Control and Monitoring of Control and Monitoring of Hydrogen Sulfide in Digester Hydrogen Sulfide in Digester
Gas Gas
Steve Walker
Craig Barnes
Metro Wastewater Reclamation District
Metro District’s Central Treatment Plant
What to Use to Control HWhat to Use to Control H22SS
• Equipment • Iron vs. Aluminum Salts
• Dewatering Issues
• 503 Regulations – Aluminum under scrutiny in Round 2
• Iron beneficial for crops and other plants
District’s Reasons to Reduce District’s Reasons to Reduce the Amountthe Amount
• Potential offsite buyer for methane - gas contaminated with 3000 + ppm H2S
• Tried ferrous chloride from supplier’s recommendation
• Tried ferric chloride as an alternative
Reasons for AlternativesReasons for Alternatives
• Cost Comparison
• Flexibility
• Impacts on Processes
ResultsResults
• Cost – active pounds/digester loading – Same
• Reaction time slower with ferrous
• Flexibility proven – could use either product
Addition Points ImpactsAddition Points Impacts
• Primary Influent• Ferrous• Ferric
• DAF Conditioning Box• Ferrous• Ferric
Use of Ferric After TestingUse of Ferric After Testing
• H2S impacts on cogeneration equipment• Equipment reliability
• Destruction of yellow metal parts
• Acidification of engine oil
• Struvite reduction
12 cyl. Turbo 2000 hp w/1200 kW gen - 1 of 4
Engines required extensive maintenance
Trigen’s Turbine control panel with PLC
Trigen’s pride and joy - Centaur 40 Turbine
Current Usage and WhyCurrent Usage and Why
• Goal – Title V Air Permit Compliance• Limit of 169 tons per year SO2 to atmosphere
• H2S ceiling of 2000 ppm with running 3 hour average of 1800 ppm
• Ferric onsite – used for struvite control in dewatering process
• Handling one chemical vs. two - KISS
Current Dosing PointsCurrent Dosing Points
• Digester Feed Line
• DAF Conditioning Box
• NSEC Influent Channel
Ni/Deni Aeration Basin - 1 of 12
Current ResultsCurrent Results
• Gas production remains at 4MSCFD
• Holding H2S levels at 900 ppm +/- 100 with consistent feed rate
• Minimal Process Impacts• Foaming• Struvite
NOTENOTE
• High flow in spring 2001 reduced sulfide generators in the collection system by flushing the piping. This made results seem better. Dosages are back to traditional levels now.
Dosage RateDosage Rate
• Roughly 0.3 gpm ferric solution to 650 gpm digester feed or……
• Roughly 2000 pounds/day to 340,000 pounds TS = 12 active lb/ton
• Digesters are fed sequentially so all get equivalent dose
CalculationCalculation
• 0.3 gal/min x 8.34 lb/gal x 1.4 (specific gravity) x % iron in solution (40%) x 1440 min/day = 2000 lb/day of iron
• Lb/day x $0.10/lb x 365 days/yr = $73,000
Note the floating cover on Digester 6
MonitoringMonitoring
• Effectiveness checked with GC Mass Spec – twice per week from grab sample
• This would not meet the requirements of the current air permit
• APCD permit required installation of Continuous Monitoring System (CMS)
Digester FlaresDigester Flares
Turbine ExhaustTurbine Exhaust
Continuous Monitoring Continuous Monitoring System (CMS) RequirementsSystem (CMS) Requirements
• Continuous gas stream H2S monitoring
• Continuous data transmission and recording
• Instrument reliability
• Relative Accuracy Test Audit (RATA) compliant
LasIR UnitLasIR Unit
Control UnitControl Unit
Control Unit DisplayControl Unit Display
Modifications Needed After Modifications Needed After Initial InstallationInitial Installation
• Inability to meet accepted calibration protocol
• Extractive method required
• Water vapor in digester gas impacted reliability
White Cell White Cell
LasIR ReconfigurationLasIR Reconfiguration
• Sensor upgrade - aka “White Cell”
Gas Out(1/2” or ¼” Teflon tubing)
DiaphragmPump
Pressure/FlowController
To LasIR Analyzer
From LasIR AnalyzerFiber-optic cable
Coaxial cable
Infrared detector
Stack Gas IN(¼” or 1/8” Teflon tubing)
Cal. Gas IN
Three-way valve
Manual Valve
~ 15”
12-m multiple reflection (White) cell
Alak Chanda – 04January 2001
Layout of the Multi-pass Extractive Monitor Head
LasIR UpgradesLasIR Upgrades
• Laser modified for extractive analysis
• Nitrogen gas used for purge and zeroing
• H2S calibration gas incorporated
Cal and Purge GasCal and Purge Gas
ResultsResults
• Instrument has proven reliable
• Permit compliance achieved
Future UseFuture Use
• Instrument will control ferric dosing