dolsmc sg001 en p
TRANSCRIPT
-
7/31/2019 Dolsmc Sg001 en p
1/32
SELECTION GUIDE
FIXED SPEED CONTROLDIRECT ONLINE STARTERS
SOFT STARTERS
THE INTELLIGENT MOTOR CONTROL SOLUTION
FOR YOUR APPLICATION REQUIREMENTS
-
7/31/2019 Dolsmc Sg001 en p
2/32
-
7/31/2019 Dolsmc Sg001 en p
3/321
Rockwell Automation, Allen-Bradley, PowerFlex, ArmorPoint, ArmorConnect, ArmorStartare registered trademarks of Rockwell Automation. DeviceLogix, DeviceNet are trademarks of
Rockwell Automation.
Intelligent Motor Control 2
Intelligent Motor Control with Fixed Speed Starters 4
Product features 6
Product selection
E1 Plus Electronic Overload Relays 8
E3 and E3 Plus Electronic Overload Relays 10
825-P Modular Protection System 12
SMC-Flex Smart Motor Controllers 14
ArmorStart Distributed Motor Controllers 18
Short-Circuit Coordination 24Functionality Overview 26
-
7/31/2019 Dolsmc Sg001 en p
4/322
FIXED SPEEDCONTROL
Direct OnlineStarters
SoftStarters
We understand that you need to control performance, reduce
downtime, improve safety, increase productivity, perform
diagnostics. Thats why weve combined leading-edge motor
control and protection devices with the advanced networking
and diagnostic capabilities of Rockwell Automations Integrated
Architecture to provide you with Intelligent Motor Control.
With solutions for a variety of motor control requirements and
devices hosting in-built intelligence, control of your motor
applications can be truly integrated into your solution. Seamless
integration allows your to monitor, control, program and
interrogate your motor control solutions to achieve the
efficiency, reliability and control you demand. With different
levels of integration available, there is an integrated solution
ideal for you.
AN INTEGRAL PART OF YOUR
INTEGRATEDARCHITECTURE
WHAT YOU CAN ACHIEVE WITH INTEGRATED ARCHITECTURE
AND INTELLIGENT MOTOR CONTROL SOLUTIONS... Optimise motor performance through intelligent equipment and networks
Reduce your energy consumption and increase efficiency Reduce downtime in the event of drive damage with automatic device replacement (ADR)
Alerts you about motor problems before a failure occurs
Embed safety functionality to protect your process, personnel and equipment health
Achieve seamless communication and system visibility for increased system performance,
simplified troubleshooting and reduced startup times
and much more...
-
7/31/2019 Dolsmc Sg001 en p
5/323
MOTIONCONTROL
VARIABLE SPEEDCONTROL
ServoMotors
ServoDrives
Medium VoltageAC Drives
Low VoltageAC Drives
NetLinx
(EtherNet/IP, ControlNet, DeviceNet)
EngineeredDrive Solutions
-
7/31/2019 Dolsmc Sg001 en p
6/324
E3 AND E3 PLUS -ELECTRONIC OVERLOAD RELAYS 0.4...860 A Current Range
9...5000 A Current Range with
Current Transformer
DeviceNet Communication
integrated
Adjustable trip Class (530)
Programmable trip and
warning settings
Diagnostic functions(History of last 5 trips)
DeviceLogix component technology
RELAYS E3 2 Inputs 1 Output
RELAYS E3 PLUS 4 Inputs 2 Outputs
Built-in ground faultsensor (through 90 A rating)
PTC thermistor input
FIXED SPEEDCONTROL
Direct OnlineStarters
E1 PLUS -ELECTRONIC OVERLOAD RELAYS 0.1...800 A Current Range
Self-Powered
Fast Phase Loss Protection
Wide adjustment Range (5:1)
Low Energy
Consumption (150mW)
Visible Trip Indication
Side mount Communications Modules
825-P - MODULARPROTECTION SYSTEM 0.55000 A Current Range
Suitable for low- and medium- voltage
applications
Modular design with pluggable options
- Voltage input cards, including
DeviceNet communications
- RTD scanner module
Comprehensive protection functions
Built-in keypad and backlit 2-Line LCD
Status LEDs
3 Output relays
2 Configurable inputs
-
7/31/2019 Dolsmc Sg001 en p
7/325
SoftStarters
Direct online StartingRockwell Automation offers a complete portfolio ofAllen-Bradley electronic motor protection relays withcommunications that allow you immediate access to statusinformation, motor performance data, and diagnostics,as well as the capability to perform control functions.
Soft StartingSmart Motor Controllers (SMCs) minimize mechanicalwear resulting from full-voltage starting of AC inductionmotors, enabling longer system life as well as limit linedisturbances from inrush currents, resulting in reduceddowntime.
Distributed Motor ControlFor your applications needing machine mounted motorcontrol, the ArmorStart Distributed Motor Controllers offera simple, cost-effective method of integrating motorcontrol, I/O and network capabilities in your on-machinearchitecture. The ArmorStart is an integrated,pre-engineered combination starter for full voltage DOL,reversing, Soft starting and variable speed drive applica-tions. The components are mounted closer to the applica-tion or on the machine reducing panel space as well as
wiring and conduit requirements making it easier to installand start-up. Save more time by configuring intelligentdevices via the network and reduce at the same timepotential errors.
ARMORSTART 280/281D -DISTRIBUTED MOTOR CONTROLLERS 0.187.5 kW (400V)
Full Voltage DOL and Reversing starting
IP69K/NEMA Type 4X or IP67/
NEMA Type 4 enclosure ratings
Modular plug and play design
Network Communications with
DeviceNet including DeviceLogix
4 Inputs and 2 Outputs
Quick Disconnects for I/O,
Communications, Motor Connection
and Control Power
ARMORSTART 283D -DISTRIBUTED MOTOR CONTROLLERS 0.375.5 kW (400V)
Current Limit Start, Soft Start, Soft Stop
IP69K/NEMA Type 4X or IP67/
NEMA Type 4 enclosure ratings
Modular plug and play design
Network Communications with
DeviceNet including DeviceLogix
4 Inputs and 2 Outputs
Quick Disconnects for I/O,
Communications, Motor Connection
and Control Power
SMC-FLEX -SMART MOTOR COTROLLERS 11250/1600 A Current Range
Soft Start
Current Limit Start
Full Voltage
Preset Slow Speed
Soft Stop
Options
Pump Control
Braking Control
-
7/31/2019 Dolsmc Sg001 en p
8/326
PROTECTION CONTROL
COMMUNICATIONS
E3 Overload Relays control functions delivereffective motor management to help preventand minimize production downtime. Criticalprotective functions can prevent motor damageand provide advance notification of a machinesperformance being outside the boundaries ofnormal operation.Network communication delivers immediateaccess to motor performance and diagnosticdata in addition to seamless control. IntegratedI/O provides convenient local termination ofmotor-related inputs and outputs, simplifyingthe control architecture. DeviceLogix compo-nent technology increases the control possibili-ties with function block programs that operate
at the device level.
E1 Plus electronic overload relays are the indus-trys first modular self-powered devices, settinga new standard for entry level motor protection.The network communications modules expandthe functionality. Its compact, simplified control,and flexibilitys allows you to network motorstarters more cost efficiently. Streamlineprocesses with enhanced control, protection,monitoring, and diagnostic capability for im-proved operating efficiency.
The unique line-side over molded power con-nections on the E1 Plus, on the E3, and E3 Plusmake for a sturdy two-component starter assem-bly that is unmatched in the industry. The pre-formed power connections allow for easy starter
assembly every time.
NETWORKCOMMUNICATION
-
7/31/2019 Dolsmc Sg001 en p
9/327
IP69K Rated ArmorStart!The IP69K rated ArmorStart Distributed Motor Controlleris suitable for harsh production environments. Rated forenvironment high pressure wash down with causticchemicals used in the food and beverage industry(i.e. sodium hydroxide exposure). The IP69K ratedArmorStart offers the same features as the IP67 ratedArmorStart.
What is DeviceLogix?DeviceLogix is a stand-alone Boolean program that resideswithin the ArmorStart.
DeviceLogix is programmed using Boolean math operationssuch as AND, OR, NOT, Timers, Counters, and Latches.
RSNetWorx for DeviceNet Version 3.0 or later is requiredto program the device.
Peer to PeerCommunications (ZIP)The new Zone Control capabilities of ArmorStart DistributedMotor Controller is ideal for large horsepower motoredconveyors. The ArmorStart Distributed Motor Controller havebuilt-in DeviceNet Communications, DeviceLogix technologyand the added Zone Interlocking Parameters (ZIP) whichallows one ArmorStart to consume data directly from upto four other DeviceNet nodes without going through thenetwork scanner. These direct communications betweenconveyor zones are beneficial in merge, diverter and
accumulation conveyor applications.
Line ConnectionDelta Connections
M
Benefits of using DeviceLogix
Faster sense-to-actuate response Local processing Higher network performance
Increased system reliability Improved diagnostics and reduced troubleshooting Reducing potential points of failure at system level Increasing uptime through distributing ControlLogic
throughout system
Enables reliability in operation under failures or duringmaintenance operations
Increased system/machine modularity Distributing control on the machine Smaller programs in the master system scan
and processing times
The SMC-Flex is a compact and cost-effective packagefor your production applications. As standard, theSMC-Flex includes I/O, electronic overload, integralbypass, advanced communication capabilities, motorstarting capabilities for both star-delta and standardsquirrel-cage induction motors, advanced protectionand diagnostics.
The SMC-Flex is also available for medium voltageapplications with the same features and benefits forcontrolling motors rated up to 7.2 kV and 7500 hp(5600 kW).
The SMC-Flex provides 3 Phase Controland excellent performance in a
compact design for your standardsquirrel cage or Star-Delta
induction motors.
M3~
2/T1 4/T2 6/T3
3/L21/L1 5/L3
-
7/31/2019 Dolsmc Sg001 en p
10/328
Description Mounts to ContactorAdjustment Range
[A] Cat. No.
Three-Phase Devices 193-ED
0.127 A Current Range
Fixed Trip Class 10
Manual Reset
100-C09100-C23
0.10.5 193-ED1AB
0.21.0 193-ED1BB
1.05.0 193-ED1CB
3.216 193-ED1DB
5.427 193-ED1EB
Three-Phase Devices 193-EE
0.1800 A Current Range
Selectable Trip Class (10, 15, 20 or 30)
Selectable Manual/Auto-Manual Reset
Single-Phase and Devices with Cage Clamp ControlTerminals are also available,see publication 193-SG009_-EN-P.
100-C09100-C23 0.10.5 193-EEAB
100-C09100-C23 0.21.0 193-EEBB
100-C09100-C23 1.05.0 193-EECB
100-C09100-C23 3.216 193-EEDB
100-C09100-C23 5.427 193-EEEB
100-C30100-C43 5.427 193-EEED
100-C30100-C43 945 193-EEFD
100-C60100-C85 1890 193-EEGE
100-D95100-D180 30150 193-EEHF
100-D95100-D180 40200 193-EEJF
100-D210100-D420 40200 193-EEJG
100-D210100-D420 60300 193-EEKG100-D210100-D420 100500 193-EELG
100-D630100-D860 120600 193-EEMH
100-D630100-D860 160800 193-EENH
0.1...800 A Current Range
Self-Powered
Fast Phase Loss Protection
Wide Adjustment Range (5:1)
1 N.O. and 1 N.C. Isolated auxiliary Contacts
(B600, AC-15 Rated)
Low Energy Consumption (150 mW)
Ambient Temperature Compensation
Visible Trip Indication
Jam/Remote Reset optional accessoiresSide-mount Modules for enhanced Motor Protection
E1 PLUS
-
7/31/2019 Dolsmc Sg001 en p
11/329
Description For Use With Cat. No.
DeviceNet Communications ModuleIntegrated I/O allow simplification of the networkarchitecture, providing local connection of motor starterrelated inputs and outputs.2 Inputs 24V DC rated, module supplied1 Output B300 rated
193-EE 193-EDN
Jam Protection Module with Remote ResetSide-mount module with trip level settings of 150, 200, 300and 400% FLA, and delay time settings of 0.5, 1.0, 2.0and 4 seconds. For remote resetting of a trip condition.Supply voltage required.
193-EE 193-EJM
Ground Fault Module with Remote ResetSide-mount module for core-balanced ground fault protection,adjustable trip level 20 mA...5 A. Supply voltage required.
193-EE 193-EGF
Ground Fault/Jam Module with Remote ResetSide-mount module for core-balanced ground fault protection,adjustable trip level 20 mA...5 A; Jam protection with fixed trip levelsetting of 400% FLA, fixed delay time setting of 0.5 seconds.
Supply voltage required.
193-EE 193-EGJ
Core Balance Ground Fault SensorsMax. 45 A; Window 19.1 mmMax. 90 A; Window 39.6 mm
100-C09...C37 193-CBCT1
100-C09...C85 193-CBCT2
Remote Reset ModuleFor remote resetting of a trip condition.Supply voltage required.
193-EE 193-ERR
DIN Rail/Panel AdapterFor separate mounting can be mountedto top-hat rail EN 50 022-35.
193-ED1_B, 193-EE_B 193-EPB193-ED1_B, 193-EE_B 193-EPD
193-EE_E 193-EPE
External Reset ButtonFor enclosed, through-the-door reset applications.Metal construction IP66, non-illuminated with rod(length: 142 mm, adjustable range 141159 mm).Refer to the 800F catalog pages for additional types.
193-ED (all)193-EE (all)
800FP-R611
800F-ATR08
Current Adjustment ShieldPrevents inadvertent adjustment of the current setting.Must be ordered in multiples of package quantities.Package Quantity = 10
193-ED (all)193-EE (all)592-EE (all)
193-BC8
External Reset AdapterFor enclosed, through-the-door reset applications.Use with External Reset Button.
193-ED (all)193-EE_B,193-EE_D,193-EE_E
193-ERA
Terminal LugsSet of 2Protection class IP2X per IEC 60529 and DIN 40 050
100-D140, 100-D180,100-D95ED180E,193-EC_F, 193 -EE_F
100-DTB180
100-D210...100-D420,193-EC_G, 193-EF2C,
193-EE_G100-DTB420
Terminal CoversProtection class IP20 per IEC 60529 and DIN 40 050For direct-on-line, reversing, two-speed,and wye-delta/star-delta assemblies
100-D95100-D180,193-EC_F, 193 -EE_F 100-DTC180
100-D210...100-D420,193-EC_G, 193-EE_G
100-DTC420
100-D630100-D860,193-EC_H, 193-EE_H
100-DTC860
Phase Barriers
Set of 4
100-D630D860,
193-EC_H, 193-EE_H
100-DPB860
-
7/31/2019 Dolsmc Sg001 en p
12/3210
Relay193-EC1
Relay193-EC2
Mounts to Contactor Adjustment Range [A] Cat. No. Cat. No.
100-C09100-C23
0.42 193-EC1PB 193-EC2PB
15 193-EC1AB 193-EC2AB
315 193-EC1BB 193-EC2BB
525 193-EC1CB 193-EC2CB
100-C30100-C43
15 193-EC1AD 193-EC2AD
315 193-EC1BD 193-EC2BD
525 193-EC1CD 193-EC2CD
945 193-EC1DD 193-EC2DD
100-C60100-C85945 193-EC1DE 193-EC2DE
1890 193-EC1EE 193-EC2EE
100-D95100-D18028140 1 193-EC1FF 193-EC2FF
42210 1 193-EC1GF 193-EC2GF
100-D210100-D420
42210 1 193-EC1GG 193-EC2GG
60302 1 193-EC1HG 193-EC2HG
84420 1 193-EC1JG 193-EC2JG
100-D630100-D860125630 1 193-EC1KH 193-EC2KH
172860 1 193-EC1LH 193-EC2LH
0.4...860 A Current Range
9...5000 A Current Range with Current Transformer
DeviceNet communication integrated
LED indicators
Test / Reset button Adjustable trip Class (530)
Integrated I/O s E3: 2 Inputs / 1 Output
E3 Plus: 4 Inputs / 2 Outputs
Low-level ground (earth) fault protection 193-EC2Ground fault range 15 A
PTC thermistor input 193-EC2
Programmable trip and warning settings
Diagnostic functions (History of last 5 trips)
DeviceLogix (series B)
1 Does not include terminal lugs.
E3 & E3 PLUS
-
7/31/2019 Dolsmc Sg001 en p
13/3211
Description For Use With Cat. No.
DIN Rail/Panel Adapter 1
193-EC__B 193-ECPM1
193-EC_D, 193-EC_ZZ 193-ECPM2
193-EC__E 193-ECPM3
AC Input Interface Modulerated 110/120V AC, 50/60 Hz
193-EC all592-EC all 193-EIMD
Core Balance Ground Fault Sensor 193-EC2_F, 193-EC2_G,193-EC2_H, 193-EC2ZZ 825-CBCT
Terminal LugsSet of 2Protection class IP2X per IEC 60529 and DIN 40 050
100-D140, 100-D180,100-D95ED180E,193-EC_F, 193-EE_F
100-DTB180
100-D210...100-D420,193-EC_G, 193-EF2C,
193-EE_G100-DTB420
Terminal CoversProtection class IP20 per IEC 60529 and DIN 40 050For direct-on-line, reversing, two-speed,and wye-delta/star-delta assemblies
100-D95100-D180,193-EC_F, 193-EE_F
100-DTC180
100-D210...100-D420,193-EC_G, 193-EE_G 100-DTC420
100-D630100-D860,193-EC_H, 193-EE_H 100-DTC860
Phase BarriersSet of 4
100-D630D860,193-EC_H, 193-EE_H
100-DPB860
CT RatioFLA SettingRange (A) CT Ratio
FLA SettingRange (A) CT Ratio
FLA SettingRange (A)
50:5 945 300:5 60302 1200:5 2401215
100:5 1890 500:5 84420 2500:5 4502250
150:5 28140 600:5 125630 5000:5 10005000
200:5 42210 800:5 172860
Description Adjustment Range [A] Cat. No.
2 Inputs 1 Output 95000 193-EC1ZZ
4 Inputs 2 Outputs Ground fault sensor input PTC thermistor input
DeviceLogix
95000 193-EC2ZZ
Current transformers supplied by customer.Order panel adapter 193-ECPM2 separately. See table below for CT Ratio to FLA setting range correlation. Discount Schedule MPC
1 The electronic motor protection relay can be mounted separately to top-hat rail EN 50 02-35.
-
7/31/2019 Dolsmc Sg001 en p
14/32
-
7/31/2019 Dolsmc Sg001 en p
15/3213
Description Cat. No.
Voltage Input CardMonitoring of VA, VB, VC, and VN
240V AC Max. 1 825-PVS
Expansion I/O Card(3) Inputs(4) Output Relays(1) 420 mA Analog Output
120V AC Rated Inputs 1 825-PIOD
24V DC Rated Inputs 1 825-PIOR
DeviceNet Communication CardDeviceLogix technology, Node address selection switches, 1ODVA conformance tested
825-PDN
Modbus RTU Communication Card 1 825-PMB
M8 connectionsSet of 34 x 16 x 102 mm (1/8 x 5/8 x 4-1/64 in.) (125 A max.)Universally applicable
Weight: 230 g
825-MVM
M8 connectionsSet of 34 x 20 x 117 mm (180 A max.)Universally applicable
825-MVM2
M6 lower connectionsSet of 3For mounting on 100-D95 and 100-D110 contactors with conventional coil
825-MVS
M8 lower connectionsSet of 3
For mounting on 100-D140, 100-D180 conventional and100-D95E100-D180E contactors with electronic coil 825-MVS2
Terminal ShieldsSet of 2Protection class IP10 per IEC 60529and DIN 40 050For direct-on-line, reversing, two-speed,and wye-delta/star-delta assemblies
100-D95, 100-D110 100-DTS110
100-D140, 100-D180,100-D95-E100-D180-E 100-DTS180
100-D210...100-D420 100-DTS420
Terminal LugsSet of 2Protection class IP2X per IEC 60529and DIN 40 050
100-D95, 100-D110 100-DTB110
100-D140, 100-D180,
100-D95ED180E,193-EC_F, 193-EE_F
100-DTB180
100-D210...100-D420,193-EC_G, 193-EF2C,
193-EE_G100-DTB420
Thermal Utilization Meter
For display of percentthermal capacity utilizedRequires the use of an
Expansion I/O Card
825-MTUM
Connection cable (replacement)825-P to 825-MCM connection
825-MCA
-
7/31/2019 Dolsmc Sg001 en p
16/3214
Rating for lineconnection ?
Rating for deltaconnection ?
WithoutOption
With PumpControl Option
With BrakingControl Option
MotorCurrent
[A]400V[kW]
MotorCurrent
[A]400V[kW] Control Voltage Cat. No. Cat. No. Cat. No.
15 2.2 1.78.7 4100...240V AC 50/60 Hz 150-F5NBD 150-F5NBDB 150-F5NBDD
24V AC/DC 150-F5NBR 150-F5NBRB 150-F5NBRD
5...25 11 8.743 22100...240V AC 50/60 Hz 150-F25NBD 150-F25NBDB 150-F25NBDD
24V AC/DC 150-F25NBR 150-F25NBRB 150-F25NBRD
8.6...43 22 14.974 37100...240V AC 50/60 Hz 150-F43NBD 150-F43NBDB 150-F43NBDD
24V AC/DC 150-F43NBR 150-F43NBDR 150-F43NBDR
12...60 30 20.8...104 55100...240V AC 50/60 Hz 150-F60NBD 150-F60NBDB 150-F60NBDD
24V AC/DC
150-F60NBR 150-F60NBRB 150-F60NBRD17...85 45 29.4147 75
100...240V AC 50/60 Hz 150-F85NBD 150-F85NBDB 150-F85NBDD
24V AC/DC 150-F85NBR 150-F85NBRB 150-F85NBRD
27108 55 47187 90100...240V AC 50/60 Hz 150-F108NBD 150-F108NBDB 150-F108NBDD
24V AC/DC 150-F108NBR 150-F108NBRB 150-F108NBRD
34135 75 59234 132100...240V AC 50/60 Hz 150-F135NBD 150-F135NBDB 150-F135NBDD
24V AC/DC 150-F135NBR 150-F135NBRB 150-F135NBRD
67201 110 116348 160100...240V AC 50/60 Hz 150-F201NBD 150-F201NBDB 150-F201NBDD
24V AC/DC 150-F201NBR 150-F201NBRB 150-F201NBRD
84251 132 145435 250100...240V AC 50/60 Hz 150-F251NBD 150-F251NBDB 150-F251NBDD
24V AC/DC 150-F251NBR 150-F251NBRB 150-F251NBRD
106317 160 183549 135100...240V AC 50/60 Hz 150-F317NBD 150-F317NBDB 150-F317NBDD
24V AC/DC
150-F317NBR 150-F317NBRB 150-F317NBRD
120361 200 208625 355100...240V AC 50/60 Hz 150-F361NBD 150-F361NBDB 150-F361NBDD
24V AC/DC 150-F361NBR 150-F361NBRB 150-F361NBRD
160480 250 277831 450100...240V AC 50/60 Hz 150-F480NBD 150-F480NBDB 150-F480NBDD
24V AC/DC 150-F480NBR 150-F480NBRB 150-F480NBRD
208625 355 283850 500110/120V AC 50/60 Hz 150-F625NBE 150-F625NBEB 150-F625NBED
230/240V AC 50/60 Hz 150-F625NBA 150-F625NBAB 150-F625NBAD
260780 450 300900 500110/120V AC 50/60 Hz 150-F780NBE 150-F780NBEB 150-F780NBED
230/240V AC 50/60 Hz 150-F780NBA 150-F780NBAB 150-F780NBAD
323...970 560 4001200 710110/120V AC 50/60 Hz 150-F970NBE 150-F970NBEB 150-F970NBED
230/240V AC 50/60 Hz 150-F970NBA 150-F970NBAB 150-F970NBAD
4161250 710 5331600 900110/120V AC 50/60 Hz 150-F1250NBE 150-F1250NBEB 150-F1250NBED
230/240V AC 50/60 Hz 150-F1250NBA 150-F1250NBAB 150-F1250NBAD
11250/1600 A Current Range
Built-in Electronic Overload Protection
Soft Start
Current Limit Start
Dual Ramp Full Voltage
Linear Speed Acceleration
Preset Slow Speed
Soft Stop
Options
Pump Control
Braking Control
SMC-FLEX
-
7/31/2019 Dolsmc Sg001 en p
17/3215
Rating for lineconnection?
Rating for deltaconnection ?
WithoutOption
With PumpControl Option
With BrakingControl Option
MotorCurrent
[A]400V[kW]
MotorCurrent
[A]400V[kW] Control Voltage Cat. No. Cat. No. Cat. No.
15 2.2 1.78.7 4100...240V AC 50/60 Hz 150-F5NCD 150-F5NCDB 150-F5NCDD
24V AC/DC 150-F5NBCR 150-F5NCRB 150-F5NCRD
5...25 11 8.743 22100...240V AC 50/60 Hz 150-F25NCD 150-F25NCDB 150-F25NCDD
24V AC/DC 150-F25NCR 150-F25NCRB 150-F25NCRD
8.6...43 22 14.974 37100...240V AC 50/60 Hz 150-F43NCD 150-F43NCDB 150-F43NCDD
24V AC/DC 150-F43NCR 150-F43NCDR 150-F43NCDR
12...60 30 20.8...104 55100...240V AC 50/60 Hz 150-F60NCD 150-F60NCDB 150-F60NCDD
24V AC/DC 150-F60NCR 150-F60NCRB 150-F60NCRD
17...85 45 29.4147 75100...240V AC 50/60 Hz 150-F85NCD 150-F85NCDB 150-F85NCDD
24V AC/DC 150-F85NCR 150-F85NCRB 150-F85NCRD
27108 55 47187 90100...240V AC 50/60 Hz 150-F108NCD 150-F108NCDB 150-F108NCDD
24V AC/DC 150-F108NCR 150-F108NCRB 150-F108NCRD
34135 75 59234 132
100...240V AC 50/60 Hz 150-F135NCD 150-F135NCDB 150-F135NCDD
24V AC/DC 150-F135NCR 150-F135NCRB 150-F135NCRD
67201 110 116348 160100...240V AC 50/60 Hz 150-F201NCD 150-F201NCDB 150-F201NCDD
24V AC/DC 150-F201NCR 150-F201NCRB 150-F201NCRD
84251 132 145435 250100...240V AC 50/60 Hz 150-F251NCD 150-F251NCDB 150-F251NCDD
24V AC/DC 150-F251NCR 150-F251NCRB 150-F251NCRD
106317 160 183549 135100...240V AC 50/60 Hz 150-F317NCD 150-F317NCDB 150-F317NCDD
24V AC/DC 150-F317NCR 150-F317NCRB 150-F317NCRD
120361 200 208625 355100...240V AC 50/60 Hz 150-F361NCD 150-F361NCDB 150-F361NCDD
24V AC/DC 150-F361NCR 150-F361NCRB 150-F361NCRD
160480 250 277831 450100...240V AC 50/60 Hz 150-F480NCD 150-F480NCDB 150-F480NCDD
24V AC/DC 150-F480NCR 150-F480NCRB 150-F480NCRD
208625 355 283850 500110/120V AC 50/60 Hz 150-F625NCE 150-F625NCEB 150-F625NCED230/240V AC 50/60 Hz 150-F625NCA 150-F625NCAB 150-F625NCAD
260780 450 300900 500110/120V AC 50/60 Hz 150-F780NCE 150-F780NCEB 150-F780NCED
230/240V AC 50/60 Hz 150-F780NCA 150-F780NCAB 150-F780NCAD
323...970 560 4001200 710110/120V AC 50/60 Hz 150-F970NCE 150-F970NCEB 150-F970NCED
230/240V AC 50/60 Hz 150-F970NCA 150-F970NCAB 150-F970NCAD
4161250 710 5331600 900110/120V AC 50/60 Hz 150-F1250NCE 150-F1250NCEB 150-F1250NCED
230/240V AC 50/60 Hz 150-F1250NCA 150-F1250NCAB 150-F1250NCAD
Options Voltage Range
D 100240V AC (5...480A units)R 24 V AC/DC (5...480A units)E 110/120V AC (625...1250A units)
A 230/240V AC (625...1250A units)
Options Voltage RangeB Up to 480V AC
C Up to 600V AC
Z Up to 690V AC,Options Description
Blank Standard
BPump Control
Provides smooth motor acceleration and deceleration,reducing surges caused by the starting and stopping
of centrifugal pumps. Starting time is adjustablefrom 030 seconds, and stopping time is
adjustable from 0120 seconds.
DBraking Control
Provides Smart Motor Braking (SMB), Accu-Stop,
and Slow Speed with Braking. Prices on request.
Controllers rated 108 A and greater are not equipped with line and load terminal lugs.? Motor FLA and Motor Running Current must fall within the running current range of the device to operate properly. Utilization category: 5...480A AC-53b: 3-50: 1750 Separate 120V or 240V single phase is required for fan operation.
625...1250A AC-53b: 3-50: 3550
, For controllers rated 108...1250A only
Optional Configurations 150-F108N B D B
a b c
a
b
c
-
7/31/2019 Dolsmc Sg001 en p
18/3216
Description Cat. No.
Protective Modules 1
480V Protective Module585 A 150-F84
1081250 A 150-F84L
600V Protective Module585 A 150-F86
1081250 A 150-F86L
IEC Terminal Covers ?
Terminal CoverIEC line or load terminal covers for 108...135 A devices.Dead front protection
150-TC1
Terminal CoverIEC line or load terminal covers for 201251 A devices.Dead front protection
150-TC2
Terminal CoverIEC line or load terminal covers for 317480 A devices.Dead front protection
150-TC3
Human Interface Modules
Hand HeldHuman Interface Modules
LCD Display,Full Numeric Keypad
20-HIM-A3
LCD Display,Programmer Only HIM
20-HIM-A5
Door MountedHuman Interface Modules
LCD Display,Full Numeric Keypad(includes 3 m cable)
20-HIM-C3S
Human Interface ModuleInterface Cables
HIM Interface Cable,1 m (39 in.)
20-HIM-H10
Communication Modules
Communication Modules (IP30/Type 1)
Remote I/O 20-COMM-R
RS-485/DF1 20-COMM-S
ProfiBUS 20-COMM-P
ControlNet 20-COMM-C
Interbus 20-COMM-I
DeviceNet 20-COMM-D
Ethernet/IP 20-COMM-E
RS-485 HVAC 20-COMM-H
ControlNet (Fiber) 20-COMM-Q
Core Balance Transformer
Core Balance Ground Fault Sensor 100:1 825-CBCT
1 The same protective module mounts on the line or load side of the SMC-Flex. For applications requiring both line and load side protection, two protective modules must be ordered.
? One terminal cover is shipped as standard with the SMC-Flex controllers.
Requires a 20-HIM-H10 cable to connect to the SMC-Flex.Discount Schedule SOF (150-), Discount Schedule 23 (20-), Discount Schedule MPC (825-CBCT)
-
7/31/2019 Dolsmc Sg001 en p
19/3217
-
7/31/2019 Dolsmc Sg001 en p
20/3218
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC
50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
0.241.2 0.37 280D-F12Z-10A-CR 280A-F12Z-10A-CR 280D-F12B-10A-CR 280A-F12B-10A-CR
0.52.5 0.75 280D-F12Z-10B-CR 280A-F12Z-10B-CR 280D-F12B-10B-CR 280A-F12B-10B-CR
1.15.5 2.2 280D-F12Z-10C-CR 280A-F12Z-10C-CR 280D-F12B-10C-CR 280A-F12B-10C-CR
3.216 7.5 280D-F23Z-25D-CR 280A-F23Z-25D-CR 280D-F23B-25D-CR 280A-F23B-25D-CR
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC
50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
0.241.2 0.37 280D-S12Z-10A-CR 280A-S12Z-10A-CR 280D-S12B-10A-CR 280A-S12B-10A-CR
0.52.5 0.75 280D-S12Z-10B-CR 280A-S12Z-10B-CR 280D-S12B-10B-CR 280A-S12B-10B-CR
1.15.5 2.2 280D-S12Z-10C-CR 280A-S12Z-10C-CR 280D-S12B-10C-CR 280A-S12B-10C-CR
3.216 7.5 280D-S23Z-25D-CR 280A-S23Z-25D-CR 280D-S23B-25D-CR 280A-S23B-25D-CR
Bulletin 280/281
On-Machine starting solution
Full-Voltage DOL and reversing starting
Modular plug and play design
Quick disconnect connections for I/O, communications,
three phase motor connection and control power
Gland plate entry: conduit entrance or ArmorConnect power media
4 Inputs and 2 Outputs (expandable with ArmorPoint)
LED status indication
DeviceNet communications
DeviceLogix component technology
Connectivity to ArmorPoint distributed I/O products
ControlNet and EtherNet communications via ArmorPoint
Factory Installed Options:- Hand/Off/Auto (HOA) keypad configuration- Safety monitor
Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
for harsh production environmentsConduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:
Replace -CRat the end of the Cat. No. with -RR(Example: 280D-S23Z-25D-RR)
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:Replace -CRat the end of the Cat. No. with -RR(Example: 280D-F23Z-25D-RR)
ARMORSTART
-
7/31/2019 Dolsmc Sg001 en p
21/3219
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC
50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
0.241.2 0.37 281D-F12Z-10A-CR 281A-F12Z-10A-CR 281D-F12B-10A-CR 281A-F12B-10A-CR0.52.5 0.75 281D-F12Z-10B-CR 281A-F12Z-10B-CR 281D-F12B-10B-CR 281A-F12B-10B-CR
1.15.5 2.2 281D-F12Z-10C-CR 281A-F12Z-10C-CR 281D-F12B-10C-CR 281A-F12B-10C-CR
3.216 7.5 281D-F23Z-25D-CR 281A-F23Z-25D-CR 281D-F23B-25D-CR 281A-F23B-25D-CR
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC
50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
0.241.2 0.37 281D-S12Z-10A-CR 281A-S12Z-10A-CR 281D-S12B-10A-CR 281A-S12B-10A-CR
0.52.5 0.75 281D-S12Z-10B-CR 281A-S12Z-10B-CR 281D-S12B-10B-CR 281A-S12B-10B-CR
1.15.5 2.2 281D-S12Z-10C-CR 281A-S12Z-10C-CR 281D-S12B-10C-CR 281A-S12B-10C-CR
3.216 7.5 281D-S23Z-25D-CR 281A-S23Z-25D-CR 281D-S23B-25D-CR 281A-S23B-25D-CR
DescriptionCat. No.
Modification
Hand Off-Auto Selector Keypad -3 Example: 281D-S23Z-25D-RR-3
Hand Off-Auto Selector Keypadwith Forward/Reverse Function
-3FR Example: 281D-S23Z-25D-RR-3FR
Safety Monitor -SM Example: 281D-S23Z-25D-RR-3FR-SM
Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
for harsh production environmentsConduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:Replace -CRat the end of the Cat. No. with -RR(Example: 281D-F23Z-25D-RR)
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:
Replace -CRat the end of the Cat. No. with -RR(Example: 281D-S23Z-25D-RR)
For factory installed options, please contact your local sales office.
Other ArmorStart versions available.Please consult publication 280-SG001_-EN-P for complete product information.
-
7/31/2019 Dolsmc Sg001 en p
22/3220
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
1.1...3.0 1.1 283D-FB3Z-10A-CR 283A-FB3Z-10A-CR 283D-FB3B-10A-CR 283A-FB3B-10A-CR
3.0...5.5 2,2 283D-FB9Z-10B-CR 283A-FB9Z-10B-CR 283D-FB9B-10B-CR 283A-FB9B-10B-CR
5.5...7.6 3.0 283D-FB16Z-10C-CR 283A-FB16Z-10C-CR 283D-FB16B-10C-CR 283A-FB16B-10C-CR
6.316 5.5 283D-FB19Z-25D-CR 283A-FB19Z-25D-CR 283D-FB19B-25D-CR 283A-FB19B-25D-CR
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
1.1...3.0 1.1 283D-SB3Z-10A-CR 283A-SB3Z-10A-CR 283D-SB3B-10A-CR 283A-SB3B-10A-CR
3.0...5.5 2,2 283D-SB9Z-10B-CR 283A-SB9Z-10B-CR 283D-SB9B-10B-CR 283A-SB9B-10B-CR
5.5...7.6 3.0 283D-SB16Z-10C-CR 283A-SB16Z-10C-CR 283D-SB16B-10C-CR 283A-SB16B-10C-CR
6.316 5.5 283D-SB19Z-25D-CR 283A-SB19Z-25D-CR 283D-SB19B-25D-CR 283A-SB19B-25D-CR
Bulletin 283 On-Machine starting solution
Soft Start motor control
Modular plug and play design
Quick disconnect connections for I/O, communications,
three phase motor connection and control power
Gland plate entry: conduit entrance or ArmorConnect power media
4 inputs and 2 outputs (expandable with ArmorPoint)
LED status indication
DeviceNet communications
DeviceLogix component technology
Connectivity to ArmorPoint distributed I/O products
ControlNet and EtherNet communications via ArmorPoint
Factory Installed Options:- Hand/Off/Auto (HOA) keypad configuration
- Source brake contactor- Safety monitor
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:Replace -CRat the end of the Cat. No. with -RR (Example: 283D-FB19Z-25D-RR)
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:
Replace -CRat the end of the Cat. No. with -RR(Example: 283D-SB19Z-25D-RR)
Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
for harsh production environmentsConduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
ARMORSTART
-
7/31/2019 Dolsmc Sg001 en p
23/3221
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC
50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPoint
CommunicationsCat. No.
1.1...3.0 1.1 283D-FC3Z-10A-CR 283A-FC3Z-10A-CR 283D-FC3B-10A-CR 283A-FC3B-10A-CR3.0...5.5 2,2 283D-FC9Z-10B-CR 283A-FC9Z-10B-CR 283D-FC9B-10B-CR 283A-FC9B-10B-CR
5.5...7.6 3.0 283D-FC16Z-10C-CR 283A-FC16Z-10C-CR 283D-FC16B-10C-CR 283A-FC16B-10C-CR
6.316 5.5 283D-FC19Z-25D-CR 283A-FC19Z-25D-CR 283D-FC19B-25D-CR 283A-FC19B-25D-CR
Current RatingMax.
Motor Power24V DC
Control Voltage240V AC
Control Voltage
[A]
[kW]400V AC50 Hz
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
DeviceNetTM
CommunicationsCat. No.
ArmorPointCommunications
Cat. No.
1.1...3.0 1.1 283D-SC3Z-10A-CR 283A-SC3Z-10A-CR 283D-SC3B-10A-CR 283A-SC3B-10A-CR
3.0...5.5 2,2 283D-SC9Z-10B-CR 283A-SC9Z-10B-CR 283D-SC9B-10B-CR 283A-SC9B-10B-CR
5.5...7.6 3.0 283D-SC16Z-10C-CR 283A-SC16Z-10C-CR 283D-SC16B-10C-CR 283A-SC16B-10C-CR
6.316 5.5 283D-SC19Z-25D-CR 283A-SC19Z-25D-CR 283D-SC19B-25D-CR 283A-SC19B-25D-CR
DescriptionCat. No.
Modification
Hand Off-Auto Selector Keypad -3 Example: 283D-SC19Z-25D-RR-3
Source Brake Contactor -SB Example: 283D-SC19Z-25D-RR-3-SB
Safety Monitor -SM Example: 283D-SC19Z-25D-RR-3-SB-SM
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:Replace -CRat the end of the Cat. No. with -RR(Example: 283D-FC19Z-25D-RR)
Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power:
Replace -CRat the end of the Cat. No. with -RR(Example: 283D-SC19Z-25D-RR)
Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
for harsh production environmentsConduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
For factory installed options, please contact your local sales office.
Other ArmorStart versions available.Please consult publication 280-SG001_-EN-P for complete product information.
-
7/31/2019 Dolsmc Sg001 en p
24/3222
Input VoltageOutput Current
[A]3-Phase Rating
[kW]
24V DCControl Voltage
240V ACControl Voltage
Cat. No. Cat. No.
200...240V, 50/60 Hz3-Phase
2.3 0.4 284D-FVB2P3Z-10-CR-EMI 284D-FVB2P3B-10-CR-EMI
5 0.75 284D-FVB5P0Z-10-CR-EMI 284D-FVB5P0B-10-CR-EMI
7.6 1.5 284D-FVB7P6Z-25-CR-EMI 284D-FVB7P6B-25-CR-EMI
380...480V, 50/60 Hz3-Phase
1.4 0.4 284D-FVD1P4Z-10-CR-EMI 284D-FVD1P4B-10-CR-EMI
2.3 0.75 284D-FVD2P3Z-10-CR-EMI 284D-FVD2P3B-10-CR-EMI
4 1.5 284D-FVD4P0Z-10-CR-EM 284D-FVD4P0B-10-CR-EMI
6 2.2 284D-FVD6P0Z-25-CR-EMI 284D-FVD6P0B-25-CR-EMI
7.6 3 284D-FVD7P6Z-25-CR-EMI 284D-FVD7P6B-25-CR-EMI
460600V, 50/60 Hz3-Phase
1.7 0.75 284D-FVE1P7Z-10-CR-EMI 284D-FVE1P7B-10-CR-EMI
3 1.5 284D-FVE3P0Z-10-CR-EMI 284D-FVE3P0B-10-CR-EMI
4.2 2.2 284D-FVE4P2Z-25-CR-EMI 284D-FVE4P2B-25-CR-EMI
6.1 4 284D-FVE6P6Z-25-CR-EMI 284D-FVE6P6B-25-CR-EMI
Bulletin 284 On-Machine starting solution
Variable frequency AC drive using PowerFlex technology
Modular plug and play design
Quick disconnect connections for I/O, communications,
three phase motor connection and control power
Gland plate entry: conduit entrance or ArmorConnect power media
4 Inputs and 2 Outputs (expandable with ArmorPoint)
LED status indication
DeviceNet communications
DeviceLogix component technology
Connectivity to ArmorPoint distributed I/O products
ControlNet and EtherNet communications via ArmorPoint
Factory Installed Options:
- Hand/Off/Auto (HOA) keypad configuration
- EMI filter
- Dynamic brake connector- Output contactor
- Source brake contactor
- Shielded motor cable
- Safety monitor
- 0...10V analog input
Sensorless Vector Control and Volts per Hertz, with DeviceNet Communications,
EMI-Filter, Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
Version with ArmorPoint Communications:Replace284Dat the beginning of the Cat. No. with 284A (Example: 284A-FVE6P6Z-25-CR-EMI)
Version with Quick Disconnects for ArmorConnect Power Media for Control and 3-Phase Power:
Replace -CRat the end of the Cat. No. with -RR(Example: 284D-FVE6P6Z-25-RR-EMI)
ARMORSTART
-
7/31/2019 Dolsmc Sg001 en p
25/3223
Input VoltageOutput Current
[A]3-Phase Rating
[kW]
24V DCControl Voltage
240V ACControl Voltage
Cat. No. Cat. No.
200...240V, 50/60 Hz
3-Phase
2.3 0.4 284D-SVB2P3Z-10-CR-EMI 284D-SVB2P3B-10-CR-EMI
5 0.75 284D-SVB5P0Z-10-CR-EMI 284D-SVB5P0B-10-CR-EMI7.6 1.5 284D-SVB7P6Z-25-CR-EMI 284D-SVB7P6B-25-CR-EMI
380...480V, 50/60 Hz3-Phase
1.4 0.4 284D-SVD1P4Z-10-CR-EMI 284D-SVD1P4B-10-CR-EMI
2.3 0.75 284D-SVD2P3Z-10-CR-EMI 284D-SVD2P3B-10-CR-EMI
4 1.5 284D-SVD4P0Z-10-CR-EMI 284D-SVD4P0B-10-CR-EMI
6 2.2 284D-SVD6P0Z-25-CR-EMI 284D-SVD6P0B-25-CR-EMI
7.6 3 284D-SVD7P6Z-25-CR-EMI 284D-SVD7P6B-25-CR-EMI
460600V, 50/60 Hz3-Phase
1.7 0.75 284D-SVE1P7Z-10-CR-EMI 284D-SVE1P7B-10-CR-EMI
3 1.5 284D-SVE3P0Z-10-CR-EMI 284D-SVE3P0B-10-CR-EMI
4.2 2.2 284D-SVE4P2Z-25-CR-EMI 284D-SVE4P2B-25-CR-EMI
6.1 4 284D-SVE6P6Z-25-CR-EMI 284D-SVE6P6B-25-CR-EMI
DescriptionCat. No.
Modification
Hand Off-Auto Selector Keypadwith JOG Function
-3 Example: 284D-SVE6P6Z-25-CR-3-EMI
Control Brake Contactor -CB Example: 284D-SVE6P6Z-25-CR-3-CB-EMI
Dynamic Brake Connector -DB Example: 284D-SVE6P6Z-25-CR-3-DB-EMI
Source Brake Contactor -SB Example: 284D-SVE6P6Z-25-CR-3-SB-EMI
0...10V Analog Input -A10 Example: 284D-SVE6P6Z-25-CR-3-SB-A10
EMI Filter -EMI Example: 284D-SVE6P6Z-25-CR-3-SB-EMI
Output Contactor -OC Example: 284D-SVE6P6Z-25-CR-3-SB-OC
Safety Monitor -SM ? Example: 284D-SVE6P6Z-25-CR-3-SB-SM
Sensorless Vector Control and Volts per Hertz, with DeviceNet Communications,EMI-Filter, Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable
Version with ArmorPoint Communications:Replace284Dat the beginning of the Cat. No. with 284A (Example: 284A-SVE6P6Z-25-CR-EMI)
Version with Quick Disconnects for ArmorConnect Power Media for Control and 3-Phase Power:Replace -CRat the end of the Cat. No. with -RR(Example: 284D-SVE6P6Z-25-RR-EMI)
? The output contactor is included with the Safety Monitor option.
For factory installed options, please contact your local sales office.
-
7/31/2019 Dolsmc Sg001 en p
26/3224
Direct-Online Class 10
Circuit Breaker 140M MCP (Magnetic Only)
Contactor 100-C / 100-D
Overload Relay E1Plus - 193-ED../193-EE..
Rated Operational Voltage 400V 50Hz
Rated Conditional S-C Current (Iq) 50kA (rms sym)
Type of Coordination (IEC 947-4-1) Type "2"
Motor Circuit Breaker Contactor Overload Relay
1500 rpm[kW] [A] Type
MagneticSetting
[A] Type Type (1)
ThermalSetting
[A]
0.06 0.24 140M-C2N-A25 3.3 100-C09 193-ED1AB 0.10 - 0.50
0.09 0.33 140M-C2N-A40 5.2 100-C09 193-ED1AB 0.10 - 0.50
0.12 0.43 140M-C2N-A63 8.2 100-C09 193-ED1AB 0.10 - 0.50
0.18 0.61 140M-C2N-A63 8.2 100-C09 193-ED1BB 0.20 - 1.0
0.25 0.80 140M-C2N-B10 13 100-C09 193-ED1BB 0.20 - 1.0
0.37 1.1 140M-C2N-B16 20 100-C09 193-ED1CB 1.0 - 5.0
0.55 1.5 140M-C2N-B16 20 100-C09 193-ED1CB 1.0 - 5.00.75 1.9 140M-C2N-B25 32 100-C09 193-ED1CB 1.0 - 5.0
1.1 2.7 140M-D8N-B40 52 100-C09 193-ED1CB 1.0 - 5.0
1.5 3.5 140M-D8N-B40 52 100-C09 193-ED1CB 1.0 - 5.0
2.2 5.0 140M-D8N-B63 82 100-C09 193-ED1CB 1.0 - 5.0
3 6.6 140M-D8N-C10 130 100-C09 193-ED1DB 3.2 - 16
4 8.5 140M-D8N-C10 130 100-C09 193-ED1DB 3.2 - 16
5.5 11 140M-D8N-C16 208 100-C12 193-ED1DB 3.2 - 16
7.5 15 140M-D8N-C16 208 100-C16 193-ED1DB 3.2 - 16
10 20 140M-D8N-C25 325 100-C23 193-EEED 5.4 - 27
11 22 140M-D8N-C25 325 100-C23 193-EEED 5.4 - 27
15 29 140M-F8N-C32 416 100-C30 193-EEFD 9 - 45
18.5 36 140M-F8N-C45 585 100-C37 193-EEFD 9 - 45
22 41 140M-F8N-C45 585 100-C43 193-EEFD 9 - 45
30 56 140M-H8P-C70 210 - 770 100-C60 193-EEFD 9 - 45
37 68 140M-H8P-C70 210 - 770 100-C72 193-EEGE 18 - 90
45 81 140M-H8P-D10 300 - 1100 100-C85 193-EEGE 18 - 90
55 99 140M-H8P-D10 300 - 1100 100-D210 193-EEJG 40 - 200
75 135 140M-J8P-D20 1000 - 2000 100-D210 193-EEJG 40 - 200
90 162 140M-J8P-D20 1000 - 2000 100-D210 193-EEJG 40 - 200
110 196 140M-J8P-D20 1000 - 2000 100-D210 193-EEJG 40 - 200
132 232 140M-J8P-D25 1250 - 2500 100-D250 193-EEKG 60 - 300
160 281 140M-L8P-D30 1500 - 3000 100-D300 193-EEKG 60 - 300
200 350 140M-L8P-D40 2000-4000 100-D420 193-EELG 100 - 500
(1)Use of current ajustment shield 193-BC8 is recommended to prevent inadvertent adjustment of the current setting
SHORT -
-
7/31/2019 Dolsmc Sg001 en p
27/3225
Direct-Online Class 10
Circuit Breaker 140M MCP (Magnetic Only)
Contactor 100-C / 100-D
Overload Relay E3 - 193-EC1 / 193-EC2
Rated Operational Voltage 400V 50Hz
Rated Conditional S-C Current (Iq) 50kA (rms sym)
Type of Coordination (IEC 947-4-1) Type "2"
Motor Circuit Breaker Contactor Overload Relay
1500 rpm[kW] [A] Type
MagneticSetting
[A] Type Type (1) (2)
ThermalSetting
[A]
0.06 0.24 140M-C2N-A25 3.3 100-C09 193-EC1PB 0.4 - 2.0
0.09 0.33 140M-C2N-A40 5.2 100-C09 193-EC1PB 0.4 - 2.0
0.12 0.43 140M-C2N-A63 8.2 100-C09 193-EC1PB 0.4 - 2.0
0.18 0.61 140M-C2N-A63 8.2 100-C09 193-EC1PB 0.4 - 2.0
0.25 0.80 140M-C2N-B10 13 100-C09 193-EC1PB 0.4 - 2.0
0.37 1.1 140M-C2N-B16 20 100-C09 193-EC1PB 0.4 - 2.0
0.55 1.5 140M-C2N-B16 20 100-C09 193-EC1PB 0.4 - 2.00.75 1.9 140M-C2N-B25 32 100-C09 193-EC1PB 0.4 - 2.0
1.1 2.7 140M-D8N-B40 52 100-C09 193-EC1AB 1 - 5
1.5 3.5 140M-D8N-B40 52 100-C09 193-EC1AB 1 - 5
2.2 5.0 140M-D8N-B63 82 100-C09 193-EC1AB 1 - 5
3 6.6 140M-D8N-C10 130 100-C09 193-EC1BB 3 - 15
4 8.5 140M-D8N-C10 130 100-C09 193-EC1BB 3 - 15
5.5 11 140M-D8N-C16 208 100-C12 193-EC1BB 3 - 15
7.5 15 140M-D8N-C16 208 100-C16 193-EC1BB 3 - 15
10 20 140M-D8N-C25 325 100-C23 193-EC1CB 5 - 25
11 22 140M-D8N-C25 325 100-C23 193-EC1CB 5 - 25
15 29 140M-F8N-C32 416 100-C30 193-EC1DD 9 - 45
18.5 36 140M-F8N-C45 585 100-C37 193-EC1DD 9 - 4522 41 140M-F8N-C45 585 100-C43 193-EC1DD 9 - 45
30 56 140M-H8P-C70 210 - 770 100-C60 193-EC1EE 18 - 90
37 68 140M-H8P-C70 210 - 770 100-C72 193-EC1EE 18 - 90
45 81 140M-H8P-D10 300 - 1100 100-C85 193-EC1EE 18 - 90
55 99 140M-H8P-D10 300 - 1100 100-D110 193-EC1FF 28 - 140
75 135 140M-J8P-D15 750 - 1500 100-D140 193-EC1FF 28 - 140
90 162 140M-J8P-D20 1000 - 2000 100-D180 193-EC1GF 42 - 210
110 196 140M-J8P-D20 1000 - 2000 100-D210 193-EC1GG 42 - 210
132 232 140M-J8P-D25 1250 - 2500 100-D250 193-EC1HG 60 - 302
160 281 140M-L8P-D30 1500 - 3000 100-D300 193-EC1HG 60 - 302
200 350 140M-L8P-D40 2000-4000 100-D420 193-EC1JG 84 - 420
(1)Use of current ajustment shield 193-BC8 is recommended to prevent inadvertent adjustment of the current setting (2)Overload Relay 193-EC2.. can also be used
SHORT -
-
7/31/2019 Dolsmc Sg001 en p
28/3226
Motor Protection 193-ED 193-EE 193-EC1 193-EC2 825-P SMC-3 SMC-FLEXOverload Underload Stall (1) Jam (1) Thermistor Input (1) Earth Fault Input (1) Phase loss
Current Imbalance Short Circuit Phase Reversal Under Voltage (1) Over Voltage (1) Starts Per Hour 2 Speed Motor Stator RTD (1)
Bearing RTD (1)
Ambient RTD (1)
Trip class 10 10...30 5...30 5...30 1...600 5...30Manual reset Automatic reset Single phase Three phase Warnings
Fault History General FeaturesCommunication (1) Logic Functions Local display I/O Soft Starter ControlSoft Start Kick Start Curent Limit Dual ramp Start Full Voltage Soft Stop Pump Control Preset Slow Speed
Linear Speed Braking Accu-Stop Slow Speed with Braking Suitable for inside the delta wiring Variable Speed ControlVariable SpeedFlying StartS - CurveProcess Control Loop (PIDFast Flux UpFast Brake to StopFlux BrakingSpeed ProfilesClose Loop Speed ControlClose Loop Torque Control
P-jump (Traverse Function)Pump/Fan Application FunctionsLifting Application FunctionsWinder Application FunctionsElectronic Gearing/Line ShaftMotion Control FunctionsSafe-OffMechanical ProtectionOverall Vibration levelUnbalanceMisalignmentFlow problemsBearing DefectsMechanical LoosenessRubbingDrive Belt Problems
-
7/31/2019 Dolsmc Sg001 en p
29/3227
PF4M PF4 PF40 PF40P PF400 PF70 PF700 PF700H PF700S XM-16X XM-12X
NA NA NA NA NA NA NA NA NA
regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated regulated
no limits no limits no limits no limits no limits no limits no limits no limits no limitsNA NA NA NA NA NA NA NA NA
variable variable variable variable variable variable variable variable variable
(1)
(1) (1) (1) (1)
(1) (1) (1) (1)
(1) (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)With add on Modules.
-
7/31/2019 Dolsmc Sg001 en p
30/3228
-
7/31/2019 Dolsmc Sg001 en p
31/3229
-
7/31/2019 Dolsmc Sg001 en p
32/32
For More Information
For more information about Rockwell Automation Services and Support go towww.rockwellautomation.com/services. To learn which other Rockwell Automation Services and
Support will be most beneficial to your maintenance strategy, contact your local authorised Allen-Bradley distributor or Rockwell Automation sales office.
PREDICT
PR
EVENT
RE
ACT
Assessment Services
Baseline evaluations of plant floor technical skills, procedures, equipment operation, spare parts inventory, risk,
safety and security as well as other automation-related assessments.
Condition Monitoring
Predictive Maintenance products and services for rotating equipment.
Asset Management Services
Maintenance Repair Operations (MRO) process and Spare Parts Management for automation assets.
Remote Support Services
Real-time troubleshooting and monitoring* of automation equipment and systems by off-site automation
specialists.
Safety, Network & Security Services
Network design and evaluation, security policy development/deployment, and machine safety services.
Training Services
Instructor-led training, self-paced training and competency testing on automation and related topics.
OnSite Support Services
Startup, troubleshooting, repair, conversions and Preventive Maintenance for automation equipment and
systems by Rockwell Automation Field Support Engineers.
Repair Services & Renewal Parts
Remanufacturing and exchange services for automation products and
build-to-order legacy automation products.
*System monitoring not available at all service levels
Rockwell Automation Services & Support