Vendor has to not provided the strand diameter. Vendor to confirm that supplied cable strand diameter shall be

67 mm

Vendor has provided Copper Conductor . Vendor has to not that copper conductor is not acceptable. Vendor to

confirm that conductor material shall be 7 Strand annealed bare electrolytic grade starndard copper conductorVendor has to note that inner sheath materials shall be Flame retardant low smoke 90 Deg C PVC to IS 5831

Type ST2. Vendor has provided PVC is not acceptable.

Vednor to confirm that outer sheath thickness shall be as per IS 1554 Part 1

Vednor to confirm that maximum smoke density shall be <= 60%

Vendor to confirm that color of outer sheath shall be black. Vendor to confirm for the same.

Vendor to confirm that marking on outer sheath shall be as follow: No. of core conductor size, voltage grade,

manufactures name, year of manufacturing & Cable Lengh.

Vendor has provided power cable with solid copper conductor which is not acceptable. Vendor to note that

conductor material shall be 7 Strand annealed bare electrolytic grade starndard copper conductor with strand

diameter 0.67 mm

Vendor to confirm that maximum conductor DC registance shall be <= 7.56 Ω / Km

Vendor to confirm that min. insulation registance of cable shall be 100 MΩ/ Km at 27 Deg C

Vendor to confirm that inner sheath thickness and outer sheath thickness shall be as per IS 1554 Part 1

Vendor to confirm that outer sheath material shall be Flame retardant low smoke 90 Deg C PVC to IS 5831 Type

ST2.

Vendor to confirm that marking on outer sheath shall be as follow: No. of core conductor size, voltage grade,

manufactures name, year of manufacturing & Cable Lengh.

Vendor has to note that inner sheath materials shall be Flame retardant low smoke 90 Deg C PVC to IS 5831

Type ST2. Vendor has provided PVC is not acceptable.

Vednor to note that smoke density rating shall be 60% Maximum when tested as per ASTMD-2843/77. Finished

Cable shall pass falmmability test as per SS 424 14 75 CLASS F3, IEEE-383 & IEC-332-I. Vendor to confirm for the

same.

Vendor to confirm that marking on outer sheath shall be as follow: No. of core conductor size, voltage grade,

manufactures name, year of manufacturing & Cable Lengh.

Vendor to confirm that strand diameter shall be 0.67 mm.

Vendor to note that maximum conductor DC resistance shall be <= 7.56 Ω / Km. The offer resistance 12.3 Ω / Km

is not acceptable. Vendor to revise the offer.

Vendor to confirm that min. insulation resistance of cable shall be 100 MΩ/ Km at 27 Deg C. Vendor has offered

25 MΩ/ Km at 20 Deg C is not acceptable. Vendor to revise the offer.

COMMENTS FOR POWER CABLE

Comments for MECAB Pvt. Ltd. (Power Cable)

Comments for Gloster Cables Limited. (Power Cable)

Comments for KEI Industries Limited (Power Cable)

Comments for SUYOG ELECTRICALS LTD. (Power Cable)

Page 4: Cable Commentvs

7/28/2019 Cable Commentvs

http://slidepdf.com/reader/full/cable-commentvs 4/6

Vendor has to note that inner sheath materials shall be Flame retardant low smoke 90 Deg C PVC to IS 5831

Type ST2. Vendor has provided PVC is not acceptable. Vendor to revise the offer.

Vendor to note that inner sheath thickness shall be as per IS 1554 Part 1. Vendor to confirm for the same.

Vendor to note that acid gas generation shall be 20% Max by weight. Vendor to confirm for the same.

Vendor to note that maximum conductor DC resistance shall be <= 7.56 Ω / Km. The offer resistance 12.3 Ω / Km

is not acceptable. Vendor to revise the offer.

Vendor to note that color of outer sheath shall be black. Vendor to confirm for the same.Vendor to confirm that marking on outer sheath shall be as follow: No. of core conductor size, voltage grade,

manufactures name, year of manufacturing & Cable Lengh.

Page 5: Cable Commentvs

7/28/2019 Cable Commentvs

http://slidepdf.com/reader/full/cable-commentvs 5/6

1

2

3

4

5

6

7

8

9

10

1

1

2

1

 

Page 6: Cable Commentvs

7/28/2019 Cable Commentvs

http://slidepdf.com/reader/full/cable-commentvs 6/6

Vednor to note conductor shall be annealed bare electrolytic grade stranded copper conductor. Venor has

provided quotation for only annealed stranded copper conductor which is not acceptable. Vendor to revise

the offer for the same.

Vendor to note that Insrument cables shall be twisted pair and 10 twists per meter shall be minimum.

Vendor to confirm for the same.

Vendor to note that pair identification with number at internal of not more then 250mm. Vendor toconfirm for the same.

Vendor to note that outer sheath color shall be black for 1T X 1.5 Sq. mm and blue for 6T X 1.5 Sq. mm.

Vendor to confirm for the same.

Vendor to note that Oxygen Index shall be over 30%. Vendor to confirm for the same.

Vendor to note that Temp. Index shall be over 250 Deg C. Vendor to confirm for the same.

Vendor to note that smoke index shall be as per ASTM : D2843/93 and Maximum 60%. Vendor to confirm

for the same.

Vendor to note that conductor insulation shall be Type 'C' PVC compound as per IS : 5831, 1984 Color :

:Black Bule and Brown for Traid. Vendor to confirm for the same.

Vendor to note that in communication pair each wire shall be 0.5mm2 of plain annealed single or multistrand copper conductor with 0.4mm thick 85 deg. C PVC insulated insulation color red and green.

Vednor has not provided min. bending radius. Vendor to confirm for the same.

Gloster Cables Limited has not provided quotation for Instrument Cables.

Vendor to note that Insrument cables shall be twisted pair and 10 twists per meter shall be minimum.

Vendor to confirm for the same.

Vendor to note that pair identification with number at internal of not more then 250mm. Vendor to

confirm for the same.

Technically Ok.

Comments for MECAB Cables (Instrument Cable)

Comments for Gloster Cables Limited (Instrument Cable)

Comments for KEI Industries Limited (Instrument Cable).

Comments for Suyog Electricals (Instrument Cable)