contents...under certain conditions, the localized electric field near an energized conductor can be...
TRANSCRIPT
Contents
1. Abstract
2. Introduction
3. Mechanism of corona formation
4. Types of corona
4.1. Positive corona
4.2. Negative corona
5. Voltage parameters of corona
5.1. Disruptive critical voltage
5.2. Visual critical voltage
6. Factors affecting corona
7. Waveform of corona current
8. Disadvantages
9. Ways to reduce corona
10. Advantages and Applications
Abstract
Corona is a phenomenon associated with all energized transmission lines. Under certain conditions, the localized electric field near an energized conductor can be sufficiently concentrated to produce a tiny electric discharge that can ionize air close to the conductors (Electric Power Research Institute (EPRI), 1982). This partial discharge of electrical energy is called corona discharge, or corona.
Corona Discharge discharge results from electrical discharge and indicates ionization of oxygen
and the formation of ozone in the surrounding air. It can eat through a Polymer insulator until it
breaks! It produces extremely corrosive Nitric Acid when in a humid atmosphere!
Several factors, including conductor voltage, shape and diameter, and surface irregularities such as scratches, nicks, dust, or water drops can affect a conductor’s electrical surface gradient and its corona performance. Corona is the physical manifestation of energy loss, and can transform discharge energy into very small amounts of sound, radio noise, heat, and chemical reactions of the air components. Because power loss is uneconomical and noise is undesirable, corona on transmission lines has been studied by engineers since the early part of this century. Many excellent references exist on the subject of transmission line corona (e.g., EPRI, 1982). Consequently, corona is well understood by engineers and steps to minimize it are one of the major factors in transmission line design for extra high voltage transmission lines (345 to 765 kilovolts (kV)). Corona is usually not a design issue for power lines rated at 230 kV and lower. The conductor size selected for the project’s transmission line is of sufficient diameter to lower the localized electrical stress on the air at the conductor surface and would further reduce already low conductor surface gradients so that little or no corona activity would exist under most operating conditions.
To prevent the formation of corona, the working voltage under fair working conditions should be
kept atleast 10% less than the disruptive critical voltage. Corona formation may be reduced by
increasing the effective radius. Thus steel cored aluminium has the advantage over hard drawn
copper conductors on account of the large diameter, other conditions remaining the same. The
effective conductor diameter can also be increased by the use of bundled conductors.
The corona discharges emit radiations which may introduce noise signals in the communication
channels, radio and television receivers in the vicinity. This is called radio interference (RI). Radio
noise from overhead power lines is caused by corona on conductors and fittings ,surface discharges
on insulators and poor contacts in fitting and insulator strings.
The importance of radio interference problem in the present age can hardly be over-emphasized.
Great attention is paid to reduce the level of radio interference from EHV lines to tolerable limits.
Corona Discharge discharge results from electrical discharge and indicates ionization of oxygen
and the formation of ozone in the surrounding air.
Corona reduces the magnitude of high voltage steep fronted waves due to lightning or switching by
partially dissipating as a corona loss. Corona act as a safety valve for lightning surges, by causing a
short circuit.
In a positive corona the electron avalanche is initiated by an exogenous ionisation event in a region
of high potential gradient. The electrons resulting from the ionisation collision are attracted toward
the positive electrode, and the positive ions are repelled from it. The secondary electrons, required
to seed further avalanches, are generated at the boundary of ionisation region by photons of light
released during the ionisation process. When these photons strike neutral gas molecules they
liberate electrons (through to the photoelectric effect), which are then drawn to the positive
electrode. It is these electrons which seed and sustain further avalanches. While the electrons travel
to the positive electrode the positive ions drift away from it towards the earthed electrode.
A feature of negative coronas is that they can only be sustained in fluids which contain
electronegative molecules, such as O2, H20 and CO2. These gases have molecules which readily
scavenge free electrons. Without electronegative molecules to capture free electrons, small negative
ions cannot form, with the result that a simple path of electron flow of ionised gas will form
between the two electrodes and an arc will develop.
Introduction
The term corona has been derived from the glow surrounding the conductor when the operating
voltage is sufficiently high.
A corona discharge is an electrical discharge brought on by the ionization of a fluid surrounding a
conductor, which occurs when the potential gradient (the change in the strength of the electric field)
exceeds a certain value, but conditions are insufficient to cause complete electrical breakdown or
arcing.
If the electric field is uniform, a gradual increase in voltage across the gap produces a breakdown of
the gap in the form of a spark without any preliminary discharges. But if the field is non-uniform,
an increase in voltage will first cause a localized discharge in the gas to appear at the points with
the highest electric field intensity, namely at sharp points.
Corona discharge usually involves two asymmetric electrodes; one highly curved (such as the tip of
a needle, or a small diameter wire) and one of low curvature (such as a plate, or the ground). The
high curvature ensures a high potential gradient around one electrode, for the generation of plasma.
Coronas may be positive or negative. This is determined by the polarity of the voltage on the
highly-curved electrode. If the curved electrode is positive with respect to the flat electrode we say
we have a positive corona, if negative we say we have a negative corona. (See below for more
details.) The physics of positive and negative coronas are strikingly different. This asymmetry is a
result of the great difference in mass between electrons and positively charged ions, with only the
electron having the ability to undergo a significant degree of ionising inelastic collision at common
temperatures and pressures.
The phenomenon of corona is accompanied by the following processes:
1. A faint glow appears around the conductor s which is visible in the dark.
2. There is an acoustical noise.
3. There is a tendency in conductors to vibrate.
4. Ozone and oxides of nitrogen are produced.
5. There is a loss of power.
6. There is radio interference.
Mechanism of corona formation
For an overhead transmission system the atmospheric air, which is the dielectric medium, behaves
practically like a perfect insulator when the potential difference between the conductors is small.
However the electrons and ions are always present to a small extent in the atmospheric air due to
the random action of the ionizing sources such as cosmic rays, ultra violet radiations from the sun,
radioactivity of the soil etc. If the voltage impressed between the conductors is of alternating
nature, sustained charging current will flow due to the capacitance of the line. With the increase of
the voltage, there is a corresponding increase in the electric field intensity.
As long as the air is subjected to a uniform electric field intensity of peak value is less than 3×106
volt/m (3000 kV/m or 30kV/cm), the flow of current between the two conductor of the line is
negligibly small for practical purposes. But when the electric field intensity (voltage gradient)
reaches this critical value of 3×106 volt/m, the air in the immediate vicinity of conductors no more
remains a dielectric but it ionizes and becomes conducting this electric break down is accompanied
by a faint glow which appears around the conductor and is visible in dark.
If the voltage gradient is increased further , the size and the brightness of the luminous envelope
goes on increasing until finally a spark or arc is established between the conductor because of the
partial breakdown of the insulating property of air between them. The effect of corona is more
pronounced at the protruding points of the conductor due to local higher field intensity there.
Steps of corona discharge are as follows:
Corona discharge of both the positive and negative variety have certain mechanisms in common.
1. A neutral atom or molecule of the medium, in a region of strong electric field (such as the
high potential gradient near the curved electrode) is ionized by an exogenous environmental
event (for example, as the result of a photon interaction), to create a positive ion and a free
electron.
2. The electric field then operates on these charged particles, separating them, and preventing
their recombination, and also accelerating them, imparting each of them with kinetic
energy.
3. As a result of the energisation of the electrons (which have a much higher charge/mass
ratio and so are accelerated to a higher velocity), further electron/positive-ion pairs may be
created by collision with neutral atoms. These then undergo the same separating process
creating an electron avalanche. Both positive and negative coronas rely on electron
avalanches.
4. In processes which differ between positive and negative coronas, the energy of these
plasma processes is converted into further initial electron dissociations to seed further
avalanches.
5. An ion species created in this series of avalanches (which differs between positive and
negative coronas) is attracted to the uncurved electrode, completing the circuit, and
sustaining the current flow.
The formation mechanism of the surface corona on dielectric plates under negative impulse
voltages has been investigated with a high-speed gated image intensifier in atmospheric air. An
acrylic plate was inserted perpendicularly to the axis of a rod-plane electrode system, and as a
backside electrode, a translucent electric conductive film was used to observe the luminosity of the
surface corona. The size and shape of the negative surface corona were measured using acrylic
plates of 1, 2, 5 and 10 mm thick and rod electrode with diameters of 10, 20, 50 and 125 mm.
Experiments show that the negative surface corona occurred just after the impulse voltage
application and formed a ring-like luminescence. The diameter of the ring increased with the
thickness of the acrylic plate and the diameter of rod electrode. The formation mechanism of the
negative surface corona is studied using a numerical analysis of the electron avalanche developing
along the electric line of force around the rod electrode. As a result, it is found that the occurrence
positions of the surface corona agree with the theoretical computed points of the maximum linear
density of positive ion.
Types of corona
There are mainly 2 types of corona namely:
1. Positive Corona
2. Negative Corona
Positive corona
A positive corona is manifested as a uniform plasma across the length of a conductor. It can often
be seen glowing blue/white, though many of the emissions are in the ultraviolet. The uniformity of
the plasma owes itself to the homogeneous source of secondary avalanche electrons described in
the mechanism section, below. With the same geometry and voltages, it appears a little smaller than
the corresponding negative corona, owing to the lack of a non-ionising plasma region between the
inner and outer regions. There are many fewer free electrons in a positive corona, when compared
to a negative corona, except very close to the curved electrode: perhaps a thousandth of the electron
density, and a hundredth of the total number of electrons.
However, the electrons in a positive corona are concentrated close to the surface of the curved
conductor, in a region of high-potential gradient (and therefore the electrons have a high energy),
whereas in a negative corona many of the electrons are in the outer, lower-field areas. Therefore, if
electrons are to be used in an application which requires a high activation energy, positive coronas
may support a greater reaction constants than corresponding negative coronas; though the total
number of electrons may be lower, the number of a very high energy electrons may be higher.
Coronas are efficient producers of ozone in air. A positive corona generates much less ozone than
the corresponding negative corona, as the reactions which produce ozone are relatively low-energy.
Therefore, the greater number of electrons of a negative corona leads to an increased production.
Beyond the plasma, in the unipolar region, the flow is of low-energy positive ions toward the flat
electrode.
Mechanism
As with a negative corona, a positive corona is initiated by an exogenous ionisation event in a
region of high potential gradient. The electrons resulting from the ionisation are attracted toward
the curved electrode, and the positive ions repelled from it. By undergoing inelastic collisions
closer and closer to the curved electrode, further molecules are ionized in an electron avalanche.
In a positive corona, secondary electrons, for further avalanches, are generated predominantly in the
fluid itself, in the region outside the plasma or avalanche region. They are created by ionization
caused by the photons emitted from that plasma in the various de-excitation processes occurring
within the plasma after electron collisions, the thermal energy liberated in those collisions creating
photons which are radiated into the gas. The electrons resulting from the ionisation of a neutral gas
molecule are then electrically attracted back toward the curved electrode, attracted into the plasma,
and so begins the process of creating further avalanches inside the plasma.
As can be seen, the positive corona is divided into two regions, concentric around the sharp
electrode. The inner region contains ionising electrons, and positive ions, acting as a plasma, the
electrons avalanche in this region, creating many further ion/electron pairs. The outer region
consists almost entirely of the slowly migrating massive positive ions, moving toward the uncurved
electrode along with, close to the interface of this region, secondary electrons, liberated by photons
leaving the plasma, being re-accelerated into the plasma. The inner region is known as the plasma
region, the outer as the unipolar region.
Negative coronas
A negative corona is manifested in a non-uniform corona, varying according to the surface features
and irregularities of the curved conductor. It often appears as tufts of corona at sharp edges, the
number of tufts altering with the strength of the field. The form of negative coronas is a result of its
source of secondary avalanche electrons (see below). It appears a little larger than the
corresponding positive corona, as electrons are allowed to drift out of the ionising region,
and so the plasma continues some distance beyond it. The total number of electrons,
and electron density is much greater than in the corresponding positive corona. However, they are
of a predominantly lower energy, owing to being in a region of lower potential-gradient. Therefore,
whilst for many reactions the increased electron density will increase the reaction rate, the lower
energy of the electrons will mean that reactions which require a higher electron energy may take
place at a lower rate.
As with the positive corona, the electron avalanche in a negative corona is initiated by an
exogenous ionisation event in a region of high potential gradient. However, the electrons travel in
the opposite direction, away from the negative electrode, while the positive ions are drawn towards
it. Unlike the positive corona, electrons ionised from the neutral gas are of relatively little use in
sustaining a negative corona because the general movement of electrons is away from the negative
electrode. Instead, the dominant process for generating secondary electrons is the photoelectric
action of photons striking the surface of the negative electrode. Indeed, the energy required to
liberate the electrons from the electrode surface is considerably lower than that required to ionise
air at standard temperatures and pressures, making it a more liberal source of secondary electrons.
Consequently, the avalanche seed electrons are generated on the surface of the electrode and are
repelled from it. As these electrons leave the ionisation region they attach themselves to neutral gas
molecules to form small negative air ions which drift towards the earthed electrode.
Mechanism
Negative coronas are more complex than positive coronas in construction. As with positive
coronas, the establishing of a corona begins with an exogenous ionization event generating a
primary electron, followed by an electron avalanche.
Electrons ionized from the neutral gas are not useful in sustaining the negative corona process by
generating secondary electrons for further avalanches, as the general movement of electrons in a
negative corona is outward from the curved electrode. For negative corona, instead, the dominant
process generating secondary electrons is the photoelectric effect, from the surface of the electrode
itself. The work-function of the electrons (the energy required to liberate the electrons from the
surface) is considerably lower than the ionization energy of air at standard temperatures and
pressures, making it a more liberal source of secondary electrons under these conditions. Again, the
source of energy for the electron-liberation is a high-energy photon from an atom within the plasma
body relaxing after excitation from an earlier collision. The use of ionized neutral gas as a source of
ionization is further diminished in a negative corona by the high-concentration of positive ions
clustering around the curved electrode.
Under other conditions, the collision of the positive species with the curved electrode can also
cause electron liberation.
The difference, then, between positive and negative coronas, in the matter of the generation of
secondary electron avalanches, is that in a positive corona they are generated by the gas
surrounding the plasma region, the new secondary electrons travelling inward, whereas in a
negative corona they are generated by the curved electrode itself, the new secondary electrons
travelling outward.
A further feature of the structure of negative coronas is that as the electrons drift outwards, they
encounter neutral molecules and, with electronegative molecules (such as oxygen and water vapor),
combine to produce negative ions. These negative ions are then attracted to the positive uncurved
electrode, completing the 'circuit'.
A negative corona can be divided into three radial areas, around the sharp electrode. In the inner
area, high-energy electrons inelastically collide with neutral atoms and cause avalanches, whilst
outer electrons (usually of a lower energy) combine with neutral atoms to produce negative ions. In
the intermediate region, electrons combine to form negative ions, but typically have insufficient
energy to cause avalanche ionization, but remain part of a plasma owing to the different polarities
of the species present, and the ability to partake in characteristic plasma reactions. In the outer
region, only a flow of negative ions and, to a lesser and radially-decreasing extent, free electrons
toward the positive electrode takes place. The inner two regions are known as the corona plasma.
The inner region is an ionizing plasma, the middle a non-ionizing plasma. The outer region is
known as the unipolar region.
One feature common to both positive and negative coronas is the formation of an electron
avalanche. Such an avalanche occurs when a strong electric field acts on naturally occurring free
electrons in the air. The electric field accelerates these electrons so that they gain sufficient kinetic
energy to cause ionisation when they collide with neutral gas molecules in their path. Additional
electrons are liberated during these collisions, which after acceleration are also able to ionise. As
the process continues more and more electrons are liberated and an avalanche rapidly builds up. In
this way a small number of seed electrons can cause ionisation of an entire gas and turn it into a
plasma. In a positive corona the avalanche electrons are drawn towards the electrode, while the
resultant positive ions are repelled. In a negative corona the avalanche is in the opposite direction,
with the electrons repelled and the positive ions drawn to the electrode. In a positive corona the
electrons accelerate as the avalanche progresses, while in a negative corona they decelerate as they
travel away from the electrode.
In an avalanche the electron collisions excite the positive ions so that photons of short wavelength
light are emitted. It is this that gives a corona discharge its characteristic glow. These photons play
an important part in producing the new seed electrons which are required to sustain the corona.
Voltage parameters of corona
There are two voltage parameters associated with corona:
1. Disruptive critical voltage
2. Visual critical voltage
Disruptive critical voltage
The minimum voltage at which the breakdown of the insulating properties occurs and corona starts
is called the disruptive critical voltage. The potential gradient corresponding to this value of the
voltage is known as disruptive critical voltage gradient.
A transmission line should operate just below the disruptive critical voltage in fair weather so that
corona only takes place during adverse atmospheric conditions. Therefore, the calculated disruptive
critical voltage is an indicator of the corona performance of the line. However, a high value of the
disruptive critical voltage is not the only criterion of satisfactory corona performance. The
sensitivity of the conductor to foul weather should also be considered, and the fact that corona
increases more slowly on stranded conductors than on smooth conductors.
According to F W Peek, for air under conditions near see level at 25o C and at a atmospheric
pressure of 760 mm of mercury (Hg) without impurities, the maximum value of voltage gradient at
which ionization of air starts is about 3×106volt/m. That is maximum value of the voltage gradient
is disruptive critical voltage gradient. The voltage corresponding to this voltage gradient is the
disruptive critical voltage.
For a three phase line,
Eo=Go mo r ln Deq Volt/phase
where,
Eo=disruptive critical voltage in volts
Go=(3×106 )/2½ = disruptive critical voltage gradient in volts/m
mo=irregularity factor or surface factor
= 1 for smooth conductors
= 0.93 to 0.98 for rough and weathered conductors
= 0.80 to 0.87 for stranded conductors
r= radius of each conductor in meters
Deq= equivalent spacing between the conductors in m = (Dab Dbc Dca)1/3
air density factor = 0.392p/(273+t)
(p= pressure ; t= temperature in oC)
Visual critical voltage
When the voltage of the line is the disruptive critical value, there is no visible corona. This is due to
the fact that the charges ions in the air must be able to receive a finite energy before they can cause
further ionization by collision, which is necessary for the corona discharge.
Visual glow of corona occurs at a voltage higher than the disruptive critical voltage. The minimum
voltage at which the visual corona starts is termed as visual critical voltage.
According to F W Peek, the actual visual corona does not start at the disruptive critical value of
voltage. The maximum value of voltage gradient responsible for starting of corona is 3×106 volt/m.
but this value of voltage gradient at the surface of conductor will not ionize the air. The maximum
value of 3×106 volt/m will cause ionization when this value is reached at a distance of (r+0.0301
r1/2) from the conductor axis, where r is in meters. The reason being that some energy is required by
the charged ions to start corona. If the maximum voltage gradient at the surface of conductor be
3×106 volt/m, the value of maximum voltage gradient at any other point away from the centre
would be less than this and, thus there will be corona discharge at that point.
Under the standard conditions of temperature and pressure, the value of visual critical voltage for a
three phase line can be written as follows when the effects of irregularity of the surface of the
conductor and air density factor are considered.
Ev= (3×106)/2½ mv r (1+0.3/√δr) ln(Deq/r) rms volts/phase
Where,
Ev= rms value of visual critical voltage
mv= irregularity factor
= 1.00 for smooth conductors
= 0.70 to 0.75 for local corona when effect is first visible at some places along line
= 0.80 to 0.85 for decided or general corona along the whole length of conductor
Factors Affecting Corona
Due to the inherent complexity and predominance of weather conditions, the theoretical analysis of
corona has always lagged behind, and it studies are mainly based upon experimental evidences.
Large number of full scale experimental lines has been constructed. The main purpose of these lines
was to determine the factors affecting corona loss and radio interference so as to form a basis for
economical and satisfactory performance of the existing EHV/UHV lines and the economical
designs of the new ones.
Corona loss depends upon large number of factors, the important being broadly classified in the
following ways:
1. Conductor surface gradient
2. Condition of conductor surface
3. Atmospheric conditions
4. Air density factor
Conductor surface gradient
Corona loss on a conductor is a function of potential gradient at the conductor surface. The surface
gradient is given by
Gmax= En / r ln (D/r) V/m
which is applicable to single conductor only when the effect of stranding, surface condition, and air
density are not considered. The field strength will be different for bundled conductor. In such case,
the surface gradient becomes non uniform by the distortion produced by induction.
From the equations of surface gradients for single conductors and multiple conductor lines, it is
seen that radius and spacing of conductors affect the surface gradients and therefore, the voltage at
which corona starts. In addition to this surface gradient also depends on the configuration of the
line and the height of the conductor above the ground. For example, in case of a line and flat
spacing, the surface gradient at the middle phase conductor is higher than the outer. The corona will
therefore start first on middle conductor.
Corona loss also depends upon the frequency and waveform of the supply voltage.
Condition of Conductor surface
The voltage at which corona starts is also affected by the condition of conductor surface. If the
conductor is smooth, the electric field will be more uniform as compared to that when its surface is
rough. The roughness of conductor may be caused by stranding, die burrs, scratches or deposition
of dust or other air borne particles on its surface. Due to the concentration of field intensity at the
rough spots local corona discharges occur there. Therefore, corona starting voltage is lower in case
of conductors with rough surface than for those with smooth surface.
It has been seen that after an operation period of six months or so, the conductors surface becomes
smooth due to weathering effects. This has been explained by the fact that during corona discharge
ozone (o3) and oxides of nitrogen are produced. They are rather unstable to give atomic oxygen
easily, which is a very active oxidizing agent. With the action of atomic oxygen at the pronounced
points, they become blunted making the surface smooth. When the conductors get aged in this way,
the corona loss is brought from the initial high value to a comparatively smaller stable value.
Atmospheric conditions
Atmospheric conditions due to weather affect the corona loss to a great extent. The corona loss is
fairly large during foul weather. Foul weather reduces the uniformity of electric field and lowers the
corona formation voltage. The increase of corona loss due to rain fall is due to the fact that the rain
drops settle on the conductor surface to form protruding points, which become the sources of local
discharges because of field intensity concentration at those points.
When the rate of rain fall increases, it is observed that the corona loss for a given conductor at any
voltage increases. But the rate of increase of loss is lesser than that of rain fall. The loss becomes
practically constant when the rate of rain fall is very high.
Air density factor
Air density is also one of the main factors to affect the corona loss. The air density factor is
defined as the ratio of density of air at any given barometric pressure, and temperature to that at the
conditions 25oC (77oF) and 760 mm (29.9 inches) of mercury barometric pressure. The value of air
density is taken to be equal to unity at standard barometric pressure of 760 mm of mercury and
25oC .
The value of at a pressure p mm of mercury and toC can be found out from the well-known gas
equation, which states that the product of pressure and volume divided by the absolute temp of a
gas is constant.
(273+25)/760 × p/(273+t)
= 0.392 p/ (273+t)
Humidity also affects corona voltage. An increase of humidity decreases corona starting voltage.
With the increase of the altitude, the air density is reduced and corona starting voltage will be
lower. However, lower average temperatures of air at high altitude compensates this effect by
increasing the corona starting voltage.
Waveform of corona current
The current flowing in the corona discharge contains high frequency components. The current
carried by the corona is determined by integrating the current density over the surface of the
conductor.
The shunt current in a line is almost purely capacitive under normal conditions, and leads the
applied voltage by 90o, and there is no power loss in the line under no load conditions.
When the applied voltage is increased and corona is formed, the air is rendered conducting, and
power loss occurs.
The shunt current would no longer be leading the voltage by 90o. Thus the current wave form
consists of two components. The lossy component would be non-sinusoidal and would occur only
when the disruptive critical voltage is exceeded in either polarity.
The corona current can be analyzed and shown to possess a strong third harmonic component.
Disadvantages of Corona
Coronas can generate audible and radio-frequency noise, particularly near electric power
transmission lines. They also represent a power loss, and their action on atmospheric particulates,
along with associated ozone and NOx production, can also be disadvantageous to human health
where power lines run through built-up areas. Therefore, power transmission equipment is designed
to minimize the formation of corona discharge.
Corona discharge is generally undesirable in electric power transmission where it causes :
1. Power loss
2. Audible noise
3. Radio interference
4. Insulation damage
5. Ozone production
6. Static electricity discharge
7. Lightning
8. Long term exposure to these radiations may not be good to health
Power loss
The power dissipated in the system due to corona discharges is called corona loss. It is very
difficult to estimate corona loss accurately because of its extremely variable nature.
According to FW Peek, the corona loss for single phases and equilaterally spaced three phase
lines under fair weather condition is given by the formula
Where,
Pc = corona power loss
f = frequency of supply in Hz
= air density factor
E = rms phase voltage in kV
Eorms = disruptive critical voltage/ phase in kV(rms)
r = radius of conductor in m
d = equivalent spacing between comductor in m
Audible noise
Transmission lines can generate a small amount of sound energy during corona activity. This
audible noise from the line can barely be heard in fair weather conditions on higher voltage lines.
During wet weather conditions, water drops collect on the conductor and increase corona activity so
that a crackling or humming sound may be heard near the line. This noise is caused by small
electrical discharges from the water drops.
Audible noise values can be calculated for transmission lines experiencing corona activity. This
modeling indicates that, during wet weather conditions, audible noise levels of approximately 46.6
to 49.6 A-weighted decibels (dBA) would occur within the right-of-way for the proposed
transmission line loop.
Audible noise will decrease with distance away from the proposed transmission line loop.
Presently, the proposed transmission line loop is located within an open farmland area, where
residences, businesses, and other receptors are not present. Due to all of these factors, impacts from
corona noise would be less than significant.
Radio interference
Radio interference is the adverse effect introduced by corona on wireless broadcasting. The corona
discharges emit radiations which may introduce noise signals in the communication lines, radio and
television receivers. It is mainly due to the brush discharges on the surface irregularities of the
conductor during positive half cycle. This leads to corona loss at the voltage less than critical
voltage. The negative discharges are less troublesome for radio reception. Radio interference is
considered as a field measured in microvolts/m at any distance from the transmission line and is
significant only at voltage greater than 200kV. There is gradual increase in RI level till the voltage
is such that measurable corona loss takes place. Above this voltage, there is rapid increase in RI
level. The rate of increase is more for smooth and larger diameter conductor. The amplitude of RI
level varies inversely as the frequency at which the interference is measured. Thus the service in the
higher frequency band e.g. television, frequency modulated broadcasting, microwave relay, radar,
etc. are less affected. RI is one of the very important factors while designing a transmission line.
Insulation damage
Inside electrical components such as transformers, capacitors, electric motors and generators.
Corona progressively damages the insulation inside these devices, leading to premature equipment
failure.
The accumulation of the nitric acid and micro-arcing within it create carbon tracks across insulating
materials. Corona can also contribute to the chemical soup destruction of insulating cements on
insulators resulting in internal flash-overs. The corona is the only indication. Defects in insulating
materials that create an intense electrical field can over time result in corona that creates punctures,
carbon tracks and obvious discoloration of NCI insulators.
Electrical field intensity producing corona on contaminated areas, water droplets, icicles, corona
rings, ... This corona activity then contributes nitric acid to form a chemical soup to change the
bonding cements and to create carbon tracks, along with ozone and ultraviolet light to change the
properties of NCI insulator coverings. Other detrimental effects include water on the surface or sub-
surface freezing and expanding when thawing, as a liquid penetrating into a material and then a
sudden temperature change causes change of state to a gas and rapid expansion causing fracture or
rupture of the material.
Ozone production
Ozone (O3), or trioxygen, is a triatomic molecule, consisting of three oxygen atoms. It is an
allotrope of oxygen that is much less stable than the diatomic allotrope (O2). Ozone in the lower
atmosphere is an air pollutant with harmful effects on the respiratory systems of animals and will
burn sensitive plants; however, the ozone layer in the upper atmosphere is beneficial, preventing
potentially damaging electromagnetic radiation from reaching the Earth's surface. Ozone is present
in low concentrations throughout the Earth's atmosphere. It has many industrial and consumer
applications.
An electrical discharge (a spark) splits an oxygen molecule into two oxygen atoms. (Electrical
discharge is also referred to as corona discharge.) These unstable oxygen atoms combine with other
oxygen molecules. This combination forms ozone.
Ways to Reduce Corona
There are several disadvantages of corona. So it becomes necessary to reduce the corona formation
for efficient power transmission. Some of the ways to minimize corona are:
1. Use of Corona Rings
Installing corona rings at the end of transmission lines.A corona ring, also called anti-corona ring, is
a toroid of (typically) conductive material located in the vicinity of a terminal of a high voltage
device. It is electrically insulated. Stacks of more spaced rings are often used. The role of the
corona ring is to distribute the electric field gradient and lower its maximum values below the
corona threshold, preventing the corona discharge.
2. Inverter duty motors
Inverter duty motors are gaining popularity across the globe. Inverter duty motors are designed for
optimized performance when run with variable frequency controllers. A wide range of products are
available including energy efficient motors, RPM A-C motors offering superior constant
horsepower ranges, and V*S Master motors offering full torque from 0 – 60 Hz. Inverter Drive
Motors are wound with 200 C moisture resistant Corona resistant magnet wire which dramatically
extends the life of the motors compared to motors wound with non-corona resistant wire.
The Corona resistant magnet wire dissipates charge build up at the surface thereby minimizing the
damaging effects of corona formation. The Corona Clear coatings offered by The P.D. George
Company use semiconducting nanoparticles to achieve optimum charge dissipation while offering
excellent coatability and dispersion stability.
3. Greater spacing between the conductor
By increasing the spacing between the conductors, disruptive voltage of the conductor (i.e. voltage
at which corona starts) increases. But this method has also got its limitations as with the increase of
spacing between the conductors, the cost of tower increases and there is an increase in the voltage
drop in the line due to the increase in the inductive reactance.
4. Hollow conductors
The method of increasing the diameter of conductors has been found to be very effective in
reducing corona. The diameter of conductors can be increased by either using hollow conductors or
steel cored aluminium conductors (ACSR) or expanded ACSR conductors.
5. Bundled conductors
The present practice is to use bundled conductors for reducing corona. The use of bundled
conductor s has become so common for transmission of larger blocks of power over longer
distances at EHV and UHV that the bundled conductors may be considered as an integral part of
EHV and UHV transmission lines.
The bundle acts as far as the electric field is concerned, like a conductor of diameter much larger
than that of the component conductors. This reduces the voltage gradient. In other words a higher
voltage can be used for permissible level of RI. The GMD of a bundle is high and therefore the
inductive reactance of the line is low.
The bundled conductors have higher capacitance and therefore low surge impedence as compared
to single conductors of equivalent diameter. The lower value of inductive reactance helps in
reducing the cost of series capacitors which are used to increase the transient stability limit of very
long transmission lines.
Advantages and applications of corona
1. Surge arresters
One of the major advantage of corona is that it provides a relief valve for surges by acting as a short
circuit. So it is specially employed in surge arresters installed on transmission lines.
2. Chemical synthesis
Many chemical products can be synthetized by corona discharges, but ozone is so far the only
one of industrial importance. It is used for the treatment of water, preserving its natural taste
and avoiding the smell of chlorine, and for other applications utilizing its large oxidation power
for instance in textile and paper industries.
The streamer type coronas used for ozone generation generally use air or oxygen filled short
gaps where one of the electrodes is covered with an insulating layer in order to prevent
streamer-arc transition. The relevant features of these so-called silent discharges for ozone
production are
- High energy electrons, providing a high yield of atomic oxygen for the main reaction
O + 02 + M --03 + M where M is a molecule, often oxygen, carrying away the excess energy;
- Low gas temperature, necessary to avoid thermal dissociation of the ozone molecules already
produced;
- High working pressure, around atmospheric.
Research is still needed to improve both chemical and energy yields, still too low ( 2 % and 6 %
respectively in dried air). Progress might be obtained by different ways.
- There is no clear evidence that a unipolar conduction current does not flow in the silent
discharge considered, in parallel with the streamers.
The catalytic effect of selected surfaces in production of activated nitrogen in coronas might
also be used for chemical synthesis of other products, as ammonia.
3. Surface treatment
Coronas are widely used as chemical reactors for surface treatment. Their oxidation and
reduction effects, Dassivating or corroding, have already been mentioned in the section dealing
with the electrochemical behavior of the discharge. Depending on the material to be treated and
the desired surface properties, the optimal corona gas composition, discharge parameters and
operating procedure may be very different.
An industrially very important application is the surface treatment of polymers, in particular to
increase their wettability and their adhesivity to ease printing, painting, sealing, coating, etc.
This is achieved simply by corona discharges in ambient air. Discharge products transfer their
activation energy to the polymer by breaking chains and creating radicals. These will rapidly
react with the further impinging particles, with the environment, and even with gas coming
from the bulk material. Polar bonds and hydrogen bonds formed in this way will increase the
polymers surface energy. The bonds most frequently encountered are C - 0, C = 0, C - 0 - O, C
– OOH.
If gap length of an air or oxygen corona is reduced so that the drift region becomes very small,
the oxygen grafted on polymers rapidly diminish due to increased etching. However, the
induced surface energy (wettability, etc.) is not reduced, even if the mechanisms involved must
have changed.
The efficiency of a corona surface treatment also depends on polarity. Negative coronas
generally appear to be less efficient than positive coronas, both for oxidation and etching.
Contributing factors are that the energy delivered to the surface by charge neutralization is
lower for negative ions than for positive ones and that the streamers generated in positive
coronas submit the surface to concentrated bursts of high energy ions.
The use of coronas to improve the wettability and adhesivity of polymer and other surfaces is
well established. However, more recent work shows that coronas also may be used to reduce
these quantities, typically by surface polymerization induced by coronas in fluorinated gases of
pressures up to atmospheric. For instance, good results have been obtained on paper and textile
materials by corona treatment in a C2 H2 F2 atmosphere.
4. Sanitization
Finally, let us note that coronas have bactericidal effects. Exposure to air coronas will stop the
growth of bacteria cultures, as recently demonstrated on Escherichia Coli. That is why, it is
being used for the sanitization purposes.
5. Electrostatic applications
The fact that unipolar corona drift regions contain ions of one sign only, and no plasma, is the
obvious reason for their extended use as chargers in electrostatic apparatus, like precipitators,
paint guns, fertilizer projectors, separators, xerographic copiers, voltage generators, and even
lightning protectors. On the other hand, charges generated by other means, typically by
turboelectricity, may easily cause coronas and sparks of their own, causing a considerable
number of explosion accidents each year. A knowledge of coronas, their transition to sparks,
and their interaction with the chemical environment is essential to further progress in these
fields.
Few more applications are
Drag reduction over a flat surface
Removal of unwanted electric charges from the surface of aircraft in flight and thus
avoiding the detrimental effect of uncontrolled electrical discharge pulses on the
performance of avionic systems
Scrubbing particles from air in air-conditioning systems
Removal of unwanted volatile organics, such as chemical pesticides, solvents, or
chemical weapons agents, from the atmosphere
Production of photons for Kirlian photography to expose photographic film
EHD thrusters, Lifters, and other ionic wind devices
Surface treatment for tissue culture (polystyrene)
Ionization of a gaseous sample for subsequent analysis in a mass spectrometer or an ion
mobility spectrometer
Solid-state cooling components for computer chips
Photocopying
Air ionizers
Nitrogen laser
References
1. Electrical Power System by Ashfaq Husain
2. Electrical Power System by C.L. Wadhwa
3. en.wikipedia.org
4. High Voltage Breakdown and Testing (online syllabus) by Professor JR Lucas
5. www.scribd.com
6. www.nipponmagnetics.com
7. www.inderscience.com