comoso fluid power sid division power unit start up manual

Upload: iossales

Post on 08-Jul-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    1/185

    i

    ♦ ♦ ♦ ♦

    Table of Contents1) Table of Contents

    Power Unit Startup  Unit Schematics, and Drawings 2) K3VL Series Piston Pump

    3) Electric Motor 4) Filtration 5) Manual Pump 6) JIC Style Reservoir

    7) RM Series Heat Exchanger

    8) Valves

    9) Miscellaneous 10) Operational/Maintenance

    Service Bulletins

     

        Y   o

       u   r    F    l   u    i    d

        P   o   w   e   r

        S   o   u   r   c   e

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    2/185

     

    SID DIVISION

    POWER UNIT START UP MANUAL

     

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    3/185

      2

    Table of Contents

    Introduction ............................................................................................................................................ 3

    Description ............................................................................................................................................   3

    Preparation of Use .............................................................................................................................   3,4

    Installation ...............................................................................................................................................   4

    Start-up Procedures .........................................................................................................................   5,6

    Special Tools ........................................................................................................................................... 6

    General Maintenance ...................................................................................................................... 6

    Maintenance Suggestions ...............................................................................................................   7,8

    Troubleshooting / General Information ................................................................................. 8,9

    Troubleshooting Pumps .................................................................................................................   9,10

    Troubleshooting Solenoid Valves ..............................................................................................   11

    WARNING

    FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THIS PRODUCTS AND/OR SYSTEMS

    DESCRIBED OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    4/185

      3

    Introduction

    This manual provides descriptive operation and maintenance instructions for standard Hydraulic Power

    Units manufactured by COMOSO. Any additional information may be obtained from COMOSO by

    referencing the Unit’s Model Number and Serial Number stamped on the Reservoir Nameplate.

    Some of the Information in this manual may not apply to your power unit. Information on custom unitsmay require service and application information from other sources.

    Warning

    It is imperative that personnel involved in the installation, service, and operation of the power unit be

    familiar with how the equipment is to be used. They should be aware of the limitations of the system and its

    component parts and have knowledge of good hydraulic practices in terms of safety, installation, and

    maintenance.

    Description

    The standard Hydraulic Power Unit usually consists of an oil reservoir which incorporates sump drain; oillevel gage, filler/breather assembly and spare return connections.

    The pump will be coupled to the motor using either an integral close-coupled configuration or flexible shaft

    coupling.

    Customer type power units may have heat exchangers for oil cooling; pressure or return filters, oil

    immersion heaters, directional valves, and other pressure and flow control valves, or monitoring

    instrumentation.

    Preparation For Use

    Unpacking and Checking

    The Power unit is mounted on skids and carefully packed for shipment. Do not remove it from the skid

    until it has been carefully checked for damage that may have occurred in transit. Report all damage

    immediately to the carrier and send a copy to the vendor. All open ports on the Power Unit were plugged at

    the factory to prevent the entry of contamination. These plugs must not be removed until just before piping

    connections are made to the unit. 

    Storage

    If the Power Unit is not going to be installed immediately it should be stored indoors, covered with

    waterproof sheet, and all open ports plugged. If long-term storage is expected (6 months or more) we

    recommend filling~ the reservoir completely with clean hydraulic fluid to prevent the entry of moisture.

    Removing from Shipping Skids

    Vertical Power Units should be removed from the skid by wrapping a heavy-duty nylon strap around the

     base of the motor mounting feet. This strap should be firmly secured to the lift truck forks when unit is

    lifted.

    Small horizontal style Power Units should be moved with a forklift truck, with 2 x 4 boards under the

    reservoir belly, to distribute and steady the load. Larger horizontal style Power Units have lifting holes in

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    5/185

      4

    the reservoir end plates. Extra heavy 1 in.  pipes can be inserted into the lifting holes for allowing movement

    with a forklift truck. L-shaped reservoirs are provided with clearance and cross braces under the base plate

    for movement with a forklift truck.

    Installation

    Locating Power Unit

    The unit should be installed indoors, and preferably in a clean, dry environment with an ambient

    temperature of 60 to 1000F. The unit can be installed outdoors if the reservoir was provided with optional

    weatherproof construction, and provisions were made for extreme temperature conditions. The reservoir

    can be secured to the floor or base using the four mounting holes located on the reservoir legs.

    Service Connections

    Water (If water cooled heat exchange has been provided) Connect the water supply to the inlet of the heat

    exchanger, with a shut-oft valve and strainer (if not supplied by COMOSO). If a temperature Control Valve

    has been provided, it also should be installed on the inlet side. The outlet of the heat exchanger should be

    connected directly to the facility drain system. On single pass heat exchangers the water connections should

     be installed as shown below. On multi-pass heat exchanger the water flow direction is not important.

    Electrical Connect the pump motor to the power source following the good practices as outlined in the

     National Electric Code and any local codes which may apply. Verify that the available voltage is the same

    as the voltage identified on the motor nameplate. Most motors have dual voltage ratings; so verify that the

    leads in the conduit box have been connected together as defined on the motor nameplate to match the

    facility power source available.

    If solenoid valves, pressure/temperature switches, or oil immersion heaters have been provided on the

     power unit, refer to the component name tag or other service information in this manual for operating

    voltage and ratings.

    Supply and Return Connections

    Complete all necessary interconnecting piping between the power unit and hydraulic actuators. The line

    sizes should be determined based on oil flow, operating pressure and allowable pressure drop between the

     power unit and actuator.

    Warning

    Check to insure that the proper rated hose or pipe is used on pressure lines.

    One of the key ingredients for good service and long life from a hydraulic system is cleanliness, and since

    most dirt infiltrates a hydraulic system during installation, we recommend the following:

    a) All open ports on the power unit, cylinders, etc. must remain plugged with tape or plastic plugs until just before the hydraulic connections are made.

     b) All interconnecting tubing, pipe, or hose should be clean, and free of rust, scale and dirt. The ends of

    all connectors should be plugged until just before they are to be installed in the system.

    c) All openings in the reservoir such as the filler /breather or access end covers holes must remainclosed during installation. --

    d) If Teflon tape or pipe dope is used, be sure it doesn’t extend beyond the first thread of the pipe fitting.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    6/185

      5

    Reservoir Filling

    The reservoir must be filled with clean fluid thru the filler cap on the reservoir. The type of fluid must be  — 

    compatible with the seals used on the power unit, and must comply with the recommendations of the 

    manufacturers of the component parts

    Refer to the component manufacturer’s catalog for  — fluid requirements. The cleanliness of the fluid goinginto the reservoir is very important, and in some cases, even new oil out of the drum is not adequate. We

    recommend that any fluid being transferred into the reservoir be done with the transfer pump with a 10 -

    micron filter installed. A Parker filter cart is available for this purpose.

    Start-Up Procedure

    1) Open any ball or gate valve (if applicable) located  — In the pump suction line.

    2) Back the system relief valve and/or pump pressure compensator adjustment knob out, so that the

     pressure will be near zero during the initial start. 

    Note:

    If the Power unit has been provided with a variable displacement pump or any piston pump , the pump case

     should be filled with clean oil prior to priming . In most cases this can be accomplished by disconnecting

    the pump case drain line and pouring the oil into the pump case drain port.

    3) If the system has been provided with an open center directional valve, the oil during start-up will flow

    directly back to tank. If the system has a closed center valve, it may be necessary to loosen a fitting

    momentarily at the pump discharge, to bleed any air in the pump during the priming operation.

    4) Jog the pump motor once, and verify that the pump is rotating in the same direction as the arrow tag on

    the pump case. If the direction is incorrect, reverse two (2) of the three (3) motor leads, and recheck the

    rotation.

    5) Jog the pump/motor (3) to (6) times to prime the pump and allow the pump to run for several minutes at

    zero pressure. Check the piping for any leaks and correct immediately. (Leaks in fittings and tubing can be

    the result of vibration during shipping.)

    6) Begin adjusting the relief valve and /or pump compensator to increase the pressure gradually. Note:

    On systems with open center directional valves, it will be necessary to actuate the valve to build pressure.

    7) Continue increasing pressure until normal operating pressure is obtained, and recheck system for leaks.

    Lock adjustment screws in place.

    Note

    If the system has been provided with a pressure compensator pump and a relief valve, adjust the relief valve

    approximately 200 PSI higher than the compensator so that excessive heat is not generated by the reliefvalve.

    8) During the start-up sequence, all filters should be monitored closely. Replace any filters element

    immediately, as soon as they begin to go into by-pass as indicated on the visual indicator.

    9) After the entire system has been wetted with fluid, refill the reservoir to the normal operating level.

    10) Verify that the cooling water to the heat exchanger (if applicable) is flowing. If the power unit has been

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    7/185

      6

     provided with a water control valve (Model WTC**), and the oil temperature is exceeding 1350F, adjust

    the valve to increase the water flow.

    Special Tools

    All normal service and maintenance on standard power units can be accomplished with standard hand tools.

     No special tools are required.

    General Maintenance

    Electric Motors  — Lubricate as recommended by the motor manufacturer

    Filters- Change or clean as required or as indicated on filters supplied with visual indicators. Make sure to

    check indicators shortly after start-up.

    Suction Strainers- Should be cleaned after 10 hours of operation initially and every 100 hours thereafter.

    Reservoirs-  Maintain oil level at all times. The oil should be checked after the first 100 hours and verify

    that the class of oil meets the requirements of the pump being used. Change the oil every 1000 to 2000hours depending on the application and operation environment.

    Recommended Spare Parts

    Spare filter elements should be purchased with the power unit, and be available during the start-upoperation. Other spare parts may be required, and are a function of the duty cycle of the hydraulic system,

    operation environment, and the acceptable down time of the equipment Please review the spare parts

    section for recommendations. 

    Preventive Maintenance

    Filter Service

    Filters must be maintained. The key to good filtration is filter maintenance. A machine may be equipped

    with the best filters available and they may be positioned in the system where they do the most good; but, if

    the filters are not serviced and cleaned when dirty, the money spent for the filters and their installation has been wasted. A filter, which gets dirty after one day of service and is cleaned 29 days later, gives 29 days

    of non-filtered fluid. A filter can be no better than the maintenance provided.

    Maintenance Suggestions

    1) Set up filter maintenance schedule and follow it diligently.

    2) Inspect filter elements that have been removed from the system for signs of failure which may indicate

    that the service interval should be shortened and of impending system problems.

    3) Never return to the system any fluid, which has leaked out.4) Always keep the supply of fresh fluid covered tightly.

    5) Use clean containers, hoses, and funnels when filling the reservoir, Use a filter cart when adding oil is

    highly recommended.

    6) Use common sense precautions to prevent entry of dirt into components that have been temporarily

    removed from the circuit.

    7) Make sure that all clean-out holes, filter caps, and breather cap filters on the reservoir are properly

    fastened.

    8) Do not run the system unless all normally provided filtration devices are in place.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    8/185

      7

    9) Make certain that the fluid used in the system is of a type recommended by the manufacturers of the

    system or components.

    10) Before changing from one type of fluid to another (e.g., from petroleum base oil to a fire resistant

    fluid), consult component and filter manufacturers in selection of the fluid and the filters that should be

    used. Also consult the publication “Recommended Practice for the use of Fire Resistant Fluids for Fluid

    Power Systems” published by the National Fluid Power Association,

    11) COMOSO offers an oil sampling kit, which can be used to ascertain the condition of the system fluid.

    Maintaining Proper Oil Temperature

    Hot oil in your equipments hydraulic system is one of the primary causes of poor operation, component

    failure and downtime. Here are some pointers on maintaining proper oil temperature.

    The oil in your hydraulic system was designed for operation within a specified temperature range. You may

     be able to run it at hotter temperatures for short periods of time, intermittently, without adverse effects. If

    you run continuously with oil that’s too hot, your equipment will operate poorly causing key component

    failure and machine downtime.

    “Hot oil” is a relative term. In most cases, 1200F at the reservoir is considered an ideal operating

    temperature. Always take an oil temperature reading at the reservoir, not at a component or any of the

     piping.

    Some hydraulic systems are designed to operate at 1300F or higher. If you don’t know the maximum

    operating temperature for your equipment, check your component manual for temperature and viscosity

    limitations.

    How can you keep your equipment’s hydraulic system from running too hot?

    1) Set up a regular schedule for checking the oil temperature, appearance, smell and feel. Change oil as

    recommended by the equipment manufacturer.

    2) Be prompt about removing, checking and repairing or replacing valves, pumps or other components that

    are running hot.--

    3) If relief or flow-control valves are running hot, check and adjust their settings. Follow your -equipment

    owner’s manual.

    4) Break in new components gradually. New, close fitting parts expand at different rates, and are especially

     prone to seize when they get too hot.

    5) Start a cold pump motor on hot oil by jogging just CCC enough to draw the hot oil into the component.

    Then wait a few minutes to allow the temperature to  equalize in all the pump’s parts. Repeat until the temperature on the outside of the pump is the same as that on the piping.

    6) Keep your equipment clean. A thick layer of dirt acts as insulation. It will prevent the hydraulic system

    from dissipating heat through the walls of the reservoir. 7) On hot days and in hot climates, check and change the oil more frequently. Be sure to use oilrecommended for hot weather operation by the equipment manufacturer or oil supplier .

    Measuring Oil TemperatureThere are several ways to check the temperature of the oil. The best, most accurate method is by means of a

    thermometer. On some machines, this is   mounted on the reservoir. Make it a habit to check   the

    thermometer periodically, after the equipment has been running for more than an hour.

    To estimate the reservoir temperature, if a thermometer is not available, one can perform a palm test. One

    should use extreme caution when performing this test. First check the reservoir with your fingertips. If it is

    not too hot to touch, place your palm on the reservoir. If you can hold your palm to the reservoir without to

    much discomfort, the average temperature of the oil is 130° F or below.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    9/185

      8

     

    Isolating Trouble-Spots

    To determine which components are running hot” and overheating the oil, feel the outlet fittings and lines

    at the valves, pumps and motors. If the oil temperature is normal going into a component but hot coming

    out, that could be one of the potential problem areas.

    A sticking valve can cause excessive heat. If a spool does not return promptly to the neutral position, the

     pump flow will be dumping continuously. This builds up heat rapidly.

    If a relief valve is set too low, part of the oil will be dumped across the valve with every cycle. This too,

    generates excessive heat. Even when all valves are set properly, they may not be operating well because of

    worn orifices or seals

    Always remove and check the hot components first.

    Check Oil Samples Periodically

    Checking oil temperature periodically is good preventive maintenance. So too is the practice of periodically

    siphoning an oil sample from the reservoir, and comparing it with a sample of clean, new oil.

    Oil that has been running too hot will look darker and feel thinner than new oil. It will also smell burned.

     Normally it will contain more contaminants, because hot oil leads to accelerated wear of component parts.

    Troubleshooting

    Dirty Oil

    1) Components not properly cleaned after servicing.

    2) Inadequate screening in fill pipe.

    3) Air breather left off. (No air breather provided or insufficient protection of air breather).

    4) Tank not properly sealed.5) Pipe lines not properly covered while servicing machine.

    6) Improper tank baffles not providing settling basin for heavy materials.7) Filter dirty or ruptured

    Fire resistant fluids

    1) Incorrect seals cause binding spools.

    2) Paint, varnish or enamel in contact with Lids can cause sludge deposits on filters and around seal areas.

    3) Electrolytic action is possible with some metals, usually zinc or cadmium.

    4) Improve mixtures can cause heavy sludge formations.

    5) High temperatures adversely affect some of (he fluids, particularly the water base fluids.

    6) Adequate identification of tanks containing these fluids should be provided so that they will be refilled

    with the proper media.

    7) As with mineral base oils, nuisance leaks should be remedied at once.8) Make certain replacement parts are compatible with fluid media

    Foaming Oil

    1) Tank line not returned below fluid level.2) Broken pipe.

    3) Line left out between a bulkhead coupling and the bottom of the tank after cleaning.

    4) Inadequate baffles in reservoir.

    5) Fluid contaminated with incompatible foreign matter.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    10/185

      9

    6) Suction leak to pump aerating oil.

    7) Lack of anti-foaming additives

    Moisture in Oils

    1) Cooling coils not below fluid levels.2) Cold water lines fastened directly against hot tank causing condensation within the tank.3) Soluble oil solution splashing into poorly sealed tanks or fill pipes left open.  —

    4) Moisture in cans used to replace fluid in tanks. Z

    5) Extreme temperature differential in certain geographical locations.

    6) Drain not provided at lowest point in tank to remove water collected over possibly long operating

     periods. 

    Overheating of System

    1) Relief valve set too close to compensator pressure setting.

    2) Water shut off or heat exchanger clogged.3) Continuous operation at relief setting.

    a. Stalling under load. etc. b. Fluid viscosity too high or too low.

    4) Excessive slippage or internal leakage.a. Check stall leakage part pump, motors and cylinders.

     b. Fluid viscosity too low.5) Reservoir sized too small6) Case drain line from pressure compensated pump-returning oil too close to suction line.

    a Re-pipe case drain line to opposite side of reservoir battling.7) Pipe, tube or hose too small causing high velocity.8) Valving to small, causing high velocity.9) Improper air circulation around reservoir.10)  System relief valve set too high.11)  Power unit operating in direct sunlight or ambient temperature is too high.

    Foreign matter sources in circuit1) Pipe scale not properly removed.2) Sealing compound (pipe dope. Teflon tape) allowed to get inside fittings.3) Improperly screened fill pipes and air breathers.4) Burrs inside piping.5) Tag ends of packing coming loose.6) Seal extrusions from pressure higher than compatible with the seal or gasket.7) Human element... not protecting components while being repaired and open lines left unprotected.8) Wipers or boots not provided on cylinders or rams where necessary.9) Repair parts and replacement components not properly protected while stored in repair depot. (Rust and

    other contaminants).

    Troubleshooting Pumps

    Pump makes excessive noise

    1) Check for vacuum leaks in the suction line. (Such as leak in fitting or damaged suction line.)2) Check for vacuum leaks in the pump shaft seal if the pump is internally drained. Flooding connectionswith the fluid being pumped may cause the noise to stop or abate momentarily. This will locate the point ofair entry.3) Check alignment with drive mechanism. -~ Misalignment will cause premature wear and it subsequenthigh noise level in the operation.4) Check manufacturer’s specifications relative to wear possibilities and identification of indications ofwear as high operating noise level etc.5) Check compatibility of fluid being pumped against E manufacturer’s recommendations6) Relief or unloading valve set too high Use reliable gauge to check operating pressure. Relief valve mayhave been set too high with a damaged pressure gauge. Check various unloading devised to see that it they

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    11/185

      10

    are properly controlling the pump delivery.7) Aeration of fluid in reservoir (return lines above fluid level).8) Worn or sticking vanes (vane type pump).9) Worn cam ring (van type pump).

    10) Worn or damaged gears and housing (gear pump).

    11) Worn or faulty bearing.

    12) Reversed rotation13) Cartridge installed backwards or improperly  —14) Plugged or restricted suction line or suction strainer.15) Plugged reservoir filler breather.16) Oil viscosity too high or operating temperature too low.17) Air leak in suction line or fittings may cause irregular movement of hydraulic system.18) Loose or worn pump parts19) Pump being driven in excess of rated speed.20) Air leak at pump shaft seal.21) Oil level to low and drawing air in through inlet. Z22) Air bubbles in intake oil.23) Suction filter too small or too dirty.24) Suction line too small or too long.

    25) Pump housing bolts loose or not properly torqued

    Pump failure to delivery fluid

    1) Low fluid level in reservoir

    2) Oil intake pipe suction strainer plugged.

    3) Air leak in suction line and preventing priming.

    4) Pump shaft turning too slowly

    5) Oil viscosity too high.

    6) Oil lift too high.

    7) Wrong shaft rotation

    8) Pump shaft or parts broken.

    9) Dirt in pump.10) Variable delivery pumps (improper stroke).

    Oil leakage around pump1) Shaft seal worn.

    2) Head of oil on suction pipe connection  — connection leaking

    3) Pump housing bolts loose or improperly torqued.

    4) Case drain line too small or restricted (shaft seal leaking).

    Excessive pump wear

    1) Abrasive dirt in the hydraulic oil being circulated through the system.2) Oil viscosity too low.3) System pressure exceeds pump rating.

    4) Pump misalignment or belt drive too tight

    5) Air being drawn in through inlet of pump.

    Pump parts inside housing broken

    1) Seizure due to lack of oil.

    2) Excessive system pressure above maximum pump rating.

    3) Excessive torquing of housing bolts.4) Solid matter being drawn in from reservoir and wedged in pump 

    Troubleshooting Solenoid ValvesSolenoid failures

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    12/185

      11

    1) Voltage too low. If voltage is not sufficient to complete the stroke of the solenoid, it will burn out the

    coil

    2) Voltage too high. Excessive voltage can also burn out coils.

    3) Signal to both solenoids of a double solenoid valve simultaneously. One or both of the solenoids will be

    unable to complete their stroke and will burn out. (Make certain the electrical signal is interlocked so that

    this condition cannot exist).

    4) Mechanical damage to leads (Short circuit, open connections, etc.)5)  Tight spool or other mechanical parts of the valve being actuated can prevent the solenoid from

    completing its stroke and subsequently burning out.

    6) Replacement springs too heavy in valve. Overloads solenoid and shortens life.

    7) Dirty contacts may not supply sufficient current to solenoid to satisfy inrush demands.

    8) Low voltage direct current solenoids may be affected by low battery capacity on cold mornings directly

    after starting cold engine (DC)

    9) Long feed lines to low voltage solenoids may cause sufficient voltage drop to cause erratic operation 

    Solenoid valve fails to operate1) Is there an electrical signal to the solenoid or  operating device? Is the voltage too low? — (Check with

    voltmeter or a test light in emergency.)

    2) If the supply to the pilot body is orificed, is the orifice restricted? (Remove orifice and check for foreign

    matter.  — Flushing is sometimes necessary because of floating impediment.)

    3) Has foreign matter jammed the main spool? (Remove end caps and see that main spool is free in its

    movement, remember that there will be a quantity of fluid escaping when the cap is removed and provide acontainer to catch it.)

    4) Is pilot pressure available? Is the pilot pressure adequate? (Check with gauge on main pressure input

     port for internally piloted types and in the supply line to the externally piloted type.)

    5) Is pilot drain restricted? (Remove pilot drain and let the fluid pour into an open container while the

    machine is again tried for normal operation. Small lines are often crushed by machine parts banging against

    them, causing a subsequent restriction to fluid flow.)

    6) Is pilot tank port connected to main tank port where pressures are high enough to neutralize pilot input

     pressure? (Combine pilot drain and pilot tank port and check for operation with the combined flow draining

    into an open container. Block line to main tank from pilot valve, if this corrects the situation, reroute pilot

    drain and tank line.)7) Are solenoids improperly interlocked so that a signal is provided to both units simultaneously? (Put test

    light on each solenoid lead in parallel and watch for simultaneous lighting. Check electrical interlock. This

    condition probably burns out more solenoids than any other factor.)

    8) Has mounting pad been warped from external heating? (Loosen mounting bolts slightly and see if valve

    functions. End caps can also be removed and check for tight spool.)

    9) Is fluid excessively hot? (Check for localized heating which may indicate an internal leak. Check

    reservoir temperature and see if it is within machine specifications.)

    10) Is there foreign matter in the fluid media causing gummy deposits? (Check for contamination. Make

    certain seals and plumbing are compatible with the type of fluid being used.)

    11) Is an adequate supply of fluid being delivered to actuate the load? (Many times there is sufficient

     pressure to shift the valve but not enough to actuate the workload. Check pump supply pressure and

    volume if necessary. Physical measurement of flow through relief valve with units blocked may be

    necessary.)12) Check circuit for possible interlocks on pressure sources to valve or to pilot.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    13/185

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    14/185

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    15/185

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    16/185

    Sizes 45, 60, 80, 112,

    140 and 200

    Up to 203 kW

    and 320bar 

    Features

    ◊ SAE and ISO mount.

    ◊ Small installation envelope.

    ◊ Through drive.

    ◊ SAE and metric ports.

    ◊ Side and rear porting.

    ◊ Vertical mount capability.

    ◊ Multiple drain ports.

    ◊ CW and CCW rotation.

    ◊ Opposed stroking pistons.

    ◊ Rated pressure 320 bar.

    ◊ Swash plate pillow support.

    ◊ Maximum displacement stop.

    ◊ Servo assist springs.

    ◊ Hydrostatic pillow bearing.

    ◊ Overcentre bleed.

    ◊ Pressure compensation.

    ◊ Integral proportional pressure.

    ◊ Load sensing.

    ◊ Integral unload.

    ◊ Torque limiter.

    ◊ Rigid construction.

    ◊ Long life roller bearings.

    ◊ Various sealing options.

    ◊ Low pulsation.

    ◊ Proven rotating group.

    ◊ Separate swash plate.

    ◊ Spherical valve plate.

    ◊ Super-finished bores.◊ Solid pistons.

    Swash-plate

     Axial Piston Pump

    B Series K3VL

    Pumps Industrial Products

    Data Sheet

    P-1002/02.09

    GB

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    17/185

    General Description

    The K3VL Series Swash Plate Type Axial Piston Pumps are designed to specifically satisfy the marine

    and general industrial machinery market where a high pressure variable displacement pump is required.

    K3VL Pumps are available in nominal displacements ranging from 45 to 200 cm3/rev with various

    pressure, torque limiter, and combination load sensing control options.

    Technical DescriptionThe components of the K3VL pump can be divided into three sub-groupings:

    Rotating Group  – Providing the main rotary pumping action.

    Swash Plate Group  – To vary the pump’s delivery flow rate.

    Valving Cover Group  – Providing the switching of oil between suction and delivery ports.

    Pumps Industrial Products

    K3VL80 Cross Section

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    18/185

    Technical Description (continued)

    The Rotating Group

    The Rotating Group comprises:

    (a) Valve plate 313(b) Cylinder block, 141

    (c) Pistons, 9 x 151 + Shoes, 9 x 152

    (d) Setting plate, 153

    (e) Spherical bush, 156

    (f) Cylinder springs, 9 x 157

    The drive shaft is coupled to the cylinder block through a splined section and supported at both of its

    ends by bearings. The shoe is swaged over the spherical end of the piston forming a spherical ball joint.

     Additionally the shoe has a hydrostatic pocket to balance the hydraulic thrust developed by the piston

    pressure allowing the shoe to lightly slide against the shoe plate.

    The subgroup consisting of the pistons and shoes are pressed against the shoe plate by the cylinder 

    springs acting through the setting plate and the spherical bush. The force developed by these cylinder 

    springs also press the cylinder block against the valve plate. Only the K3VL45-60 units use a single

    centralised spring with individual push pins provide the shoe and cylinder block hold down force.

    Swash Plate Group

    The Swash Plate Group comprises:

    (a) Swash plate, 212

    (b) Shoe plate, 211(c) Swash plate support, 251

    (d) Tilting bush, 214

    (e) Tilting pin, 531

    (f) Servo piston, 532

    The swash plate on the reverse side to the shoe location is a cylindrical form which is a “pillow”

    supported by the hydrostatic bearing provided by the swash plate support. The tilting bush is inserted

    into the swash plate and into this is installed the spherical portion of the tilting pin which is coupled to

    the servo piston.

     Any linear movement of the servo piston produced by the regulator pressure applied to either end is

    translated through the tilting pin into an angular movement of the swash plate which varies the tilting or 

    swash angle of the pump. A screw adjuster and lock nut is available to adjust the maximum tilting angle

    condition. The servo assist springs are provided to ensure good on stroking response particularly at low

    operating pressures.

    Pumps Industrial Products

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    19/185

    Technical Description (continued)

    Valve Cover Group

    The Valve Cover Group comprises:

    (a) Valve cover, 312(b) Valve pin, 885

    The valve plate with its two “kidney” shaped ports is installed onto the valve plate located by the valve

    plate pin. These two ports serve to supply and exhaust oil to and from the cylinder block. The oil

    passage switched by the valve plate is connected to the externally piped suction and outlet pressure

    ports through the valve cover. This valve plate is spherical in form for all but the smallest 45-60 unit.

    Pump Operation

    When the pump’s drive shaft is driven by a prime mover (Electric motor, Engine etc.), the cylinder block

    being spline coupled to the shaft will also rotate. If the swash plate has been tilted, the pistons arranged

    in the cylinder block due to the shoe being retained on the swash plate surface will both rotate with the

    cylinder block and reciprocate once per revolution. Paying attention to one such piston then it will move

    away from the valve plate for half a rotation (suction stroke) and move towards the valve plate for the

    second half of rotation (oil delivery stroke). The larger the tilt angle, the longer the piston stroke and the

    higher is the pump’s displacement. As the swash plate tilting angle approaches so the piston makes no

    stroke and thereby delivers no oil.

    Through Drive Option

    By suitable use of adaptors and splined couplings a wide variety of through drive mounting capabilitiesare available. The formation of these kits and their relevant part numbers will be found in the installation

    section.

    Pumps Industrial Products

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    20/185

    Technical Data

    For applications outside the following parameters, please consult Kawasaki Precision Machinery (UK) Ltd.

    Hydraulic Data

    Pressure Fluid Mineral oil, polyol ester and water glycol.

      Use a high quality, anti-wear, mineral based hydraulic fluid when the

      pressure exceeds 207 bar. In applications where fire resistant fluids

      are required consult Kawasaki Precision Machinery (UK) Ltd. The

      following chart illustrates the effects on pump life when non-standard

      fluids are used:

    Fluid selection

    Pumps Industrial Products

    V   G   2   2   

    V   G   3   2   

    V   G   4   6   

    V   G   6   8   

    V   G   1   0   0   

    1000

    600

    200

    100

    10-20° 0° 20° 40° 60° 80° 100°

    15

    20

    40

    6080

    allowable temperature range

    fluid temperature (°C)

       k   i  n  e  m  a

       t   i  c  v   i  s  c

      o  s

       i   t  y

       (  c   S   t   )

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    21/185

    Technical Data (cont inued)

    Filtration & Contamination Control

    Filtration

    The most important means to prevent premature damage to the pump and associated equipment and toextend its working life, is to ensure that hydraulic fluid contamination control of the system is working

    effectively.

    This begins by ensuring that at the time of installation that all piping, tanks etc. are rigorously cleaned in

    a sanitary way. Flushing should be provided using an off line filtration system and after flushing the filter

    elements should be replaced.

     A full flow return line filter of 10 micron nominal should be utilised and in addition a 150 micron mesh

    suction strainer is recommended. Typical filtration circuits are shown in the K3VL brochure.

    To prevent contaminant ingress from the external environment a 5 to 10 micron filter within the tanks

    breather is also recommended.

    Suggested Acceptable Contamination Level

    The relationship between contamination level and pump life is very dif ficult to predict as it depends on

    the type and nature of the contaminant present in the system. Sand or Silica in particular, due to its

    abrasive nature, does significantly reduce the expected life of a pump. Based on the precondition that

    there is no significant presence of Silica type substances then a minimum Cleanliness level of -/18/15

    ISO 4406 or SAE AS 4059E Table 1 Class 9 (NAS 9).

    Working Fluid Types

     Anti-Wear Type Hydraulic fluid

    It is generally recommended to use an anti-wear type hydraulic fluid as the mineral oil type when the

    operating pressure exceeds 210 bar.

    Fire-resistant Fluids

    Some kind of fire-resistant fluids require special materials for seals, paint and metal finishing. Please

    consult Kawasaki Precision Machinery (UK) Limited and provide details of the particular fluid

    specification and the working conditions so that any special requirements can be ascertained.

    In general, fire-resistant fluids have a low viscosity index and their viscosity also changes significantly

    with operating temperature and service life. For this reason, the circuit should be provided with an

    adequately sized cooler or forced cooling so that temperatures can be stabilised. Due to the inherent

    water content of some of these fluids the minimum allowable suction pressure will be higher than that

    of an equivalent mineral oil and so needs to be fully evaluated by Kawasaki Precision Machinery (UK)

    Limited. The following table provides an overview of the precautions and characteristics

    that can be expected with these types of fluids.

    Pumps Industrial Products

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    22/185

    Technical Data (cont inued)

    Fire-resistant Fluids (continued)

    Pumps Industrial Products

    Maximum Pressure

    (bar)320 320 210

    mineral oilfluid type:- polyol ester water glycolparameter:-

    Recommended Temperature

    Range (deg C)20 ~ 60 20 ~ 60 10 ~ 50

    Expected life expectancy compared

    to mineral oil100% 50% ~ 100% 20% ~ 80%

    Cavitation susceptability

    recommended usable (higher density)

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    23/185

    Technical Data (cont inued)

    Pump Start Up Precautions

    Pump Case Filling

    Be sure to fill the pump casing with oil through the drain port filling only the suction line with oil is totallyin suf ficient. The pump contains bearings and high-speed sliding parts including pistons with shoes and

    spherical bushes that need to be continuously lubricated. Part seizure or total premature failure will

    occur very quickly if this procedure is not rigidly followed.

    Piping & Circuit Checking

    Check to see that the piping and full hydraulic circuit is completed and that any gate valves etc. are

    open.

    Direction of Rotation

    Check to ensure that direction of rotation is correct and that the suction and delivery lines are

    connected correctly.

    Start Up

    Jog start the motor and check once more for correct rotation. Run the pump unloaded for a period to

    ensure that all residual air within the system is released. Check for external leakage, abnormal noise

    and vibrations.

    Case Drain Pressure

    Please ensure, as stated previously, that the maximum steady state drain line pressure at the pump

    casing does not exceed 1 bar. (Maximum peak pressure 4 bar). A suitable drain line hose and drain line

    filter when required must be selected to ensure this.

    Long Term Out of Usage

    It is undesirable to leave the pump out of use for a long period of a year or more. In such a situation

    it is recommended that the pump is run for a short period on a more frequent basis even if it is just

    unloaded. With regard to a pump held in storage then rotating the shaft on a frequent basis is suf ficient.

    If the pump is left out for more than the suggested time it will require a service inspection.

    Pumps Industrial Products

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    24/185

    pump model

    capacity

    pressure ratingsrated

    peak

    cc/rev

    bar 

    bar 

    bar 

    bar 

    Kg

    L

    Nm 150 150

    25

    0.6

    45 60

    60

    250

    280

    2400

    3000

    45

    320

    350

    2700

    3250

    225 225

    ISISO100

    ISO 25mm ISO

    SAE “E”

    SAE “D”

    SAE “C-C”

    SAE “B-B”

    SAE “C”

    SAE “B”

    SAE “A”

    input shaft

    mounting flange

    maximum allowable input torque

    case fill capacity

    weight

    case drain

    pressure

    max. continuous

    minimum operating speed

    max. boosted

    self primespeed ratings

    peak

    allowable

    through drive

    torque

    SAE B-BSAE B-B

    SAE B-B SAE B-B SAE B-B SAE B-B

    SAE BSAE B

    Nm

    cSt

    type

    type

    form Spline SplineSpline & Key Spline & KeyKey

    maximum contamination level

    viscosity range

    temperature range

    bolts

    rpm

    rpm

    rpm

    22222

    C

    Pumps

    Technical Data (cont inued)

    Specifi cations

    The following table indicates all of the specifications for the complete K3VLpump range from 45-200cc.

    More detailed ef ficiency curves and other related information will be found in a later section.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    25/185

    Industrial Products

    34

    4

    1

    600

    80 112

    112 140

    140 200

    200

    350

    400

    1900

    2200

    320

    350

    80

    2400 2200 2100

    2700 25003000

    0.8

    60 60 100

    1.4 1.4 3

    400 1000 1800

    SAE ESAE EISO180ISO125

    ISO 32mm ISO 45mm ISO 45mm

    ISO180 SAE DSAEAE C

    AE C SAE D SAE FSAE C, C-C

    and D

    SAE C, C-C

    and D

    e & Key Spline & Key Spline & Key Spline & Key SplineKey

    61

    150

    225

    400

    680

    699

    -20 – + 95

    10 to 1,000

    699

    Key Key

    981*1 981*1

    44442 2 and 4 bolt 2 and 4 bolt2

    8/15 ISO 4406 or SAE AS 4059E Table 1 Class 9 ( NAS 9 )

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    26/185

    Technical Data (cont inued)

    Specifi cations

    Notes:

      Rated Pressure

      Pressure at which life and durability will not be affected. 

    Peak Pressure

      The instant allowable surge pressure as defined by BS ISO 2944:2000. Life and durability

    however will be shortened.

     

    Maximum Self Priming Speed

      Values are valid for an absolute suction pressure of 1 bar. If the flow is reduced, or 

      if the inlet pressure is increased the speed may also be increased

    Maximum Boosted Speed

      Values stated are the absolute maximum permitted speed for which an increased inlet

      pressure will be required.

     

    Weight

       Approximate dry weights, dependant on exact pump type. Hydraulic Fluid Mineral anti wear 

      hydraulic fluid – for other fluid types please consult KPM

     

    Viscosity Range

      If viscosity is in range 200 to 1,000 cSt, then warming up is necessary before commencing

      full scale running.

      *1

    In case of reduced torque input shafts

      SAE C shaft Input Torque reduced to 400 Nm

      SAE CC shaft Input Torque Reduced to 680 Nm

    Pumps Industrial Products

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    27/185

    Ordering Code – K3VLSeries

    Pumps Industrial Products

    K3VL 80 B - 1 0 R S S L 0 12D /1-H*

    K3VL Series Pump

    Maximum displacement

    45 45 cm3/rev

    60 60 cm3/rev

    80 80 cm3/rev

    112 112 cm3/rev

    140 140 cm3/rev

    200 200 cm3/rev

    Design series

    B

    Hydraulic Fluid Type

     – Mineral oil

    W Water glycol (not K3VL 200)

     All other fluids contact Kawasaki

    Circuit Type

    1 Open Circuit

    Through drive & porting

    0 Single pump, side ported

     A SAE-A through drive, side ported

    B SAE-B through drive, side ported

    BB SAE-BB through drive, side ported

    C SAE-C through drive, side ported

    D SAE-D through drive, side ported

    E SAE-E (K3VL 200 only)

    R Single pump, rear portedS Single pump with plastic cover (Stock Pump)

    N Single pump with Steel cover, side ported

    Direction of rotation

    R Clockwise rotation

    L Counter-clockwise rotation

    Mounting flange & shaft

    S SAE spline & mount (see drawing for detail)

    M ISO key & mount (see drawing for detail) (not 200)

    F SAE-D mount with SAE-F spline shaft

    K SAE key & mount (see drawing for detail)

    T* SAE-B spline & SAE- B 2 bolt mount for 45

      (not 80) SAE- CC spline & SAE- D 4 bolt mount

      for 112/140 (not 200)

    U* 45 only, SAE-B key & SAE-B 2 bolt mount

    C* 112/140 only, SAE-C spline & SAE- C 2 bolt mount

    R* 112/140 only, SAE- C spline & SAE- D 4 bolt mount

    X* 112/140 only, SAE- C key & SAE- C 2 bolt mount

    W* 112/140 only, SAE -CC spline & SAE- C 2 bolt mount

    (*Non standard options)

     A

     Addit ional control op tions

    Blank Without additional

      limiter Torque limit contro l

    /1-S* Special low setting

      contact Kawasaki

    /1-L* Low setting range

    /1-M* Medium setting

    range

    /1-H* High setting range

    Displacement control

    (Without torque limit)

    /1-E0 Electrical displacement

      control (pilot pressure

      required)

    /1-Q0 Pilot operated

      displacement control

    Unloader solenoid

    (Type N below)

    blank For all other options

      except PN & LN

    115A 115V AC, 50.60Hz,

      DIN 43550 Plug

    235A 230V AC, 50.60Hz,

      DIN 43550 Plug

    12D 12V DC, DIN 43550 Plug

    24D 24V DC, DIN 43550 Plug

    Design

     Addit ional pressure control

    0 No additional control

    N With integrated unloading valve

    V With integrated remote control valve

    M With integrated unloading control valve

    1 Load sensing only (R4 plugged)

    Control device configuration

    P Remote pressure compensator 

    L Load sensing & pressure control

    Porting threads

    M Metric threaded

    S UNC threaded

    / - -

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    28/185

    Bearing Life

    Noise Level

    Performance K3VL45

    Pumps Industrial Products

    1.00 0.75 0.50 0.25

    0

    0 50 100 150 200 250 300 350

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    60

    70

    75

    80

    83

    86

    88

    89

    90

    Ratio of displacement

    Delivery Pressure (bar)

       V  o

       l  u  m  e

       t  r   i  c   E   f   f   i  c   i  e  n  c  y

       (   %   )

       R  a

       t   i  o  o

       f   D   i  s  p   l  a  c  e  m  e  n

       t

    Pump Ef fi ciency (%)

    28 30 32 34 36 38 40 42 44

    -0.2 bar 

    -0.1 bar 

    0 bar 

    +0.1 bar 

    +0.2 bar 

    2200

    2400

    2600

    2800

    3000

    3200

    Displacement q [cc/rev]

       S  p  e  e

       d   N   (  r  p  m   )

    Suction

    PressurePs (bar)

    gauge

    at the suction

    pump of the

    port pump

    Self Priming Capability

    1

       B  e  a  r   i  n  g   L   i   f  e   L   1   0   [   h  r   ]

    1000000

    1000

    1000rpm1200rpm

    1500rpm1800rpm

    E/M capacity [kW]

    100

    10000

    100000

    85

    80

    75

    70

    65

    60

    55

    50

    100 150

    Delivery pressure Pd [kgf/cm2]

       N  o   i  s  e   L  e  v  e   l   [   d   b   (   A   )   ]

    200 250 300 350

    1800rpm

    1500rpm

    q = 45cc/rev

    10

    500

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    29/185

    Pumps Industrial Products

    Bearing Life

    Noise Level

    Pump Ef fi ciency (%)

    Self Priming Capability

    Performance K3VL60

       B  e  a  r   i  n  g   L   i   f  e   L   1   0   [   h  r   ]

    1000000

    1000

    1500rpm1000rpm1800rpm1200rpm

    E/M capacity [kW]

    100

    10000

    100000

    85

    80

    75

    70

    65

    60

    55

    50150100 200

    Delivery pressure Pd [kgf/cm2]

       N  o   i  s  e   L  e  v  e   l   [   d   b   (   A   )   ]

    250 300 350

    1500rpm

    1800rpm

    q = 60cc/rev

    1.00 0.75 0.50 0.25

    0 100 150 200 250

    100

    75

    50

    25

    00.00

    0.25

    0.50

    0.75

    1.00

    86

    85

    84

    8280

    75

    7065

    60

    Ratio of displacement

    Delivery Pressure Pd (kgf / cm2 )

       R  a   t   i  o  o   f   D   i  s  p   l  a  c  e  m  e  n   t   [  q   /  q  m  a  x   ]

       V  o   l  u  m  e   t  r   i  c   E   f   f   i  c

       i  e  n  c  y   (   %   )

    36 39 42 45 48 51 54 57 60

    Ps = -0.2bar 

    Ps = -0.1bar 

    Ps = 0bar 

    Ps = +0.1bar 

    Ps = +0.2bar 

    2000

    1800

    2200

    2400

    2600

    2800

    3000

    Displacement q [cc/rev]

       S  p  e  e   d   N   (  r  p  m

       )

    50

    1

    0 50

    10

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    30/185

       B  e  a  r   i  n  g

       L   i   f  e

       L   1   0   [   h  r   ]

    1000000

    1000

    1500rpm

    1000rpm

    1800rpm

    1200rpm

    1 10

    E/M capacity [kW]

    100

    10000

    100000

    Bearing Life

    Noise Level

    Performance K3VL80

    Pumps Industrial Products

    1.00 0.75 0.50 0.25

    0

    0 50 100 150 200 250 300 350

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    70

    75

    80

    83

    8587

    89

    91

    92

    Ratio of displacement

    Delivery Pressure Pd [kgf/cm2]

       V  o   l  u  m  e   t  r   i  c   E   f   f   i  c

       i  e  n  c  y   (   %   )

       R  a   t   i  o  o   f   D   i  s  p   l  a  c  e  m  e  n   t

    Pump Ef fi ciency (%)

    Self Priming Capability Ps = +0.3bar 

    Ps = +0.2bar 

    Ps = +0.1bar 

    Ps = 0bar 

    Ps = -0.1bar 

    Ps = -0.2bar 

    3000

    2800

    2600

    2400

    2200

    2000

    50 55 60 65 70 75 80

    Displacement q [cc/rev]

       S  p  e  e

       d   N   [  m   i  n  -   1

       ]

    85

    80

    75

    70

    65

    60

    55

    50

    150100 200

    Delivery pressure Pd [kgf/cm2]

       N  o   i  s  e   L  e  v  e   l   [   d   b   (   A   )   ]

    250 300 350

    1800rpm

    1500rpm

    q = 80cc/rev

    0 50

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    31/185

    Performance K3VL112

    Pumps Industrial Products

    1.00 0.75 0.50 0.25

    0

    0 50 100 150 200 250 300 350

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    83

    80

    75

    70

    85

    87

    89

    91

    92

    Ratio of displacement

    Delivery Pressure (bar)

       V  o   l  u  m  e   t  r   i  c   E   f   f   i  c   i  e  n  c  y   (   %   )

       R  a   t   i  o  o   f   D   i  s  p

       l  a  c  e  m  e  n   t

    Pump Ef fi ciency (%)

    70 80 90 100 110

    Ps = -0.2bar 

    Ps = -0.1bar 

    Ps = 0bar 

    Ps = +0.1bar 

    Ps = +0.3bar 

    Ps = +0.2bar 

    1800

    2000

    2200

    2400

    2600

    2800

    Displacement q [cc/rev]

       S  p  e  e

       d   N   [  m   i  n  -   1

       ]

    Bearing Life

    Noise Level

    Self Priming Capability

    1000000

    1000

    1000rpm1200rpm

    1500rpm1800rpm

    E/M capacity [kW]

    100

    10000

    100000

    85

    80

    75

    70

    65

    60

    55

    50

    150100 200

    Delivery pressure Pd [kgf/cm2]

       N  o   i  s  e   L  e  v  e   l   [   d   b   (   A   )   ]

    250 300 350

    1800rpm

    1500rpm

    q = 112cc/rev

    1

    0 50

    10

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    32/185

    10

    0

    1

       B  e  a  r   i  n  g   L   i   f  e   L   1   0   [   h  r   ]

    1000000

    1000

    1000rpm 1200rpm

    1500rpm

    1800rpm

    E/M capacity [kW]

    100

    10000

    100000

    85

    80

    75

    70

    65

    60

    55

    50

    150100 200

    Delivery pressure Pd [kgf/cm2]

       N  o   i  s  e   L  e  v  e   l   [   d   b   (   A   )   ]

    250 300 350

    1800rpm

    1500rpm

    q = 140cc/rev

    Performance K3VL140

    Pumps Industrial Products

    1.00 0.75 0.50 0.25

    0

    0 50 100 150 200 250 300 350

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    0.00

    0.10

    0.20

    0.30

    0.40

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    91

    89

    87

    85

    83

    807570

    92

    Ratio of displacement

    Delivery Pressure Pd [kgf / cm2 ]

       V  o

       l  u  m  e

       t  r   i  c   E   f   f   i  c   i  e  n  c  y

       (   %   )

       R  a

       t   i  o  o

       f   D   i  s  p

       l  a  c  e  m  e  n

       t   [  q   /  q  m  a  x

       ]

    Pump Ef fi ciency (%)

    Self Priming Capability

    Bearing Life

    90 100 110 120 130 140

    Ps = -0.2bar 

    Ps = -0.1bar 

    Ps = 0bar 

    Ps = +0.1bar 

    Ps = +0.3bar 

    Ps = +0.2bar 

    1800

    2000

    2200

    2400

    2600

    2800

    Displacement q [cc/rev]

       S  p  e  e

       d   N   [  m   i  n  -   1

       ]

    Noise Level

    50

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    33/185

    120 140 160 180 200

    Ps = -0.2bar 

    Ps = -0.1bar 

    Ps = 0bar 

    Ps = +0.1bar 

    Ps = +0.2bar 

    1700

    1600

    1800

    1900

    2000

    2100

    3000

    Displacement q [cc/rev]

       S  p  e  e   d   N   (  m   i  n  -   1   )

    85

    80

    75

    70

    65

    60

    55

    50

    150100 200

    Delivery pressure Pd [kgf/cm2]

       N  o   i  s  e   L  e  v  e   l   [   d   b   (   A   )   ]

    250 300 350

    1500rpm

    1800rpm

    q = 200cc/rev

       B  e  a  r   i  n  g   L   i   f  e   L   1   0   [   h  r   ]

    1000000

    100000

    10000

    1000

    1000rpm

    1200rpm1500rpm

    1800rpm

    10 100 1000

    E/M capacity [kW]

    Performance K3VL200

    Pumps Industrial Products

    1.00 0.75 0.50 0.25

    0 50 100 150 200 250 300 350

    100

    75

    50

    25

    00.00

    0.25

    0.50

    0.75

    1.00

    89

    87

    85

    83

    80

    75

    70

    91

    90

    Ratio of displacement

    Delivery Pressure (bar)

       V  o

       l  u  m  e

       t  r   i  c   E   f   f   i  c   i  e  n  c  y

       (   %   )

       R  a

       t   i  o  o

       f   D   i  s  p   l  a  c  e  m  e  n

       t

    Pump Ef fi ciency (%)

    Self Priming Capability

    Bearing Life

    Noise Level

    0 50

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    34/185

    Bearing Life (continued)

    Bearing Life Correction Factors for Partial Displacement

    Pumps Industrial Products

    75%

    Displacement %

       B  e  a  r   i  n  g   l   i   f  e  a   d   j  u  s   t  m  e  n   t   f  a  c   t  o  r   (   %   )

    50%

    0%

    200%

    260%

    400%

    600%

    800%

    1000%

    1200%

    60% 70% 80% 85% 90%

     All bearing life curves on the previous pages refer to L10 life at full displacement. The foregoing curveis therefore to be used where duty cycle considerations require one to compute weighted life, which

    include partial displacement conditions.

    For example as shown above if the bearing life at full displacement from the previous graphs was say

    50,000 hours, then at the same operating condition with only 75% displacement the bearing life would

    be 260% of 50,000 hours or 130,000 hours.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    35/185

    Radial Loading Capacity

    No axial shaft loading possible Radial loading is achievable but in specific orientation:-

    In addition because of the high bearing capacity of this front bearing, radial shaft loading can be

    allowed provided that its orientation is such that it is this front bearing that takes the additional load

    (See diagram below).

    Pumps Industrial Products

    acceptable

    not acceptable

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    36/185

    Functional Description of Regulator 

    Pumps Industrial Products

    Key to Hydraulic Circuit Annotations

     Annotat ions

     A1

     A2

    a1

    a2

    B2

    B1

    b

    Dr 

    Pi

    Pc

    Pi

    PL

    Psv

    Ps

    Description

    Main pump delivery

     Auxiliary pump delivery

    Gauge port main pump delivery

    Gauge port auxiliary pump delivery

    Gear pump suction

    Main pump suction

    Suction gauge port

    Drain

    Pilot pressure

    Remote pilot port, Pressure compensator 

    Pilot port displacement control

    Load sense port

    Pressure assist port

    Inlet pressure

    Notes: The optional attached gear pump is recommended for all displacement control options.

    Hydraulic circuit diagrams illustrate the attached gear pump.

    Regulator Code Control Curves Hydraulic Circuit

    L0/L1 Load Sense and

    Pressure Cut-off 

    Pump displacement is

    controlled to match the flow

    requirement as a function

    of the system differential

    pressure (load pressurevs delivery pressure). In

    addition, there is a pressure

    cut off function incorporated

    into the control. With the L1

    option,the bleed-off orifice

    R4 is plugged.

    Q

    P

    PL

    Dr 

    Tair 

    R1

    R4

    DifferentialPressure Spool

    Cut-off Pressure Spool

    B

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    37/185

    Functional Description of Regulator (continued)

    Pumps Industrial Products

    Regulator Code Control Curves Hydraulic Circuit

    LN Load Sense and

    Pressure Cut-off w ith

    Integrated Unloading Valve(Normally Closed)

     An integrated unloading

    valve is sandwiched between

    the Load Sense regulator

    and pump to effectively

    de-stroke the swashplate

    when an electric signal is

    provided.

    Q

    P

    Dr B

     A

    Tair 

    PL

    R3

    R1

    Cut-off Pressure Spool

    UnloadingSolenoid

    Valve

    DifferentialPressure Spool

    Regulator Code Control Curves Hydraulic Circuit

    LM Load Sense and

    Pressure Cut-off w ith

    Integrated Unloading Valve

    (Normally Open)

     An integrated unloading

    valve is sandwiched between

    the Load Sense regulator

    and the pump. An electricalsignal must be provided to

    prevent the Load Sense line

    from draining.

    Q

    P

    Dr B

     A

    Tair 

    PL

    R3

    R1

    Cut-off Pressure Spool

    DifferentialPressure Spool

    Regulator Code Control Curves Hydraulic Circuit

    LV Load Sense and Pressure

    Cut-off with Integrated

    Proportional Relief Valve

     An integrated proportional relief

    valve is sandwiched between

    the Load Sense regulator and

    pump to control the maximum

    pressure setting by varying an

    electric signal to the valve.

     A separate amplifier is required.

    Q

    P

    Dr B

     A

    Tair 

    PL

    R3

    R1

    Cut-off Pressure Spool

    ProportionalRelief Valve

    DifferentialPressure Spool

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    38/185

    Functional Description of Regulator (continued)

    Pumps Industrial Products

    Regulator Code Control Curves Hydraulic Circuit

    L0/1 Load Sense and

    Pressure Cut-off with

    Torque Limiting

    L0/L1 control functions as

    previously noted. In response

    to a rise in delivery pressure

    the swashplate angle is

    decreased, restricting the

    input torque. This regulator

    prevents excessive load

    against the prime mover.

    The torque limit control

    module is comprised of two

    springs that oppose the spool

    force generated by the systempressure. By turning an outer

    and inner spring adjustment

    screw, the appropriate input

    torque limit can be set.

    Q

    P

    Dr B

     A

    Tair 

    PL

    R4

    R1

    Cut-off Pressure Spool

    Torque Limiter Spool

    DifferentialPressure Spool

    Regulator Code Control Curves Hydraulic Circuit

    P0 Pressure Cut-off 

     As system pressure rises

    to the cut-off setting, the

    swashplate de-strokes

    to prevent the system

    pressure from exceeding the

    compensator setting. It is

    imperative that a safety relief 

    valve be installed in the

    system.

    Note: By connecting the Pc

    port to a remote pressure

    control, variable pump

    pressure control can be

    achieved.

    Q

    P

    Dr B

     A

    Tair 

    Pc

    R2

    R1

    Cut-off Pressure Spool

    DifferentialPressure Spool

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    39/185

    Functional Description of Regulator (continued)

    Pumps Industrial Products

    Regulator Code Control Curves Hydraulic Circuit

    PN Pressure Cut-off with

    Integrated Unloading Valve

    (Normally Closed)

     An integrated unloading valve

    is sandwiched between the

    Pressure Cut-off regulator and

    pump to effectively de-stroke

    the swashplate when an

    electric signal is provided.

    Q

    P

    Regulator Code Control Curves Hydraulic Circuit

    PM Pressure Cut-off with

    Integrated Unloading Valve

    (Normally Open)

     An integrated unloading valve

    is sandwiched between the

    Pressure Cut-off regulator

    and the pump.

     An electrical signal must

    be provided to prevent the

    Pressure cut-off line from

    draining. Dr B

     A

    Tair 

    Pc

    R2

    R1

    Cut-off Pressure Spool

    DifferentialPressure Spool

    Dr B

     A

    Tair 

    Pc

    R2

    R1

    Cut-off Pressure Spool

    SolenoidValve

    DifferentialPressure Spool

    Q

    P

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    40/185

    Functional Description of Regulator (continued)

    Pumps Industrial Products

    Regulator Code Control Curves Hydraulic Circuit

    PV Pressure Cut-off with

    Integrated Proportional

    Relief Valve

     An integrated proportional

    relief valve is sandwiched

    between the Pressure Cut-

    off regulator and the pump

    to control the maximum

    pressure setting by varying an

    electric signal to the valve.

     A separate amplifier is

    required.

    Q

    P

    Dr B

     A

    Tair 

    Pc

    R2

    R1

    Cut-off Pressure Spool

    ProportionalRelief Valve

    DifferentialPressure Spool

    Regulator Code Control Curves Hydraulic Circuit

    P0/1 Pressure Cut-off withTorque Limit ing

    P0/1 control functions as

    previously noted. In responseto a rise in delivery pressure

    the swashplate angle is

    reduced, restricting the input

    torque. This regulator prevents

    excessive load against the

    prime mover.

    The torque limit control module

    is comprised of two springs

    that oppose the spool force

    generated by the system

    pressure. By turning an outerand inner spring adjustment

    screw, the appropriate input

    torque limit can be set.

    Note: By connecting the Pc

    port to a remote pressure

    control, variable pump

    pressure control can be

    achieved.

    Dr B

     A

    Tair 

    PC

    R2

    R1

    Cut-off Pressure Spool

    Torque SpoolLimiter 

    DifferentialPressure Spool

    Q

    P

    Outer Spring

     Adjustment

    Delivery Pressure

       P  u  m  p   F   l  o  w

    Outer Plus Inner Spring Adjustment

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    41/185

    Functional Description of Regulator (continued)

    Pumps Industrial Products

    Regulator Code Control Curves Hydraulic Circuit

    /1-E0 Electrical

    Displacement Control

    Varying the input current

    signal to the pump controller’s

    electronic proportional

    pressure reducing valve

    (PPRV) allows the user

    to control the pump

    displacement. As the current

    signal to the PPRV increases,

    the pump displacement

    increases proportionally.

    Note: An external pressure

    supply of 40 bar is required at

    the PSV Port (50bar max).

    Qmax

       P  u  m  p   F   l  o  w   R  a   t  e

       (   Q   )

    Qmin

    Input Current (mA) of Proportional

    Pressure Reading Valve

    360 600

    Customer Supplied

    Psv

    Pc

    Regulator Code Control Curves Hydraulic Circuit

    /1-Q0 Pilot Operated

    Displacement Control

    Varying the input pressure

    signal to the PSV port allows

    the user to control the pump

    displacement. As the pressure

    signal to the PSV increases,

    the pump displacement

    increases proportionally.

    Qmax

       P  u  m  p   F   l  o  w   R  a   t  e   (   Q   )

    Qmin

    Pilot Pressure (bar)

    90 28

    a

    Psv

    Pc

     A

    BDr 

    Customer 

    Supplied

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    42/185

     

    Torque Limiter Settings

    The following tabulations show the power limitation at various electric motor speeds for a specific pump.

    When selecting a control setting please ensure that the power limitation of a particularly sized electric

    motor to your national standard is not exceeded.

    Pumps Industrial Products

    K3VL45

    KW 970 1150 1450 1750

    3.7 S3 S4

    5.5 L3 S1 S3 S4

    7.5 L1 L2 L4 S2

    11 M1 M3 L1 L2

    15 H3 H4 M2 M4

    18.5 H2 H4 M2

    22 H3 H4

    30 H1

    37

    45

    55

    75

    90

    K3VL60

    KW 970 1150 1450 1750

    3.7

    5.5 S2 S4

    7.5 L4 S1 S3

    11 M4 L2 L4 S1

    15 M2 M3 L1 L3

    18.5 H2 M1 M3 L1

    22 H2 M2 M3

    30 H1 H3

    37 H1

    45

    55

    75

    90

    K3VL80

    KW 970 1150 1450 1750

    3.7

    5.5 S2 S4

    7.5 L6 S1 S3

    11 L2 L4 L6 S1

    15 M4 L1 L3 L5

    18.5 M1 M3 L1 L3

    22 H3 M1 M4 L1

    30 H1 H2 H4 M2

    37 H2 H4

    45 H1 H2

    55 H1

    75

    90

    K3VL112

    KW 970 1150 1450 1750

    3.7

    5.5

    7.5 S5 S6

    11 S1 S3 S5 S6

    15 L3 L4 S2 S4

    18.5 M4 L2 L4 S2

    22 M2 M4 L3 L4

    30 H4 M1 M3 L1

    37 H2 H3 M1 M3

    45 H2 H4 M1

    55 H2 H4

    75 H1

    90

    K3VL140

    KW 970 1150 1450 1750

    3.7

    5.5

    7.5

    11 S2 S4

    15 L6 S1 S3

    18.5 L3 L5 S1 S3

    22 L1 L3 L6 S1

    30 M2 M3 L2 L4

    37 H4 M1 M3 L2

    45 H2 H4 M2 M3

    55 H2 H4 M2

    75 H1 H3

    90 H1

    K3VL200

    KW 970 1150 1450 1750

    3.7

    5.5

    7.5

    11

    15

    18.5 S1

    22 L4 S1

    30 L2 L3 L5

    37 M3 L1 L3

    45 M1 M3 L2

    55 H5 M1 M3

    75 H1 H3 H6

    90

    110

    132

    H1 H4

    H2

    S2

    L5

    L3

    L2

    M2

    H6

    H4

    H2

    S-rating Springs

    Please contact Kawasaki

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    43/185

    Installation

    Recommended Pump Mounting

    The pump should be mounted horizontally with the case drain piping initially rising above the level of the

    pump before continuing to the tank as shown in the illustration below. Do not connect the drain line to

    the suction line.

    The uppermost drain port should be used and the drain piping should be equal or larger in size than the

    drain port to minimise pressure in the pump case. The pump case pressure should not exceed 1 bar as

    shown in the illustration below. (Peak pressure should never exceed 4 bar.)

    Pumps Industrial Products

    Drain line

    “Goose neck” configuration is required, this prevents direct drop of oil level in the pump case.

      Cautions

      A) Suction and drain pipes must be immersed by 200mm

    minimum from the lowest oil level under operating conditions.

      B) Height from the oil level to the centre of the shaft must be

    within 1m.

      C) The oil in the pump case must be refilled when the pump

      has not been operated for one month or longer.

    4 bar (peak)

    1 bar 

    (normal)

    0.1 sec

    P

    Mounting the Pump Above the Tank

    Suction line

    200mmminimum

    depth

    200mmminimum

    depth  w

       i   t   h   i  n   1  m

       M  u  s

       t   b  e

       h   i  g   h  e  r

       t   h  a  n

       t  o  p  o

       f   P  u  m  p

       C  a  s  e

    200mmminimum

    depth

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    44/185

    Installation (continued)

    Mounting the Pump Vertically (shaft up)

    For applications requiring vertical installation (shaft up) please remove the air bleed plug and connect

    piping as shown in the illustration below.

    The oil level in the tank should be higher than the pump-mounting flange as shown in illustration [a]

    below. If the oil level in the tank is lower than the pump mounting flange then forced lubrication is

    required through the air bleed port 1 ~ 2 l/min.

    When installing the pump in the tank and submerged in the oil, open the drain port and air bleed port to

    provide adequate lubrication to the internal components.

    When installing the pump outside the tank run piping for the drain and air bleed ports to tank (see

    illustration [c]). If the drain or air bleed piping rise above the level of oil (see illustration [b]) fill the lines

    with oil before operation.motor to your national standard is not exceeded.

    Pumps Industrial Products

     A check valve with cracking pressure of 0.1 bar should be fitted to the case drain line as shown.

    Recommended Kawasaki check valves are as follows: (refer to Kawasaki industrial valve

    information - data sheet C1001)

    pipe for air bleeding

    min. oil level

    air bleeder plug port

    drain portpipe for draining

    Dr 

    T

    TDr 

    Dr  Dr 

    [c][b][a]

    check valvecracking pressure

    0.1 bar 

    oiloil

    Model

    K3VL45/60

    K3VL80

    K3VL112

    K3VL140

    K3VL200

    Recommended Kawasaki check valve

    C10G – 10/01-*

    C15G – 10/01-*

    C15G – 10/01-*

    C15G – 10/01-*

    C15G – 10/01-*

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    45/185

    datums

    LP1

    L1

    LA1’

    LA2’

    LP2’

    LP3’

    LA1

    LP2

    MP2MP1 MP3

    LA2L2

    L2 L3

    dial gauge (reading a)

    δ =a/2 0.025mm

    dial gauge (reading b)

    α=SIN-1 (b/D)

    0.2°

       δ

          D

        α

    datums

    b

    MA2MA1

    Drive Shaft Coupling

    Use a flexible coupling to connect the pump shaft to an engine flywheel or electric motor shaft.

     Alignment should be within 0.05mm TIR as shown in the illustration below.

    Do not apply any radial or axial loading to the pump shaft. For applications where radial or side loads

    exist please contact Kawasaki Precision Machinery (UK) Ltd. for recommendations.

    Do not force the coupling on or off the pump shaft. Use the threaded hole in the end of the pump shaft

    to fix or remove the coupling.

    Pumps Industrial Products

    For engine drives a split type pinch bolt drive flange and flexible coupling is recommended.

    Through Drive Limitations

     Apart from predefined maximum throughput limitations, one must also ensure that to prevent a possible

    excessive bending moment occurring that the maximum combined bending moment of the combination

    is not exceeded as determined in the following expression

    MPX = mass of pump [kg]

    LPX = length of pump [mm]

    Lx = distance of CofG from pump mounting face [mm]

    MAX = mass of adaptor kit [kg]LAX = width of adaptor kit [mm]

    Bending Moment = ((L1.mP1) + (LA1’.mA1) + (LP2’.mP2) +(LA2’.mA2) +LP3’.mP3) +…)/102[Nm]

      ((L1.mP1)

      + (LP1+(LA1/2)).mA1

      + (LP1+LA1+L2).mP2

      + (LP1+LA1+LP2(LA2/2)).mA2)

      + (LP1+LA1+LP2+LA2).mP3)  +……)/102

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    46/185

    Through Drive Limitations (continued)

    Electrical Displacement Control Appl ication

    The standard minimum flow setting for the K3VL pump is 0.5-3.0% of the maximum pump delivery. The

    pumps minimum displacement stop can be modified if a greater minimum flow rate is required. In order

    for the electronic displacement control to function, a minimum pilot pressure for 40 bar must be supplied

    to the Psv port on the regulator. A gear pump attached to the rear of the K3VL pump or an external

    pressure source can be used to provide the required pilot pressure.

    Proportional Pressure Reducing Valve Specifi cation

    Maximum Pilot Pressure : 50 bar If higher pressure required contact KPMMax Flow : 10 l/min

    Hydraulic oil : Mineral oil

    Oil temp range : -20~+90°C

    Viscosity range : 5~500 cst

     Allowable contamination : NAS grade 10 and below

    Electrical specifications,

    Rated current : 700 mA

    Recommended dither : 80 Hz / 200 mAp-p

    Coil resistance : 17.5 (at 20°C)

     Ambient temperature range : -30~+80°C

    Water resistance : According to JIS D 0203 S2

    Pumps Industrial Products

    Pump overall length [mm] (Lp)

      Single Stock

    Pump Pump Pump

    Size Type “0” Type “S”45/60 244 244

    80 272 272

    112/140 308 308

    200 359 359

    Pump approximate weight [kg] (Mp)

      Without torque limiter With torque limiter 

      Single Stock Single Stock

    Pump Pump Pump Pump Pump

    Size Type “0” Type “S” Type “0” Type “S”

    45/60 25 28 27 30

    80 35 38 37 40112/140 65 69 67 71

    200 95 103 97 105

    Pump CofG from mount [mm] (L)

      Single Stock

    Pump Pump Pump

    Size Type “0” Type “S”

    45/60 120 120

    80 130 130

    112/140 150 150

    200 190 190

    Pump

    Size

    45/60

    80

    112/140

    200

    Maximum Permisable

    Bending Moment (Nm)

    137

    244

    462

    930

     Adaptor Ki ts weight (Ma) & Wid th (La)

    Pumpsize

    45/60

     Adaptor Kit

    Weight(Max)

    Width(Lax)

    SAE “A” 0 0

    SAE “B” & “BB” 2 20

    80

    SAE “A” 0 0

    SAE “B” & “BB” 3 20

    SAE “C” 4 24.5

    SAE “A” 0 0

    SAE “B” & “BB” 3 25

    SAE “C” & “CC” 5 30

    SAE “D” 10 43

    112& 140

    SAE “A” 1 6

    SAE “B” & “BB” 8 25

    SAE “C” & “CC” 8 30

    SAE “D” 10 38

    SAE “E” 15 38

    200

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    47/185

    Unit Dimensions (continued)

    Electrical Displacement Control

    Pumps Industrial Products

    G

    F

     ACB

    Pc

    ED

    PsvPsv

    Pump Size

    Installation Dimensions (mm)

    K3VL45/60 21

     A

    K3VL80

    K3VL112/140

    K3VL200

    25

    38

    57

    52

    B

    59

    64

    61

    90

    C

    83

    78

    80

    187

    D

    202

    244

    258

    157

    E

    172

    214

    229

    226

    F

    233

    247

    257

    210

    G

    217

    231

    249

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    48/185

    Unit Dimensions (continued)

    Pumps Industrial Products

    Unloading valve module (Type N,M)

    K3VL45-60

    K3VL80

    K3VL112/140

    K3VL200

     A

    169

    169

    202

    212

    B

    155

    166

    190

    205

    Proportional pressure module (*V)

    K3VL45-60

    K3VL80

    K3VL112/140

    K3VL200

     A

    179

    179

    212

    222

    B

    233

    244

    280

    295

     A: Distance between the centre line of the pump and the top of the bolt head for the cut off regulator.

    B: Distance between the centre line of the pump and top of the solenoid valve.

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    49/185

    Unit Dimensions

    K3VL45/60 Installation

    K3VL45 with Cut-Off / Load Sense Control

    & Torque Limit Module (Clockwise Rotation)

    Pumps Industrial Products

    See Torque Limit Detail

    and Adjustment

    See Max. Flow Adjustment Detail

     Adjustment screw for 

    horsepower setting

     Adjustment screw for 

    differential pressure

     Adjustment screw

    for cut-off pressure

    See PortDetails

    See PortDetails

    119

    154

    160

    218

    184

    1   4   . 3   

    1   

    4   . 3   

    91

    ø38ø25

     A

    91

    184

    26.2 ±0.2

       5   2

     .   4   ±   0

     .   2

    13

    35.7 ±0.2

       6   9

     .   8   ±   0

     .   2

       7   3

       1

       6   5   7

       0

       7   0

      ø   9   0

       1   4   4   4

       0

       4   0

       8   0

       8   0

       9   9   8

       9

       5   5

    6.5

    PLPC

    PLPC

    PLPCPLPCPLPC

    Tair Tair 

    4     5      °     

    4     5      °      Dr 

    Dr 

    Dr 

    Dr 

    B

     A

    Dr 

    Dr 

    B

    B

     A

    Note

    for counter clockwise rotation,the suction port “B” and the

    delivery port “A” are reversed

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    50/185

    Unit Dimensions (continued)

    K3VL45/60 Mounting Flange and Shaft Options

    Pumps Industrial Products

       ø    1    4    6

       ø    1

        4     0

    SAE "B" 2 hole

    SAE J744-101-2

    SAE "BB" 30° Involute Spline Shaft

    SAE J744-25-4 15T 16/32 DP

    SAE "BB" Straight Shaft

    SAE J744-25-1

    Shaft end

    ISO 3019/2-G25N

    Flange

    ISO 3019/2-100A2HW

    9.7

    52

    38

    19

    38

    32

    M8

    25

    42

    36

    M8

    19

    25

      ø   2   4

     .   9   8   1

    33

    46

      ø   1   0   1

     .   6   h   7

       0 -   0 .   0

       3   5

      ø   1   0   0   h   8

       0 -   0 .   0

       5   4

      ø   2   5

     .   4   0 -   0

     .   0   5

       6   3

     .   5   +   0

     .   0   3

       0

       2   8

     .   1   ±   0

     .   1   3

    9 +0.50

      ø   2   8

       0 -   0

     .   3

      ø

       8   0 -   0

     .   0   3   6

      ø   2   5   j   6

       +   0

     .   0   0   9

      -   0 .   0   0

       4

    SAE Type ISO Type

    SAE Spline Shaft SAE Straight Shaft

    ISO Straight Shaft

  • 8/19/2019 COMOSO Fluid Power SID Division Power Unit Start Up Manual

    51/185

    Unit Dimensions (continued)

    K3VL45/60 Rear Por t

    Pumps Industrial Products

    PLPCPLPC