thermal modelling of a building with an integrated ventilated pv façade
TRANSCRIPT
Thermal modelling of a building with an integratedventilated PV facade
Li Meia,*, David Infielda, Ursula Eickerb,1, Volker Fuxb
aCentre for Renewable Energy Systems Technology (CREST), Department of Electronic and Electrical Engineering,
Loughborough University, Loughborough, Leicestershire LE11 3TU, UKbDepartment of Building Physics, Hochschule fur Technik, Schellingstr. 24, 70174 Stuttgart, Germany
Received 15 November 2001; accepted 25 September 2002
Abstract
This paper presents a dynamic thermal model based on TRNSYS, for a building with an integrated ventilated PV facade/solar air collector
system. The building model developed has been validated against experimental data from a 6.5 m high PV facade on the Mataro Library near
Barcelona. Preheating of the ventilation air within the facade is through incident solar radiation heating of the PV elements and subsequent
heat transmission to the air within the ventilation gap. The warmed air can be used for building heating in winter. Modelled and measured air
temperatures are found to be in good agreement. The heating and cooling loads for the building with and without such a ventilated facade have
been calculated and the impact of climatic variations on the performance such buildings has also been investigated. It was found that the
cooling loads are marginally higher with the PV facade for all locations considered, whereas the impact of the facade on the heating load
depends critically on location.
# 2002 Elsevier Science B.V. All rights reserved.
Keywords: Thermal modelling; Ventilated facade; PV; Building performance
1. Introduction
Integrating photovoltaic panels into a building facade
represents a significant step forward in the application of
this relatively new technology. Such a facade serves not only
as a renewable source of electricity, but also as a source of
heat for building heating and cooling. The authors have
recently completed an EU project which built on the experi-
ence gained in an earlier project concerned with the venti-
lated photovoltaic facade of the Mataro public library, near
Barcelona [1]. This recent project has taken the issue of
building integration an important step further, in that dedi-
cated solar air heaters have been incorporated into the upper
part of the facade in order to provide air heated to a
temperature sufficient for direct space heating purposes.
In order to achieve good heat transfer within the facade
and solar collectors and also to reduce the operating tem-
perature of the PV modules, forced convection was found
necessary since stack effect/buoyancy driven flow rates were
too limited.
Various authors have modelled the ventilated PV facade
by evaluation of energy inputs and outputs through radiation,
convection, conduction and power generated, [2] and [3].
These studies of the thermal energy balance are however
restricted to steady state conditions. In earlier work by the
authors, a dynamic general finite element thermal model for
ventilated PV facades was developed [4]. Based on this and
the TRNSYS program, a complete thermal building model
incorporating a ventilated PV facade and solar air collectors
has been assembled. The building model comprised of three
major components: the PV facade (PV panel, air gap and
inner double glazing); the solar air collectors; and a
TRNSYS single zone building model together with appro-
priate controller models. This paper outlines the main
features of the complete model. An investigation of the
heating and cooling energy required for the building has
been undertaken using the model. To assess the thermal
impact of the ventilated PV facade, heating and cooling
loads for the building with and without facade have been
calculated. In addition, the model has been used to assess the
performance of such buildings at different European loca-
tions, exhibiting contrasting climatic conditions.
Energy and Buildings 35 (2003) 605–617
* Corresponding author. Tel.: þ44-1509-228145;
fax: þ44-1509-610031.
E-mail addresses: [email protected] (L. Mei), [email protected]
(U. Eicker).1 Tel.: þ49-711-121-2831; fax: þ49-711-121-2666.
0378-7788/02/$ – see front matter # 2002 Elsevier Science B.V. All rights reserved.
PII: S 0 3 7 8 - 7 7 8 8 ( 0 2 ) 0 0 1 6 8 - 8
2. Thermal building model
The geometry of the Mataro library building is a rectan-
gular block which can be considered as having two levels. In
the modelling, only the upper level is taken into account
treated as a single zone, and the lower level is represented
through a constant temperature partition. This is appropriate
because the PV facade is attached only to the south wall of
the upper level with the lower level adjoining the soil. The
south side of the building is formed by the PV panels, the
solar air collectors and a conventional brick wall. The PV
panels contain blue polycrystalline silicon solar cells encap-
sulated in a clear glass–glass laminate in such a way to give
an overall transparency of 15%. The non-south facing
opaque walls are constructed of cellular concrete with
external steel covering. Windows of different size are fitted
on the north, west and east elevations. Fig. 1 gives a view of
the building showing the south and east elevations.
2.1. PV facade model
The PV facade structure consists of the PV panels and a
double glazed window, with a 14 cm air gap between.
Exterior air is entrained at the base of the facade and injected
via the air collector at the top into the building ventilation
system. Fig. 2 shows the PV facade structure and the thermal
transfer scheme. G represents the solar irradiation striking
the PV panel; Tp and Tg are the temperatures of ventilated
gap inside surfaces; hc,p and hc,g the respective convective
Nomenclature
Ac effective air collector area (m2)
Ap total PV panel area (m2)
Aw total windows area (m2)
bt, ct and
dt
transfer function coefficients
Cp specific heat capacity of air (J/kg K)
FR overall collector heat removal efficiency
factor
GrH Grashof number
GT incident radiation on the collector surface
(W/m2)
Gw incident radiation on the building surface
(W/m2)
hc,g convective heat transfer coefficient of
ventilated gap—glass window side
(W/m2 K)
hc,i heat transfer coefficient on the window
double glazing room side (W/m2 K)
hc,o heat transfer coefficient on the PV panel
exterior (W/m2 K)
hc,p convective heat transfer coefficient of venti
lated gap—PV panel side (W/m2 K)
kair thermal conductive coefficient of air
(W/m K)
kg thermal conductive coefficient of glazing
(W/m K)
ki thermal conductive coefficient of different
materials in Eq. (1) (W/m K)
kp thermal conductive coefficient of PV panel
(W/m K)
L long wave heat exchange gain (W/m2)
m ventilated air flow rate (kg/s)
Nu Nusselt number
qi internal heat source generated per unit
volume of the medium in Eq. (1) (W/m3)
Qinf l infiltration gain (W)
Qu total useful energy gain of air collector (W)
Qvent ventilation gain (W)
Qwd diffuse radiation entering windows (W)
Qwbf beam radiation through windows striking
floor (W)
Qwbs beam radiation through windows striking
other surfaces (W)
Qz heat gain through the wall and roof to the
building inside space (W/m2)
Re Reynolds number
S short wave radiation gain (W/m2)
Ta ambient air temperature (8C)
Teq equivalent room inside temperature, defined
by Eq. (15)
Tfacade facade room side surface temperature (8C)
Tg inner surface temperature of ventilated
gap—glass window side (8C)
Ti temperatures of the different construction
layers (8C)
Ti,c air collector inlet temperature (8C)
Tm air temperature in the gap (8C)
Tm,mean mean air temperature in the gap (8C)
To,c air collector outlet temperature (8C)
Tp inner surface temperature of ventilated
gap—PV panel side (8C)
Tsa solar air temperature (8C)
UL overall heat loss coefficient of collector
(W/m2 K)
Uw heat transfer coefficient of windows
(W/m2 K)
Greek letters
ai thermal diffusivity (m2/s)
eg surface emmisivity of double glazing
ep surface emmisivity of PV panel
Z air collector efficiency
n air velocity (m/s)
s Stefan–Boltzmann constant ¼ 5:67 � 10�8
W/m2 K4
ta effective transmittance–absorptance
product
u kinematic viscosity of air (m2/s)
606 L. Mei et al. / Energy and Buildings 35 (2003) 605–617
heat transfer coefficients for their inside surfaces; Tðx ¼ 0Þand Tðx ¼ LÞ the temperatures of PV panel outside surface
and the double glazing room side; hc,o and hc,i the convective
heat transfer coefficients for the PV panel outside surface
and the room inside surface; and x and y are the co-ordinates
associated with facade thickness and height.
Earlier studies made use of a simplified steady state
analysis [5], whereas here, a fully dynamic thermal model
for the ventilated PV facade, based on a numerical solution,
is presented.
From Fig. 2, it can be seen that the dynamical form of one-
dimension heat conduction in the x-direction for PV facade
can be expressed by Fourier’s equation:
@T2i
@x2þ qi
ki
¼ 1
ai
@Ti
@t(1)
where the Ti represent the temperatures of the different
construction layers, and are functions of time t and the layer
position x; ai ¼ ki=rcp is thermal diffusivities, ki is the thermal
conductivties of various materials; and qi represent the internal
heat sources generated per unit volume of the various materi-
als, corresponding to the part of solar radiation absorbed and
converted into thermal energy at the PV panel and the double
glazing. In this study, the transmittance–absorptance product
for PV panel has been taken to be constant at 0.8 to account for
the 15% transparency of the PV laminates mentioned above
and reflectance from the PV modules. At the same time, the
semi-transparency of the PV panel allows 15% of the short-
wave radiation to pass directly through the PV panel and the
double glazed window (i.e. ignoring absorption by the glass).
The boundary/initial conditions for Eq. (1) are determined
by the exterior and interior temperatures and the heat
flux:
�kp@T
@xjx¼0 ¼ hc;o½To � Tðx ¼ 0; tÞ (2)
and
�kg@T
@xjx¼L ¼ hc;i½Tðx ¼ L; tÞ � Ti (3)
with Tðx; t ¼ 0Þ ¼ 20 8C taken as initial value.
Here, kp and kg are the thermal conductivities of the PV
panel and the glazing, respectively, and hc,o and hc,i are the
surface heat transfer coefficients on the PV panel exterior
and double glazing, respectively. In the computations, hc,o
and hc,i are considered to be constant at 15 and 5 W/m2 K,
respectively. The constant value of hc,o represents a fixed low
wind speed and this reflects the lack of available local wind
speed data for model validation purposes.
A Crank–Nicolson method [6] was used to solve the
Eqs. (1)–(3). This method compared with the other finite
difference solutions has the advantage of being uncondi-
tionally stable and tolerating variable time-steps. This
numerical model can be integrated easily into other dynamic
simulation programs, such as TRNSYS.
The energy balance between the facade and the ventila-
tion air can be expressed by
hc;pðTp � TmÞ þ hc;gðTg � TmÞ ¼ mCp
dTm
dy(4)
Fig. 1. Geometry of the Mataro library building.
Fig. 2. PV facade structure and thermal transfer scheme.
L. Mei et al. / Energy and Buildings 35 (2003) 605–617 607
where m is the air flow rate and Cp the specific heat capacity
of air. Surface temperatures of the PV panel and glass
window within the air gap can be determined by the layer
temperatures given by Eqs. (1)–(3). By solving Eq. (4), the
air temperature in the gap Tm can be expressed as a function
of the gap height y:
TmðyÞ ¼ exp �ðhc;p þ hc;gÞymCp
� �Tin
þ 1�exp �ðhc;p þ hc;gÞymCp
� �� �hc;pTp þ hc;gTg
hc;p þ hc;g
� �:
(5)
The mean air temperature can be obtained by integrating Tm
from y ¼ 0 to H:
Tm;mean ¼ 1
H
Z H
0
TmðyÞdy ¼ 1 � exp �ðhc;p þ hc;gÞHmCp
� �� �
� Tin � ðhc;pTp þ hc;gTgÞ=ðhc;p þ hc;gÞðhc;p þ hc;gÞH=mCp
� �
þ hc;pTp þ hc;gTg
hc;p þ hc;g(6)
where Tin is the inlet temperature for the ventilated chamber
which is approximately equal to the ambient air temperature,
and for simplicity is taken to be exactly so in this study.
It can be seen from Eq. (6) that the air temperature in the
ventilated chamber only depends on the two surface tem-
peratures, Tp and Tg, when the air mass flow rate, the inlet
temperature Tin and the convective coefficients are known.
Inserting Tm,mean as a layer temperature between Tp and Tg,
the finite deference solution can be applied to whole PV
facade for thermal transmission through the air gap.
The convective heat transfer coefficients within the gap,
hc,p and hc,g, are far from straightforward to estimate. This is
because, in reality, the heat transfer processes involve a
combination of forced and natural convection, laminar and
turbulent flow and, certainly in the entrance region, simul-
taneously developing flow (in which the hydrodynamic and
thermal flow profiles are both evolving). For such lower air
flow velocities (<0.5 m/s), it is essential to model an appro-
priate mixture of flow conditions. As is common, the non-
dimensional Nusselt number has been used to estimate the
heat convection coefficient hc. A useful expression of the
Nusselt number, for mixed flow condition is [7]:
�Nu ¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi�Nu2
lam þ �Nu2turb
q(7)
with
�Nulam ¼ 0:644ffiffiffiffiffiffiRe
p ffiffiffiffiffiPr
3p
;
�Nuturb ¼ 0:037Re0:8Pr
1 þ 2:444Re�0:1ðPr2=3 � 1Þwhere
Re ¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiRe2
force þ Re2H;free
q(8)
and
Reforce ¼nH
u; ReH;free ¼
ffiffiffiffiffiffiffiffiGrH
2:5
r
where Re is the Reynolds number, Pr the Prandtl number and
GrH the Grashof number, n the air velocity, and u the
kinematic viscosity of air (m2/s). Using the properties of
air at the mean air temperature, the convection heat transfer
coefficient can be obtained directly from the Nusselt number
in the normal way:
hc ¼�Nu � kair
D(9)
where kair is the thermal conductivity of air and D the plate
spacing.
By applying Eqs. (7)–(9) independently for the two vertical
surfaces, namely, the PV panel and the double glazing, the
coefficients hc,p and hc,g can be calculated. These are found to
provide a good agreement between the measured and calcu-
lated air chamber temperatures, and justify the idealisation of
two independent surfaces irrespective of the relatively small
distance (140 mm) between them.
The long wave radiant heat exchange between the sur-
faces inside the PV gap is straightforwardly modelled by
Qp=g ¼ Ap
sðT2p þ T2
g ÞðTp þ TgÞð1=epÞ þ ð1=egÞ � 1
ðTp � TgÞ (10)
where ep and eg are the surface emmisivities of the PV panel
and double glazing (0.88), respectively, and s the Stefan–
Boltzmann constant. Eq. (10) presents a standard linearised
internal heat exchange relation and will be used throughout
to approximate the radiative heat exchange for the facade. In
the numerical solution of the PV facade model, the calcu-
lated radiative heat flow is added (i.e. as treated heat gain) to
the colder surface, and is subtracted (as heat loss) from the
warmer surface. The complete calculation (i.e. solution of
Eqs. (1)–(6)) is repeated with the already calculated heat
gains/losses, and the resulting layer temperatures re-deter-
mined as before. This iterative process is repeated until
sufficient convergence is achieved.
Considering the different thermal properties of materials,
the PV facade is considered as three distinct sections: the PV
panel; the double glazing; and the air gap between. The PV
panel itself contains three distinct layers: glass/PV/glass.
The double glazing also in principal contains three layers but
these are not differentiated in this model. The thermal
properties for the various layers are listed in Table 1.
The numerical method described here is for one-dimen-
sional heat transfer, although the model allows the facade
to be divided into up to 50 segments in order to better
calculate the gap air temperature profile. All this assumes a
uniform temperature within each segments of each layer in
the vertical direction, and uniform solar radiation on the
exterior surface. For each segment the layer temperature
608 L. Mei et al. / Energy and Buildings 35 (2003) 605–617
(including the gap surface temperatures) and the gap outlet
temperature is calculated. The gap outlet temperature from
one segment becomes the inlet temperature for the next
segment placed above and so on.
2.2. Solar air collector model
The standard thermal model for solar air collectors, as
incorporated within the top section of the facade, is given by
the Hottel–Whillier, Bliss equation [8]:
Z ¼ Qu
GTAc¼ FRðtaÞ �
FRULðTi;c � TaÞGT
(11)
and
To;c ¼Qu
Cp _mþ Ti;c (12)
where Z is the collector efficiency, Qu the useful energy gain,
GT the total incident radiation on the collector surface, Ac the
effective collector surface area, FR the overall collector heat
removal efficiency factor, and UL the overall heat loss
coefficient of the collector. Ta, Ti,c and To,c are the tempera-
tures of the ambient air, the air collector inlet and the
collector outlet, respectively. It should be noted that the
inlet air temperature of the solar air collector, Ti,c is the outlet
air temperature of the ventilated facade since these are
connected in series. The back of the solar air collector is
assumed to be perfectly insulated from the interior of the
room.
Collector test results are normally presented as a linear
relation between Z and ðTi;c � TaÞ=GT with a intercept a
(FR(ta)) and slope of b (FRUL). With the values of a and b
known, this linear efficiency model can be used to straight-
forwardly calculate the useful energy gain and the collector
outlet temperature.
The values of a and b for different air velocities, were
obtained from experimental data provided by the manufac-
turer; these are listed in Table 2.
2.3. The completed building model
It can be seen from Fig. 1 that, aside from the limited
lower brick section, the south facing elevation of the build-
ing is taken up with the ventilated PV facade and solar air
collectors. The remaining surfaces of the building, the walls
orientated to the north, west and east, the ceiling and floor
are taken into account within the single zone representation
of the building.
In contrast to the facade model, the transient heat response
of the other surfaces of the building is represented using the
transfer function method [9]. This has been done in order to
keep the overall model manageable, and because the mod-
elling challenge of this work relates specifically to the
facade and not the conventional parts of the structure. In
this transfer function approach, which is supported by
TRNSYS, a conduction transfer function is used to describe
the heat fluxes at the inside of walls and the roof as a function
of previous values of the heat fluxes and previous values of
inside and outside temperatures. Application of the transfer
function approach to the heat gain/loss through the building
construction layers allows the heat flux to be expressed as
[9,10]:
Qz ¼Xt¼0
ðbtTsa;t � ctTeq;tÞ �Xt¼1
dtQz;t (13)
where t represents the time step (1 h steps are often sufficient
for building analysis and have been used here). The value of
t ¼ 0 represents the current time, t ¼ 1 represents previous
hour, and so on. Qz is the heat gain through walls and roof to
the building inside space via the corresponding transfer
function coefficients, and bt, ct and dt, the conduction
transfer function coefficients pre-calculated for representa-
tive wall and roof assemblies. These coefficients depend
only on the building construction layers and their thermo-
physical properties. For example, the west wall of the
Mataro building consists of three layers. These are a
0.007 m steel cover, a 0.14 m air space and a 0.25 m cellular
concrete wall. For this construction the transfer function
Table 1
The thermal properties of the PV facade
Left side wall Air gap Right side wall
Layer 1 Layer 2 Layer 3Layer 4
Layer 5 Layer 6 Layer 7
Material Glazed PV Glazed Air Glazed Air Glazed
Conductivity (W/m K) 0.8 0.8 0.8 0.8 0.021 0.8
Density (kg/m3) 2500 2500 2500 2500 1 2500
Capacity (J/K) 1000 1000 1000 1000 1000 1000
Width (m) 0.004 0.0045 0.004 0.14 0.004 0.012 0.004
Table 2
The collector test data
Velocity (m/s) Value a (W/m2 K) Value b (W/m2 K)
2.8 0.65 �11.6
2.2 0.64 �12.2
1.7 0.61 �13.1
1.1 0.51 �12.7
0.55 0.46 �11.7
L. Mei et al. / Energy and Buildings 35 (2003) 605–617 609
coefficients bt, ct and dt are estimated following [10] and
given by Table 3.
From Eq. (13), it can be seen that the conduction transfer
function represented by bt is driven by the solar air tem-
perature, Tsa. In TRNSYS this is calculated according to the
solar radiation and convective heat transfer occurring on the
exposed external surfaces [10]:
Tsa ¼ Ta þGw
hc;o(14)
where hc,o is the building outside convection heat transfer
coefficient which itself is a function of wind speed:
hc;o ¼ 5:7 þ 3:8 � wind speed, Ta is the ambient air tem-
perature, and Gw the total incident solar radiation absorbed
by walls or roof. As the surfaces are at the different
orientations they will receive differing amounts of solar
radiation, Tsa is therefore different for the each individual
surface of the building.
Teq of Eq. (15) is an equivalent room inside temperature
defined by
Teq ¼ Ti þS þ L
hc;i(15)
where Ti is the actual internal space air temperature. This
equivalent room inside temperature is coupled to the short-
wave radiation heat gain, S, absorbed by the internal surfaces
and the longwave heat exchange, L, between the internal
surfaces.
Direct shortwave radiation heat gain, S, due to solar
radiation penetrating windows is calculated from the inci-
dent beam and diffuse radiation components available from
climate data for the site. The proportion of incoming radia-
tion distributed onto the surfaces of wall, ceiling and floor is
calculated according to the total exchange factor as given for
example by [10]. To take the case of the floor for example,
the net shortwave radiation received is given by:
Sf ¼ Ffwð1 � rfÞQwd
Af
þ ð1 � rfÞQwbf
Af
þX
rsQwbsFfsð1 � rfÞAs
Af
(16)
where the subscripts f, w and s are for the floor, window and
other surfaces, respectively, r the surface reflectance, A the
surface area, F the exchange factor, Qwd the diffuse radiation
entering windows, and Qwbf and Qwbs are the fractional beam
radiation through the window striking floor and other sur-
faces, respectively. The first term of Eq. (16) represents the
diffuse radiation to the floor from the window, the second is
the beam radiation to the floor from the window, and the third
is the diffusely reflected beam radiation from other surfaces
absorbed by floor. If required, radiation from people, lighting
and equipment can also be added to the term S.
The longwave radiation heat exchange, L, between the
surfaces inside the zone is modelled using the linearised
radiative heat transfer coefficient, hr,s, which is a function of�T
3. For the purpose of estimating this coefficient, �T has been
assumed to be 20 8C. The small error introduced by this
assumption is not critical.
The thermal conduction through the window from ambi-
ent is given by
Qw ¼ AwUwðTa � TeqÞ (17)
where Uw is the reciprocal of the sum of the resistances of
the window, outside air and inside air surface, Aw the total
area of windows. Teq is the estimated equivalent zone
temperature.
The ventilation gains/losses to the zone are assumed to be
due to the building design ventilation rate of 9000 m3/h,
hence,
Qvent ¼ Cp _mventðTa � TiÞ (18)
where Qvent is the ventilation gain, _mvent the ventilation air
flow rate, Cp the specific heat of air.
The infiltration gain is given by
Qinf ¼ Cp _minf lðTa � TiÞ (19)
where Qinf l is the infiltration gain; the infiltration air flow
rate is given by
_minf l ¼ raVð0:1 þ 0:023jTa � Tij þ 0:07WÞ (20)
where V (12509 m3) is the building volume, and W the
external wind speed loading the building. This expression
for the infiltration flow rate is taken from the ASHRAE
Handbook of Fundamentals [9].
3. Model simulation and comparison withmeasured data
3.1. Integration of the PV facade model with TRNSYS
building model
As discussed previously, the dynamic PV facade thermal
model is solved using a finite difference method. Heat
transfer modelling for the other surfaces of the building
are based on the transfer function method as implemented in
Table 3
Transfer function coefficients for the west wall
t b c d
West wall
0 0.0000 5.60 1.00
1 0.0000 �13.93 �2.18
2 0.0015 12.51 1.68
3 0.0074 �5.01 �0.56
4 0.0076 0.91 0.08
5 0.0021 �0.07 �0.01
6 0.0002 0.00 0.00
7 0.0000 0.00 0.00
610 L. Mei et al. / Energy and Buildings 35 (2003) 605–617
the TRNSYS building simulation environment. In order to
combine the PV facade model with the building model, a
dynamic link library file (DLL) has been created containing
the new special type code (written in Delphi). This DLL file
is compiled in the TRNSYS simulation project and linked to
Fortran code which passes the input and output variables
associated with the facade model. All the thermal properties
of the PV facade are stored in a pre-processing input file
which can be edited by users and read by the TRNSYS
program.
To illustrate how the interface to this new special type
operates, the heat transfer to the interior from the facade is
examined. The heat flux from the room side surface of the
PV facade to the building internal space is considered as an
additional heat gain/loss to the single zone building model.
This heat gain/loss is calculated by
Qin ¼ hc � Ap � ðTfacade � TeqÞ
where Tfacade is the layer temperature of room side surface of
the facade, Teq the equivalent zone temperature calculated by
the single zone model, Ap the facade area, hc the convective
heat transfer coefficient, assumed to be 5 W/m2 K. In the
simulation, Teq is taken as the value calculated by the single
zone building model at the previous timestep.
3.2. Model validation for sample periods
Outputs from the complete thermal building model have
been compared with measured data from Mataro Library.
Three sets of measured temperatures during unoccupied
periods were used for comparison to the simulated results.
These were selected because during these times the HVAC
plant was not operating and there is thus no additional
thermal energy supplied to or extracted from the zone. In
these circumstances, the building performance is determined
only by the incident solar radiation and ambient environ-
ment (ambient temperature and wind speed).
The measured data from Mataro, including total horizon-
tal global radiation, outside air temperature and wind speed
are used as the time dependent input data for the building
model simulation. Other measured data, such as the building
inside air temperature, the outlet temperatures of the PV
facade gap and the air collectors are used to validate the
model.
Fig. 3. Room temperature comparison (summer).
Fig. 4. Room temperature comparison (summer).
L. Mei et al. / Energy and Buildings 35 (2003) 605–617 611
The horizontal radiation measured is used to generate the
total incident and beam incident radiation on the vertical
surfaces of the building in different orientations. This cal-
culation has been undertaken using the TRNSYS imple-
mentation of the Reindl solar processor and the Isotropic sky
models [10].
Measured data has been used to initialise the model.
However, the initial value of zone temperature was set to
a constant of 20 8C through the simulation in order to
calculate the longwave radiation heat exchange coefficient,
hr,s ð�T ¼ 20 �CÞ.
Figs. 3–5 show the measured room temperature together
with the simulated temperature for the three periods in
question. It can be seen that the simulated temperature
fluctuations are very close to the measured data. However,
the model response is slightly slower than the building’s.
This reflects the approximate value taken for the effective
internal thermal capacity used in the room temperature
calculation. The peak room temperature in summer is about
30 8C without air conditioning of the building. In winter the
room temperature can rise to 25 8C without heating. It is
clear that for the Mataro library building, with its large
Fig. 5. Room temperature comparison (winter).
Fig. 6. PV facade outlet temperature comparison (summer).
Fig. 7. Air collector outlet temperature comparison (summer).
612 L. Mei et al. / Energy and Buildings 35 (2003) 605–617
glazed south facing facade, the cooling load exceeds the
heating load.
The PV facade air gap outlet temperature and the air
collector outlet temperature for both simulation and mea-
surement are presented in the Figs. 6–11 for the different
measurement periods. The calculated PV gap outlet air
temperature compares well with the measured data. It
reaches up about 50 8C in summer, and about 35 8C on a
typical winter day. The simulated air collector outlet tem-
perature agrees reasonably the measured data, which can
reach up to 60 8C in summer and 50 8C in winter, although
during winter the measured air collector temperature
remains slightly higher than the simulated values for
extended periods.
Fig. 8. PV facade outlet temperature comparison (late summer).
Fig. 9. Air collector outlet temperature comparison (late summer).
Fig. 10. PV facade outlet temperature comparison (winter).
L. Mei et al. / Energy and Buildings 35 (2003) 605–617 613
4. Predicting the cooling load and heating loadusing the building model
4.1. The temperature control
The cooling and heating loads of the building depend of
course on the required interior temperature levels. In energy
rate control strategy for building heating/cooling loads
calculation was developed within TRNSYS. The maximum
and minimum room temperature limits are user-set con-
stants. For the purpose of estimating the heating/cooling
energy required for real buildings, the temperature setpoints
for occupied and unoccupied periods should be allowed to
differ. TRNSYS does not facilitate a straightforward imple-
mentation of this.
In order to represent the building energy management
approach used at Mataro, a simple energy control strategy
was developed. In this approach, a general HVAC plant
control model is connected to the Mataro building model for
calculating the heating/cooling energy required to maintain
the inside space temperature at the required setpoints. The
control strategy is illustrated in Fig. 12; it is a normal
feedback control loop in which the controller output U is
the required energy for heating or cooling purposes (equiva-
lent to the building heating and cooling loads). Heating loads
are treated as positive, whilst cooling loads take negative
values.
The temperature setpoints for the heating and cooling
seasons are selected as the actual building plant control
parameters used at Mataro:
� heating season: occupied time 20 8C, unoccupied time
17 8C;
� cooling season: occupied and unoccupied time 26 8C;
� weekend days are unoccupied time.
4.2. The air gap ventilator control
Since a ventilated PV facade can supply preheated air to
the building interior, improvements to the building control
system may be required in order to make effective use of the
warm air produced by the facade. Forced ventilation of air
through the facade can be controlled according to strategies
which reflect the varying conditions occurring during the
heating and cooling seasons. The ON/OFF control modelled
here can be summarised as:
� Winter condition (occupied time): if the facade tempera-
ture is 5 8C higher than the exterior air temperature and
the room temperature is lower than the setpoint, the
ventilator is operated and the pre-heated ventilation air
is directed to the air conditioning unit.
� Winter condition (unoccupied time): if the facade tem-
perature is 5 8C higher than the room temperature and the
room temperature is lower than the setpoint, the ventilator
is operated and the pre-heated ventilation air is directed to
the air conditioning unit.
� Summer condition: if facade temperature is higher than
38 8C, the ventilator is operated and the ventilated air is
vented directly to the exterior for facade cooling purposes.
Since continuous measurements from the Mataro library
spanning a whole year are not available, weather data
generated using the proprietary code, METEONORM
[11] has been used in the heating and cooling loads estima-
tion. Time dependent hourly data sets including global
horizontal radiation, ambient temperature and wind velocity
have been created for three locations: Barcelona; Stuttgart;
and Loughborough, in order to assess the performance of the
PV ventilated facade concept for differing EU climates.
Fig. 11. Air collector outlet temperature comparison (winter).
Fig. 12. The scheme for heating/cooling load prediction.
614 L. Mei et al. / Energy and Buildings 35 (2003) 605–617
4.3. The prediction results
Figs. 13 and 14 provide a snap-shot of room temperature
and the corresponding ambient temperature variations for
Barcelona during January and August, respectively. In
Fig. 13 (heating season), the last 2 days cover the weekend,
and the room temperature setpoint is 17 8C. It is clear that
during these 2 days the room temperature is higher than the
setpoint due to the higher ambient temperature. Thus, no
heating energy is required for these days. For remaining days
the library is in use and the room temperature is kept at the
setpoint (20 8C) by the heating system.
In Fig. 14 (cooling season), the supplied cooling power
must keep the room temperature at 26 8C. Of course, if the
room temperature is lower than the setpoint, cooling power
is not required. Thus, there is no cooling power supplied at
night during this period.
Simulations for Stuttgart and Loughborough have also
been carried out also based on METEONORM weather data.
The room temperature is maintained at the setpoint if it
lower than 17 8C/20 8C in winter or higher than 26 8C in
summer, using heating and cooling as required.
By integrating the heating and cooling power from the
simulations, the annual heating and cooling loads have been
estimated for the library building design located in Barce-
lona, Stuttgart and Loughborough. Note that no changes
were made to the building control specification. This was to
enable a comparison of operational performance in these
different climates. In reality marginally different levels of
insulation and plant design would apply. Fig. 15 shows the
annual heating/cooling loads calculated using the Mataro
simulation model for the three locations. The results reflect
the climatic conditions: as might be expected, the highest
heating loads are experienced in Stuttgart, whereas Barce-
lona with the hottest climate gives the highest cooling loads.
4.4. Comparison of heating and cooling loads for
the PV facade and a conventional structure
The building with neither PV facade nor solar air collec-
tors has been modelled to assess, by comparison, the facade
effects on the heating and cooling energy. The PV facade
(including the inner double glazing) and air collectors, of the
south side of the library are replaced by a conventional brick
construction with glazed window and entrance door. The
combined area of the window and door was chosen to match
to the 15% transparency of the PV facade.
Fig. 13. Estimated room temperature (winter).
Fig. 14. Estimated room temperature (summer).
Fig. 15. Annual heating/cooling loads.
L. Mei et al. / Energy and Buildings 35 (2003) 605–617 615
In Figs. 16 and 17, the heating and cooling loads for the
building with and without facade are compared. It can be
seen, contrary to expectation, that the ventilated PV facade
does not result in a larger heating contribution to the
conventional building for the colder climate areas of Stutt-
gart and Loughborough. This is because the PV facade
exhibits a larger heat loss coefficient than the conventional
brick wall. The higher heat loss from PV facade is not fully
compensated for by the pre-heating of useful ventilated air.
Reflecting the high solar gain, the cooling load is the
largest for the PV facade in Barcelona, where an annual
value of 51546 kWh is indicated by the simulation. For
Loughborough, the cooling loads with and without the
facade are both small and can be safely ignored.
4.5. The analysis for the ventilation heat gain
Simulation of the Mataro building with its PV facade and
solar air collectors also facilitates prediction of the ventila-
tion heat gain to be expected at three different locations.
Because of the differing climatic conditions, the proportion
of the total required heat load met from the heated ventila-
tion air varies significantly. It can be seen from Table 4 that
12% of the heating load can be supplied from the facade in
Barcelona, whereas only 2% of the ventilation heat load can
be supplied in Stuttgart or Loughborough. The average of
the outside temperature and incident solar radiation for
winter season are also illustrated in Table 4.
5. Conclusions
In this paper, a thermal building model that includes sub-
models of the ventilated PV facade and the additional solar
air collectors has been described. The model has been
validated against measured performance data when the
HVAC plant was not being operated. The modelled con-
tributions from the solar gain, and the heat loss for the
building as a whole, were captured with acceptable accuracy.
This model will be applied to refine the design of such
building, and the controls, as part of a planned future study.
Fig. 16. Cooling loads comparison.
Fig. 17. Heating loads comparison.
Table 4
Ventilation heat gains for three locations
Location Stuttgart Lboro Barcelona
Average outside temperature (8C) 3.35 5.27 11.1
Average incident radiation (kJ/h m2) 363 308 466
Average air collector temperature (8C) 8.93 10.05 16.5
Ventilation heat gain (kWh) 3779 3161 9339
Proportion of vent gain to heat load (%) 2.05 1.83 12.37
616 L. Mei et al. / Energy and Buildings 35 (2003) 605–617
Based on the developed building model, the heating
and cooling loads for the building, in different European
locations, have been estimated. From both measurement
and simulation, it can be seen that the PV facade outlet
air temperature reaches around 50 8C in summer and 40 8Cin winter. Twelve percent of heating energy can be saved
using the pre-heated ventilation of the air for the building
location in Barcelona in winter season. For Stuttgart
and Loughborough, only 2% heating energy can be saved,
although of course the design was not made within
these locations in mind. Indeed it is clear that for such
northern latitude, a far higher proportion of solar air
collector area would be appropriate. The work establishes
that accurate modelling of buildings incorporating venti-
lated PV facades can be achieved within the TRNSYS
environment, but an appropriate special type, as described
here, to represent the novel features of the facade itself
must be used.
Acknowledgements
The authors are grateful for the financial support from
the European commission, through contract JOR3-CT97-
0185.
References
[1] A. Lloret, et al., Lessons learned in the electrical system design,
installation and operation of the Mataro Public Library, in:
Proceedings of the 14th European PV Solar Energy Conference,
Barcelona, 1997, pp. 1659–1664.
[2] S. Krauter et al., Combined photovoltaic and solar thermal system for
facade integration and building insulation, Solar Energy 67 (2)
(1999) 239–248.
[3] J.A. Clarke, J.W. Hand, C.M. Johnstone et al., Photovoltaic-
integrated building facades, Renewable Energy 8 (1996) 475–479.
[4] U. Eicker, V. Fux, D. Infield, L. Mei, K. Vollmer, Thermal
performance of building integrated ventilated PV facades, in:
Proceedings of the ISES Solar World Congress, Jerusalem, 1999.
[5] D. Infield, L. Mei, U. Eicker, V. Fux, Understanding the potential of
ventilated PV facades, in: Proceedings of the ISES Solar World
Congress, Jerusalem, 1999.
[6] J.A. Clarke, Energy Simulation in Building Design, Hilger, Bristol,
1985, p. 84.
[7] F.P. Incropera, D.P. Dewitt, Introduction to Heat Transfer, Wiley,
New York, 1990, p. 524.
[8] J.A. Duffie, W.A. Beckman, Solar Engineering of Thermal Process,
Wiley, New York, 1993, p. 270.
[9] ASHRAE, Handbook of Fundamentals, New York, 1993.
[10] TRNSYS Reference Manual, Solar Energy Laboratory, University of
Wisconsin, Madison, USA, 1996.
[11] METEONORM-Global Meteorological Database for Solar Energy
and Applied Climatology, Handbook, Meteotest, Fabrikstrasse 14,
CH-3012 Bern, Switzerland.
L. Mei et al. / Energy and Buildings 35 (2003) 605–617 617