c> motor starter protectors (msp) selection · c> motor starter protectors (msp) selection...

4
c> Motor Starter Protectors (MSP) selection SIRIUS 3RV10 Manual Combination Starters, also for Group Installation, Class 10 Description The 3RV102 3RV103, and 3RV104 MSP's can be used as Type E self-protected manual combination starters per UL508 or as com- ponents in Group Installation per NEC 430-53(0 to turn motors on and off. Each device has built-in heater elements that provide over- load protection and magnetic trip elements to protect the motor. When using the 3RV as a manual combination starter, upstream protection is not required. When the 3RV is used as a component in Group Installation, multiple MSP's can be installed below one circuit breaker to protect its own motor. A contactor can be mounted to the MSP to provide a remotely operated starter. Ordering Information > ON/OFF rotary handle with lockout and visible trip indication. >• Adjustment dial for setting to motor FLA. *• Class 10 overload trip characteristics. > Short circuit trip at 12 times the maximum setting of the FLA adjustment dial. > Short circuit current rating:® >• Ambient compensated up to 140° F (applies to side by side mounting). > Phase loss sensitivity. > Test trip function. > Accessories see pages 275-279. > General Information see pages 270-271. »• Technical Data see pages 362-368. *• Dimensions see pages 383-386. Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only. ®Short Circuit Ratings: Group Installation: 50kA @ 480V, 25kA @ 600V (30kA for 3RV104) Manual Combination Starter: 3RV102—50kA @ 240V, 480Y/277V, 25kA @ 600Y/347V up to 12.5 amps. 3RV103—50kA @ 240V, 480Y/277V, 25kA 600Y/347V 3RV104—50kA @ 240V, 480Y/277V, 30kA @ 600Y/347V up to 75 amps. © Shaded Ratings apply for Group Installation Only! These Ratings do not apply as UL Listed Manual Combination Starters. For UL Listed Manual Combination Starters: 3RV102—0.11-22 A up to 480V Max. 0.11-12.5 A up to 575V Max. 3RV103—11-50 A up to 575V Max. 3RV104— 28-100 A up to 480V Max. 28-75 A up to 575V Max. Illustration X <R - J 1 _ = '*fc{ .->™^ <& i 4 "^S" <* | . l|5» 4B9bg| -- *• Mm, ' <m ** '• ,.,^ IP ®, ^ pr < *'*:| 1 i m, .. », ; y -—?--^B " 1 FLA Adjustment Range Single-Phase HP Ratings 115V 230V Three-Phase HP Ratings 200V 230V 460V 575V Catalog No Price S 3RV102 0.11-0.16 0.14-0.2 0.18-0.25 0.22-0.32 0.28-04 0.35-0.5 0.45-0.63 0.55-0 8 0.7-1 0.9-1.25 1.1-1.8 1.4-2 1 8-2.5 22-3.2 2.8-4 3.5-5 4.5-6.3 5.5-8 7-10 9-12.5 11-16 14-20 17-22 20-25 '/n % Vt % '/:. / '/I 1 I'/! 2 'A '/« % '/.• 'A 1 I/; 2 3 3 3 - - '/ 7< 1 r/ 2 3 3 5 5 T/: 7 1/:® / 1 1 Vh 2 3 3 5 TA 17: 7'A® '/ v> 1 r/ Vh 3 5 5 TA r/' 10 15 15 15® - •fi I/a / 1 Vh Vh 2 3 3 5 5 10 10 15® 20® 20® 20® 3RV1021-DAA10 3RV1021 QBA10 3RV1021-OCA10 3RV1021-ODA10 3RV1021-OEA10 3RV1021-OFA10 3RV1021-OGA10 3RV1G21 OHA10 3RV1021-OJA10 3RV1021-OKA10 3RV1021 1AA10 3RV1021-1BA10 3RV1021-1CA10 3RV1021 1DA10 3RV1021-1EA10 3RV1021 1FA10 3RV1021 1GA10 3RV1021 1HA10 3RV1021-1JA10 3RV1021-1KA10 3RV1021-4AA10 3RV1021 4BA10 3RV1021-4CA10 3RV1021 40A10 136. 136. 136. 136. 136. 150. 150. 150. 150. 150. 150. 150. 150. 150. 150. 150. 150. 150. 150. 179. 179. 179. 179. 179. 3RV103 11-16 14-20 18-25 22-32 28-40 36^15 40-50 1 114 2 3 3 5 5 3 3 5 5 Th Tk 10 5 5 TA 10 15 15 15 5 TA 10 10 15 15 20 10 15 20 25 30 30 40 15 20 25 30 40 40 50 3RV1031-4AA10 3RV1031 4BA10 3RV1031 4DA10 3RV1031-4EA10 3RV1031-4FA10 3RV1031-4GA10 3RV1031 4HA10 289. 289. 289. 289. 325. 325. 325. 3RV104 28-40 36-50 45-63 57-75 70-90 80-100 3 5 5 TA 10 10 TA 10 15 15 20 25 15 15 20 25 30 40 15 20 25 25 30 40 30 40 50 60 75 75 40 50 60 75 100® 100® 3RV1041-4FA10 3RV1041-4HA10 3RV1041-4JA10 3RV1041-4KA10 3RV1041-4LA10 3RV1041-4MA10 357. 357. 357. 375. 400. 450. Discount Code: SIRIUS 3R Contactors, OL's, MSP's Siemens Industrial Control Products

Upload: phungduong

Post on 30-Jun-2018

249 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: c> Motor Starter Protectors (MSP) selection · c> Motor Starter Protectors (MSP) selection ... >• Adjustment dial for setting to motor FLA. ... 10 adjustable bimetallic overload

c> Motor Starter Protectors (MSP) selectionSIRIUS 3RV10 Manual Combination Starters, also for Group Installation, Class 10

Description

The 3RV102 3RV103, and 3RV104 MSP's can be used as Type Eself-protected manual combination starters per UL508 or as com-ponents in Group Installation per NEC 430-53(0 to turn motors onand off. Each device has built-in heater elements that provide over-load protection and magnetic trip elements to protect the motor.When using the 3RV as a manual combination starter, upstreamprotection is not required. When the 3RV is used as a componentin Group Installation, multiple MSP's can be installed belowone circuit breaker to protect its own motor. A contactor can bemounted to the MSP to provide a remotely operated starter.

Ordering Information

> ON/OFF rotary handle with lockout and visible trip indication.>• Adjustment dial for setting to motor FLA.*• Class 10 overload trip characteristics.> Short circuit trip at 12 times the maximum setting of the FLA adjustment dial.> Short circuit current rating:®>• Ambient compensated up to 140° F (applies to side by side mounting).> Phase loss sensitivity.> Test trip function.> Accessories see pages 275-279.> General Information see pages 270-271.»• Technical Data see pages 362-368.*• Dimensions see pages 383-386.

Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.

®Short Circuit Ratings:Group Installation: 50kA @ 480V,

25kA @ 600V (30kA for 3RV104)Manual Combination Starter:3RV102—50kA @ 240V, 480Y/277V,

25kA @ 600Y/347V up to 12.5 amps.3RV103—50kA @ 240V, 480Y/277V,

25kA 600Y/347V3RV104—50kA @ 240V, 480Y/277V,

30kA @ 600Y/347V up to 75 amps.

© Shaded Ratings apply for Group Installation Only!These Ratings do not apply as UL Listed ManualCombination Starters.

For UL Listed Manual Combination Starters:3RV102—0.11-22 A up to 480V Max.

0.11-12.5 A up to 575V Max.

3RV103—11-50 A up to 575V Max.3RV104— 28-100 A up to 480V Max.

28-75 A up to 575V Max.

Illustration

X<R-

J1

_ • =

'*fc{

.->™^

<&

i

4

"̂ S"

<*

|

. l|5»

4B9bg|

-- *•

Mm, ' <m

** '•— ,.,^ IP®, ^ pr

<*'*:|1i

m, .. »,; y

-—?--̂ B

" 1

FLA AdjustmentRange

Single-PhaseHP Ratings

115V 230V

Three-Phase HP Ratings

200V 230V 460V 575V Catalog No Price S

3RV102

0.11-0.160.14-0.20.18-0.250.22-0.320.28-040.35-0.50.45-0.630.55-0 80.7-10.9-1 .251.1-1.81.4-21 8-2.522-3.22.8-43.5-54.5-6.35.5-87-109-12.511-1614-2017-2220-25

'/n%Vt%'/:./'/I1I'/!

22®

'A'/«%

'/.•'A1I/;

23335®

-

-

'/

7<1r/23355T/:7 1/:®

/

11Vh2335TA17:7'A®

'/

v>1r/Vh

355TAr/'10151515®

-

•fiI/a/1VhVh23355101015®20®20®20®

3RV1021-DAA103RV1021 QBA103RV1021-OCA103RV1021-ODA103RV1021-OEA103RV1021-OFA103RV1021-OGA103RV1G21 OHA103RV1021-OJA103RV1021-OKA103RV1021 1AA103RV1021-1BA103RV1021-1CA103RV1021 1DA103RV1021-1EA103RV1021 1FA103RV1021 1GA103RV1021 1HA103RV1021-1JA103RV1021-1KA103RV1021-4AA103RV1021 4BA103RV1021-4CA103RV1021 40A10

136.136.136.136.136.150.150.150.150.150.150.150.150.150.150.150.150.150.150.179.179.179.179.179.

3RV103

11-1614-2018-2522-3228-4036^1540-50

111423355

3355ThTk10

55TA10151515

5TA1010151520

10152025303040

15202530404050

3RV1031-4AA103RV1031 4BA103RV1031 4DA103RV1031-4EA103RV1031-4FA103RV1031-4GA103RV1031 4HA10

289.289.289.289.325.325.325.

3RV104

28-4036-5045-6357-7570-9080-100

355TA1010

TA1015152025

151520253040

152025253040

304050607575

40506075100®100®

3RV1041-4FA103RV1041-4HA103RV1041-4JA103RV1041-4KA103RV1041-4LA103RV1041-4MA10

357.357.357.375.400.450.

Discount Code: SIRIUS 3R Contactors, OL's, MSP's

Siemens Industr ia l Control Products

Page 2: c> Motor Starter Protectors (MSP) selection · c> Motor Starter Protectors (MSP) selection ... >• Adjustment dial for setting to motor FLA. ... 10 adjustable bimetallic overload

^^^

Motor Starter Protectors (MSP)SIRIUS3RV10MSP

General

Description3RV10 Motor Starter Protectors (MSP's)are built for a world of applicationswhile meeting the requirements of con-trol users worldwide. Each MSP fea-tures a manual ON/OFF switch, a Class10 adjustable bimetallic overload relay(Class 20 available in the two largestframe sizes), and magnetic trip ele-ments for short circuit protection.

Sizes3RV10 MSP's are available in four framesizes:

3RV101—Width of 45 mmMaximum rated current is 12 Amps.Suitable for motors up to 10 hp at 600V.Available in both screw terminal andCage Clamp versions.

3RV102—Width of 45 mmMaximum rated current is 25 Amps.Suitable for motors up to 20 hp at 600V.

3RV103—Width of 55 mmMaximum rated current is 50 Amps.Suitable for motors up to 50 hp at 600V.

3RV104—Width of 70 mmMaximum rated current is 100 Amps.Suitable for motors up to 100 hp at600V

Motor Protection3RV MSP's use bimetallic heater ele-ments to provide class 10 or 20 over-current protection for both AC and DCmotors. The bimetallic heaters sensethe motor current directly, so the over-loads are insensitive to high frequen-cies, harmonic waves and sinusoidalcurrents and voltages.

Each MSP has a fourth bimetallic stripthat reacts only to the ambient temper-ature inside the control panel. Thisambient compensation prevents theMSP from nuisance tripping when thepanel temperature is higher than theambient temperature of the motor.

A built-in differential trip bar causes theMSP to trip faster on a phase loss con-dition, to help reduce motor damagefrom phase loss.

Magnetic trip elements in each MSPtake the device off line when it sensescurrents of 12 times the maximum FLAdial setting.

Operating Mechanisms

The 3RV101 MSP uses a rocker mecha-nism which has two positions: ON andOFF.

The 3RV102, 3RV103, and 3RV104MSP's have a rotary handle that hasthree positions: ON, OFF and TRIPPED.To reset these devices, the handle mustbe rotated back to the OFF position.The device can then be turned backON. A separate rotary thru-the-dooroperator is available for these devices.

All versions of the 3RV MSP include aprovision for padlocking the operator inthe OFF position.

Installation3RV101and 3RV102 MSP's can besnapped onto a standard 35 mm DINrail. They can also be removed withoutthe use of tools. Separate plug-in lugsare available for screw panel mountingof these devices.

3RV103 MSP's can also be snappedonto a 35 mm DIN rail, but a screw-driver must be used to remove it. The3RV103 includes provisions for screwpanel mounting.

3RV104 MSP's can be snapped onto a35 mm or 75 mm DIN rail, but a screw-driver must be used to remove it. The3RV104 includes provisions for screwpanel mounting.

ouo

3RV101 withScrew Terminals

3RV101 withCage Clamp 3RV102

Siemens Industrial Control Products

Page 3: c> Motor Starter Protectors (MSP) selection · c> Motor Starter Protectors (MSP) selection ... >• Adjustment dial for setting to motor FLA. ... 10 adjustable bimetallic overload

^

Motor Starter Protectors (MSP)SIRIUS3RV10MSP

General

ApplicationsThe 3RV10 MSP's can be used in avariety of applications:

As a Manual StarterAll 3RV MSP's are UL listed as ManualMotor Controllers per UL508. Thismakes them ideal for applicationsrequiring simple manual starting andstopping of motors. A separate shortcircuit protective device, such as a cir-cuit breaker or fuses, is still requiredahead of the MSP. This up-stream pro-tective device should be sized per NECcode, not to exceed 400% of the maxi-mum FLA adjustment dial setting.

As a Self-protected ManualCombination StarterMost 3RV MSP's have also been UL'~>ted as UL508 Type E, Self-protected.Manual Combination Starters. This ULlisting allows the MSP to be mounted ina manually operated machine withouthaving to add separate short circuit pro-tection upstream. These devices have ashort circuit current rating of 50kA @240V, 480Y/277V and up to 30kA @600Y/347V.

As a Component in aCombination StarterBy using a link module, a 3RT10 contac-tor can be directly mounted to the loadside of a 3RV MSP. This assembly of a3RV and a 3RT provides a complete,remotely operated, combination starter.

As a Component in aGroup InstallationA group motor installation indicatesmultiple motor controllers under oneshort circuit protective device, such as acircuit breaker. 3RV MSP's have a groupinstallation short-circuit current rating of50kA at 480V and up to 30kA at 600V.By using a link module, a 3RT contactorcan be directly mounted to the loadside of the MSP. 3RV MSP's have beenUL tested with and without 3RT contac-tors for group installation.

As a Circuit Breaker for ExportWhen exporting to many countries out-side of the U.S. and North America, the3RV can be applied as a thermal mag-netic circuit breaker for use in motorbranch circuits.

Components Required for 100 AmpCombination Starter

8 Amp Combination Starter

*&&-

* 9,

* » %

22 Amp Combination Starter

a«**«*«s.'it: IB,ft *.

«** « ***«,''

8 Amp Reversing Combination Starter

oo

Siemens Industrial Control Products

Page 4: c> Motor Starter Protectors (MSP) selection · c> Motor Starter Protectors (MSP) selection ... >• Adjustment dial for setting to motor FLA. ... 10 adjustable bimetallic overload

oU

Motor Starter Protectors (MSP)SIRIUS3RV101-3RV104

Technical

rTechnical Data

Standards: IEC 947-1; IEC 947-2; IEC 947-4-1;DIN VDE 0660 Part 100; DIN VDE 0660 Part 101; DIN VDE Part 102SizeNumber of polesMax. rated current /„ max .(= max. rated operational current le)Permissible ambient temperature storage/transport °F/°C

operation °F/°C

Ambient temperaturepermissible rated current

Rated operational voltage U, VRated frequency HzRated insulation voltage U, VRated impulse withstand voltage Ulmf kVUtilization category IEC 947-2 (circuit breaker)

IEC 947-4-1 (motor starter)Class IEC 947-4-1Rated short-circuit breaking capacity /cn

Power loss P» per MSPdepending on rated current /„(upper setting range)

Shock resistance ace. to IEC 68 Teil 2-27 gDegree of protectionShock-hazard protection ace. to DIN VDE 0106 Part 100Temperature compensation ace. to IEC 957-4-1 °F/°CPhase failure sensitivity ace to IEC 60947-4-1Explosion protection ace. to EC Directive 94191 ECIsolator characteristics ace to IEC 947-3Main and EMERGENCY-STOP switchcharacteristics® ace. to DIN VDE 01 1 3Safe Isolation between acc VDE Q106 pgrt

mam and auxiliary circuitMechanical endurance operating cyclesElectrical endurance operating cyclesMax. switching frequency per hour (motor starts) 1 /h

Type3RV101soo

3RV102SO

3RV103S2

3RV104S3

3

12

-58 to 4-4 to +

+ 140°F100%

25

176/-50to+8058/-20to +70 (over +6

+ 158°F +60°C

87% 100%

50 100

]°C current reduction required)

+70°C87%

69050/606906AAC-310 | 10/20see table on page 31 4

MA) P,(W)up to 1.25 51.6 to 6.3 68 to 12 7

MA)up to 0.630.8 to 6.38 to 1620 to 25

P,(W)5678

MA) P.(W)up to 25 1232 1540 to 50 20

MA)up to 6375&90100

P^W)

203038

25IP20 IP20 IP2Q® IP20®safe from finger touch-4 to +140/-20to-t-60

yesyes (KEMA test cert. no. Ex-97.4.3236.DMT)

yes

yes

up to 400V

100,000100,00015

100,000100.00015

50,00025,00015

50,00025,00015

Conductor cross-sections for main circuitTerminal typeTerminal screwMinimum/maximum conductor cross-sectionsfinely stranded witb end sleeve1 conductor mm2

2 conductors mm2

solid or stranded1 conductor mm2

2 conductors mm2

solid or stranded AWGstranded AWGTerminal type

mm2

AWGPermissible mounting position

Screw typePozidrive

0.5/2.50.5/2.5

0.5/40.75/2.5 (max. 4)2 x (18 to 14)

Screw typePozidrive

1/61/2.5 or 2.5/6

1/6 (max. 10)1/2.5 or 2.5/62 x (14 to 10)

Box terminalPozidrive

0.75/250.75/16

0.75/350.75/252 x (18 to 2)

Allen screw%i" or 4 mm

2.5/50®2.5/35®

2.5/70®2.5/50®

2 x (10 to 1/0)

Cage Clamp

2 x (0.5 to 2.5)

2 x (18 to 14) I—

any

©Terminal housing IPOO.©With appropriate accessories.©After removing the box terminals,

connection with cable lugs and busbarsis possible.

Siemens Industrial Control Products