Transcript

On time Deliveries | High Quality | Efficiency | Integrity | Knowledge | Dedication to Excellence

Air Handling Insulation Solution

Members of:SMACNA, SPIDA, SMWIA, IHACI

Superior Duct Fabrication | 1683 Mount Vernon Ave. | Pomona, Ca. 91768 | Hours: Monday - Friday 5:00am to 5:00pm(800) 797-Duct (3828) Toll-Free | (909) 620-6374 Main Fax | www.sdfab.com

Superior Duct Fabrication is pleased to now offer Owens Corning® QuietZone®Spiral Duct Liner. It is both anti-bacterial and anti-fungal. QuietZone® Spiral DuctLiner is available in 1", 1.5", and 2" thicknesses. It is tested according to UL 181standards and is listed with UL Laboratories® The R-value and sound absorptionof QuietZone® Spiral Duct Liner outperforms other compressed insulationavailable in the market.

Superior Duct Fabrication’s highly trained and experienced mechanics and sheetmetal workers use Superior’s special equipment and processes to assure thatevery QuietZone® Spiral Duct Liner board is carefully grooved, cut to size andfitted in spiral duct and fittings. The surface is fitted with a durable and permanentairstream surface that is longer lasting, when compared to insulating productswith sprayed-on coatings that tend to get brittle and crack over time. SuperiorDuct Fabrication round, internally-lined systems are the perfect, economicalsolution..

QuietZone® Spiral Duct Liner

Key Features• Outstanding thermal and acoustical performance• Cleanable surface with a black mat facing that provides a smooth, durable surface making it easier to clean the duct liners using methods and equipment described in North American Insulation Manufacturers Association (NAIMA) Publication AH122, Cleaning Fibrous Glass Insulated Duct Systems: Recommended Practice• Bacterial and fungal growth resistant with an EPA registered biocide that protects the airstream surface from microbial growth Standards, Codes Compliance• National Fire Protection Association Standards

NFPA 90A/90B• ICC International Mechanical Code• NYC MEA# 186-69• Meets requirements of ASTM C1338, ASTM G21, fungi test) and ASTM G22 (bacteria test)• ASTM C1071, Type II Rigid

Superior Duct Fabrication is an independent contractor and not an affiliate of Owens Corning InsulatingSystems, LLC or its affiliated companies. The color PINK is a registered trademark of Owens Corning.

Quiet Zone.qxp_Layout 1 4/28/15 2:37 PM Page 1

On time Deliveries | High Quality | Efficiency | Integrity | Knowledge | Dedication to Excellence

Air Handling Insulation Solution

Superior Duct Fabrication | 1683 Mount Vernon Ave. | Pomona, Ca. 91768 | Hours: Monday - Friday 5:00am to 5:00pm(800) 797-Duct (3828) Toll-Free | (909) 620-6374 Main Fax | www.sdfab.com

1. The surface burning characteristics of these products have been determined in accordance with UL 723. This standard should be used tomeasure and describe the properties of materials, products or assemblies in response to heat and flame under controlled laboratory conditionsand should not be used to describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions.However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent toan assessment of the fire hazard of a particular end use. Values are reported to the nearest 5 rating. ASTM E84 and UL 723 are the same testmethod.

Thermal Performanceat 75ºF (24ºC) Mean Temperature

Physical Property Data

1" (25mm) 1.5" (38mm) 2.0” (5lmm)

R-value: ft2•ºF/Btu (RSI: m2•ºC/W) 4.3 (0.76) 6.5 (1.15) 8.7 (1.53)k-value: Btu•in/hr•ft2•ºF (W/m2•ºC) 0.23 (0.033) 0.23 (0.033) .23 (0.033)

Property Test Method Value

Maximum Temperature Limits UL 181 Internal 250°F (121ºC)External 150°F (66ºC)

Maximum Air Velocity UL 181 Erosion Test 6,000 fpm (30.5 m/s)

Water Vapor Sorption (by weight) ASTM C1104 <3% at 120°F (49ºC), 95% R.H.

Mold Growth UL 181/ASTM C1338 Meets requirements

Fungi Resistance ASTM G21 Meets requirements

Bacteria Resistance ASTM G22 Meets requirements

Surface Burning CharacteristicsFlame Spread

Smoke Developed

UL 7231ASTM E84

25 50

Acoustical Performance - ASTM C 423

Thickness 125 250 500 1000 2000 4000 NRC

1.0” 0.08 0.19 0.69 0.94 0.99 0.98 0.70

1.5” 0.12 0.33 0.92 1.04 1.03 1.02 0.85

2.0” 0.14 0.72 1.15 1.12 1.06 1.07 1.00

Quiet Zone.qxp_Layout 1 4/28/15 2:37 PM Page 2


Top Related