    Low-VoltageControlgear for Industry

    Order No.:E86060-K1002-A101-A4-7600

    LV 10 Contactors and contactor assemblies Semiconductorcontrolgear, soft starters, controllers Circuit-breakers Overload relays Load feeders Switch disconnectorsand fuses SIMIREL time, monitoring, coupling relaysand converters Control and signaling devices BETAelectrical installation technology: Selected products SIGUARD safety systems SIDAC-T transformers SIDAC-S power supplies ALPHA FIX terminal blocks

    Power DistributionProducts and Systems forPower Distribution

    Order No.:E86060-K1801-A101-A4-7600

    LV 30 BETA protect installation equipment Communication-capable circuit-breakers Compact circuit-breakers(MCCB) Air circuit-breakers (ACB) SENTRIC switchdisconnectors and fuse switch disconnectors Switch-gear, distribution systems and cabinets

    SIVACON 8PSBusbar Trunking Systems CD,BD01, BD2 up to 1250 A

    Order No.:E86060-K1870-A101-A1-7600

    LV 70 Busbar Trunking Units, Overview System CD (25 A - 40 A) System BD01 (40 A - 160 A) System BD2 (160 A - 1250 A)

    SIVACON 8PSBusbar Trunking Systems CD,BD01, BD2 up to 1250 A

    Order No.:E86060-P1870-A101-A2-7600

    LV 70 P Price List

    System CD (25 A - 40 A) System BD01 (40 A - 160 A) System BD2 (160 A - 1250 A)

    SIVACON 8PSBusbar Trunking SystemsBD2A/BD2C, LDA/LDCfrom 160 A to 5000 A

    Order No.:E86060-T1871-A101-A1-7600

    LV 71 T Technical Information

    System Overview BD2A/BD2C System LDA/LDC System Further Information

    SIVACON 8PSBusbar Trunking SystemsLXA/LXC over 800 A

    Order No.:E86060-T1872-A101-A1-7600

    LV 72 T Technical Information

    System Overview LXA/LXC System Further Information

    Automation and DrivesThe Offline Mall for A&D

    Order No.:E86060-D4001-A110-C3-7600

    CA 01 All the products from Automation and Drives includingthe products from the catalogs listed above.

    A&D Mall

    Internet:http://www.siemens.de/automation/mall

    All the products from Automation and Drives includingthe products from the catalogs listed above.

    Registered trademarks Explanations

    All product designations may be registered trademarksor product names of Siemens AG or other supplyingcompanies. Third parties using these trademarks orproduct names for their own purposes might infringeupon the rights of the trademark owners.

    Further information about low-voltage switchgear andcontrolgear is available on the Internet at:

    http://www.siemens.com/lowvoltage

    Type:If a type designation contains * characters, it is notcomplete and must be supplemented according to specifi-cations in the list.

    Order No.: For an order, BVP: must be placed before theOrder No. stated in the catalog (034262 --> BVP:034262).

    Packaging size (PS):The packaging size defines thenumber of units, sets or meters, for outer packaging.Only the quantity defined by the packaging size or amultiple thereof can be ordered!

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    3/180

    s

    Invalid: LV 71 2004/2005Errata Sheet for LV 71 2004/2005

    Siemens AG 2005

    SIVACON 8PSBusbar TrunkingSystems LDA/LDCfrom 1100 to 5000 A

    Catalogue LV 71 2005

    Introduction

    Busbar Trunking Systems,Overview

    LD Busbar Trunking System

    Annex

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    4/180Siemens LV 71 20052

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    5/180Siemens LV 71 2005

    1/2 Welcome to Automation and Drives

    1/3 Low-voltage switchgear the basis for progressive solutions

    1/4 Totally Integrated Automation innovations for more productivity

    1/6 Totally Integrated Power energy distribution and managementfrom one source

    1/8 SIVACON 8PS Busbar Trunking Systems in Action

    1/10 SIVACON 8PS Engineering Tools for preciselydimensioned, economical solutions

    Introduction

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    6/180

    1/2

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    7/1801/3

    Low-voltage switchgear and controlgear

    the basis for progressive solutions

    Everyday life would be unimaginable without electric power. Competence and innovations

    in switching and electrical installation technology are prerequisites so that power can be

    used without danger and user-friendly in industrial facilities and buildings. We have been

    providing you with these prerequisites for more than 110 years and are permanently de-

    veloping new features innovations which permit you to use power more safely and eco-

    nomically.

    Low-voltage switchgear from Siemens offers a comprehensive and innovative range of

    products covering switching devices for load feeders or the distribution of power, control

    and signaling devices as well as complete cabinet systems. Multi-functional, uniform con-

    cepts such as Totally Integrated Power, Safety Integrated or ECOFAST additionally permit

    our product portfolio to be combined into optimized systems.

    All in all, we can provide you with innovative components for switching and electrical in-

    stallation technology which utilize state-of-the-art features such as integration and com-

    munication as the basis for advanced and uniform solutions which provide you with many

    benefits.

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    8/1801/4

    PROCESS FIELD

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    9/1801/5

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    10/1801/6

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    11/1801/7

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    12/1801/8

    The BD 01 system is quick to install and

    ideally suited for use in workshops andtrade premises, as here, at a photo-graphers.

    In the petrochemical industry, it is the PEC system that providesreliable and fault-free power supply.

    The ideal system for production linesneeding a great deal of power is theLD system up to 5000 A.

    SIVACON 8PS

    Busbar Trunking Systems in Action

    Busbar trunking systems in the low-voltge range

    perform the safe and reliable transmission and

    distribution of electrical power from transformer

    via main distribution board and sub-distribution

    board right to the load. Siemens busbar trunking

    systems are the complete and efficient answer

    in this area:

    The CD system for 25 A to 40 A

    The BD01 system for 40 A to 160 A

    The BD2 system for 160 A to 1250 A

    The PEC system for 800 A to 6000 A

    The LD system for 1100 A to 5000 A

    The LX system for 800 A to 6300 A

    Alle these systems are Type-tested LV switch-

    gear assemblies (TTA) to IEC 60 439-1 and -2.

    This ensures that they offer a standard of safety

    and reliability that meets the particularly high

    performance expectations of automated pro-

    duction and for building services provision.

    Performance characteristics:

    Clear network structure

    Unproblematic retrofitting in the event of load

    changes

    Low operating costs due to uninterrupted ser-

    viceability

    Simple planning and installation

    Room-covering systems for lighting installa-

    tions and small loads

    The CD system (up to 40 A) allows you to supply

    lighting installations covering the whole expan-

    se of, say, furniture showrooms, supermarkets

    or greenhouses with power, and also provides

    the means to easily fix them in position.

    Due to its pleasing appearance, the equipment

    is well suited for use in sales rooms visited by

    the public. On the other hand, its high degree ofprotection, to IP54, allows the CD system to be

    used even in harsh environments.

    The power source for loads with no fixed

    location

    The BD01 system is ideally suited for the power

    supply (up to 160 A) in workshops and trade

    premises. The trunking units are easy and quick

    to put together. The anti-rotation feature on the

    tap-off units makes sure that the units are

    correctly fitted and allows for easy retrofitting

    even while the production is running.

    Other benefits: minimum stock holding and un-

    complicated planning due to one standard

    frame size for five different current ratings.

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    13/1801/9

    Universal power distribution

    The BD2 system (up to 1250 A) can supply

    power to medium-size loads in buildings and in

    all industrial applications. Prefabricated tap-off

    units fitted with many differing component

    combinations make this equipment universally

    applicable. Two standard frame sizes covering

    all current ratings simplify stock keeping and

    planning.

    Safe and reliable power transmission in the

    petrochemical industry

    The PEC resin-insulated system, up to 6000 A,

    has a high degree of insulation protection and

    thus an enormous resistance to external interfe-

    rence factors. This ensures safe and reliable

    transport of power even in rough weather or in

    highly dust and dirt and corrosion polluted

    industrial environments. Typical applications of

    this system is the petrochemical industry, waste

    incinerators and power stations.

    High system serviceability in production

    The louvred LD busbar trunking system, up to5000 A, is the system for transporting current in

    production lines with a large energy require-

    ment, such as in the automotive industry. A

    separate PE busbar ensures that the protective

    device in such a system responds reliably even

    if the current paths are relatively long. The high

    short-circuit rating allows medium-voltage

    switches to be used as protective elements for

    the transmission of power between transformer

    and main circuit-breaker. Tap-off units up to

    1250 A available as standard.

    Flexible power distribution in multi-storey

    buildingsThe LX sandwich-style system, up to 6300 A, is

    used where large quantities of power need to be

    transported, uninfluenced by the mounting posi-

    tion of the system.

    Conductor configurations with the PE conductor

    insulated along its entire length, and a double-

    size neutral can ensure the interference-free dis-

    tribution of power in places such as radio

    stations, computer centres or at internet

    providers. The system is protected to IP54 as

    standard, and tap-off units up to 1250 A availa-

    ble as standard.

    Siemens offers modular component cabinets for indication, control and monitoring of theflow of power through busbar trunking systems. These cabinets are equipped with businterfaces, control circuit devices and power meters.

    The LX busbar trunking system is the perfect equipment for multi-storey buildings where large quantities of power need to be transpor-ted, uninfluenced by the mounting position of the system.

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    14/1801/10

    Engineering tools from Siemens help generate

    precisely dimensioned and economical plan-

    ning and design solutions, even for complex ap-

    plications.

    MatSelect

    Using MatSelect, product and material data can

    be administered with self designed or

    standardised classification systems. It has inter-

    faces to Eldanorm, Datanorm, ASCII format and

    ProPlan.

    NetPlan

    Planning software for power flow, short-circuit

    calculation and device dimensioning with selec-

    tivity analysis and protective against electric

    shock of low-voltage networks, available in

    English, German, French and Italian.

    NetSelect

    Selection software for protective switches to en-

    able star networks to be correctly dimensioned;

    available in several languages.

    BusbarSelect

    Selection aid for generating quotations, invitati-

    ons to tender and orders for busbar trunking

    systems up to 1250 A; available in several

    languages.

    Quotation texts

    Prepared texts (in German) for generating

    customer specifications in the formats: Architext

    excellent, GAEB 81 and Word 97.

    Should you have any queries concerning instal-lation, functionality or application options

    please mail us at

    [email protected]

    We will be pleased to assist you.

    NetPlan enables you to graphically represent the network and tocalculate the load flow and the prospective one-pole to all-pole shortcircuitcurrent/load.

    In BusbarSelect, you select the trunking units for your system from a menu,and then transfer them into an order or quotation list.

    SIVACON 8PS - Engineering Tools for

    precisely dimensioned, economical solutions

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    15/180Siemens LV 71 2005

    2/2 Technical Overview

    2/4 System Overview

    Busbar Trunking Systems,Overview

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    16/180

    Technical Overview

    Siemens LV 71 20052/2

    Busbar Trunking Systems, Overview

    Busbar trunking systems Ratedcurrent

    A

    Rated operationalvoltage

    V AC

    Frequency

    Hz

    Number ofactive conductors

    Degree ofprotection

    Ambienttemperaturemin./max.C

    CD 3040225

    400 50 ... 60 2, 3, 4, 24(PE = enclosure)

    IP54 5/+40

    BD01 4063100125160

    400 50 ... 60 4(PE = enclosure)

    IP54 5/+40

    BD2ABD2C

    160 ... 400500 ... 1250

    690 50 ... 60 5 IP52,IP54 withaccessories,IP55 on request

    5/+40

    LDA1 LDA8LDC2 LDC8

    1100 ... 40002000 ... 5000

    1000 50 ... 60 4 or 5 IP34,IP54

    5/+40

    LXA01 LXA10LXC01 LXC10

    800 ... 45001000 ... 6300

    690 50 ... 60 3, 4, 5, 6(PE = enclosure)

    IP54,IP55 with

    accessories

    5/+40

    NSV0_00201

    NSV0_00241

    NSV0_00421

    NSV0_00681

    NSV0_00321

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    17/180

    Technical Overview

    Siemens LV 71 2005 2/3

    Busbar Trunking Systems, Overview

    2

    Mountingposition

    Length

    m

    Tap-off points Tap-off units Material Combustiveenergy

    kWh/m

    Edgewise 23

    On one side:every 0.5 or 1 mOn both sides:

    every 0.5 or 1 m

    Up to 16 A InsulatedCu conductors,painted sheet

    steel housing

    0.1 ... 0.48

    Edgewise,flat(tap-off pointsdownwards)

    23

    On one side:every 0.5 or 1 m

    Up to 63 A InsulatedAl or Cuconductors,painted sheetsteel housing

    0.76 Can be combined with networkabletap-off units for lighting control sys-tems

    Edgewise,flatand vertical

    0.5 ... 3.25 Without,on both sides:every 0.25 or0.5 m offset

    Up to 400 A Al or Cu busbars,painted sheetsteel housing

    0.6 ... 0.67(without tap-offpoints)

    Can be combined with networkabletap-off units for lighting control sys-tems, remote switching and load mon-itoring

    Horizontal,edgewiseand vertical

    0.5 ... 3.2 Without,on one side:every 1 m,on both sides:every 1 m

    Up to 1250 A InsulatedAl or Cu busbars,painted sheetsteel housing

    4.16 ... 8.83(without tap-offpoints)

    Information about the LD andLX systems: from yourSiemens sales outlet.

    Can be combined with networkabletap-off units for remote switching andload monitoring

    Horizontal,edgewise

    and vertical

    0.35 ... 3 Without,on one side:

    every 0.5 m,on both sides:every 0.5 m

    Up to 1250 A InsulatedAl or Cu busbars,

    painted alumini-um housing

    1.95 ... 11.07(without tap-off

    points)

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    18/180

    System Overview

    Siemens LV 71 20052/4

    Busbar Trunking Systems, Overview

    6

    6

    6

    3

    2

    1

    5

    4

    6

    10

    DB

    DB

    BK-10

    -10DB

    BK

    28600_

    0VSN

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    19/180

    System Overview

    Siemens LV 71 2005 2/5

    Busbar Trunking Systems, Overview

    2

    Up to 40 A

    CD system 1

    Reduced planning costs by simplified engineering

    Quick-release plug-in connection for fast assembly

    Tap-off points on both sides for optimized utilization of the busbar

    Even electrical loading of the CD system conductors achieved by connect-ing an equal number of tap-off plugs to each individual phase

    Versatility through high degree of protection to IP54 of the standardversion

    Tap-off plugs allow fast, flexible load relocation (even on live sytems).

    a Catalog LV 70

    Up to 160 A

    BD01 system 2

    Flexible power supply

    Junction units for changes in direction

    Quick, straightforward planning

    Time-saving assembly

    Reliable mechanical and electrical connections

    High level of stability, low weightPositive opening and closing of tap-off points

    Versatile tap-off units

    Few basic elements

    Modular system reduces stock-holding

    High degree of protection to IP54 with tap-off points at sides and bottomfor extreme ambient conditions, otherwise IP50.

    a Catalog LV 70

    Up to 1250 A

    BD2 system 3

    Quick, straightforward planningTime-saving, cost-efficient assembly

    Reliable, safe operation

    Flexible modular system with simple solutions for every application

    Early planning of power distribution possible without precise knowledge ofconsumer locations

    Fast operational readiness through quick, easy assembly

    High degree of protection to IP54 for use in harsh industrial environments

    Innovative construction:No compensating units for expansion compensation required.

    a Catalog LV 70

    Up to 5000 A

    LD system 4

    The busbar trunking system for optimized power distribution in industry.

    Reliable, safe operation

    Time-saving, cost-efficient assembly

    Space-saving compact construction type up to 5000 A in an enclosure

    Plug-in tap-off units up to 1250 A

    Type-tested connection to service distribution boards and transformers

    a Chapter 3

    Up to 6300 A

    LX system 5

    The busbar trunking system for power transmission and distribution inbuildings.

    Detailed information about this system is available from your Siemens salesoutlet.

    Catalog LV 72

    PEC system

    The busbar trunking system for power transmission under extreme environ-mental conditions (IP68).

    Detailed information about this system is available from your Siemens salesoutlet.

    Networkable busbar trunking system 6

    Networkable function expansions for combination with known tap-offunits

    Applications: large area lighting control systems remote switching and signalling in industrial applications load monitoring of decentral power tap-offsEIB, AS-i and PROFIBUS bus systems

    Quick, straightforward planning

    Flexible with expansion and modification

    Module system

    Can be retrofitted to existing installations

    Simple contact establishment of bus line with insulation displacementconnection feature

    Can be used with the BD01, BD2, LD, and LX systems

    Design software

    BusbarSelectDesign software for busbar trunking systems up to 1250 A

    This CD-ROM is available free of charge from your Siemens sales outlet.

    Technical Information

    LV 71.T

    Planning guideSIVACON 8PSBusbar trunking systems BD2A/BD2C and LDA/LDC from 160 A to 5000 A

    LV72.T

    Planning guideSIVACON 8PSBusbar trunking systems LXA/LXC over 800 A

    These planning aids are available from your Siemens sales outlet.

    Leaflet

    E20001-A220-P309

    SIVACON 8PSSafe and flexible power distribution up to 6300 A

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    20/180

    Notes

    Siemens LV 71 20052/6

    Busbar Trunking Systems, Overview

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    21/180Siemens LV 71 2005

    3/2 System overview

    Selection and ordering data

    3/6 Straight trunking units

    3/10 Branch and junction units

    3/22 Distribution board connection units

    3/28 Connection units

    3/40 Reduction units

    3/41 Tap-off units

    3/46 Accessories

    Technical data

    3/48 Trunking units

    3/60 Connection units

    3/61 Tap-off units

    3/64 Weights

    Engineering

    3/68 Basics

    3/77 Dimensioning of busbar runs,Production of parts lists

    3/82 Incoming connections

    3/91 Fire barrier

    3/95 Expansion compensation and fixed po

    3/99 Examples

    3/106 Tap-offs

    3/112 Special cases

    Dimensions

    3/118 Straight trunking units

    3/119 Connection units

    3/140 Tap-off units

    3/146 Accessories

    LD Busbar Trunking System

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    22/180

    System Overview

    Siemens LV 71 20053/2

    LD Busbar Trunking System

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    23/180

    System Overview

    Siemens LV 71 2005 3/3

    LD Busbar Trunking System

    3

    Straight trunking units 3

    Without or with f ire barrier,fire resistance class S 120 to DIN 4102 Part 9

    Degree of protection IP34 and IP54

    4- and 5-conductor systems

    Standard lengths of 1.6 m/2.4 m/3.2 m Optional lengths of 0.5 ... 3..19 m

    for horizontal and vertical installationStraight trunking units with tap-off points

    Tap-off points above, below or at both sides

    Coding brackets as protection against incorrect fitting

    (key-lock principle) protection against confusing tap-off units

    (4/5-conductor system) sliding contacts for PE in 5-conductor systems

    IP20 touch protection with the tap-off point open

    Page 3/6

    Connection/feeder units 5

    Incoming transformer connection, enclosed for rated currents from 1100 ... 5000 A connecting lugs for all standard clearances phase sequence as required

    Incoming distribution board connection for rated currents from 1100 ... 5000 A phase sequence as required

    Incoming cable connection for rated currents from 1100 ... 2500 A cable entry via cable grommets with cable supporting

    rail

    Page 3/28

    Branch and junction units 4

    Flexible engineering for matching to buildingconstruction, with elbow (L unit flat), offset elbow knee (L unit edgewise), offset knee Z unit T unit U unit

    Without or with fire barrier

    Page 3/10

    Tap-off units 2

    Modification possible while the system is energized

    Leading PE(N) connecting contact during mounting

    IP20 touch protection of the contact assembly duringfitting and removing

    Coding brackets

    Sealing

    Cable entry at the side with additional cablecompartment

    Safety by specified sequence of fitting/removal

    Sheet steel enclosure with IP30 or IP54 degree ofprotection resulting from additional cover

    Page 3/35

    Distribution board connection units 6

    For distribution board connection toSiemens SIVACON PV Power Distribution System

    from above from below

    Page 3/22

    Accessories 1

    End flanges

    Distribution board blank plates

    Protective sleeves

    Fixing brackets

    Suspension brackets

    Torque spanner

    Page 3/40

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    24/180

    System OverviewType key

    Siemens LV 71 20053/4

    LD Busbar Trunking System

    Straight trunking units, junction units and distribution board connection units

    LD connection units2)

    Notes:

    N/PEN = 1/2L,possible from LD.4... to LD.8...

    Rated current le[A]

    IP31 IP54 IP31/IP54 CodeNo.Horizontal edgewise

    including offsetsHorizontaledgewiseandvertical

    Horizontalflat

    < 1.3 m > 1.3 m

    Al Cu Al Cu Al Cu Al Cu1100 950 900 700 1

    1250 2000 1100 1650 1000 1600 750 1200 2

    1600 2600 1250 2100 1200 2000 1000 1550 3

    2000 1700 1500 1200 4

    2500 2100 1800 1700 5

    3000 3400 2300 2700 2000 2600 1800 2000 6

    3700 4400 2800 3500 2400 3200 2200 2600 7

    4000 5000 3400 4250 2700 3600 2350 3000 8

    Conductor material

    Al A

    Cu C

    Version

    4 4-conductor

    6 5-conductor

    N/PEN

    1 1/2L

    2 L

    Degree of protection

    3 IP34 (31)1)

    5 IP54

    Fire barrier

    120 ALDA 1 LDA 3LDC 2 LDC 3

    120 BLDA 4 LDA 8LDC 6 LDC 8

    Fire barrier

    Positioning of(X*, Y*, Z*)(see Engineering)

    LD -.... +LD-L -

    Type Type suffix

    Notes:

    N/PEN = 1/2L,possible from LD.4... to LD.8...

    1) IP31 for horizontal flat units.2) Horizontal/edgewise

    with connecting lugs below.3) IP54 on request.

    Rated current le[A]

    IP31 CodeNo.Horizontal/

    edgewiseSystem

    Al Cu LDA LDC

    1100 1

    31250 2000 2 2

    1600 2600 3 3

    2000 4

    62500 5

    3000 3400 6 6

    3700 4400 7 7 7

    4000 5000 8 8 8

    Conductor material

    Al A

    Cu C

    Version

    4 4-conductor6 5-conductor

    N/PEN

    1 1/2L

    2 L

    Degree of protection

    3 IP34 (31)3)

    Type lug clearance [mm]

    State of

    delivery

    Adjustable

    on site

    1 150 ... 160 165 ... 180

    2 190 ... 280 285 ... 380

    3

    450 ... 600 610 ... 750

    PEN(N)-L2200 ... 300

    PEN(N)-L2200 ... 400

    4

    450 ... 600 605 ... 750

    PEN(N)-L3(1)150 ... 250

    PEN(N)-L3(1)250 ... 350

    LD -.... +AS

    Type

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    25/180

    System OverviewImportant notes

    Siemens LV 71 2005 3/5

    LD Busbar Trunking System

    3

    Please note the following for selection and ordering:

    Dimensions

    Length details in the selection tables are quoted in metres(m). Optional lengths may be chosen in 0.01 m stages.

    Type

    All types designated with * must be completed by the cor-responding dimension. Add the type suffix to the type ifappropriate.

    Type suffix

    The type suffixes, e. g. fixed point, fire barrier, flange pla-te, and phase sequence, must always be quoted togetherwith the type.

    Type suffix for fire barrier

    For the fire barrier type suffix, the distance from the hookend (+LD-....-X*) or bolt end (+LD-L....-Y*) to the center ofthe fire barrier must be entered in metres (m).The minimum distance from the hook or bolt end to thecenter of the fire barrier must be observed.

    Type key

    The LDA/LDC type keys are shown on the opposite page.For selecting complete types, these type keys must betransferred to the selection tables.

    In special cases, the type key is to be found on the selec-tion page itself: for example for tap-off units and cableconnection units.

    Legend

    Order number supplement

    For an order, BVP:mut be placed before the ordernumber stated in the catalog.

    Example: the order number in the catalog is 034262.When placing an order, please write BVP:034262.

    Dimension Description Dimension Description

    A Length of the fitted unit (straight) T For T units: Length of the basic trunking unit

    AD Distance between the center of tap-off pointand the trunking unit end at the hook

    TX Distance from center of the T branch to theunit end at the hook

    AD min Minimum distance between the center ofthe tap-off point and the trunking unit end

    TY Distance from the center of the T branch tounit end at the bolt

    AX Unit fitted: Length of the X leg W Optional length

    AY Unit fitted: Length of the Y leg X Length of the X leg

    D Length of expansion compensation units Y Length of the Y leg

    DX Distance between the center of the expan-sion compensation unit and the trunkingunit end at the hook

    Z Length of the Z leg

    S Standard length

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    26/180

    Selection and Ordering DataStraight trunking units for horizontal installation without tap-off points

    Siemens LV 71 20053/6

    LD Busbar Trunking System

    Length

    S/W/D

    m

    Type

    Type suffix

    Fire barrier

    Type suffix

    Fixed point

    Standard lengths

    3.2 LD.....-3,2 +LD-L....-X* +LD-FP

    2.4 LD.....-2,4 +LD-L....-X* +LD-FP

    1.6 LD.....-1,6 +LD-L....-X* +LD-FP

    Optional lengths

    0.50 ... 0.89 LD.....-1W* +LD-FP

    0.90 ... 1.59 LD.....-2W* +LD-L....-X* +LD-FP

    1.61 ... 2.39 LD.....-3W* +LD-L....-X* +LD-FP

    2.41 ... 3.19 LD.....-4W* +LD-L....-X* +LD-FP

    Optional lengths with double bolt

    0.50 ... 0.89 LD.....-J-1W* +LD-FP

    0.90 ... 1.59 LD.....-J-2W* +LD-L....-Y* +LD-FP

    1.60 ... 2.39 LD.....-J-3W* +LD-L....-Y* +LD-FP

    2.40 ... 3.20 LD.....-J-4W* +LD-L....-Y* +LD-FP

    Expansion compensation

    1.20DX= 0.6Expansion =

    LD.....-D

    Fire barrier note:

    Fire barrier can be used for LD.1...- to LD.7...from 0.92 m (0.96 m for double bolt) and for LD.8...-from 1.12 m(1.16 mfor double bolt) length.

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-2W1,4,

    +LD-L120A-X0,54

    S

    W

    W

    D

    Dx

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    27/180

    Selection and Ordering DataStraight trunking units for horizontal installation with tap-off points

    Siemens LV 71 2005 3/7

    LD Busbar Trunking System

    3

    Length

    W

    m

    Position1)of the

    tap-off points

    AD (m)

    Type

    Type suffix

    Fixed point

    Standard lengths with 3 tap-off points

    3.2 0.6 + 1.6 + 2.6

    above LD.....-K-3,2-3AD +LD-FP

    bottom LD.....-K-3,2-3ADU +LD-FP

    above or bottom LD.....-K-3,2-3ADO+U +LD-FP

    Standard lengths with 2 tap-off points

    3.2 0.8 + 2.4

    above LD.....-K-3,2-2AD +LD-FP

    bottom LD.....-K-3,2-2ADU +LD-FP

    above or bottom LD.....-K-3,2-2ADO+U +LD-FP

    Standard lengths with 1 tap-off point

    3.2 2.4

    above LD..-K-3,2-AD2,4 +LD-FP

    bottom LD..-K-3,2-ADU2,4 +LD-FP

    above or bottom LD..-K-3,2-ADO+U2,4 +LD-FP

    3.2 0.8

    above LD..-K-3,2-AD0,8 +LD-FP

    bottom LD..-K-3,2-ADU0,8 +LD-FP

    above or bottom LD..-K-3,2-ADO+U0,8 +LD-FP

    1) Position of the tap-off point ...-AD(U) (O+U)* from the hook end. Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-K-3,2-3AD

    LDA4623-K-3,2-2ADU

    S

    AD

    S

    ADADmin

    S

    AD

    S

    AD

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    28/180

    Selection and Ordering DataStraight trunking units for horizontal installation with tap-off points

    Siemens LV 71 20053/8

    LD Busbar Trunking System

    Length

    W

    m

    Position1)of the

    tap-off points

    AD (m)

    Type

    Type suffix

    Fixed point

    Optional lengths with 2 tap-off points

    Minimum distance between the tap-offpoint and the trunking unit end AD 0.6 m

    2.20 ... 2.40 above LD.....-K-2W*-2AD* +LD-FP

    bottom LD.....-K-2W*-2ADU* +LD-FP

    above or bottom LD.....-K-2W*-2ADO+U* +LD-FP

    first fixed at 0.6,second variable at1.4 ... 1.8in stages of 0.2

    2.41 ... 3.20 above LD.....-K-3W*-2AD* +LD-FP

    bottom LD.....-K-3W*-2ADU* +LD-FP

    above or bottom LD.....-K-3W*-2ADO+U* +LD-FP

    first fixed at 0.6,second variable at1.4 ... 2.6

    in stages of 0.2

    Optional lengths with 1 tap-off point

    1.20 ... 1.60 above LD.....-K-1W*-AD* +LD-FP

    bottom LD.....-K-1W*-ADU* +LD-FP

    above or bottom LD.....-K-1W*-ADO+U* +LD-FP

    variable at0.6 ... 1.0in stages of 0.2

    1.61 ... 2.40 above LD.....-K-2W*-AD* +LD-FP

    bottom LD.....-K-2W*-ADU* +LD-FP

    above or bottom LD.....-K-2W*-ADO+U* +LD-FP

    variable at0.6 ... 1.8in stages of 0.2

    2.41 ... 3.20 above LD.....-K-3W*-AD* +LD-FP

    bottom LD.....-K-3W*-ADU* +LD-FP

    above or bottom LD.....-K-3W*-ADO+U* +LD-FP

    variable at0.6 ... 2.6in stages of 0.2

    1) Position of the tap-off point ...-AD(U) (O+U)* from the hook end. Complete ordering details:

    See Type key/Important notes

    (System overview, pages 3/4 and 3/5)Examples: LDA1423-K-2W2,20-ADU1,4 +LD-FPLDA4623-K-3W2,60-AD1,6

    W

    ADAD

    min

    W

    AD

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    29/180

    Selection and Ordering DataStraight trunking units for vertical installation, always with expansion and fixed point

    Siemens LV 71 2005 3/9

    LD Busbar Trunking System

    3

    Length

    S/W

    m

    Position1)of the

    tap-off points

    AD (m)

    Type

    Type suffix

    Fire barrier

    Standard lengths

    3.2 LD.....-V-3,2 +LD-L....-X*

    2.4 LD.....-V-2,4 +LD-L....-X*

    Optional lengths

    2.29 ... 2.80 LD.....-V-1W* +LD-L....-X*

    2.81 ... 3.00 LD.....-V-2W* +LD-L....-X*

    3.01 ... 3.19 LD.....-V-3W* +LD-L....-X*

    Standard lengths with 1 tap-off point

    above

    3.2 1.4 LD.....-K-V-3,2-AD1,4 +LD-L....-X*

    3.2 1.8 LD.....-K-V-3,2-AD1,8 +LD-L....-X*

    2.4 1.4 LD.....-K-V-2,4-AD1,4

    Optional lengths with 1 tap-off point

    above

    2.29 ... 2.80 1.4 LD.....-K-V-1W*-AD1,4 +LD-L....-X*

    1.8 LD.....-K-V-1W*-AD1,8

    2.81 ... 3.00 1.4 LD.....-K-V-2W*-AD1,4 +LD-L....-X*

    1.8 LD.....-K-V-2W*-AD1,8

    3.01 ... 3.19 1.4 LD.....-K-V-3W*-AD1,4 +LD-L....-X*

    1.8 LD.....-K-V-3W*-AD1,8 +LD-L....-X*

    1) Position of the tap-off point ...-AD(U) (O+U)* from the hook end.

    Fire barrier note:Minimum fire barrier dimensions owing to integrated expansion compensation:For LD.1...- to LD.8...-: X 1,10.For AD 1.8trunking units, the fire barrier is possiblefromX 2.45on.For AD 1.4trunking units, the fire barrier is possible fromX 2.05on.

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-V-1W2,60 +LD-L120A-X1,8

    LDA4623-K-V-2W2,90-AD1,4

    S

    W

    S

    AD

    W

    AD

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    30/180

    Selection and Ordering DataJunction units for horizontal installation

    Siemens LV 71 20053/10

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Elbow trunking units

    right

    X 0.5/Y 0.5 LD.....-LR

    X 0.51 ... 1.24/Y 0.5 LD.....-LR-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LR-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LR-X*/Y* +LD-L....-X*+LD-L....-Y*

    left

    X 0.5/Y 0.5 LD.....-LL

    X 0.51 ... 1.24/Y 0.5 LD.....-LL-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LL-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LL-X*/Y* +LD-L....-X*+LD-L....-Y*

    Z trunking units, flat

    right

    X 0.5/Y 0.5Z 0.36 ... 0.99 with LD.1 to LD.3Z 0.48 ... 0.99 with LD.4 to LD.8

    LD.....-ZR-Z*

    left

    X 0.5/Y 0.5Z 0.36 ... 0.99 with LD.1 to LD.3Z 0.48 ... 0.99 with LD.4 to LD.8

    LD.....-ZL-Z*

    Fire barrier note:

    Fire barrier possible with optional length from

    X 0.86or Y 0.90with LD.1...- to LD.3...-X 0.92or Y 0.96with LD.4...- to LD.7...-X 1.12or Y 1.16with LD.8...-

    Complete ordering details:

    See Type key/Important notes

    (System overview, pages 3/4 and 3/5)Examples: LDA1423-LR-X1,22 +LD-L120A-X0,65

    LDA4623-ZL-Z0,84

    YX

    X

    Y

    Z

    Y

    X

    Y

    Z

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    31/180

    Selection and Ordering DataJunction units for horizontal installation

    Siemens LV 71 2005 3/11

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    U trunking units, flat

    right

    X 0.5/Y 0.5Z 0.46 ... 0.99 with LD.1 to LD.3

    Z 0.58 ... 0.99 with LD.4 to LD.8

    LD.....-UR-Z*

    left

    X 0.5/Y 0.5Z 0.46 ... 0.99 with LD.1 to LD.3Z 0.58 ... 0.99 with LD.4 to LD.8

    LD.....-UL-Z*

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA4623-UL-Z0,84

    Y

    ZX

    X

    ZY

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    32/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 20053/12

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Knee trunking units

    front

    X 0.5/Y 0.5 LD.....-LV

    X 0.51 ... 1.24/Y 0.5 LD.....-LV-X* +LD-L....-X*X 0.5/Y 0.51 ... 1.24 LD.....-LV-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LV-X*/Y* +LD-L....-X*+LD-L....-Y*

    rear

    X 0.5/Y 0.5 LD.....-LH

    X 0.51 ... 1.24/Y 0.5 LD.....-LH-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LH-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LH-X*/Y* +LD-L....-X*+LD-L....-Y*

    Z trunking units, edgewise

    front

    X 0.5/Y 0.5Z 0.36 ... 0.99

    LD.....-ZV-Z*

    rear

    X 0.5/Y 0.5Z 0.36 ... 0.99

    LD.....-ZH-Z*

    Fire barrier note:

    Fire barrier possible for elbow units with optional length fromX 0.86or Y 0.90with LD.1...- to LD.7...-X 1.06or Y 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-LV-X1,22 +LD-L120A-X0,65

    Y

    X

    Y

    X

    Z

    X

    Y

    Z

    Y

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    33/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 2005 3/13

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    U trunking units, edgewise

    front

    X 0.5/Y 0.5Z 0.5 ... 0.99

    LD.....-UV-Z*

    rear

    X 0.5/Y 0.5Z 0.5 ... 0.99

    LD.....-UH-Z*

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-UV-Z0,89

    Z

    X

    Y

    Z

    X

    Y

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    34/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 20053/14

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset knee trunking units

    front right

    X 0.5/Y 0.5 LD.....-LVR

    X 0.51 ... 1.24/Y 0.5 LD.....-LVR-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LVR-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LVR-X*/Y* +LD-L....-X*+LD-L....-Y*

    front right with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LVR-Z* +LD-L....-Z*

    rear right

    X 0.5/Y 0.5 LD.....-LHR

    X 0.51 ... 1.24/Y 0.5 LD.....-LHR-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LHR-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LHR-X*/Y* +LD-L....-X*+LD-L....-Y*

    rear right with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LHR-Z* +LD-L....-Z*

    Fire barrier note:

    Fire barrier possible for offset elbow units with optional length fromX 0.86or Y 0.90or Z 0.84with LD.1...- to LD.3...-X 0.92or Y 0.90or Z 0.90with LD.4...- to LD.7...-X 1.12or Y 1.10or Z 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-LVR-X1,22 +LD-L120A-X0,65

    LDA4623-LHR

    Y

    X

    Z

    YX

    Y

    X

    Y

    X Z

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    35/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 2005 3/15

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset knee trunking units

    front left

    X 0.5/Y 0.5 LD.....-LVL

    X 0.51 ... 1.24/Y 0.5 LD.....-LVL-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LVL-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LVL-X*/Y* +LD-L....-X*+LD-L....-Y*

    front left with Z dimension

    X 0,5/Y 0,5Z 0,36 ... 1,30 with LD.1 to LD.3Z 0,42 ... 1,30 with LD.4 to LD.8

    LD.....-LVL-Z* +LD-L....-Z*

    rear left

    X 0.5/Y 0.5 LD.....-LHL

    X 0.51 ... 1.24/Y 0.5 LD.....-LHL-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LHL-Y* +LD-L....-Y*

    X/Y 0.51 to 1.24 LD.....-LHL-X*/Y* +LD-L....-X*+LD-L....-Y*

    rear left with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LHL-Z* +LD-L....-Z*

    Fire barrier note:

    Fire barrier possible for offset elbow units with optional length from

    X 0.86or Y 0.90or Z 0.84with LD.1...- to LD.3...-X 0.92or Y 0.90or Z 0.90with LD.4...- to LD.7...-X 1.12or Y 1.10or Z 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes

    (System overview, pages 3/4 and 3/5)Examples: LDA1423-LHL-X1,22 +LD-L120A-X0,65

    LDA4623-LVL

    Y

    X

    Y

    X

    Z

    X

    Y

    Y

    X

    Z

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    36/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 20053/16

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset elbow trunking units

    right front

    X 0.5/Y0.5 LD.....-LRV

    X 0.51 ... 1.24/Y 0.5 LD.....-LRV-X* +LD-L....-X*X 0.5/Y0.51 ... 1.24 LD.....-LRV-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LRV-X*/Y* +LD-L....-X*+LD-L....-Y*

    right front with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LRV-Z* +LD-L....-Z*

    right rear

    X 0.5/Y 0.5 LD.....-LRH

    X 0.51 ... 1.24/Y 0.5 LD.....-LRH-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LRH-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LRH-X*/Y* +LD-L....-X*+LD-L....-Y*

    right rear with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LRH-Z* +LD-L....-Z*

    Fire barrier note:

    Fire barrier possible for offset elbow units with optional length fromX 0.86or Y 0.90or Z 0.84with LD.1...- to LD.3...-X 0.86or Y 0.96or Z 0.90with LD.4...- to LD.7...-X 1.06or Y 1.16orZ 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-LRV-X1,22 +LD-L120A-X0,65

    LDA4623-LRH

    X

    Y

    Z

    X

    Y

    X Y

    Z

    X

    Y

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    37/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 2005 3/17

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset elbow trunking units

    left front

    X 0.5/Y 0.5 LD.....-LLV

    X 0.51 ... 1.24/Y 0.5 LD.....-LLV-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-LLV-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LLV-X*/Y* +LD-L....-X*+LD-L....-Y*

    left front with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LLV-Z* +LD-L....-Z*

    left rear

    X 0.5/Y0.5 LD.....-LLH

    X 0.51 ... 1.24/Y0.5 L D.....-LLH-X* +LD-L....-X*

    X 0.5/Y0.51 ... 1.24 L D.....-LLH-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-LLH-X*/Y* +LD-L....-X*+LD-L....-Y*

    left rear with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-LLH-Z* +LD-L....-Z*

    Fire barrier note:

    Fire barrier possiblefor offset elbow units with optional length fromX 0.86or Y 0.90or Z 0.84with LD.1...- to LD.3...-X 0.92orY 0.90or Z 0.90with LD.4...- to LD.7...-X 1.12or Y 1.10or Z 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-LLH-X1,22 +LD-L120A-X0,65

    LDA4623-LLV

    X

    Y

    Z

    X

    Y

    X

    Y

    Y

    Z

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    38/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 20053/18

    LD Busbar Trunking System

    l

    Length

    m

    Type

    T units with branching unit above

    straight

    T 1.2 trunking unit(TX 0.58 and TY 0.62)A 0.5 branching unit

    LD.....-T-AD-T

    offset, front right

    Trunking unit as -T-AD-T

    AX 0.5 and AY 0.3 branching unit

    LD.....-T-AD-TVR

    offset, front left

    Trunking unit as aboveAX 0.5 and AY 0.3 branching unit

    LD.....-T-AD-TVL

    Complete ordering details:

    Example: LDA1423-T-AD-TVL

    A

    TX

    TY

    T

    AY

    AX

    AY

    AX

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    39/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 2005 3/19

    LD Busbar Trunking System

    3

    Length

    m

    Type

    T units with branching unit above

    offset, rear right

    Trunking unit as -T-AD-TAX 0.5 and AY 0.3 branching unit

    LD.....-T-AD-THR

    offset, rear left

    Trunking unit as aboveAX 0.5 and AY 0.3 branching unit

    LD.....-T-AD-THL

    Complete ordering details:

    Example: LDA1423-T-AD-THL

    AY

    AX

    AY

    AX

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    40/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 20053/20

    LD Busbar Trunking System

    Length

    m

    Type

    T units with branching unit below

    straight

    T 1.2 trunking unit(TX 0.58 and TY 0.62)A 0.5 branching unit

    LD.....-T-ADU-T

    offset, front right

    Trunking unit as -T-ADU-TAX 0.5 and AY 0.3 branching unit

    LD.....-T-ADU-TVR

    offset, front left

    Trunking unit as above

    AX 0.5 and AY 0.3 branching unit

    LD.....-T-ADU-TVL

    Complete ordering details:

    Example: LDA1423-T-ADU-TVL

    A

    TX

    TY

    T

    AX

    AY

    AY

    AX

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    41/180

    Selection and Ordering DataJunction units for horizontal and vertical installation

    Siemens LV 71 2005 3/21

    LD Busbar Trunking System

    3

    Length

    m

    Type

    T units with branching unit below

    offset, rear right

    Trunking unit as -T-ADU-TAX 0.5 and AY 0.3 branching unit

    LD.....-T-ADU-THR

    offset, rear left

    Trunking unit as aboveAX 0.5 and AY 0.3 branching unit

    LD.....-T-ADU-THL

    Complete ordering details:

    Example: LDA1423-T-ADU-THL

    AX

    AY

    AX

    AY

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    42/180

    Selection and ordering dataDistribution board connection units for non-Siemens distribution boards, cable connection and AS connection/feeder units

    Siemens LV 71 20053/22

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Distribution board connecting flange

    S 0.185

    LD.1... to LD.3... LD-VEG1

    LD.4... to LD.8... LD-VEG2

    VE knee

    front

    X 0.5/Y 0.3 LD.....-VEV

    X 0.51 ... 1.24/Y 0.3 LD.....-VEV-X* +LD-L....-X*

    rear

    X 0.5/Y 0.3 LD.....-VEH

    X 0.51 ... 1.24/Y 0.3 LD.....-VEH-X* +LD-L....-X*

    Fire barrier note:

    Fire barrier possible for VE knee with optional length from:X 0.86with LD.1...- to LD.7...-X 1.06with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Example: LDA1423-VEV-X1,22 +LD-L120A-X0,65

    S

    Y

    X

    Y

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    43/180

    Selection and ordering dataDistribution board connection units for non-Siemens distribution boards, cable connection and AS connection/feeder units

    Siemens LV 71 2005 3/23

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset VE knee

    front right

    X 0.5/Y 0.3 LD.....-VEVR

    X 0.51 ... 1.24/Y 0.3 LD.....-VEVR-X* +LD-L....-X*

    front right with Z dimension

    X 0.5/Y 0.3Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEVR-Z*

    front left

    X 0.5/Y 0.3 LD.....-VEVL

    X 0.51 ... 1.24/Y 0.3 LD.....-VEVL-X* +LD-L....-X*

    front left with Z dimension

    X 0.5/Y 0.3

    Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEVL-Z*

    Fire barrier note:

    Fire barrier possible for offset VE knee with optional length from:X 0.86with LD.1...- to LD.3...-X 0.92with LD.4...- to LD.7...-X 1.12with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA1423-VEVL-Z0,9

    LDA1423-VEVR-X1,22 +LD-L120A-X0,65

    Y

    X

    Y

    Z X

    Y

    X

    Y

    Z

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    44/180

    Selection and ordering dataDistribution board connection units for non-Siemens distribution boards, cable connection and AS connection/feeder units

    Siemens LV 71 20053/24

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset VE knee

    rear right

    X 0.5/Y 0.3 LD.....-VEHR

    X 0.51 ... 1.24/Y 0.3 LD.....-VEHR-X* +LD-L....-X*

    rear right with Z dimension

    X 0.5/Y 0.3Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEHR-Z*

    rear left

    X 0.5/Y 0.3 LD.....-VEHL

    X 0.51 ... 1.24/Y 0.3 LD.....-VEHL-X* +LD-L....-X*

    rear left with Z dimension

    X 0.5/Y 0.3Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEHL-Z*

    Fire barrier note:

    Fire barrier possible for offset VE knee with optional length from:X 0.86with LD.1 ...- to LD.3...-X 0.92with LD.4...- to LD.7...-X 1.12with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA4523-VEHL-Z0,9

    LDA1423-VEHR-X1,22 +LD-L120A-X0,65

    Y

    X

    Y

    Z

    X

    Y

    X

    Y

    Z

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    45/180

    Selection and ordering dataDistribution board connection units for SIVACON 8PV and 8PT power distribution systems

    Siemens LV 71 2005 3/25

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    Trunking units

    straight

    W 0.50 ... 1.60 LD.....-VEU-1W* +LD-L....-X*

    W 1.61 ... 2.40 LD.....-VEU-2W* +LD-L....-X*

    W 1.41 ... 3.20 LD.....-VEU-3W* +LD-L....-X*

    Knee

    front

    X 0.5/Y 0.5 LD.....-VEU-LV

    X 0.51 ... 1.24/Y 0.5 LD.....-VEU-LV-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-VEU-LV-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-VEU-LV-X*/Y* +LD-L....-X*+LD-L....-Y*

    rear

    X 0.5/Y 0.5 LD.....-VEU-LH

    X 0.51 ... 1.24/Y 0.5 LD.....-VEU-LH-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-VEU-LH-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-VEU-LH-X*/Y* +LD-L....-X*+LD-L....-Y*

    Fire barrier note:

    Fire barrier possible for knee with optional length from:X 0.86with LD.1 ...- to LD.7...-X 1.06with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Example: LDA1423-VEU-LH-X1,22

    +LD-L120A-X0.65

    W

    Y

    X

    Y

    X

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    46/180

    Selection and ordering dataDistribution board connection units for SIVACON 8PV and 8PT power distribution systems

    Siemens LV 71 20053/26

    LD Busbar Trunking System

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset knee

    front right

    X 0.5/Y 0.5 LD.....-VEU-LVR

    X 0.51 ... 1.24/Y 0.5 LD.....-VEU-LVR-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-VEU-LVR-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-VEU-LVR-X*/Y* +LD-L....-X*+LD-L....-Y*

    front right with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEU-LVR-Z* +LD-L....-Z*

    front left

    X 0.5/Y 0.5 LD.....-VEU-LVL

    X 0.51 ... 1.24/Y 0.5 LD.....-VEU-LVL-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-VEU-LVL-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-VEU-LVL-X*/Y* +LD-L....-X*+LD-L....-Y*

    front left with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEU-LVL-Z* +LD-L....-Z*

    Fire barrier note:

    Fire barrier possible for offset knee with optional length from:X 0.86or Z 0.84with LD.1...- to LD.3...-X 0.92or Z 0.90with LD.4...- to LD.7...-X 1.12or Z 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA4623-VEU-LVR-Z0,84

    LDA1423-VEU-LVL-X1,20+LD-L120A-X0,80

    X

    Y

    Y

    Z

    X

    Y

    X

    Y

    ZX

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    47/180

    Selection and ordering dataDistribution board connection units for SIVACON 8PV and 8PT power distribution systems

    Siemens LV 71 2005 3/27

    LD Busbar Trunking System

    3

    Length

    m

    Type

    Type suffix

    Fire barrier

    Offset knee

    rear right

    X 0.5/Y 0.5 LD.....-VEU-LHR

    X 0.51 ... 1.24/Y 0.5 LD.....-VEU-LHR-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-VEU-LHR-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-VEU-LHR-X*/Y* +LD-L....-X*+LD-L....-Y*

    rear right with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEU-LHR-Z* +LD-L....-Z*

    rear left

    X 0.5/Y 0.5 LD.....-VEU-LHL

    X 0.51 ... 1.24/Y 0.5 LD.....-VEU-LHL-X* +LD-L....-X*

    X 0.5/Y 0.51 ... 1.24 LD.....-VEU-LHL-Y* +LD-L....-Y*

    X/Y 0.51 ... 1.24 LD.....-VEU-LHL-X*/Y* +LD-L....-X*+LD-L....-Y*

    rear left with Z dimension

    X 0.5/Y 0.5Z 0.36 ... 1.30 with LD.1 to LD.3Z 0.42 ... 1.30 with LD.4 to LD.8

    LD.....-VEU-LHL-Z* +LD-L....-Z*

    Fire barrier note:

    Fire barrier possible for offset knee with optional length from:X 0.86or Z 0.84with LD.1...- to LD.3...-X 0.92or Z 0.90with LD.4...- to LD.7...-X 1.12or Z 1.10with LD.8...-

    Complete ordering details:

    See Type key/Important notes(System overview, pages 3/4 and 3/5)Examples: LDA4623-VEU-LHR-Z0,84

    LDA1423-VEU-LHL-X1,22+LD-L120A-X0,65

    X

    Y

    X

    Z

    Y

    X

    Y

    X Z

    Y

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    48/180

    Selection and ordering dataAS 1, AS 2 and AS 4 connection/feeder units

    Siemens LV 71 20053/28

    LD Busbar Trunking System

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS1: Length 725 mmAS2: Length 1085 mmAS4: Length 1930 mm

    LD.....-AS. +LD-1A +LD-FLP

    LD.....-AS. +LD-2A +LD-FLP

    LD.....-AS. +LD-1B +LD-FLP

    LD.....-AS. +LD-2B +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to1 150 ... 160 165 ... 180

    2 190 ... 280 285 ... 380

    4

    450 ... 600 605 ... 750

    PEN(N) L3(1)150 ... 250

    PEN(N) L3(1)250 ... 350

    (PE)

    PEN(N)L3

    L2

    NSV0

    _0056

    4

    L1

    NSV0

    _00560

    NSV0

    _0056

    5

    L2L3

    PEN(N)

    (PE)

    L1

    NSV0

    _005

    61

    NSV0

    _0056

    6

    PEN(N)

    L2L1

    (PE)

    L3

    NSV0

    _00560

    NSV0

    _00567

    L1

    L3L2

    PEN(N)

    (PE)

    NSV0

    _005

    61

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    49/180

    Selection and ordering dataAS 1, AS 2 and AS 4 connection/feeder units

    Siemens LV 71 2005 3/29

    LD Busbar Trunking System

    3

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS1: Length 725 mmAS2: Length 1085 mmAS4: Length 1930 mm

    LD.....-AS. +LD-1C +LD-FLP

    LD.....-AS. +LD-2C +LD-FLP

    LD.....-AS. +LD-1D +LD-FLP

    LD.....-AS. +LD-2D +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to1 150 ... 160 165 ... 180

    2 190 ... 280 285 ... 380

    4

    450 ... 600 605 ... 750

    PEN(N) L3(1)150 ... 250

    PEN(N) L3(1)250 ... 350

    (PE)

    PEN(N)L1

    L2

    NSV0

    _0056

    8

    L3

    NSV0

    _0056

    0

    L3L2

    L1PEN(N)

    (PE)

    NSV0

    _0056

    9

    NSV0

    _005

    61

    (PE)

    PEN(N)

    L2L1

    NSV0

    _00570

    L3

    NSV0

    _0056

    0

    L3

    L1L2

    PEN(N)

    (PE)

    NSV0

    _00571

    NSV0

    _005

    61

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    50/180

    Selection and ordering dataAS 3 connection/feeder units

    Siemens LV 71 20053/30

    LD Busbar Trunking System

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS3: Length 1430 mm

    LD.....-AS3 +LD-1E +LD-FLP

    LD.....-AS3 +LD-2E +LD-FLP

    LD.....-AS3 +LD-1F +LD-FLP

    LD.....-AS3 +LD-2F +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to

    3

    450 ... 600 605 ... 750

    PEN(N) L3(1)200 ... 300

    PEN(N) L3(1)200 ... 400

    (PE)

    PEN(N)

    L1L2

    NSV0

    _00572

    L3

    NSV0

    _00560

    L3

    L2L1

    PEN(N)

    (PE)

    NSV0

    _0057

    3

    NSV0

    _005

    61

    (PE)

    PEN(N)L3

    L2

    NSV0

    _0057

    4

    L1

    NSV0

    _00560

    L1

    L3

    L2

    PEN(N)

    (PE)

    NSV0

    _0057

    5

    NSV0

    _005

    61

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    51/180

    Selection and ordering dataAS 3 connection/feeder units

    Siemens LV 71 2005 3/31

    LD Busbar Trunking System

    3

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS3: Length 1430 mm

    LD.....-AS3 +LD-1G +LD-FLP

    LD.....-AS3 +LD-2G +LD-FLP

    LD.....-AS3 +LD-1H +LD-FLP

    LD.....-AS3 +LD-2H +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to

    3

    450 ... 600 605 ... 750

    PEN(N) L3(1)200 ... 300

    PEN(N) L3(1)200 ... 400

    (PE)

    L1

    PEN(N)L2

    NSV0

    _0057

    6

    L3

    NSV0

    _0056

    0

    L1

    L3L2

    PEN(N)

    (PE)

    NSV0

    _00577

    NSV0

    _005

    61

    (PE)

    PEN(N)L1

    L2

    NSV0

    _0057

    8

    L3

    NSV0

    _0056

    0

    L3

    L1

    L2

    PEN(N)

    (PE)

    NSV0

    _0057

    9

    NSV0

    _005

    61

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    52/180

    Selection and ordering dataAS1 and AS2 connection/feeder units with T tap-off

    Siemens LV 71 20053/32

    LD Busbar Trunking System

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS1: Length 725 mmAS2: Length 1085 mm

    Additionally, a VEG, VEV or VEHmust be engineered.

    LD.....-AS.-T +LD-1A +LD-FLP

    LD.....-AS.-T +LD-1B +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to1 150 160 165 180

    2 190 280 285 380

    (PE)

    NSV0

    _005

    30

    PEN(N)L3

    L2L1

    NSV

    0_

    00580

    (PE)

    PEN(N)L3

    L2

    NSV0

    _005

    32

    L1NS

    V0

    _00580

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    53/180

    Selection and ordering dataAS1 and AS2 connection/feeder units with T tap-off

    Siemens LV 71 2005 3/33

    LD Busbar Trunking System

    3

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS1: Length 725 mmAS2: Length 1085 mm

    Additionally, a VEG, VEV or VEHmust be engineered.

    LD.....-AS.-T +LD-1C +LD-FLP

    LD.....-AS.-T +LD-1D +LD-FLP

    Note for lug clearance:Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to1 150 160 165 180

    2 190 280 285 380

    (PE)

    PEN(N)

    L3L2

    NS

    V0

    _00534

    L1 N

    SV

    0_

    00580

    (PE)

    NS

    V0

    _00536

    PEN(N)

    L3L2

    L1

    NSV0

    _00580

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    54/180

    Selection and ordering dataAS3 connection/feeder units with T tap-off

    Siemens LV 71 20053/34

    LD Busbar Trunking System

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS3: Length 1430 mm

    Additionally, a VEG, VEV or VEHmust be engineered.

    LD.....-AS3-T +LD-1E +LD-FLP

    LD.....-AS3-T +LD-1F +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to

    3

    450 600 605 750

    PEN(N) L3(1)200 300

    PEN(N) L3(1)200 400

    (PE)

    L1

    PEN(N)L2

    L3

    NSV0_

    00538a

    NSV

    0_

    00580

    PEN(N)L3

    L2L1

    (PE)

    NSV0_

    00540a

    NS

    V0

    _00580

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    55/180

    Selection and ordering dataAS3 connection/feeder units with T tap-off

    Siemens LV 71 2005 3/35

    LD Busbar Trunking System

    3

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS3: Length 1430 mm

    Additionally, a VEG, VEV or VEHmust be engineered.

    LD.....-AS3-T +LD-1G +LD-FLP

    LD.....-AS3-T +LD-1H +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to

    3

    450 600 605 750

    PEN(N) L3(1)200 300

    PEN(N) L3(1)200 400

    (PE)

    L3

    PEN(N)L2

    L1

    NSV0_

    00542a

    NSV

    0_

    00580

    PEN(N)L1

    L2L3

    (PE)

    NSV0_

    00544a

    NSV0

    _00580

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    56/180

    Selection and ordering dataAS4 connection/feeder units with T tap-off

    Siemens LV 71 20053/36

    LD Busbar Trunking System

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS4: Length 1930 mm

    Additionally, a VEG, VEV or VEHmust be engineered.

    LD.....-AS4-1T +LD-1A +LD-FLP

    LD.....-AS4-2T +LD-1B +LD-FLP

    LD.....-AS4-1T +LD-1B +LD-FLP

    LD.....-AS4-2T +LD-1A +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to

    4

    450 600 605 750

    PEN(N) L3(1)150 250

    PEN(N) L3(1)250 350

    (PE)

    PEN(N)

    L1L2

    L3

    NSV0_

    00546

    NSV

    0_

    00580

    (PE)

    PEN(N)L3

    L2L1

    NSV0_

    00547

    NSV0

    _00581

    (PE)

    PEN(N)

    L3L2

    L1

    NSV0_

    00548

    NSV0

    _00580

    (PE)

    PEN(N)

    L1L2

    L3

    NSV0_

    00549

    NSV0

    _00581

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    57/180

    Selection and ordering dataAS4 connection/feeder units with T tap-off

    Siemens LV 71 2005 3/37

    LD Busbar Trunking System

    3

    Phase sequence

    Transformer

    and LD connection

    Mounting position of

    trunking units to be connected

    Type

    Type suffix

    Phase sequenceTransformer andLD connection

    Type suffix

    Flange plate forenclosure ofdistribution board/transformer

    Note:Values in brackets and dottedlines are only valid for the

    5-conductor systemAS4: Length 1930 mm

    Additionally, a VEG, VEV or VEHmust be engineered.

    LD.....-AS4-1T +LD-1C +LD-FLP

    LD.....-AS4-2T +LD-1D +LD-FLP

    LD.....-AS4-1T +LD-1D +LD-FLP

    LD.....-AS4-2T +LD-1C +LD-FLP

    Note for lug clearance:

    Lug clearances are adjustable on site: A larger clearance of the termi-nal lugs can be attained by turning the lugs. The lug clearances givenare valid for flexible ribbon conductors and copper bars with a widthof 120 mm.

    Note for flange plate:

    Flanging to enclosure of distribution board/transformer:With fitting a flange plate of aluminium (Type suffix+LD-FLP), the connection unit can be flanged to the enclosureof the distribution board/transformer.

    Setting range of lug clearance [mm]

    State of delivery Adjustable on

    site to

    4

    450 600 605 750

    PEN(N) L3(1)150 250

    PEN(N) L3(1)250 350

    (PE)

    PEN(N)

    L3L2

    L1

    NSV0_

    00550

    NSV

    0_

    00580

    (PE)

    PEN(N)L1

    L2L3

    NSV0_

    00551

    NSV0

    _00581

    (PE)

    PEN(N)

    L1L2

    L3

    NSV0_

    00552

    NSV0

    _00580

    (PE)

    PEN(N)

    L3L2

    L1

    NSV0_

    00553

    NSV0

    _00581

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    58/180

    Selection and ordering dataIncoming cable connection units

    Siemens LV 71 20053/38

    LD Busbar Trunking System

    Phase sequence

    Transformer

    and LD connection

    Type Type suffix1)

    Base plate of aluminiums

    LD.....-KE1 +LD-BPAL

    LD.....-KE2 +LD-BPAL

    1) Note for cable entries:

    For single-core cable entries, the type suffix Base plate of aluminium must be indicated.

    Note:

    N/PEN = 1/2 Lpossible with LDA 4(5)...

    Rated current[A]

    IP 31 IP 54 CodeNo.

    Al Cu Al Cu

    1100 900 1

    1250 2000 1000 1600 2

    1600 2600 1200 2100 3

    2000 1600 4

    2500 2000 5

    Conductor material

    Al A

    Cu C

    Version

    4 4-conductor

    6 5-conductor

    N/PEN

    1 1/2L

    2 L

    Degree of protection

    3 IP31

    5 IP54

    Cable entries

    System max. [mm2]

    LDA 1, LDA 2 4 300

    LDC 2, LDA 3, LDA 4 6

    300LDC 3, LDA 5 8 300

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    59/180

    Selection and ordering dataFA 1 adapters for connection to non-Siemens distribution boards

    Siemens LV 71 2005 3/39

    LD Busbar Trunking System

    3

    Type

    LD.....-FA1

    Note:Screws, conical spring washers and threaded platesare incuded in the scope of supply.

    Note for limit temperature:

    When adapters for connection to non-Siemens distribution boards areused, it must be assured, that the admissible limit temperature of 100 Kfor the busbars, at an ambient temperature of 35 C im 24-h-Mittel, isnot exceeded.The rated current values given in the table are valid for a limit tempera-ture of 100 K.

    Note for short-circuit strength:

    The short-circuit strength of the connection units for non-Siemens distribution boards are determinated by the designof the terminal assemblies of the distribution system.

    Note:N/PEN = 1/2L possible fromLD.4... to LD.8...

    LDA LDC

    Rated currentIeA

    LDAsystem

    CodeNo.

    Rated currentIeA

    LDCsystem

    CodeNo.

    1100 12

    1250 2 2000 2 21600 3 3 2600 3 3

    2000 45

    2500 5

    3000 67

    3400 6 6

    3700 7 4400 7 7

    4000 8 8 5000 8 8

    Conductor material

    Al A

    Cu C

    Version

    4 4-conductor

    6 5-conductor

    N/PEN

    1 1/2L

    2 L

    Degree of protection

    0 IP00

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    60/180

    Selection and ordering dataReduction units for horizontal and vertical installation

    Siemens LV 71 20053/40

    LD Busbar Trunking System

    Degree of protection Length S

    m

    Rated current

    A

    Conductor cross-section

    N/PEN of the

    7/8/9-conductor system

    Type

    4-conductor-system

    Type

    5-conductor-system

    LDA

    for horizontal (vertical) installation

    IP 31 1.2 1600 (1250) 1/2L LDA5413/LDA3423 LDA5613/LDA3623

    L LDA5423/LDA3423 LDA5623/LDA3623

    IP 54 1.2 1200 (1200) 1/2L LDA5415/LDA3425 LDA5615/LDA3625

    L LDA5425/LDA3425 LDA5625/LDA3625

    LDC

    for horizontal (vertical) installation

    IP 31 1.2 2600 (2100) 1/2L LDC7413/LDC3423 LDC7613/LDC3623

    L LDC7423/LDC3423 LDC7623/LDC3623

    IP 54 1.2 2000 (2000) 1/2L LDC7415/LDC3425 LDC7615/LDC3625

    L LDC7425/LDC3425 LDC7625/LDC3625

    Complete ordering details:

    Example: LDC7423/LDC3423

    S

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    61/180

    Selection and ordering dataTap-off units with GSTA fuse switch disconnectors

    Siemens LV 71 2005 3/41

    LD Busbar Trunking System

    3

    Type Type suffix

    LD-K-.AK./....... see next page

    Equipment features: Fuse switch-disconnector with virtually instantaneous switching (3-pole version)

    sizes NH 00, 2xNH 00, NH 1, NH2, NH3 Can be fitted/removed while the system is live Degree of protection IP30 as standard, IP54 with type suffix

    Cable entry for multi-core or single-core cables (Type suffix always equired) Cable entry at the end (standard), at the side as a type suffix Electrical interlock and trip indication (on request) Current measurement (on request)

    Note:

    1) 630 A when using fuse l inks of make Jean-Mller, Type M3 gL 630/69,Article No. N306900

    Examples for complete ordering details:

    LD-K-1AK4/3ST250 +LD-MLLD-K-1AK4/3ST250 +LD-ML +LD-IP54

    Version

    4 4-conductor

    5 5-conductor

    Rated current le[A]

    Ue= 400 V Ue= 690 V

    IP 30 IP 54 IP 30 IP 54

    31ST125 1 125 1 125 1 100 1 100

    32ST125 2 125 2 100 2 100 2 100

    3ST250 1 250 1 200 1 200 1 200

    3ST400 1 400 1 315 1 315 1 315

    3ST630 1 630 1 500 1 500 (630)1) 1 500

    LD system Code No.

    LDA 1... to LDA 3...LDC 2... to LDC 3...

    1

    LDA 4.1. to LDA 8.1.LDC 6.1. to LDC 8.1.

    2

    LDA 4.2. to LDA 8.2.LDC 6.2. to LDC 8.2.

    3

    LD-K-.AK./.......

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    62/180

    Selection and ordering dataTap-off units with GSTA fuse switch disconnectors

    Siemens LV 71 20053/42

    LD Busbar Trunking System

    Type Type suffix

    Type suffixes

    Cable entry

    Multi-core LD-K-.AK./....... +LD-ML

    Single-core 1) LD-K-.AK./....... +LD-EL

    Cable entry at the side

    (additional cabling box)

    LD-K-.AK./....... +BD2-800-KR

    Degree of protection IP54

    LD-K-.AK./....... +LD-IP54

    Accessory box for loose spacersfor the respective tap-off point2)

    LD-K-.AK./....... +LD-DS

    Note:

    1) Aluminium plate, not drilled2) For storing the loose spacers for the respective tap-off point.

    Examples for complete ordering details:

    LD-K-1AK4/3ST250 +LD-MLLD-K-1AK4/3ST250 +LD-ML +LD-IP54

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    63/180

    Selection and ordering dataTap-off units with GSTZ fuse switch disconnectors

    Siemens LV 71 2005 3/43

    LD Busbar Trunking System

    3

    Type Type suffix

    LD-K-.AK./GSTZ.

    Equipment features: Rated current 400 A and 630 A Fuse switch-disconnectors (GSTZ) sizes NH 2, NH 3 (3-pole version) Can be fitted/removed while the system is live Degree of protection IP30 as standard, IP54 as a type suffix Cable entry for multi-core or single-core cables

    (Type suffix always required) Cable entry at the end or side

    Cable entry

    Multi-core +LD-AB4

    Single-core2),

    1 cable per phase

    +LD-AB7

    Single-core2),2 cables per phase

    +LD-AB8

    Degree of protection IP54, with door

    Door hinged onthe left

    +LD-TL2

    Door hinged onthe right

    +LD-TR2

    Note:

    1) 630 A when using fuse l inks of make Jean-Mller, Type M3 gL 630/69,Article No. N306900.

    2) Aluminium plate, drilled, with PG glands(see Technical Data).

    Examples for complete ordering details:

    LD-K-1AK4/GSTZ2 +LD-AB4LD-K-1AK4/GSTZ2 +LD-AB4 +LD-TR2

    LD system Code No.

    LDA 1... to LDA 3...LDC 2... to LDC 3...

    1

    LDA 4.1. to LDA 8.1.LDC 6.1. to LDC 8.1.

    2

    LDA 4.2. to LDA 8.2.LDC 6.2. to LDC 8.2.

    3

    Version

    4 4-conductor

    5 5-conductor

    Rated current le[A]

    Ue= 400 V Ue= 690 V

    2 400 315

    3 630 500 (630) 1)

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    64/180

    Selection and ordering dataTap-off units up to 570 A with circuit-breaker

    Siemens LV 71 20053/44

    LD Busbar Trunking System

    (Type suffix always required)

    Type Type suffix

    Circuit-breaker with handle LD-K-.AK./LSH . . . H-.

    Circuit-breaker with motor drive LD-K-.AK./LSM . . . H-.

    Equipment features: Circuit-breaker (3- and 4-pole version), H version (high capacity) Can be fitted/removed while the system is live Degree of protection IP54 as standard Cable entry for multi-core or single-core cables at the side Standard auxiliary contact and trip-indicating auxiliary contact as standard Control connections wired to terminal Handle (black) for manual drive External power supply AC 220 ... 240 V, 50/60 Hz for motor drive

    Type suffixes for tap-off units

    Releases Circuit-breaker version

    Undervoltage release up to 250 A +U-NZM 7 (220 240 V AC)

    400 ... 570 A +U-NZM 10 (220 240 V AC)

    Shunt release up to 250 A +A-NZM 7 (220 240 V AC)

    400 ... 570 A +A-NZM 10 (220 240 V AC)

    NEW: Standard tap-off units with Siemens circuit-breakers.Units up to 630 A will be published in the next catalog version (2006),as product development and tests have not yet been completed.For preliminary solutions, please contact your product managers.

    Version

    4 4-conductor

    5 5-conductor

    Rated current le

    80 80 A

    100 100 A

    125 125 A

    160 160 A

    200 200 A

    250 250 A

    400 400 A

    570 570 A

    Circuit-breaker

    3 3-pole

    4 4-pole

    LD system Code No.

    LDA 1... to LDA 3...LDC 2... to LDC 3...

    1

    LDA 4.1. to LDA 8.1.LDC 6.1. to LDC 8.1.

    2

    LDA 4.2. to LDA 8.2.LDC 6.2. to LDC 8.2.

    3

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    65/180

    Selection and ordering dataTap-off units from 800 to 1250 A with circuit-breaker

    Siemens LV 71 2005 3/45

    LD Busbar Trunking System

    3

    1) Aluminium plate not drilled, cable glands not included in the scope of supply.

    Type Type suffix

    Circuit-breaker with handle LD-K-.AK./LSH-. . . . . -LS

    Circuit-breaker with motor drive LD-K-.AK./LSM-. . . . . -LS

    Equipment features: Circuit-breaker (3- and 4-pole version) for system protection, L version (100 kA) Can be fitted/removed while the system is live Degree of protection IP54 as standard Cable entry for multi-core or single-core cables1)at the side With adjustable overload release and fixed-set short-circuit-release 4-pole circuit-breakers without overload and short-circuit-release

    in the N -conductor with two auxiliary switches (1 NO + 1 NC) and an alarm switch (1 NO) Control connections wired to terminal Handle (black) for manual drive External power supply AC 220 ... 250 V, 50/60 Hz for motor drive

    Type suffixes for tap-off units

    Auxiliary releases Version

    Undervoltage release AC 220 ... 250 V +2H

    Shunt release AC 208 ... 277 V +8T

    Version

    4 4-conductor

    5 5-conductor

    Circuit-breaker

    AE 3-pole

    BE 4-pole

    Rated current le

    at Ue= AC 400 V

    800 800 A

    1000 1000 A

    1250 1250 A

    LD system Code No.

    LDA 1... to LDA 3...LDC 2... to LDC 3...

    1

    LDA 4.1. to LDA 8.1.LDC 6.1. to LDC 8.1.

    2

    LDA 4.2. to LDA 8.2.LDC 6.2. to LDC 8.2.

    3

    NSV0

    _0058

    2

    NSV0

    _00583

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    66/180

    Selection and ordering dataAccessories for horizontal und vertical installation

    Siemens LV 71 20053/46

    LD Busbar Trunking System

    Length

    m

    for system Number of

    loose spacers

    supplied

    Type

    End flanges with hooks

    0.325 LD.142. to LD.342. 4 LD-1EF4-H

    LD.162. to LD.362. 5 LD-1EF6-H

    LD.441. to LD.841. 7 LD-2EF4-H

    LD.461. to LD.861. 8 LD-2EF6-H

    LD.442. to LD.842. 8 LD-3EF4-H

    LD.462. to LD.862. 9 LD-3EF6-H

    End flanges with bolts

    0.325 LD.142. to LD.342. LD-1EF4-B

    LD.162. to LD.362. LD-1EF6-B

    LD.441. to LD.841. LD-2EF4-B

    LD.461. to LD.861. LD-2EF6-B

    LD.442. to LD.842. LD-3EF4-B

    LD.462. to LD.862. LD-3EF6-B

    Distribution board blank plate

    0.325 LD.1 to LD.3 LD-VE-BF1

    LD.4 to LD.8 LD-VE-BF2

    Protective sleeves

    0.25 LD.1 to LD.3 LD-DF1

    LD.4 to LD.8 LD-DF2

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    67/180

    Selection and ordering dataAccessories for horizontal und vertical installation

    Siemens LV 71 2005 3/47

    LD Busbar Trunking System

    3

    Length

    m

    for system Number of

    loose spacers

    supplied

    Type

    Suspension bracket for horizontal suspension

    LD.1 to LD.3 LD-B1

    LD.4 to LD.8 LD-B2

    Fixing bracket for vertical fixing

    LD.1 to LD.8 LD-BV

    Torque spanner

    LD.1 to LD.8 LD-DR

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    68/180

    Technical Data

    LDA.4.. Trunking Units

    Siemens LV 71 20053/48

    LD Busbar Trunking System

    SiemensLV71 2005CatalogLV71 EN,Chapter 3,Part 1

    Type LDA.4.. system (4-conductor system)

    Standards and Regulations IEC 60439-1 and -2,EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502),NF C 63-410 and -411,BS 5486 Part 1 and 2,SEV/ASE 3625-1 and 2

    Climatic Proofing Damp heat, constant, toIEC 60068-2-78Damp heat, cyclic, to IEC 60068-2-30

    Ambient temperature, min./max./mean level over 24 hours C 5/+40/+35

    Degree of protection

    ventilated (horizontal busbar edgewise) IP34

    enclosed IP54

    Standard mounting position Busbars edgewise in the system

    Torque for single-bolt clamp terminal Nm 80

    Busbar surface treatment Insulation-plated, nickel-plated and tinnedover the entire length

    Material of trunking units, tap-off units Powder spray paint finished steel enclosure

    Color of trunking units, tap-off units RAL 7035 (light grey)

    Dimensions See Dimension drawings, page 3/118

    Weight See page 3/64

    Rated insulation voltage V~ 1000

    to EN 60664-1 (VDE 0110 Part 1) V 1200

    Overvoltage category/pollution degree

    to EN 60947 III/3

    for power transmission to EN 60947 IV/3

    Rated operational voltage

    with vervoltage category III/3 V~ 1000

    with vervoltage category IV/3 V~ 690

    Rated frequency Hz 16 2/3... 60

  • 7/25/2019 Catalogo Lv71 04 Sivacon 8ps_ind 2

    69/180

    Technical Data

    LDA.4.. Trunking Units

    Siemens LV 71 2005 3/49

    LD Busbar Trunking System

    3

    System-dependent data LDA 142.

    PEN = L

    LDA 242.

    PEN = L

    LDA 342.

    PEN = L

    LDA 441.

    PEN = L

    LDA 442.

    PEN = L

    LDA 541.

    PEN = L

    LDA 542.

    PEN = L

    Rated current Ie1)

    horizontal/edgewise2) IP34 Ie A 1100 1250 1600 2000 2000 2500 2500

    IP54 Ie A 900 1000 1200 1500 1500 1800 1800

    vertical IP34 Ie A 950 1100 1250 1700 1700 2100 2100

    IP54 Ie A 900 1000 1200 1500 1500 1800 1800

    horizontal/flat IP31/IP54 Ie A 700 750 1000 1200 1200 1700 1700

    Impedance

    of the conductorsat 50 Hz and +20 Cbusbar temperature

    Resistance R'20 m/m 0.073 0.047 0.047 0.037 0.037 0.023 0.024

    Reactance X'20 m/m 0.045 0.043 0.043 0.025 0.030 0.023 0.030