current switch

4
1 - 8 0 0 - 6 3 3 - 0 4 0 5 e22-2 Sensors Vol ume 13 AC Cu rrent Switc hes, Transducers and Indicato r Overview The ACU  AMP ser ies of AC curre nt sensors is a family of high-performance cur rent sensors offeri ng out st anding features, flexibility, and durability at an incredibl e pri ce. Choose from a wide selection of current transducers, switches and indicators, all designed in a rugged industry -standard feed-through package, including both fixed core and split core models.  ACT and ACS models have multiple input ranges (set by movable jumpers) for  maximum flexibility across many current rat ings . The curr ent transduc er output choices include 4 to 20mA, 24 VDC loop- powered, and 0 to 10 volt self-powered analog outputs. The Current Switch outputs are isolated solid state switches and are available in Normally Open and Normally Closed configurations.  A unit featuring field adjustable time delay is also offered in the Current Switch series. The ACL1 Current Indicator sens es AC current ranging from 0.5 to 100 A and requires no power for the indicating LED.  All models are panel-mountable; conve- nient DIN- rail adapter acce ssor ies are available. Use the Selection Guide to find the best sensor for your requirements.  ACU  AMP AC Spe cif ica tio ns by Mod el T ype Specifications T ransducer Transducer (True RMS) Switch Indicator  Model ACT ACTR ACS150 ACS200 ACSX ACL1  Input Range Jumpe r selec table: ACT005: 0 to2A 0 to 5A ACT 05 0: 0 to10 A 0 to20 A 0 to50 A ACT 20 0: 0 to10 0A 0 to150 A 0 to200 A ACT750: 0 to37 5A 0 to500 A 0 to750 A ACT 200 0: 0 to 100 0A 0 to 1333A 0 to 20 00A Jumpe r selec table: AC TR 00 5: 0 to2A 0 to 5A ACT R0 50 : 0 to10 A 0 to20 A 0 to50 A AC TR 20 0: 0 to100 A 0 to150 A 0 to200 A AC TR750: 0 to375 A 0 to500 A 0 to750 A ACT R20 00: 0 to 100 0A 0 to 13 33 A 0 to 20 00 A Norma lly Open: -Fcore:1 to150 A -S co re: 1.75 to 150A Norma lly Close d: -Fcore:1 to150 A -S co re: 1. 75 to 15 0A Jumpe r Selectable : Norma lly Open: -Fcor e:1 to6A 6 to40 A 40 to17 5A -S core: 1. 75 to 6A 6 to40 A 40 to 20 0A Norma lly Close d: -Fcor e:1 to6A 6 to40 A 40 to 17 5A -S core: 1. 75 to 6A 6 to40 A 40 to 200A Jumpe r Selec table : Norma lly Open: -F core: 1. 5 to 12 A 12to 55 A 55 to 175A -Score:2 to12A 12to 55 A 55 to 20 0A Norma lly Close d: -F core: 1.5 to 12 A 12to 55A 55 to 175A -Scor e:2 to12A 12to 55 A 55to 20 0A 0.5 to 100 A Output -10models : 0–1 0 VDC -42 L mod els : 4–2 0 mA, loop-powered 4–2 0 mA, loop- powe red true RMS Norma lly Open: 0.15A @ 24 0 VACor VD C Norma lly Close d: 0.2A@ 13 5 VACor VD C Norma lly Open  /Nor mally Close d AC model: 1A@ 24 0 V AC Norma lly Open  /Nor mally Close d DC mod el: 0. 15 A @ 30VDC Norma lly Open  /Nor mally Close d AC model: 1A@ 24 0 VAC Norma lly Open  /Nor mally Close d DC model: 0.2A @ 135 VA C/V DC LED Onl y (flash ing, red) Frequency Range -1 0 mo de ls: 50to 60Hz sinus oidal wave forms only -42 L mod els : 20– 100 Hz 10 to40 0 Hz non-sinusoidal waveforms 6 to 100 Hz 6 to 100 Hz 50 to 100 Hz 50 - 400 Hz Response Time -1 0 mo de ls : 10 0 ms -42 L mod els : 300 ms 600 ms 120 ms 40 to 120 ms Fie ld adj ust abl e time del ay: 0.12 to 15 seconds N/A Sensing Aperture ACT00 5, ACT05 0, ACT20 0: -F co re: 0.75 in [19 mm] di a. -S core: 0. 85 in [2 1. 6 mm] sq. ACT75 0, ACT20 00: 3. 0 in [76.2 mm] dia ACTR0 05, ACTR0 50, ACTR2 00: -Fcore: 0.75 in [19 mm] di a. -S core: 0. 85 in [2 1. 6 mm] sq. ACTR7 50, ACTR2 000: 3. 0 in [7 6. 2 mm] di a -F core: 0. 75 in [1 9 mm] di a. -S co re: 0. 85 in [21 .7 mm] sq. -F core: 0. 55in [13 .97 mm] dia . -S core: 0. 85 in [21 .7 mm] sq. -F core: 0. 75in [1 9 mm] di a. -S core: 0. 85 in [21 .7 mm] sq. 0. 32 in [8. 13 mm]

Upload: sreekanth-raveendran

Post on 08-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Current Switch

8/6/2019 Current Switch

http://slidepdf.com/reader/full/current-switch 1/4

1 - 8 0 0 - 6 3 3 - 0 4 0 5e22-2Sensors

Volume 13

AC Current Switches, Transducersand Indicator

OverviewThe ACU AMP series of AC current

sensors is a family of high-performancecurrent sensors offering outstandingfeatures, flexibility, and durability at anincredible price. Choose from a wideselection of current transducers, switchesand indicators, all designed in a ruggedindustry-standard feed-through package,including both fixed core and split coremodels.

 ACT and ACS models have multiple inputranges (set by movable jumpers) for 

maximum flexibility across many currentratings. The current transducer outputchoices include 4 to 20mA, 24 VDC loop-powered, and 0 to 10 volt self-poweredanalog outputs. The Current Switch outputsare isolated solid state switches and areavailable in Normally Open and NormallyClosed configurations.

 A unit featuring field adjustable time delayis also offered in the Current Switch series.

The ACL1 Current Indicator senses ACcurrent ranging from 0.5 to 100 A andrequires no power for the indicating LED.

 All models are panel-mountable; conve-nient DIN-rail adapter accessories areavailable. Use the Selection Guide to findthe best sensor for your requirements.

 ACU AMP AC Specifications by Model Type

Specifications Transducer Transducer (True RMS) Switch Indicator  

Model ACT ACTR ACS150 ACS200 ACSX ACL1  

Input Range 

Jumper selectable:ACT005: 0 to2A0 to 5A

ACT050: 0 to10A0 to20A0 to50A

ACT200: 0 to100A0 to150A0 to200A

ACT750: 0 to375A0 to500A0 to750A

ACT2000: 0 to 1000A0 to 1333A0 to 2000A

Jumper selectable:ACTR005: 0 to2A0 to 5A

ACTR050: 0 to10A0 to20A0 to50A

ACTR200: 0 to100A0 to150A0 to200A

ACTR750: 0 to375A0 to500A0 to750A

ACTR2000: 0 to 1000A0 to 1333A0 to 2000A

Normally Open:-Fcore:1 to150A-S core: 1.75 to 150A

Normally Closed:-Fcore:1 to150A-S core: 1.75 to 150A

Jumper Selectable:Normally Open:-Fcore:1 to6A

6 to40A40 to 175A

-S core: 1.75 to 6A6 to40A40 to 200A

Normally Closed:-Fcore:1 to6A

6 to40A40 to 175A

-S core: 1.75 to 6A6 to40A40 to 200A

Jumper Selectable:Normally Open:-F core: 1.5 to 12A

12to 55A55 to 175A

-Score:2 to12A12to 55A55 to 200A

Normally Closed:-F core: 1.5 to 12A

12to 55A55 to 175A

-Score:2 to12A12to 55A55 to 200A

0.5to

100 A

Output -10models: 0–10 VDC-42L models: 4–20 mA,

loop-powered

4–20 mA,

loop-powered true RMS

Normally Open:0.15A @ 240 VACor VDC

Normally Closed:

0.2A@ 135 VACor VDC

Normally Open /Normally ClosedAC model:1A@ 240 VACNormally Open /Normally ClosedDC model:0.15A @ 30VDC

Normally Open /Normally ClosedAC model:1A@ 240 VACNormally Open /Normally ClosedDC model:0.2A @ 135 VAC/VDC

LED Only(flashing, red)

Frequency Range 

-10 models: 50to 60Hzsinusoidal waveforms only

-42L models: 20–100 Hz

10 to400 Hznon-sinusoidal waveforms

6 to 100 Hz 6 to 100 Hz 50 to 100 Hz 50 - 400 Hz

Response Time 

-10 models: 100 ms-42L models: 300 ms

600 ms 120 ms 40 to 120 msField adjustable time delay:0.12 to 15 seconds

N/A

Sensing Aperture 

ACT005, ACT050, ACT200:-F core: 0.75 in [19 mm] dia.-S core: 0.85 in [21.6 mm] sq.

ACT750, ACT2000:3.0 in [76.2 mm] dia

ACTR005, ACTR050, ACTR200:-Fcore: 0.75 in [19 mm] dia.-S core: 0.85 in [21.6 mm] sq.

ACTR750, ACTR2000:3.0 in [76.2 mm] dia

-F core: 0.75 in[19 mm] dia.

-S core: 0.85 in[21.7 mm] sq.

-F core: 0.55 in[13.97 mm] dia.

-S core: 0.85 in[21.7 mm] sq.

-F core: 0.75 in[19 mm] dia.

-S core: 0.85 in[21.7 mm] sq.

0.32 in[8.13 mm]

Page 2: Current Switch

8/6/2019 Current Switch

http://slidepdf.com/reader/full/current-switch 2/4

w w w . a u t o m a t i o n d i r e c t . c o m / c u r r e n t - s e n s o r sSensors

e22-3

CompanyInformatio

SystemsOverview

ProgrammControlle

Field I/O

Software

C-more &other HM

Drives

SoftStarters

Motors &Gearbox

Steppers/Servos

Motor Controls

ProximitySensors

PhotoSensors

LimitSwitches

Encoders

CurrentSensors

PressureSensors

TemperatSensors

PushbuttoLights

Process

Relays/Timers

Comm.

TerminalBlocks &Wiring

Power 

CircuitProtectio

Enclosure

Tools

Pneumat

Appendix

ProductIndex

Part #Index

Volume 13

AC Current Sensors, Switches andTransducers Application Guide

Pump Jam & Suction Loss Protection 

Crusher/Grinder/Shredder Motor Interlocks 

Electric Motor Load Status 

Pump Load Monitoring 

The performance of size reduction equipment like crushers orgrinders can be optimized by controlling the in-feed in order to• Help prevent jamming• improve the uniformity of the resultant product• Enhance overall production efficiency

 Application Guide ACU AMP current sensors are a great fit

for many applications including materialhandling, fan and pump applications, andheating systems. With current transducers,current switches and current indicators,this sensor family gives you valuable data

for processes ranging from monitoring

loads to preventive maintenance. Modelswith the ability to read True RMS non-sinu-soidal waveforms make it easy to monitor applications using variable frequencydrives.

Use the application examples to help

choose the best sensor model for your application.

Motor ControlSignal

Motor Starter 

DigitalInput

 ACS SeriesCurrentOperated

Switch

0-10v or 4-20mA Inputto Controller 

TrueRMSTransducer 

VariableFrequencyDrive

PLCInputs

Current Switchor Transducer 

Motor Starters

PLCOutputs

Lamp Failure Detection 

 ACS Series CurrentOperated Switch

L1

L2InactiveRelayContact

When L1 fails, the current drops. The Current OperatedSwitch detects the drop in current and activates the relay

which turns on the back-up lamp L2. The system may be

configured fail-safe by using a Normally Open Currentswitch together with Normally Closed relay contacts

Use: ACTR Series - True RMS Current

Current I

Current Switch

or Transducer 

Heater Life Prediction 

Page 3: Current Switch

8/6/2019 Current Switch

http://slidepdf.com/reader/full/current-switch 3/4

1 - 8 0 0 - 6 3 3 - 0 4 0 5e22-8Sensors

Volume 13

 ACS150 Series current operated switchescombine a current transformer, signalconditioner and limit alarm into a singlepackage for use in monitoring or proof of operation applications. Offering anadjustable setpoint range of 1 to 150amps and universal, solid-state outputs,

the self-powered ACS150 can be tailoredto provide accurate and dependabledigital indication of over-current condi-tions across a broad range of applica-tions. The ACS150 is available infixed-core and split-core models.

 Applications

Electronic Proof of Flow

• Current operated switch eliminates the

need for multiple pipe or duct

penetrations.

• More reliable than electromechanical

pressure or flow switches.

Conveyors

• Detect jams and overloads; useful when

interlocking multiple conveyor sections

Heating Circuits

• Detect ON/OFF status; faster response

times than with temperature sensors.

Loss of Load Detective• Detect belt or coupling breaks with fast

response times

Lighting Circuits

• Easier and faster than photocells

Features• Five-year warranty

• Choose from N.O. output models,

0.15 A @ 240 VAC/VDC or

N.C. output, 0.20 A @ 240 VAC/VDC.

• Status LED provides visual indication of 

setpoint trip and contact action.

• Self-powered operation cuts installation

time and operating costs.

• Potentiometer-adjustable trip points

speed start-up and allow for tailored oper-

ation.

• Choose either split-core or fixed-core

enclosure style. Split-core packages allow

easy installation on existing systems ;

fixed-core enclosures offer more compact

package for OEM or new installations.

• Built-in feet with optional 35 mm DIN rail

adapter available.

Agency Approvals

UL, cUL, CE approvals accepted worldwide

ACS150 Series Specifications

Power Supply  None - Self-powered

Output  Isolated solid-state switch

Output Rating N.O. 0.15 A @ 240 VAC or VDCN.C. 0.20 A @ 135 VAC or VDC

Response Time  120 ms

Off State Leakage  < 10 µA

Input Ranges N.O.: Fixed-core: 1 to 150 A. Split-core: 1.75 to 150 A

N.C.: Fixed-core: 1 to 150 A. Split-core: 1.75 to 150 A

Hysteresis  5% of Setpoint

Overload (1 second duration)  1,000 A

Isolation Voltage  UL listed to 1,270VAC. Tested to 5,000 VAC (1 minute max)

Frequency Range  6 to 100 Hz

Case  UL 94V-0 flammability rated

Environmental Temperature  -58 to 149°F (-50 to 65°C)

Humidity  0 to 95% RH, non-condensing

Agency Listings  UL listed 508, UL file E222847, CE approved

ACS150 AC Current Operated Switches

Part Number Description Pcs/Pkg Wt (lb) Price  

ACS150-AE-F  N.O. AC/DC adjustable current switch in fixed core enclosure 1 0.30 <--->

ACS150-AE-S  N.O. AC/DC adjustable current switch in split core enclosure 1 0.35 <--->

ACS150-CE-F  N.C. AC/DC adjustable current switch in f ixed core enclosure 1 0.30 <--->

ACS150-CE-S  N.C. AC/DC adjustable current switch in f ixed core enclosure 1 0.35 <--->

Accessories

DRA-2  DIN rail adapters, 1.69”x0.39”x0.75” (43x10x19 mm) 2 0.40 <--->

ACS150 Series AC Current Switches

ACS150 Maximum Input Ranges

Type Range - Adjustable 

Maximum Input Amps 

Continuous 6 Sec.max 

1 Sec.max 

N.O. Fixed Core 1 to 150 A 150 400 1000

N.O. Split Core 1.75 to 150 A 150 400 1000N.C. Fixed Core 1 to 150 A 150 400 1000

N.C. Split Core 1.75 to 150 A 150 400 1000

Page 4: Current Switch

8/6/2019 Current Switch

http://slidepdf.com/reader/full/current-switch 4/4

w w w . a u t o m a t i o n d i r e c t . c o m / c u r r e n t - s e n s o r sSensors

e22-9

CompanyInformatio

SystemsOverview

ProgrammControlle

Field I/O

Software

C-more &other HM

Drives

SoftStarters

Motors &Gearbox

Steppers/Servos

Motor Controls

ProximitySensors

PhotoSensors

LimitSwitches

Encoders

CurrentSensors

PressureSensors

TemperatSensors

PushbuttoLights

Process

Relays/Timers

Comm.

TerminalBlocks &Wiring

Power 

CircuitProtectio

Enclosure

Tools

Pneumat

Appendix

ProductIndex

Part #Index

Volume 13

      S      P      M      A

TIME

Startup Inrush

Normal Operation Belt or Coupling Breaks

      S      P      M      A

TIME

Startup Inrush

Normal Operation

 Jam

MOTOR

OFF

Overload or JamUnderload or Status

Connections

ACS150 Series AC CurrentSwitches

ACS150 Series Fixed Core ACS150 Series Split Core

DimensionsInches [mm]