chapter 9-design of services final edition_24!11!2011

Upload: umesh-chamara

Post on 06-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    1/44

    M-City Development Project Final Report

    1

    9. Design of Services9.1

    Design of Vertical and Horizontal Circulation Systems

    9.1.1 IntroductionNormally buildings must have corridors and stairways sufficiently wide to cope with the pedestrian

    traffic. But in multistory buildings (high-rise buildings) in addition to that, there are lifts (elevators)

    and sometimes escalators and moving walkways.

    There are several types of lifts available for different purposes. In high rise buildings rather than the

    passenger lifts there are service lifts also available. In here there are three types of high-rise buildings

    available. Those are,

    1. Residential Tower2. Office Complex3. Shopping Complex

    Therefore three different buildings have separate vertical and horizontal circulation systems. Those are

    indicated below.

    Table 9-1: Different Types of Circulation Systems

    Type of Building Types of Circulation Systems

    Residential Lifts, Stairway

    Office Complex Lifts, Stairway

    Shopping Complex Lifts, Stairway, Escalator

    To design of lifts we are using soft zoning for all of the 3 buildings. Therefore all the lifts will serve

    every floor in their particular building.

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    2/44

    M-City Development Project Final Report

    2

    9.1.2 Residential Tower9.1.2.1Lift Design CalculationAssumptions

    Basement height is 4.5m Parking floor height is 2.7m Additional floor height is 2.4m (This is used where the transfer plate is located) Floor height of other floors 3.6m Midrange type apartment Population density is 2 per bedroom (Table 25)

    Number of 6 apartment floors = Number of 2 bedroom houses =

    =

    Number of 4 apartment floors =

    Number of 3 bedroom houses = =

    Number of occupants in a bedroom =

    Total number of bedrooms = =

    Total Number of population in Residential Building =

    Total Number of floors to be served =

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    3/44

    M-City Development Project Final Report

    3

    Lift system is designed for 5 minutes peak capacity.

    % of population handles in 5 minutes = 6% (Table 25.5)

    # Of population handle to be in 5 minutes = =

    Average interval = Capacity of a lift car = Elevator speed = (Table 25.4)Round Trip Time = (Figure 25.7.2)(Round trip time is based on 3.6m building height. Therefore correction must be done)

    Correction of RTT =

    =

    Corrected RTT = # of lifts required =

    =

    =

    Since the building height is greater than the 18m have to provide a fire fighting lift (service lift)

    according to building regulations. (BS 5588-5 : Fire precautions in the design, construction and use of

    buildings)

    Therefore rather than the 3 passenger lifts additional service lift is same as the passenger lift. Lift

    arrangement is indicated in the next page.

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    4/44

    M-City Development Project Final Report

    4

    Figure 9-1: Lift Arrangement of Residential Tower

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    5/44

    M-City Development Project Final Report

    5

    9.1.2.2Stairway Design Calculation

    Rise and thread of the stairs are taken as 180mm and 230mm respectively.Floor to floor height =

    of steps needed floor to floor =

    = As the numbers of steps are more than the recommended value for a single flight, 2 flights of

    10 steps are used.

    Width of the flight is taken as 1.0m. Therefore depth of the landing is selected as 0.9m(lessthan width of the flight)

    (Building services hand book, 5th edition, Fred Hall and Roger Greeno)

    Let angle of the flight to the horizontal to be :

    Check for the angle ;

    ( )

    ( )

    Therefore angle is of satisfactory value and design was done accurately.

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    6/44

    M-City Development Project Final Report

    6

    Figure 9-2: Side View of a Residential Building Stairway

    9.1.3

    Office Complex

    9.1.3.1Lift Design CalculationAssumptions

    Floor to floor height is 3.6m Area allocated per one person is 10m2 Building type is investment, downtown Service core is 25% from the total area

    Note: Calculation procedure is same as the above (Lift design calculation of Residential Tower).

    Therefore it is not shown in here. Calculation is indicated in Annex.

    # of lifts required Since the building height is greater than the 18m have to provide a fire fighting lift (service lift)

    according to building regulations. (BS 5588-5 : Fire precautions in the design, construction and use of

    buildings)

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    7/44

    M-City Development Project Final Report

    7

    Therefore rather than the 2 passenger lifts additional service lift which is same size as the passenger

    lift. Lift arrangement is indicated in the next page.

    Figure 9-3: Lift Arrangement of Office Complex

    9.1.3.2Stairway Design Calculation

    Note: Calculation procedure is same as the above (Stairway design calculation of Residential Tower).

    Therefore it is not shown in here. Calculation is indicated in Annex.

    9.1.4 Shopping Complex9.1.4.1Service LiftIn a shopping complex we are using a service lift to transport the goods for upper floors. Dimensions

    of the lift indicate in next figure.

    Operational speed 2.5m/s Shaft width 1.8m Shaft depth 2.1m Shaft pit depth 2.8m

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    8/44

    M-City Development Project Final Report

    8

    Shaft head height 5m Minimum area of lift motor room 14m2 Lift car width 1100mm Lift car depth 1400mm Clear height of lift car 2200mm

    Figure 9-4 : Lift Arrangement of Shopping Complex

    9.1.4.2Escalator DesignEscalators are moving stairs used to convey people between floor levels. The maximum carryingcapacity depends on the step width and conveyor speed.

    Step width = People per step = Speed of lift =

    Escalator capacity formula to estimate the number of persons (N) moved per hour, (Building serviceshand book, 5th edition, Fred Hall and Roger Greeno)

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    9/44

    M-City Development Project Final Report

    9

    PNumber of person per step

    VSpeed of travel (m/s)

    Angle of incline

    LLength of each step (m)

    Here we used cross over escalator to move up. Cross section of the escalator is indicated in below.

    Figure 9-5 : Cross Section of the Escalator

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    10/44

    M-City Development Project Final Report

    10

    9.1.4.3Stairway Design Calculation

    Note: Calculation procedure is same as the above (Stairway design calculation of Residential Tower).

    Therefore it is not shown in here. Calculation is indicated in Annex.

    9.2 Design of Sanitary Appliances9.2.1 Office Tower9.2.1.1Sanitary Appliances for Ground, 1st, 2nd, 3rd, 4th & 5th floorsSanitary appliances mainly used in public area,

    1. WCs2. Urinals3. Lavatory Basins4. Cleaners Sinks

    Assumptions

    10m2 need per person Male to female ratio is 60:40 Service area is about 20% Ground floor consists of reception area. It is also consider as the office area.

    Total usable floor area =

    # of population per floor = = # of males = # of females = Therefore, these are the selected sanitary appliances for 1st, 2nd, 3rd, 4th & 5th floors.

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    11/44

    M-City Development Project Final Report

    11

    Table 9-2: Sanitary Appliances required for 1st to 5th floors (Office Tower)

    Types of

    Appliances

    Male Female

    WC 2 2

    Urinals 2 -

    Lavatory Basin 2 2

    Cleaners Sink 1 1

    (Ref: Table 2- Metric Hand Book Planning and Design Data)

    Figure 9-6 : Sanitary Arrangement of 1st to 5th floors in Office Complex

    Provide an additional sanitary appliances for staff in reception area (Ground Floor CommonArea)

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    12/44

    M-City Development Project Final Report

    12

    Selected sanitary appliances for ground floor,

    Table 9-3: Sanitary Appliances required for ground floor in Office Complex

    Types of

    Appliances

    Male Female

    WC 3 3

    Urinals 3 -

    Lavatory Basin 3 3

    Cleaners Sink 1 1

    9.2.1.2Sanitary Appliances for 6th floor (Top floor)

    Note: Calculation procedure is same as the above (Sanitary appliances calculation for ground to 5 th

    floor of Office Tower). Therefore it is not shown in here. Calculation is indicated in Annex.

    Therefore selected sanitary appliances for top floor,

    Table 9-4: Sanitary Appliances required for top floor in Office Complex

    Types of

    Appliances

    Male Female

    Confer. Cafeteria Total Confer. Cafeteria Total

    WC 2 1 3 2 2 4

    Urinals 2 1 3 - - -

    Lavatory Basin 2 1 3 2 2 4

    Cleaners Sink 1 - 1 1 - 1

    Note: Sanitary arrangement of top floor is indicated in Annex.

    9.2.2 Residential Tower9.2.2.1Sanitary Appliances for 2 bedroom apartment

    Each apartment consists of master bathroom and common bathroom.

    Following chart indicate the types of appliances used for different bathrooms

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    13/44

    M-City Development Project Final Report

    13

    Table 9-5: Sanitary Appliances needed in Residential Tower-2 bed room apartment

    Master Bath room Common Bath room

    Shower Shower

    Bath tub WC

    WC Wash Basin

    Wash Basin Washing Machine

    Figure 9-7 : Sanitary Arrangement of Master Bath room

    Figure 9-8 : Sanitary Arrangement of Common Bath room

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    14/44

    M-City Development Project Final Report

    14

    9.2.2.2Sanitary Appliances for 3 bedroom apartment

    Note: Calculation procedure is same as the above (Sanitary appliances calculation for 2 bed room

    apartment). Therefore it is not shown in here. Calculation is indicated in Annex.

    Arrangements of bathrooms are same as the arrangement of bathrooms in 2 bed room apartments.

    Arrangement is indicated in the Annex.

    9.2.2.3Sanitary Appliances for 4th floor (Swimming Pool and Gym)Note: Calculation procedure is same as the above (Sanitary appliances calculation for office tower).

    Therefore it is not shown in here. Calculation is indicated in Annex.

    Therefore selected sanitary appliances for Gym,

    Table 9-6: Sanitary Appliances for 4th floor in Residential Tower-Gym

    Types of

    Appliances

    Male Female

    WC 2 2

    Urinals 2 -Lavatory Basin 3 2

    Cleaners Sink 3 2

    ( Ref: Metric Handbook Planning & Design Data)

    Therefore selected sanitary appliances for swimming pool area,

    Table 9-7: Sanitary Appliances for 4th floor in Residential Tower-Swimming Pool

    Types of

    Appliances

    Male Female

    WC 3 5

    Urinals 3 -

    Lavatory Basin 4 3

    Cleaners Sink 4 3

    ( Ref: Metric Handbook Planning & Design Data)

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    15/44

    M-City Development Project Final Report

    15

    9.2.2.4Sanitary Appliances for Ground floor (Reception Area)Ground floor has a recreation area. Therefore in reception area has to provide sanitary facilities for

    staff.

    Therefore selected sanitary appliances for Ground floor,

    Table 9-8: Sanitary Appliances for Ground floor in Residential Tower

    Types of

    Appliances

    Male Female

    WC 1 1

    Urinals 1 -

    Wash Basin 1 1

    ( Ref: Metric Handbook Planning & Design Data)

    9.2.3 Shopping ComplexSanitary appliances mainly used in public area,

    1. WCs2. Urinals3. Lavatory Basins4. Cleaners Sinks

    9.2.3.1Sanitary Appliances for Shopping Complex 1th floorAssumptions

    Basement and ground floor reserved for parking. There isnt any sanitary items installed in thisarea

    Male to female ratio is 50:50 Area allocated for a person is 6m2 Service area is about 25% from the total area

    Total area of first floor = Usable area of first floor =

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    16/44

    M-City Development Project Final Report

    16

    =

    # of customers in first floor = =

    # of males = # of females = Therefore selected sanitary appliances for 1st floor,

    Table 9-9: Sanitary Appliances for 1st floor in Shopping Complex

    Types of

    Appliances

    Male Female

    WC 2 3

    Urinals 2 -

    Lavatory Basin 2 3

    Cleaners Sink 1 1

    ( Ref: Table 2-Metric Handbook Planning & Design Data)

    9.2.3.2Sanitary Appliances for Shopping Complex 2nd floorNote: Calculation procedure is same as the above (Sanitary appliances calculation for Shopping

    Complex 1st floor). Therefore it is not shown in here. Calculation is indicated in Annex.

    Therefore selected sanitary appliances for second floor,

    Table 9-10: Sanitary Appliances for 2nd floor in Shopping Complex

    Types of

    Appliances

    Male Female

    Shopping Cinema Total Shopping Cinema Total

    WC 2 2 4 3 4 7

    Urinals 2 2 4 - - -

    Lavatory Basin 2 2 4 3 3 6

    Cleaners Sink 1 - 1 1 - 1

    ( Ref: Table 2-Metric Handbook Planning & Design Data)

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    17/44

    M-City Development Project Final Report

    17

    9.2.3.3Sanitary Appliances for Shopping Complex 3rd floorNote: Calculation procedure is same as the above (Sanitary appliances calculation for Shopping

    Complex 1st floor). Therefore it is not shown in here. Calculation is indicated in Annex.

    Therefore selected sanitary appliances for third floor,

    Table 9-11 Sanitary Appliances for 3rd floor in Shopping Complex

    Types of

    Appliances

    Male Female

    Shopping Restaurant Total Shopping Restaurant Total

    WC 1 2 3 1 6 7

    Urinals 1 4 5 - - -

    Lavatory Basin 1 3 4 1 6 7

    Cleaners Sink 1 - 1 1 - 1

    ( Ref: Table 2-Metric Handbook Planning & Design Data)

    9.3 Design of Water Supply SystemWater sump is designed to locate at basement level with two day storage. Same pump is used to

    distribute the water for three buildings. And another domestic water tank is located at the roof top

    level in order to provide the water to the buildings. In here we did not go for an intermediate water

    tanks. Therefore we can save that space also.

    But when we supply the water to the lower floors from the roof top level domestic tank pressure

    develops will be higher when the head increased. Therefore in order to control the pressure we have

    located several break water pressure valves at every 8 floors.

    9.3.1 Calculation of Water Requirement for Residential BuildingPer capital demand of water = Total population at building =

    Water Requirement of Upper 7 floors# of occupants per bedroom =

    # of bedrooms per apartment =

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    18/44

    M-City Development Project Final Report

    18

    # of apartment per floor = # of floors = Total population =

    = Required water storage =

    = Note: Calculation procedure for water requirement of other floors of the residential building is same

    as above.(water requirement calculation for upper 7 floors). Therefore, calculations of water

    requirement of other floors are indicated in Annex. Here indicate the final values only.

    Table 9-12: Water Requirement of Residential Building

    Type of Floors Water Requirement (m /day)

    19t

    25t

    30

    11t

    18t

    35

    3

    rd

    10

    th

    351

    st,2

    nd, Gym & Parking 16

    Total 116

    Therefore Total water requirement of Residential Tower per day = 9.3.2 Calculation of Water requirement for Office ComplexAssumptions

    Water required per person is 45l/day in office area Water required per person is 20l/day in conference hall Water required per person (customer) is 10l/day in cafeteria Water required per person (staff member) is 20l/day in cafeteria

    Common Area (Ground Floor),

    Usable floor area of ground floor =

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    19/44

    M-City Development Project Final Report

    19

    =

    Expected population = =

    Water requirement in common area = =

    Note: Calculation procedure for water requirement of other floors of the office complex is same as

    above.(water requirement calculation for Ground floor). Therefore, calculations of water requirement

    of other floors are indicated in Annex. Here indicate the final values only.

    Table 9-13: Water Requirement of Office Complex

    Type of Floors Water Requirement (m3/day)

    1st 2.5

    2nd

    2.8

    3r

    3.0

    4th

    3.0

    5th

    3.0

    6t

    3.6

    Total 20.0

    Total water requirement in Office Complex 9.3.3 Calculation of Water requirement for Shopping ComplexAssumptions

    Water required per staff member is 45l/day Water required per customer is 10l/day Water required per meal is 7l/meal Staff to customer ratio is 20:80 # of seats available in restaurant is 300 5 meals will be served from a seat per day

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    20/44

    M-City Development Project Final Report

    20

    Water requirement for cooking is 20l/ person (person meal) Water sump is designed for 2 days

    First Floor

    Usable area =

    # of population = =

    Water requirement in first floor = =

    Note: Calculation procedure for water requirement of other floors of the Shopping Complex is same

    as above.(water requirement calculation for first floor). Therefore, calculations of water requirement

    of other floors are indicated in Annex. Here indicate the final values only.

    Table 9-14: Water Requirement of Shopping Complex

    Type of Floors Water Requirement (m /day)

    1st 3.4

    2nd

    4.9

    3rd

    42.0

    Total 50.0

    Total water requirement in shopping complex Total water requirement in all 3 buildings =

    = Capacity of the basement water storage tank =

    = 9.4 Design of Above Ground Disposal SystemAll the sanitary appliances could generate a certain quantity of waste water. This has to be disposed

    with due care to ensure habitable conditions within the building. In here all the buildings we are using

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    21/44

    M-City Development Project Final Report

    21

    two pipe systems. Therefore waste water from WCs, urinals is collected to one pipe ( soil stack) and

    waste water from wash basins, sink, kitchens and bath tubs is collected to another pipe which is called

    waste stack.

    Figure 9-9 : Typical Arrangement of Two pipe System

    9.4.1 Calculation for Residential Building9.4.1.1Internal Diameter for TrapsInternal diameter for traps, (Ref: Building Services Handbook-5 th edition-Fred Hall and Roger

    Greeno)

    Table 9-15: Internal Diameter of Traps for Residential Building

    Types of Fitments Trap Size (internal-mm)

    Bath tub 40

    Shower 40

    Water closet (WC) 50

    Wash Basin 32

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    22/44

    M-City Development Project Final Report

    22

    Washing Machine 40

    9.4.1.2Calculation of Diameters of Vertical Stack and Horizontal BranchDischarge units of 3 Bedroom Apartments (7 floors-24th to 30th floor),

    Table 9-16: Discharge units of 3 Bedroom Apartments

    Appliances Discharge Unit

    (per item)

    # of Appliances

    per Floor

    Total Discharge

    Units Per Floor

    Total Discharge

    Units

    WC 7 8 56 392

    Wash Basin 1 8 8 56Shower 1 8 8 56

    Bath tub 6 4 24 168

    Washing Machine 3 4 12 84

    Discharge units of 2 Bedroom Apartments (18 floors-6th to 23rd floor),

    Table 9-17: Discharge units of 2 Bedroom Apartments

    Appliances Discharge Unit

    (per item)

    # of Appliances

    per Floor

    Total Discharge

    Units Per Floor

    Total Discharge

    Units

    WC 7 12 84 1512

    Wash Basin 1 12 12 216

    Shower 1 12 12 216

    Bath tub 6 6 36 648

    Washing Machine 3 6 18 324

    Discharge units of Ground Floor,

    Ground floor has a recreation area. Therefore in reception area, has to provide sanitary facilities for

    staff,

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    23/44

    M-City Development Project Final Report

    23

    Table 9-18: Discharge units of Ground Floor-Residential Tower

    Appliances Discharge Unit

    (per item)

    # of Appliances

    per Floor

    Total Discharge

    Units per Floor

    Total Discharge

    Units

    WC 7 2 14 14

    Wash Basin 1 2 2 2

    Urinals 2 1 2 2

    Discharge units of 4th Floor (Gym and Swimming Pool Area),

    Table 9-19: Discharge units of 4th Floor-Residential Tower

    Appliances Discharge Unit

    (per item)

    # of Appliances

    per Floor

    Total Discharge

    Units per Floor

    Total Discharge

    Units

    WC 14 12 168 168

    Wash Basin 2 12 24 24

    Urinals 2 5 10 10

    Showers 2 12 24 24

    Note: Calculation procedure for total discharge units is indicated in the Annex. Here indicated the

    tabulated form of final values only. As well as the calculation of vertical and horizontal branch pipe

    sizes are indicated in Annex. Here indicate the final values only.

    Table 9-20: Vertical & Horizantal Branch Pipe Sizes of Residential Building

    Type of Pipe Total Discharge

    Units

    Pipe Diameter

    (mm)

    Slope

    Soil Stack Vertical Stack 2098 125 -

    Hoizantal Branch Pipe 150 1:100

    Waste Stack Vertical Stack 1838 125 -

    Hoizantal Branch Pipe 150 1:100

    Vent Pipe (0.5D) - 63 -

    References:

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    24/44

    M-City Development Project Final Report

    24

    BS EN 12056-2 : Gravity drainage systems inside buildings Building Services Handbook : 5th edition

    Figure 9-10 : Section of Above Ground Water Disposal System-Residential Tower

    9.4.2 Calculation for Office Complex9.4.2.1Internal Diameter for TrapsInternal diameter for traps, (Ref: Building Services Handbook-5 th edition-Fred Hall and Roger

    Greeno)

    Table 9-21: Internal Diameter of Traps for Office Complex

    Types of Fitments Trap Size (internal-mm)

    Water closet (WC) 50

    Urinal 40

    Lavatory Basin 32

    Cleaners Sink 40

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    25/44

    M-City Development Project Final Report

    25

    9.4.2.2Calculation of Diameters of Vertical Stack and Horizontal BranchDischarge units of Basement,

    Two taps are fitted in basement area,

    Discharge unit of basement (for waste stack) = Discharge units of Ground floor and1st to 5th floors

    Table 9-22: Discharge units of Ground floor to 5th floors-Office Complex

    Appliances Discharge Unit

    (per item)

    Total # of Appliances Total Discharge Units

    WC 14 28 392

    Urinals 2 12 24

    Lavatory Basin 2 28 56

    Cleaners Sink 14 12 168

    Discharge units of Top floor (6th floor)

    Table 9-23: Discharge units of Top floor-Office Complex

    Appliances Discharge Unit

    (per item)

    Total # of Appliances Total Discharge Units

    WC 14 7 98

    Urinals 2 3 6

    Lavatory Basin 2 7 14

    Cleaners Sink 14 2 28

    Note: Calculation procedure for total discharge units is indicated in the Annex. Here indicated the

    tabulated form of final values only. As well as the calculation of vertical and horizontal branch pipe

    sizes are indicated in Annex. Here indicate the final values only.

    Table 9-24: Vertical & Horizantal Branch Pipe Sizes of Office Complex

    Type of Pipe Total Discharge

    Units

    Pipe Diameter

    (mm)

    Slope

    Soil Stack Vertical Stack 520 100 -

    Hoizantal Branch Pipe 125 1:100

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    26/44

    M-City Development Project Final Report

    26

    Waste Stack Vertical Stack 270 90 -

    Hoizantal Branch Pipe 125 1:100

    Vent Pipe (0.5D) - 50 -

    References:

    BS EN 12056-2 : Gravity drainage systems inside buildings Building Services Handbook : 5th edition

    9.4.3 Calculation for Shopping Complex9.4.3.1Internal Diameter for TrapsInternal diameter for traps, (Ref: Building Services Handbook-5 th edition-Fred Hall and Roger

    Greeno)

    Table 9-25: Internal Diameter of Traps for Shopping Complex

    Types of Fitments Trap Size (internal-mm)

    Water closet (WC) 50

    Urinal 40

    Lavatory Basin 32

    Cleaners Sink 40

    9.4.3.2Calculation of Diameters of Vertical Stack and Horizontal BranchDischarge units of first floor

    Table 9-26: Discharge units of First floor -Shopping Complex

    Appliances Discharge Unit

    (per item)

    Total # of Appliances Total Discharge Units

    WC 14 5 70

    Urinals 2 2 4

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    27/44

    M-City Development Project Final Report

    27

    Lavatory Basin 2 5 10

    Cleaners Sink 14 2 28

    Discharge units of Second floor

    Table 9-27: Discharge units of Second floor -Shopping Complex

    Appliances Discharge Unit

    (per item)

    Total # of Appliances Total Discharge Units

    WC 14 11 154

    Urinals 2 4 8

    Lavatory Basin 2 10 20

    Cleaners Sink 14 2 28

    Discharge units of Third floor

    Table 9-28: Discharge units of Third floor -Shopping Complex

    Appliances Discharge Unit

    (per item)

    Total # of Appliances Total Discharge Units

    WC 14 10 140

    Urinals 2 5 10

    Lavatory Basin 2 11 22

    Cleaners Sink 14 4 56

    Note: Calculation procedure for total discharge units is indicated in the Annex. Here indicated the

    tabulated form of final values only. As well as the calculation of vertical and horizontal branch pipe

    sizes are indicated in Annex. Here indicate the final values only.

    Table 9-29: Vertical & Horizantal Branch Pipe Sizes of Shopping Complex

    Type of Pipe Total Discharge

    Units

    Pipe Diameter

    (mm)

    Slope

    Soil Stack Vertical Stack 386 90 -

    Hoizantal Branch Pipe 125 1:100

    Waste Stack Vertical Stack 164 90 -

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    28/44

    M-City Development Project Final Report

    28

    Hoizantal Branch Pipe 100 1:100

    Vent Pipe (0.5D) - 50 -

    References:

    BS EN 12056-2 : Gravity drainage systems inside buildings Building Services Handbook : 5th edition

    9.5 Below Ground Water Disposal System Wastewater generated from the building is 90% of its daily requirement Sewer waste water capacity is 40% of total generated waste water Total quantity of water used in 14 hours Peak discharge is six times the average discharge

    9.5.1 Residential Tower9.5.1.1Estimation of Sewer Line Characteristics in Residential TowerGenerated waste water capacity =

    = Generated sewer waste quantity =

    Average Discharge = =

    Peak Discharge = =

    Assume,

    Half of the pipe is filled Self-cleansing velocity (V) is

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    29/44

    M-City Development Project Final Report

    29

    If the diameter of pipe D,

    ,

    Where,

    Therefore, we used 150mm diameter pipe.

    Then,

    Where,

    ( )

    150mm diameter pipe with 1:140 inclination pipe is used for the sewer line.9.5.1.2Estimation of Waste Water Line Characteristics in Residential TowerGenerated Total waste water capacity = Generated waste water quantity =

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    30/44

    M-City Development Project Final Report

    30

    Average Discharge =

    = Peak Discharge =

    = Assume,

    Half of the pipe is filled Self-cleansing velocity (V) is

    If the diameter of pipe D,

    ,Where,

    Therefore, we used 150mm diameter pipe.

    Then,

    Where,

    ( )

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    31/44

    M-City Development Project Final Report

    31

    Use 150mm diameter pipe with 1:140 inclination pipe for the waste water line.9.5.2 Office ComplexAssumptions

    Water requirement per person is 45l/day in office area Water requirement per person is 20l/day in conference hall Water requirement per person (customer) is 10l/day in cafeteria Water requirement per person (staff member) is 20l/day in cafeteria

    9.5.2.1Estimation of Sewer Line Characteristics in Office TowerNote: Calculation procedure is same as the above (Estimation of Sewer Line Characteristics in

    Residential Building). Therefore here indicate the final values only. Calculation is indicated in Annex.

    Peak Discharge =

    Use 65mm diameter pipe with 1:60 inclination for the sewer line.9.5.2.2Estimation of Waste Water Line Characteristics in Office TowerNote: Calculation procedure is same as the above (Estimation of Waste Water Line Characteristics in

    Residential Building). Therefore here indicate the final values only. Calculation is indicated in Annex.

    Peak Discharge =

    Use 65mm diameter pipe with 1:60 inclination pipe for the waste water line.

    9.5.3 Shopping ComplexAssumptions

    Staff to customers ratio is 20:80 Water requirement per person (customer) is 10l/day Water requirement per person (staff member) is 45l/day Water requirement for cooking 20l/day

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    32/44

    M-City Development Project Final Report

    32

    Water requirement per meal 7l/day # of seats available in Restaurant 300

    9.5.3.1Estimation of Sewer Line Characteristics in Shopping ComplexNote: Calculation procedure is same as the above (Estimation of Sewer Line Characteristics in

    Residential Building). Therefore here indicate the final values only. Calculation is indicated in Annex.

    Peak Discharge = Use 100mm diameter pipe with 1:90 inclination for the sewer line.

    9.5.3.2Estimation of Waste Water Line Characteristics in Office TowerNote: Calculation procedure is same as the above (Estimation of Waste Water Line Characteristics in

    Residential Building). Therefore here indicate the final values only. Calculation is indicated in Annex.

    Peak Discharge = Use 100mm diameter pipe with 1:90 inclination pipe for the waste water line.9.6 Design of Fire Fighting Services9.6.1 Introduction to Fire Fighting ServicesFirefighting system of a high-rise building can be divided in to mainly in two parts. Those are,

    1) Fire PreventionFire Prevention means the methods we can used to prevent a fire taking place. This includes,

    a. Fire doors, fire wallsthese doors and walls given a rating such as 1 hour, 2 hour, andetc.

    b. Fire meetings, fire education, fire inspection these methods specially used infactories

    2) Fire ManagementFire management means how we can manage the fire after taking place. This can be categorized into 3

    parts.

    1. Fire Detection

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    33/44

    M-City Development Project Final Report

    33

    It has two types of methods. Those are smoke detectors and heat detectors. Heat detectors

    available in two types as: fixed temperature detectors (it detects the temperature rising above a

    pre-defined level) which are the heat detectors going to be used in the emperor building and

    rising temperature detectors. (Detects rate of increasing temperature)

    2. Fire ProtectionThis method includes,

    a. Sprinkler It has a bulb filled with alcohol which is burst at particular temperature.(For the Emperor Tower this temperature is 630) And after burst the bulb it sprays

    water to control fire.

    b. Hose reelHose reel can be handle by single person for small scale of firesc. Wet Riser It is the pipe running vertically through the whole building and which is

    filled with water under pressure. (this cant be handle by normal person but fire fighter

    only)

    d. Breaching inletIt is available at the outside of the building to connect the fire enginedirectly to the fire system of the building

    e. Fire extinguishers 0 these have different color-coded for easy to identified CO2Blackfor oil and electrical fires Foam SpreadsPink/Creamordinary and oil fires WaterRedOrdinary fires Chemical PowderBlueany fire (specially for electrical fires)

    c. EvacuationIn case of fire, it is better to plan the evacuation in high rise building. This includes,

    Fire staircase we have provided staircase in an emergency it can be used forevacuation

    Emergency exit Fire escape plan showing escape route this plan should be displayed normally at

    every floor. It should be shown the way to emergency exit.

    Signboards Sounders Public Announce System

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    34/44

    M-City Development Project Final Report

    34

    9.6.2 Sprinkler SystemFire of the building depends on the usage of the building. According to the usage of the building

    sprinkler system is categorized in to three classes. Such as,

    Extra Light Hazard Ordinary Hazard Extra High Hazard

    9.6.2.1Design of Sprinkler System in Residential Building

    Table 9-30: Hazard Conditions of Residential building

    Floor Number Function Hazard Condition

    Basement Car park + Storage Extra light

    Ground floor to 3r

    floor Car Park Extra light

    4th

    floor Gym + Spa Extra light

    5t

    to 29t

    floor Residential Extra light

    According to the hazard condition we can calculate the S (design spacing of sprinklers) and D

    (distance between rows of sprinklers) values.

    Table 9-31: Design of Sprinkler System in Office Tower

    Hazard Condition

    Extra Light 21 4.5 4.5

    Table 9-32: Hazard Conditions of Office Complex

    Floor Number Function Hazard Condition

    Basement Car parking Extra light

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    35/44

    M-City Development Project Final Report

    35

    Ground floor Common area Extra light

    1st

    to 5t

    floor Office area Extra light

    6t

    floor Conference hall Extra light

    According to the hazard condition we can calculate the S (design spacing of sprinklers) and D

    (distance between rows of sprinklers) values.

    Table 9-33: Dimensions of Sprinkler System in Office Complex

    Hazard Condition

    Extra Light 21 4.5 4.5

    9.6.2.2Design of Sprinkler System in Shopping Complex

    Table 9-34: Hazard Conditions of Shopping Complex

    Floor Number Function Hazard Condition

    Basement + Ground

    floor

    Car parking Extra light

    1st

    to 2nd

    floor Shopping area Ordinary

    3rd

    floor Restaurant + Cinema Ordinary

    According to the hazard condition we can calculate the S (design spacing of sprinklers) and D

    (distance between rows of sprinklers) values.

    Table 9-35: Dimensions of Sprinkler System in Shopping Complex

    Hazard Condition

    Extra Light 21 4.5 4.5

    Ordinary 12 4 3

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    36/44

    M-City Development Project Final Report

    36

    Figure 9-11 : Section of Wet Riser Schematic Diagram

    9.6.3 Hose ReelsHose reels are firefighting equipment for the use as a first aid measure by building occupants. They

    should be located (near stair case), where users are less likely to be endangered by the fire.

    Discharge of a hose reel = Hose reel should supply water at least one hour.

    Tank volume needed = =

    = One hose reel is not enough, when the area of the floor greater than the 800m2. Therefore we have to

    provide two hose reels per floor in apartment complex and shopping mall. But in office complex one

    hose reel is enough per each floor.

    All tanks should be located top of the building.

    Hose reel tank capacity needed,

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    37/44

    M-City Development Project Final Report

    37

    Table 9-36: Hose Reel Tank Capacity Needed

    Building Type Capacity (m3)

    Apartment 4

    Shopping 4

    Office 2

    Figure 9-12 : Section of Hose Reel Schematic Diagram

    9.7 Design of Lighting System9.7.1 Introduction to Lighting System of Residential BuildingLighting is very important in Residential building since it is a major factor related to energy

    requirement of the building. We have to provide adequate lighting with required illumination level to

    the different areas. In here we have three types of options to provide lighting to the Residential

    Building. Those are,

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    38/44

    M-City Development Project Final Report

    38

    1. Use Incandescent Light Bulbs2. Use Compact Fluorescent Lights (CFL)3. Use LED Lighting Systems

    In order to identify the best option we did a comparison between above three lighting systems.

    Table 9-37: Comparison of Three Lighting Systems

    Comparison Factors

    LEDs Incandescent

    Light Bulbs

    CFLs

    Life Span (average) 50000 hours 1200 hours 8000 hours

    Watts of electricity used

    (equivalent to 60 watt bulb)

    6-8 watts 60 watts 13-15 watts

    Kilo-watts of Electricity used

    (30 Incandescent Bulbs per yearequivalent)

    329 KWh/yr 3285 KWh/yr 767 KWh/yr

    Annual Operating Cost

    (30 Incandescent Bulbs per yearequivalent)

    $32.85/yr $328.59/yr $76.85/yr

    Contains the TOXIC Mercury No No Yes

    Carbon Dioxide Emissions

    (30 bulbs per year)

    451 pounds/yr 4500 pounds/yr 1051 pounds/yr

    Heat Emitted 3.4 btus/hour 85 btus/hour 30btus/hour

    Durability Very Durable Not very durable Not very durable

    Therefore finally after comparison we decided to go for LED Lighting systems. Different areas need

    different illumination levels according to next table. (Ref: CIBSE (Chartered Institute of Building

    Services Engineers) Code for Lighting Part 2 (2002)

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    39/44

    M-City Development Project Final Report

    39

    Table 9-38: Illumination Level of Different areas

    Area Illumination Level (lux)

    Living 250

    Bed Room 50

    Kitchen 250

    Bathroom 150

    Corridor and Stairs 100

    Dinning 200

    Following indicate the different illumination levels of different types of LEDs.

    Table 9-39: Illumination level of three lighting Systems

    9.7.2 Calculation of Number of Lamps required in different areasFollowing indicate the sample calculation for number of lamps required in living area of 2 bedroom

    apartments.

    Ref: Building Services Handbook

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    40/44

    M-City Development Project Final Report

    40

    Where,

    N = number of lamps

    E = average illuminance on the working plane (lux)

    A = area of the working plane (m2)

    F = flux from one lamp (lumens)

    U = utilization factor

    M = maintenance factor

    Assumptions:

    Utilization factor is 0.5 Maintenance factor is 0.8 Used 25W LEDs with 2600 lumens Area of living 20.4m2 Illumination level of living is 300

    Therefore number of lamps required in living area of 2 bedroom apartments.

    Likewise we can calculate the amount of LEDs required for the entire Residential Building. Following

    tables indicate the amount of LEDs required for the apartments.

    Lamps Required in 2 Bed Room Apartments

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    41/44

    M-City Development Project Final Report

    41

    Table 9-40: LED Lamps required in 2 Bed room apartments

    2 Bed Room

    Apartment

    Area Type Area (m2) Illumination

    Level(lux)

    Number Of

    Lamps

    Master Bed Room 13 50 1

    Master Bath Room 5 150 1

    Bed Room 12 50 1

    Bath Room 4 150 1

    Living 20 250 5

    Dinning 9 200 2

    Kitchen 9 250 2

    Corridor & Lobby 10 100 1

    TV Longe 8 200 2

    Total 14

    Total number of Lamps required 5th -22nd floors=

    per floor

    = Lamps Required in 3 Bed Room Apartments

    Table 9-41: LED Lamps required in 3 Bed room apartments

    3 Bed RoomApartment

    Area Type Area (m2) IlluminationLevel(lux)

    Number OfLamps

    Master Bed Room 20 50 1Master Bath Room 7 150 1

    Bed Room 1 18 50 1

    Bath Room 7 150 1

    Bed Room 2 13 50 1

    Living 23 250 6

    Dinning 14 200 3

    Kitchen 12 250 3

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    42/44

    M-City Development Project Final Report

    42

    Corridor & Lobby 11 100 1

    TV Longe 10 200 2

    Total 19

    Total number of Lamps required 23rd -29th floors= per floor =

    9.7.3 Calculation of Energy Required for Lighting Total amount of lamps required =

    Energy required for lighting =

    = w=

    After calculating the energy requirement for lighting we can calculate the energy requirement for

    entire Residential Building approximately. Average energy consumption in a Residential building is

    indicated below.

    Figure 9-13 : Residential Site Energy Consumption

    Space Cooling

    45%

    Water Heating

    18%

    Space Heating

    9%

    Lighting

    6%

    Electronics

    5%

    Cooking

    4%

    Refrigeration

    4%

    Wet Cleaning

    3%Computers

    1%

    Other

    3%

    Adjust to seds

    2%

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    43/44

    M-City Development Project Final Report

    43

    This is design for America. But Sri Lanka is tropical country. Since our site is located in Nawala area

    space heating is not required. Due to Sri Lanka is tropical country we decided to used 45% for space

    cooling.

    Note: Here indicate the Energy requirement in tabulated form only. Calculations are indicating in the

    Annex.

    Table 9-42: Energy Requirement of the Building

    Requirement Energy Required (kW)

    Space Cooling Water Heating

    Lighting Electronics Cooking Refrigeration Wet cleaning Computers Others

    Total

  • 8/3/2019 Chapter 9-Design of Services Final Edition_24!11!2011

    44/44

    M-City Development Project Final Report

    9.8 Design of Gondola Window Cleaning SystemIt is very difficult task to cleaning the windows in high rise buildings. Therefore to do that, we have

    provided a Gondola Window Cleaning system to our residential building.

    Figure 9-14 : Image of Gondola window Cleaning System

    Figure 9-15 : Section of Gondola Window Cleaning System-Autocad Drawing