FORM 150.27-EG1 (1210) 50 Through 170 Tons 175 Through 597 Kw 60Hz Model YCRL Remote Condenser Scroll Liquid Chiller Style A Products are produced at a facility whose quality- management systems are ISO9001 certified.

Upload: khangminh22

Post on 26-Mar-2023

0 views

Category:

Documents


0 download

TRANSCRIPT

FORM 150.27-EG1 (1210)

50 Through 170 Tons 175 Through 597 Kw

60Hz

Model YCRL Remote Condenser Scroll Liquid ChillerStyle A

Products are produced at afac i l i t y whose qua l i t y -management systems areISO9001 certified.

2 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

0096

Introduction ........................................................................................................................................................................................................... 3Specification ......................................................................................................................................................................................................... 4Microprocessor Controls ..................................................................................................................................................................................... 5Microprocessor Controls - continued ................................................................................................................................................................ 6Accessories and Options .................................................................................................................................................................................... 7Unit Components .................................................................................................................................................................................................. 8Refrigerant Flow Diagram .................................................................................................................................................................................... 9Design Parameters – English & SI .................................................................................................................................................................... 10Pressure Drop Curves - English & SI ..................................................................................................................................................... 11Selection Data ..................................................................................................................................................................................................... 12Ratings- English ................................................................................................................................................................................................. 16Physical Data – Standard & High Efficiency – English ................................................................................................................................... 18Isolator Selection Data ....................................................................................................................................................................................... 19Isolator Information ............................................................................................................................................................................................ 20Isolator Information - Continued ............................................................................................................................................................. 22Sound Data .......................................................................................................................................................................................................... 23Unit Dimensions - English - Four Compressor ................................................................................................................................................ 24Unit Dimensions - English - Five & Six Compressor ...................................................................................................................................... 26Electrical Data - Single Point ............................................................................................................................................................................. 28Electrical Data - Dual Point ................................................................................................................................................................................ 30Electrical Notes................................................................................................................................................................................................... 32Ground Wire Sizing ............................................................................................................................................................................................ 33Typical Control Panel Wiring ............................................................................................................................................................................. 34Customer Wiring Information ............................................................................................................................................................................ 38Application Data ................................................................................................................................................................................................. 40Guide Specifications .......................................................................................................................................................................................... 41

Table of Contents

NOMENCLATURE

3JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

YORK YCRL Remote Condenser Liquid Chillers provide chilled water for all air conditioning applications that use cen-tral station air handling or terminal units. They are self-contained and are designed for indoor (new or retrofit) installa-tion. Each unit includes hermetic scroll compressors, a liquid evaporator, and a user-friendly, diagnostic Microcomputer Control Center all mounted on a rugged steel base. Remote condensers (model VDC) are available seperately from Johnson Controls. The units are produced at an ISO 9001 registered facility. The YCRL chillers are rated in accordance with ARI Standard 550/590.

Model YCRL Remote Condenser Scroll Liquid Chillers

Introduction

4 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

GENERAL

The chiller will be completely assembled with all intercon-necting refrigerant piping and internal wiring, ready for field connection to a remote condenser.

The unit will be pressure-tested, evacuated, and charged with a nitrogen holding charge, and York ‘V’ (POE) syn-thetic oil.

The unit can be covered with an optional overspray coat of Caribbean Blue enamel. Units are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety Code for Mechanical Refrigeration. All units are produced at an ISO 9001 registered facility. All YCRL condensing units are rated in accordance with ARI Stan-dard 550/590 at ARI conditions.

COMPRESSORS

The chiller has suction-gas cooled, hermetic, scroll com-pressors. The YCRL’s compressors incorporate a compli-ant scroll design in both the axial and radial direction. All rotating parts are statically and dynamically balanced. A large internal volume and oil reservoir provides greater liquid tolerance. Compressor crankcase heaters are also included for extra protection against liquid migration. All compressors are mounted on isolator pads to reduce transmission of vibration to the rest of the unit.

REFRIGERANT CIRCUIT

Two independent refrigerant circuits will be furnished on each unit. All piping will be copper with brazed joints. The liquid line will include: a shutoff valve with charging port;

sight-glass with moisture indicator; thermal expansion valve; solenoid valve; and high-absorption removable-core filter drier. The entire suction line and the liquid line be-tween the expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation.

POWER AND CONTROL PANELS

All controls and motor starting equipment necessary for unit operation shall be factory wired and function tested. The panel enclosures shall be designed to NEMA 1 (IP 32) and manufactured from powder-painted galvanized steel.

The Power and Control Panel shall be divided into a power section for each electrical system, a common input section and a control section.

Each power panel shall contain:

Compressor starting contactors, control circuit serving compressor capacity control, compressor contactor coils and compressor motor overloads. The compressor motor overloads contain current transformers which sense each phase, as an input to the microprocessor, to protect the compressor motors from damage due to: low input current, high input current, unbalanced current, single phasing, phase reversal, and compressor locked rotor.

The common input section shall contain:

The control supply transformer providing 115V, customer relay board and control circuit switch dis-connect/emergency stop device.

Specification

5JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

MICROPROCESSOR CONTROLS

The control section shall contain:

On/Off rocker switch, microcomputer keypad and display, microprocessor board, I/O expansion board, relay boards, and 24V fused power supply board.

The control display shall include: Liquid Crystal Display with Light Emitting Diode

backlighting for outdoor viewing: • Two display lines • Twenty characters per line

Color coded 12-button non-tactile keypad with sec-tions for:

Display/Print of typical information: • Chilled liquid temperatures • System pressures (each circuit) • Operating hours and starts (each compressor) • Print calls up to the liquid crystal display: • Operating data for the systems • History of fault shutdown data for up to the last

six fault shutdown conditions • An RS-232 port, in conjunction with this press-

to-print button, is provided to permit the capabil ity of hard copy print-outs via a separate printer (by others).

Entry section to: • ENTER setpoints or modify system values

Setpoints updating can be performed to: • Chilled liquid temperature setpoint and range • Remote reset temperature range • Set daily schedule/holiday for start/stop • Manual override for servicing • Number of compressors • Low liquid temperature cutout • Low suction pressure cutout • High discharge pressure cutout • Anti-recycle timer (compressor start cycle time) • Anti-coincident timer (delay compressor starts)

Unit section to: • Set time • Set unit options

The microprocessor control center is capable of dis-playing the following:

• Return and leaving chilled liquid temperature • Low leaving liquid temperature cutout setting • English or Metric data • Suction pressure cutout setting • Each system suction pressure • Discharge pressure • Liquid Temperature Reset via a Building

Microprocessor Controls

FIG. 1 – CONTROL PANEL DETAILS

6 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Automation System via a 4-20 milliamp input or a 0-10 VDC input

• Anti-recycle timer status for each system • Anti-coincident system start timer condition • Compressor run status • No cooling load condition • Day, date and time • Daily start/stop times • Holiday status • Automatic or manual system lead/lag control • Lead system definition • Compressor starts & operating hours (each com

pressor) • Status of hot gas valves (if supplied) • Run permissive status • Number of compressors running • Liquid solenoid valve status • Load & unload timer status

The standard controls shall include: automatic pumpdown, run signal contacts, demand load limit form external build-ing automation system input, remote reset liquid tempera-ture reset input, unit alarm contacts, chilled liquid pump control, automatic reset after power failure, automatic system optimization to match operating conditions.

The operating program software shall be stored in non-volatile memory (EPROM) to eliminate chiller failure due to AC power failure. Programmed setpoints are retained in lithium battery-backed regulated time clock (RTC) memory for 5 years minimum.

COMMUNICATIONS• Native communication capability for BACnet (MS/TP)

and Modbus• Optional communciation available for N2 and LON via

eLink option

FIG. 2 – POWER PANEL DETAILS

Microprocessor Controls - continued

7JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

POWER OPTIONS:SINGLE POINT SUPPLY TERMINAL BLOCK - The standard power wiring connection on all models is a single point power connection to a factory provided terminal block. Components included are the enclosure, terminal-block and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring. (Factory-Mounted)

SINGLE POINT CIRCUIT BREAKER - An optional unit mounted circuit breaker with external, lockable handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power voltage for servicing. (Factory-Mounted)

MULTIPLE POINT CIRCUIT BREAKER – Optional mul-tiple point supply with independent system circuit breakers and locking external handles (in compliance with Article 440-14 of N.E.C.) can be factory supplied. (Factory-Mounted).

CONTROL TRANSFORMER – Converts unit power volt-age to 115-1-60 (0.5 or 1.0 KVA capacity). Factory mount-ing includes primary and secondary wiring between the transformer and the control panel. (Factory-Mounted)

CONTROLS OPTIONS:LANGUAGE LCD AND KEYPAD - Standard display language and keypad is in English. Spanish, French, German, and Italian are available as an option. (Factory-Mounted)

HEAT EXCHANGER OPTIONS:FLOW SWITCH – An optional flow switch can be factory supplied for the evaporator. Vapor-proof SPDT, NEMA 3R switch, 150 psig (10.3 bar) DWP, 20°F to 250°F (-29°C to 121°C) with 1” NPT (IPS) connection for upright mounting in horizontal pipe. The flow switch or its equivalent must be furnished with each unit. (Field mounted)

DIFFERENTIAL PRESSURE SWITCH - An alternative option to the paddle-type flow switch. 3-45 psig (0.2-3 bar) range with ¼” NPTE pressure connections. (Field Mounted)

PRESSURE VESSEL CODES - Evaporator is supplied (Standard) in conformance with the A.S.M.E. pres sure codes.

FLANGES (ANSI/AWWA C-606 COUPLINGS TYPE) – Consists of (2) flange adapters for grooved end pipe on evaporator. Standard 150 psig (10.3 bar). (Field Kit, matching pipe flange by contractor.)

DOUBLE THICK INSULATION – Doubled thickness (total-ling 1-1/2” or 38mm) insulation provided on the evaporator. (Factory-Mounted)

CHILLER OPTIONS:FINAL PAINT OVERSPRAY - Overspray painting of unit after assembly. (Factory-Mounted)

SERVICE ISOLATION VALVE - Service suction isolation valve added to unit per system in addition to the standard discharge service valve. (Factory-Mounted)

HOT GAS BY-PASS – Permits continuous, stable opera-tion at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit and operating conditions) by introducing an artificial load on the evaporator. Hot gas by-pass is installed on only refrigerant system #2 on two-circuited units. (Fac-tory-Mounted)

COMPRESSOR ACOUSTIC SOUND BLANKET – Each compressor is individually enclosed by an acoustic sound blanket. The sound blankets are made with one layer of acoustical absorbent textile fiber of 5/8” (15mm) thickness; one layer of anti-vibrating heavy material thickness of 1/8” (3mm). Both are closed by two sheets of welded PVC, reinforced for temperature and UV resistance. (Factory- Mounted)

VIBRATION ISOLATION:Rubber Isolators – Recommended for normal in stallations. Provides very good performance in most applications for the least cost. (Field-mounted)

1” Spring Isolators – Level adjustable, spring and cage type isolators for mounting under the unit base rails. 1” nominal deflection may vary slightly by ap plication. (Field -Mounted)

2” Seismic Isolators – Restrained Spring-Flex Mount ings incorporate a rugged welded steel housing with vertical and horizontal limit stops. Housings designed to withstand a minimum 1.0g accelerated force in all directions to 2”. Level adjustable, deflection may vary slightly by applica-tion. (Field-Mounted)

Accessories and Options

8 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

(OPT)

Unit Components

9JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Refrigerant Flow Diagram

Low-pressure liquid refrigerant enters the evaporator tubes and is evaporated and superheated by the heat energy absorbed from the chilled liquid passing through the evaporator shell. Low-pressure vapor enters the compressor where pressure and superheat are increased. High-pressure vapor is passed through a remote condenser where heat is rejected to the air flow passing through the coil. The fully condensed and subcooled liquid leaves the condenser and enters the expansion valve, where pressure reduction and further cooling take place. The low pressure liquid refrigerant then returns to the evaporator.

�������������

������������������������ �

������������

� ������

������������������

�����������������

������������

����������

������������������������������

�������������������

����� ���� �

�������������������

�������­��������  ���� �

�������������������� ���� �

���������

��­���������������������������

������������������������������

��­����������������������������

� ��������

����������������������

10 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Design Parameters – English & SI

NOTES:1. For leaving brine temperature below 40°F (4.4°C), contact the nearest Johnson Controls Office for application requirements.2. For leaving water temperature higher than 50°F (10°C), contact the nearest Johnson Controls Office for application guidelines.

DESIGN PARAMETERS – ENGLISH

YCWL MODEL

NUMBER

EVAPORATOR FLOW (GPM)

LEAVING EVAP. WATER TEMP. (°F)

MIN SAT. DISCH.

TEMP. (°F)

MAX. SAT DISCH TEMP

(°F)

EQUIPMENT ROOM TEMP. (°F)

MIN MAX MIN1 MAX2 MIN MAX MIN MAX 0064 100 450 40 50 80 130 40 115 0074 140 450 40 50 80 130 40 115 0084 140 450 40 50 80 130 40 115 0096 150 700 40 50 80 130 40 115 0118 140 700 40 50 80 130 40 115 0126 200 700 40 50 80 130 40 115 0156 200 700 40 50 80 130 40 115 0177 200 700 40 50 80 130 40 115 0198 200 700 40 50 80 130 40 115

DESIGN PARAMETERS – SI

YCWL MODEL

NUMBER

EVAPORATOR FLOW (L/S) LEAVING EVAP. WATER TEMP. (°C)

MIN SAT. DISCH.

TEMP. (°C)

MAX. SAT DISCH TEMP

(°C)

EQUIPMENT ROOM TEMP. (°C)

MIN MAX MIN1 MAX2 MIN MAX MIN MAX 0064 6.3 28.4 4.4 10 26.7 54 4.4 46 0074 8.8 28.4 4.4 10 26.7 54 4.4 46 0084 8.8 28.4 4.4 10 26.7 54 4.4 46 0096 9.5 44.2 4.4 10 26.7 54 4.4 46 0118 8.8 44.2 4.4 10 26.7 54 4.4 46 0126 12.6 44.2 4.4 10 26.7 54 4.4 46 0156 12.6 44.2 4.4 10 26.7 54 4.4 46 0177 12.6 44.2 4.4 10 26.7 54 4.4 46 0198 12.6 44.2 4.4 10 26.7 54 4.4 46

11JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Pressure Drop Curves - English & SI

1.0

10.0

100.0

10 100 1000Water Flow Rate (GPM)

C

B

DA

YCRL Evaporator Pressure Drop (English Units)

PressureDrop(ft.H

2O)

1.0

10.0

100.0

1000.0

1.0 10.0 100.0Water Flow Rate (l/s)

D

BA

C

YCRL Evaporator Pressure Drop (SI Units)

PressureDrop(kPa)

YCRL MODEL NUMBER EVAP

0064HE A

0074HE, 0084HE, 0118HE, B

0096HE C

0126HE, 0156HE, 0177SE, 198SE D

12 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Selection DataGUIDE TO SELECTIONComplete water chilling capacity ratings for YORK YCRL condensing units are shown on the following pages to cover the majority of job requirements. For any application beyond the scope of this Engineering Guide, consult your nearest Johnson Controls office.

SELECTION RULES

1. RATINGS - All YCRL ratings are in accordance with ARI Standard 550/590, at the ARI standard condi tions. Ratings not at standard ARI conditions are rated in ac-cordance with ARI rating procedures. These ratings may be interpolated but should not be extrapolated.

2. COOLING WATER QUANTITY - Ratings are based on 10ºF chilled water range with the evaporator at sea level. Use the chilled water correction factors (below) for other ranges except as limited by water pressure drop, minimum or maximum water flows for the evapo-rator.

3. FOULING FACTORS – Ratings are based on 0.0001 evaporator fouling factor. For other fouling factors, con-sult the table below or contact your Johnson Controls representative.

4. ETHYLENE GLYCOL CORRECTION FACTORS – The following factors are to be applied to the standard ratings for units cooling ethylene glycol.

Note: Temperature split factors @ 85ºF Entering Condenser Water Temp (ECWT)

5. PROPYLENE GLYCOL CORRECTION FACTORS – The following factors are to be applied to the standard ratings for units cooling propylene glycol.

METHOD OF SELECTION

If the duty requires a 10ºF (6°C) range on the evaporator, see “Ratings”. For water ranges other than 10ºF (6°C), use the following procedure. Line sizes can be determined by reviewing York DX Piping Guide 050.40-ES2.

EVAPORATOR CORRECTION FACTORS

0.0001 0.0003

Tons Tons

6 0.976 0.998 0.969 0.997

8 0.990 0.999 0.980 0.998

10 1.000 1.000 0.991 0.999

12 1.009 1.001 0.999 1.000

14 1.017 1.002 1.007 1.001

FF = Temp

Split Compr kW Compr kW

ETHYLENE GLYCOL

% WEIGHT TONS GPM

10 1 1 1 1.1 26

20 1 1 1 1.2 18

30 1 1 1.1 1.3 7

40 0.9 1 1.1 1.4 -8

50 0.9 1 1.1 1.6 -29

COMPR

KW

PRESS

DROP

FREEZE

PT

PROPELENE GLYCOL

% WEIGHT TONS GPM

10 1 1 1 1.1 26

20 1 1 1 1.2 19

30 0.9 1 1 1.3 9

40 0.9 1 1 1.4 -6

50 0.9 1 1 1.6 -28

COMPR

KW

PRESS

DROP

FREEZE

PT

13JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

1. Determine capacity required from the following for-mula

2. After applying any fouling factor corrections, the actual condenser heat rejection may be determined as fol-lows:

= (Tons x 12) = (kW x 3.415)

3. Size condenser using manufacturer’s recommenda-tions.

SAMPLE SELECTION

Water Cooled Chiller (YCRL)

GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and 0.0001 evaporator fouling factor with 125°F saturated discharge temperature.

FIND – The required unit size capacity, kW, EER, and water pressure drop, and the condenser MBH heat re-jection.

SOLUTION:

1. Chilled water range = 56ºF - 44ºF = 12ºF and correc-tion factors are 1.009 for Tons and 1.001 for kW for the evaporator.

2. From the rating, a model YCRL01180SE has a ca-pacity range required. For the evaporator leaving water temperature of 44ºF and a saturated discharge temperature of 125°F, the unit capacity rating table indicates:

Tons = 101.7KW = 110.0EER = 11.1

Capacity (Tons) =

GPM x Chilled Water Range (ºF)

24

Heat Rejection (MBH) =

Heat Rejection (Btuh)

1000

Correcting for the 12ºF chilled water range:

Tons = 101.7 x 1.009 = 102.6 TRKW = 110.0 x 1.001 = 110.1 kW

The unit is suitable.

3. Determine the average full load kW and EER at 100 Tons

4. Determine the cond. Heat rejection as follows:

Heat Rejection (MBH) = (Tons x 12) + (kW x 3.415)= (102.6 x 12) + (110.1 x 3.415)= 1231.2 + 376.0= 1607.2

5. From curves on page 11, locate the pressure drops with 200 GPM through the evaporator of the Model YCRL118SE:

Evaporator Pressure Drop at 200 GPM = 8 ft

Capacity (Tons) =

GPM x Chilled Water Range

24

= 200 x 12

24 = 100TR

�������� �������������������

����� �� ���������

�������������� ������

14 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Selection Data – continuedREFRIGERANT PIPING

General – When the unit has been located in its final position, the unit piping may be connected. Normal instal-lation precautions should be observed in order to receive maximum operating efficiencies. System piping should conform to the York DX Piping Guide form 050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and installation is the responsibility of the user.

JOHNSON CONTROLS ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM OPERATION OR FAIL-URES DUE TO IMPROPER PIPING OR PIPING DESIGN.

All filter driers, sight glasses, expansion valves and liquid line solenoid valves are factory installed on each refriger-ant circuit. Interconnecting refrigerant piping and refriger-ant charge are supplied and installed by others.

Table 2 lists refrigerant line connections sizes per unit model number.

REFRIGERANT LINE SIZING

Refrigerant piping systems must be designed to provide practical line sizes without excessive pressure drops, pre-vent compressor oil from being “trapped” in the refrigerant piping, and ensure proper flow of liquid refrigerant to the thermal expansion valve. Be sure to review form 050.40-ES2. Considerations should be given to:

1) Discharge line pressure drop due to refrigerant flow.

2) Discharge line refrigerant velocity for oil return.3) Liquid line pressure drop due to refrigerant flow.4) Liquid line pressure drop (or gain) due to vertical rise

of the liquid line.

To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line pressure drop should never exceed 40 psig (2.8 barg). Refrigerant vapor in the liquid line will measurably reduce valve capacity and poor system performance can be expected.

To allow adequate oil return to the compressor, discharge risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure oil return up the suction riser.

Chiller Below Condenser – On a system where the chiller is located below the condenser, the discharge line must be sized for both pressure drop and oil return. In some cases a double discharge riser must be installed to ensure reliable oil return at reduced loads.

Condenser Below Chiller – When the condenser is located below the chiller, the liquid line must be designed for both friction loss and static head loss due the vertical rise. The value of static head loss of 5 PSI/ft. (3.4 kPa/30 cm) must be added to the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc.

OIL TRAPS

All horizontal discharge lines should be pitched at least 1/4” per foot (2 cm/m) in the direction of the refrigerant flow to aid in the return of oil to the chiller. All discharge lines with a vertical rise exceeding 3 feet (.91 meters) should have a “P” trap at the bottom and top of the riser. Discharge lines with a vertical rise exceeding 25 feet (7.6 meters) should be trapped every 15 feet (4.6 meters).

REFRIGERANT CHARGE

The chiller is charged and shipped with a dry nitrogen holding charge. The operating charge for the chiller, remote condenser and refrigerant piping must be weighed in after all refrigerant piping is installed, leak checked, and evacuated. Final adjustment of refrigerant charge should be verified by subcooling values (refer to IOM section on Pre-Startup for checking subcooling).

REFRIGERANT PIPING REFERENCE

For more details, refer to ASHRAE Refrigeration Hand-book, Chapter 2.

15JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

TABLE 1 – YCRL CHILLER CHARGES

TABLE 2 – YCRL LINE CONNECTION SIZES

Note: Charge for remote condenser and interconnecting piping must be calculated separately.

MODEL 60Hz TOTAL HFC-410A CHARGE, lb. PER SYSTEM, lb

0064HE 34 17

0074HE 40 20

0084HE 82 41

0096HE 106 53

0118HE 90 45

0126HE 126 63

0156HE 126 63

0177SE 122 63/59

0198SE 126 63

UNIT SIZE (60HZ)

LIQUID LINE SYSTEM 1, IN.

LIQUID LINE SYSTEM 2, IN.

DISCHARGE LINE SYSTEM 1, IN.

DISCHARGE LINE SYSTEM 2, IN.

0064HE 7/ 8 7/ 8 1 3/ 8 1 3/ 8

0074HE 1 1/ 8 7/ 8 1 5/ 8 1 3/ 8

0084HE 1 1/ 8 1 1/ 8 1 5/ 8 1 5/ 8

0096HE 1 1/ 8 1 1/ 8 1 3/ 8 1 3/ 8

0118HE 1 1/ 8 1 1/ 8 1 5/ 8 1 5/ 8

0126HE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8

0156HE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8

0177SE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8

0198SE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8

16 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Ratings- English

NOTES:1. Tons = Unit Cooling Capacity Output2. KW = Compressor Input Power3. MBH = Condenser Heat Rejection4. EER = Chiller Energy Efficiency Ratio5. LCWT = Leaving Chilled Water Temperature

MODEL YCRL0064HE IPLV= 17.7SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 60.5 46.3 15.7 58.8 48.9 14.4 57.0 51.8 13.2 55.3 54.9 12.1 53.5 58.3 11.0 51.6 62.0 10.042.0 62.7 46.4 16.2 61.0 49.0 14.9 59.3 51.9 13.7 57.4 55.0 12.5 55.6 58.4 11.4 53.6 62.0 10.444.0 65.2 46.6 16.8 63.3 49.1 15.5 61.5 52.0 14.2 59.7 55.0 13.0 57.7 58.4 11.9 55.8 62.1 10.845.0 66.4 46.7 17.0 64.6 49.2 15.7 62.7 52.0 14.5 60.8 55.1 13.2 58.8 58.4 12.1 56.8 62.1 11.046.0 67.6 46.9 17.3 65.8 49.3 16.0 63.9 52.1 14.7 62.0 55.1 13.5 60.0 58.5 12.3 57.9 62.1 11.248.0 70.1 47.1 17.9 68.3 49.5 16.5 66.3 52.2 15.2 64.3 55.2 14.0 62.3 58.6 12.8 60.2 62.2 11.650.0 72.6 47.4 18.4 70.7 49.8 17.1 68.8 52.4 15.7 66.7 55.4 14.5 64.6 58.7 13.2 62.5 62.2 12.0

MODEL YCRL0074HE IPLV= 17.7SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 70.5 54.0 15.7 68.4 56.8 14.4 66.3 60.0 13.3 64.1 63.4 12.1 61.9 67.0 11.1 59.7 71.1 10.142.0 73.3 54.2 16.2 71.1 57.1 15.0 68.9 60.1 13.7 66.7 63.5 12.6 64.4 67.2 11.5 62.1 71.2 10.544.0 76.1 54.5 16.8 73.9 57.3 15.5 71.6 60.4 14.2 69.3 63.7 13.1 67.0 67.4 11.9 64.6 71.3 10.945.0 77.6 54.6 17.1 75.3 57.4 15.8 73.0 60.5 14.5 70.7 63.8 13.3 68.3 67.5 12.2 65.9 71.4 11.146.0 79.1 54.7 17.4 76.8 57.5 16.0 74.4 60.6 14.7 72.1 63.9 13.5 69.7 67.6 12.4 67.2 71.5 11.348.0 82.1 55.0 17.9 79.8 57.8 16.6 77.3 60.8 15.3 74.9 64.1 14.0 72.4 67.8 12.8 69.8 71.7 11.750.0 85.2 55.2 18.5 82.8 58.0 17.1 80.3 61.0 15.8 77.8 64.4 14.5 75.2 68.0 13.3 72.6 71.9 12.1

MODEL YCRL0084HE IPLV= 19.6SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 79.9 59.5 16.1 77.4 62.5 14.9 74.9 65.8 13.7 72.4 69.3 12.5 69.9 73.1 11.5 67.4 77.3 10.542.0 83.1 59.8 16.7 80.5 62.8 15.4 78.0 66.0 14.2 75.4 69.5 13.0 72.8 73.4 11.9 70.2 77.6 10.944.0 86.4 60.0 17.3 83.7 63.1 15.9 81.1 66.3 14.7 78.4 69.8 13.5 75.7 73.7 12.3 73.0 77.8 11.345.0 88.1 60.2 17.6 85.4 63.2 16.2 82.7 66.5 14.9 80.0 70.0 13.7 77.2 73.8 12.6 74.5 78.0 11.546.0 89.8 60.3 17.9 87.1 63.3 16.5 84.3 66.6 15.2 81.6 70.1 14.0 78.8 73.9 12.8 76.0 78.1 11.748.0 93.3 60.5 18.5 90.5 63.6 17.1 87.6 66.9 15.7 84.8 70.4 14.4 81.9 74.2 13.2 79.0 78.4 12.150.0 96.9 60.7 19.1 94.0 63.8 17.7 91.0 67.2 16.3 88.1 70.7 14.9 85.1 74.5 13.7 82.1 78.7 12.5

MODEL YCRL0096HE IPLV= 18.3SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 92.2 69.5 15.9 89.6 73.4 14.7 87.0 77.7 13.4 84.3 82.4 12.3 81.6 87.5 11.2 78.7 93.0 10.242.0 95.7 69.8 16.5 93.1 73.6 15.2 90.4 77.8 13.9 87.6 82.5 12.7 84.8 87.6 11.6 81.9 93.1 10.644.0 99.3 70.1 17.0 96.6 73.8 15.7 93.8 78.0 14.4 91.0 82.6 13.2 88.1 87.7 12.1 85.1 93.1 11.045.0 101.2 70.3 17.3 98.4 74.0 16.0 95.6 78.1 14.7 92.7 82.7 13.5 89.7 87.7 12.3 86.7 93.1 11.246.0 103.0 70.4 17.5 100.2 74.1 16.2 97.4 78.2 14.9 94.4 82.8 13.7 91.4 87.8 12.5 88.4 93.2 11.448.0 106.8 70.9 18.1 104.0 74.4 16.8 101.0 78.5 15.4 98.0 83.0 14.2 94.9 87.9 13.0 91.7 93.3 11.850.0 110.7 71.3 18.6 107.8 74.8 17.3 104.7 78.8 16.0 101.6 83.2 14.7 98.5 88.1 13.4 95.2 93.4 12.2

MODEL YCRL0118HE IPLV= 20.1SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 109.7 84.0 15.7 106.8 88.5 14.5 103.9 93.2 13.4 100.8 98.3 12.3 97.7 103.7 11.3 94.4 109.5 10.342.0 113.8 84.3 16.2 110.8 88.8 15.0 107.8 93.5 13.8 104.6 98.6 12.7 101.4 104.0 11.7 98.0 109.8 10.744.0 118.0 84.5 16.8 114.9 89.0 15.5 111.8 93.8 14.3 108.5 98.9 13.2 105.2 104.3 12.1 101.7 110.0 11.145.0 120.2 84.6 17.0 117.0 89.1 15.8 113.8 93.9 14.5 110.5 99.0 13.4 107.1 104.4 12.3 103.6 110.2 11.346.0 122.3 84.8 17.3 119.2 89.3 16.0 115.9 94.1 14.8 112.6 99.1 13.6 109.1 104.5 12.5 105.5 110.3 11.548.0 126.7 85.0 17.9 123.5 89.5 16.5 120.1 94.3 15.3 116.7 99.4 14.1 113.1 104.8 12.9 109.4 110.6 11.950.0 131.2 85.2 18.5 127.8 89.8 17.1 124.4 94.6 15.8 120.9 99.7 14.5 117.2 105.1 13.4 113.4 110.9 12.3

17JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

MODEL YCRL0126HE IPLV= 20.6SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 120.6 91.2 15.9 117.0 95.8 14.7 113.3 100.8 13.5 109.6 106.1 12.4 105.8 112.0 11.3 102.0 118.5 10.342.0 125.3 91.6 16.4 121.6 96.2 15.2 117.9 101.2 14.0 114.0 106.6 12.8 110.1 112.4 11.8 106.2 118.8 10.744.0 130.1 91.9 17.0 126.3 96.6 15.7 122.4 101.6 14.5 118.6 107.0 13.3 114.6 112.9 12.2 110.5 119.2 11.145.0 132.5 92.1 17.3 128.7 96.8 15.9 124.8 101.8 14.7 120.8 107.2 13.5 116.8 113.1 12.4 112.7 119.5 11.346.0 135.0 92.3 17.6 131.1 97.0 16.2 127.1 102.0 15.0 123.1 107.5 13.8 119.1 113.3 12.6 114.9 119.7 11.548.0 140.1 92.6 18.1 136.0 97.4 16.8 131.9 102.5 15.5 127.8 107.9 14.2 123.7 113.8 13.0 119.4 120.1 11.950.0 145.2 92.9 18.8 141.1 97.8 17.3 136.9 102.9 16.0 132.6 108.3 14.7 128.3 114.2 13.5 124.0 120.6 12.3

MODEL YCRL0156HE IPLV= 19.4SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 139.1 108.0 15.5 135.5 113.6 14.3 131.9 119.4 13.3 128.2 125.5 12.3 124.4 132.1 11.3 120.4 139.1 10.442.0 144.3 108.2 16.0 140.6 113.8 14.8 136.8 119.7 13.7 133.0 125.9 12.7 129.1 132.4 11.7 125.0 139.4 10.844.0 149.6 108.3 16.6 145.8 114.1 15.3 141.9 120.0 14.2 138.0 126.2 13.1 133.9 132.7 12.1 129.7 139.7 11.145.0 152.3 108.4 16.9 148.4 114.2 15.6 144.5 120.1 14.4 140.5 126.3 13.3 136.4 132.9 12.3 132.1 139.9 11.346.0 155.1 108.4 17.2 151.1 114.2 15.9 147.1 120.2 14.7 143.1 126.5 13.6 138.9 133.0 12.5 134.5 140.0 11.548.0 160.8 108.5 17.8 156.6 114.4 16.4 152.5 120.4 15.2 148.3 126.7 14.0 144.0 133.3 13.0 139.5 140.4 11.950.0 166.6 108.5 18.4 162.3 114.5 17.0 158.0 120.6 15.7 153.7 127.0 14.5 149.2 133.6 13.4 144.6 140.7 12.3

MODEL YCRL0177SE IPLV= 18.9SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 162.0 124.9 15.6 157.7 132.7 14.3 153.2 141.1 13.0 148.5 150.2 11.9 143.8 159.8 10.8 138.8 170.2 9.842.0 167.9 125.0 16.1 163.4 132.8 14.8 158.8 141.2 13.5 154.0 150.2 12.3 149.1 159.9 11.2 144.0 170.2 10.244.0 173.9 125.1 16.7 169.3 132.9 15.3 164.6 141.2 14.0 159.6 150.2 12.8 154.6 159.9 11.6 149.4 170.3 10.545.0 177.0 125.2 17.0 172.3 132.9 15.6 167.5 141.3 14.2 162.5 150.2 13.0 157.4 159.9 11.8 152.1 170.3 10.746.0 180.1 125.2 17.3 175.4 133.0 15.8 170.5 141.3 14.5 165.4 150.3 13.2 160.2 159.9 12.0 154.8 170.3 10.948.0 186.5 125.4 17.8 181.6 133.1 16.4 176.5 141.4 15.0 171.3 150.3 13.7 166.0 159.9 12.5 160.4 170.3 11.350.0 193.0 125.5 18.4 188.0 133.2 16.9 182.8 141.4 15.5 177.4 150.4 14.2 171.9 160.0 12.9 166.2 170.3 11.7

MODEL YCRL0198SE IPLV= 19.1SATURATED DISCHARGE TEMP

LCWT (°F)

100.0 105.0 110.0 115.0 120.0 125.0TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER

40.0 191.6 149.8 15.3 186.5 159.2 14.1 181.3 169.3 12.8 175.9 180.2 11.7 170.4 191.8 10.7 164.6 204.2 9.742.0 198.5 149.9 15.9 193.3 159.3 14.6 187.9 169.4 13.3 182.4 180.2 12.1 176.6 191.8 11.0 170.7 204.3 10.044.0 205.6 150.1 16.4 200.2 159.4 15.1 194.7 169.4 13.8 188.9 180.2 12.6 183.0 191.9 11.4 177.0 204.3 10.445.0 209.1 150.1 16.7 203.7 159.4 15.3 198.1 169.5 14.0 192.3 180.3 12.8 186.3 191.9 11.7 180.1 204.3 10.646.0 212.8 150.2 17.0 207.3 159.5 15.6 201.6 169.5 14.3 195.7 180.3 13.0 189.6 191.9 11.9 183.4 204.3 10.848.0 220.3 150.4 17.6 214.6 159.6 16.1 208.7 169.6 14.8 202.6 180.3 13.5 196.4 191.9 12.3 189.9 204.4 11.250.0 227.9 150.5 18.2 222.0 159.7 16.7 216.0 169.7 15.3 209.7 180.4 14.0 203.3 192.0 12.7 196.7 204.4 11.5

NOTES:1. Tons = Unit Cooling Capacity Output2. KW = Compressor Input Power3. MBH = Condenser Heat Rejection4. EER = Chiller Energy Efficiency Ratio5. LCWT = Leaving Chilled Water Temperature

18 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Physical Data – Standard & High Efficiency – English

HIGH EFFICIENCY (HE)

YCRL MODEL 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE 0177SE 0198SE

GENERAL UNIT DATA

NOMINAL UNIT CAPACITY (TONS) 55.8 64.6 73 85.1 101.7 110.5 129.7 170.5 203.2NUMBER OF INDEPENDENT REFRIGERANT CIRCUITS 2 2 2 2 2 2 2 2 2

OIL CHARGE, CKT. 1/CKT. 2, (GAL.) 2.2/2.2 2.5/2.2 2.5/2.5 3.3/3.3 3.3/3.1 3.7/3.7 4.7/4.7 4.7/4.7 4.7/4.7

SHIPPING WEIGHT (LBS.) 2743 3133 3311 3664 3629 4345 4903 4418 4868

OPERATING WEIGHT (LBS.) 2950 3419 3597 4106 3915 4788 5346 4773 5223

COMPRESSORS, SCROLL

QUANTITY PER CHILLER 4 4 4 6 4 6 6 5 6

NOMINAL SIZE CKT. 1/ CKT. 2 15-15/15-15 20-20 /15-15 20-20/20-20 15-15-15/15-15-15 32-32/25-25 20-20-20/

20-20-2025-25-25/25-25-25

32-32-32/32-32

32-32-32/32-32-32

EVAPORATOR

WATER VOLUME (GALS.) 37.3 59.8 59.8 57.6 59.8 77 77 77 77

MAXIMUM WATER SIDE PRESSURE (PSIG) 150 150 150 150 150 150 150 150 150MAXIMUM REFRIGERANT SIDE PRESSURE (PSIG) 450 450 450 450 450 450 450 450 450

DIA. X LENGTH (INCHES X FEET) 13” X 8’ 16” X 8’ 16” X 8’ 15” X 10’ 16” X 8’ 17” 10’ 17” 10’ 17” 10’ 17” 10’

WATER NOZZLE CONNECTION SIZE, (IN.) 6 8 8 8 8 8 8 8 8

19JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

B A

C D CONTROL PANEL

Isolator Selection Data

60 HZ (ASME)

UNIT SHIPPING WEIGHT

TOTAL OPERATING

WEIGHT

WEIGHT ON EACH FRONT

ISOLATOR

WEIGHT ON EACH BACK ISOLATOR

STANDARD ISOLATOR

SELECTION

NEOPRENE ISOLATOR

SEISMIC ISOLATOR SLRS-2-C2-

0064HE 2883 2973 699 766 CP-1D-1200 GRAY RD-3 CHARCOAL RED/BLACK

0074HE 3261 3531 797 913 CP-1D-1200 GRAY RD-4 BRICK RED RED/BLACK

0084HE 3439 3709 821 977 CP-1D-1200 GRAY RD-4 BRICK RED RED/BLACK

0096HE 3753 4043 896 1112 CP-1D-1360 WHITE RD-4 BRICK RED PINK

0118HE 3705 3975 866 1092 CP-1D-1360 WHITE RD-4 BRICK RED PINK

0126HE 4587 5037 1008 1386 CP-1D-1785N GRAY/RED RD-4 BRICK RED PINK/GRAY

0156HE 4989 5439 1084 1609 C2P-1D-2400 GRAY RD-4 BRICK RED PINK/GRAY

0177SE 4418 4773 1380 1054 CP-1D-1785N GRAY/RED RD-4 BRICK RED PINK

0198SE 4868 5223 1522 1089 C2P-1D-1800 DK. GREEN RD-4 BRICK RED PINK/GRAY

20 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Isolator InformationONE INCH DEFLECTION SPRING ISOLATOR CROSS-REFERENCE

CPX-X-

����

������

��

��

�������������������������� ��

Mount TypeDimension Data (Inches)

W D L B C T H

CP1 3 5/8 7–3/4 6–1/2 4–3/4 ½ 5–5/8

CP2 3 5/8 10–1/2 9–1/4 7–3/4 9/16 6

MODEL NUMBER COLOR CODE

CP1-1D-85 85 1.360 LT. PURPLE

CP1-1D-120 120 1.200 DK. YELLOW

CP1-1D-175 175 1.170 DK. BLUE

CP1-1D-250 250 1.400 YELLOW

CP1-1D-340 340 1.130 RED

CP1-1D-510 510 1.020 BLACK

CP1-1D-675 675 1.320 DK. PURPLE

CP1-1D-900 900 1.020 DK. GREEN

CP1-1D-1200 1200 0.900 GRAY

CP1-1D-1360 1360 0.770 WHITE

CP1-1D-1785N 1785 0.880 GRAY/RED

MODEL NUMBER COLOR CODE

CP2-1D-1020 1020 1.020 BLACK

CP2-1D-1350 1350 1.320 DK. PURPLE

CP2-1D-1800 1800 1.020 DK. GREEN

CP2-1D-2400 2400 0.900 GRAY

CP2-1D-2720 2720 0.770 WHITE

CP2-1D-3570N 3570 0.880 GRAY / RED

RATED CAPACITY

(LBS.)

DEFLECTION RATED

(IN)

RATED CAPACITY

(LBS.)

DEFLECTION RATED

(IN)

21JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

NEOPRENE ISOLATOR CROSS-REFERENCE

ELASTOMER

RD-Style Isolators

Mount TypeDimension Data (inches)

L W HF AL AD BT CD DW

RD1-WR 3.13 1.75 1.25 2.38 0.34 0.19 5/16-18 UNC X 3/4 1.25

RD2-WR 3.88 2.38 1.75 3.00 0.34 0.22 3/8-16 UNC X 1 1.75

RD3-WR 5.50 3.38 2.88 4.13 0.56 0.25 1/2-13 UNC X 1 2.50

RD4-WR 6.25 4.63 2.75 5.00 0.56 0.38 1/2-13 UNC X 1 3.00

MODEL NUMBER DURO (± 5) MODEL NUMBER DURO (± 5)

RD2-Light Blue-WR 35 0.4 30 RD3-Brown-WR 250 0.5 40

RD2-Brown-WR 45 0.4 40 RD3-Brick Red-WR 525 0.5 50

RD2-Brick Red-WR 70 0.4 50 RD3-Lime-WR 750 0.5 60

RD 2-Lime-WR 120 0.4 60 RD3-Charcoal-WR 1100 0.5 70

MODEL NUMBER DURO (± 5)MODEL NUMBER DURO (± 5)

RD2-Light Blue-WR 135 0.5 30

RD2-Brown-WR 170 0.5 40 RD4-Brown-WR 1500 0.5 40

RD2-Brick Red-WR 240 0.5 50 RD4-Brick Red-WR 2250 0.5 50

RD 2-Lime-WR 380 0.5 60 RD4-Lime-WR 3000 0.5 60

RD2 Charcoal-WR 550 0.5 70 RD4-Charcoal-WR 4000 0.5 70

RATED

CAPACITY

[LBS]

RATED

DEFLECTION [IN]

RATED

CAPACITY

[LBS]

RATED

DEFLECTION

[IN]

RATED

CAPACITY

[LBS]

RATED

DEFLECTION [IN]RATED

CAPACITY

[LBS]

RATED

DEFLECTION [IN]

22 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

TWO INCH DEFLECTION, SEISMIC SPRING ISOLATOR CROSS-REFERENCE

Y2RS

3/4”

7/8”

3/8” GAP

3/4”TYP. (4)

5/8” 2-3/4”

1-1/8”

2-3/4”

8P

4

8

STOP &8-3/8”OPER.HEIGHT

4

4

Isolator Information - Continued

MODEL Y2RSI-2D SEISMICALLY RESTRAINED VIBRATION ISOLATOR FOR 2" DEFLECTION

SEISMIC MOUNT SIZE RATED LOAD (LBS) SOLID LOAD (LBS) COLOR CODE

Y2RSI-2D-150 150 2.4 62 234 WHITE 34.7

Y2RSI-2D-320 320 2.3 140 490 YELLOW 16.3

Y2RSI-2D-460 460 2.3 200 688 GREEN 11.3

Y2RSI-2D-710 710 2.2 330 1072 DK BROWN 7.3

Y2RSI-2D-870 870 1.9 460 1312 RED 6

Y2RSI-2D-1200N 1200 1.9 638 1818 RED/BLACK 4.3

Y2RSI-2D-1450 1450 1.8 900 2450 TAN 3.6

Y2RSI-2D-1690 1690 1.7 1140 2892 PINK 3.1

Y2RSI-2D-2000N 2000 1.7 1318 3342 PINK/BLACK 2.6

Y2RSI-2D-2640N 2640 1.5 1854 4283 PINK/GRAY 2

Y2RSI-2D-2870N 3080 1.5 2004 4629 PINK/GRAY/ORANGE 1.7

Y2RSI-2D-3280N 3740 1.8 2134 4930 1.4

RATED DEFLECTION

(IN)

SPRING RATE

(LBS/IN)

ALLOWABLE G

RATING HORIZONTAL

PINK/GRAY/DK

BROWN

23JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Sound DataYCRL

BASE UNITS (ARI 575 SOUND PRESSURE LEVELS DB RE: 20 MICROPASCALS)63 125 250 500 1000 2000 4000 8000 DBA

0064HE 59 52 54 68 68 69 62 53 740074HE 60 56 63 70 70 75 68 57 780084HE 60 58 66 71 72 77 70 59 800096HE 61 54 55 69 70 71 64 55 750118HE 69 68 74 77 78 76 70 57 820126HE 62 59 68 73 73 79 72 61 820156HE 72 65 71 78 79 76 72 58 820177SE 69 71 78 80 79 79 71 58 840198SE 69 72 78 80 80 80 72 59 85

YCRLCOMPRESSOR ACOUSTIC BLANKETS (ARI) 575 SOUND PRESSURE LEVELS DB RE: 20 MICROPASCALS)

63 125 250 500 1000 2000 4000 8000 DBA0064HE 59 52 53 66 63 63 56 48 690074HE 60 56 62 68 65 69 62 52 720084HE 60 58 65 69 67 71 64 54 740096HE 61 54 54 67 65 65 58 50 700118HE 69 68 73 75 73 70 64 52 770126HE 62 59 67 71 68 73 66 56 760156HE 72 65 70 76 74 70 66 53 780177SE 69 71 77 78 74 73 65 53 800198SE 69 72 77 78 75 74 66 54 80

24 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Unit Dimensions - English - Four Compressor

H* - for 200/230 volt units, which require a larger electrical enclosure

YCWL (4 COMP) 0064HE 0074HE 0084HE 0118HE

W 32.5 33.7 33.7 33.7H 56.6 63.6 63.6 63.3L 121.5 120.5 123.2 120.5A 13.8 13.8 13.8 13.8B 27.5 27.5 27.5 27.5D 11.8 16.0 16.0 16.0E 8.6 8.6 8.6 8.6F 24.5 29.0 29.0 29.0G 29.0 29.0 29.0 29.0J 17.7 17.7 17.7 17.7K 12.3 12.8 12.8 12.8M 12.3 12.3 12.3 12.3N 12.3 12.3 12.3 12.3R 85.0 83.0 83.0 83.0S 3.5 4.5 4.5 4.5T 116.7 115.7 118.3 115.7U 24.7 23.7 26.3 22.1X 21.0 22.2 22.3 22.2

AA 21.0 21.0 21.0 21.0BB 50.0 50.0 50.0 50.0CC 13.5 13.5 13.5 14.0DD 30.7 33.0 33.0 33.0EE 81.1 82.1 78.7 79.1FF 37.3 34.9 34.4 34.8

GG-1 39.5 39.5 39.5 41.0GG-2 39.5 39.5 39.5 41.0HH 18.3 14.7 14.7 14.9

Ship Wt. 2743 3133 3311 3629Oper Wt. 2950 3419 3597 3915

25JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

RELIEFVALVE INLET

OUTLET

26 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Unit Dimensions - English - Five & Six Compressor

H* - for 200/230 volt units, which require a larger electrical enclosure

YCWL (6 COMP) 0096HE 0126HE 0156HE 0177SE 0198SE

W 38.0 38.0 38.0 38.0 38.0H 59.1 64.6 64.5 64.5 64.5L 140.6 142.6 140.8 140.8 140.8A 13.8 13.8 13.8 13.8 13.8B 27.5 27.5 27.5 27.5 27.5D 16.0 16.0 16.0 16.0 16.0E 8.6 8.6 8.6 8.6 8.6F 28.0 28.0 28.0 28.0 28.0G 29.0 29.0 29.0 29.0 29.0J 17.7 17.7 17.7 17.7 17.7K 17.8 17.8 15.3 15.3 15.3M 12.3 12.3 12.3 12.3 12.3N 12.3 12.3 12.3 12.3 12.3R 102.0 102.0 102.0 102.0 102.0S 7.0 7.0 7.0 7.0 7.0T 135.8 137.6 135.8 135.8 135.8U 19.8 21.6 19.8 19.8 19.8X 23.3 23.3 23.2 23.2 23.2

AA 32.8 32.8 32.8 32.8 32.8BB 50.0 50.0 50.0 50.0 50.0CC 15.0 15.3 17.8 17.8 17.8DD 33.3 33.8 33.8 33.8 33.8EE 94.2 95.4 95.4 95.4 95.4FF 32.0 33.2 33.2 33.2 33.2

GG-1 57.9 57.7 53.7 53.7 53.7GG-2 57.9 57.7 53.7 53.7 53.7HH 14.7 14.9 14.9 14.9 14.9

SHIP WT. 3664 4345 4903 4418 4773OPER WT. 4016 4788 5346 4868 5223

27JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

INLET

RELIEFVALVE

OUTLET

EE

28 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Electrical Data - Single PointW/O EXTERNAL COMPRESSOR OVERLOADS

MODEL YCRL VOLT HZ

MINIMUM CIRCUIT

AMPS MCA

MIN N/F DISC SW MDSW

MIN DUAL ELEM FUSE

MAX DUAL ELEM FUSE

LUGS PER PHASE

CIRCUIT BREAKER LUG SIZE (OPT)

TERMINAL BLOCK LUG SIZE (STD)

QTY/∅ LUG INFO QTY/∅ LUG INFO

0064HE

208 60 237 400 300 300 1 250 - 500 KCM 1 # 4 - 500 KCM230 60 237 400 300 300 1 250 - 500 KCM 1 # 4 - 500 KCM380 60 153 200 175 175 1 # 4 - 300 KCM 1 # 10 - 300 KCM460 60 114 150 125 125 1 # 2 - 4/0 AWG 1 # 10 - 300 KCM575 60 101 150 110 110 1 # 2 - 4/0 AWG 1 # 10 - 300 KCM

0074HE

208 60 278 400 300 350 1 250 - 500 KCM 1 # 4 - 500 KCM230 60 278 400 300 350 1 250 - 500 KCM 1 # 4 - 500 KCM380 60 158 200 175 175 1 # 4 - 300 KCM 1 # 10 - 300 KCM460 60 122 150 150 150 1 # 2 - 4/0 AWG 1 # 10 - 300 KCM575 60 103 150 110 125 1 # 2 - 4/0 AWG 1 # 10 - 300 KCM

0084HE

208 60 314 400 350 350 1 250 - 500 KCM 1 # 4 - 500 KCM230 60 314 400 350 350 1 250 - 500 KCM 1 # 4 - 500 KCM380 60 162 200 175 200 1 # 4 - 300 KCM 1 # 10 - 300 KCM460 60 129 150 150 150 1 # 2 - 4/0 AWG 1 # 10 - 300 KCM575 60 105 150 125 125 1 # 2 - 4/0 AWG 1 # 10 - 300 KCM

0096HE

208 60 349 400 400 400 1 250 - 500 KCM 2 #10 - 300 KCM230 60 349 400 400 400 1 250 - 500 KCM 2 #10 - 300 KCM380 60 225 250 250 250 1 # 6 - 350 KCM 1 # 4 - 500 KCM460 60 168 200 175 175 1 # 4 - 300 KCM 1 # 4 - 500 KCM575 60 148 200 175 175 1 # 6 - 350 KCM 1 # 4 - 500 KCM

0118HE

208 60 425 600 500 500 2 250 - 500 KCM 2 #10 - 300 KCM230 60 425 600 500 500 2 250 - 500 KCM 2 #10 - 300 KCM380 60 265 400 300 300 1 250 - 500 KCM 1 # 4 - 500 KCM460 60 208 250 225 250 1 # 6 - 350 KCM 1 # 4 - 500 KCM575 60 175 200 200 200 1 # 6 - 350 KCM 1 # 4 - 500 KCM

0126HE

208 60 462 600 500 500 2 250 - 500 KCM 2 # 10 - 300 KCM230 60 462 600 500 500 2 250 - 500 KCM 2 # 10 - 300 KCM380 60 239 400 250 250 1 # 6 - 350 KCM 1 # 4 - 500 KCM460 60 190 250 200 200 1 # 6 - 350 KCM 1 # 4 - 500 KCM575 60 154 200 175 175 1 # 6 - 350 KCM 1 # 4 - 500 KCM

0156HE

208 60 557 800 600 600 2 250 - 500 KCM 2 # 4 - 500 KCM230 60 557 800 600 600 2 250 - 500 KCM 2 # 4 - 500 KCM380 60 341 400 400 400 1 250 - 500 KCM 2 # 10 - 300 KCM460 60 268 400 300 300 1 250 - 500 KCM 1 # 4 - 500 KCM575 60 201 250 225 225 1 250 - 500 KCM 1 # 4 - 500 KCM

0177SE380 60 338 400 400 400 * * 2 # 10 - 300 KCM460 60 279 400 300 300 1 250 - 500 KCM 1 # 4 - 500 KCM575 60 223 250 250 250 1 #6 AWG - 350 KCM 1 # 4 - 500 KCM

0198SE380 60 402 600 450 450 2 250 - 500 KCM 2 #10 - 300 KCM460 60 332 400 350 350 2 #3/0 - 250 KCM 1 # 4 - 500 KCM575 60 266 400 300 300 1 250 - 500 KCM 1 # 4 - 500 KCM

* - Contact Johnson Controls

29JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

W/O EXTERNAL COMPRESSOR OVERLOADS

MODELYCRL

SYSTEM # 1 SYSTEM # 2

COMPR 1 COMPR 2 COMPR 3 COMPR 1 COMPR 2 COMPR 3

RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA

0064HE

55.8 425 55.8 425 55.8 425 55.8 42555.8 425 55.8 425 55.8 425 55.8 42536.0 239 36.0 239 36.0 239 36.0 23926.9 187 26.9 187 26.9 187 26.9 18723.7 148 23.7 148 23.7 148 23.7 148

0074HE

73.9 505 73.9 505 55.8 425 55.8 42573.9 505 73.9 505 55.8 425 55.8 42538.2 290 38.2 290 36.0 239 36.0 23930.4 225 30.4 225 26.9 187 26.9 18724.6 180 24.6 180 23.7 148 23.7 148

0084HE

73.9 505 73.9 505 73.9 505 73.9 50573.9 505 73.9 505 73.9 505 73.9 50538.2 290 38.2 290 38.2 290 38.2 29030.4 225 30.4 225 30.4 225 30.4 22524.6 180 24.6 180 24.6 180 24.6 180

0118HE

109.6 599 109.6 599 89.1 500 89.1 500109.6 599 109.6 599 89.1 500 89.1 50069.2 358 69.2 358 54.5 305 54.5 30554.5 310 54.5 310 42.9 250 42.9 25049.4 239 49.4 239 32.1 198 32.1 198

0096HE

55.8 425 55.8 425 55.8 425 55.8 425 55.8 425 55.8 42555.8 425 55.8 425 55.8 425 55.8 425 55.8 425 55.8 42536.0 239 36.0 239 36.0 239 36.0 239 36.0 239 36.0 23926.9 187 26.9 187 26.9 187 26.9 187 26.9 187 26.9 18723.7 148 23.7 148 23.7 148 23.7 148 23.7 148 23.7 148

0126HE

73.9 505 73.9 505 73.9 505 73.9 505 73.9 505 73.9 50573.9 505 73.9 505 73.9 505 73.9 505 73.9 505 73.9 50538.2 290 38.2 290 38.2 290 38.2 290 38.2 290 38.2 29030.4 225 30.4 225 30.4 225 30.4 225 30.4 225 30.4 22524.6 180 24.6 180 24.6 180 24.6 180 24.6 180 24.6 180

0156HE

89.1 500 89.1 500 89.1 500 89.1 500 89.1 500 89.1 50089.1 500 89.1 500 89.1 500 89.1 500 89.1 500 89.1 50054.5 305 54.5 305 54.5 305 54.5 305 54.5 305 54.5 30542.9 250 42.9 250 42.9 250 42.9 250 42.9 250 42.9 25032.1 198 32.1 198 32.1 198 32.1 198 32.1 198 32.1 198

0177SE64.3 355.4 64.3 355.4 64.3 355.4 64.3 355.4 64.3 355.453.1 290.0 53.1 290.0 53.1 290.0 53.1 290.0 53.1 290.042.5 254.6 42.5 254.6 42.5 254.6 42.5 254.6 42.5 254.6

0198SE64.3 355.4 64.3 355.4 64.3 355.4 64.3 355.4 64.3 355.4 64.3 355.453.1 290.0 53.1 290.0 53.1 290.0 53.1 290.0 53.1 290.0 53.1 290.042.5 254.6 42.5 254.6 42.5 254.6 42.5 254.6 42.5 254.6 42.5 254.6

30 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

W/O EXTERNAL COMPRESSOR OVERLOADS

Electrical Data - Dual Point

CHILLER YCRL VOLT HZ

SYSTEM 1 WIRING SYSTEM 2 WIRING

MINIMUMCIRCUIT

AMPS

MIN N/F DISC SW

MIN DUAL ELEM FUSE

& MIN CB

MAX DUAL ELEM FUSE & MAX CB

MINIMUMCIRCUIT

AMPS

MIN N/F DISC SW

MIN DUAL ELEM FUSE

& MIN CB

MAX DUAL ELEM FUSE & MAX CB

0064HE

208 60 126 150 150 175 126 150 150 175230 60 126 150 150 175 126 150 150 175380 60 81 100 90 110 81 100 90 110460 60 61 100 70 80 61 100 70 80575 60 53 60 60 70 53 60 60 70

0074HE

208 60 166 200 200 225 126 150 150 175230 60 166 200 200 225 126 150 150 175380 60 86 100 100 110 81 100 90 110460 60 68 100 80 90 61 100 70 80575 60 55 60 70 70 53 60 60 70

0084HE

208 60 166 200 200 225 166 200 200 225230 60 166 200 200 225 166 200 200 225380 60 86 100 100 110 86 100 100 110460 60 68 100 80 90 68 100 80 90575 60 55 60 70 70 55 60 70 70

0118HE

208 60 247 400 300 350 200 250 225 250230 60 247 400 300 350 200 250 225 250380 60 156 200 175 200 123 150 150 175460 60 123 150 150 175 97 100 110 125575 60 111 150 125 150 72 100 90 100

0096HE

208 60 181 200 200 225 181 200 200 225230 60 181 200 200 225 181 200 200 225380 60 117 150 150 150 117 150 150 150460 60 87 100 100 110 87 100 100 110575 60 77 100 90 100 77 100 90 100

0126HE

208 60 240 400 300 300 240 400 300 300230 60 240 400 300 300 240 400 300 300380 60 124 150 150 150 124 150 150 150460 60 99 150 110 125 99 150 110 125575 60 80 100 90 100 80 100 90 100

0156HE

208 60 290 400 350 350 290 400 350 350230 60 290 400 350 350 290 400 350 350380 60 177 200 200 225 177 200 200 225460 60 139 150 175 175 139 150 175 175575 60 104 150 125 125 104 150 125 125

0177SE

230 60 345 400 400 450 239 250 300 300380 60 209 250 250 250 145 150 175 200460 60 173 200 200 225 119 150 150 150575 60 138 150 150 175 96 100 110 125

0198SE

230 60 345 400 400 450 345 400 400 450380 60 209 250 250 250 209 250 250 250460 60 173 200 200 225 173 200 200 225575 60 138 150 150 175 138 150 150 175

31JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

W/O EXTERNAL COMPRESSOR OVERLOADS

MODEL YCRL VOLT

SYSTEM 1 CIRCUIT BREAKER LUG SIZE

SYSTEM # 1SYSTEM 2 CIRCUIT BREAKER LUG SIZE

SYSTEM # 2

COMPR 1 COMPR 2 COMPR 3 COMPR 1 COMPR 2 COMPR 3QTY/ LUG INFO QTY LUG INFORLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA

0064HE

208 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0230 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0380 1 #14 - 1/0AWG 36.0 239.0 36.0 239.0 1 #14 - 1/0AWG 36.0 239.0 36.0 239.0460 1 #14 - 1/0AWG 26.9 187.0 26.9 187.0 1 #14 - 1/0AWG 26.9 187.0 26.9 187.0575 1 #14 - 1/0AWG 23.7 148.0 23.7 148.0 1 #14 - 1/0AWG 23.7 148.0 23.7 148.0

0074HE

208 1 #6 - 350KCMIL 73.9 505.0 73.9 505.0 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0230 1 #6 - 350KCMIL 73.9 505.0 73.9 505.0 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0380 1 #2 - 4/0AWG 38.2 290.0 38.2 290.0 1 #14 - 1/0AWG 36.0 239.0 36.0 239.0460 1 #14 - 1/0AWG 30.4 225.0 30.4 225.0 1 #14 - 1/0AWG 26.9 187.0 26.9 187.0575 1 #14 - 1/0AWG 24.6 180.0 24.6 180.0 1 #14 - 1/0AWG 23.7 148.0 23.7 148.0

0084HE

208 1 #6 - 350KCMIL 73.9 505.0 73.9 505.0 1 #6 - 350KCMIL 73.9 505.0 73.9 505.0230 1 #6 - 350KCMIL 73.9 505.0 73.9 505.0 1 #6 - 350KCMIL 73.9 505.0 73.9 505.0380 1 #2 - 4/0AWG 38.2 290.0 38.2 290.0 1 #2 - 4/0AWG 38.2 290.0 38.2 290.0460 1 #14 - 1/0AWG 30.4 225.0 30.4 225.0 1 #14 - 1/0AWG 30.4 225.0 30.4 225.0575 1 #14 - 1/0AWG 24.6 180.0 24.6 180.0 1 #14 - 1/0AWG 24.6 180.0 24.6 180.0

0096HE

208 1 250 - 300KCMIL 55.8 425.0 55.8 425.0 55.8 425.0 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0 55.8 425.0230 1 250 - 300KCMIL 55.8 425.0 55.8 425.0 55.8 425.0 1 #6 - 350KCMIL 55.8 425.0 55.8 425.0 55.8 425.0380 1 #6 - 350KCMIL 36.0 239.0 36.0 239.0 36.0 239.0 1 #6 - 350KCMIL 36.0 239.0 36.0 239.0 36.0 239.0460 1 #6 - 350KCMIL 26.9 187.0 26.9 187.0 26.9 187.0 1 #2 - 4/0AWG 26.9 187.0 26.9 187.0 26.9 187.0575 1 #2 - 4/0AWG 23.7 148.0 23.7 148.0 23.7 148.0 1 #14 - 1/0AWG 23.7 148.0 23.7 148.0 23.7 148.0

0118HE

208 1 #6 - 350KCMIL 109.6 599.0 109.6 599.0 1 #6 - 350KCMIL 89.1 500.0 89.1 500.0230 1 #6 - 350KCMIL 109.6 599.0 109.6 599.0 1 #6 - 350KCMIL 89.1 500.0 89.1 500.0380 1 #2 - 4/0AWG 69.2 358.0 69.2 358.0 1 #2 - 4/0AWG 54.5 305.0 54.5 305.0460 1 #14 - 1/0AWG 54.5 310.0 54.5 310.0 1 #14 - 1/0AWG 42.9 250.0 42.9 250.0575 1 #14 - 1/0AWG 49.4 239.0 49.4 239.0 1 #14 - 1/0AWG 32.1 198.0 32.1 198.0

0126HE

208 1 250 - 300KCMIL 73.9 505.0 73.9 505.0 73.9 505.0 1 250 - 300KCMIL 73.9 505.0 73.9 505.0 73.9 505.0230 1 250 - 300KCMIL 73.9 505.0 73.9 505.0 73.9 505.0 1 250 - 300KCMIL 73.9 505.0 73.9 505.0 73.9 505.0380 1 #2 - 4/0AWG 38.2 290.0 38.2 290.0 38.2 290.0 1 #2 - 4/0AWG 38.2 290.0 38.2 290.0 38.2 290.0460 1 #2 - 4/0AWG 30.4 225.0 30.4 225.0 30.4 225.0 1 #2 - 4/0AWG 30.4 225.0 30.4 225.0 30.4 225.0575 1 #14 - 1/0AWG 24.6 180.0 24.6 180.0 24.6 180.0 1 #14 - 1/0AWG 24.6 180.0 24.6 180.0 24.6 180.0

0156HE

208 1 250 - 300KCMIL 89.1 500.0 89.1 500.0 89.1 500.0 1 250 - 300KCMIL 89.1 500.0 89.1 500.0 89.1 500.0230 1 250 - 300KCMIL 89.1 500.0 89.1 500.0 89.1 500.0 1 250 - 300KCMIL 89.1 500.0 89.1 500.0 89.1 500.0380 1 #6 - 350KCMIL 54.5 305.0 54.5 305.0 54.5 305.0 1 #6 - 350KCMIL 54.5 305.0 54.5 305.0 54.5 305.0460 1 #6 - 350KCMIL 42.9 250.0 42.9 250.0 42.9 250.0 1 #6 - 350KCMIL 42.9 250.0 42.9 250.0 42.9 250.0575 1 #2 - 4/0AWG 32.1 198.0 32.1 198.0 32.1 198.0 1 #2 - 4/0AWG 32.1 198.0 32.1 198.0 32.1 198.0

0177SE

230 1 (2) #3/0 AWG - 250 kCMIL 106.2 578.4 106.2 578.4 106.2 578.4 1 (1) 250 - 500 kCMIL 106.2 578.4 106.2 578.4380 1 (1) #4 AWG - 300 Kcmil 64.3 355.4 64.3 355.4 64.3 355.4 1 (1) #6 AWG - 350 kCMIL 64.3 355.4 64.3 355.4460 1 (1) #4 AWG - 300 Kcmil 53.1 290.0 53.1 290.0 53.1 290.0 1 (1) #2 - 4/0 AWG 53.1 290 53.1 290575 1 (1) #2 - 4/0 AWG 42.5 254.6 42.5 254.6 42.5 254.6 1 (1) #2 - 4/0 AWG 42.5 254.6 42.5 254.6

0198SE

230 1 (1) 250 - 500 kCMIL 106.2 578.4 106.2 578.4 106.2 578.4 1 (1) 250 - 500 kCMIL 106.2 578.4 106.2 578.4 106.2 578.4380 1 (1) #6 AWG - 350 kCMIL 64.3 355.4 64.3 355.4 64.3 355.4 1 (1) #6 AWG - 350 kCMIL 64.3 355.4 64.3 355.4 64.3 355.4460 1 (1) #4 AWG - 300 kCMIL 53.1 290 53.1 290 53.1 290 1 (1) #4 AWG - 300 kCMIL 53.1 290 53.1 290 53.1 290575 1 (1) #2 - 4/0 AWG 42.5 254.6 42.5 254.6 42.5 254.6 1 (1) #2 - 4/0 AWG 42.5 254.6 42.5 254.6 42.5 254.6

32 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Electrical Notes1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the

rated load amps for all other loads included in the circuit, per N.E.C. Article 43024. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: 17, add 2.5 amps; 28, add 2.3 amps; 40, add 1.5 amps, 46, add 1.3 amps; 58, add 1 amps.

2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in the circuit, per N.E.C. Article 440.

3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at startup due to lock rotor amps. It is not rec-ommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated.

4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440-22.

5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, an HACR type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.

6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.

7. An equipment ground lug(s) is provided for the incoming power. Ground line sizing shall be in accordance with the current NEC Table 250-122.

8. Field Wiring by others which complies to the National Electrical Code & Local Codes.

9. Voltage Utilization Range

LEGEND

ACR ACROSS THE LINE STARTC.B. CIRCUIT BREAKERD.E. DUAL ELEMENT FUSEDISC SW DISCONNECT SWITCHFACT MOUNT CB FACTORY MOUNTED CIRCUIT BREAKERFLA FULL LOAD AMPSHZ HERTZMAX MAXIMUMMCA MINIMUM CIRCUIT AMPACITYMIN MINIMUMMIN NF MINIMUM NON FUSEDRLA RATED LOAD AMPSS.P. WIRE SINGLE POINT WIRINGUNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH)LRA LOCKED ROTOR AMPSECWT ENTERING CONDENSER WATER TEMPERATURE

Rated Voltage Utilization Range200/60/3 180 - 220230/60/3 208 - 254380/60/3 342 - 402460/60/3 414 - 508575/60/3 520 - 635

33JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Ground Wire SizingGROUND LUG SIZING

CIRCUIT BREAKER OPTION

RATING INCOMING WIRE GROUND WIRE

60A # 14 - 1/0 AWG # 14 - 6 AWG

70A # 14 - 1/0 AWG # 14 - 6 AWG

80A # 14 - 1/0 AWG # 14 - 6 AWG

90A # 14 - 1/0 AWG # 14 - 6 AWG

100A # 14 - 1/0 AWG # 8 - 2 AWG

125A # 14 - 1/0 AWG # 8 - 2 AWG

125A # 2 - 4/0 AWG # 8 - 2 AWG

150A # 2 - 4/0 AWG # 8 - 2 AWG

175A # 4 - 300 KCM # 6 - 1/0 AWG

200A # 4 - 300 KCM # 6 - 1/0 AWG

225A # 4 - 300 KCM # 6 - 1/0 AWG

250A # 6 - 350 KCM # 4 - 3/0 AWG

400A # 250 - 500 KCM # 2 - 4/0 AWG

400A (2) # 3/0 - 250 KCM (2) # 6 - 1/0 AWG

600A (2) # 250 - 500 KCM (2) # 2 - 4/0 AWG

TERMINAL BLOCK OPTION

RATING INCOMING WIRE GROUND WIRE

130A # 12 - 1 AWG # 8 - 2 AWG

165A # 10 - 3/0 AWG # 6 - 1/0 AWG

240A # 10 - 300 KCM # 4 - 3/0 AWG

320A # 4 - 500 KCM # 2 - 4/0 AWG

480A (2) # 10 - 300 KCM (2) # 4 - 3/0 AWG

Instructions:

1) Start in correct power option table (breaker, terminal block)

2) Match engineering guide value for Amperage

3) Match engineering guide value for wire range

4) Note corresponding ground wire range

34 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Typical Control Panel Wiring4 Compressor

35JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

4 Compressor

36 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Typical Control Panel Wiring - continued

5 & 6 Compressor

37JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

5 & 6 Compressor

38 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Customer Wiring Information

FIGURE 1: SINGLE POINT POWER SUPPLY CONNECTION – STANDARD UNIT

1 2

39JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

FIG. 2 – DUAL POINT POWER SUPPLY CONNECTION – OPTIONAL

��������������������������������

� �

�������������

����������

����������

���������

��������

��������

 ��

���������������������­����­��������������

�������������������������� �������������������

�������

40 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

UNIT LOCATIONChillers are designed for indoor installation. Units should be located away from noise-critical areas. Service clear-ance must be allowed and include space for remov ing condenser tubes. A doorway or window can sometimes provide space for tube removal. Units should be installed indoors where they are not exposed to rain or water splash. Chillers should be located near a drain. The use of chillers in corrosive, dusty or ex plosive atmospheres should be avoided unless the unit is properly protected. A unit located in a clean room will run best, require least maintenance, and last longest. Heat or ventilation may be required to maintain the ambient between 40°F and 115°F (4.4°C and 46.1°C).

UNIT ISOLATIONThe chiller foundation must be rigid to reduce vibration transmission to a minimum. All upper story installations should use vibration isolators under the unit base. To main-tain isolator efficiency, no mechanical ties should be made to the building. Properly selected flexible connectors and piping isolators are recommended. All the above recom-mendations will help to reduce vibration transmission and result in a quieter operation.

FIELD CONNECTED WATER PIPINGPiping must comply in all respects with applicable local plumbing codes and ordinances. In no case should the unit support the weight of connecting piping. Since elbows, tees, and valves increase pressure drop, all piping should be kept as simple as possible. Hand stop valves should be installed where required to facilitate servicing. Piping to the inlet and outlet connections of the evaporator and condenser may include high-pressure rubber hose or piping loops to ensure against water pump transmission of vibration.

Facilities should be provided for measuring temperature and pressure in the evaporator and condenser field water pip ing. Drain connections should be provided at all low points to permit complete drainage of the evaporator(s) and system piping. This is especially im portant if the unit is located in an unheated room where freezing could prevail. Water lines subjected to ambient temperatures below freezing may require heater cables or antifreeze (by others).

Water loops should contain provisions for venting. A strainer, preferably 40 mesh, should be installed in the evaporator inlet line, located where it will protect the cir-culating pump and the heat exchanger tube bundles. It should be determined that the maximum water pressure at the evaporator does not exceed the maximum design working pressure.

The water circulating pump should be located on the inlet side of the heat exchanger. If, however, space does not permit this, the pumps may be located in the outlet water piping. The net positive suction head must be considered when applying pumps.

FIELD WIRINGAll field wiring must comply with the National Electric Code and all applicable local codes. YORK liquid chiller units are factory wired for optimum reliability. Therefore the unit controls must not be modified without ex pressed written consent by Johnson Controls. The use of a simple switch or timer from a remote point is permitted; but it must be connected to the unit panel at points expressly indicated for that purpose.

REFRIGERANT RELIEF PIPINGEach chiller is equipped with pressure relief valves. The purpose of the relief valves is to quickly relieve excess pressure of the refrigerant charge as a safety precaution in the event of an emergency such as a fire. Sized to the requirements of applicable local codes, a vent line must be run from the relief valve to the outside of the building. Vent piping must be arranged to avoid imposing a strain on the relief valves and should include flexible connections.

The low side relief valve is located on the suction line. It has a pressure setting of 400 psig (27.6 bar) and a capac-ity of 28.6 lbs. air/min ( 166.3 l/s).

The 0064, 0074, and 0096 units have additional relief valves on the discharge line(s) in lieu of compressor in-ternal relief. The valve has a pressure setting of 650 psig (44.5 barg), a capacity of 44.6 lbs air/min (277 l/s) and a 1/2” flare connection.

Application Data

41JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

Guide SpecificationsPART 1 – GENERAL

1.01 SCOPE

A. The requirements of the General Conditions, Supple-mentary Conditions, Division 1, and Drawings apply to all Work herein.

B. Provide Microprocessor controlled, multiple-scroll compressor, water-cooled, liquid chillers of the scheduled capacities as shown and indicated on the Drawings, including but not limited to:

1. Chiller package 2. Electrical power and control connections 3. Chilled water connections 4. Charge of refrigerant and oil 5. Factory start-up

1.02 QUALITY ASSURANCE

A. Products shall be Designed, Tested, Rated and Certi-fied in accordance with, and installed in compliance with applicable sections of the following Standards and Codes:1. ANSI/ASHRAE Standard 15 – Safety Code for

Mechanical Refrigeration 2. ASHRAE 90.1– Energy Efficiency compliance. 3. ANSI/NFPA Standard 70 – National Electrical

Code (N.E.C.) 4. ASME Boiler & Pressure Vessel Code, Section

VIII, Division 1 5. ASHRAE 34 – Number Designation and Safety

Classification of Refrigerants 6. ARI Standard 550/590 – Positive Displacement

Compressors and Water Cooled Rotary Screw Water-Chilling Packages

7. Conform to UL code 1995 for construction of chillers and provide ETL/cETL Listing label

8. Manufactured in facility registered to ISO 9001 9. OSHA - Occupational Safety and Health Act

B. Factory Test: Chiller shall be pressure-tested, evacu-ated and fully charged with oil and a nitrogen holding charge. Refrigerant shall be field supplied.

C. Chiller manufacturer shall have a factory trained and supported service organization that is within a 50 mile radius of the site.

D. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture against defects in workmanship and material for a period of one year from date of initial start-up or eighteen (18) months from date of shipment, whichever occurs first.

1.03 DELIVERY AND HANDLING

A. Unit shall be delivered to job site fully assembled, and charged with refrigerant and oil by the Manufac-turer.

B. Unit shall be stored and handled per Manufacturer’s

instructions.

C. Unit and its accessories shall be protected from the weather and dirt exposure during shipment.

D. During shipment, a covering shall be provided over vulnerable components. Nozzles and open ends shall be fitted with plastic enclosures.

PART 2 – PRODUCTS

2.01 CHILLER MATERIALS AND COMPONENTS

A. General: Install and commission, as shown on the schedules and plans, factory assembled, charged, and tested water-cooled scroll compressor chiller(s) as specified herein. Chiller shall be designed, selected, and constructed using a refrigerant with Flammability rating of “1”, as defined by ANSI/ASHRAE STANDARD - 34 Number Designation and Safety Classification of Refrigerants. Chiller shall include, but is not limited to: a complete system with not less than two refrigerant circuits, scroll compressors, direct expansion type evaporator, lubrication system, interconnecting wir-ing, safety and operating controls including capacity controller, control center, motor starting components, and special features as specified herein or required for safe, automatic operation.

2.02 COMPRESSORS

Compressors Shall be hermetic, scroll-type, including:1. Compliant design for axial and radial sealing.2. Refrigerant flow through the compressor with

100% suction cooled motor.3. Large suction side free volume and oil sump to

provide liquid handling capability.4. Compressor crankcase heaters to provide extra

liquid migration protection.5. Annular discharge check valve and reverse vent

assembly to provide low pressure drop, silent shutdown and reverse rotation protection.

6. Initial Oil charge. 7. Oil Level sightglass. 8. Vibration isolator mounts for compressors. 9. Brazed-type connections for fully hermetic refrig-

erant circuits.10. Microprocessor controlled, Factory installed

Across-the-Line type compressor motor starters

42 JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

2.03 REFRIGERANT CIRCUIT COMPONENTS

Each refrigerant circuit shall include: liquid line shutoff valve with charging port, low side pressure relief device, filter-drier, solenoid valve, discharge service valve, sight glass with moisture indicator, expansion valves, and flex-ible, closed-cell foam insulated suction line.

2.04 HEAT EXCHANGER

A. Evaporator:1. Evaporator shall be a direct expansion shell and

tube construction, dual circuit heat exchanger capable of refrigerant working pressure of 450 Psig (31.0 bar) and liquid side pressure of 150 psig (10.3 bar).

2. Evaporator shall be covered with 3/4” (19mm), flexible, closed-cell insulation, thermal conductiv-ity of 0.26k ([BTU/HR-Ft2-°F]/in.) maximum. Water nozzles shall be insulated by Contractor after pipe installation.

3. Heat exchangers shall be ASME pressure vessel code certified.

4. Installing contractor must include accommoda-tions in the chilled water piping to allow proper drainage and venting of the heat exchanger.

5. The water connections shall be fully accessible and grooved to accept ANSI/AWWA C-606 cou plings if used (by others).

2.05 CONTROLSA. General: Automatic start, stop, operating, and pro-

tection sequences across the range of scheduled conditions and transients.

B. Microprocessor Enclosure: NEMA 1 (IP32) powder- painted steel cabinet with hinged, latched, and gasket sealed door.

C. Microprocessor Control Center:1. Automatic control of compressor start/stop, anti

coincidence and anti-recycle timers, automatic pumpdown on shutdown, evaporator pump, and unit alarm contacts. Automatic reset to normal chiller operation after power failure.

2. Software stored in non-volatile memory, with programmed setpoints retained in lithium battery backed regulated time clock (RTC) memory for minimum 5 years.

3. Forty character liquid crystal display, numeric data in English (or Metric) units. Sealed keypad with sections for Setpoints, Display/Print, Entry, Unit Options & clock, and On/Off Switch. Display descriptions and membrane keypad graphics shown in English language.

4. Programmable Setpoints (within Manufacturer’s limits): display language; chilled liquid tempera-ture setpoint and range, remote reset tempera-

ture range, set daily schedule/holiday for start/ stop, manual override for servicing, number of compressors, low liquid temperature cutout, low suction pressure cutout, high discharge pressure cutout, anti-recycle timer (compressor start cycle time), and anti-coincident timer (delay compres-sor starts).

5. Display Data: Return and leaving evaporator liq-uid temperatures, low leaving liquid temperature cutout setting, English or metric data, suction pressure cutout setting, each system suction pressure, discharge pressure, liquid tempera-ture reset via a 4-20milliamp or 0- 10 VDC input or contact closure, anti-recycle timer status for each compressor, anti-coincident system start timer condition, compressor run status, no cool-ing load condition, day, date and time, daily start/ stop times, holiday status, automatic or manual system lead/lag control, lead system definition, compressor starts/operating hours (each), status of hot gas valves (if supplied), run permissive status, number of compressors running, liquid solenoid valve status, load & unload timer status, water pump status.

6. System Safeties: Shall cause individual compres-sor systems to perform auto shut down; manual reset required after the third trip in 90 minutes. Includes: high discharge pressure, low suction pressure, high pressure switch, and motor pro-tector. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings.

7. Unit Safeties: Shall be automatic reset and cause compressors to shut down if low ambient, low leaving chilled liquid temperature, under voltage, and flow switch operation. Contractor shall pro-vide flow switch installation and wiring per chiller Manufacturer’s requirements.

8. Alarm Contacts: Low ambient, low leaving chilled liquid temperature, low voltage, low battery, and (per compressor circuit): high discharge pressure, and low suction pressure.

9. BAS/EMS Temperature Reset: Chiller to accept 4 to 20mA, 0 to 10 VDC, or discrete contact closure input to reset the leaving chilled liquid tempera-ture.

D. Pressure Transducers and Readout Capability1. Discharge Pressure Transducers: Permits unit to

sense and display discharge pressure.

2. Suction Pressure Transducers: Permits unit to sense and display suction pressure.

E. Manufacturer shall provide any controls not listed above, necessary for automatic chiller operation. Me-

Guide Specifications – continued

43JOHNSON CONTROLS

FORM 150.27-EG1 (1210)

chanical Contractor shall provide field control wiring necessary to interface sensors to the chiller control system.

2.06 POWER CONNECTION AND DISTRIBUTION

A. Power Panels:1. NEMA 1 (IP32), powder painted steel cabinets

with hinged, latched, and gasket sealed outer doors. Provide main power connection(s), control power connections, compressor start contactors, current overloads, and factory wiring.

2. Power supply shall enter unit at a single location, be 3 phase of scheduled voltage, and connect to individual terminal blocks per compressor. Separate disconnecting means and/ or external branch circuit protection (by Contractor) required per applicable local or national codes.

B. Exposed compressor and control power wiring shall be routed through liquid tight conduit.

C. Power Supply Connection shall be: Single Point Power Supply: Single point Terminal Block

for field connection and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring, which must comply with the National Electric Code and/or local codes.

2.07 ACCESSORIES AND OPTIONS

Some accessories and options supersede standard prod-uct features. Your Johnson Controls sales representative will be pleased to provide assistance.

A. Power Supply Connections (Factory Mounted):1. Single Point Circuit Breaker: Single point Terminal

Block with Circuit Breaker and lockable external handle (in compliance with Article 440 14 of N.E.C.) can be supplied to isolate power voltage for servicing. Incoming power wiring must com-ply with the National Electric Code and/or local codes.

B. Control Power Transformer (Factory Mounted): Con-verts unit power voltage to 120-1-60 (500 VA capacity). Factory mounting includes primary and secondary wir-ing between the transformer and the control panel.

C. Flow Switch (Field-mounted): Vapor proof SPDT, NEMA 3R switch (150 Psig), -20°F to 250°F. Available with evaporator.

D. Differential Pressure Switch (Field mounted): Alterna-tive to the paddle-type flow switch. 3-45 Psig (0.2-3 bar) range with ¼” NPTE pressure connections. Avail-able with evaporator.

E. Double Thick Evaporator Insulation (Factory Mounted): Evaporator covered with double thick (1-1/2”) flexible, closed-cell Insulation in lieu of standard (3/4”) insula-tion. Water nozzles shall be insulated by Contractor after pipe installation.

F. ANSI/AWWA C-606 Flange Kit (Field Mounted): ANSI/AWWA C-606 flange adapters included with the water connections on the evaporator providing raised face flanges for field piping connection.

G. Service Isolation valves (Factory Mounted): Service suction (ball type) isolation valves are added to unit per circuit in addition to the standard discharge service valve. (Factory-mounted.)

H. Hot Gas By-Pass (Factory Mounted): Permits continu-ous, stable operation at capacities below the minimum step of unloading to as low as 5% capacity (depending on both the unit & operating conditions) by introducing an artificial load on the evaporator. Hot gas by-pass is installed on only one refrigerant circuit (System #2).

I. Microprocessor Membrane Keypad Graphics on in lieu of Standard English:1. Spanish language.2. French language.3. German language.4. Italian language.

J. Sound Reduction (Factory-mounted): 1. Each compressors is individually enclosed in an

acoustic sound blankets.

K. Vibration Isolation (Field-mounted): 1. Neoprene Pad Isolators.2. 1 Inch Deflection Spring Isolators: Level adjust-

able, spring and cage type isolators for mounting under the unit base.

3. 2 Inch Deflection Seismic Isolators: Level ad-justable, restrained isolators, mounts in rugged welded steel housing with vertical and horizontal limit stops. Housings shall be designed to with-stand a minimum 1.0g accelerated force in all directions to 2 inches.

L. Final Paint Overspray: Overspray painting of as-sembled unit with Caribbean blue enamel.

PART 3 – EXECUTION

3.01 INSTALLATION

A. General: Rig and Install in full accordance with Manufacturer’s requirements, Project drawings, and Contract documents.

B. Location: Locate chiller as indicated on drawings, including cleaning and service maintenance clear-ance per Manufacturer’s instructions. Adjust and level chiller on support structure. If equipment provided exceeds height of scheduled chiller, installing con-tractor is responsible for additional costs associated with extending the height of parapet or screening walls/enclosures

C. Components: Installing Contractor shall provide and install all auxiliary devices and accessories for fully operational chiller.

D. Electrical: Coordinate electrical requirements and connections for all power feeds with Electrical Con-tractor.

E. Controls: Coordinate all control requirements and connections with Controls Contractor.

F. Finish: Installing Contractor shall paint damaged and abraded factory finish with touch-up paint matching factory finish.

10Form 150.27-EG1 (1210) Supersedes: 201.27-EG1 (210)