECT WIRING SHALL
BE REPLACED BY THE SUBCONTRACTOR.
NOTES
DOTTED INDICATES EXISTING EQUIPMENT
(REFER TO LEGEND FOR TYPE)
EXISTING TO REMAIN(E)
(R)
(RL)
(ER)EXISTING IN NEW LOCATION
(XN)
FIRE ALARM RED
BLUE
SIGNAL (NURSE CALL, PA)
AUDIO VISUAL
480V
277V
120V
208V
PURPLE
WHITE
BROWN
ORANGE
BLACK
GENERAL NOTES GENERAL NOTES (CON'T) EXISTING
EQUIPMENT LEGEND
JUNCTION BOX IDENTIFICATION
COLOR CODE CHART
EXISTING TO BE DISCONNECTED AND REMOVED
EXISTING TO BE DISCONNECTED AND RELOCATED
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH
THE LATEST EDITION OF NFPA 70, NATIONAL ELECTRICAL
CODE (NEC), OSHA REGULATIONS, AS WELL AS APPLICABLE
REGULATIONS OF THE PERTINENT FEDERAL, STATE, COUNTY,
AND CITY AGENCIES. PROVIDE MATERIALS AND EQUIPMENT
THAT COMPLY WITH ANSI, IEEE, IES, AND NEMA STANDARDS.
WHERE APPLICABLE, PROVIDE ONLY MATERIALS THAT ARE
U.L. LISTED AND LABELED.
THE ELECTRICAL SUBCONTRACTOR SHALL VISIT THE SITE
AND INSPECT EXISTING CONDITIONS, SERVICES, CONDUITS,
SPATIAL CONSIDERATIONS AND ALL OTHER PERTINENT
CONDITIONS TO FULLY FAMILIARIZE HIMSELF WITH
CONDITIONS TO BE ENCOUNTERED IN THE PERFORMANCE
OF THIS WORK. THE ELECTRICAL SUBCONTRACTOR SHALL
COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR
DURING CONSTRUCTION. FAILURE TO DO SO WILL NOT
RELIEVE THE ELECTRICAL SUBCONTRACTOR OF THE
RESPONSIBILITY FOR FULL COMPLETION OF THE WORK
IN ACCORDANCE WITH APPLICABLE DRAWINGS AND
SPECIFICATIONS. VERIFY EXISTING SYSTEMS THAT WILL BE
UTILIZED FOR CONNECTION TO THE NEW SYSTEM. IF
DISCREPANCIES EXIST BETWEEN THE CONTRACT DRAWINGS
AND THE ACTUAL EXISTING CONDITIONS, THE ELECTRICAL
SUBCONTRACTOR SHALL NOTIFY THE ENGINEER/OWNER
PRIOR TO PROCEEDING WITH THE INSTALLATION.
CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY. INSTALL
CONDUIT WITH A MINIMUM OF BENDS IN THE SHORTEST
PRACTICAL DISTANCE CONSIDERING THE BUILDINGS
CONSTRUCTION AND OBSTRUCTIONS, EXCEPT WHERE
OTHERWISE NOTED.
ALL MOTOR SAFETY SWITCHES, DISCONNECTS AND MOTOR
STARTERS THAT ARE NOT PROVIDED BY OTHER DIVISIONS,
SHALL BE PROVIDED BY DIVISION 26, UNLESS SPECIFICALLY
NOTED OTHERWISE.
ALL PENETRATIONS THROUGH FIRE-RATED FLOORS, WALLS
AND PARTITIONS SHALL BE SEALED WITH UL APPROVED
FIRE SEALANT MATERIAL TO MAINTAIN THE RATING
OF THE SEPARATION.
WHERE MATERIAL IS CALLED OUT IN THE LEGEND BY
MANUFACTURER, TYPE OR CATALOG NUMBER, SUCH
DESIGNATIONS ARE TO ESTABLISH STANDARDS OR
DESIRED QUALITY. ACCEPTANCE OR REJECTION OF
THE PROPOSED SUBSTITUTIONS SHALL BE SUBJECT
TO THE APPROVAL OF THE OWNER.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION OF EQUIPMENT, DEVICES, AND FURNITURE
REQUIREMENTS, PRIOR TO ROUGHING IN FOR SAME.
ALL GENERAL NOTES, SYMBOLS, LISTS, ABBREVIATIONS
AND DETAILS ARE TO BE CONSIDERED APPLICABLE TO
ALL ELECTRICAL DRAWINGS FOR THIS PROJECT.
IN AREAS AFFECTED BY THIS RENOVATION, THE
ELECTRICAL SUBCONTRACTOR SHALL MAINTAIN
CONTINUITY OF EXISTING ELECTRICAL SERVICE.
PRIOR TO REMOVAL OF EQUIPMENT, THE OWNER WILL
INDICATE WHICH EXISTING DEVICES OR MATERIALS
SHALL BE SALVAGED AND TURNED OVER FOR STORAGE.
WHERE EXISTING EQUIPMENT AND DEVICES ARE TO BE
RELOCATED, ALL ASSOCIATED WIRING, CONDUIT AND
ACCESSORIES SHALL BE EXTENDED, RELOCATED OR
REPLACED WHERE REQUIRED.
ALL VARIABLE FREQUENCY DRIVES (VFD) SHALL BE
PROVIDED BY MECHANICAL CONTRACTOR AND
INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL
CONTRACTOR SHALL CIRCUIT ALL VFDS AND PROVIDE
ALL MOTOR RATED SWITCHES AND DISCONENCT SWITCHES.
18.NEW DEVICES SHALL BE RECESSED. SURFACE MOUNTED
DEVICES SHALL ONLY BE USED WHEN SPECIFICALLY
APPROVED BY OWNER AND ARCHITECT. WHEN SURFACE
MOUNTED DEVICES ARE APPROVED THEY SHALL BE
INSTALLED IN A FINISHED WIREMOLD TYPE BOX AND
WIREMOLD WIREMANAGEMENT SYSTEM. SURFACE
MOUNTED CONDUIT AND JUNCTION BOXES WITH
KNOCKOUT LOCATIONS WILL NOT BE ACCEPTED.
REF:B1
--
E L E C T R I C A L L E G E N D
LP#1,3 HOMERUN TO PNLBRD - ARROWS INDICATE NUMBER OF CIRCUITS. CROSS LINES INDICATE NUMBER OF
CONDUCTORS OTHER THAN TWO (PROVIDE NUMBER OF WIRES REQUIRED TO ALLOW SWITCHING SHOWN - E10
SERIES LIGHTING DRAWINGS).
CIRCUIT NUMBER(S)
PANEL DESIGNATION
J JUNCTION BOX
DUPLEX CONVENIENCE RECEPTACLE - MOUNTED C/L UP 24" UNLESS NOTED OTHERWISE
GFI GFCI DUPLEX CONVENIENCE RECEPTACLE - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE
UNFUSED DISCONNECT SWITCH
## KEYNOTE TAG
CONTROL PANEL
PANELBOARD
1.
a.
2.
b.
FIRE ALARM
SYSTEM NOTES
REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES
AND LOCATIONS OF ALL FIRE ALARM DEVICES
ASSOCIATED WITH FIRE PROTECTION SYSTEMS.
c. MAKE ALL CONNECTIONS AS REQUIRED.
d. PROVIDE ALL REQUIRED PROGRAMMING.
REF:B2
--
LEGEND LIGHTING FIXTURE SCHEDULE
PROVIDE NEW CARBON MONOXIDE
DETECTORS WHERE INDICATED.
PROVIDE NEW FIRE ALARM SMOKE
DETECTORS WHERE INDICATED.
COMBINATION STARTER DISCONNECT SWITCH
MOTOR RATED SWITCH WITH OVERCURRENT PROTECTION
COFIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR
SINGLE POLE SWITCH - MOUNTED 48" AFF
THREE WAY SWITCH - MOUNTED 48" AFF
FOUR WAY POLE SWITCH - MOUNTED 48" AFF
NEW (N)
EXISTING TO BE REPLACED WITH NEW
CONTROL PANEL
FIRE ALARM SYSTEM SMOKE DETECTOR
SFIRE ALARM SYSTEM SPEAKER STROBE
LAMPS, HANGERS, FITTINGS, ETC. FOR A COMPLETE AND PROPER INSTALLATION
ALL FIXTURES SHALL BE FURNISHED COMPLETE WITH ALL HARDWARE
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NO. MTG. VOLTNO. WATT
LAMPS
TYPEREMARKS/BALLAST INFORMATION
72UNVA
LITHONIA
72UNVAE
LITHONIA
1LED120/277UE
LED
LQM-S-3-G-120/277-ELN-SDLITHONIA
UNIVERSAL MOUNTED SINGLE/DUAL FACE BLACK EXIT SIGN WITH GREEN LETTERS AND NICAD BATTERY
LED
LED
LED
LED
SAME AS TYPE A EXCEPT WITH EMERGENCY BATTERY PACK
S OR C
S OR C
IN FIELD TO AVOID DUCTWORK AND PIPING.COORDINATE LOCATION AND MOUNTING TYPE
IN FIELD TO AVOID DUCTWORK AND PIPING.COORDINATE LOCATION AND MOUNTING TYPE
4' LED SURFACE OR CHAIN MOUNTED GASKETED INDUSTRIAL LIGHT
FEM-L48-6000LM-MD-MVOLT-GZ10-35K-90CRI-MHCH36
FEM-L48-6000LM-MD-MVOLT-GZ10-35K-90CRI-BSL-520MHCH36
TIMER SWITCH - MOUNTED 48" AFF. - WATTSTOPPER MODEL #TS-400-G
MODIFY THE EXISTING NOTIFIER NFS2-640(E)
MAIN FIRE ALARM CONTROL PANEL TO
ACCOMMODATE THE NEW DEVICES INDICATED.
PROVIDE NEW ZONES(IDENTIFY AS REQUIRED).
NEW CONTACTS, ADDITIONAL POWER SUPPLIES
AND ALL OTHER ACCESSORIES FOR A COMPLETE
AND OPERATIONAL SYSTEM.
VARIABLE FREQUENCY DRIVE
EXIT SIGN
AUBURN PORTLAND PORTSMOUTH
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2018
Proj North
DescriptionDate
Key Plan
Issues and Revisions
CONSTRUCTION
NOT FOR
PRELIMINARY
BOSTON
DURHAM, NEW HAMPSHIRE
16642
PROJECT ID: 2016-0402
BOILER UPGRADES
UNH NEC
JWT
APG
E00.1
ELECTRICAL LEGEND,
NOTES AND
SCHEDULES
05-26-17 DESIGN DEVELOPMENT
08-18-17 50% REVIEW
05-31-18 FINAL REVIEW
1NEC BASEMENT PART PLANSCALE: 1/8" = 1'-0"
PUMP SET
BOILER 1
BOILER 2
CHEMICAL FEED PUMP
CHEMICAL FEED PUMP
CONDENSATE PUMPS
003003A MP1 PP1
F
PUMP SET
AUBURN PORTLAND PORTSMOUTH
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2018
Proj North
DescriptionDate
Key Plan
Issues and Revisions
CONSTRUCTION
NOT FOR
PRELIMINARY
BOSTON
DURHAM, NEW HAMPSHIRE
16642
PROJECT ID: 2016-0402
BOILER UPGRADES
UNH NEC
JWT
APG
E05.1
1/8" = 1'-0"0 4' 8' 12'
BASEMENT FLOOR
EXISTING CONDITIONS
05-26-17 DESIGN DEVELOPMENT
08-18-17 50% REVIEW
PART PLAN
05-31-18 FINAL REVIEW
Room
B04
Room
B04A
Room
B04B
Room
B04C
003003A MP1 PP1
F
1NEC BASEMENT PART PLANSCALE: 1/8" = 1'-0"
CO
CO
CO
B-2
P-2P-1
P-3
P-4
P-5P-6
NEW 208/120V, 225A, 42 POLE PANEL PP2
4#4/0+1#4G IN 2 1/2"C
NEW 480V, 150A, 42 POLE PANEL 003B
A
A
A
A
A
AE
AE
AE
AE
AE
A
A
A
A
A
A
A
A
A
A
A
A
E
E
3#1/0+1#6G IN 1 1/2"C
003B#1,3,5003B#7,9,11
1,3,5
7,9,11
003B#13,15,17
003B#19,21,2313,15,17
19,21,23
003B#25,27,29
25,27,29
003B#31,33,35
31,33,35
B-1
P01 3#12+1#12G IN 3/4"C
P02 3#10+1#10G IN 3/4"C
P02
P02
P01 P01
P01
P01
P01
IN SPACE 4 TO SERVE NEW PANEL PP2
REUTILIZE EXISTING 225A, 3-POLE SPARE BREAKER
IN SPACE 11 TO SERVE NEW PANEL 003B
REUTILIZE EXISTING 150A, 3-POLE SPARE BREAKER
PP2#1 PP2#3
1 3
PP2#5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
A
5
5
5
ID ID
WATT LOADS
MOUNTING:
LOCATION:
LOAD DESCRIPTIONA
MP
PO
LE
CRKTDWG
NO. PO
LE
WATTSPH A PH B PH C
WATTS
PO
LE
CRKTDWG
NO. PO
LE
AM
P
LOAD DESCRIPTION
FEEDER:AIC RATING:MAIN BREAKER:VOLTAGE:
BUSES:PH & WIRES:
120/208
3P 4W
225
MLO
22K AIC
SURFACE
BASEMENT
SEE DRAWINGPP2
TUB 1 OF 1 - REMARKS:
BOILER B-1 20 1 1 1 500 500 --- --- 0 2 2 1 30 SPARE
BOILER B-2 20 1 3 3 500 --- 500 --- 4 - - -
BOILER RM B04 LIGHTING 20 1 5 5 1656 --- --- 1656 6 - - -
SPARE 20 1 7 7 0 0 --- --- 0 8 8 1 30 SPARE
SPARE 20 1 9 9 0 --- 0 --- 10 - - -
SPARE 20 1 11 11 0 --- --- 0 12 - - -
SPARE 20 1 13 13 0 0 --- --- 0 14 14 1 25 SPARE
SPARE 20 1 15 15 0 --- 0 --- 16 - - -
SPARE 20 1 17 17 0 --- --- 0 18 - - -
SPARE 20 1 19 19 0 0 --- --- 0 20 20 1 20 SPARE
SPARE 20 1 21 21 0 --- 0 --- 22 - - -
SPARE 20 1 23 23 0 --- --- 0 24 - - -
SPARE 20 1 25 25 0 0 --- --- 0 26 26 1 15 SPARE
SPARE 20 1 27 27 0 --- 0 --- 28 - - -
SPARE 20 1 29 29 0 --- --- 0 30 - - -
SPARE 20 1 31 31 0 0 --- --- 0 32 32 1 15 SPARE
SPARE 20 1 33 33 0 --- 0 --- 34 - - -
SPARE 20 1 35 35 0 --- --- 0 36 - - -
SPARE 20 1 37 37 0 0 --- --- 0 38 38 1 100 SPARE
SPARE 20 1 39 39 0 --- 0 --- 40 - - -
SPARE 20 1 41 41 0 --- --- 0 42 - - -
TOTAL AMPS: 7.4 500 500 1656 TOTAL WATTS: 2656
REMARKS:
05/31/2018
ID ID
WATT LOADS
MOUNTING:
LOCATION:
LOAD DESCRIPTION
AM
P
PO
LE
CRKTDWG
NO. PO
LE
WATTSPH A PH B PH C
WATTS
PO
LE
CRKTDWG
NO. PO
LE
AM
P
LOAD DESCRIPTION
FEEDER:AIC RATING:MAIN BREAKER:VOLTAGE:
BUSES:PH & WIRES:
/480
3P 4W
150
MLO
22K AIC
SURFACE
BASEMENT
SEE DRAWING003B
TUB 1 OF 1 - REMARKS:
PUMP P-1 25 1 1 1 11639 11639 --- --- 0 2 2 1 30 SPARE
- - - 3 --- 0 --- 4 - - -
- - - 5 --- --- 0 6 - - -
PUMP P-2 25 1 7 7 11639 11639 --- --- 0 8 8 1 30 SPARE
- - - 9 --- 0 --- 10 - - -
- - - 11 --- --- 0 12 - - -
PUMP P-3 20 1 13 13 9141 9141 --- --- 0 14 14 1 25 SPARE
- - - 15 --- 0 --- 16 - - -
- - - 17 --- --- 0 18 - - -
PUMP P-4 20 1 19 19 9141 9141 --- --- 0 20 20 1 25 SPARE
- - - 21 --- 0 --- 22 - - -
- - - 23 --- --- 0 24 - - -
PUMP P-5 15 1 25 25 6315 6315 --- --- 0 26 26 1 20 SPARE
- - - 27 --- 0 --- 28 - - -
- - - 29 --- --- 0 30 - - -
PUMP P-6 15 1 31 31 6315 6315 --- --- 0 32 32 1 20 SPARE
- - - 33 --- 0 --- 34 - - -
- - - 35 --- --- 0 36 - - -
SPARE 15 1 37 37 0 0 --- --- 0 38 38 1 15 SPARE
- - - 39 --- 0 --- 40 - - -
- - - 41 --- --- 0 42 - - -
TOTAL AMPS: 65.2 54190 0 0 TOTAL WATTS: 54190
REMARKS:
05/31/2018
AUBURN PORTLAND PORTSMOUTH
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2018
Proj North
DescriptionDate
Key Plan
Issues and Revisions
CONSTRUCTION
NOT FOR
PRELIMINARY
BOSTON
DURHAM, NEW HAMPSHIRE
16642
PROJECT ID: 2016-0402
BOILER UPGRADES
UNH NEC
JWT
APG
E20.1
BASEMENT FLOOR
POWER AND SYSTEMS
05-26-17 DESIGN DEVELOPMENT
08-18-17 50% REVIEW
PART PLAN
1/8" = 1'-0"
0 4' 8' 12'
05-31-18 FINAL REVIEW