Centrifugal Pump Isolation Hazards:
Case Histories and Prevention Methodologies
Peter N. LodalEastman Chemical Company
![Page 2: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/2.jpg)
What is a B.L.E.V.E.?
Boiling
Liquid
Expanding
Vapor
Explosion
Boiling liquid expanding vapor explosion, often referred to by the acronym BLEVE, is a phenomenon which occurs when a vessel containing a pressurized liquid substantially above its boiling point is ruptured, releasing the contents explosively.
![Page 3: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/3.jpg)
3
Heat
P
Liquid
Vapor
PressureIncreases
TemperatureIncreases
T
What Causes a BLEVE?
ClosedSystem
![Page 4: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/4.jpg)
4
Heat
P
Liquid
Vapor
PressureRapidlyDecreases
LiquidFlashVaporizes
VesselRuptures
1600xVapor
Volumetric
Expansion
![Page 5: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/5.jpg)
What can BLEVE?
Tanks• External pool fire
• If flammable, fireball is enormous
Hot water heaters• BLEVE does not necessarily involve flammables
Drums• External pool fire 15-20 minutes
• Launch
Cylinders• Launch like a missile
Railcars• External pool fire
• Launch over 1 mile in the air
Pumps• Running isolated (suction & discharge closed)
• As little as 20-30 minutes
![Page 6: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/6.jpg)
Case 1
Sludge Pump
![Page 7: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/7.jpg)
7
Case 1:Description of Incident
A loud sound was heard and a 20 foot long white to whitish-gray cloud was seen in the area of Sludge Pump. Inspection showed Pump was fractured and small pieces were found as far away as 35 feet. Pump suction and discharge valves were found closed and the local pump run switch was found in the auto position.
![Page 8: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/8.jpg)
8
![Page 9: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/9.jpg)
9
![Page 10: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/10.jpg)
10
![Page 11: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/11.jpg)
11
![Page 12: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/12.jpg)
12
Case 1: Data
Pump suction & discharge valves were closed. Pump local hand switch was set in Auto. DCS was set telling the pump to run. Electrical evaluation of the pump power breaker
indicated the pump was running until some “incident” tripped the breaker.
![Page 13: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/13.jpg)
13
Case 1: Data (continued)
Pump fracture analysis suggests approximately 200-210 psig pressure was generated.
Pegged pressure gauge on pump discharge suggests pressure reached 200-210 psig.
Vapor pressure data suggests temperature required to reach 200-210 psig was approximately 230 C.
![Page 14: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/14.jpg)
14
Case 1: Data (continued)
Differential Scanning Calorimeter (DSC) on actual pump sample showed no exotherm until 376 C.
Autoignition temperature on actual pump sample was measured at 485 C.
![Page 15: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/15.jpg)
15
Case 1:Conclusions
No evidence of deflagration.Material does not appear to be thermally
sensitive at our temperatures. Autoignition does not appear to be credible.Root Cause -- Pump was inadvertently started by
DCS and left running with process material blocked into the pump head which built up enough temperature to raise the vapor pressure to 200-210 psig which caused the pump to fail.
![Page 16: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/16.jpg)
Case 2
Caustic Pump
![Page 17: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/17.jpg)
17
![Page 18: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/18.jpg)
18
![Page 19: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/19.jpg)
19
![Page 20: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/20.jpg)
20
![Page 21: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/21.jpg)
21
![Page 22: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/22.jpg)
22
![Page 23: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/23.jpg)
23
![Page 24: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/24.jpg)
24
![Page 25: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/25.jpg)
25
![Page 26: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/26.jpg)
26
Case 2: Data
Pump suction & discharge valves were closed. Pump was inadvertently started when operator threw
a hand switch thinking it was for a ventilation fan.
![Page 27: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/27.jpg)
27
Case 2: Conclusions
Material was non-flammable, so deflagration was ruled out.
Root Cause = Pump was inadvertently started and left running with process material blocked into the pump head which built up enough temperature to raise the pressure to a point which caused the pump to fail.
![Page 28: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/28.jpg)
Case 3
Condensate Pump
![Page 29: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/29.jpg)
29
![Page 30: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/30.jpg)
30
![Page 31: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/31.jpg)
31
![Page 32: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/32.jpg)
32
![Page 33: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/33.jpg)
33
![Page 34: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/34.jpg)
34
![Page 35: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/35.jpg)
35
Case 3: Data
Pump suction & discharge valves were closed during a power interruption and system shutdown.
Pump was started remotely 3 days after the shutdown.
![Page 36: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/36.jpg)
36
Case 3: Conclusions
Material was non-flammable, so deflagration was ruled out.
One 5-lb piece of the casing was found 400 feet from the pump installation.
Root Cause = Pump was started automatically and left running with condensate blocked into the pump head which built up enough temperature to raise the pressure to a point which caused the pump to fail.
![Page 37: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/37.jpg)
37
Common Features
1. Complete Isolation (Suction and Discharge Blocked), not deadheaded (discharge only blocked).
2. Fluid Filled
3. Remote Start Capability
4. Seal Failure did not provide adequate pressure relief
![Page 38: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/38.jpg)
38
Case Pump Summaries
Case 1 3500 RPM, 15 HP,140 psig
Organic Acids & decomposition solids
Case 2 1750 RPM, 10 HP,55 psig
50% SodiumHydroxide solution
Case 3 2600 GPM, 75 HP,110 psig
Steam condensate
![Page 39: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/39.jpg)
39
Conclusions
Pump Explosions can occur with completely isolated fluids, even when those fluids are non-flammable
Damage potential increases as horsepower increases (increasing inability to dissipate energy)
Seal failure as a relief mechanism is NOT a safe assumption
![Page 40: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/40.jpg)
40
Recommendations
So, what are the best ways of preventing pump explosions?
1. Use local start only (remote shutoff is not an issue)2. Avoid the ability to isolate the pump
Lock open or remove valves on the suction and/or discharge
3. Train operators on the significance of this issue
![Page 41: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/41.jpg)
Centrifugal Pump with Remote Stop
![Page 42: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/42.jpg)
42
Recommendations
If local start and lock open valving are not options (e.g., spared pump installations with auto-throwover), there are a number of control options that can be evaluated on a case-by-case basis for adequacy of risk reduction:• Relief device (rupture disc or relief valve)
• High Temp Shutdown
• High Pressure Shutdown
• Limit switches on isolation valves to ensure they are open (or at least not closed)
• Low flow interlock
• Low power draw interlock (limited application—reliability issues)
Next
![Page 43: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/43.jpg)
Centrifugal Pump with Relief
Back
![Page 44: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/44.jpg)
Centrifugal Pump with SIF
Back
![Page 45: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/45.jpg)
45
Pump Protection Selection MatrixPump Protection Selection Guidance
Type of Pump Hazard Pump Service TypesVersion: B 3/2/2011By KBYount (HPCC)
PRELIMINARY DRAFT
<- Protec
tion Metho
d
Centrifical
Pumps
Variable Speed Drive
Centrifical
Pump
Positive Displacement Pump
Reactive
Chemical
Exotherm
Liquid Vapor
Pressure
Expansion
Hazard (Bleve)
Thermal
Expansion
Hazard (Casing
Bust Open)
Pump Seal/Be
aring Failure
Safety Rated
Protection
Required (SIL 1-
3)
Batch (ON/OF
F) Pumpin
g Service
Analog Control Valve/L
oop Involve
d
Auto Pump
Throwover
Service
Variable Process Composition
Variable Process Temp
Slurry Service
Interlock On-line
Testing Require
dPump Type, Process Service/Conditions -> A B C D E F G H I J K L M N O
Low Power Monitor Interlock 1 Y N N
N Y C C Y Y N C N N
Low Amps Interlock 2 Y N N
N Y C C Y N C N N
Low Flow Interlock (transmitter or switch) 3 Y C N
Y Y Y Y Y C Y Y C
High Temperature Interlock (Pump Casing) 4 Y Y N
Y Y N Y Y Y Y Y Y Y Y
High Pump Discharge Pressure Interlock 5 Y Y Y
N Y Y C Y Y Y Y Y Y YC
Overpressure Relief Valve 6 Y Y Y
C N C Y Y Y Y Y CN
Minimum Flow/Recirculation Line 7 Y N na
Y N Y Y C Y Y CY
Minimum Flow Control Loop (DCS or Mechanical FC) 8 Y N na
Y N Y Y C C
YBlock Valve Position Indication Interlock 9 Y Y Y
Y Y Y C Y C C Y Y
Operational Locks on Manual Isolation Valves 10 Y Y Y
Y Y Y Y N N N N Y Y Y na
Local Only Operator Start Switch (New) 11
Y = Yes, Typically good for this service
N = No, Typically not a good fit for this service
C = Conditionally good for the service, additional design details are required, see notes
na = Not Applicable
![Page 46: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/46.jpg)
46
Share Learnings
Communicate the hazard Identify potential pump explosion
hazards in our areas• Remote start capability
Evaluate each potential pump explosion hazard
Make recommendations to mitigate risk
![Page 47: Centrifugal Pump Isolation Hazards: Case Histories and Prevention Methodologies Peter N. Lodal Eastman Chemical Company](https://reader034.vdocuments.mx/reader034/viewer/2022042507/551b5740550346d31b8b5367/html5/thumbnails/47.jpg)
47
Questions?