ccp manual 2 6 1

Upload: anonymous-xs9jahy1pe

Post on 03-Jun-2018

223 views

Category:

Documents


3 download

TRANSCRIPT

  • 8/12/2019 CCP Manual 2 6 1

    1/20

    Copyright July 2013 CTC Global Corporation All Rights Reserved 1

    CCPTMcan help make the right choice

    The CCP software tool can make a difference to system planners and project

    engineers , making it easy to compare conductors being considered for any project

    Customized to conditions for the specific project requirements

    Allows comparison of most conductor types, not just ACCC versus ACSR

    Illustrates both performance and economic impact of conductor selection

    Compatible with results from PLS CADDTMand Sag 10

    Easy to use and supported by CTC Global for any

    project planning

    When the program is first installed, a CTC icon

    will appear on your desktop Program runs in Excel 2007/2010/2013, Windows only

    Can contact [email protected]

    technical assistance

    mailto:[email protected]:[email protected]
  • 8/12/2019 CCP Manual 2 6 1

    2/20

    Copyright July 2013 CTC Global Corporation All Rights Reserved 2

    Review of CCP

    CCP is downloaded from DropBox after invitation from CTC Global.

    The COMPARISONS tab is the functional program.

  • 8/12/2019 CCP Manual 2 6 1

    3/20

    Copyright July 2013 CTC Global Corporation All Rights Reserved 3

    CCP: Project Questionnaire

    All of the information

    needed for an initialconductor comparison is

    captured in the Project

    Questionnaire.

    Everything in yellow are

    required fields to fill out Allows CTC Global to get a

    good assessment of the

    project and more quickly

    come to a recommendation

    of an ACCC option for the

    project

  • 8/12/2019 CCP Manual 2 6 1

    4/20

    Copyright July 2013 CTC Global Corporation All Rights Reserved 4

    CCP: Overview of CCP tab

    The CCP has a high level

    overview of the sections ofdata entry as a reference

    for new users.

    Gives a brief overview of

    the program and its

    purposes

    This instruction manual

    provides more detail of

    terms and the impact the

    selections will have on the

    calculated results

  • 8/12/2019 CCP Manual 2 6 1

    5/20

    Copyright July 2013 CTC Global Corporation All Rights Reserved 5

    Input Company and/or Project Name

    Conductor Information Base Conductor Conductor #1 Conductor #2 Version Language Voltage Type Select Units

    Type: ACCC ACSR ACSS/TW/HS-285 2.5.2 Beta English AC US Units

    Size (kcmil Al - Code Word): 1026 - DRAKE 795 - DRAKE 960 - SUWANNEE Environmental Inputs 1

    Aluminum Area (kcmil): 1025.6 795.0 959.6 95.9 Sun Radiation (W/ft)

    Diameter (in.): 1.108 1.108 1.108 25 Ambient Temp. (C)

    Rated Strength (lbf): 41,200 31,500 38,600 2.00 Wind (ft/sec)

    Weight (lb/kft): 1,051.8 1,094.0 1,316.5 0 Elevation (ft)

    DC Resistance at 20C (ohms/kft): 0.01634 0.02138 0.01720 0.5 Solar Absorptivity

    AC Resistance at 25C (ohms/kft): 0.01689 0.02208 0.01782 0.5 Emissivity

    AC Resistance at 75C (ohms/kft): 0.02017 0.02633 0.02134 90 Wind Angle (deg.)

    0

    Conductors per phase: 1 1 1 32 Latitude (neg = South)

    Circuits: 1 1 1 June Month

    Ampacity (A) at Temperature (C): 70 978 65 800 175 1,708 21 Day of Month

    Ampacity (A) at Rated Operating Temp (C): 180 1,786 75 908 200 1,828 12 Time (24 hrs.)

    Ampacity (A) at Maximum Temp (C): 200 1,884 100 1,120 250 2,043 Clear Atmosphere

    Line Loss (Based on Inputted Peaking Operating Amps Value) Load and Generation Cost Assumptions

    Steady-State Temperature (C) at Peak Ampacity: 65 75 67 3.9 Line Length (miles)

    Resistance at Peak Operating Amps (ohm/mile): 0.10290 0.13901 0.10955 88 Voltage (kV)

    First Year Line Losses (MWh): 4,489 6,065 4,779 908 Peak Operating Amps

    ACCC 1026 - DRAKE - Reduces First Year COGenerated by (MT): 929 171 70% Load Factor

    ACCC 1026 - DRAKE - Reduces First Year Line Losses by (MWh): 1,576 290 52% Loss Factor

    ACCC 1026 - DRAKE - Reduces First Year Line Losses by (%): 26% 6% 138 Peak Power per Circuit (MW)

    ACCC 1026 - DRAKE - Reduces First Year Line Losses by ($/Year): 157,566 29,014 3 Phases/Circuit

    ACCC 1026 - DRAKE - Line Loss Savings per ft of Conductor ($/ft): 2.58 0.47 100 Cost of Energy Generation ($/MWh)

    1.300 CO(lb/kWh)

    ACCC 1026 - DRAKE - Reduces 30 year line loss by ($): 4,726,976 870,426 0% Load Increase/Year

    ACCC 1026 - DRAKE - Reduces 30 year COgeneration by (MT): 27,874 5,133

    Revenue Attainable during Peak Capacity (Limited by Max Sag) Resistance at Peak Capacity (ohm/mile) 4592.69368. . . ea a ac ( )

    Peak Power Available for Delivery (20 hrs.) (MWh): 5,621 3,370 4,202 20 Hours/Year at Peak Capacity (hr.)

    Potential Revenue for Power Delivered ($): 4,496,963 2,696,285 3,361,731 800 Price of Energy at Peak Capacity ($/MW h)

    Initial Sag and Tension: Initial Sag and Tension:

    % RTS: 15.0% 20.0% 20.0% 1148.29396 Ruling Span (ft)

    Sag at Initial Sagging Temperature (ft): 28.10 28.60 28.10 21 Initial Sagging Temperature (C)

    Initial Tension at Sagging Temperature (lbf): 6,180.0 6,300.0 7,720.0 39.4 Maximum Allowable Sag (ft)

    Sag/Tension at Above Stringing Temperature: Sag Comparison Graph

    Temp(C): 65 75 67

    Sag (ft): 33.50 35.30 33.90

    Tension (lbf): 5,180.0 5,115.0 6,404.0

    Temp(C): 180 75 200

    Sag (ft): 35.10 35.30 43.80

    Tension (lbf): 4,938.0 5,115.0 4,953.0

    Temp(C): 200 100 250

    Sag (ft): 35.20 38.10 46.50

    Tension (lbf): 4,920.0 4,736.0 4,667.0

    Max. Temp(C): 200 100 121

    Temperature at Maximum Allowable Sag Sag (ft): 35.20 38.10 39.40

    Tension (lbf): 4,920.0 4,736.0 5,510

    Ampacity (A): 1,884 1,120 1,398

    Wind / Ice or Cold Temperature Sag/Tension: Wind / Ice Conditions

    Sag (ft): 26.90 26.20 26.20 0 Temperature (C) Sag (ft):

    Tension (lbf): 6,459.0 6,876.0 8,287.0 12.0 Windspeed (mph)

    0.00 NESC K-Factor (lb/ft)

    Knee Point Temperature Sag/Tension: 0.00 Radial Ice Thickness (in.)

    Knee Point Temperature (C): 74 114 109 0.0 Ice Density (lb/ft)Sag (ft): 34.40 39.50 38.70

    Tension (lbf): 5038.0 4561.0 5608.0

    Ampacity Cells Turn Red if Max Capacity is not reached

    Sag at Maximum Temperature

    Input Company and/or Project Name

    Sag at Peak Operating Amps

    Sag at Rated Operating Temperature

    Azimuth of Line (NS=0, EW=90)

    0

    5

    10

    15

    2025

    30

    35

    40

    45

    50

    0 50 100 150 200 250

    Sag

    (ft):

    Temperature (C)

    ACCC-1026 -DRAKE

    ACSR-795 -DRAKE

    ACSS/TW/HS-285-960- SUWANNEE

    Maximum AllowableSag (ft)

    SetDefault

    EnvironmentalInputs

    Reviewing steps in making a Comparison

    1. Demonstrate the

    areas for inputs,

    conductor selectionand outputs.

    1. Environmental Inputs

    2. Line factors/Cost

    factors

    3. Conductor Selection

    4. Ice/wind conditions

    5. Sag calculation factors6. Temperature and line

    loses

    7. Sag and tension

    results

    8. Visual sag and limits

    9. Efficiency and

    emissions

    10. Thermal Knee Point

    calculations

    2. All yellow cells are

    inputs, can enter

    own value or

    choose from

    dropdown list

    1

    2

    5

    6

    78

    4

    9

    3

    10

  • 8/12/2019 CCP Manual 2 6 1

    6/20

    Copyright July 2013 CTC Global Corporation All Rights Reserved 6

    Step 1: Adjusting environmental conditions

    CCP is adjustable to Metric or US units for AC

    and DC Transmission lines.

    Can select language, presently includes English , Chinese,Russian, Vietnamese , Czech, Polish and Spanish

    ,Sun Radiation (W/m3): IEEE 738 calculates the affect of

    the sun radiation on heating the conductor. Is determined

    by:

    Latitude (neg = South): Determines sun location in

    sky

    Month: Enter desired month

    Day of Month: Enter desired day

    Time (24 hrs.): Enter desired time

    Atmosphere: Condition of sky

    Elevation (m): Determines the atmospheric impact

    on the amount of sun radiation on the conductor

    Ambient Temp. (C): This sets the base temperature for

    performing the ampacity and conductor temperature

    calculations. In countries with high seasonal variance, it

    can be important to consider summer and winter

    conditions separately.

    Wind (m/sec): Used to determine the amount of cooling

    at the surface of the conductor.

    Solar Absorptivity: This factor is used to calculate the

    percentage of solar radiation absorbed by the

    conductor and converted to heat

    Emissivity: This factor is used to calculate the amount

    of heat shed by the conductor surface

    Wind Angle (deg.): Modifies the effect of wind cooling

    Azimuth of Line (NS=0, EW=90): Effects the solar

    radiation impact based on the average compass angle

    of the line

    1

  • 8/12/2019 CCP Manual 2 6 1

    7/20Copyright July 2013 CTC Global Corporation All Rights Reserved 7

    Step 1: Typical range and impact of changes

    These inputs effect the basic capacity rating of

    the line, and assumptions made during planning

    can result in significant changes in the rating

    Sun Radiation (W/m3): The higher the sun radiation value,

    the higher the starting temperature of the conductor, and

    hence the lower the available capacity of the line

    Ambient Temp. (C): The higher the assumed ambient

    temperature, the lower the available capacity of the line.

    Most calculations are based on temperature at time of peakloading. A 1 C change in temperature results in ~1 to 2%

    change in ampacity.

    Wind (m/sec): The cooling effect based on wind speed can

    have a significant impact on the ampacity rating. A 10%

    change in wind speed can have a 5% affect on the ampacity

    rating.

    Elevation (m): Higher the elevation, the higher the sunradiation amount. Up to 30% more radiation at 4500

    meters (15,000 ft) vs. sea level.

    Solar Absorptivity: 0.5 is generally assumed for a matte

    finished conductor, which will age to 0.9 over time. A 0.9

    value results in a ~10% reduction in line ampacity.

    However, this is offset by emissivity.

    Emissivity: 0.5 is generally assumed for a matte

    finished conductor, which will age to 0.9 over time. A

    0.9 value results in a 10% increase in line ampacity.

    However, this is offset by solar absorptivity.

    Wind Angle (deg.): The cooling effect of a 5 angle

    change is about 1% change in ampacity. A complete

    90 change results in ~30% change in ampacity.

    Azimuth of Line (NS=0, EW=90): Depending on the

    latitude, the value of the azimuth of the line will

    have a small impact on ampacity.

    1

  • 8/12/2019 CCP Manual 2 6 1

    8/20Copyright July 2013 CTC Global Corporation All Rights Reserved 8

    Step 2: Voltage/CO2/Cost Assumption Inputs

    These entries are used as the basis for calculating

    operating conditions and economic impact

    Line Length (km): Line length is primarily used to determine

    the amount of line losses for a project.

    Voltage (kV): Impacts only the power delivered by the line.

    Presently no power factor is considered.

    Peak Op. Amps: The expected maximum amps to be

    delivered.

    Load Factor: Represents a percentage of peak annual ampsused to calculate the average amps demanded on a daily

    basis.

    Loss Factor: Is calculated based on load factor by a standard

    electrical engineering formula assuming cyclical demand

    distribution.

    Peak Power per Circuit (MW): Calculated based on standard

    formulas for DC and AC power delivery

    Phases/Circuit: Based on AC or DC line configuration

    Cost of Energy Generation ($/MWh): Based on an

    assumption for the weighted average cost of generation.

    CO2(kg/kWh): Assumed average CO2generated for each

    kWh.

    Load Increase/Year: Expected increase load due to demand.

    CCP also considers peak loading performance

    and economics:

    Hours/Year at Peak Capacity (hr.): Hoursexpected to operate during the year at

    peak amps

    Price of Energy at Peak Capacity ($/MWh):

    Selling price per MWh at peak operating

    capacity

    2

  • 8/12/2019 CCP Manual 2 6 1

    9/20Copyright July 2013 CTC Global Corporation All Rights Reserved 9

    Step 2: Typical range and impact of changes

    These values affect the economics of the planned

    transmission line project:

    Line Length (km): The longer the line, the greater the line losses.Any percentage increase in line length is directly proportional to

    line losses, assuming constant ampacity across the entire line

    length.

    (This version of CCP does not calculate voltage drop, SIL, or

    other loss factors that can occur along the line)

    Voltage (kV): Impacts the peak power of the circuit.

    Peak Op. Amps (A): This impacts the calculated resistance of theline. This is a non-linear relationship between resistance and

    ampacity. A 10% change in peak operating amps results in a 10%

    change in temperature and a 20% change in line losses.

    Load Factor: Shifts the minimum and average load distribution.

    A 10% change in Load Factor results in a 20% change in line

    losses.

    Loss Factor: Relates the peak operating amps to the daily

    fluctuations in the load and is used in calculating line losses.

    Peak Power per Circuit (MW): A calculated circuit load.

    Phases/Circuit: Calculated based on voltage type.

    Cost of Energy Generation ($/MWh): Basis for economics.

    CO2(kg/kWh): Basis for greenhouse gas calculations.

    Load Increase/Year: Basis for 30 year calculations.

    The revenue achievable during peak operating

    conditions is a direct function of these two

    inputs. But, this value is also related to themaximum sag condition set for the conductor.

    See section 5.

    Hours/Year at Peak Capacity (hr.)

    Price of Energy at Peak Capacity ($/MWh)

    2

  • 8/12/2019 CCP Manual 2 6 1

    10/20Copyright July 2013 CTC Global Corporation All Rights Reserved 10

    Step 3: Selection of Conductors and Amps Calculations

    All conductor information is

    derived directly from the

    manufactures conductorspecification and wire files.

    Type: Choose from dropdown list.

    Size (AlCode Word): Select a size for

    that type of conductor for comparison.

    Aluminum Area (mm2): The cross

    sectional area of the Al only. Diameter (mm): Outside diameter of

    the selected conductor size.

    Rated Strength (kN): Rated maximum

    tensile strength of the conductor.

    Weight (kg/km): The unit weight of the

    conductor.

    DC Resistance at 20C (ohms/km):

    Nominal DC resistance of the

    conductor at 20C

    AC Resistance at 25C/75C (ohms/km):

    Nominal AC resistance of conductor at

    25C and 75C

    Conductors per phase: Number of conductor bundled in the phase

    Circuits: Number of circuit to perform the line loss/CO2calculations.

    Capacity ratings are dependent upon the environmental inputs:

    Ampacity (A) at Temperature (C): User chooses a temperature at

    which they want the ampacity calculated, based upon the inputted

    environmental assumptions.

    Ampacity (A) at Rated Operating Temp (C): Value is from the

    database, shows the ampacity at the rated operating temperature of

    the conductor, based upon the inputted environmental assumptions

    Ampacity (A) at Maximum Temp (C): Value is from the database,

    shows the ampacity at the rated operating temperature of the

    conductor, based upon the inputted environmental assumptions

    3

  • 8/12/2019 CCP Manual 2 6 1

    11/20Copyright July 2013 CTC Global Corporation All Rights Reserved 11

    Step 3: Impact of conductor properties

    Data in this section is used

    to show ampacity, temperature

    and sag. Type: First conductor type is the base

    conductor, will impact the rest of the

    comparisons. (Suggest ACCC conductor.)

    Size (AlCode Word): Impact the

    calculated capacity of the conductor.

    Aluminum Area (mm2): Impact the

    calculated capacity of the conductor.

    Diameter (mm): Impact the capacity, and the

    wind load sags.

    Rated Strength (kN): Determine if factor of

    safeties on the conductor are being meant and

    will impact the sags.

    Weight (kg/km): Impact the sags. DC Resistance at 20C (ohms/km): Impact the line

    loss comparison, can chose a lower resistance

    conductors to make comparisons against.

    AC Resistance at 25C/75C (ohms/km): Impacts

    the resistance, these values are used to calculate

    the resistance at any other calculated

    temperature of the conductor

    Conductors per phase: Impact the line loss calculations, the more

    conductors per phase, the lower the overall resistance of the

    circuit.

    Circuits: Impacts the line loss calculations, the more circuits, the

    more line losses will be calculated in the comparison.

    Ampacity (A) at Temperature (C): Choosing a specific

    temperature, can show differences in ampacity at differenttemperatures that might be a larger interest to the user than the

    rated and maximum temperatures.

    Ampacity (A) at Rated Operating Temp (C): Can be used to

    compare what the rated capacities will be.

    Ampacity (A) at Maximum Temp (C): Can be used to compare

    what the absolute maximum capacity of the line could be.

    3

  • 8/12/2019 CCP Manual 2 6 1

    12/20Copyright July 2013 CTC Global Corporation All Rights Reserved 12

    Step 4: Setting initial sag conditions

    The project conditions for initial sag, tension and installation temperature will allow CCP

    to calculate the sags at various operating conditions.

    Ruling Span (m): The approximate average distance between two towers for each line section

    used to determine all sags and tensions within that section. Larger spans in the section willinfluence this calculation the most.

    Initial Sagging Temperature (C): The expected ambient temperature when initially stringing the

    line.

    Maximum Allowable Sag (m): Based on clearance requirements.

    % RTS: The tension at initial sagging based on the rated tensile strength (RTS) of the conductor.

    Can also be considered Ultimate Tensile Strength (UTS) and Rated Breaking Strength (RBS).

    Sag at Initial Sagging Temperature (m): This number is calculated based on the initial tension in

    the conductor.

    Initial Tension as Sagging Temperature (kN): This number is calculated based on the percent RTS

    of the conductor chosen at a given temperature.

    4

  • 8/12/2019 CCP Manual 2 6 1

    13/20Copyright July 2013 CTC Global Corporation All Rights Reserved 13

    Step 4: Impact of Initial Sagging Conditions

    The initial tension, ruling span and installation temperature will have a significant

    influence on the sags and the knee point temperature of the selected conductor.

    Ruling Span (m): Set by the number of towers in a section of the line. The selection of a ruling can be affected

    by clearance requirements, tower cost/height/strength, and conductor properties. The economics impact ofthe ruling span on a project are a complicated trade off of all of these factors.

    Initial Sagging Temperature (C): The initial temperature is used as a basis to calculate sags at all other

    temperatures. The impact of installation temperature needs to be considered for initial tension and final sag

    conditions.

    Maximum Allowable Sag (m): Based on clearance requirements, maximum sag may limit the ampacity of a

    conductor with high thermal sag. This will impact each conductor individually.

    % RTS: Ensure tension on the conductor does not exceed regulated limit, such as factor of safety thatdetermine the maximum tensions the conductor can exhibit under specific weather conditions.

    Sag at Initial Sagging Temperature (m): Shows what the initial ruling span sag should be when the conductor is

    newly installed.

    Initial Tension as Sagging Temperature (kN): Shows the tension the conductor will exhibit when its first

    installed.

    4

  • 8/12/2019 CCP Manual 2 6 1

    14/20Copyright July 2013 CTC Global Corporation All Rights Reserved 14

    Step 5: Set wind and ice conditions & Impacts

    Ice/wind conditions typically cause

    the largest loading on the towers.

    Temperature (C): Temperature at which the worst

    loading case (either ice or wind) would exist.

    Windspeed (km/hr): Speed of the wind for a

    specific worst weather case.

    Safety Factor (N/m): An additional weight added

    to the conductor to build in a factor of safety to

    ensure the maximum tension on the towers is notexceeded.

    Radial Ice Thickness (mm): The thickness of ice

    formed on the line for a specific worst weather

    case. This adds additional weight to the

    conductor.

    Ice Density (kg/m3): The density of ice during the

    specific worst weather case.

    These calculations do not consider dynamic

    forces that affect the line, hardware or

    appropriate safety factors for a project. These

    strictly relate to the weather impact on sag

    clearance.

    Typical Range and Impact of Changes.

    Temperature (C): The colder the weather, the moretension there is on the conductor.

    The temperature should be equal to the expected

    ambient temperature, not the operating temperature.

    Windspeed (km/hr): The wind speed is translated into

    a unit weight that is added to the conductor weight,

    and adds additional sag and tension to the conductor.

    Safety Factor (N/m): Typically set by country or utilityrequirements.

    Radial Ice Thickness (mm): Set by regulatory

    requirements.

    Ice Density (kg/m3): Set by regulatory requirements.

    5

  • 8/12/2019 CCP Manual 2 6 1

    15/20Copyright July 2013 CTC Global Corporation All Rights Reserved 15

    Step 6: Evaluate line loss reduction and benefits

    CCP uses the resistances of

    the cables to calculate the

    differences in temperature,line losses and CO2emission

    Steady-State Temperature at

    Peak Ampacity: Temperature of the conductor when operating at peak operating amps. Large differences in

    temperature will lead to differences in line losses/CO2emissions between the selected conductors.

    First Year Line Losses (MWh): The amount of line losses generated for the selected conductor. Is based upon the line

    length, number of conductors per phase, the number of circuits, the resistance of the cable at the calculated

    temperature and the load (loss) factor.

    Comparisons are based on the conductor in the first column. When the number is positive, means the base conductor is

    reducing the line losses/CO2generated over the other selected conductor. When the number is negative, means the base

    conductor is increasing the line losses/CO2generated over the other selected conductor.

    Base Conductor Reduces First Year CO2Generated by (MT): Shows the difference in the amount of CO2generated vs.

    the base conductor.

    Base Conductor Reduces First Year Line Losses by (MWh): Shows the difference in MWh the base conductorreduces/increases the line losses by.

    Base Conductor Reduces First Year Line Losses by (%): Shows the difference, in percentage, the base conductor

    reduces/increases the line losses by.

    Base Conductor Reduces First Year Line Losses by ($/Year): Shows the amount of money the base conductor would

    save/not save over the other conductors.

    Base Conductor Line Loss Savings per meter of Conductor ($/m): Shows the line loss savings on a per meter of

    conductor basis.

    6

  • 8/12/2019 CCP Manual 2 6 1

    16/20Copyright July 2013 CTC Global Corporation All Rights Reserved 16

    Step 7: Sag/Tension Calculations & Impacts

    CCP uses manufacturers

    specifications and wire files to

    calculate the operating sag of the

    conductor.

    Sag at Peak Operating Amps (Temp/Sag/Tension):

    Shows the sags for the selected conductors at the

    user specified peak operating amps. The colors

    coordinate with the values found in sections 3 & 6.

    Sag at Rated Operating Temp (Temp/Sag/Tension):

    The sag at the rated operating temperature of theselected conductors.

    Sag at Maximum Temp (Temp/Sag/Tension): The sag at

    the maximum operating temperature of the selected

    conductors.

    Temperature at Maximum Allowable Sag (Max.

    Temp/Sag/Tension/Ampacity): Shows the temperature

    at which the selected conductor reaches the maximumallowable sag, set by the user in section 5. Ampacity

    values turn red when the selected conductors

    maximum capacity cannot be reached due to being sag

    limited.

    Wind/Ice or Cold Temperature Sag/Tension

    (Sag/Tension): Shows the sag for the ice/wind condition

    specified by the user inputs.

    Impacts of these sag/tension calculations:

    Results show the differences in the sags of the

    selected conductors at key temperatures

    Show the impact of limiting the sags, and how the

    limit may reduce the maximum capacity of the

    selected conductor in order to ensure clearances arenot violated

    7

  • 8/12/2019 CCP Manual 2 6 1

    17/20Copyright July 2013 CTC Global Corporation All Rights Reserved 17

    Step 8: Visual sag presentation at temperature

    A graphical representation of the sags as a

    function of temperature, driven by

    ampacity and maximum allowed

    conductor temperature.

    Shows the sags for the three conductors

    selected

    The bend in sag graph shows the location of

    the knee point temperature

    Below the knee point, the conductor

    sags are dictated by the composite

    conductor properties

    Above the knee point, the conductor

    sags are dictated by the core properties

    alone

    Sags are only shown for the range of

    temperatures the conductor is rated to.

    The maximum sag line is also shown, to

    demonstrate where the potential sag limit

    may be and how it will impact conductor

    performance.

    8

  • 8/12/2019 CCP Manual 2 6 1

    18/20Copyright July 2013 CTC Global Corporation All Rights Reserved 18

    Step 9: Understand the long term impact

    CCP performs basic 30 year line loss calculations and can calculate the potential revenue

    when operating at peak amps for a certain number of hours per year

    Base conductor Reduces 30 Year Line Losses by ($): Calculation is determined by the user inputted

    year load increase, allows all conductors to grow in load until the maximum use temperature of the

    base conductor is reached, and then cuts off the load growth. Calculation shows the differences in

    the line loss savings between the base and selected conductors over a 30 year period with no

    discount rate or NPV calculation performed.

    Base Conductor Reduces 30 Year CO2Generated by (MT): As with the 30 year line loss calculation,

    performs the same calculation for the CO2reduction.

    Peak Power Available for Delivery (User inputted hrs.) (MWh): This peak capacity is determined by

    the sag limitation shown in section 8. Calculation shows the peak power that is delivered at the end

    of the line, minus the line losses over the line at peak capacity.

    Potential Revenue for Power Delivered ($): Utility may charge a different selling price when the line

    is operating at peak capacity. Knowing what the peak power delivered potential can be, is multiplied

    by the cost of selling the power while at peak capacity. Shows differences in revenue each conductor

    choice can achieve.

    9

  • 8/12/2019 CCP Manual 2 6 1

    19/20Copyright July 2013 CTC Global Corporation All Rights Reserved 19

    Step 10: Thermal Knee Point Calculation

    CCP can calculate the thermal knee point temperature of each of the selected conductorsAll Bi-metallic conductors have a thermal knee point temperature

    For conventional ACSR, the thermal knee point is typically above its maximum use

    temperatureOther high temperature, low sag conductor types, this knee point transition typically occurs

    within the operating range of the conductor

    Thermal Knee Point is not a set value though, it is dependent on several factors:

    1) Al/core area ratio

    2) Span length (or ruling span length)3) Initial installation tension on the conductor

    Thermal Knee Points results are:

    A) Temperature at which the thermal knee point occurs at

    B) The sag at the thermal knee point

    C) The tension at which the thermal knee point

    10

  • 8/12/2019 CCP Manual 2 6 1

    20/20

    Additional CTC Application Engineering Support

    The Application Engineering Group at CTC Global is ready to support your project in

    a number of ways. Once a project questionnaire is received, which is also embedded into the CCP program, the

    application engineering team will begin the process of selecting the best conductor for the project,

    whether its a reconductoring or new line project

    First evaluate the capabilities of the old conductor and looking at the project goals, determine which

    ACCC option could potentially meet the requirements

    Can perform sag/tension calculations based on known stress-strain curves for nearly every conductortype, using either PLS-CADD or Sag10 software packages, and verify the sags shown on CCP are close

    to what these software programs would calculate for similar starting sagging conditions.

    Once conductors are chosen, write up a technical summary of which conductors CTC Global feels can

    meet the project requirements and send analysis back to the customer who requested the analysis.

    Once a project is identified as being a potential project for the ACCC option, application engineers

    can directly communicate with the engineer of the project to help with any additional analysis or

    answer technical questions about the ACCC option for the project

    CTC Global Application Engineers though are not line designers, but are able to help facilitate the

    choice of using an ACCC option for a project