ccp manual 2 6 1
TRANSCRIPT
-
8/12/2019 CCP Manual 2 6 1
1/20
Copyright July 2013 CTC Global Corporation All Rights Reserved 1
CCPTMcan help make the right choice
The CCP software tool can make a difference to system planners and project
engineers , making it easy to compare conductors being considered for any project
Customized to conditions for the specific project requirements
Allows comparison of most conductor types, not just ACCC versus ACSR
Illustrates both performance and economic impact of conductor selection
Compatible with results from PLS CADDTMand Sag 10
Easy to use and supported by CTC Global for any
project planning
When the program is first installed, a CTC icon
will appear on your desktop Program runs in Excel 2007/2010/2013, Windows only
Can contact [email protected]
technical assistance
mailto:[email protected]:[email protected] -
8/12/2019 CCP Manual 2 6 1
2/20
Copyright July 2013 CTC Global Corporation All Rights Reserved 2
Review of CCP
CCP is downloaded from DropBox after invitation from CTC Global.
The COMPARISONS tab is the functional program.
-
8/12/2019 CCP Manual 2 6 1
3/20
Copyright July 2013 CTC Global Corporation All Rights Reserved 3
CCP: Project Questionnaire
All of the information
needed for an initialconductor comparison is
captured in the Project
Questionnaire.
Everything in yellow are
required fields to fill out Allows CTC Global to get a
good assessment of the
project and more quickly
come to a recommendation
of an ACCC option for the
project
-
8/12/2019 CCP Manual 2 6 1
4/20
Copyright July 2013 CTC Global Corporation All Rights Reserved 4
CCP: Overview of CCP tab
The CCP has a high level
overview of the sections ofdata entry as a reference
for new users.
Gives a brief overview of
the program and its
purposes
This instruction manual
provides more detail of
terms and the impact the
selections will have on the
calculated results
-
8/12/2019 CCP Manual 2 6 1
5/20
Copyright July 2013 CTC Global Corporation All Rights Reserved 5
Input Company and/or Project Name
Conductor Information Base Conductor Conductor #1 Conductor #2 Version Language Voltage Type Select Units
Type: ACCC ACSR ACSS/TW/HS-285 2.5.2 Beta English AC US Units
Size (kcmil Al - Code Word): 1026 - DRAKE 795 - DRAKE 960 - SUWANNEE Environmental Inputs 1
Aluminum Area (kcmil): 1025.6 795.0 959.6 95.9 Sun Radiation (W/ft)
Diameter (in.): 1.108 1.108 1.108 25 Ambient Temp. (C)
Rated Strength (lbf): 41,200 31,500 38,600 2.00 Wind (ft/sec)
Weight (lb/kft): 1,051.8 1,094.0 1,316.5 0 Elevation (ft)
DC Resistance at 20C (ohms/kft): 0.01634 0.02138 0.01720 0.5 Solar Absorptivity
AC Resistance at 25C (ohms/kft): 0.01689 0.02208 0.01782 0.5 Emissivity
AC Resistance at 75C (ohms/kft): 0.02017 0.02633 0.02134 90 Wind Angle (deg.)
0
Conductors per phase: 1 1 1 32 Latitude (neg = South)
Circuits: 1 1 1 June Month
Ampacity (A) at Temperature (C): 70 978 65 800 175 1,708 21 Day of Month
Ampacity (A) at Rated Operating Temp (C): 180 1,786 75 908 200 1,828 12 Time (24 hrs.)
Ampacity (A) at Maximum Temp (C): 200 1,884 100 1,120 250 2,043 Clear Atmosphere
Line Loss (Based on Inputted Peaking Operating Amps Value) Load and Generation Cost Assumptions
Steady-State Temperature (C) at Peak Ampacity: 65 75 67 3.9 Line Length (miles)
Resistance at Peak Operating Amps (ohm/mile): 0.10290 0.13901 0.10955 88 Voltage (kV)
First Year Line Losses (MWh): 4,489 6,065 4,779 908 Peak Operating Amps
ACCC 1026 - DRAKE - Reduces First Year COGenerated by (MT): 929 171 70% Load Factor
ACCC 1026 - DRAKE - Reduces First Year Line Losses by (MWh): 1,576 290 52% Loss Factor
ACCC 1026 - DRAKE - Reduces First Year Line Losses by (%): 26% 6% 138 Peak Power per Circuit (MW)
ACCC 1026 - DRAKE - Reduces First Year Line Losses by ($/Year): 157,566 29,014 3 Phases/Circuit
ACCC 1026 - DRAKE - Line Loss Savings per ft of Conductor ($/ft): 2.58 0.47 100 Cost of Energy Generation ($/MWh)
1.300 CO(lb/kWh)
ACCC 1026 - DRAKE - Reduces 30 year line loss by ($): 4,726,976 870,426 0% Load Increase/Year
ACCC 1026 - DRAKE - Reduces 30 year COgeneration by (MT): 27,874 5,133
Revenue Attainable during Peak Capacity (Limited by Max Sag) Resistance at Peak Capacity (ohm/mile) 4592.69368. . . ea a ac ( )
Peak Power Available for Delivery (20 hrs.) (MWh): 5,621 3,370 4,202 20 Hours/Year at Peak Capacity (hr.)
Potential Revenue for Power Delivered ($): 4,496,963 2,696,285 3,361,731 800 Price of Energy at Peak Capacity ($/MW h)
Initial Sag and Tension: Initial Sag and Tension:
% RTS: 15.0% 20.0% 20.0% 1148.29396 Ruling Span (ft)
Sag at Initial Sagging Temperature (ft): 28.10 28.60 28.10 21 Initial Sagging Temperature (C)
Initial Tension at Sagging Temperature (lbf): 6,180.0 6,300.0 7,720.0 39.4 Maximum Allowable Sag (ft)
Sag/Tension at Above Stringing Temperature: Sag Comparison Graph
Temp(C): 65 75 67
Sag (ft): 33.50 35.30 33.90
Tension (lbf): 5,180.0 5,115.0 6,404.0
Temp(C): 180 75 200
Sag (ft): 35.10 35.30 43.80
Tension (lbf): 4,938.0 5,115.0 4,953.0
Temp(C): 200 100 250
Sag (ft): 35.20 38.10 46.50
Tension (lbf): 4,920.0 4,736.0 4,667.0
Max. Temp(C): 200 100 121
Temperature at Maximum Allowable Sag Sag (ft): 35.20 38.10 39.40
Tension (lbf): 4,920.0 4,736.0 5,510
Ampacity (A): 1,884 1,120 1,398
Wind / Ice or Cold Temperature Sag/Tension: Wind / Ice Conditions
Sag (ft): 26.90 26.20 26.20 0 Temperature (C) Sag (ft):
Tension (lbf): 6,459.0 6,876.0 8,287.0 12.0 Windspeed (mph)
0.00 NESC K-Factor (lb/ft)
Knee Point Temperature Sag/Tension: 0.00 Radial Ice Thickness (in.)
Knee Point Temperature (C): 74 114 109 0.0 Ice Density (lb/ft)Sag (ft): 34.40 39.50 38.70
Tension (lbf): 5038.0 4561.0 5608.0
Ampacity Cells Turn Red if Max Capacity is not reached
Sag at Maximum Temperature
Input Company and/or Project Name
Sag at Peak Operating Amps
Sag at Rated Operating Temperature
Azimuth of Line (NS=0, EW=90)
0
5
10
15
2025
30
35
40
45
50
0 50 100 150 200 250
Sag
(ft):
Temperature (C)
ACCC-1026 -DRAKE
ACSR-795 -DRAKE
ACSS/TW/HS-285-960- SUWANNEE
Maximum AllowableSag (ft)
SetDefault
EnvironmentalInputs
Reviewing steps in making a Comparison
1. Demonstrate the
areas for inputs,
conductor selectionand outputs.
1. Environmental Inputs
2. Line factors/Cost
factors
3. Conductor Selection
4. Ice/wind conditions
5. Sag calculation factors6. Temperature and line
loses
7. Sag and tension
results
8. Visual sag and limits
9. Efficiency and
emissions
10. Thermal Knee Point
calculations
2. All yellow cells are
inputs, can enter
own value or
choose from
dropdown list
1
2
5
6
78
4
9
3
10
-
8/12/2019 CCP Manual 2 6 1
6/20
Copyright July 2013 CTC Global Corporation All Rights Reserved 6
Step 1: Adjusting environmental conditions
CCP is adjustable to Metric or US units for AC
and DC Transmission lines.
Can select language, presently includes English , Chinese,Russian, Vietnamese , Czech, Polish and Spanish
,Sun Radiation (W/m3): IEEE 738 calculates the affect of
the sun radiation on heating the conductor. Is determined
by:
Latitude (neg = South): Determines sun location in
sky
Month: Enter desired month
Day of Month: Enter desired day
Time (24 hrs.): Enter desired time
Atmosphere: Condition of sky
Elevation (m): Determines the atmospheric impact
on the amount of sun radiation on the conductor
Ambient Temp. (C): This sets the base temperature for
performing the ampacity and conductor temperature
calculations. In countries with high seasonal variance, it
can be important to consider summer and winter
conditions separately.
Wind (m/sec): Used to determine the amount of cooling
at the surface of the conductor.
Solar Absorptivity: This factor is used to calculate the
percentage of solar radiation absorbed by the
conductor and converted to heat
Emissivity: This factor is used to calculate the amount
of heat shed by the conductor surface
Wind Angle (deg.): Modifies the effect of wind cooling
Azimuth of Line (NS=0, EW=90): Effects the solar
radiation impact based on the average compass angle
of the line
1
-
8/12/2019 CCP Manual 2 6 1
7/20Copyright July 2013 CTC Global Corporation All Rights Reserved 7
Step 1: Typical range and impact of changes
These inputs effect the basic capacity rating of
the line, and assumptions made during planning
can result in significant changes in the rating
Sun Radiation (W/m3): The higher the sun radiation value,
the higher the starting temperature of the conductor, and
hence the lower the available capacity of the line
Ambient Temp. (C): The higher the assumed ambient
temperature, the lower the available capacity of the line.
Most calculations are based on temperature at time of peakloading. A 1 C change in temperature results in ~1 to 2%
change in ampacity.
Wind (m/sec): The cooling effect based on wind speed can
have a significant impact on the ampacity rating. A 10%
change in wind speed can have a 5% affect on the ampacity
rating.
Elevation (m): Higher the elevation, the higher the sunradiation amount. Up to 30% more radiation at 4500
meters (15,000 ft) vs. sea level.
Solar Absorptivity: 0.5 is generally assumed for a matte
finished conductor, which will age to 0.9 over time. A 0.9
value results in a ~10% reduction in line ampacity.
However, this is offset by emissivity.
Emissivity: 0.5 is generally assumed for a matte
finished conductor, which will age to 0.9 over time. A
0.9 value results in a 10% increase in line ampacity.
However, this is offset by solar absorptivity.
Wind Angle (deg.): The cooling effect of a 5 angle
change is about 1% change in ampacity. A complete
90 change results in ~30% change in ampacity.
Azimuth of Line (NS=0, EW=90): Depending on the
latitude, the value of the azimuth of the line will
have a small impact on ampacity.
1
-
8/12/2019 CCP Manual 2 6 1
8/20Copyright July 2013 CTC Global Corporation All Rights Reserved 8
Step 2: Voltage/CO2/Cost Assumption Inputs
These entries are used as the basis for calculating
operating conditions and economic impact
Line Length (km): Line length is primarily used to determine
the amount of line losses for a project.
Voltage (kV): Impacts only the power delivered by the line.
Presently no power factor is considered.
Peak Op. Amps: The expected maximum amps to be
delivered.
Load Factor: Represents a percentage of peak annual ampsused to calculate the average amps demanded on a daily
basis.
Loss Factor: Is calculated based on load factor by a standard
electrical engineering formula assuming cyclical demand
distribution.
Peak Power per Circuit (MW): Calculated based on standard
formulas for DC and AC power delivery
Phases/Circuit: Based on AC or DC line configuration
Cost of Energy Generation ($/MWh): Based on an
assumption for the weighted average cost of generation.
CO2(kg/kWh): Assumed average CO2generated for each
kWh.
Load Increase/Year: Expected increase load due to demand.
CCP also considers peak loading performance
and economics:
Hours/Year at Peak Capacity (hr.): Hoursexpected to operate during the year at
peak amps
Price of Energy at Peak Capacity ($/MWh):
Selling price per MWh at peak operating
capacity
2
-
8/12/2019 CCP Manual 2 6 1
9/20Copyright July 2013 CTC Global Corporation All Rights Reserved 9
Step 2: Typical range and impact of changes
These values affect the economics of the planned
transmission line project:
Line Length (km): The longer the line, the greater the line losses.Any percentage increase in line length is directly proportional to
line losses, assuming constant ampacity across the entire line
length.
(This version of CCP does not calculate voltage drop, SIL, or
other loss factors that can occur along the line)
Voltage (kV): Impacts the peak power of the circuit.
Peak Op. Amps (A): This impacts the calculated resistance of theline. This is a non-linear relationship between resistance and
ampacity. A 10% change in peak operating amps results in a 10%
change in temperature and a 20% change in line losses.
Load Factor: Shifts the minimum and average load distribution.
A 10% change in Load Factor results in a 20% change in line
losses.
Loss Factor: Relates the peak operating amps to the daily
fluctuations in the load and is used in calculating line losses.
Peak Power per Circuit (MW): A calculated circuit load.
Phases/Circuit: Calculated based on voltage type.
Cost of Energy Generation ($/MWh): Basis for economics.
CO2(kg/kWh): Basis for greenhouse gas calculations.
Load Increase/Year: Basis for 30 year calculations.
The revenue achievable during peak operating
conditions is a direct function of these two
inputs. But, this value is also related to themaximum sag condition set for the conductor.
See section 5.
Hours/Year at Peak Capacity (hr.)
Price of Energy at Peak Capacity ($/MWh)
2
-
8/12/2019 CCP Manual 2 6 1
10/20Copyright July 2013 CTC Global Corporation All Rights Reserved 10
Step 3: Selection of Conductors and Amps Calculations
All conductor information is
derived directly from the
manufactures conductorspecification and wire files.
Type: Choose from dropdown list.
Size (AlCode Word): Select a size for
that type of conductor for comparison.
Aluminum Area (mm2): The cross
sectional area of the Al only. Diameter (mm): Outside diameter of
the selected conductor size.
Rated Strength (kN): Rated maximum
tensile strength of the conductor.
Weight (kg/km): The unit weight of the
conductor.
DC Resistance at 20C (ohms/km):
Nominal DC resistance of the
conductor at 20C
AC Resistance at 25C/75C (ohms/km):
Nominal AC resistance of conductor at
25C and 75C
Conductors per phase: Number of conductor bundled in the phase
Circuits: Number of circuit to perform the line loss/CO2calculations.
Capacity ratings are dependent upon the environmental inputs:
Ampacity (A) at Temperature (C): User chooses a temperature at
which they want the ampacity calculated, based upon the inputted
environmental assumptions.
Ampacity (A) at Rated Operating Temp (C): Value is from the
database, shows the ampacity at the rated operating temperature of
the conductor, based upon the inputted environmental assumptions
Ampacity (A) at Maximum Temp (C): Value is from the database,
shows the ampacity at the rated operating temperature of the
conductor, based upon the inputted environmental assumptions
3
-
8/12/2019 CCP Manual 2 6 1
11/20Copyright July 2013 CTC Global Corporation All Rights Reserved 11
Step 3: Impact of conductor properties
Data in this section is used
to show ampacity, temperature
and sag. Type: First conductor type is the base
conductor, will impact the rest of the
comparisons. (Suggest ACCC conductor.)
Size (AlCode Word): Impact the
calculated capacity of the conductor.
Aluminum Area (mm2): Impact the
calculated capacity of the conductor.
Diameter (mm): Impact the capacity, and the
wind load sags.
Rated Strength (kN): Determine if factor of
safeties on the conductor are being meant and
will impact the sags.
Weight (kg/km): Impact the sags. DC Resistance at 20C (ohms/km): Impact the line
loss comparison, can chose a lower resistance
conductors to make comparisons against.
AC Resistance at 25C/75C (ohms/km): Impacts
the resistance, these values are used to calculate
the resistance at any other calculated
temperature of the conductor
Conductors per phase: Impact the line loss calculations, the more
conductors per phase, the lower the overall resistance of the
circuit.
Circuits: Impacts the line loss calculations, the more circuits, the
more line losses will be calculated in the comparison.
Ampacity (A) at Temperature (C): Choosing a specific
temperature, can show differences in ampacity at differenttemperatures that might be a larger interest to the user than the
rated and maximum temperatures.
Ampacity (A) at Rated Operating Temp (C): Can be used to
compare what the rated capacities will be.
Ampacity (A) at Maximum Temp (C): Can be used to compare
what the absolute maximum capacity of the line could be.
3
-
8/12/2019 CCP Manual 2 6 1
12/20Copyright July 2013 CTC Global Corporation All Rights Reserved 12
Step 4: Setting initial sag conditions
The project conditions for initial sag, tension and installation temperature will allow CCP
to calculate the sags at various operating conditions.
Ruling Span (m): The approximate average distance between two towers for each line section
used to determine all sags and tensions within that section. Larger spans in the section willinfluence this calculation the most.
Initial Sagging Temperature (C): The expected ambient temperature when initially stringing the
line.
Maximum Allowable Sag (m): Based on clearance requirements.
% RTS: The tension at initial sagging based on the rated tensile strength (RTS) of the conductor.
Can also be considered Ultimate Tensile Strength (UTS) and Rated Breaking Strength (RBS).
Sag at Initial Sagging Temperature (m): This number is calculated based on the initial tension in
the conductor.
Initial Tension as Sagging Temperature (kN): This number is calculated based on the percent RTS
of the conductor chosen at a given temperature.
4
-
8/12/2019 CCP Manual 2 6 1
13/20Copyright July 2013 CTC Global Corporation All Rights Reserved 13
Step 4: Impact of Initial Sagging Conditions
The initial tension, ruling span and installation temperature will have a significant
influence on the sags and the knee point temperature of the selected conductor.
Ruling Span (m): Set by the number of towers in a section of the line. The selection of a ruling can be affected
by clearance requirements, tower cost/height/strength, and conductor properties. The economics impact ofthe ruling span on a project are a complicated trade off of all of these factors.
Initial Sagging Temperature (C): The initial temperature is used as a basis to calculate sags at all other
temperatures. The impact of installation temperature needs to be considered for initial tension and final sag
conditions.
Maximum Allowable Sag (m): Based on clearance requirements, maximum sag may limit the ampacity of a
conductor with high thermal sag. This will impact each conductor individually.
% RTS: Ensure tension on the conductor does not exceed regulated limit, such as factor of safety thatdetermine the maximum tensions the conductor can exhibit under specific weather conditions.
Sag at Initial Sagging Temperature (m): Shows what the initial ruling span sag should be when the conductor is
newly installed.
Initial Tension as Sagging Temperature (kN): Shows the tension the conductor will exhibit when its first
installed.
4
-
8/12/2019 CCP Manual 2 6 1
14/20Copyright July 2013 CTC Global Corporation All Rights Reserved 14
Step 5: Set wind and ice conditions & Impacts
Ice/wind conditions typically cause
the largest loading on the towers.
Temperature (C): Temperature at which the worst
loading case (either ice or wind) would exist.
Windspeed (km/hr): Speed of the wind for a
specific worst weather case.
Safety Factor (N/m): An additional weight added
to the conductor to build in a factor of safety to
ensure the maximum tension on the towers is notexceeded.
Radial Ice Thickness (mm): The thickness of ice
formed on the line for a specific worst weather
case. This adds additional weight to the
conductor.
Ice Density (kg/m3): The density of ice during the
specific worst weather case.
These calculations do not consider dynamic
forces that affect the line, hardware or
appropriate safety factors for a project. These
strictly relate to the weather impact on sag
clearance.
Typical Range and Impact of Changes.
Temperature (C): The colder the weather, the moretension there is on the conductor.
The temperature should be equal to the expected
ambient temperature, not the operating temperature.
Windspeed (km/hr): The wind speed is translated into
a unit weight that is added to the conductor weight,
and adds additional sag and tension to the conductor.
Safety Factor (N/m): Typically set by country or utilityrequirements.
Radial Ice Thickness (mm): Set by regulatory
requirements.
Ice Density (kg/m3): Set by regulatory requirements.
5
-
8/12/2019 CCP Manual 2 6 1
15/20Copyright July 2013 CTC Global Corporation All Rights Reserved 15
Step 6: Evaluate line loss reduction and benefits
CCP uses the resistances of
the cables to calculate the
differences in temperature,line losses and CO2emission
Steady-State Temperature at
Peak Ampacity: Temperature of the conductor when operating at peak operating amps. Large differences in
temperature will lead to differences in line losses/CO2emissions between the selected conductors.
First Year Line Losses (MWh): The amount of line losses generated for the selected conductor. Is based upon the line
length, number of conductors per phase, the number of circuits, the resistance of the cable at the calculated
temperature and the load (loss) factor.
Comparisons are based on the conductor in the first column. When the number is positive, means the base conductor is
reducing the line losses/CO2generated over the other selected conductor. When the number is negative, means the base
conductor is increasing the line losses/CO2generated over the other selected conductor.
Base Conductor Reduces First Year CO2Generated by (MT): Shows the difference in the amount of CO2generated vs.
the base conductor.
Base Conductor Reduces First Year Line Losses by (MWh): Shows the difference in MWh the base conductorreduces/increases the line losses by.
Base Conductor Reduces First Year Line Losses by (%): Shows the difference, in percentage, the base conductor
reduces/increases the line losses by.
Base Conductor Reduces First Year Line Losses by ($/Year): Shows the amount of money the base conductor would
save/not save over the other conductors.
Base Conductor Line Loss Savings per meter of Conductor ($/m): Shows the line loss savings on a per meter of
conductor basis.
6
-
8/12/2019 CCP Manual 2 6 1
16/20Copyright July 2013 CTC Global Corporation All Rights Reserved 16
Step 7: Sag/Tension Calculations & Impacts
CCP uses manufacturers
specifications and wire files to
calculate the operating sag of the
conductor.
Sag at Peak Operating Amps (Temp/Sag/Tension):
Shows the sags for the selected conductors at the
user specified peak operating amps. The colors
coordinate with the values found in sections 3 & 6.
Sag at Rated Operating Temp (Temp/Sag/Tension):
The sag at the rated operating temperature of theselected conductors.
Sag at Maximum Temp (Temp/Sag/Tension): The sag at
the maximum operating temperature of the selected
conductors.
Temperature at Maximum Allowable Sag (Max.
Temp/Sag/Tension/Ampacity): Shows the temperature
at which the selected conductor reaches the maximumallowable sag, set by the user in section 5. Ampacity
values turn red when the selected conductors
maximum capacity cannot be reached due to being sag
limited.
Wind/Ice or Cold Temperature Sag/Tension
(Sag/Tension): Shows the sag for the ice/wind condition
specified by the user inputs.
Impacts of these sag/tension calculations:
Results show the differences in the sags of the
selected conductors at key temperatures
Show the impact of limiting the sags, and how the
limit may reduce the maximum capacity of the
selected conductor in order to ensure clearances arenot violated
7
-
8/12/2019 CCP Manual 2 6 1
17/20Copyright July 2013 CTC Global Corporation All Rights Reserved 17
Step 8: Visual sag presentation at temperature
A graphical representation of the sags as a
function of temperature, driven by
ampacity and maximum allowed
conductor temperature.
Shows the sags for the three conductors
selected
The bend in sag graph shows the location of
the knee point temperature
Below the knee point, the conductor
sags are dictated by the composite
conductor properties
Above the knee point, the conductor
sags are dictated by the core properties
alone
Sags are only shown for the range of
temperatures the conductor is rated to.
The maximum sag line is also shown, to
demonstrate where the potential sag limit
may be and how it will impact conductor
performance.
8
-
8/12/2019 CCP Manual 2 6 1
18/20Copyright July 2013 CTC Global Corporation All Rights Reserved 18
Step 9: Understand the long term impact
CCP performs basic 30 year line loss calculations and can calculate the potential revenue
when operating at peak amps for a certain number of hours per year
Base conductor Reduces 30 Year Line Losses by ($): Calculation is determined by the user inputted
year load increase, allows all conductors to grow in load until the maximum use temperature of the
base conductor is reached, and then cuts off the load growth. Calculation shows the differences in
the line loss savings between the base and selected conductors over a 30 year period with no
discount rate or NPV calculation performed.
Base Conductor Reduces 30 Year CO2Generated by (MT): As with the 30 year line loss calculation,
performs the same calculation for the CO2reduction.
Peak Power Available for Delivery (User inputted hrs.) (MWh): This peak capacity is determined by
the sag limitation shown in section 8. Calculation shows the peak power that is delivered at the end
of the line, minus the line losses over the line at peak capacity.
Potential Revenue for Power Delivered ($): Utility may charge a different selling price when the line
is operating at peak capacity. Knowing what the peak power delivered potential can be, is multiplied
by the cost of selling the power while at peak capacity. Shows differences in revenue each conductor
choice can achieve.
9
-
8/12/2019 CCP Manual 2 6 1
19/20Copyright July 2013 CTC Global Corporation All Rights Reserved 19
Step 10: Thermal Knee Point Calculation
CCP can calculate the thermal knee point temperature of each of the selected conductorsAll Bi-metallic conductors have a thermal knee point temperature
For conventional ACSR, the thermal knee point is typically above its maximum use
temperatureOther high temperature, low sag conductor types, this knee point transition typically occurs
within the operating range of the conductor
Thermal Knee Point is not a set value though, it is dependent on several factors:
1) Al/core area ratio
2) Span length (or ruling span length)3) Initial installation tension on the conductor
Thermal Knee Points results are:
A) Temperature at which the thermal knee point occurs at
B) The sag at the thermal knee point
C) The tension at which the thermal knee point
10
-
8/12/2019 CCP Manual 2 6 1
20/20
Additional CTC Application Engineering Support
The Application Engineering Group at CTC Global is ready to support your project in
a number of ways. Once a project questionnaire is received, which is also embedded into the CCP program, the
application engineering team will begin the process of selecting the best conductor for the project,
whether its a reconductoring or new line project
First evaluate the capabilities of the old conductor and looking at the project goals, determine which
ACCC option could potentially meet the requirements
Can perform sag/tension calculations based on known stress-strain curves for nearly every conductortype, using either PLS-CADD or Sag10 software packages, and verify the sags shown on CCP are close
to what these software programs would calculate for similar starting sagging conditions.
Once conductors are chosen, write up a technical summary of which conductors CTC Global feels can
meet the project requirements and send analysis back to the customer who requested the analysis.
Once a project is identified as being a potential project for the ACCC option, application engineers
can directly communicate with the engineer of the project to help with any additional analysis or
answer technical questions about the ACCC option for the project
CTC Global Application Engineers though are not line designers, but are able to help facilitate the
choice of using an ACCC option for a project