pentair binrun control valve user manual

40
PENTAIR BINRUN Control Valve User Manual

Upload: khangminh22

Post on 25-Apr-2023

0 views

Category:

Documents


0 download

TRANSCRIPT

PENTAIR BINRUN Control ValveUser Manual

Table of Contents

Function………….………………………………….……………………………….……..01

Features……………………................................................…......................................01

Specifications………………………………….……………………….……………….…...01 Standard Universal Models.…………….……………………………………………..01 Product Models………………….…………..………………….…………………..01 Product Specifications…………………………………..…………………….…....01 Standard Parts…………..….…...……………………..……………………….…..01 Optional Parts………………………………………..………………………….…..02 Other Optional Accessories…………………………………………………….…..02 Warning………………..…………………………..…………………………….…..02

Valve Features and Dimensions…..………………………………………………………05

Installation Instructions…..…………………………………………………………………03

Softener Timer Valve / Filter Valve profile……………….…..………………… ……..05 Softener Meter Valve profile……………………………….……………………………..06

Standard Electric Valve profile…………………………….…………………………. .07 Electric Flow Meter Valve profile………………………………………………… ……..08

Water Conditioner Flow Diagrams….……………………….……….………..………. 09

Control Start-up Procedures……….…………………………………………………..…. 11 Mechanical Softener Valve………….…………………………………………………..11 Mechanical Softener Flow Meter Valve………….…………………………… ……..12 Mechanical Filter Valve.……………..………………………………………..…… …..13 Electric Valve……..……………....………………………………………………… …..14

Service Instructions………………………………………………………………….……27 To Remove Brine Valve, Injectors and Screen..……..……….……………………….27 To Replace Timer………..………….…..………………………………..………...…..28 To Replace Piston Assembly…………..………..……………………………..…...…28 To Replace Seals and Spacers…..…………………………………………….….…..29 To Replace Flow Meter……...……………………………...……………..……….….30 To Replace Meter Cover and/or Impeller.………...………………………..………...31

Troubleshooting…….……………………………………………….…………….………32 Softener Valve…….……………………………………………..……………………….32 Filter Valve…….………………………………………..…………………….…………..33 Electric Valve………………………………… ………..…………………….…………..34

BINRUN Control Valve User Manual

Pentair Water

BINRUN Control Valve User Manual

Pentair Water | Page 01

Function

Widely used in residential Softeners, Filters and other water solution products to perform automatic resin regeneration and filter media backwash.

Features

◆ Aesthetic Appearance Small and Compact◆ Clear Display Clear display for regeneration and backwash◆ Different control mode Timer or Metered regeneration◆ Reliable performance Durable and has passed leak test and Quality Checks◆ Manual Function Regeneration or Backwash can be reset manually◆ Simple operation Automatic, User-friendly, 7- or 12- day regeneration cycle

Specifications

◆ Standard Universal ModelProduct Models

Product Specifications

* (14.5 PSI = 0.1MPA)

Standard Parts

X X

XXX

X

BINRUN Control Valve User Manual

Pentair Water | Page 02

1BLFC (Brine Line Flow Control), refill rate for filling brine tank.2DLFC (Drain Line Flow Control), backwash and rapid rinse flow rates.

Optional Parts

NOTE: Due to varying water conditions, tank sizes and water pressures, the above settings should be used only as a guideline. (14.5 PSI = 0.1MPA)1BLFC (Brine Line Flow Control), refill rate for filling brine tank. 2DLFC (Drain Line Flow Control), backwash and rapid rinse flow rates.

Other Optional Accessories

Warning

WATER PRESSURE: A minimum of 1.5Bar(0.15MPa) of water pressure is required for regeneration valve to operate effectively.ELECTRICAL FACILITIES: An uninterrupted alternating current (A/C) supply is required. Note: Other voltages are available. Please make sure your voltage supply is compatible with your unit before installation.EXISTING PLUMBING: Condition of existing plumbing should be free from lime and iron buildup. Piping that is built up heavily with lime and/or iron should be replaced. If piping is clogged with iron, a separate iron filter unit should be installed ahead of the water softener.LOCATION OF SOFTENER AND DRAIN: The softener should be located close to a drain to prevent air breaks and back flow.

BY-PASS VALVES: Always provide for the installation of a by-pass valve if unit is not equipped with one.CAUTION: Water pressure is not to exceed 90Psi(0.6MPa), water temperature is not to exceed 104°F(40℃), and the unit can‘t be subjected to freezing conditions.INSTALLATION INSTRUCTIONS:1. Place the softener tank where you want to install the unit making sure the unit is level

and on a firm base.2. During cold weather, the installer should warm the valve to room temperature before

operating.3. All plumbing should be done in accordance with local plumbing codes. The pipe size

for residential drain line should be a minimum of 1/2” (13 mm). Backwash flow rates in excess of 7 gpm (26.5 Lpm) or length in excess of 20’ (6 m) require 3/4” (19 mm) drain line. Commercial drain lines should be the same size as the drain line flow control.

4. Refer to the dimensional drawing for cutting height of the distributor tube. If there is no dimensional drawing, cut the distributor tube flush with the top of the tank.

5. Lubricate the distributor O-ring seal and tank O-ring seal. Place the main control valve on tank. Note: Only use silicone lubricant.

6. Solder joints near the drain must be done prior to connecting the Drain Line Flow Control fitting (DLFC). Leave at least 6” (15 cm) between the DLFC and solder joints when soldering pipes that are connected on the DLFC. Failure to do this could cause interior damage to the DLFC.

BINRUN Control Valve User Manual

Pentair Water | Page 03

Installation Instructions

figure 1

figure 2

BINRUN Control Valve User Manual

Pentair Water | Page 04

7. Teflon tape is the only sealant to be used on the drain fitting. The drain from twin tank units may be run through a common line.

8. Make sure that the floor is clean beneath the salt storage tank and that it is level.9. Place approximately 1” (25 mm) of water above the grid plate. If a grid is not utilized,

fill to the top of the air check (Figure 2) in the salt tank. Do not add salt to the brine tank at this time.

10. on units with a bypass, place in bypass position. Turn on the main water supply. Open a cold soft water tap nearby and let run a few minutes or until the system is free from foreign material (usually solder) that may have resulted from the installation. Once clean, close the water tap.

11. Slowly place the bypass in service position and let water flow into the mineral tank. When water flow stops, slowly open a cold-water tap nearby and let run until the air is purged from the unit.

12. Plug unit into an electrical outlet. Note: All electrical connections must be connected according to local codes. Be certain the outlet is uninterrupted.

Valve Features and Dimensions

◆ Softener Timer Valve / Filter Valve profile (unit: mm)

BINRUN Control Valve User Manual

Pentair Water | Page 05

◆ Softener Meter Valve profile (unit: mm)

BINRUN Control Valve User Manual

Pentair Water | Page 06

◆ Standard Electric Valve profile (unit: mm)

BINRUN Control Valve User Manual

Pentair Water | Page 07

123

45

6

193 184

182

211

3

78

◆ Electric Flow Meter Valve profile (unit: mm)

BINRUN Control Valve User Manual

Pentair Water | Page 08

12

3

45

6

8

7

9

193 186

182

211

Water Conditioner Flow Diagrams

1. SERVICE POSITION

2. PRELIMINARY RINSE POSITION 4. BRINE POSITION

3. BACKWASH POSITION

Hard water enters the unit at the valve inlet – flows around the lower piston groove - thru the passage to the top of tank - down thru the resin and enters the distributor as conditioned water. The conditioned water flows up thru the center tube to the valve outlet.

Hard water enters the unit at the valve inlet - flows aroundthe lower piston groove - down thru the top of tank passage - downward thru the resin - up the distributor tube - thru the center hole in the piston - over the top edge of the piston and out the drain line.

Hard water enters the unit at the valve inlet - flows around the lower piston groove - thru the injector nozzle and orifice to draw brine from the brine tank. The brine flows down thru the resin - into the distributor - up thru the center tube - thru the center hole in the piston and out the drain line.

Hard water enters the unit at the valve inlet – flows around the lower piston groove and lower piston land - down thru the center tube and out the distributor – up thru the resin - thru the top of tank passage – around the upper piston groove and out the drain line.

BINRUN Control Valve User Manual

Pentair Water | Page 09

Water Conditioner Flow Diagrams

BINRUN Control Valve User Manual

Pentair Water | Page 10

5. SLOW RINSE POSITION

6. RAPID RINSE POSITION 8. BRINE TANK FILL POSITION

7. SETTLING RINSE POSITION

After all the brine has been drawn from the brine tank, hard water continues to enter thru the valve inlet - flows around the lower piston groove – thru the nozzle and orifice - down thru the resin and into the distributor - up thru the center tube - thru the center hole in the piston and out the drain line.

Hard water enters the unit at the valve inlet – flows around the lower piston groove and lower piston land - down thru the center tube and out the distributor – up thru the resin - thru the top of tank passage - around the upper piston groove and out the drain line.

Hard water enters the unit at the valve inlet - flows around the lower piston groove - thru the injector throat - thru the brine valve and flow control to fill the brine tank. Hard water also flows around the lower piston groove - thru the passage to the top of tank - down thru the resin and enters the distributor as conditioned water. The conditioned water flows up thru the center tube to the valve outlet.

Hard water enters the unit at the valve inlet – flows around the lower piston groove - down thru the top of tank passage - downward thru the resin - up the distributor tube - thru the center hole in the piston - over the top edge of the piston and out the drain line.

Control Start-up Procedures

◆ Mechanical Softener ValveManually index the softener control into the service position and let water flow into the resin tank. When the water flow stops, open a softened water tap until all air is released from the lines, then close the tap.

1. Manually index the control to the backwash position and allow water to flow at the drain for 3 or 4 minutes.

NOTE: the various regeneration positions may be dialed manually by turning the knob on the front of the control until the indicator shows that the softener is in the desired position.

2. Remove back cover plate.

3. Make sure that the salt dosage is set as recommended by the manufacturer. If necessary, set salt in accordance with the setting instruction sheet. Manually index the control to the brine fill position and allow the brine tank to fill to the top of the air check.

4. Manually index the control to the brine draw position and allow the control to draw water from the brine tank until it stops.

5. Plug in the electrical cord and look in the sight hole in the back of the motor to see that it is running. Set the days that regeneration is to occur by sliding tabs on skipper wheel outward to expose trip fingers. Each tab is one day. Finger at red pointer is tonight. Moving clockwise from red pointer, extend or retract fingers to obtain the desired regeneration schedule.

6. Manually advance the control to the beginning of the brine fill position; and allow the control to return to the service position automatically.

7. Fill the brine tank with salt.

8. Replace back cover on the control

9. Make sure that any by-pass valve/line is left in the normal service position.

BINRUN Control Valve User Manual

Pentair Water | Page 11

BINRUN Control Valve User Manual

Pentair Water | Page 12

◆ Mechanical Softener Flow Meter ValveThe water softener should be installed with the inlet, outlet and drain connections made in accordance with manufacturer’s recommendations and to meet applicable plumbing codes.

1. Manually index the softener control into the service position and let water flow into the resin tank. When the water flow stops, open a softened water tap until all air is released from the lines, then close the tap.

NOTE: The various regeneration positions may be dialed manually by turning the knob on the front of the control until the indicator shows that the softener is in the desired position.

2. Set water usage program wheel using any one of the following procedures:

Typical Residential Application3. To program, just set the time, set the hardness and it automatically monitors system needs and regenerates only when necessary. To set time of day press red time set button and turn 24 hour gear until present time of day is at “time of day”. Set program wheel by lifting the “people” dial and rotating it so that the number of people in the household is aligned with the household grains per gallon water hardness. Release the dial and check for firm engagement at setting. (This method will provide reserve capacity based on 75 gallons per person.)

Optional Programming Procedures4. Calculate the gallon capacity of the system, subtract the necessary reserve requirement and set the gallons available at the small white dot on program wheel gear. Note, drawing shows 850 gallon setting. The capacity (gallons) arrow denotes remaining gallons exclusive of fixed reserve.

5. Rotate the program wheel counterclockwise until it stops at regeneration position.

6. Manually index the control to the backwash position and allow water to flow at the drainfor 3 or 4 minutes.

7. Remove back cover plate.

8. Make sure than the salt dosage is set as recommended by the manufacturer. Manually index the control to the brine fill position and allow the brine tank to fill to the top of the air check.

9. Manually index the control to the brine rinse position and allow the control to draw water from the brine tank until it stops.

10. Plug in the electrical cord and look in the sight hole in the back of the motor to see that it is running.

11. Manually advance the control to the beginning of the brine fill position and allow the control to return to the service position automatically.

12. Fill the brine tank with salt.

13. Replace back cover on the control. Be sure cable is not pinched between cover and housing.

14. Make sure that any by-pass valve/line is left in the normal service position.

BEFORE PLUGGING THE UNIT IN

1. Open a treated water tap down stream of the filter.

2. Manually index the filter to the service position and allow the mineral tank to fill by slowly opening the main water supply valve. (any by pass should be in the service position)

NOTE: The water flowing from the down stream tap will be cloudy and/or contain media fines as well as air. Allow water to run until it appears clean and free of air.

3. When a steady clean flow appears at the tap, close the tap and the main water supply valve and allow the filter media bed to settle 15 - 20minutes.

4. Manually index the filter to the backwash position.

5. To prevent a sudden surge of water and air, partially open the main water supply valve so that the flow at the drain of the filter is approximately 1 gpm. The water at the drain will again be cloudy and/or contain media fines as well as air. Allow water to run until it appears clean and free of air.

◆ Mechanical Filter ValveThe filter should be installed with the inlet, outlet, and drain connections made in accordance with the manufacturer’s recommendations and to meet applicable plumbing codes.

BINRUN Control Valve User Manual

Pentair Water | Page 13

BINRUN Control Valve User Manual

Pentair Water | Page 14

6. Continue to open the water supply valve until it is completely open. Allow water to flow at the drain until all media fines are washed out of the filter.

7. Manually index the filter to the service position, and again open the down stream tap. Check to be sure that the water flows clear. If necessary allow water to flow until all media fines are gone. If the tap is equipped with an aerator check that it is not plugged with media fines and pipe scale.

8. Plug in the electrical cord and look in the sight hole on the back of the timer motor to ensure that it is running. Set the days backwashing is to occur by sliding tabs on the

skipper wheel outward to expose trip fingers. Each tab is one day. Finger at red pointer is tonight. Moving clockwise from red pointer, extend or retract fingers to obtain the desired backwash schedule.

9. Set time of day by depressing red button and spin the 24 hr gear until the present time of day is visible above the time of day arrow.

Step 1-Backwash

Regeneration Display

Step 2-Brine/RinseStep 3-Rapid RinseStep 4-Brine/Refill

Electric Valve◆

BINRUN Control Valve User Manual

Pentair Water | Page 15

1. Timer Features

2. Features of the SXT:• Power backup that continues to keep time and the passage of days for a minimum of 48

hours in the event of power failure. During a power outage, the control goes into a power-saving mode. It does not monitor water usage during a power failure, but it does store the volume remaining at the time of power failure.

• Settings for both valve (basic system) and control type (method used to trigger a regeneration).

• Day-of-the-Week controls.• While in service, the display alternates between time of day, volume remaining or days

to regeneration, and tank in service (twin tank systems only).• The Flow Indicator flashes when outlet flow is detected.• The Service Icon flashes if a regeneration cycle has been queued.• A Regeneration can be triggered immediately by pressing the Extra Cycle button for five

seconds.• The Parameter Display displays the current Cycle Step (BW, BF, RR, etc) during

regeneration, and the data display counts down the time remaining for that cycle step. While the valve is transferring to a new cycle step, the display will flash. The parameter display will identify the destination cycle step (BW, BF, RR, etc) and the data display will read “----”. Once the valve reaches the cycle step, the display will stop flashing and the data display will change to the time remaining. During regeneration, the user can force the control to advance to the next cycle step immediately by pressing the extra cycle button.

3. Setting the Time of Day 1) Press and hold either the Up or Down buttons until the programming icon replaces the

service icon and the parameter display reads TD.2) Adjust the displayed time with the Up and Down buttons.3) When the desired time is set, press the Extra Cycle button to resume normal operation.

The unit will also return to normal operation after 5 seconds if no buttons are pressed.

BINRUN Control Valve User Manual

Pentair Water | Page 16

4. Queueing a Regeneration1) Press the Extra Cycle button. The service icon will flash to indicate that a regeneration

is queued.2) To cancel a queued regeneration, press the Extra Cycle button.Regenerating Immediately1) Press and hold the Extra Cycle button for five seconds.

5. TIMER OPERATIONMeter Immediate ControlA meter immediate control measures water usage and regenerates the system as soon as the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity (typically expressed in grains/unit volume) by the feedwater hardness and subtracting the reserve. Meter Immediate systems generally do not use a reserve volume. However, in twin tank systems with softwater regeneration, the reserve capacity should be set to the volume of water used during regeneration to prevent hardwater break-through. A Meter Immediate control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.Meter Delayed ControlA Meter Delayed Control measures water usage and regenerates the system at the programmed regeneration time after the calculated system capacity is depleted. As with Meter Immediate systems, the control calculates the system capacity by dividing the unit capacity by the feedwater hardness and subtracting the reserve. The reserve should be set to insure that the system delivers treated water between the time the system capacity is depleted and the actual regeneration time. A Meter Delayed control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.Time Clock Delayed ControlA Time Clock Delayed Control regenerates the system on a timed interval. The control will initiate a regeneration cycle at the programmed regeneration time when the number of days since the last regeneration equals the regeneration day override value.Day of the Week ControlThis control regenerates the system on a weekly schedule. The schedule is defined in Master Programming by setting each day to either “off” or “on.” The control will initiates a regeneration cycle on days that have been set to “on” at the specified regeneration time.

6. User Programming ModePress the Up and Down buttons for five seconds while in service, and the time of day is NOT set to 12:01 PM.1) Day Override

Use this display to adjust the Day Override. This option setting is identified by “DO” in the upper left hand corner of the screen.

2) Regeneration TimePress the Extra Cycle button. Use this display to adjust the Regeneration Time. This option setting is identified by “RT” in the upper left hand corner of the screen.

3) Feed Water HardnessPress the Extra Cycle button. Use this display to adjust the Feed Water Hardness. This option setting is identified by “H” in the upper left hand corner of the screen.

4) Fixed Reserve CapacityPress the Extra Cycle button. Use this display to adjust the Fixed Reserve Capacity. This option setting is identified by “RC” in the upper left hand Corner of the screen.

BINRUN Control Valve User Manual

Pentair Water | Page 17

Range: 4-199 hardness

5) Current DayPress the Extra Cycle button. Use this display to set the Current Day of the Week. This option setting is identified by ”CD” in the upper left hand corner of the screen.

6) Press the Extra Cycle button to end User Programming Mode.

7. Master Programming ModeEntering Master Programming ModeSet the Time Of Day display to 12:01 P.M. Press the Extra Cycle button (to exit Setting Time of Day mode). Then press and hold the Up and Down buttons together until the programming icon replaces the service icon and the Display Format screen appears.Exiting Master Programming ModePress the Extra Cycle button to accept the displayed settings and cycle to the next parameter. Press the Extra Cycle button at the last parameter to save all settings and return to normal operation. The control will automatically disregard any programming changes and return to normal operation if it is left in Master Programming mode for 5 minutes without any keypad input.Resets:Soft Reset: Press and hold the Extra Cycle and Down buttons for 25 seconds while in normal Service mode. This resets all parameters to the system default values, except the volume remaining in meter immediate or meter delayed systems and days since regeneration in the time clock system.Master Reset: Hold the Extra Cycle button while powering up the unit. This resets all of the parameters in the unit. Check and verify the choices selected in Master Programming Mode.CAUTION: Before entering Master Programming, please contact your local professional water dealer.1) Display Format (Display Code DF)

This is the first screen that appears when entering Master Programming Mode. The Display Format setting specifies the unit of measure that will be used for volume and how the control will display the Time of Day. This option setting is identified by “DF” in the upper left hand corner of the screen. There are three possible settings:

BINRUN Control Valve User Manual

Pentair Water | Page 18

2) Valve Type (Display Code VT)Press the Extra Cycle button. Use this display to set the Valve Type. The Valve Type setting specifies the type of cycle that the valve follows during regeneration. Note that some valve types require that the valve be built with specific subcomponents. Ensure the valve is configured properly before changing the Valve Type setting. This option setting is identified by “VT” in the upper left hand corner of the screen. There are 6 possible settings:

3) Control Type (Display Code CT)Press the Extra Cycle button. Use this display to set the Control Type. This specifies how the control determines when to trigger a regeneration. For details on how the various options function, refer to the “Timer Operation” section of this service manual. This option setting is identified by “CT” in the upper left hand corner of the screen. There are four possible settings:Meter Delayed: FdMeter Immediate: FITime Clock: tcDay of Week: dAY

BINRUN Control Valve User Manual

Pentair Water | Page 19

Display Format Setting GALLtrCu

AbbreviationdF1bdF2bFltr

UFbdUFtrOthr

ParameterStandard Downflow/Upflow, Single BackwashStandard Downflow/Upflow, Double Backwash

FilterUpflow Brine First

Upflow FilterOther

Unit of VolumeU.S. Gallons

LitersCubic Meters

Time Display12-Hour AM/PM

24-Hour24-Hour

4) Number of Tanks (Display Code NT)Press the Extra Cycle button. Use this display to set the Number of Tanks in your system. This option setting is identified by “NT” in the upper left hand corner of the screen. There are two possible settings:Single Tank System: 1Two-Tank System: 2

5) Tank in Service (Display Code TS)Press the Extra Cycle button. Use this display to set whether tank one or tank two is in service. This option setting is identified by “TS” in the upper left hand corner of the screen. This parameter is only available if the number of tanks has been set to 2. There are two possible settings:Tank One in Service: U1Tank Two in Service: U2

6) Unit Capacity (Display Code C)Press the Extra Cycle button. Use this display to set the Unit Capacity. This setting specifies the treatment capacity of the system media. Enter the capacity of the media bed in grains of hardness when configuring a softener system, and in the desired volume capacity when configuring a filter system. This option setting is identified by “C” in the upper left hand corner of the screen. The Unit Capacity parameter is only available if the control type has been set to one of the metered options. Use the Up and Down buttons to adjust the value as needed.

BINRUN Control Valve User Manual

Pentair Water | Page 20

Range: 1-999,900 gallons (100-9,999,000 Liters)

7) Feedwater Hardness (Display Code H)Press the Extra Cycle button. Use this display to set the Feedwater Hardness. Enter the feedwater hardness in grains per unit volume for softener systems, or 1 for filter systems. This option setting is identified by “H” in the upper left hand corner of the screen. The feedwater hardness parameter is only available if the control type has been set to one of the metered options. Use the Up and Down buttons to adjust the value as needed.

8) Reserve Selection (Display Code RS)Press the Extra Cycle button. Use this display to set the Safety Factor. Use this display to select the type of reserve to be used in your system. This setting is identified by “RS” in the upper left-hand corner of the screen. The reserve selection parameter is only available if the control type has been set to one of the metered options. There are two possible settings.

9) Safety Factor (Display Code SF)Press the Extra Cycle button. Use this display to set the Safety Factor. This setting specifies what percentage of the system capacity will be held as a reserve. Since this value is expressed as a percentage, any change to the unit capacity or feedwater hardness that changes the calculated system capacity will result in a corresponding change to the reserve volume.This option setting is identified by “SF” in the upper left hand corner of the screen. Use the Up and Down buttons to adjust the value from 0 to 50% as needed.

BINRUN Control Valve User Manual

Pentair Water | Page 21

Range: 1-199 hardness

Range: 0-50%

SFrc

Safety FactorFixed Reserve Capacity

10) Fixed Reserve Capacity (Display Code RC)Press the Extra Cycle button. Use this display to set the Reserve Capacity. This setting specifies a fixed volume that will be held as a reserve. The reserve capacity cannot be set to a value greater than one-half of the calculated system capacity. The reserve capacity is a fixed volume and does not change if the unit capacity or feedwater hardness are changed. This option setting is identified by “RC” in the upper left-hand corner of the screen. Use the Up and Down buttons to adjust the value as needed.

11) Day Override (Display Code DO)Press the Extra Cycle button. Use this display to set the Day Override. This setting specifies the maximum number of days between regeneration cycles. If the system is set to a timertype control, the day override setting determines how often the system will regenerate. A metered system will regenerate regardless of usage if the days since last regeneration cycle equal the day override setting. Setting the day override value to “OFF” disables this function. This option setting is identified by “DO” in the upper left hand corner of the screen. Use the Up and Down buttons to adjust the value as needed.

12) Regeneration TimePress the Extra Cycle button. Use this display to set the Regeneration Time. This setting specifies the time of day the control will initiate a delayed, manually queued, or day override triggered regeneration. This option setting is identified by “RT” in the upper left hand corner of the screen. Use the Up and Down buttons to adjust the value as needed.

BINRUN Control Valve User Manual

Pentair Water | Page 22

Range: 0-half the calculated capacity

Range: Off-99 days

13) Regeneration Cycle Step TimesPress the Extra Cycle button. Use this display to set the Regeneration Cycle Step Times. The different regeneration cycles are listed in sequence based on the valve type selected for the system, and are identified by an abbreviation in the upper left-hand corner of the screen. The abbreviations used are listed below. If the system has been configured with the “OTHER” valve type, the regeneration cycles will be identified as R1, R2, R3, R4, R5, and R6. Each cycle step time can be set from 0 to 199 minutes. Setting a cycle step time to 0 will cause the control to skip that step during regeneration, but keeps the following steps available. Use the Up and Down buttons to adjust the value as needed. Press the Extra Cycle button to accept the current setting and move to the next parameter.

14) Day of Week SettingsPress the Extra Cycle button. Use this display to set the regeneration schedule for a system configured as a Day of Week control. The different days of the week are identified as D1, D2, D3, D4, D5, D6, and D7 in the upper left-hand corner of the display. Set the value to “ON” to schedule a regeneration or “OFF” to skip regeneration for each day. Use the Up and Down buttons to adjust the setting as needed. Press the Extra Cycle button to accept the setting and move to the next day. Note that the control requires at least one day to be set to “ON”. If all 7 days are set to “OFF”, the unit will return to Day One until one or more days are set to “ON.”

BINRUN Control Valve User Manual

Pentair Water | Page 23

Range: 0-199 minutes

AbbreviationBDBFBWRRSV

Cycle StepBrine DrawBrine Fill

BackwashRapid Rinse

Service

15) Current Day (Display Code CD)Press the Extra Cycle button. Use this display to set the current day on systems that have been configured as Day of Week controls. This setting is identified by “CD” in the upper left-hand corner of the screen. Use the Up and Down buttons to select from Day 1 through Day 7.

16) Flow Meter Type (Display Code FM)Press the Extra Cycle button. Use this display to set the type of flow meter connected to the control. This option setting is identified by “FM” in the upper left-hand corner of the screen. Use the Up and Down buttons to select one of the 7 available settings.

17) Meter Pulse Setting (Display Code K)Press the Extra Cycle button. Use this display to specify the meter pulse setting for a non-standard flow meter. This option setting is identified by “K” in the upper left-hand corner of the screen. Use the Up and Down buttons to enter the meter constant in pulses per unit volume.

BINRUN Control Valve User Manual

Pentair Water | Page 24

t0.7P0.7T1.0P1.0T1.5P1.5P2.0GEn

Fleck 3/4” Turbine MeterFleck 3/4” Paddle Wheel Meter

Fleck 1” Turbine MeterFleck 1” Paddle Wheel Meter

Fleck 1 1/2” Turbine MeterFleck 1 1/2” Paddle Wheel Meter

Fleck 2” Paddle Wheel MeterGeneric/Other Meter

18) End of Master Programming ModePress the Extra Cycle button to save all settings and exit Master Programming Mode.

1) Flow Rate (FR)Use this display to view the current Flow Rate. This option setting is identified by “FR” in the upper left hand corner of the screen.

2) Peak Flow Rate (PF)Press the Up button. Use this display to view the Peak Flow Rate since the last regeneration cycle. This option setting is identified by “PF” in the upper left hand corner of the screen.

3) Hours in Service (HR)Press the Up button. Use this display to view the Hours in Service since the last regeneration cycle. This option setting is identified by “HR” in the upper left hand corner of the screen.

4) View the Volume (VU)Press the Up button. Use this display to view the Volume Used since the last regeneration cycle. This option setting is identified by “VU” in the upper left hand corner of the screen.

NOTE: Some items may not be shown depending on timer configuration. The timer will discard any changes and exit User Mode if any button is not pressed for sixty seconds.

8. Diagnostic Programming ModePress the Up and Extra Cycle buttons for five seconds while in service.

BINRUN Control Valve User Manual

Pentair Water | Page 25

5) Reserve CapacityPress the Up button. Use this display to view the Reserve Capacity. This option setting is identified by “RC” in the upper left hand corner of the screen.

6) Software Version Press the Up button. Use this display to view the Software Version. This option setting is identified by “SV” in the upper left hand corner of the screen.

7) Press the Extra Cycle button to end Diagnostic Programming Mode.

BINRUN Control Valve User Manual

Pentair Water | Page 26

9. Reconnect brine tube and drain line.

10. Return by-pass or inlet valve to normal service position. Water pressure should now be applied to the conditioner, and any by-pass line shut off.

11. Check for leaks at all seal areas. Check drain seal with the control in the backwash position.

12. Plug electrical cord into outlet.

A. TO REMOVE TIME BRINE VALVE, INJECTORS, AND SCREEN

1. Unplug electrical cord from outlet.

2. Turn off water supply to conditioner: a. If the conditioner installation has a “three valve” by-pass system, first open the valve in the by pass line, then close the valves at the conditioner inlet and outlet. b. If the conditioner has an integral by-pass valve, put it in the by-pass position. c. If there is only a shut-off valve near the conditioner inlet, close it.

3. Relieve water pressure in the conditioner by putting the control in the backwash position momentarily. Return the control to the service position.

4. Disconnect brine tube and drain line connections at the injector body.

5. Remove the two injector body mounting screws. The injector and brine module can now be removed from the control valve. Remove and discard valve body O-rings

6a. To Replace Brine Valve

1. Pull brine valve from injector body, also remove & discard O-ring at bottom of brine valve hole.

2. Apply silicone lubricant to new O-ring and reinstall at bottom of brine valve hole.

3. Apply silicone lubricant to O- ring on new valve assembly and press into brine valve hole, shoulder on bushing should be flush with injector body.

6b. To replace injectors and screen.

4. Remove injector cap and screen, discard O-ring Unscrew injector nozzle and throat from injector body.

5. Screw in new injector throat and nozzle, be sure they are seated tightly. Install a new screen.

6. Apply silicone lubricant to new “O” ring and install around oval extension on injector cap.

7. Apply silicone lubricant to three new O-rings and install over three bosses on injector body.

8. Insert screws with washers thru injector cap and injector. Place this assembly thru hole in timer housing and into mating holes in the valve body. Tighten screws. (Be sure to reinstall brass spacers with injector on model 4600 valve.)

Service Instructions

BINRUN Control Valve User Manual

Pentair Water | Page 27

BINRUN Control Valve User Manual

Pentair Water | Page 28

13. Set time of day and cycle the control valve manually to assure proper function. Make sure the control valve is returned to the service position.

14. Make sure there is enough brine in the brine tank.

15. Rotate program wheel counter-clockwise until it stops at regeneration position

16. Start regeneration cycle manually if water is hard.

B. TO REPLACE TIMER

1. Unplug electrical cord from outlet.

2. Turn off water supply to conditioner: a. If the conditioner installation has a “three valve” by-pass system, first open the valve in the bypass line, then close the valves at the conditioner inlet and outlet. b. If the conditioner has an integral by-pass valve, put it in the by-pass position. c. If there is only a shut-off valve near the conditioner inlet, close it.

3. Relieve water pressure in the conditioner by putting the control in the backwash position momentarily Return the control to the service position.

4. Pull cable out of meter cover. Remove the control valve back cover.

5. Remove screw and washer at drive yoke. Remove timer mounting screws. The entire timer assembly will now lift off easily.

6. Put new timer on top of valve. Be sure drive pin on main gear engages slot in drive yoke (rotate control knob if necessary).

7. Replace timer mounting screws. Replace screw and washer at drive yoke.

8. Return by-pass or inlet valve to normal service position. Water pressure should now be applied to the conditioner, and any by-pass line shut off.

9. Plug electrical cord into outlet.

10. Set time of day, program wheel, and salt usage. Cycle the control valve manually to assure proper function. Make sure the control valve is returned to the service position.

11. Replace the control valve back cover. Be sure grommet at cable hole is in place.

12. Make sure there is enough brine in the brine tank.

13. Rotate program wheel counter-clockwise until it stops at regeneration position.

14. Start regeneration cycle manually if water is hard.

15. Plug cable into meter cover, rotate cable to align.

C. TO REPLACE PISTON ASSEMBLY

1. Unplug electrical cord from outlet.

2. Turn off water supply to conditioner: a. If the conditioner installation has a “three valve” by-pass system, first open the valve in the bypass line, then close the valves at the conditioner inlet and outlet.

b. If the conditioner has an integral by-pass valve, put it in the by-pass position. c. If there is only a shut-off valve near the conditioner inlet, close it.

3. Relieve water pressure in the conditioner by putting the control in the backwash position momentarily. Return the control to the service position.

4. Pull cable out of meter cover. Remove the control valve back cover.

5. Remove screw and washer at drive yoke. Remove timer mounting screws. The entire timer assembly will now lift off easily. Remove end plug retainer plate.

6. Pull upward on end of piston yoke until assembly is out of valve.

7. Inspect the inside of the valve to make sure that all spacers and seals are in place, and that there is no foreign matter that would interfere with the valve operation.

8. Take new piston assembly as furnished and push piston into valve by means of the end plug. Twist yoke carefully in a clockwise direction to properly align it with drive gear. Replace end plug retainer plate.

9. Place timer on top of valve. Be sure drive pin on main gear engages slot in drive yoke (rotate control knob if necessary).

10. Replace timer mounting screws. Replace screw and washer at drive yoke.

11. Return by-pass or inlet valve to normal service position. Water pressure should now be applied to the conditioner, and any by-pass line shut off.

12. Plug electrical cord into outlet.

13. Set time of day. Cycle the control valve manually to assure proper function. Make sure the control valve is returned to the service position.

14. Replace the control valve back cover. Be sure grommet at cable hole is in place.

15. Make sure there is enough brine in the brine tank.

16. Rotate program wheel counter-clockwise until it stops at regeneration position.

17. Start regeneration cycle manually if water is hard.

18. Plug cable into meter cover. Rotate cable to align drive flat if necessary.

D. TO REPLACE SEALS AND SPACERS

1. Unplug electrical cord from outlet.

2. Turn off water supply to conditioner. a. If the conditioner installation has a “three valve” by-pass system, first open the valve in the bypass line, then close the valves at the conditioner inlet and outlet. b. If the conditioner has an integral by-pass valve, put it in the by-pass position. c. If there is only a shut-off valve near the conditioner inlet, close it.

BINRUN Control Valve User Manual

Pentair Water | Page 29

3. Relieve water pressure in the conditioner by putting the control in the backwash position momentarily. Return the control to the service position.4. Pull cable out of meter cover. Remove the control valve back cover.

BINRUN Control Valve User Manual

Pentair Water | Page 30

5. Remove screw and washer at drive yoke. Remove timer mounting screws. The entire timer assembly will now lift off easily. Remove end plug retainer plate.

6. Pull upward on end of piston rod yoke until assembly is out of valve. Remove and replace seats and spacers with fingers.

E. TO REPLACE METER

1. Unplug electrical cord from outlet.

2. Turn off water supply to conditioner:a. If the conditioner installation has a “three valve” by-pass system, first open the valve in

the by-pass line, then close the valves at the conditioner inlet and outlet. b. If the conditioner has an integral by-pass valve, put it in the by-pass position. c. If there is only a shut-off valve near the conditioner inlet, close it.

3. Relieve water pressure in the conditioner by putting the control in the backwash position momentarily. Return the control to the service position.

4. Pull cable out of meter cover.

5. Remove two screws and clips at by-pass valve or yoke. Pull resin tank away from plumbing connections.

6. Remove two screws and clips at control valve. Pull meter module out of control valve.

7. Apply silicone lubricant to four new O-rings and assemble to four ports on new meter module.

8. Assemble meter to control valve. Note, meter portion of module must be assembled at valve outlet.

9. Attach two clips and screws at control valve. Be sure clip legs are firmly engaged with lugs.

10. Push resin tank back to the plumbing connections and engage meter ports with by-pass valve or yoke.

11. Attach two clips and screws at by-pass valve or yoke. Be sure clip legs are firmly engaged with lugs.

12. Return by-pass or inlet valve to normal service position. Water pressure should now be applied to the conditioner, and any by-pass line shut off.

13. Check for leaks at all seal areas.

14. Plug electrical cord into outlet.

15. Set time of day. Make sure the control valve is in the service position.

16. Rotate program wheel counter-clockwise until it stops at regeneration position.

17. Start regeneration cycle manually if water is hard.

18. Plug cable into meter cover. Rotate cable to align drive flat if necessary.

F. TO REPLACE METER COVER AND/OR IMPELLER

1. Unplug electrical cord from outlet.

2. Turn off water supply to conditioner:

a. If the conditioner installation has a “three valve” by-pass system, first open the valve in the bypass line, then close the valves at the conditioner inlet and outlet.

b. If the conditioner has an integral by-pass valve, put it in the by-pass position.

c. If there is only a shut-off valve near the conditioner inlet, close it.

3. Relieve water pressure in the conditioner by putting the control in the backwash position momentarily. Return the control to the service position.

4. Pull cable out of meter cover.

5. Remove four screws on cover.

6. Lift cover off of meter module, discard O-ring.

7. Remove and inspect impeller for gear or spindle damage, replace if necessary.

8. Apply silicone lubricant to new O-ring and assemble to the smallest diameter on meter cover.

9. Assemble cover to meter module. Be sure impeller spindle enters freely into cover. Press firmly on cover and rotate if necessary to assist in assembly.

10. Replace four screws and tighten.

11. Return by-pass or inlet valve to normal service position. Water pressure should now be applied to the conditioner, and any by-pass line shut off.

12. Check for leaks at all seal areas.

13. Plug electrical cord into outlet.

14. Set time of day. Make sure the control valve is in the service position.

15. Rotate program wheel counter-clockwise until it stops at regeneration position.

16. Start regeneration cycle manually if water is hard.

17. Plug cable into meter cover. Rotate cable to align drive flat if necessary.

BINRUN Control Valve User Manual

Pentair Water | Page 31

Troubleshooting

BINRUN Control Valve User Manual

A. Assure permanent electrical service (check fuse, plug, pull chain or switch).B. Replace timer.C. Reset time of day.

A. Electrical service to unit has been interrupted.

B. Timer is defective.C. Power failure.

1. Softener fails to regenerate

A. Check salt usage and salt setting.B. See problem No. 7.

A. Improper salt setting.B. Excess water in brine tank.

3. Unit uses too much salt.

A. Close by-pass valve.B. Add salt to brine tank and maintain salt level above water level.C. Replace injectors and screen.D. Check brine tank fill time and clean brine line flow control if plugged.E. Make sure distributor tube is not cracked. Check O-ring and tube pilot.F. Replace seals and spacers and/or piston.

A. By-pass valve is open.B. No salt in brine tank.

C. Injectors or screen plugged.D. Insufficient water flowing into brine

tank.E. Leak at distributor tube.

F. Internal valve leak.

2a. Softener delivers hard water.

A. Iron buildup in line to water conditioner.B. Iron buildup in water conditioner.

C. Inlet of control plugged due to foreign material broken loose from pipes by recent work done on plumbing system.

A. Clean line to water conditioner.

B. Clean control and add resin cleaner to resin bed. Increase frequency of regeneration.C. Remove piston & clean control.

4. Loss of water pressure.

5. Loss of resin through drain line.

A. Air in water system. A. Assure that well system has proper air eliminator control. Check for dry well condition.

6. Iron In Conditioned Water. A. Fouled resin bed. A. Check backwash, brine draw and brine tank fill, increase frequency of regeneration. Increase backwash time.

7a. Excessive water in brine tank.

A. Plugged drain line flow control. A. Clean flow control.

7b. Salt water in service line A. Plugged injector system.B. Timer not cycling.C. Foreign material in brine valve.D. Foreign material in brine line flow control.

A. Clean injector and replace screen.B. Replace timer.C. Clean or replace brine valve.D. Clean brine line flow control.

8. Softener fails to draw brine. A. Drain line flow control is plugged.B. Injector is plugged.C. Injector screen plugged.D. Line pressure is too low.

E. Internal control leak.

A. Clean drain line flow control.B. Clean or replace injectors.C. Replace screen.D. Increase line pressure. (Line pressure must be at least 20 PSI at all time.)E. Change seals and spacers and/or piston assembly.

PROBLEM CAUSE CORRECTION

Softener Valve

Pentair Water | Page 32

Troubleshooting

Filter Valve

A. Remove piston assembly and inspectbore, remove foreign material & check

control in various regeneration positions.B. Replace seals and/or piston assembly.C. Replace seals and/or piston assembly.

D. Replace timer.

A. Foreign material in control.

B. Internal control leak.C. Control valve jammed in brine or backwash position.D. Timer motor stopped or jammed

10. Drain flows continuously.

9. Control cycles continuous A. Faulty timer mechanism A. Replace timer.

A. Assure Permanent Electrical Service (Check Fuse,Plug,Pull Chain or Switch).

B. Replace or replace timer.C. Reset time of Day.

A. Electrical Service to unit has been interrupted.B. Timer is Defective.C. Power Failure.

1. Filter fails to backwash.PROBLEM CAUSE CORRECTION

A. Close by-pass valve.B. Reduce days between backwashing (see timer instructions.) Make sure that there is not a leaking valve in the toilet bowl or sinks.C. Repeated flushing of the hot water tank is required.D. Make sure distributor tube is not cracked. Check O-ring and tube pilot.E. Replace bed.

F. Make sure filter has correct drain flow control. Be sure flow control is not clogged or drain line restricted. Be sure water pressure has not dropped. Increase backwash flow rate according to specifications for your unit. See your dealer for recommendations.

A. By-pass valve is open.B. Excessive water usage.

C. Hot water tank rusty.

D. Leak at distributor tube.

E. Defective or stripped filter medium bed.F. Inadequate backwash flow rate.

2. Filter “bleeds” iron.

A. Iron or turbidity buildup in water filter.

B. Inlet of control plugged due to foreign material broken loose from pipes by recent work done on plumbing system.

A. Reduce days between backwashing so filter backwasher more often. Note: Make sure filter is sized large enough to handle water usage.B. Remove piston and clean control.

3. Loss of water pressure.

4. Loss of filter medium through drain line.

A. Broken or missing top screen. A. Replace top screen, must have . 020˝ wide slots.

A. Remove piston assembly and inspect bore, remove foreign material and check control in various cycle position.B. Replace seals and/or piston assembly.C. Replace piston and seals and spacers. (and drive motor if necessary).

A. Foreign material in control.

B. Internal control leak.C. Control valve jammed in rinse orbackwash.

5. Drain flows continuously

BINRUN Control Valve User Manual

Pentair Water | Page 33

Electric Valve

Troubleshooting

BINRUN Control Valve User Manual

Pentair Water | Page 34

Error CodesNOTE: Error codes appear on the In Service display.

ErrorCode Error Type Cause Reset and Recovery

Err - 0 Cam SenseError

The valve drive took longer than 6 minutes to advance to the next regeneration position

Unplug the unit and examine the powerhead. Verify that all cam switches are connected to the circuit board and functioning properly. Verify that the motor and drive train components are in good condition and assembled properly. Check the valve and verify that the piston travels freely. Replace/reassemble the various components as necessary.

Plug the unit back in and observe its behavior. The unit should cycle to the next valve position and stop. If the error re-occurs, unplug the unit and contact technical support.

Unplug the unit and examine the powerhead. Verify that all cam switches are connected to the circuit board and functioning properly. Enter Master Programming mode and verify that the valve type and system type are set correctly with regard to the unit itself.

Step the unit through a manual regeneration and verify that it functions correctly. If the error re-occurs unplug the unit and contact technical support.

The control experienced an unexpected cycle input

Cycle StepError

Err - 1

Troubleshooting

BINRUN Control Valve User Manual

Pentair Water | Page 35

ErrorCode Error Type Cause Reset and Recovery

The system has not regenerated for more than 99 days (or 7 days if the Control Type has been set to Day-of-Week)

Control board memory failure

RegenFailure

MemoryError

Err - 2

Err - 3

Perform a Manual Regeneration to reset the error code.

If the system is metered, verify that it is measuring flow by running service water and watching for the flow indicator on the display. If the unit does not measure flow, verify that the meter cable is connected properly and that the meter is functioning properly.

Enter a Master Programming Mode and verify that the unit is configured properly. As appropriate for the valve configuration, check that the correct system capacity has been selected, that the day override is set properly, and that meter is identified correctly. If the unit is configured as a Day-of-Week system.

Mode. After reconfiguring the system, step the valve through a manual regeneration. If the error re-occurs unplug the unit and contact technical support.

Pentair Water (Factory)Add.: No. 371, Heshan Road, New District, Suzhou China. 215011Tel.: 86 512 66617690Fax.: 86 512 66611178Website: www.pentairwater.cnHot line: 800-820-6671

Pentair Water (Office)Add.: 19F. Cloud 9 Plaza, No. 1118, West Yan’an Road, Shanghai, P.R.C. 200052 Tel.: 86 21 52507888Fax.: 86 21 52507996 / 52507998Website: www.pentairwater.cnHot line: 800-820-6671 BRMA002_Rev.B