Siemens AG 2008

BD01 System 40 ... 160 AIntroduction Overview Benefits Design Accessories

4General data Technical specifications Trunking units Selection and ordering data Junction units Selection and ordering data Feeder units Selection and ordering data Tap-off units for international use Selection and ordering data Ancillary equipment units for international use Selection and ordering data Tap-off units and ancillary equipment units for Belgium Selection and ordering data Tap-off units and ancillary equipment units for Denmark Selection and ordering data Tap-off units for France Selection and ordering data Tap-off units for the United Kingdom Selection and ordering data Tap-off units for Switzerland Selection and ordering data Accessories Selection and ordering data Configuration information Overview Design Function Project planning aids Dimensional drawings

4/2 4/3 4/3 4/6 4/9 4/11 4/12 4/12 4/13

4/19

4/21

4/22 4/23 4/24 4/25 4/27 4/29 4/30 4/32 4/34

Siemens LV 70 2009

Siemens AG 2008

BD01 System 40 ... 160 AIntroduction

Overview2

1

4

5

3NSV0_00041

4 6

1

4

2 3 4

4Version Type-tested low-voltage switchgear and controlgear assembly (TTA) according to IEC/EN 60439-1 IEC/EN 60439-2 Degree of protection High degree of protection IP54 with tap-off points at sides and bottom Degree of protection IP50 with tap-off points at the top Degree of protection increase to IP55 with optional equipment Components Trunking units 5-wire system 2 or 3 tap-off points spaced 1 m apart 4 or 6 tap-off points spaced 0.5 m apart Lengths of 2 m and 3 m Junction units Flexible change of direction Feeder units Universal infeed

5 6

Trunking unit Junction unit Feeder unit Tap-off unit Ancillary equipment unit Accessories

Tap-off units Up to 63 A With built-in parts or for customized device installation For 3, 4 or 8 modular widths (MW) With or without device installation unit Ancillary equipment units For 4 or 8 modular widths (MW) With or without device installation unit With or without socket assembly Accessories Mounting sets for degree of protection IP55 Fixing and suspending Coding sets Fire protection kit S90

4/2

Siemens LV 70 2009

Siemens AG 2008

BD01 System 40 ... 160 AIntroduction

Benefits7 7 7 7 7 7 7 7 7 7 7

Connections

Flexible power supply Easy and quick planning Time-saving mounting Reliable mechanical and electrical connection High stability, low weight Few basic modules required Storage-friendly system Variable change of the direction of the busbar line Versatile tap-off units Positive opening and closing of tap-off points Optional equipment for increasing the degree of protection to IP55 for extreme environmental conditions

NSV0_000

45

DesignTrunking units

Assembly of the trunking units, also with end flanges and feeder units, is fast and inherently secure. The trunking unit or end flange is simply inserted in the lower housing of the joint block. Once the upper part of the joint block or feeder unit is fitted, a secure connection is established by tightening four screws. The PE path is established automatically when the enclosures are connected. An expansion compensation mechanism is built into the joint block. End flanges

NSV0_00042

Trunking units are available in 2 m and 3 m lengths. They consist of a galvanized metal enclosure with a light gray (RAL 7035) painted finish. They are equipped with 4 busbars for L1, L2, L3 and N (aluminum conductors; copper for 160 A; silver-plated copper pick-up and connection contacts). The enclosure of the trunking unit also serves as PE conductor. Five levels of current are available in only one frame size: 40 A, 63 A, 100 A, 125 A and 160 A. The tap-off points are spaced at regular intervals of 0.5 m or 1 m on one side. The 2 m lengths have two or four tap-off points, the 3 m lengths have three or six.

The end flanges provide touch protection against direct contact at the ends of the busbar line. They are suitable for use with all systems. Two end flanges are supplied as standard with each feeder unit. Junction units

NSV0_00046

4

L1 L2 N PENSV0_00043

L3

The junction units, which consist of flexible conducting paths, are available in versions for 100 A and 160 A, each in 0.5 m and 1 m lengths. Flexible junction units mean that the busbar line can be routed in any direction. The 0.5 m version is recommended for right angles, the 1 m version for fitting around obstacles or for adapting to variations in height.

The tap-off points are finger-safe. They are opened automatically by the tap-off units and close by themselves when the tap-off units are removed.

NSV0_00044

NSV0_00047

Siemens LV 70 2009

4/3

Siemens AG 2008

BD01 System 40 ... 160 AIntroductionFeeder units Insulated tap-off units Common features Molded-plastic enclosure Partially transparent cover for protective devices Power pick-up through silver-plated lyre-shaped contacts Reliable prevention of incorrect mounting Cable entry is from one side only (use plastic cable glands with strain relief, not included in scope of supply). The tap-off unit must first be removed from the trunking before it can be opened and the cable can be connected. The connecting cable should be supported separately if necessary. Tap-off units with components fitted One size for 1 cylindrical fuse (10 38 mm), phase assignment L1, L2 or L3 freely selectable One size for 3 cylindrical fuses (10 38 mm) One size with 3 MW (1 MW = 18 mm; MW = modular width)NSV0_000 49

There is one version each for 100 A and 160 A. The feeder unit can be used as: Entry feeder unit

NSV0_00048

There are various versions with fuse bases, miniature circuit breakers, Schuko and CEE socket outlets up to 32 A

End feeder unit52

NS

V0

_0

00

NSV0_00050

BD01-AK01X/ZS

4 Center feeder unit

V NS

0_

00

05

3

NSV0_0

0051

BD01-AK02X/ZS3

Two end flanges are included in the scope of supply with each unit. M32, M40 and M50 cable entries are possible from four sides. For 160 A, an M63 cable entry can be fitted in a side. Plastic cable glands with strain relief must be used (not included in scope of supply).BD01-AK02M0/CEE165A1634 05 00 0_ SV N

4/4

Siemens LV 70 2009

Siemens AG 2008

BD01 System 40 ... 160 AIntroductionTap-off units for free arrangement of components One size with 3 MW; can be operated from outside through hinge switch incorporated in cover (1 MW = 18 mm; MW = modular width). Installation of devices (e.g. miniature circuit breakers) according to DIN 43871 possible up to 32 A. Tap-off units for free arrangement of components Two sizes with 4 MW and 8 MW (1 MW = 18 mm; MW = modular width) With or without device installation unit for external operation (two sizes with 4 MW and 8 MW respectively) Installation of devices (e.g. miniature circuit breakers) according to DIN 43871 possible up to 63 A.

NSV0_00055

BD01-AK02M0/F

Aluminum tap-off units Common features Common features: The enclosure is made from aluminum and molded plastic at both ends. A standard mounting rail is built-in for component mounting. Power pick-up through silver-plated lyre-shaped contacts The isolator built into the tap-off unit ensures that the tap-off unit is voltage-free when the cover is open. The tap-off unit can only be fitted to or removed from the tapoff point with its cover open (contacts retracted). Reliable prevention of incorrect mounting Cable entry is possible from three directions (use plastic cable glands with strain relief; not included in scope of supply). Can be combined with ancillary equipment units for additional functions. The connecting cables should be supported separately if necessary. Tap-off units with components fitted Two sizes with 4 MW or 8 MW (1 MW = 18 mm; MW = modular width) Various versions with fuse bases, miniature circuit breakers up to 63 A, with Schuko and CEE socket outlets up to 32 A. Versions with fitted miniature circuit breaker have a device installation unit.

BD01-AK1M1/A161

Ancillary equipment units Common features The enclosure is made from aluminum and molded plastic at both ends. Cable entry is possible from four directions (use plastic cable glands with strain relief; not included in scope of supply). The connecting cable should be supported separately if necessary. Can be combined with tap-off or feeder units A standard mounting rail is built-in for component mounting. Two sizes with 4 MW and 8 MW (1 MW = 18 mm; MW = modular width) Without or with Schuko or CEE socket outlets With or without device installation unit for external operation (two sizes with 4 MW and 8 MW respectively) Installation of devices (e.g. fuse bases) according to DIN 43871 possible up to up to 35 A.

NSV0_00057

4

BD01-GK2X/FNSV0_00056

BD01-AK2M1/CEE165A163

BD01-GK2X/2SD163CEE165

NSV0_00059

NSV0_00058

Siemens LV 70 2009

4/5

Siemens AG 2008

BD01 System 40 ... 160 AIntroduction

AccessoriesOptional equipment for IP55 Trunking units The higher degree of protection is achieved by means of additional seals and a flange at the tap-off point or connection point. With mounting position at the side, the higher degree of protection is achieved by means of additional seals and an edge protector at the sides of the feeder unit. When the feeder unit is installed at the end of a busbar line, just one seal and one edge protector