weg...

202
www.weg.net Automation Low Voltage Industrial Controls

Upload: daniel-garcia-rodriguez

Post on 20-Jan-2015

126 views

Category:

Technology


13 download

DESCRIPTION

Cátalogo de Automatización WEG Contactores, Relays, Interruptores.

TRANSCRIPT

www.weg.net

Automation

Low Voltage Industrial Controls

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-2

www.weg.net

B-2

High Technology in Manufacturing

Research and Development

Product Certifications

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-3

TIM

ING

RELA

YSM

PW S

ERIE

SEN

cLoS

Ed S

TART

ERS

PuSh

buTT

oNS

AcW

SER

IES

RW S

ERIE

SSR

W01

SER

IES

coNT

AcTo

RSTE

RMIN

AL b

LocK

SPo

WER

FAc

ToR

Table of ContentsIndex – Industrial Controls

Miniature Contactors – CWC SeriesFeatures ..................................................................................... B-12Product Selection ....................................................................... B-17Technical Data ............................................................................ B-24Dimensions ................................................................................ B-28

IEC Contactors – CWM SeriesFeatures ..................................................................................... B-29Product Selection ................................................................... B-35Technical Data ............................................................................. B-45Dimensions ................................................................................. B-57

NEMA Rated Contactors – CWM-N SeriesFeatures ..................................................................................... B-39Product Selection ........................................................................ B-41Technical Data ............................................................................. B-45Dimensions .................................................................................. B-57

Overload Relays – RW SeriesFeatures ...................................................................................... B-68Product Selection ........................................................................ B-70Technical Data ............................................................................ B-72Dimension .................................................................................. B-76

Smart Relays – SRW SeriesFeatures ...................................................................................... B-85Product Selection ...................................................................... B-92Technical Data ............................................................................. B-96Dimensions .................................................................................. B-97

Molded Case Circuit Breakers - ACW SeriesMolded Case Circuit Breakers – ACW Series ............................. B-105Features – Trip Units ................................................................ B-106Product Selection ...................................................................... B-108 Technical Data .......................................................................... B-116Trip Curves ................................................................................ B-123Dimensions ................................................................................ B-136

Manual Motor Protectors – MPW SeriesFeatures .................................................................................... B-147Product Selection .................................................................... B-154Technical Data ........................................................................... B-173Dimensions ................................................................................ B-196

1-800-ASK-4WEG Data is subject to change without notice.B-4

TIMING RELAYS

MPW

SERIESENcLoSEd STARTERS

PuShbuTToNSAcW

SERIESRW

SERIESSRW

01 SERIEScoNTAcToRS

TERMINAL bLocKS

PoWER FAcToR

B-4

TIMING RELAYS

MPW

SERIESENcLoSEd STARTERS

PuShbuTToNSAcW

SERIESRW

SERIESSRW

01 SERIEScoNTAcToRS

TERMINAL bLocKS

PoWER FAcToR

Table of ContentsIndex – Industrial Controls

Enclosed StartersFeatures ................................................................................... B-203Non-Combination Starters Product Selection ........................... B-208Combination Starters Product Selection ................................... B-209Dimensions ............................................................................... B-248

Pushbuttons and Pilot Lights – CSW SeriesFeatures ................................................................................... B-254CSW Series (22mm) Product Selection ..................................... B-258CSW Series (22mm) Dimension ................................................ B-265CSW30 Series (30mm Industrial) Product Selection ................... B-267CSW30 Series (30mm Industrial) Dimension ............................. B-274CSW30H Series (30mm Hazardous) Product Selection ............. B-279CSW30H Series (30mm Hazardous) Dimension ........................ B-284Pushbutton Stations Product Selection ..................................... B-290

Timing Relays RTW Series – Protection Relays RPW SeriesLevel Relays RNW SeriesFeatures .................................................................................... B-291Product Selection ..................................................................... B-293RTW Technical Data .................................................................. B-299RPW Technical Data ................................................................. B-305RNW Technical Data ................................................................ B-310

Terminal Blocks – BTW SeriesFeatures .................................................................................... B-312BTWP Series Product Selection ................................................. B-317BTWM Series Product Selection ............................................... B-324

Power Factor CorrectionSuggested Maximum Capacitor Ratingfor T-Frame NEMA Motors ......................................................... B-335Overview – Concepts ................................................................ B-341Sizing ....................................................................................... B-344Product Selection - Single & Three Phase Capacitor Elements .. B-356Enclosed Three Phase Capacitors ............................................. B-363Contactors for Capacitive Switching .......................................... B-368

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-5

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Contactors and Overload Relays

Operation and Protection of Motors

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-6

coNTAcToRS

www.weg.net

coNTAcToRS

Overview

Reference 3 poles cWc07 cWc09 cWc012 cWc016 cWc025

Rated operational power 1)

Single-phase

115Vac Hp 1/3 1/3 1/2 1 1 1/2

230Vac Hp 3/4 1 2 2 3

Three-phase

230Vac Hp 1 1/2 3 3 5 7 1/2

460Vac Hp 5 5 7 1/2 10 15

575Vac Hp 5 7 1/2 7 1/2 10 15

General PurposeRating A 18 20 22 22 32

Overload relay A

0.28. . .0.40.4. . .0.630.56. . .0.80.8. . .1.21.2. . .1.81.8. . .2.8

2.8. . .4 4. . .6.35.6. . .8 7. . .10

8. . .12.510. . .1511. . .17

7…108…12.510…1511…17 15…2322…32

Auxiliary contact blocks

BFC0-20 (2NO)BFC0-22 (2NO + 2NC)BFC0-11 (1NO + 1NC)BFC0-04 (4NC)BFC0-02 (2NC)BFC0-31 (2NO + 1NC)BFC0-40 (4NO)BFC0-13 (1NO + 3NC)

BFC025-11 (1NO+1NC) BFC025-20 ( 2NO) BFC025-02 (2NC)

Mechanical interlock

BICO

_

TimerON-Delay (TECO)OFF-Delay (TDCO)Star-Delta (TETCO)

Surge suppressor

RC block: RCC0-1 D49 12-24V 50/60HzRCC0-2 D53 24-48V 50/60HzRCC0-3 D55 50-127V 50/60HzRCC0-4 D63 130-250V 50/60HzRCC0-5 D84 275-380V 50/60HzRCC0-6 D73 400-510V 50/60Hz

Varistor block: VRC0-1 E01 12-48V 50/60Hz / 12-60VDCVRC0-2 E34 50-127V 50/60Hz / 60-180VDCVRC0-3 E50 130-250V 50/60Hz / 180-300VDC VRC0-4 E41 277-380V 50/60Hz / 300-510VDCVRC0-5 D73 400-510V 50/60Hz

Diode block(CWC07-16):DIC0-1 C33 12-600VDC

RW17-1D RW17-2D

Notes: 1) Some motor characteristics may vary according to each manufacturer.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-7

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Reference cWM9 cWM12 cWM18 cWM25 cWM32 cWM40 cWM50 cWM65 cWM80 cWM95 cWM105

Rated operational power 1)

Single-phase

115Vac Hp 1/2 3/4 1 2 3 3 3 5 7 1/2 7 1/2 10

230Vac Hp 1 1/2 2 3 5 5 5 7 1/2 10 15 15 20

Three-phase

230Vac Hp 3 3 5 7 1/2 10 15 15 20 25 30 40

460Vac Hp 5 7 1/2 10 15 20 30 40 50 50 60 75

575Vac Hp 7 1/2 10 15 15 25 25 40 50 60 75 75

General Purpose A Rating 25 25 32 45 60 60 90 110 110 140 140

0.28. . .0.40.4. . .0.630.56. . .0.80.8. . .1.21.2. . .1.81.8. . .2.82.8. . .4 4. . .6.3

5.6. . .8 7. . .10

8. . .12.510. . .1511. . .1715…2322…32

25...40 32...50

40...5750...6357...70 63...80

63...8075...9790...112

BCXMF10 (1NO)BCXMF01 (1NC)BCXMFA10 (1NC)BCXMFR01 (1NC)

BCXML 11 (1NO+1NC)BCXML 20 (2NO)BCXMRL 11 (1NO+1NC)BCXMRL 20 (2NO)

BLIM9-105

BLIM.02 9-105 (2NC)

Timing Relays - RTW Series (Please refer to page B-264)

RC block:BAMRC4 D53 24-48 V 50/60HzBAMRC5 D55 50-127 V 50/60HzBAMRC6 D63 130-250 V 50/60Hz

Varistor block:BAMV1 D68 270-380 V 50/60HzBAMV2 D73 400-510 V 50/60Hz

RC block: BAMRC7 D53 24-48 V 50/60HzBAMRC8 D55 50-127 V 50/60HzBAMRC9 D63 130-250 V 50/60Hz

Varistor block: BAMV1 D68 270-380 V 50/60HzBAMV2 D73 400-510 V 50/60Hz

RW27-1D RW67-1D RW67-2D RW117-1D

Overview

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-8

coNTAcToRS

www.weg.net

coNTAcToRS

Reference 3 Poles cWM112 cWM150 cWM180 cWM250 cWM300

Rated operational power 1)

Single-phase

115Vac Hp - - - - -

230Vac Hp - - - - -

Three-phase

230Vac Hp 50 60 75 100 125

460Vac Hp 100 125 150 200 250

575Vac Hp 100 150 200 250 350

General Purpose

Rating A180 225 225 350 410

Overload relays A75...9790...112

100...150140...215200...310275...420

Auxiliary contact blocks

BCXML11 (1NO+1NC)BCXML20 (2NO)BCXMRL11 (1NO+1NC)BCXMRL20 (2NO)

Mechanical interlock BLIM112-300

Surge suppressor

1) Note: Some motors characteristics may vary according to each manufacturer.

Overview

RW117-2D RW317-1D

built-in with electronic module

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-9

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

cWM400 cWM630 cWM800

- - -

- - -

150 250 300

300 500 600

300 500 600

450 660 900

400…600 560…840

BCXML11 CWM800 (1NO+1NC) BCXMRL11 CWM800 (1NO+1NC)

BLIM CWM400 BLIM CWM800

(Built-in with electronic module)

RW407-1D

Reference

Rated operational power 1)

Single-phase

220 / 230Vac Hp

380Vac Hp

Three-phase

230Vac Hp

460Vac Hp

575Vac Hp

General Purpose

Rating A

Overload relays A

Auxiliary contact blocks

Mechanical interlock

Surge suppressor

Overview

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-10

coNTAcToRS Overview – NEMA Contactors

Reference cWM9N cWM18N cWM32N cWM50N cWM95N

NEMA Size 00 0 1 2 3

Rated operational power 1)

Single-phase

115Vac Hp 1/3 1 3 3 7 1/2

230Vac Hp 1 3 5 7 1/2 15

Three-phase

230Vac Hp 1 1/2 3 7 1/2 15 30

460Vac Hp 2 5 10 25 50

575Vac Hp 2 5 10 25 50

General Purpose A Rating 25 32 60 90 140

0.28. . .0.40.4. . .0.630.56. . .0.80.8. . .1.21.2. . .1.81.8. . .2.82.8. . .4 4. . .6.3

5.6. . .8 7. . .10

8. . .12.510. . .1511. . .17

25…40 40...57 63...8075...97

BCXMF10 (1NO)BCXMF01 (1NC)BCXMFA10 (1NC)BCXMFR01 (1NC)

BCXML 11 (1NO+1NC)BCXML 20 (2NO)BCXMRL 11 (1NO+1NC)BCXMRL 20 (2NO)

BLIM9-105

BLIM.02 9-105 (2NC)

Timing Relays - RTW Series (Please refer to page B-291)

RW27-1D RW67-1D RW67-2D RW117-1D

RC block:BAMRC4 D53 24-48 V 50/60HzBAMRC5 D55 50-127 V 50/60HzBAMRC6 D63 130-250 V 50/60Hz

Varistor block:BAMV1 D68 270-380 V 50/60HzBAMV2 D73 400-510 V 50/60Hz

RC block: BAMRC7 D53 24-48 V 50/60HzBAMRC8 D55 50-127 V 50/60HzBAMRC9 D63 130-250 V 50/60Hz

Varistor block: BAMV1 D68 270-380 V 50/60HzBAMV2 D73 400-510 V 50/60Hz

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-11

coNT

AcTo

RS

Overview – NEMA Contactors

Reference 3 Poles cWM150N cWM300N

NEMA Sizes 4 5

Rated operational power 1)

Single-phase

115Vac Hp - -

230Vac Hp - -

Three Phase

230Vac Hp 50 100

460Vac Hp 100 200

575Vac Hp 100 200

General Purpose

Rating A225 410

Overload relays A

Auxiliary contact blocks

BCXML11 (1NO+1NC)BCXML20 (2NO)BCXMRL11 (1NO+1NC)BCXMRL20 (2NO)

Mechanical interlock BLIM112-300

Surge suppressor built-in with electronic module

1) Note: Some motors characteristics may vary according to each manufacturer.

RW317-1DRW117-2D RW317-1D

75...9790...112

100... 150

100… 150140… 215200… 310275… 420

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-12

coNTAcToRS

www.weg.net

coNTAcToRS

Featuresg Rated up to 15 HP @ 460Vg Direct mounting to the WEG RW17D

overload relay and MPW16 & MPW25 manual motor protectors with ECCMP-C0 accessory

g Frame size remains the same for AC and DC coil contactors up to 16A

g Heavy-duty operationg Tool-free DIN rail mountingg Complete line of snap-on accessories

WEG‘s new generation of miniature contactors has arrived. Introducing the new technologically advanced CWC Series, manufactured by WEG‘s Controls and Switchgear Division.

More Horse Power in a Smaller Frame The CWC Series miniature contactor features more horsepower for its size than any other miniature contactor on the market. The CWC’s compact dimensions for its current rating, up to 25A, AC-3 utilization category, allows it to take up less space inside electrical enclosures while still maintaining a powerful 15 HP @ 460V. Dimensions from 7A to 16A remain the same whether the coil voltage is AC or DC making panel design and assembly easier. DC models feature low consumption coils allowing the CWC to be operated directly from a PLC without interface relays.

The following configurations are available “off-the-shelf.”

g 3 Pole Normally Open Power Contacts with one built-in Auxiliary Contact (Either Normally Open or Normally Closed)

g 3 Pole Normally Open Reversing Contactors rated AC-4 Utilization Category

g 4 Pole Power Contacts (four Normally Open, or two Normally Open and two Normally Closed)

g Control Relay (multiple auxiliary contacts configurations)

An extensive lineup of modular and tool-free accessories makes the CWC Series the most flexible and easy-to-use miniature contactor available today.

Controls Miniature Contactors - CWC Series

Certifications

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-13

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Mirror Contacts for Safety-Related ApplicationsThe increase demand for reliable and safety –related circuits for personnel protection has considerably increased within the last two decades. Not only the standards for personnel protection are leading this evolution on high level of system availability, but also the financial aspects of critical operation downtime events.

Although there are significant differences between Mechanically Linked Contact Element(s) described on Annex L of IEC60947-5-1 and Mirror Contacts described on Annex F of IEC60947 -4-1, those differences do not prevent a given auxiliary contact to comply with both requirements.

The following paragraphs will describe key aspects of above Annex and its difference in order to help engineers to select an appropriate device for each application. WEG has incorporated the Mirror Contact feature on all contactors and standard auxiliary contact blocks extending this safety feature to all standard applications. See table at following page.

Mechnicaly Linked Auxiliary Contact Elements: Defined by IEC60947 -5-1 (Annex L) it is a combination of "n" Make contact element(s) and "m" Break contact element (s) designed in such way that they cannot be in closed position simultaneously.

• While any of the "n" Make contact element(s) is closed, none of the "m" Break contact elements(s) shall be closed;

• While any of the "m" Break contact element(s) is closed, none of the "n" Make contact elements(s) shall be closed.

Mirror Contacts:

So, if you export your motor control panels Defined by IEC60947 -4-1 (Annex F) it is a limited feature related to an auxiliary contact normally closed (N.C.) form, which is used to mirror the status of all mechanically linked main contact normally open (N.O.) form. Thus, Control Relays can never feature a mirror contact since it has no main contact to be mechanically linked to.

The indication of this feature is observed when any of the main normally open (N.O.) contact is welded. The auxiliary normally closed (N.C.) contact will not be closed under any possibility providing a clear status of main switching elements.

Mirror Contacts are used where it is essential to rely on switch position of auxiliary contacts and it’s linked main contacts. A typical application for mirror contacts is to implement very reliable monitoring of switched state of a contactor in machine control circuits. It is prudent to emphasize that it is not recommended to rely exclusively on mirror contacts as a safety device, and it recommends self -monitoring of the mirror contact circuit.

Controls Miniature Contacts - CWC Series

Note: both contact configurations have previously been referred to as forced contacts, positive activated contacts or linked contacts.

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-14

coNTAcToRS

www.weg.net

coNTAcToRS Controls Miniature Contacts - CWC Series

Mirror contacts for Safety-Related Applications

Ac and dc coilcontactors

Integrated auxiliary break contact element

to main contacts

Mirror contactsacc. to IEc60947-4-1

(Annex F)

Additional auxiliarybreak contact blocks to

main contacts

Mirror contactsacc. to IEc60947-4-1

(Annex F)

cWc07-10 tocWc016-10

No auxiliary breakcontact NO

bFc0-11; bFc0-02;bFc0-22; bFc0-04;bFc0-31; bFc0-13

YES

cWc07-01 tocWc016-01 built-in YES

bFc0-11; bFc0-02;bFc0-22; bFc0-04;bFc0-31; bFc0-13

YES

cWcI07-10 tocWcI016-10

No auxiliary breakcontact NO

bFc0-11; bFc0-02;bFc0-22; bFc0-04;bFc0-31; bFc0-13

YES

cWcI07-01 tocWcI016-01

cWcI07-01 tocWcI016-01

built-inYES

bFc0-11; bFc0-02;bFc0-22; bFc0-04;bFc0-31; bFc0-13

YES

cWc07-00-40 tocWc016-00-40

No auxiliary breakcontact NO

bFc4-11; bFc4-02;bFc4-22; bFc4-04;bFc4-31; bFc4-13

YES

cWcA0 No main contacts NO No main contacts NO

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-15

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

1 - Miniature contactors CWC07...16

2 - Front auxiliary contact block BFC0

3 - Mechanical interlock block BIC0

4 - Surge supressor blocks RCC0 (RC), VRC0 (Varistor), DIC0 (Diode)

5 - Manual motor protector MPW25

6 - Connector ECCMP-C0 (MPW25 + CWC07...16)

7 - Overload Relay RW17-1D

8 - Electronic timers TEC0, TDC0 and TETC0

12

14

1

7

6

1

7

5

13

10

15

4

2

3

3

3

1

9 - Link module for printed circuit board CIC0

10 - Mini contactor CWC025

11 - Front auxiliary contact block BFC025

12 - Manual motor protector MPW16

13 - Connector ECCMP-C025 (MPW25 + CWC025)

14 - Connector ECCMP-C016 (MPW16 + CWC07...16)

15 - Overload Relay RW17-2D

1

8

29

4

8

4

10

11

Controls Miniature Contactor Overview

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-16

coNTAcToRS

www.weg.net

coNTAcToRS

Catalog part number composition

Controls Miniature Contactors - CWC Series

- -CWC 10 30 V18016

MINIATURE CONTACTOR SERIES:

CWC : Miniature Power Contactor CWCA: Control Relay

AUXILIARY CONTACTS:

For CWC0 00: None 10: 1 NO 01: 1 NC

For CWCA0 22: 2 NO + 2 NC 31: 3 NO + 1 NC 13: 1 NO + 3 NC 40: 4 NO 04: 4 NC

POWER POLE

00: Control Relay (4 auxiliary terminals) 30: CWC0 with 3 NO Power Poles 22: CWC0 with 2 NO + 2 NC Power Poles 40: CWC0 with 4 NO Power Poles

COIL VOLTAGE

VAC COI V04: 24Vac 60Hz V18: 120Vac 60Hz V24: 208-240Vac 60Hz V47: 480Vac 60Hz

C ( A DA CONSUMPTIO C03: 24Vdc C12: 110Vdc

VDC COIL (LOW CONSUMPTION) L03: 24Vdc

FRAME RATING:

Blank: Control Relay (Ith = 10Amps) 7: 07Amps 9: 09Amps 12: 012Amps 16: 016Amps 25: 025Amps

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-17

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Note: Other voltages available upon request.

+ DC COIL VOLTAGE CODE SELECTION

Note: Other voltages available upon request.* See page B-22 for coil consumption

Vdc 24V 110V 24V LOW CONSUMPTION*

codE c03 c12 L03

Three Pole Miniature Contactor with AC Coil

* AC COIL VOLTAGE CODE SELECTION

60 Hz 24V 120V 208-240V 480V

codE V04 V18 V24 V47

50 Hz - 110V - 400-415V

Maximum uL horsepower Auxiliary contacts

current Rating Amps

catalog NumberList

PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

1/3 3/4 1-1/2 1-1/2 5 51 0

7cWc07-10-30* $48 Z6

0 1 cWc07-01-30* $48 Z6

1/3 1 2 3 5 7-1/21 0

9cWc09-10-30* $52 Z6

0 1 cWc09-01-30* $52 Z6

1/2 2 3 3 7-1/2 7-1/21 0

12cWc012-10-30* $64 Z6

0 1 cWc012-01-30* $64 Z6

1 2 3 5 10 101 0

16cWc016-10-30* $70 Z6

0 1 cWc016-01-30* $70 Z6

1-1/2 3 5 7 -1/2 15 15 0 0 25 cWc025-00-30* $80 Z6

To complete the selection- Replace “*” with desired coil voltage from Coil Voltage Code Table

Three Pole Miniature Contactors with DC Coil

Maximum uL horsepower Auxiliary contacts

current Rating Amps

catalog NumberList

PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

1/3 3/4 1-1/2 1-1/2 5 51 0

7cWc07-10-30+ $62 Z6

0 1 cWc07-01-30+ $62 Z6

1/3 1 2 3 5 7-1/21 0

9cWc09-10-30+ $68 Z6

0 1 cWc09-01-30+ $68 Z6

1/2 2 3 3 7-1/2 7-1/21 0

12cWc012-10-30+ $74 Z6

0 1 cWc012-01-30+ $74 Z6

1 2 3 5 10 101 0

16cWc016-10-30+ $79 Z6

0 1 cWc016-01-30+ $79 Z6

To complete the selection- Replace “+” with desired coil voltage from Coil Voltage Code Table

Controls Miniature Contactors - CWC Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-18

coNTAcToRS

www.weg.net

coNTAcToRS

Three Pole Reversing Miniature Contactors with AC Coil

* AC COIL VOLTAGE CODE SELECTION

60 Hz 24V 120V 208-240V 480V

codE V04 V18 V24 V47

50 Hz - 110V - 400-415V

Three Pole Reversing Miniature Contactors with DC Coil

Note: Other voltages available upon request.

To complete the selection- Replace “*” with desired coil voltage from Coil Voltage Code Table

+ DC COIL VOLTAGE CODE SELECTION

Note: Other voltages available upon request.* See page B-22 for coil consumption

Vdc 24V 110V 24V LOW CONSUMPTION*

codE c03 c12 L03

Maximum uL horsepower Auxiliary contacts

current Rating Amps

catalog Number List PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

1/3 3/4 1-1/2 1-1/2 5 51 0

7cWcI07-10-30* $106 Z6

0 1 cWcI07-01-30* $106 Z6

1/3 1 2 3 5 7-1/21 0

9cWcI09-10-30* $114 Z6

0 1 cWcI09-01-30* $114 Z6

1/2 2 3 3 7-1/2 7-1/21 0

12cWcI012-10-30* $138 Z6

0 1 cWcI012-01-30* $138 Z6

1 2 3 5 10 101 0

16cWcI016-10-30* $150 Z6

0 1 cWcI016-01-30* $150 Z6

Maximum uL horsepower Auxiliary contacts

current Rating Amps

catalog Number List PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

1/3 3/4 1-1/2 1-1/2 5 51 0

7cWcI07-10-30+ $134 Z6

0 1 cWcI07-01-30+ $134 Z6

1/3 1 2 3 5 7-1/21 0

9cWcI09-10-30+ $146 Z6

0 1 cWcI09-01-30+ $146 Z6

1/2 2 3 3 7-1/2 7-1/21 0

12cWcI012-10-30+ $158 Z6

0 1 cWcI012-01-30+ $158 Z6

1 2 3 5 10 101 0

16cWcI016-10-30+ $168 Z6

0 1 cWcI016-01-30+ $168 Z6

To complete the selection- Replace “+” with desired coil voltage from Coil Voltage Code Table

Controls Miniature Contactors - CWC Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-19

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Miniature Control Relay with AC Coil

Miniature Control Relay with DC Coil

* AC COIL VOLTAGE CODE SELECTION

60 Hz 24V 120V 208-240V 480V

codE V04 V18 V24 V47

50 Hz - 110V - 400-415V

+ DC COIL VOLTAGE CODE SELECTION

Note: Other voltages available upon request.* See page B-22 for coil consumption

Vdc 24V 110V 24V LOW CONSUMPTION*

codE c03 c12 L03

current Rating Amps

RatingAuxiliary contacts

catalog Number List PriceMultiplier SymbolN.o. N.c.

10 A600, Q600

2 2 cWcA0-22-00* $45 Z6

3 1 cWcA0-31-00* $45 Z6

4 0 cWcA0-40-00* $45 Z6

1 3 cWcA0-13-00* $45 Z6

0 4 cWcA0-04-00* $45 Z6

current Rating Amps

RatingAuxiliary contacts

catalog Number List PriceMultiplier SymbolN.o. N.c.

10 A600, Q600

2 2 cWcA0-22-00+ $59 Z6

3 1 cWcA0-31-00+ $59 Z6

4 0 cWcA0-40-00+ $59 Z6

1 3 cWcA0-13-00+ $59 Z6

0 4 cWcA0-04-00+ $59 Z6

To complete the selection- Replace “*” with desired coil voltage from Coil Voltage Code Table

Note: Other voltages available upon request.

To complete the selection- Replace “+” with desired coil voltage from Coil Voltage Code Table

Controls Miniature Contactors - CWC Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-20

coNTAcToRS

www.weg.net

coNTAcToRS

Four Pole Contactors with AC Coil

* AC COIL VOLTAGE CODE SELECTION

60 Hz 24V 120V 208-240V 480V

codE V04 V18 V24 V47

50 Hz - 110V - 400-415V

+ DC COIL VOLTAGE CODE SELECTION FOR CWC0_-00-40+

Note: Other voltages available upon request.

60 Hz 24V 110V

codE c03 c12

Four Pole Contactors with DC Coil

Note: Other voltages available upon request.

To complete the selection- Replace “*” with desired coil voltage from Coil Voltage Code Table

To complete the selection- Replace “+” with desired coil voltage from Coil Voltage Code Table

current Rating Amps

Main contactscatalog Number List Price

Multiplier SymbolN.o. N.c.

184 0 cWc07-00-40*

$48 Z62 2 cWc07-00-22*

204 0 cWc09-00-40*

$52 Z62 2 cWc09-00-22*

224 0 cWc016-00-40*

$70 Z62 2 cWc016-00-22*

current Rating Amps

Main contactscatalog Number List Price

Multiplier SymbolN.o. N.c.

184 0 cWc07-00-40+

$62 Z62 2 cWc07-00-22+

204 0 cWc09-00-40+

$68 Z62 2 cWc09-00-22+

224 0 cWc016-00-40+

$79 Z62 2 cWc016-00-22+

Controls Miniature Contactors - CWC Series

+ DC COIL VOLTAGE CODE SELECTION FOR CWC0_-00-22+

Note: Other voltages available upon request.

60 Hz 24V 110V

codE R03 R12

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-21

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Front Auxiliary Contact Block

bIc0 $10

Mechanical Interlock Block

• Front Mounting

• Mechanical interlock without width increase

• Allows assembly of auxiliary contact blocks, surge

suppressor and timing relay

Z6

catalog Number

ListPrice

MultiplierSymbol

Controls Miniature Contactors - CWC Series Accessories

“*”: Low consumption 24Vdc contactors can only use 2 pole auxiliary contact blocks

For usewith

Max. number of contacts/ mini

contactor

Auxiliary contacts

For use with cWc0 (3 pole)

For use with cWc0 (4 pole) For use with cWcA0

ListPrice

MultiplierSymbolNo Nc

Terminal markings

catalog Number

Terminal markings

catalog Number

Terminal markings

catalog Number

cWc07...16cWcA0

2

2 0 bFc0-20 bFc4-20 bFcA-20

$15

$26

$15

Z6

Z6

Z6

1 1 bFc0-11 bFc4-11 bFcA-11

0 2 bFc0-02 bFc4-02 bFcA-02

4

4 0 bFc0-40* bFc4-40* bFcA-40*

2 2 bFc0-22* bFc4-22* bFcA-22*

0 4 bFc0-04* bFc4-04* bFcA-04*

3 1 bFc0-31* bFc4-31* bFcA-31*

1 3 bFc0-13* bFc4-13* bFcA-13*

cWc025 2

2 0 bFc025-20 - - - -

1 1 bFc025-11 - - - -

0 2 bFc025-02 - - - -

CWC07...16CWCA0

For use with

For use with circuit diagram Voltage catalog NumberList

PriceMultiplierSymbol

cWc07...25cWcA0

24-48V 50/60Hz Rcc0-2 d53

$18 Z6

50-127V 50/60Hz Rcc0-3 d55130-250V 50/60Hz Rcc0-4 d63400-510V 50/60Hz Rcc0-6 d73

12-48V 50/60Hz / 12-60VDC VRc0-1 E0150-127V 50/60Hz / 60-180VDC VRc0-2 E34

130-250V 50/60Hz / 180-300VDC VRc0-3 E38

400-510V 50/60Hz VRc0-5 d73

cWc07...16cWcA0

12-600VDC dIc0-1 c33

Surge suppressors- Fast front mounting (clip on).- Allows mounting with all the accessories.

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-22

coNTAcToRS

www.weg.net

coNTAcToRS Controls Miniature Contactors - CWC SeriesEletronic timing relay- Right-side fast mounting- Up to 30 minutes timing- LED status indication

Function Time Voltages catalog NumberList

PriceMultiplierSymbol

On-Delay (TECO)

3 - 0,3 to 3 seconds

24-240V 50/60Hz - DC

TEc0-u003S-E05

$72

$72

$65

Z6

Z6

Z6

10 - 1 to 10 seconds TEc0-u010S-E0530 - 3 to 30 seconds TEc0-u030S-E0560 - 6 to 60 seconds TEc0-u060S-E05

100 - 10 to 100 seconds TEc0-u100S-E05300 - 30 to 300 seconds TEc0-u300S-E05

1800 - 180 to 1800 seconds TEc0-u030M-E05

Off-Delay (TDCO)

-

24-60V 50/60Hz - DC

100-240V 50/60Hz - DC

24-60V Ac/dc 100-240V Ac/dc3 - 0,3 to 3 seconds Tdc0-u010S-E04 Tdc0-u003S-E0910 - 1 to 10 seconds Tdc0-u003S-E04 Tdc0-u010S-E0930 - 3 to 30 seconds Tdc0-u030S-E04 Tdc0-u030S-E0960 - 6 to 60 seconds Tdc0-u060S-E04 Tdc0-u060S-E09

100 - 10 to 100 seconds Tdc0-u100S-E04 Tdc0-u100S-E09300 - 30 to 300 seconds Tdc0-u300S-E04 Tdc0-u300S-E09

1800 - 180 to 1800 secondsTdc0-

u030M-E04Tdc0-

u030M-E09

Start-Delta (TETCO) 30 - 3 to 30 seconds

24-28V 50/60Hz - DC

TETc0-u030S-d52

110-130V 50/60Hz - DC

TETc0-u030S-d61

220-240V 50/60Hz - DC

TETc0-u030S-d66

Functions on-delay TEc0 off-delay Tdc0 Start-delta TETc0

Functional Diagram

Led On

Led Off

Diagrams

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-23

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

• Quick and easy assembly for wye-delta and reversing starters

• Allows assemble of overload relay RW17D, manual motor protectors MPW16 & MPW25 and timer

Easy-Connection Busbar

Printed Circuit Board Connector

• Each CIC0 comes with a set of two connectors • Mounting on contactor’s top and bottom

• No derating on contactor’s rating

Rating (HP) Contactor

230V 460V 575V K1=K2 K3

3 7-1/2 7-1/2 CWC07 CWC07

5 7-1/2 10 CWC09 CWC07

5 10 10 CWC012 CWC07

7-1/2 15 15 CWC016 CWC09

Rating (HP) Contactor

230V 460V 575V K1=K2

1-1/2 5 5 CWC07

3 5 7-1/2 CWC09

3 7-1/2 7-1/2 CWC012

5 10 10 CWC016

Wye-Delta

Reversing

Controls Miniature Contactors - CWC Series

catalog Number

cIc0 $20 Z6

catalog Number

Ecco-Sd $34 Z6

Ecco-R $ 34 Z6

ListPrice

MultiplierSymbol

ListPrice

MultiplierSymbol

For use with

CWC07...16

CWCA0

For use with

CWC07...16

CWCA0

1-800-ASK-4WEGB-24

www.weg.net

Data is subject to change without notice.

www.weg.net

110-130 Vac 50/60 (TETC0)

Inputs

Time Adjust

AWG Cables

Auxiliary contact block

Timing Relay

Controls Miniature Contactors - CWC Series

Type cWc07 cWc09 cWc012 cWc016 cWc025

300.8

2....30,27

Standard 2.6...3.7 / Low Consumption 1.7...2.7Standard 2.6...3.7 / Low Consumption 1.7...2.7

580.8

4.5....5.8

--

-

--

--

1....1.8(8.9.....15.9)

AC (60Hz)

DC

0.27

Single Coil No Load

CW

C S

eR

ieS

General Purpose Rating

Electrical Lifespan

(A) 18 20 22 22 32

(Ops x 106) 1.4 1.3 1.2 1.2 0.6

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-25

coNT

AcTo

RS

TYPE cWc07 cWc09 cWc012 cWc016 cWc025Standard UL/CSA Ratings

Rated Operating Voltage [V] 600

General Purpose Rating [A] 18 20 22 22 32

Switching Motor Loads Full Voltage - 50/60Hz

1-phase 115V [A] 7.2 9.8 12.8 16 22

230V [A] 9 12 16 17 25

115V [HP] 1/3 1/3 1/3 1 1 1/2

230V [HP] 3/4 1 2 2 3

3-phase 230V [A] 7 9 12 16 22

460V [A] 7 9 12 16 22

575V [A] 9 11 17 17 27

230V [HP] 1 1/2 3 3 5 7 1/2

460V [HP] 5 5 7 1/2 10 15

575V [HP] 5 7 1/2 7 1/2 10 15

Short Circuit Rating 600V [kA] 5 5 5 5 5

Standard IEC Ratings (IEC EN 60947)

Rated Operating Voltage [V] 690

Rated Thermal Current Ith [A] 18 20 22 22 32

Switching Motor Loads

AC-3 - 50/60Hz

3-phase 220-240V [A] 7 9 12 16 22

380-400V [A] 7 9 12 16 22

415-440V [A] 7 9 12 16 22

500V [A] 6.2 7.5 8.8 13 16

660-690V [A] 4.5 5.5 6.6 10 13

220-240V [HP] 2 3 4 5 7.5

380-400V [HP] 4 5 7.5 10 15

415-440V [HP] 5 6 7.5 10 15

500V [HP] 5 6 7.5 10 15

660-690V [HP] 4 5 7.5 10 15

Maximum Switching Rate

AC-1 [ops/hr] 600

AC-3 [ops/hr] 600

no load [ops/hr] 2500 (AC coil) / 2000 (DC coil)

AC-4

200,000 operations; [A] 2.8 3.5 4.5 5 9

50/60Hz 220-230V [kW] 0.55 0.75 0.75 1.1 2.2

[HP] 0.7 1 1 1.5 2.9

380-400V [kW] 1.1 1.1 1.8 2.2 4

[HP] 1.5 1.5 2.4 2.9 5.4

415-440V [kW] 1.1 1.5 2.2 2.2 4.5

[HP] 1.5 2 2.9 2.9 6

500V [kW] 1.1 1.5 2.2 2.2 4.5

[HP] 1.5 2 2.9 2.9 6

660-690V [kW] 1.1 1.5 2.2 2.2 4.5

[HP] 1.5 2 2.9 2.9 6

Maximum Switching Rate [ops/hr] 360 360 360 360 360

Making Capacity [A] 70 90 120 160 250

Power Contacts

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-26

coNTAcToRS

TYPE cWc07 cWc09 cWc012 cWc016 cWc025

Breaking Capacity Ue=400V [A] 50 72 96 128 200

Ue=500V [A] 50 72 96 128 200

Ue=690V [A] 35 54 72 96 150

Impedance per Pole [mW] 2.41 2.41 2.35 1.65 1.28

Power Dissipation per Pole

AC-1 [W] 1.9 2.4 2.4 2.4 6.1

AC-3 [W] 0.3 0.5 0.7 1.3 3.8

Short Time Current Icw0° ≤ 104°F

1 sec. [A] 250 250 250 250

5 sec. [A] 125 125 125 125 -

10 sec. [A] 95 95 95 95 -

30 sec. [A] 70 70 70 70 -

1 min. [A] 50 50 50 50 -

3 min. [A] 40 40 40 40 -

Rec. time [min.] 10 10 10 10 -

Power Contacts

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-27

coNT

AcTo

RS

www.weg.net

coNT

AcTo

RS

Electrical Lifespan

Num

ber o

f ope

ratio

n (1

06 )

0,1

0,011

Rated operational current Ie (A)

16,8 24,6 45,57 8520,4

35,3

4

6036

64,8

0 100

1

Num

ber o

f ope

ratio

n (1

06 )

1

10

0,11 7 910

Rated operational current Ie (A)

12 16 25 100

CWC025

CWC016

CWC012

CWC09CW

C07

Mounting position of all miniature contactors

Electrical Lifespan

Controls Miniature Contactors - CWC Series

AC-4 (Ue ≤ 460VAC) AC-3 (Ue ≤ 460VAC)

360°360°30°30°30°30°

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-28

coNTAcToRS

www.weg.net

coNTAcToRS

www.weg.net

Dimensions mm (in)

Controls Miniature Contactors - CWC Series

CWC07...016 AND CWCA0

45/ [1.8] 9/ [0.4]

58/ [

2.3]

56/ [2.2]

83/ [3.3]

TDCOTECOTETCO

BFC025

CWC025

TDCOTECOTETCO

VRCORCCODICO

RMCO & BICO

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-29

coNT

AcTo

RS

The CWM general-purpose contactor line has been designed taking into consideration industrial duty and reliability in mind.

Rated for inductive loads up to 800A or 600Hp@460V, WEG can offer the suitable contactor for your application.

Given their compact footprints, CWM contactors allow total panel space optimization, with only a few compact frame sizes from 5 to 600Hp@460V. Reducing inventory is a “snap” with CWM’s common accessories. For example, side-mounted auxiliary contact blocks are the same from 5 to 250 Hp@460V..

Designed for extended mechanical and electrical life, dependable switching in even the most heavy-duty applications can be achieved. No matter how demanding the application, all WEG contactors are tested and approved to be used under Type 1 and Type 2 short circuit coordination.

Ensuring global acceptance, all components conform to UL508, CSA C.22.2, IEC60947 and CE.

All contactors are manufactured to assure the highest quality manufacturing processes and component materials. This way, WEG offers reliable solutions for low-voltage applications in electric panel assemblers, OEMs, distributors and end users.

Certifications

Controls Standard IEC Contactors

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-30

coNTAcToRS

The Flexible Line from 5 to 75HPThe 5 to 75HP @ 460V range is differentiated by five frame sizes and only 4 varying widths, with the choice of either screw or DIN rail mounting. WEG offers one of the most compact 75HP @ 460V contactors in the market.

AccessoriesAll WEG contactor accessories are common for the range of 5 to 75HP @ 460V.

Our mechanical interlock is even suitable between two contactors of different size, for special applications such as automatic switching in emergency systems.

WEG contactors have one built-in auxiliary contact up to 10HP @ 460V and front and/or side mountable auxiliary contact blocks.

Coils WEG Contactor AC coils have 4 terminals up to 30HP @ 460V, which allows an easy connection no matter the complexity of the application and wiring.

The state-of-the-art DC coil contactors from 9A up to 25A are true DC voltage coil contactors. From 32A up to 105A the contactors are equipped with an electronic circuit that provides an unmatched space saving solution, making the 50A through 105A contactors depth the same size.

Controls Standard IEC Contactors

The Tough Line from 100 to 600HPWith reliability as our goal, WEG contactors are modern and very compact, but they are also one of the most rugged line of contactors in the range from 100 to 600HP, assuring an extended life under the most challenging conditions of today’s industry.

AccessoriesSide mounted auxiliary contacts blocks are common for all CWM contactors, from 5 to 250HP @ 460V.

Electronic Module From 100 to 600HP @ 460V, WEG offers contactors with electronic module for AC/DC Coil Applications. Such coils provide a smoother switching, therefiore enhancing contactor‘s performance. Built-in surge suppressor is also standard.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-31

coNT

AcTo

RS

MIRROR CONTACTS FOR SAFETY-RELATED APPLICATIONSThe increase demand for reliable and safety –related circuits for personnel protection has considerably increased within the last two decades. Not only standards for personnel protection are leading this evolution on high level of system availability, but also the financial aspects of critical operation downtime events.

Although there are significant differences between Mechanically Linked Contact Element(s) described on Annex L of IEC60947-5-1 and Mirror Contacts described on Annex F of IEC60947 -4-1, those differences do not prevent a given auxiliary contact to comply with both requirements.

The following paragraphs will describe key aspects of above Annex and its difference in order to help engineers to select an appropriate device for each application. WEG has incorporated the Mirror Contact feature on all contactors and standard auxiliary contact blocks extending this safety feature to all standard applications. See table at the following page.

Mechnicaly Linked Auxiliary Contact Elements: Defined by IEC60947 -5-1 (Annex L) it is a combination of "n" Make contact element(s) and "m" Break contact element (s) designed in such way that they cannot be in closed position simultaneously.

• While any of the "n" Make contact element(s) is closed, none of the "m" Break contact elements(s) shall be closed;

• While any of the "m" Break contact element(s) is closed, none of the "n" Make contact elements(s) shall be closed.

Mirror Contacts:

Defined by IEC60947 -4-1 (Annex F) it is a limited feature related to an auxiliary contact normally closed (N.C.) form, which is used to mirror the status of all mechanically linked main contact normally open (N.O.) form . Thus, Control Relays can never feature a mirror contact since it has no main contact to be mechanically linked to.

The indication of this feature is observed when any of the main normally open (N.O.) contact is welded. The auxiliary normally closed (N.C.) contact will not be closed under any possibility providing a clear status of main switching elements.

Mirror Contacts are used where it is essential to rely on switch position of auxiliary contacts and it’s linked main contacts. A typical application for mirror contacts is to implement very reliable monitoring of switched state of a contactor in machine control circuits. It is prudent to emphasize that it is not recommended to rely exclusively on mirror contacts as a safety device, and it recommends self -monitoring of the mirror contact circuit.

Controls Standard IEC Contactors

Note: both contact configurations have previously been referred to as forced contacts, positive activated contacts or linked contacts.

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-32

coNTAcToRS Controls Standard IEC Contactors

Mirror contacts for Safety-related Applications

Ac and dc coilcontactors

Integrated auxiliary breakcontact element to main

contacts

Mirror contactsacc. to IEc60947-4-1

(Annex F)

Additional auxiliarybreak contact blocks

to main contacts

Mirror contactsacc. to

IEc60947-4-1(Annex F)

CWM9-10 toCWM18-10

No auxiliary breakcontact NO

bcXMF01;bcXML01;bcXML11

YES

CWM9-01 toCWM18-01 built-in YES

bcXMF01;bcXML01;bcXML11

YES

CWM25-00 toCWM105-00

No auxiliary breakcontact NO

bcXMF01;bcXML01;bcXML11

YES

CWM25-11 toCWM105-11

Front Mountable1xbcXMF01 YES

bcXMF01;bcXML01;bcXML11

YES

CWM112-22 toCWM300-22

Side* Mountable2xBCXML11

YES bcXMRL11 YES

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-33

coNT

AcTo

RS

Standard Features g General purpose motor applicationsg Fractional power through 600HP @ 460Vg Compact frame sizesg Panel mountable or 35mm DIN rail up to 75HP @ 460Vg Built-in auxiliary contacts up to 10HP @ 460Vg Front and side mountable auxiliary contact blocksg Finger-touch protection IP20g Wide coil voltage selection AC or DCg AC/DC coils with electronic modules available from 100HP and upg Replaceable main contacts for entire line

Certifications Conformity to Standardsg UL508g CSA C22.2 No 14g IEC60947-1; IEC60947-4-1

Controls Standard IEC Contactors

Applicationsg Pumpsg Blowersg Cranesg Agitatorsg Machine toolsg Pressing machinesg Cutting and sawing machinesg Material handling equipmentg Kneading and mixing machinesg By-pass / isolationg Elevator

Approvalasg cULus Listedg CE markedg Bureau Veritas

Certifications

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-34

coNTAcToRS

Catalog part number composition

Controls Standard IEC Contactors - CWM Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-35

coNT

AcTo

RS

3 pole contactors with AC coil

Maximum uL horsepowerAuxiliary contacts current

RatingAmps

catalog Number1 List PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

1/2 1 1/2 3 3 5 7 1/21 0

9cWM9-10-30*

$72 Z10 1 cWM9-01-30*

3/4 2 3 3 7 1/2 101 0

12cWM12-10-30*

$89 Z10 1 cWM12-01-30*

1 3 5 5 10 151 0

18cWM18-10-30*

$103 Z10 1 cWM18-01-30*

2 5 7 1/2 7 1/2 15 150 0

25cWM25-00-30* $118 Z1

1 1 cWM25-11-30* $138 Z1

3 5 10 10 20 250 0

32cWM32-00-30* $140 Z1

1 1 cWM32-11-30* $160 Z1

3 7 1/2 10 15 30 250 0

40cWM40-00-30* $164 Z1

1 1 cWM40-11-30* $184 Z1

3 10 15 15 40 400 0

50cWM50-00-30* $190 Z1

1 1 cWM50-11-30* $210 Z1

5 10 20 20 50 500 0

65cWM65-00-30* $215 Z1

1 1 cWM65-11-30* $235 Z1

7 1/2 15 20 25 50 600 0

80cWM80-00-30* $261 Z1

1 1 cWM80-11-30* $281 Z1

7 1/2 15 25 30 60 750 0

95cWM95-00-30* $294 Z1

1 1 cWM95-11-30* $314 Z1

10 20 30 40 75 750 0

105cWM105-00-30* $393 Z1

1 1 cWM105-11-30* $413 Z1

Controls IEC Contactors - CWM Series

To complete the selection- Replace “*” with desired coil voltage from Coil Voltage Code Table

Note:1) Stock available only for contactor version …-10-30... and …-00-30…. -10 = 1 N.O. Auxilliary contact. -00 = No Auxilliary contact For … -11-30… = 1 N.O. & 1 N.C. version or other auxilliary contact configurations please refer to page B-42.

60 Hz 24V1) 48V1) 120V 208-240V 277V1) 480V 600V1)

codE V04 V10 V18 V24 V37 V47 V56

50 Hz - 42V 110V - 230-240V 400-415V 500V

* Ac coIL VoLTAGE codE SELEcTIoN FoR coNTAcToRS cWM9...cWM105

- Other coil voltages available upon request

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-36

coNTAcToRS

Maximum uL horsepowerAuxiliary contacts current

RatingAmps

catalog Number List PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

1/2 1 1/2 3 3 5 7 1/21 0

9cWM9-10-30+

$93 Z10 1 cWM9-01-30+

3/4 2 3 3 7 1/2 101 0

12cWM12-10-30+

$111 Z10 1 cWM12-01-30+

1 3 5 5 10 151 0

18cWM18-10-30+

$125 Z10 1 cWM18-01-30+

2 5 7 1/2 7 1/2 15 15 0 0 25 cWM25-00-30+ $141 Z1

3 5 10 10 20 25 0 0 32 cWM32-00-30+ $180 Z1

3 7 1/2 10 15 30 25 0 0 40 cWM40-00-30+ $230 Z1

3 10 15 15 40 40 0 0 50 cWM50-00-30+ $255 Z1

5 10 20 20 50 50 0 0 65 cWM65-00-30+ $280 Z1

7 1/2 15 20 25 50 60 0 0 80 cWM80-00-30+ $335 Z1

7 1/2 15 25 30 60 75 0 0 95 cWM95-00-30+ $360 Z1

10 20 30 40 75 75 0 0 105 cWM105-00-30+ $470 Z1

+ DC COIL VOLTAGE CODE SELECTION FOR CONTACTORS CWM9...105

3 pole contactors with DC coil

Voltage 24V 110V

codE c03 c12

Voltage 24-28V 110-130V

codE c34 c40

FOR CONTACTORS CWM9...CWM25

FOR CONTACTORS CWM32...CWM105

Controls IEC Contactors - CWM Series

Note: Other voltage available upon request.

To complete the selection- Replace “+” with desired coil voltage from Coil Voltage Code Table- For different auxiliary contact configuration please refer to page B-35

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-37

coNT

AcTo

RS

3 pole contactors with AC/DC electronic module coil

Maximum uL horsepowerAuxiliary contacts current

RatingAmps

catalog Number List PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.o. N.c.

- - 40 50 100 100 2 2 112 cWM112-22-30# $765 Z1

- - 50 60 125 150 2 2 150 cWM150-22-30# $945 Z1

- - 60 75 150 200 2 2 180 cWM180-22-30# $1,260 Z1

- - 75 100 200 250 2 2 250 cWM250-22-30# $1,755 Z1

- - 100 125 250 300 2 2 300 cWM300-22-30# $1,890 Z1

- - 125 150 300 300 2 2 400 cWM400-22-30^ $2,520 Z1

- - 200 250 500 500 2 2 630 cWM630-22-30^ $3,870 Z1

- - 200 300 600 600 2 2 800 cWM800-22-30^ $5,670 Z1

Voltage 24-28Vac/Vdc 110-130Vac/Vdc 208-250Vac/Vdc 430-500Vac/Vdc

codE E02 E10 E13 E21

Mounting on CWM112-CWM300 CWM112-CWM300 CWM112-CWM300 CWM112-CWM300

Voltage 100-240Vac/100-220Vdc 100-127Vac/100-110Vdc 200-240Vac/200-220Vdc 440-575Vac

codE E36 E35 E39 d82

Mounting on CWM400 CWM630-CWM800 CWM630-CWM800 CWM400-CWM800

# AC/DC COIL VOLTAGE CODE SELECTION FOR CONTACTORS CWM112, 150, 180, 250, 300

Controls IEC Contactors - CWM Series

^ AC/DC COIL VOLTAGE CODE SELECTION FOR CONTACTORS CWM400...800

Note: Other voltage available upon request.

To complete the selection- Replace “#” or “^”with desired coil voltage from Coil Voltage Code Table- For different auxiliary contact configuration please refer to page B-35

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-38

coNTAcToRS

www.weg.net

Controls IEC Contactors - CWM Series

Maximum uL horsepower Auxiliary contacts current

RatingAmps

catalog Number List PriceMultiplier SymbolSingle Phase

115V 230V N.o. N.c.

1/2 1 1/2 0 0 9 cWM9-00-20* $65 Z1

3/4 2 0 0 12 cWM12-00-20* $68 Z1

1 3 0 0 18 cWM18-00-20* $73 Z1

2 5 0 0 25 cWM25-00-20* $99 Z1

3 5 0 0 32 cWM32-00-20* $126 Z1

3 7 1/2 0 0 40 cWM40-00-20* $160 Z1

3 10 0 0 50 cWM50-00-20* $174 Z1

5 10 0 0 65 cWM65-00-20* $200 Z1

7 1/2 15 0 0 80 cWM80-00-20* $231 Z1

7 1/2 15 0 0 95 cWM95-00-20* $273 Z1

10 20 0 0 105 cWM105-00-20* $321 Z1

* AC COIL VOLTAGE CODE SELECTION

60 Hz 24V 120V 208-240V

codE V04 V18 V24

50 Hz - 110V -

FOR CONTACTORS CWM9...CWM105

Note1: Availability upon request.

To complete the selection- Replace “*” with desired coil voltage from Coil Voltage Code Table- For different auxiliary contact configuration please refer to page B-35

2 pole contactors with AC coil1

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-39

coNT

AcTo

RS

www.weg.net

Controls

NEMA Rated ContactorsNEMA contactors have been a mainstay in the industrial marketplace in the US for decades. NEMA contactors were known for being robust & able to handle any industrial application.

WEG’s NEMA rated contactors meet or exceed the standards defined by the National Electrical Manufacturers Association (NEMA), for full voltage or reduced voltage motor starting. (1)

• Available from size 00 to size 5

• Designed for Industrial Applications with Reliability in mind

• Enclosed NEMA Starters & Custom NEMA Starter panels, available on request

• Reduced inventory with common accessories

• Ease of choosing product

• Adjustable Overload Protection available (No heaters needed)

(1) NEMA Standards Publication ICS 2-2000 (R2005) Industrial Control and Systems Controllers, Contactors and Overload Relays Rated 600 Volts

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-40

coNTAcToRS

www.weg.net

Controls

NEMA Rated Contactors

The WEG CWM_N series NEMA rated contactor line has been designed for industrial duty and with reliability in mind. Rated for inductive loads up to 300 Amps or 200 Hp @ 460V, WEG can offer the suitable contactor for your application.

Customers who are used to specifying contactors (and starters), by a particular NEMA Size (size 00, 0, 1, 2, 3, 4, 5), now can use the WEG CWM_N series, NEMA rated contactors. Customers get the ease of choosing the product, the reliability of WEG quality, and still get the sophisticated arc quenching techniques to reduce excess heat on the contacts.

Given their compact footprints, CWM_N contactors allow total panel space optimization, with only a few compact frame sizes from 5 to 200 Hp @ 460 V. Reducing inventory is a “snap” with CWM’s common accessories. For example, side mounted auxiliary contact blocks are the same from 5 to 200 Hp @ 460 V.

• Ease of choosing product

• Compact footprint

• Arc Quenching technique

• Reduced inventory with common accessories

• Adjustable thermal overload relay for motor

protection

• Reliable WEG Quality

NEMA Size NEMA Continuous Amp rating

WEG Continuous Amp rating

HP @ 230 V HP @ 460 V

00 9 9 1.5 2

0 18 18 3 5

1 27 32 7.5 10

2 45 50 15 25

3 90 95 30 50

4 135 150 50 100

5 270 300 100 200

LISTED

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-41

coNT

AcTo

RS

www.weg.net

Controls

NEMA Rated Contactors

CWM_N Series

3 POLE NEMA CONTACTORS WITH AC COIL

NEMA Size

Maximum UL HorsepowerAuxiliary Contacts Current

RatingAmps

Catalog Number List PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V N.O. N.C.

00 1/3 1 1.5 1.5 2 21 0

9cWM9N-10-30*

$72 Z10 1 cWM9N-01-30*

0 1 2 3 3 5 51 0

18cWM18N-10-30*

$103 Z10 1 cWM18N-01-30*

1 2 3 7.5 7.5 10 10 0 0 32 cWM32N-00-30* $140 Z1

2 3 7.5 10 15 25 25 0 0 50 cWM50N-00-30* $190 Z1

3 7.5 15 25 30 50 50 0 0 95 cWM95N-00-30* $294 Z1

4 - - 40 50 100 100 2 2 150 cWM150N-22-30# $945 Z1

5 - - 75 100 200 200 2 2 300 cWM300N-22-30# $1,890 Z1

Note:1) CWM_N Series - 9 to 95 A - AC COIL2) CWM_N Series - 150 to 300 A - AC/DC Coil with Electronic Module

# FoR coNTAcToRS: cWM150N, cWM300N

Voltage24-28

Vac/Vdc110-130 Vac/Vdc

208-250 Vac/Vdc

430-500 VAC/VDC

CODE E02 E10 E13 E21

# Ac / dc coIL VoLTAGE codE SELEcTIoN

FoR coNTAcToRS cWM9N...cWM95N

60 Hz 24V 120V 208-240V 480V 600V

CODE V04 V18 V24 V47 V56

50 Hz - 110V - 400-415V 500V

* Ac coIL VoLTAGE codE SELEcTIoN

- For additional auxilliary contacts, see page B-42

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-42

coNTAcToRS

Auxiliary contacts block

Location/description Mounting on contactorsAuxiliarycontacts

catalog NumberList

PriceMultiplier SymbolN.o. N.c.

Front Mounting

CWM9…105CWM9N…95N

1 0 bcXMF10 $10 Z1

Front Mounting 0 1 bcXMF01 $10 Z1

Front Mounting, Early Make 1 0 bcXMFA10 $13 Z1

Front Mounting, Late Break 0 1 bcXMFR01 $13 Z1

Side Mounting

CWM9…CWM300CWM9N…300N

1 1 bcXML11 $22 Z1

Side Mounting 2 0 bcXML20 $22 Z1

Side Mounting, Second Block 1 1 bcXMRL11 $22 Z1

Side Mounting, Second Block 2 0 bcXMRL20 $22 Z1

Side MountingCWM400…CWM800

1 1 bcXML11 cWM800 $54 Z1

Side Mounting, Second Block 1 1 bcXMRL11 cWM800 $54 Z1Maximum # of added auxiliary contacts per contactor frame size: Note that side mountable version has 2 aux. contacts per block. cWM9…25 = 4 aux. contacts; cWM32…40 = 6 aux. contacts; cWM50…300E = 8 aux. contacts.

Mechanical Interlock block

Location/description Mounting on contactorsAuxiliarycontacts

catalog NumberList

PriceMultiplier SymbolN.o. N.c.

Side mounted between two contactors

CWM9...105CWM9N…95N

0 0 bLIM 9-105 $29 Z1

0 2 bLIM.02 9-105 $40 Z1

CWM112…3001CWM150NCWM300N

0 0 bLIM 112-300 $63 Z1

Bottom mounted

CWM400 0 0 bLIM cWM400 $63 Z1

CWM630…CWM800 0 0 bLIM cWM800 $1,620 Z1

For CWM9…CWM105 the mechanical interlock can be used to interlock different frame sizes. For CWM112…CWM300, the mechanical interlock has to be used with contactors that have the same mechanical frame size.

For BLIM CWM800, a metal mount base is provided with this accessory for an accurate assembling of the contactors.

Surge Suppressors

description Mounting on contactors Voltage Range catalog NumberList

PriceMultiplier Symbol

Limits switching transients from contactor pick-up

CWM9...40CWM9N . . .32N

4...48Vac bAMRc4 d53 $20 Z1

50...127Vac bAMRc5 d55 $20 Z1

130...250Vac bAMRc6 d63 $20 Z1

CWM50...105CWM50N. . . 95N

24...48Vac bAMRc7 d53 $20 Z1

50...127Vac bAMRc8 d55 $20 Z1

130...250Vac bAMRc9 d63 $20 Z1

CWM9...105270 - 380Vac bAMV d68 $20 Z1

400 - 510Vac bAMV d73 $20 Z1

cWM112...300 with Electronic Module and cWM400…800 already have the surge suppressor built-in on the electronic module

Accessories

Controls IEC Contactors - CWM Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-43

coNT

AcTo

RS

Terminal cover for cWM_E contactor Series

Location/description Mounting on contactors catalog NumberList

PriceMultiplier Symbol

Protection for contactor terminals

(3 covers per package)

CWM400 bMP cWM400 $60 Z1

CWM630…CWM800 bMP cWM800 $110 Z1

Lugs for cWM contactor Series (3 units per package)

description / Wire Range Mounting on contactors catalog NumberList

PriceMultiplier Symbol

300 MCM…6 AWG CWM112...150 LW1-S300 $52 Z1

300 MCM…6 AWG CWM180 LW2-S300 $52 Z1

600 MCM…4 AWG CWM250…CWM300 LW1-S600 $98 Z1

(2) 3-4/0 AWG CWM400 bMJ cWM400 $98 Z1

(2) 3/0-600 MCM CWM630…CWM800 bMJ cWM800 $158 Z1

Accessories

Controls IEC Contactors - CWM Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-44

coNTAcToRS

description Mounting on contactors catalog Number List Price MultiplierSymbol

Replacement Coil

Coil voltage code is required to complete part number

Ac coILCWM9... 25

CWM9N... 18N bcA4-25* $28 Z1

CWM32...40CWM32N... 105N bcA4-40* $35 Z1

CWM50...105CWM50N... 95N bcA-105* $44 Z1

dc coILCWM9...25 bcc-25+ $30 Z1CWM32...40 bEcc4-40+ $40 Z1CWM150N bEcc-105+ $60 Z1

Ac/dc ELEcTRoNIcModuLE & coIL1

CWM112...150CWM150N

bcE-150# $90 Z1ME-300# $215 Z1

CWM180bcE-215# $118 Z1ME-300# $215 Z1

CWM250…300CWM300N

bcE-300# $146 Z1ME-300# $215 Z1

CWM400 bcE-400 ^ $610 Z1CWM630…800 bcE-800 ^ $740 Z1

Controls IEC Contactors - CWM Series

+ DC COIL VOLTAGE CODE SELECTION

Voltage 24V 110V

codE c03 c12

Voltage 24-28V 110-130V

codE c34 c40

# AC/DC COIL VOLTAGE CODE SELECTION - Electronic Contactor Required

Voltage 24-28Vac/Vdc 110-130Vac/Vdc 208-250Vac/Vdc 430-500Vac/Vdc

codE E02 E10 E13 E21

Mounting on CWM112-CWM300 CWM112-CWM300 CWM112-CWM300 CWM112-CWM300

^ AC/DC COIL VOLTAGE CODE SELECTION - Electronic Contactor Required

Voltage 100-240Vac/100-220Vdc 100-127Vac/100-110Vdc 200-240Vac/200-220Vdc 440-575Vac

codE E36 E35 E39 d82

Mounting on CWM400 CWM630-CWM800 CWM630-CWM800 CWM400-CWM800

FOR CONTACTORS CWM9...CWM25

FOR CONTACTORS CWM32...CWM105

FOR CONTACTORS CWM112, 150, 180, 250, 300, CWM150N, CWM300N

FOR CONTACTORS CWM400, 630, 800

60 Hz 24V 48V 120V 208-240V 277V 480V 600V

codE V04 V10 V18 V24 V37 V47 V56

50 Hz - 42V 110V - 230-240V 400-415V 500V

* AC COIL VOLTAGE CODE SELECTION FOR CONTACTORS CWM9...CWM105, CWM150N, CWM300N, CWM9N...95N

1) Stock available only for contactor version …-10-30... and …-00-30…. Example CWM9-10-30V24 or CWM50-00-30V24

- 1) Module (ME-) & Coil (BCE-) must be used together for a proper contactor operation.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-45

coNT

AcTo

RS

TYPE cWM9 cWM12 cWM18 cWM25 cWM32 cWM40 cWM50 cWM65 cWM80 cWM95 cWM105

StandardsDevices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1,

Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Rated Insulation Voltage ui

Acc. IEC; VDE 0660 [V] 1000

Acc. UL; CSA [V] 600

Rated Impulse Voltage uimp6 8

Acc. IEC60947-1 [kV]

Rated operating Frequency [Hz] 25…400

degree of Protection Protection against direct contact Acc. VDE 0160 - Part. 100

Main terminals IP20 IP10

Coil terminals IP20

Auxiliary terminals IP20

Ambient Temperature

Storage -55 to +80oC (-67 to +176oF)

Operating -25 to +55oC (-13 to +131oF)

Altitude

Up to 1,500m Nominal values

Other altitudes See graphic on page B-45

Pollution degree 3

climatic Withstand According to IEC 60680-2

Mounting 35mm rail Acc. DIN EN 50 022

Vibration Resistance(5 to 200 hz)

Contactor open [g] 3 3 3 7.5 8 8 4.5 4.5 4.5 5 5

Contactor closed at Uc [g] 6 6 6 8 12 12 9 9 9 7 7

Mechanical Endurance

AC Coil Million ops. 10

Electrical Endurance Ac-3 Million ops. 1.8 1.6 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1

Shock Resistance (1/2 sin wave = 11ms)

Contactor open [g] 8 8 8 8 7 7 6 6 6 6 6

Contactor closed at Uc [g] 12 12 12 12 12 12 10 10 10 10 10

Weight [kg] 0.30 0.30 0.30 0.30 0.52 0.54 1.11 1.12 1.13 1.45 1.47

AC Coil [lb] 0.65 0.65 0.65 0.65 1.15 1.19 2.44 2.47 2.49 3.20 3.24

Terminal capacity Allen Head

Fine - Stranded with sleeve Top [mm2] 2x0.5-2.5 2x0.5-2.5 2x0.5-2.5 2x1-2.5 0.75-16 0.75-16 1-35 1-35 1-35 1.5-50 1.5-50

Bottom [mm2]

or 2x2.5-6 or 2x2.5-6 or 2x2.5-6 or 2x2.5-10 1.0-16 1.0-16 2.5-35 2.5-35 2.5-35 4-35 4-35

coarse - Stranded / Solid Top [mm2] 2x1-2.5 2x1-2.5 2x1-2.5 2x1-2.5 1-16 1-16 1.5-35 1.5-35 1.5-35 2.5-50 2.5-50

Bottom [mm2]

or 2x2.5-6 or 2x2.5-6 or 2x2.5-6 or 2x2.5-10 1.5-16 1.5-16 6-35 6-35 6-35 6-35 6-35

Stranded / Solid (uL / cSA) Top [AWG] 2x20-12 2x20-12 2x20-12 2x18-12 18-6 18-6 16-2 16-2 16-2 16-1 16-1

Bottom [AWG]

or 2x12-10 or 2x12-10 or 2x12-10 or 2x12-8 16-6 16-6 14-2 14-2 14-2 10-2 10-2

drive Size Philips #2 5/32” (4mm.)

Tightening Torquelb-in (Nm)

8.9...15 (1...1.7)

8.9...15 (1...1.7)

8.9...15 (1...1.7)

14.2...26.6 (1.6...3)

22.1...35..4 (2.5...4)

22.1...35..4 (2.5...4)

35.4...53.1 (4...6)

35.4...53.1 (4...6)

35.4...53.1 (4...6)

44.3...57.5 (5...6.5)

44.3...57.5 (5...6.5)

General Ratings

Controls IEC Contactors - CWM Series

Cross / Slotted Combination

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-46

coNTAcToRS

General Ratings

Controls IEC Contactors - CWM Series

TYPE cWM112 cWM150 cWM180 cWM250 cWM300 cWM400 cWM630 cWM800

Standards Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Rated Insulation Voltage ui

Acc. IEC; VDE 0660 [V] 1000

Acc. UL; CSA [V] 600

Rated Impulse Voltage uimp

Acc. IEC60947-1 [kV] 8

Rated operating Frequency [Hz] 25…400

degree of protection Protection against direct contact acc. VDE 0160 - Part. 100

Main terminals IP00

Coil terminals IP20

Auxiliary terminals IP20

Ambient Temperature

Storage -55 to +80oC (-67 to +176oF)

Operating -25 to +55oC (-13 to +131oF)

Altitude

Up to 1,500m Nominal values

Other altitudes See graphic on page 45 up to 2000m

Pollution degree 3

climatic withstand According to IEC 68-2

Mounting Screw to panel

Vibration Resistance (5 to 200 hz)

Contactor open [g] 4

Contactor closed at Uc [g] 4

Mechanical Endurance

AC Coil Million ops 10 5

Electrical Endurance Ac-3 Million ops 1.1 1.1 1.0 1.0 1.0 0.5

Shock Resistance (1/2 sin wave = 11ms)

Contactor open [g] 3

Contactor closed at Uc [g] 3

Weight

AC/DC Coil

[kg] 2.54 2.54 4.04 6.14 6.14 9.2 22.4 22.4

[lb] 5.60 5.60 8.91 13.54 13.54 20 49 49

Terminal capacity

Fine - Stranded with sleeve [mm2] 2 x (25-70) 2 x (50-120) 2 x (50-150) 1 x 150 1 x 240 1 x 240

AWG wires with end sleeve 1 x 300 or 2 x 107 1 x 500 or 2 x 300 Nº2 30×5 Nº2 50×5 Nº2 60×5

Busbars [mm] 2 x (15 x 3) 2 x (20 x 3) 2 x (30 x 5) - - -

Tightening Torque lb-in (Nm) 47.8-53.1(5.4-6) 123.9-141.6 (14-16) 203.6-230.1 (23-26) 203.6 (23) 504.5 (57) 504.5 (57)

0.50.5

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-47

coNT

AcTo

RS

TYPE cWM9 cWM12 cWM18 cWM25 cWM32 cWM40 cWM50 cWM65 cWM80 cWM95 cWM105

Standard uL/cSA Ratings

Rated operating Voltage [V] 600

General Purpose Rating [A] 25 25 32 32 60 60 90 110 110 140 140

Switching Motor Loads

Full Voltage - 50/60Hz

1-phase 115V [A] 9.8 13.8 16 24 34 34 56 56 80 80 100

230V [A] 10 12 17 28 28 28 40 50 68 68 88

115V [HP] 1/2 3/4 1 2 3 3 5 5 7-1/2 7-1/2 10

230V [HP] 1-1/2 2 3 5 5 7 1/2 10 10 15 15 20

3-phase 200V [A] 11 11 17.5 25 32.2 32.2 48.3 62.1 62.1 78.2 92

230V [A] 9.6 9.6 15.2 22 28 42 42 54 68 80 104

460V [A] 7.6 11 14 21 27 40 52 65 65 77 96

575V [A] 9 11 17 17 27 27 41 52 62 77 77

200V [HP] 3 3 5 7-1/2 10 10 15 20 20 25 30

230V [HP] 3 3 5 7-1/2 10 15 15 20 25 30 40

460V [HP] 5 7-1/2 10 15 20 30 40 50 50 60 75

575V [HP] 7-1/2 10 15 15 25 25 40 50 60 75 75

Short circuit Rating 600V [kA] 5 5 5 5 5 5 10 10 10 10 10

Standard IEc Ratings (IEc EN 60947)

Rated operating Voltage [V] 690 1000

Rated Thermal current Ith [A] 25 25 32 45 60 60 90 110 110 140 140

Switching Motor Loads

AC-3 - 50/60Hz

3-phase 220-240V [A] 9 12 18 25 32 40 50 65 80 95 105

380-400V [A] 9 12 18 25 32 40 50 65 80 95 105

415-440V [A] 9 12 18 25 32 40 50 65 80 95 105

500V [A] 7.5 10.5 14 19 24 32 38 55 63 79 85

660-690V [A] 7 9 13 15 22 25 34 44 48 60 80

220-240V [kW] 2.2 3 4 7.5 9 11 15 18.5 22 25 30

380-400V [kW] 4 5.5 7.5 11 15 18.5 22 30 37 45 55

415-440V [kW] 4 5.5 7.5 11 15 22 25 37 45 50 55

500V [kW] 5.5 7.5 10 15 18.5 25 30 40 45 55 65

660-690V [kW] 5.5 7.5 10 15 18.5 30 35 45 45 55 65

Maximum Switching Rate

AC-1 [ops/hr] 1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200

AC-3 [ops/hr] 1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200 1,200 600 600

no load [ops/hr] 9,000 9,000 9,000 9,000 9,000 9,000 5,000 5,000 5,000 5,000 5,000

AC-4

200,000 operations; <= 690V [A] 5 7 8 12 16 18.5 23 30 37 44 50

50/60Hz 220-230V [kW] 1.1 1.5 1.5 3 4 4.5 5.5 7.5 9.2 11 12.5

[HP] 1.5 2 2 4 5.4 6 7.5 10 12.5 15 17

380-400V [kW] 2.2 3 3.7 5.5 7.5 9.2 11 15 18.5 22 22

[HP] 3 4 5 7.5 10 12.5 15 20 25 30 30

415-440V [kW] 2.2 3.7 4.5 5.5 9.2 11 11 15 22 22 30

[HP] 3 5 6 7.5 12.5 15 15 20 30 30 40

500V [kW] 3 4 5.5 7.5 10 11 15 18.5 22 25 30

[HP] 4 5.4 7.5 10 13 15 20 25 30 33 40

660-690V [kW] 3 4.5 5.5 7.5 11 12.5 15 20 25 30 33

[HP] 4 6 7.5 10 15 17 20 27 33 40 45

Maximum Switching Rate [ops/hr] 360 360 360 360 360 200 200 200 200 200 200

Making capacity [A] 300 300 300 450 550 550 1000 1000 1000 1280 1280

Power Contacts

Controls IEC Contactors - CWM Series

1-800-ASK-4WEGB-48

www.weg.net

Data is subject to change without notice.

coNTAcToRS

Built-in Auxiliary Contacts

TYPE CWM9 CWM12 CWM18

Rated Insulation Voltage ui

Acc. IEC; VDE 0660 [V] 1000 Acc. UL; CSA [V] 600Rated operating Voltage ue Acc. IEC; VDE 0660 [V] 690 Acc. UL; CSA [V] 600Rated Thermal current Ith <=55oc [A] 20Rated operating current Ie Acc. IEC 60947-5-1 / AC-15 110-127V [A] 10

220-240V [A] 10380-400V [A] 6415-450V [A] 5500V [A] 4660-690V [A] 2

Acc. UL; CSA A600Rated operating current Ie Acc. IEC 60947-5-1 / DC-13 24V [A] 6

48V [A] 4110V [A] 2220V [A] 0.7440V [A] 0.7

Acc. UL; CSA P600Making capacity Im AC-15 / AC-11 Ue <= 690V 50/60Hz [A] 250 DC-13 / DC-11 Ue <= 440Vdc [A] 250breaking capacity Ic AC-15 / AC-11 Ue <= 400V 50/60Hz [A] 250 DC-13 / DC-11 Ue <=220Vdc [A] 2Short circuit Protection with Fuses Acc. IEC 60947-5-1 - gL/gG [A] 10Minimum Switching capacity [V/mA] 17/5Electrical Endurance Million ops. 1Mechanical Endurance Million ops. 10Guaranteed Non-overlap Time [ms] 1.5Insulation Resistance [MOhm] >10

Controls IEC Contactors - CWM SeriesPower Contacts cont.

breaking capacity Ue=400V [A] 250 250 250 450 450 920 920 920 920 1050 1050

Ue=500V [A] 250 250 250 320 450 920 920 920 920 1050 1050

Ue=690V [A] 130 130 130 170 205 780 780 780 780 950 950

Impedance per Pole [mW] 2.41 2.41 2.35 1.65 1.28 0.95 0.85 0.86 0.86 0.76 0.76

Power dissipation per Pole

AC-1 [W] 1.47 1.47 2.46 3.34 4.6 3.42 6.86 10.40 10.40 14.89 14.89

AC-3 [W] 0.19 0.34 0.78 1.03 1.31 1.52 2.12 3.63 5.5 6.86 8.37

Short Time current Icw

1 sec. [A] 455 455 570 630 1010 1265 1580 2530 2530 3300 3300

5 sec. [A] 205 205 254 280 450 450 710 1130 1130 1485 1485

10 sec. [A] 144 144 180 200 320 400 500 800 800 1050 1050

30 sec. [A] 85 85 104 115 185 230 290 460 460 600 600

1 min. [A] 60 60 74 80 130 165 205 325 325 430 430

3 min. [A] 35 35 46 50 90 100 120 185 185 250 250

Rec. time [min.] 10 10 10 10 10 10 10 10 10 10 10

Short circuit coordination

Acc. to IEC

Coordination Type “1” gL/gG [A] 50 50 63 63 100 125 200 200 200 250 250

Coordination Type “2” gL/gG [A] 25 35 35 50 63 80 100 125 125 160 200

Acc. to UL/CSA J Type [A] 25 35 40 45 60 70 100 125 125 150 200

CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105

Power Contacts cont.

0° ≤ 104°F

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-49

coNT

AcTo

RS

Power Contact

Controls IEC Contactors - CWM Series

TYPE cWM112 cWM150 cWM180 cWM250 cWM300 cWM400 cWM630 cWM800

NEMA Ratings

Rated operating Voltage [V] 600

General Purpose Rating [A] 170 170 200 300 400 450 660 900

Switching Motor Loads

Full Voltage - 50/60Hz

1-phase 115V [A] - - - - - - - -

230V [A] - - - - - - - -

115V [HP] - - - - - - - -

230V [HP] - - - - - - - -

3-phase 200V [A] 120 150 177 221 285 359 414 552

230V [A] 130 154 192 248 312 360 480 772

460V [A] 124 156 180 240 302 361 477 -

575V [A] 99 144 192 242 336 289 382 -

200V [HP] 40 50 60 75 100 125 150 200

230V [HP] 50 60 75 100 125 150 200 300

460V [HP] 100 125 150 200 250 300 400 600

575V [HP] 100 150 200 250 350 300 400 600

Short circuit Rating 600V [kA] 10 10 10 18 18 18 30 30

Standard IEc Ratings (IEc/EN 60947)

Rated operating Voltage [V] 1000

Rated Thermal current Ith [A] 180 225 225 350 350 450 660 900

Switching Motor Loads

AC-3 - 50/60Hz

3-phase 220-240V [A] 112 150 180 250 300 400 630 800

380-400V [A] 112 150 180 250 300 400 630 800

415-440V [A] 112 150 180 250 300 400 630 800

500V [A] 95 130 155 220 265 350 500 720

660-690V [A] 82 110 135 185 220 300 420 630

220-240V [kW] 30 45 55 75 90 110 185 220

380-400V [kW] 55 75 90 132 160 220 330 450

415-440V [kW] 55 90 110 150 185 220 370 500

500V [kW] 55 90 110 160 200 220 330 500

660-690V [kW] 75 110 110 160 200 260 400 560

Maximum Switching Rate

AC-1 [ops/hr] 600 600 600 600 600 500 500 500

AC-3 [ops/hr] 600 600 600 600 600 500 500 500

no load [ops/hr] 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-50

coNTAcToRS

Power Contact cont.

Controls IEC Contactors - CWM Series

TYPE cWM112 cWM150 cWM180 cWM250 cWM300 cWM400 cWM500 cWM630 cWM800

AC-4

200,000 operations; <= 690V [A] 50 55 58 100 130 - - -

50/60Hz 220-230V [kW] 18.5 20 22 37 45 90 110 185

[HP] 25 27 30 50 60 125 150 250

380-400V [kW] 30 33 37 55 75 150 220 330

[HP] 40 44 50 75 100 200 300 450

415-440V [kW] 37 40 45 63 80 185 220 370

[HP] 50 54 60 84 107 250 300 500

500V [kW] 40 45 50 75 90 - - -

[HP] 54 60 67 100 121 - - -

660-690V [kW] 45 50 55 90 100 - - -

[HP] 600 67 75 121 133 - - -

Maximum Switching Rate [ops/hr] 150 150 150 150 150 - - -

Making capacity [A] 1430 1820 2100 2600 3000

breaking capacity

Ue<=400V [A] 1290 1350 1400 2000 - 4000 6300 8000

Ue=500V [A] 1290 1350 1400 2000 - 4000 6300 8000

Impedance per pole [mW] 0.5 0.5 0.45 0.3 0.3 - - -

Power dissipation per Pole

AC-1 [W] 16 25 21.6 35 45.7 - - -

AC-3 [W] 6.2 11.1 13.8 17.9 25.7 - - -

Short Time current Icw

°≤ 104°F 1 sec. [A] 3165 3763 4649 4427 - - - -

5 sec. [A] 1820 2164 2673 2546 - - - -

10 sec. [A] 1430 1700 2100 2000 - - - -

30 sec. [A] 826 980 1212 1155 - - - -

1 min. [A] 584 694 857 816 - - - -

3 min. [A] 337 401 495 471 - - - -

Recovery time [min.] 10 10 10 10 10 - - -

Short circuit coordination

Acc. to IEC

Coordination type “1” gL/gG [A] 315 355 355 500 630 630 800 1000

Coordination type “2” gL/gG [A] 224 250 250 400 500 - - -

Acc. to UL/CSA J Type [A] 250 350 400 500 700 700 900 1100

TYPE cWM9 cWM12 cWM18 cWM25 cWM32 cWM40 cWM50 cWM65 cWM80 cWM95 cWM105

Rated Insulation Voltage ui Acc. IEC; VDE 0660 [V]Acc. UL; CSA [V]

1000600

Standard Voltages [V] 12...440 24...240 24...240

coil operating limits Pick-up xUc [V] Drop-out xUc [V]

0.4...0.70.15...0.4

0.85...1.1

0.45...0.750.15...0.45

0.7...0.8

0.4...0.6

operating Time Coil energization - N.O. [ms] Coil de-energization - N.O. [ms]

35...457...12

40...5530...65

50...6055...60

coil consumption Sealed [W] Inrush [W]

3.8...7.53.8...7.5

6240

6.5340

Stranded / Solid(uL / cSA)

[AWG]2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-51

coNT

AcTo

RS

TYPE cWM9 cWM12 cWM18 cWM25 cWM32 cWM40 cWM50 cWM65 cWM80 cWM95 cWM105

Rated Insulation Voltage ui

Acc. IEC; VDE 0660 [V] 1000

Acc. UL; CSA [V] 600

Rated operating Voltage ue

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Standard Voltages 60hz [V] 24...600

coil operating limits

Monofrequency coils xUc 0.85…1.1

Pick-up xUc [V] 0.4...0.76 0.5...0.76 0.5...0.76

Drop-out xUc [V] 0.25...0.65 0.3...0.65 0.25...0.6

operating Time

Coil energization - N.O. [ms] 8...20 10...19 15...30

Coil de-energization - N.O. [ms] 6...13 5...25 9...15

coil consumption

Single coils

Sealed [VA] 4...7.2 6.6...12.5

Inrush [VA] 70 98

Thermal Power dissipation

60Hz [W] 2.6 4.3 8.0

Power Factor

Closed Cos phi 0.28 0.34 0.32

Opened Cos phi 0.85 0.69 0.54

Stranded / Solid(uL / cSA)

[AWG]2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10 2x12-10

Control circuit ratings - AC Coil

Control circuit ratings - DC Coil

Controls IEC Contactors - CWM Series

13.1...19.1

255

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-52

coNTAcToRS

Electronic Module Control Circuit

Controls IEC Contactors - CWM Series

TYPE CWM112 CWM150 CWM180 CWM250 CWM300 CWM400 CWM630 CWM800

Rated Insulation Voltage ui

Acc. IEC; VDE 0660 [V] 1000

Acc. UL; CSA [V] 600

Rated operating Voltage ue

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Standard Voltages 50hz; 60hz; dc [V] 24…600

coil operating limits

xUc [V] 0.65…1.1

Pick-up xUc [V] 0.70...0.85

Drop-out xUc [V] 0.40...0.60

operating Time

Coil energization - N.O. [ms] 60…70 60…70 60…70 60…70 60…70 64…68 66…70 66…70

Coil de-energization - N.O. [ms] 13…17 13…17 13…17 13…17 13…17 43…47 45…49 45…49

coil consumption

Sealed AC [VA] 14.8 14.8 14.1 14.1 14.1 14 17 29

Inrush AC [VA] 213 213 214 229 229 571 1000 1000

Sealed DC [VA] 2.4 2.4 2.4 2.5 2.5 14 17 29

Inrush DC [VA] 166 166 154 171 171 571 1000 1000

Thermal Power dissipation

AC [W] 3.9 3.9 3.8 3.7 3.7 4.7 4.9 5.3

DC [W] 2.4 2.4 2.4 2.5 2.5 5.0 6.3 7.8

0.85...1.1

0.77...0.83

0.48...0.53

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-53

coNT

AcTo

RS

TYPE bcXMF bcXML bcXMRL bLIM.02

Rated Insulation Voltage ui

Acc. IEC; VDE 0660 [V] 1000

Acc. UL; CSA [V] 600

Rated operating Voltage ue

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Thermal current Ith <=55oC [A] 10

Rated operating current Ie

Acc. IEC 60947-5-1 / AC-15 110-127V [A] 6

220-240V [A] 6

380-400V [A] 4

415-450V [A] 3.5

500V [A] 2.5

660-690V [A] 1.5

Acc. UL; CSA A600

Rated operating current Ie

Acc. IEC 60947-5-1 / DC-13 24V [A] 4

48V [A] 2

110V [A] 0.7

220V [A] 0.3

440V [A] 0.15

Acc. UL; CSA Q600

Making capacity Im

AC-15 / AC-11 Ue <= 400V 50/60Hz [A] 90

DC-13 / DC-11 Ue <= 220Vdc [A] 90

breaking capacity Ic

AC-15 / AC-11 Ue <= 400V 50/60Hz [A] 60

DC-13 / DC-11 Ue <= 220Vdc [A] 0.95

Short circuit Protection with Fuses

Acc. IEC 60947-5-1 - gL/gG [A] 10

Minimum Switching capacity [V/mA] 17/5

Electrical Endurance Million ops. 1

Mechanical Endurance Million ops. 10

Guaranteed Non-overlap Time [ms] 1.5

Insulation Resistance [MOhm] >10

MetersNOTE:

Altitude compensation in CWM Series contactors, considers a factor

according to which the rated power must be reduced.

The derating of the permissible operating power for installation altitudes

above 1,500 m (5,000 ft) is calculated according to:

Total derating = Derating current x Derating voltage

Example: Altitude: 3,000 m (10,000 ft):

Derating current K1 = 0.85

Derating voltage K2 = 0.88

Total derating = 0.85 x 0.88 = 0.75 x HP

derating Factor

Graphic Altitude

Auxiliary contact block ratings

Controls IEC Contactors - CWM Series

1-800-ASK-4WEGB-54

www.weg.net

Data is subject to change without notice.

coNTAcToRS

32 60 1100.1

1

10

1 10 100 1000Current Ic = Ie (A)

Num

ber o

f ope

ratio

ns -

mill

ion

of o

pera

tions

CWM

9

CWM

32

CWM

12

CWM

40

CWM

18

CWM

25

CWM

105

CWM

65

CWM

80

CWM

95

CWM

50Category A C-1 ( Ue 690 Vac )

225 4100.1

1

10

10 100 1000Current Ic = Ie (A)

Num

ber o

f ope

ratio

ns -

mill

ion

of o

pera

tions

CWM

112

CWM

150

CWM

250

CWM

180

CWM

300

Category AC-1 ( Ue 690 Vac )

Control of resistive circuits

(power factor >= 0.95) The

current broken (Ic) in category

AC-1 is equal to the current

(Ie) drawn by the load.

Control of resistive circuits

(power factor >= 0.95) The

current broken (Ic) in category

AC-1 is equal to the current

(Ie) drawn by the load.

Control of 3-phase asynchro-

nous squirrel cage motors

with breaking while running.

The current broken (Ic) in

category AC-3 is equal to the

operational current of the mo-

tor (Ie).

AC-1: CWM9...105 Electric Lifespan

AC-1: CWM112...300 Electric Lifespan

AC-3: CWM9...300 Electric Lifespan

Controls IEC Contactors - CWM Series

CW

M9

CW

M12

CW

M18

18 32

CW

M32

CW

M40

CW

M50

65

CW

M65

CW

M80

CW

M10

5

CW

M11

2

150

CW

M15

0

CW

M18

0

CW

M25

0

300

CW

M30

0

0 1

1

10

1 10 100 1000Current Ic Ie (A)

Num

ber o

f ope

ratio

ns -

mill

ion

of o

pera

tions

Category AC-3 ( Ue 440 Vac )

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-55

coNT

AcTo

RS

Control of 3-phase asynchronous

squirrel cage motors with breaking

while motor stalled.

The current broken (Ic) in category

AC-4 is equal to 6 times the opera-

tional current of the motor (Ie).

Control of 3-phase asynchronous

squirrel cage motors with breaking

while motor stalled.

The current broken (Ic) in category

AC-4 is equal to 6 times the opera-

tional current of the motor (Ie).

In many applications there is a mixture of AC-3 and AC-4 duty. For these applications the electric

lifespan of a particular contactor can be estimated using the formula:

W

E= Estimated electric lifespan for mixed duty application.

AC-3= Number of electrical operations taken from the AC-3 Duty life curve.

AC-4= Number of electrical operations taken from the AC-4 Duty life curve.

P= Proportion of AC-4 operations to total operations for the application, expressed as a percentage.

CWM

9

CWM

12

CWM

18

CWM

25

CWM

32

CWM

40

CWM

50

CWM

65CW

M80

CWM

95CW

M10

5

30 72 180 3000.01

0.1

1

10

1 10 100 1000

Current Ic = 6 x Ie (A)

Num

ber o

f ope

ratio

ns -

mlli

on o

f ope

ratio

ns

Category AC-4 ( Ue 440 Vac )C

WM

112E

CW

M15

0E

CW

M18

0E

CW

M25

0E

1800

CW

M30

0E

0.01

0.1

1

10

10 100 1000 10000Current Ic = 6 x Ie (A)

Num

ber o

f ope

ratio

ns -

mill

ion

of o

pera

tions

Category AC-4 ( Ue 440 )

AC-4: CWM9...105 Electric Lifespan

AC-4: CWM112...300 Electric Lifespan

Controls IEC Contactors - CWM Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-56

coNTAcToRS

Electrical Lifespan

Ue ≤ 220-240 VAC

Ue ≤ 380-460 VAC

Rated operational current Ie (A)

Num

ber o

f ope

ratio

ns (1

05 )Nu

mbe

r of o

pera

tions

(105 )

Controls IEC Contactors - CWM Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-57

coNT

AcTo

RS

BCXML BCXML BCXMF

BCXMF

144 [5.67]115 [4.53]

Vac Contactors Vdc Contactors

BCXML

BCXML

BCXMF

146 [5.75]117 [4.61]

147.29 [5.80]

118 [4.65]

5

BCXMLBCXML BCXMF

BCXMF

6 [4

Mechanical Drawings mm (in)

CWM9, CWM9N, CWM12, CWM18, and CWM18N

CWM25

CWM32, CWM32N and CWM40

Controls IEC & NEMA Contactors - CWM and CWM-N Series

Vac Contactors Vdc Contactors

Vac Contactors Vdc Contactors

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-58

coNTAcToRS

BCXML

BCXML

BCXMF

Vac / Vdc Contactors

BCXML BCXML

BCXMF

Vac / Vdc Contactors

CWM95, CWM95N, and CWM105

Controls IEC & NEMA Contactors - CWM and CWM-N SeriesMechanical Drawings mm (in)

CWM50, CWM50N, CWM65 and CWM80

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-59

coNT

AcTo

RS

Mechanical Drawings mm (in)

Controls IEC & NEMA Contactors - CWM and CWM-N Series

CWM180

CWM112. CWM150 and CWM150N

CWM250, CWM300 and CWM300N

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-60

coNTAcToRS

Mechanical Drawings mm (in)

CWM400

CWM630 and CWM800

Controls IEC & NEMA Contactors - CWM and CWM-N Series

80/ [3 16]

160/ [6 31]

6xØ

17/ [

Ø0.

67]

270/

[10.

62]

40/ [1 57]

329/

[12.

96]

243/ [9 58]

2xØ12/ [Ø0 47]

250/ [9 84]

250/

[9.8

4]

289/

[11.

38]

284/ [11 18]

R6/ [R0 24]

284/ [11 18]

310/

[12.

19]

20/ [

0.78

]

149/ [5 88]

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-61

coNT

AcTo

RS

Mechanical Drawings mm (in)

CWM112 - CWM150 + LW1-S300 (contactor with lugs)

Controls IEC & NEMA Contactors - CWM and CWM-N Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-62

coNTAcToRS

Mechanical Drawings mm (in)

CWM180 + LW2-S300 (contactor with lugs)

Controls IEC & NEMA Contactors - CWM and CWM-N Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-63

coNT

AcTo

RS

Mechanical Drawings mm (in)

CWM250 + LW1-S600 (contactor with lugs)

Controls IEC & NEMA Contactors - CWM and CWM-N Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-64

coNTAcToRS

www.weg.net

Mechanical Drawings mm (in)

CWM400 + BMJ (contactor with lugs)

Controls IEC & NEMA Contactors - CWM and CWM-N Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-65

coNT

AcTo

RS

Mechanical Drawings mm (in)

CWM630-CWM800 + BMJ (contactor with lugs)

Controls IEC & NEMA Contactors - CWM and CWM-N Series

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-66

coNTAcToRS

BLIM9-105

A

B

C A

51

64.5

D

BLIM112-300

Controls IEC & NEMA Contactors - CWM and CWM-N SeriesReversing Contactors mm (in)

BLIM CWM400

BLIM CWM800

440/ [17 32]

4xØ12

/ [Ø0.4

72]

86/ [3]

318/ [13]

351/

[13

82]

321/

[12

64]

680/ [26 77]

75/ [2 94]

41 6/ [1 64]

60/

[2.4

]

84/ [3 3]

145/ [5 71]

222/

[874

]

50/ [1 97]

58/ [2 28]

145/ [5 71]

58/ [2 28]

41 6/ [1 6]

331 6/ [13 06]

Ø9

[Ø0

35]

R5 [R0.18]

Models A b c d

cWM9…25 35 (1,4) 72,5 (2,9) 22 (0,9) 102 (4)

cWM32…40 45 (1,8) 79 (3,1) 22 (0,9) 122 (4,8)

cWM50…80 57 (2,2) 90 (3,5) 21 (0,8) 144 (5,7)

cWM95…105 57 (2,2) 90 (3,5) 29,8 (1,2) 153 (6)

Models A b c d

cWM112…150 100 (3,9) 130 (5,1) 51 (2) 272,5 (10,7)

cWM180 110 (4,3) 160 (6,3) 58,5 (2,3) 303,5 (11,9)

cWM250…300 120 (4,7) 180 (7,1) 57 (2,2) 325,4 (12,8)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-67

coNT

AcTo

RS

CWM9...105

CWM112...300

Mounting position1

30°

30°

CWM400...800

Controls IEC & NEMA Contactors - CWM and CWM-N Series

Note: 1) Consult WEG if application requires a different mounting position

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-68

RW SERIES

Rated for the new industryRW overload relays are an important part of WEG Controls’ range of products. As usual in WEG products, an extended operational service life is one of the main features you can find in RW overload relays.

WEG’s RW Class 10 Thermal Overload Relays are designed for use with, and as perfect compliment to, the CWC miniature and CWM standard contactors.

Effectively, RW overload relays can be mounted directly under WEG contactors, assuring electrical and mechanical operation as an open across-the-line starter, from fractional power to 75HP @ 460V. Accessories are also available for separate mounting. RW overload relays are available in compact frame sizes, from 0.28 to 840A.

Modern ArchitecturePrevious models of open overloads with “heaters” encounter problems in the field, includingg Inaccurate trip point, because of

uneven screw tightness when installed on the field, one phase at a time.

g Ambient problems, such as dust and other contaminants, because of their open design,

g Inability to protect in case of single phase failure,

g Nuisance tripping, because no temperature compensation is possible.

WEG overload relays’ modern design solves all of these problems. RW overload relays are fitted with fixed bimetallic elements, which eliminate any need for heater elements for field installation or future upgrading to a more efficient motor. All sizes provide complete motor protection by offering

g Ambient temperature compensation (-40F to +1400F)g Phase loss sensitivity protection,g Current unbalance sensitivity.

Dial FLA SettingThe trip-current is set via an infinitely adjustable dial designed with the motor’s full load current (FLA) in mind.

Temperature CompensationBecause RW overload relays include a fourth bimetallic strip in addition to the three that are directly heated by the motor current, ambient temperature variations in the range of -4ºF to +140ºF are no obstacle for accurate protection of your motors even in the toughest conditions.

Phase Failure SensitivityWEG overload relays include phase failure sensitivity protection as standard. This feature ensures fast tripping in case of phase loss, protecting your motor and avoiding expensive repairs / corrective maintenances.

Multi Function Button “R”The programmable RESET button can be selected to operate in a Manual or Automatic mode, with or without TEST capabilities of the isolated “trip” NC and “alarm” NO auxiliary contacts. The “R” multifunction RESET / TEST button can be set in four different positions; H (manual RESET only), HAND (manual RESET/TEST), AUTO (automatic RESET/TEST) and A (automatic RESET only).In HAND and AUTO positions, when gray R button is pushed, both N.O. 97-98 and N.C. 95-96 contacts change states.

Standards and Approvals

IEC 60947 and VDE 0660.

cULus

CE

Marine

Thermal Overload Relays

Controls - RW Series

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-69

RW S

ERIE

S

Certifications

Controls Thermal Overload Relays - RW SeriesN OL

3 - U00427-1DRW

OVERLOAD RELAY SERIES:

RW: Thermal overload relay

POWER POLE:

3: 3 NO Power Poles 2: 2 NO Power Poles

OVERLOAD SETTING CURRENT:

RW17 D004: 0,28 ... 0,40A ... U032: 11 … 32A

RW27 D004: 0,28 ... 0,40A ... U032: 11 … 32A

RW67 U040: 25 ... 40A ... U080: 63 … 80A ________________________________ For more details refer to selection table

RW117 U080: 63 … 80A ... U112: 90 ... 112A

RW317 U150: 100 … 150A ... U420: 275 ... 420A

RW407 U600: 400 … 600A ... U840: 560 ... 840A

Catalog part number composition

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-70

RW SERIES

Three-pole Thermal Overload Relay Class 10

Matching contactorSetting Range [A]

Max. Fuse [A] catalog Number List Price Multiplier SymbolMin. Max.

cWc07…cWc016cWcA0(Mini-contactor)

0.28 0.40 15 RW17-1d3-d004 $46 Z20.40 0.63 15 RW17-1d3-c063 $46 Z20.56 0.80 15 RW17-1d3-d008 $46 Z20.80 1.20 15 RW17-1d3-d012 $46 Z21.20 1.80 15 RW17-1d3-d018 $46 Z21.80 2.80 15 RW17-1d3-d028 $46 Z22.80 4.00 15 RW17-1d3-u004 $46 Z24.00 6.30 25 RW17-1d3-d063 $46 Z25.60 8.00 30 RW17-1d3-u008 $46 Z27.00 10.0 40 RW17-1d3-u010 $46 Z28.00 12.5 50 RW17-1d3-d125 $46 Z210.0 15.0 60 RW17-1d3-u015 $46 Z211.0 17.0 60 RW17-1d3-u017 $46 Z2

cWc025 (Mini-contactor)15.0 23.0 90 RW17-2d3-u023 $46 Z2

22.0 32.0 100 RW17-2d3-u032 $46 Z2

cWM9...cWM40cWM9N...cWM32N

0.28 0.40 15 RW27-1d3-d004 $50 Z20.40 0.63 15 RW27-1d3-c063 $50 Z20.56 0.80 15 RW27-1d3-d008 $50 Z20.80 1.20 15 RW27-1d3-d012 $50 Z21.20 1.80 15 RW27-1d3-d018 $50 Z21.80 2.80 15 RW27-1d3-d028 $50 Z22.80 4.00 15 RW27-1d3-u004 $50 Z24.00 6.30 25 RW27-1d3-d063 $50 Z25.60 8.00 30 RW27-1d3-u008 $50 Z27.00 10.0 40 RW27-1d3-u010 $50 Z28.00 12.5 50 RW27-1d3-d125 $50 Z210.0 15.0 60 RW27-1d3-u015 $50 Z211.0 17.0 60 RW27-1d3-u017 $50 Z215.0 23.0 90 RW27-1d3-u023 $50 Z222.0 32.0 90 RW27-1d3-u032 $50 Z2

cWM32...cWM40cWM32N

25.0 40.0 90 RW67-1d3-u040 $73 Z232.0 50.0 125 RW67-1d3-u050 $73 Z2

cWM50...cWM80cWM50N

25.0 40.0 90 RW67-2d3-u040 $85 Z232.0 50.0 125 RW67-2d3-u050 $85 Z240.0 57.0 150 RW67-2d3-u057 $85 Z250.0 63.0 150 RW67-2d3-u063 $85 Z257.0 70.0 175 RW67-2d3-u070 $85 Z263.0 80.0 175 RW67-2d3-u080 $110 Z2

cWM95...cWM105cWM95N

63.0 80.0 200 RW117-1d3-u080 $150 Z275.0 97.0 225 RW117-1d3-u097 $192 Z290.0 112 250 RW117-1d3-u112 $192 Z2

cWM112...cWM150cWM150N

75.0 97 225 RW117-2d3-u097 $232 Z290.0 112 250 RW117-2d3-u112 $232 Z2

cWM112…cWM300cWM300N

100 150 300 RW317-1d3-u150 $285 Z2140 215 350 RW317-1d3-u215 $285 Z2200 310 500 RW317-1d3-u310 $320 Z2

cWM400...cWM800275 420 700 RW317-1d3-u420 $320 Z2400 600 1000 RW407-1d3-u600 $690 Z2560 840 1250 RW407-1d3-u840 $690 Z2

Note: RW117-2D, RW317-1D and RW407-1D are for separate mounting - Connector links for contactors CWM112…CWM300 are available as an accessory on page B-59.

Controls Thermal Overload Relays - RW Series

g Adjustable tripping current g Phase-loss sensitivity g Tripping class 10 g Auxiliary contacts 1NO + 1NCg Temperature compensation from -40F to +1400Fg Hand/Auto/Reset button

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-71

RW S

ERIE

S

Two-pole Thermal Overload Relays Class 101 (used for single phase applications)

Controls Thermal Overload Relays - RW Series

g Adjustable tripping current g Phase-loss sensitivity g Tripping class 10 g Auxiliary contacts 1NO + 1NCg Temperature compensation from -40F to +1400Fg Hand/Auto/Reset button

Matching contactorSetting Range [A] Max. Fuse [A] catalog Number List Price Multiplier

SymbolMin. Max.

cWc07…cWc016cWcA0(Mini-contactor)

0.28 0.40 15 RW17-1d2-d004 $36 Z2

0.40 0.63 15 RW17-1d2-c063 $36 Z2

0.56 0.80 15 RW17-1d2-d008 $36 Z2

0.80 1.20 15 RW17-1d2-d012 $36 Z2

1.20 1.80 15 RW17-1d2-d018 $36 Z2

1.80 2.80 15 RW17-1d2-d028 $36 Z2

2.80 4.00 15 RW17-1d2-u004 $36 Z2

4.00 6.30 25 RW17-1d2-d063 $36 Z2

5.60 8.00 30 RW17-1d2-u008 $36 Z2

7.00 10.0 40 RW17-1d2-u010 $36 Z2

8.00 12.5 50 RW17-1d2-d125 $36 Z2

10.0 15.0 60 RW17-1d2-u015 $36 Z2

11.0 17.0 60 RW17-1d2-u017 $36 Z2

cWc025 (Mini-contactor)15.0 23.0 90 RW17-2d2-u023 $36 Z2

22.0 32.0 100 RW17-2d2-u032 $36 Z2

cWM9...cWM40

0.28 0.40 15 RW27-1d2-d004 $40 Z2

0.40 0.63 15 RW27-1d2-c063 $40 Z2

0.56 0.80 15 RW27-1d2-d008 $40 Z2

0.80 1.20 15 RW27-1d2-d012 $40 Z2

1.20 1.80 15 RW27-1d2-d018 $40 Z2

1.80 2.80 15 RW27-1d2-d028 $40 Z2

2.80 4.00 15 RW27-1d2-u004 $40 Z2

4.00 6.30 25 RW27-1d2-d063 $40 Z2

5.60 8.00 30 RW27-1d2-u008 $40 Z2

7.00 10.0 40 RW27-1d2-u010 $40 Z2

8.00 12.5 50 RW27-1d2-d125 $40 Z2

10.0 15.0 60 RW27-1d2-u015 $40 Z2

11.0 17.0 60 RW27-1d2-u017 $40 Z2

15.0 23.0 90 RW27-1d2-u023 $40 Z2

22.0 32.0 90 RW27-1d2-u032 $40 Z2

cWM32...cWM4025.0 40.0 90 RW67-1d2-u040 $65 Z2

32.0 50.0 125 RW67-1d2-u050 $65 Z2

cWM50...cWM80

25.0 40.0 90 RW67-2d2-u040 $75 Z2

32.0 50.0 125 RW67-2d2-u050 $75 Z2

40.0 57.0 150 RW67-2d2-u057 $75 Z2

50.0 63.0 150 RW67-2d2-u063 $75 Z2

57.0 70.0 175 RW67-2d2-u070 $75 Z2

63.0 80.0 175 RW67-2d2-u080 $100 Z2

Note: 1 Availability upon request.

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-72

RW SERIES

description Mounting on overload Relays (2 or 3 pole) catalog Number List Price Multiplier Symbol

Enables overload relay to be directly mounted to a back panel via screws or DIN rail

RW27-1D bF27d $14 Z2

RW67-1D and RW67-2D bF67.1d $23 Z2

RW117-1D bF117d $26 Z2

description Mounting in cover of control Panel catalog Number List Price Multiplier Symbol

Enables overload relay to be Reset from control panel, without opening the cover

22 MM Flush Reset PB Blue 'R' cSW-RSbF4R $20 Z5

30 MM Flush Reset PB Black 'Reset' cSW30-RSbW $22 Z5

description contactor overload Relay catalog Number List Price Multiplier Symbol

Link connectors for easier CWM contactors and RW overload relays assembly

CWM112 RW117-2D3 GA117d $41 Z2CWM150 RW317-1D3 GA317-1d $68 Z2CWM180 RW317-1D3 GA317-2d $70 Z2

CWM250 / CWM300 RW317-1D3 GA317-3d $118 Z2CWM400 RW317-1D3 GA317-10d $118 Z2

Controls Thermal Overload Relays - RW Series

TYPE RW17d RW27d RW67d RW117d RW317d RW407d

StandardsDevices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 /

60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Number of Poles 2 or 3

Tripping class 10

Phase Failure Sensitivity Yes

Temperature compensation Yes

Rated Insulation Voltage ui

Acc. IEC 60947-4-1 [V] 690 1000

Acc. UL; CSA [V] 600

Rated operation Voltage ue

Acc. IEC 60947-4-1 [V] 690 1000

Acc. UL; CSA [V] 600

Rated Impulse Voltage uimp [kV] 6

current

Direct YES NO

Alternating [Hz] up to 400 50/60

degree of Protection Protection against direct contact acc. VDE 0160 - Part 100 - IP20

Ambient Temperature

Storage -50 to +80ºC (-58 to 176ºF)

Operating -20 to +70ºC (-4 to 158ºF)

Ambient temperature compensation -20 to +60ºC (-4 to 140ºF)

Pollution degree 3

Mounting Direct on contactor or separately with accessory Separate

current heat Loss

Lower value of setting range (W) 0.9 0.9 1.5 2.3 1 1

Higher value of setting range (W) 1.4 1.7 4.7 4.7 1.9 1.9

Weight [kg] 0.15 0.15 0.31 0.52 2.30 3.12

[lb] 0.33 0.32 0.68 1.15 5.06 6.88

Shock Resistance

IEC 60 068 part 2-27 [g/ms]

Main Terminals capacity Cross / Slotted Combination1 Allen Head Slide Bar Slide Bar

Fine - Stranded with Sleeve [mm2] 1.5 - 10 1.5 - 10 6.0 - 35 6.0 - 35 - -

Coarse - Stranded / Solid [mm2] 1.5 - 6.0 1.5 - 6.0 6.0 - 35 25 - 35 - -

Slide Bars [mm2] - - - - 2x(25x5) 2x(60x10)

Stranded / Solid (UL / CSA) [AWG] 14 - 6 14 - 6 18 - 2 8 – 1/0 8 – 1/0 8 – 1/0

Tightening Torque [N.m] 1.4 - 2.3 1.4 - 2.3 4.0 - 6.0 4.0 - 6.0 14 - 26 23 - 26

[lb-in] 12.4 - 20.4 12.4 - 20.4 35.4 - 53.1 35.4 - 53.1 123.9 - 230.1 203.6 - 230.1

Short circuit Rating 600V [kA] 5 5 5 (40-57A)10(50-63A) 10 10 200

General Ratings

8/10

External Reset Button

Connector links (3 per package)

Separate Mounting Bracket

Assemblies with

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-73

RW S

ERIE

SAuxiliary Contacts General Ratings

TYPE RW17d RW27d RW67d RW117d RW317d RW407d

Front Auxiliary contact 1 NO + 1 NC

Rated Auxiliary contacts

AC-14/15 24V [A] 4.0

60V [A] 3.5

125V [A] 3.0

230V [A] 2.0

400V [A] 1.5

500V [A] 0.5

690V [A] 0.3

DC-13/14 24V [A] 1.0

60V [A] 0.5

110V [A] 0.25

220V [A] 0.1

UL/CSA C600 ; R300

Rated Thermal current [A] 6

Short circuit Protection

Fuses Type D or NH gL/gG [A] 6

Auxiliar Terminals capacity

Fine - Stranded with Sleeve [mm2] 1.0 - 2.5

Coarse - Stranded / Solid [mm2] 1.0 - 2.5

Stranded / Solid (UL / CSA) [AWG] 16 - 12

Tightening Torque [N.m] 1.0 - 1.5

[lb-in] 8.9 - 13.3

Controls Thermal Overload Relays - RW Series

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-74

RW SERIES

The derating of the permissible operating current for installation altitudes above 2,000m

(6,667 ft) and ambient temperatures over 60ºC (140ºF) is calculated according to:

Total derating = Derating altitude x Derating ambient temperature

Example;

Altitude: 3,000 m (10,000 ft) K1 = 0.96

Ambient temperature: 70ºC (158ºF) K2 = 0.87

Total current derating = 0.96 x 0.87 = 0.84 x Ie

In this case, the maximum rated voltage we can connect to our RW overload relay is

550V.

In order to select the proper overload relay, you have to choose a device with a cur-

rent range that accommodates:

Overload Setting Point = FLAmotor / (K1 x K2)

As in the example above, K1 x K2 = 0.84

For a motor with FLA = 20Amps

Overload Setting Point = 20 / 0.84 = 23.8Amps

RW Tripping Characteristics

The derating of a RW overload relay has two possible factors:

1) Ambient temperature

• Temperature compensation considers a factor according to which the rated

current must be reduced when ambient temperature is higher than 60ºC (140ºF).

2) Altitude

• Altitude compensation involves both, rated current and voltage.

• Current compensation considers a factor according to the rated current

must be reduced.

• For voltage, altitude limits the higher operating voltage the overload relay

can be used.

Meters

Derating Factor

Controls Thermal Overload Relays - RW Series

These tripping characteristics show the tripping of RW in relation to the

current. They show the mean values of the tolerance ranges at on ambient

temperature of 68ºF (20ºC), starting from cold stats. The tripping time of the

overloa d releases at operational temperature is reduced to approximately

25% of the values shown.

Under normal operational conditions, all three phases of the RWs should

be loaded.

x Setting current

Altitude & Temperature Derating

149ºF158ºF167ºF176ºF

(65ºC)(70ºC)(75ºC)(80ºC)

Temperature Compensation

Altitude

Current Correction

Voltage Correction [Ue]

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-75

RW S

ERIE

S

Operating Positions1

RW17D, RW27D, RW67D, RW117D, RW317D, RW407D

RW17D with CWC Series

RW27D, RW67D, RW117D, RW317D, RW407D with CWM/CWM Series

Mou ing w h contac or

Controls Thermal Overload Relays - RW Series

Th elay us b mou t

r ll , s

sho ed t t ri tio s

Mo t ng w

to 0º deg es no

180º, owever the mounting w h the elay above t

Mounting without contactor

The overload relays can be mounted at any position.

As showed at the left figure below, the inclination can not exceed ±30º degrees for a perfectly functioning of the contactor. Laterally, asshowed at the right figure below, the mounting position isequivalent to 0º degrees - not requiring a correction factor on thedial of the relay. The assembly can work with mounting variationsof 0º to 180º.

The mounting position showed at the left figure below is equivalentto 0º degrees - not requiring a correction factor on the dial of therelay. The assembly can work with mounting variations of 0º to135º for each side, however the mounting with the relay above the contactor,position between 135º and 225º, is required a correction factor of+10% on the dial of the relay. Laterally, as showed at the rightfigure below, the inclination can not exceed ± 30º for a perfectfunctioning of the contactor.

Note: 1 Please consult WEG for different mounting positions.

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-76

RW SERIES

Controls Thermal Overload Relays - Dimensions mm (in)

RW17-1D

45/ [1.77]

71,5

/ [2

.81]

82,45/ [3.25]

RW17-2D

45/ [1.77]

71/

[2.8

0]

82.45/ [3.25]

RW27

82,5/ [3.25]

51,5

/ [2

.03]

45/ [1.77]

70,5

/ [2

.78]2A

RW27 + BF27

RW67

106/ [4.17]

100/ [3.94]50/ [1.97]

76/

[2.9

9]

50/

[1.9

7]

125A

RW27D

2A

79/

[3.1

1]

45/ [1 77]

60/

[2.3

6]

4,5/

[0.1

8]

6 8/ [0 27]

4,5/

[0.1

8]

35/ [1 38]

5/ [0 20]

RW27D

BF27D92 5/ [3 64]

2A RW27D2A

125A

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-77

RW S

ERIE

S

Controls Thermal Overload Relays - Dimensions mm (in)

RW67 + BF67

RW117-1D RW117-2D

6,8/ [0.27]

4,5/

[0.1

8]

60/

[2.3

6]

7,5/ [0.30]

35/ [1.38]

4,5/

[0.1

8]

5/ [0.20]

50/ [1.97]

71/

[2.8

0]

100/ [3.94]

106/ [4.17]

BF67D

RW67

RW67D

1 5A

80,5

/ [3

.17]

99,5

/ [3

.92]

75/ [2.95]

24/ [0.94] 24/ [0.94]

8,4/ [0.33]

98,5/ [3.88]

20/

[0.7

9]

40/ [1.57] 3/ [0.12]

00A

106 2/ [4 18]

98 3/ [3 87]

106/

[417

]

7,4/

[029

]

5,4/

[021

]

7 4/ [0 29]

5 4/ [0 21]

56

75/ [2 95]

BF117D

116,

4/ [

8]

2 0A

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-78

RW SERIES

Controls Thermal Overload Relays - Dimensions mm (in)

RW317

RW407

93

/ [3

.66]

130/

[5.1

2]15

5/ [6

.10]

48,5/ [1.91]

120/ [4.72]7/

[028

]166/ [6.54]

4/ [0.16]

A A

B

5 A

250/ [9.84]

162/ [6.38]

260/ [10.24]

150/

[5.9

1]

O5/ [O

0.20]

50/

[1.9

7]11

9/ [4

.69]

60/

[2.3

6]

13/ [0.51]

182,5/ [7.19]

50/ [1.97]

90/ [3.54]

9,5/ [0.37]32/ [1.26]81/ [3.19]

1 5 A

A

current ranges A b

100...150A39(1.5) 20(0.8)

140...215A

200...310A45(1.8) 25(1.0)

275...420A

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-79

RW S

ERIE

SCWC07...16 + RW17-1D

45/ [1.78]

38,2/ [1.50]

51,5

/ [2

.03]

85/ [3.33]

57/

[2.2

4]

114/

[4.4

9]

52/ [2.05]

CWC025 + RW17-2D

114,

3/ [4

.50]

85,1/ [3.35]45/ [1.77]

50,5

/ [1

.99]

1/ [0

.04]

2/ [0.08] 36/ [1.42]

50,6

/ [1

.99]

1/ [0

Controls Thermal Overload Relays - Dimensions mm (in)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-80

RW SERIES

CWM9...25 + RW27, CWM9N...CWM18N + RW27

CWM32 + RW27, CWM32N + RW27

A

2A

55/ [2.17]

138/

[5.4

3]

4,5/ [0.18]

79/

[3.1

1]

16,5

/ [0

.65]

12,5

/ [0

.49]

45/ [1.77]

98/ [3.86]A

cWM32 AAC coil 98(3.9)DC coil 118 (4.7)

Controls Thermal Overload Relays - Dimensions mm (in)

cWM9...25 AAC coil 94(3.7)DC coil 124(4.9)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-81

RW S

ERIE

S

Controls Thermal Overload Relays - Dimensions mm (in)

CWM32/32N/40 + RW67-1D

CWM50/50N...80 + RW67-2D

66/ [2.60]

1 5A

167.

5/ [6

.59]

90/

[3.5

4]

56/ [2.20]

60/ [2.36]

70/ [2.76]

6/ [0

.24]

4.5/ [0.18]

5.5/

[0.2

2]

7.5/ [0.30]

A

cWM50...80 A

AC coil 116(4.6)

DC coil 116(4.6)

25A

55/ [2.17]

143,

5/ [5

.65]

4,5/ [0.18]

79/

[3.1

1]

16,5

/ [0

.65]

12,5

/ [0

.49]

45/ [1.77]

A

cWM32/40 A

AC coil 106,5(4.2)

DC coil 116(4.6)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-82

RW SERIES

Controls Thermal Overload Relays - Dimensions mm (in)

CWM112/CWM150/CWM150N + RW117-2D

CWM95/95N/105 + RW117-1D

189/

[7.4

5]

2 A

75/ [2.95]

4/ [0 18]

6/ [0

.24]

60/ [2.36]

56/ [2.20]90/

[3.5

4]

8/ [0 30]

6/ [0

.22]

A

CWM95/105 AAC coil 127,5(5.0)DC coil 127,5(5.0)

GA117D

130/

[5.1

2]10

6/ [4

.17]

7,4/ [0.29]

5,4/ [0.21]

56/ [2.20]

147/ [5.79]

100/ [3.94]

9,5/

[0.3

7]

121,5/ [4.78]

4T2

3L2

2T1

1L1

7/ [0.28]

5L3

6T3

64/

[2.5

2]

AB

20 A

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-83

RW S

ERIE

S

Controls Thermal Overload Relays - Dimensions mm (in)

CWM180 + RW317

5 A

12/ [

0.47]

160/

[6.30

]11

0/ [4

.33]

40/ [1 57]7/ [0.28]

110/ [4 33]

150/

[5.91

]

7/ [0 28]

5L3

6T32T1 4T2

1L1 3L2

52,5/

[2.07

]GA317 2D

172/ [6 77]

358/

[14.0

9]

139/ [5 47]

CWM250/300/300N + RW317

5A

181/ [7 13]

148 4/ [5 84]

1L1

2T1 4T2 6T3

5L33L2

380/

[14.

96]

175/

[6.8

9]18

0/ [7

.09]

120/ [4 72]

10 5/ [0 41]

13/

[0.5

1]

110/

[4.3

3]

40/ [1 57]

GA317 3D

55/

[2.1

7]

7 [0.28]

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-84

RW SERIES

Controls Thermal Overload Relays - Dimensions mm (in)

CWM400 + RW317

30/ [1 19]

54/ [2 13] 54/ [2 13]

45/ [1 77]

90/ [3 54]

120/ [4 73]

163/ [6 42]

188/ [7 39]

72/

[2.8

4]

127/

[5.0

1]

155/

[6.1

1]

44/

[173

]

240/

[946

]

50/ [1 98]

168/ [6 62]

107/ [4 22]

127/ [5 02] 6

198/ [7 81]

145/ [5 71]

58/ [2 28]

58/ [2 28]

145/ [5 71]

110/

[4.3

4]

40/ [1 57]

222/

[874

]62

/ [2

.43]

394/

[15.

51]

7/ [0.28]

R5/ [R0 18] R5/ [R0 18]

9/ [0 35]

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-85

SRW

01 S

ERIE

S

Smart Relay SRW01Controls

VersatilityThe SRW01 supports the following communication network protocols: DeviceNet, Modbus-RTU, and ProfiBus-DP. The communication modules can be easily exchanged due to plug-and-play capabilities. An HMI also can be used for quick system monitoring and relay parameterization. Additionally, the SRW01 provides a USB port for relay monitoring and programming through PC when using WLP software. The SRW01 includes a thermal memory circuit in order to maintain a motor thermal image, even if power supply is removed.

FlexibilityThe SRW01 modular concept allows easy functionality expansions. The control unit can also be mechanically assembled with the control measurement unit or separately (up to 2 meters), allowing system integration versatility.

The relay offers pre-programmed operating modes that perform various types of standard starting or monitoring conditions. Its friendly parameterization mode allows users to program the relay according to their needs.

The SRW01 is a low-voltage electric motor management system with

state-of-the-art technology and network communication capabilities.

Additionally, its modular concept allows to be used in various applications.

Certifications

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-86

SRW01 SERIES

Controls Smart Relays - SRW01 Series

The SRW01 incorporates a main control unit (SRW01-UC) and a current measurement unit (SRW01-UMC) to provide flexible assembly options.

The SRW01-UC and SRW01-UMC are electrically connected using the SRW01-CB flat cable.

The interface with the relay may be performed in three ways:

g Via Fieldbus (ModBus, DeviceNet, Profibus)g Via Keypad (SRW01-IHM)g Via software – WLP (USB)

Through Fieldbus, the user can operate, monitor, and configure the SRW01 remotely, via PLC or supervisory system.

Modular Design

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-87

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 Series

The SRW01 relay has a (110...240Vac / Vdc) supply voltage range, making system integration flexible. The reduced size of SRW01-UC, with a width of 45mm and

height of 100mm, makes it a compact product

The SRW01-UC control unit provides LED indicators for input and output activations, status, operation mode, power supply status, failure and alarm status.The assembly of the control unit can be done either by 35mm DIN rail or onto back panel mounting.

Communication protocols: DeviceNet, Modbus, and Profibus are defined using proper protocol installed in the communication drawer.

The plug and play concept automatically recognizes and configures the SRW01 for safe operation avoiding manual error connections.

ProfiBus - DPnetwork connection

ModBus, DeviceNetor ProfiBus - DP connection

Mini USB port

Connection forHMI and accessories

Communication module

Reset button

Characteristics

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-88

SRW01 SERIES

Controls Smart Relays - SRW01 Series

Width (mm) Current (A) Power connection

45

0.25 - 2.5

Cable through UMC0.5 - 5

1.25 - 12.5

2.5 - 25

Width (mm) Current (A) Power connection

66 12.5 - 125 Cable through UMC

Width (mm) Current (A) Power connection

120 42 - 420 Busbar

Width (mm) Current (A) Power connection

265 84 - 840 Cable through UMC or busbar

SRW01-CB connection cableThe SRW01-CB connects the control units SRW01-UC to the current measuring unit SRW01-UMC allowing the two units to be separate assembled up to 2 meters.

Current Measuring Units

The current measuring unit SRW01-UMC shall be chose according to motor rated current ranging from 0.25A through 840A

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-89

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 SeriesFunctionsThe SRW01 protection, monitoring and operating functions enhance system protection reliability and precision. The operating modes are auto-adjustable, meaning the user selects the operating mode and the relay automatically search for proper parameters. This feature ensures quick and safe parameterization, allowing motor monitoring. Its friendly parameterization mode allows users to access all digital inputs and outputs, thus increasing flexibility to cover many applications.

Protectiong Overload protection (adjustable tripping class 5-45).g Thermal protection via PTC.g Phase loss protection.g Protection against current umbalance between phases.g Protection against overcurrent and locked rotor.g Protection against undercurrent.g Internal ground fault protection.g Protection against out of range frequency.

Operating Modes1

g Transparent operation - Digital input and output can be configured according to application needs .

g Operation as overload relay – similar to an overload relay.

g Direct starter - direct-on-line starter for single and three phase motors

g Reversing starter - reversing starter for three phase motors.

g Star-Delta starter - star-delta starter for three phase motors.

g Dahlander starter- starter for Dahlander three phase motors.

g Two windings starter - starter for two windings three phase motors.

g PLC mode – similar to the running of a PLC. In this mode the SRW01 – UMC current measuring

unit is not used.

Monitoringg Digital input and output activation.g RMS current of each phase and average in amperes or % of In adjusted current.g Motor frequencyg Number of activation per failute type.g Number of start ups.g Motor running hours.g Relay running hours.g Phase umbalance levels.g Internal ground fault current.

1 When applicable, additional power components are required.

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-90

SRW01 SERIES

Controls Smart Relays - SRW01 SeriesWLP SoftwareThe WLP is the SRW01 configuration software for Windows environment with user friendly interface that enables system parameterization, programmig, controlling and monitoring.

The WLP software enables the user to configure the relay, edit parameters and program in LADDER. Through the WLP configuration assistants the user has a guided routine that enables relay configuration. When necessary, the relay can be programmed in LADDER using mathematical and control blocks.

The LADDER program has a 64 Kbyte memory and can be used with relay digital inputs and outputs.

Communication between software and relay can be performed through USB port or ModBus network.

The WLP software is free of charge and supplied with the product. It can be also obtained from the website www.weg.net.

Configuration AssistantsThese routines have been especially created to assist relay configuration. They help the user to configure the relay in an easy self explanatory manner.g Configuration Assistant: Control Configuration.

Monitoring DialoguesThese dialogues have been especially created to monitor the relay. They monitor exclusive relay information.g Monitoring dialogues: Diagnostic.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-91

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 SeriesApplications

The main function of the SRW01 is to protect and control electric motors in their most diverse industrial applications. Due to its reduced size and modular design, the relay is frequently used when space for its assembly is a determining point, e.g. in Intelligent Motor Control Centers.

Its high reliability and precision make the SRW01 suitable for the toughest industrial applications.The on-line monitoring options, failure diagnosis and failure statistics allow preventive maintenance to be more effective, thus reducing the number of downtimes. It covers wide application for continuous process plants in the following market segments:

g Chemical and Petrochemicalg Pulp and Paperg Mining and Cementg Food and Beverageg Metal and Fabricationg Plastics and rubberg Automotiveg Ceramicsg Textileg Refrigerationg Other segments

Benefits

g Greater reliability for the protection system

g Operator safety in operation, supervision and maintenance.

g System modularity and easy expansion.

g Reduction in control wiring.g Reduction in motor control hardware.g Remote monitoring, supervision and

control via fieldbus network, computer (WLP) or Human-Machine Interface.

g Remot reset of the relayg Quick and precise defect identification.g Automation in defect records and

statistics.

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-92

SRW01 SERIES

Controls Smart Relays - SRW01 Series

Selection guide

Current range1 = 0.5...5 A2 = 1.25....12.5 A3 = 2.5...25 A4 = 12.5...125 A5 = 42...420 A6 = 84...840 A

SRW01-UMC 1

UMC - Current Measuring Unit

For current range of 0.25 to 2.5A pass the cable twice through the primary when using SRW01 – UMC1 .

UC - Control Unit

Supply voltageE47 = 110-240Vac / Vdc

Communication protocolB = without communicationD = DeviceNetM = ModBusP = ProfiBus

SRW01-U C T E47

Digital input operating voltage1 = 24Vdc2 = 110Vac

Terminal S1-S2 FunctionT = PTC

Supply Voltage

catalog Number List PriceMult.

Symbol

110-240Vac/Vdc

SRW01-ucbT1E47 $ 680.00

Z8

SRW01-ucbT2E47 $ 680.00 SRW01-ucdT1E47 $ 770.00 SRW01-ucdT2E47 $ 770.00 SRW01-ucMT1E47 $845.00 SRW01-ucMT2E47 $ 845.00 SRW01-ucPT1E47 $ 1010.00 SRW01-ucPT2E47 $ 1010.00

current Range

catalog Number List PriceMult.

Symbol0.5 ... 5A SRW01-uMc1 $ 290.00

Z8

1.25 ... 12.5A SRW01-uMc2 $ 290.00 2.5 ... 25A SRW01-uMc3 $ 290.00

12.5 ... 125A SRW01-uMc4 $ 480.00 42 ... 420A SRW01-uMc5 $ 600.00 84 ... 840A SRW01-uMc6 $ 800.00

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-93

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 Series

Communication protocolD = DeviceNetP = ProfiBus - DPM = ModBus

SRW01-MC D

Length

1 = 120 mm2 = 500 mm3 = 2000 mm

SRW01-CB 1

Communication Module

UC-UMC Connection Cable

Selection guide

connection cable

catalog Number List PriceMult.

Symbol120mm (4.7in) SRW01-cb1 $ 12.00

Z8500mm (20in) SRW01-cb2 $ 15.00 2000mm (79in) SRW01-cb3 $ 25.00

communication Protocol

catalog Number List PriceMult.

SymbolDeviceNet SRW01-Mcd $ 90.00

Z8ModBus SRW01-McM $ 165.00 ProfiBus SRW01-McP $ 330.00

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-94

SRW01 SERIES

Controls Smart Relays - SRW01 Series

Selection guide

HMI - Human - Machine Interface

Can be used for monitoring parameterization and operation of the relay SRW01-HMI

UC-HMI Cable Connection

USB Cable Connection

Shielded miniUSB cable for communication with PC. Available in length of 2000 mm.

SRW01-USB

SRW01-CH 1Length

1 = 500 mm2 = 1000 mm3 = 1500 mm

For use with

catalog Number List PriceMult.

Symbol

SRW01 SRW01-IhM $ 210.00 Z8

connection cable

catalog Number List PriceMult.

Symbol500mm (20in) SRW01-ch1 $ 22.00

Z81000mm (40in) SRW01-ch2 $ 30.00 15000mm (59in) SRW01-ch3 $ 35.00

connection cable

catalog Number List PriceMult.

Symbol2000mm (79in) SRW01-uSb5 $ 35.00 Z8

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-95

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 Series

Available for UMC6 only

SRW01-BARBus bar for UMC

Adaptor for screw mounting.

Note: Quantity per package: 2 pieces.

PLMP

Fixing adaptor

For use with

catalog Number List PriceMult.

SymbolSRW01 PLMP $ 0.50 Z8

For use with

catalog Number List PriceMult.

Symbol

UMC6 only SRW01-bAR $ 260.00 Z8

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-96

SRW01 SERIES

Controls Smart Relays - SRW01 SeriesTechnical Characteristics

Assembly position Any Degree of protection (IEC 60529)UC - Control Unit IP20Current measurement: - without connection bus bar IP20- with connection busbar IP00Human Machine Interface (HMI) IP20Acceptable ambient temperature:- Operation 0...+60ºC (+32...+1400F)- Strorage and transport -25...+80ºC (-10...+1760F)UC - Control UnitInsulation Rated Voltage Ui 300VSupply Rated Voltage Us 110...240Vac/Vdc a 50/60HzOperating range 0.90Us ...1.10Us Consumption 13W Number of digital inputs 4 optically insulated inputsNumber of digital outputs 4 relay outputsMotor protection via – PTC:

- TRIP value > 3.9kΩ- Rearm value < 1.6kΩ

Terminals (connectors)- Torque 0.8...1.2Nm (7.1...+11lb-in)Conductor diameter: Rigid and no end sleeve 1 x (0.5...4 mm2); 2 x (0.5...2.5 mm2) Flexible with/without terminals 1 x (0.5...2.5 mm2); 2 x (0.5...1.5 mm2)

RESET buttonError or failure reset– System

TRIP or alarm reset - Protections Current Measuring Unit (UMC)Current ranges 0.25...840AacDegree of insulation Ui 690VacOperating rated voltage Ue - IEC 60947-4-1 690Vac - UL 508 600VacImpulse voltage Uimp 6kVMotor rated frequency Up to 99HzApplication Single phase and three phaseDiameter for cables:SRW01-UMC1, SRW01-UMC2, SRW01-UMC3 8mmSRW01-UMC4 15mmSRW01-UMC5 BusbarSRW01-UMC6 31mm or busbarDigital inputsNumber of digital inputs 4 optically insulated inputsSource for digital inputs 24Vdc internal source (insulated)Digital inputs current 11mA to 24VdcInsulation 3kVDigital outputsNumber of digital outputs 4 relay outputs

Contact grouping 2 SPST2 SPST commom shared

Contact voltage range 12...250Vac/VdcLowest operating power 1W or 1 VAOperating capacity per relay contact:

AC-15 (IEC 60947-5-1)6 A / 24 Vac

6 A / 120 Vca3 Aac / 230 Vca

DC-13 (IEC60947-5-1)2 A / 24 Vdc

0.55 A / 60 Vdc0.25 A / 125 Vdc

External protection against short circuit 6 A gL/gG fuseMechanical life 1.000.000 operationsElectrical life (AC-15): 100.000 operations (0.5 A/250 Vac)

50.000 operations (1.5 A/250 Vac)Electrical life (DC-13): 100.000 operations (0.5 A/250 Vdc)

50.000 operations (1.5 A/250 Vdc)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-97

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 Series

Dimensions (mm)SRW01-UC - Control Unit

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-98

SRW01 SERIES

Controls Smart Relays - SRW01 Series

UMC 1- UMC 2- UMC 3

SRW01-UMC - Current Measuring Unit

Dimensions (mm)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-99

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 SeriesDimensions (mm)

SRW01-UMC - current Measuring Unit

UMC 5

UMC 6

(without busbar)

UMC 6

(with busbar)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-100

SRW01 SERIES

Controls Smart Relays - SRW01 Series

HMI - Human Machine Interface

Dimensions (mm)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-101

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 Series

Operating Modes Diagrams

Contactor WEG

Fuses

Fuses G

Direct Starter

Transparent operation

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-102

SRW01 SERIES

Controls Smart Relays - SRW01 Series

Fuses

Contactor WEG

Contactor WEG

Fuses

Contactor WEG

Operating Modes Diagrams

Operation as overload relay

Reversing starter

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-103

SRW

01 S

ERIE

S

Controls Smart Relays - SRW01 Series

Operating Modes Diagrams

Fuses

Contactor WEG Contactor WEG Contactor WEG

Fuses

Contactor WEG Contactor WEGContactor WEG

Star-Delta starter

Dahlander starter

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-104

SRW01 SERIES

Controls Smart Relays - SRW01 Series

Fuses WEG

Contactor WEG Contactor WEG

Operating Modes Diagrams

Two windings starter

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-105

AcW

SER

IES

Introducing the WEG ACW Series of Molded Case Circuit Breakers now availa-ble with UL489 certification. Available in four different compact frames, the New ACW Series will assure top performance for both thermal and short-circuit pro-tection from 15 to 800Amps.

The ACW series is also available in two levels of short-circuit interrupting capacity – “P” for standard industrial and commercial standard applications and “W” for high-performance applications.

Common plug-in accessories simplify field installation and minimize inventory va-riations on distributors’ shelves.

ACW

Molded-Case Circuit BreakerUL 489 Listed

ACW125

In 15…125

ACW250

In 128…250

ACW400

In 240…400

ACW800

In 400…800

UL interrupting rating (kA)

Current ratings

Mccb AcW125 AcW250 AcW400 AcW800

Type P W P W P W P W

@ 120V 50 100 - - - - - -

@ 240V 50 100 50 100 50 100 50 100

@ 480V 35 65 35 65 35 65 35 65

@ 600V 10 14 10 18 14 20 18 25

Reference Rated current In (A)

AcW125 15, 20, 30, 40, 50, 60, 80, 100, 125

AcW250 128-160, 160-200, 200-250

AcW400 240-300, 320-400

AcW800 400-500, 480-600, 640-800

Certifications:

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-106

AcW SERIES

Trip type

Ratings (A) @ 40oC

Number of poles

Short-circuit current setpoint, Im

Overload current setpoint, Ir

Trip unitsFTU - Fixed thermal and fixed magnetic

FMU - Adjustable thermal and fixed magnetic

ATU - Adjustable thermal and adjustable magnetic

Trip type

Ratings (A) @ 40oC

Number of poles

Short-circuit trip current, Im

Applicable to AcW125, 250, 400, and 800 frames

FTUFixed thermal15…800A rated currentFixed magnetic400…8000A trip current

Im

t

0 Ir

Applicable to AcW125, 250, 400, and 800 frames

FMUAdjustable thermal40…800A rated currentAdjustable: 0.8, 0.9, 1xInFixed magnetic400…8000A trip current

Applicable to AcW125, 250, 400, and 800 frames

ATUAdjustable thermal160…800A rated currentAdjustable: 0.8, 0.9, 1xInAdjustable magnetic800…8000A trip currentAdjustable: 5, 6, 7, 8, 9, 10xIn

Note: WEG is committed to maintain stock for immediate delivery of the following trip units: FTU – ACW125P and ACW125W FMU – ACW250P, ACW250W, ACW400P, ACW400W, ACW800P, ACW800W Please contact your WEG representative office for availability of other trip units.

Trip type

Ratings (A) @ 40oC

Number of poles

Short-circuit tripcurrent, Im

Overload current setpoint, Ir

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-107

AcW

SER

IES

Selection guide

Rated current In code

15A 15

20A 20

30A 30

40A 40

50A 50

60A 60

80A 80

100A 100

125A 125

160A 160

200A 200

250A 250

300A 300

400A 400

500A 500

600A 600

700A 700

800A 800

A C W 1 2 5 P - F T U 8 0 - 3

Number of poles

code

3 3

Trip unit code

Fixed thermal and fixed magnetic FTU

Adjustable thermal and fixed magnetic FMU

Adjustable thermal and adjustable magnetic

ATU

Frame code

125 ACW125

250 ACW250

400 ACW400

800 ACW800

kA rating @ 460VAc

code

35 P

65 W

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-108

AcW SERIES

MCCB for power distribution - standard interrupting capacity

ACW125P - FTU trip unit – Fixed thermal and fixed magnetic

ACW250P - FMU trip unit – Adjustable thermal and fixed magnetic

ACW400P - FMU trip unit – Adjustable thermal and fixed magnetic

ACW800P - FMU trip unit – Adjustable thermal and fixed magnetic

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price

Multiplier Symbol[A] [A] 480VAc 600VAc

15 400

35kA 10kA

AcW125P-FTu15-3 $665.00 Z1020 400 AcW125P-FTu20-3 $665.00 Z1030 400 AcW125P-FTu30-3 $665.00 Z1040 400 AcW125P-FTu40-3 $665.00 Z1050 500 AcW125P-FTu50-3 $665.00 Z1060 600 AcW125P-FTu60-3 $665.00 Z1080 800 AcW125P-FTu80-3 $728.00 Z10

100 1000 AcW125P-FTu100-3 $728.00 Z10125 1250 AcW125P-FTu125-3 $1,499.00 Z10

Note: Wiring terminal (lugs) not included. Lugs are available as accessory at page B-115.

Note: Wiring terminal (lugs) not included. Lugs are available as accessory at page B-115.

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier

Symbol[A] [A] 480VAc 600VAc128...160 1600

35kA 10kAAcW250P-FMu160-3 $1,550.00 Z10

160...200 2000 AcW250P-FMu200-3 $1,550.00 Z10200...250 2500 AcW250P-FMu250-3 $1,550.00 Z10

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier

Symbol[A] [A] 480VAc 600VAc400...500 5000

35kA 18kAAcW800P-FMu500-3 $4,757.00 Z10

480...600 6000 AcW800P-FMu600-3 $4,757.00 Z10640...800 8000 AcW800P-FMu800-3 $5,393.00 Z10

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier

Symbol[A] [A] 480VAc 600VAc240...300 3000

35kA 14kAAcW400P-FMu300-3 $2,505.00 Z10

320...400 4000 AcW400P-FMu400-3 $2,505.00 Z10

Note: WEG is committed to maintain stock for immediate delivery of the following trip units: FTU – ACW125P and ACW125W FMU – ACW250P, ACW250W, ACW400P, ACW400W, ACW800P, ACW800WPlease contact your WEG representative offce for availability of other trip units.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-109

AcW

SER

IES

Note: Wiring terminal (lugs) not included. Lugs are available as accessory at page B-115.

Note: Wiring terminal (lugs) not included. Lugs are available as accessory at page B-115.

MCCB for power distribution - high interrupting capacity

ACW125W - FTU trip unit – Fixed thermal and fixed magnetic

ACW250W - FMU trip unit – Adjustable thermal and fixed magnetic

ACW400W - FMU trip unit – Adjustable thermal and fixed magnetic

ACW800W - FMU trip unit – Adjustable thermal and fixed magnetic

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier Symbol

[A] [A] 480VAc 600VAc15 400

65kA 14kA

AcW125W-FTu15-3 $965.00 Z1020 400 AcW125W-FTu20-3 $965.00 Z1030 400 AcW125W-FTu30-3 $965.00 Z1040 400 AcW125W-FTu40-3 $965.00 Z1050 500 AcW125W-FTu50-3 $965.00 Z1060 600 AcW125W-FTu60-3 $965.00 Z1080 800 AcW125W-FTu80-3 $1,055.00 Z10100 1000 AcW125W-FTu100-3 $1,055.00 Z10125 1250 AcW125W-FTu125-3 $2,101.00 Z10

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier Symbol

[A] [A] 480VAc 600VAc128...160 1600

65kA 18kAAcW250W-FMu160-3 $2,826.00 Z10

160...200 2000 AcW250W-FMu200-3 $2,826.00 Z10200...250 2500 AcW250W-FMu250-3 $2,826.00 Z10

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier Symbol

[A] [A] 480VAc 600VAc400...500 5000

65kA 25kAAcW800W-FMu500-3 $6,392.00 Z10

480...600 6000 AcW800W-FMu600-3 $6,392.00 Z10640...800 8000 AcW800W-FMu800-3 $7,358.00 Z10

Thermal Setting Magnetic Setting Short-circuit interrupting capacitycatalog Number List Price Multiplier Symbol

[A] [A] 480VAc 600VAc240...300 3000

65kA 20kAAcW400W-FMu300-3 $4,312.00 Z10

320...400 4000 AcW400W-FMu400-3 $4,312.00 Z10

Note: WEG is committed to maintain stock for immediate delivery of the following trip units: FTU – ACW125P and ACW125W FMU – ACW250P, ACW250W, ACW400P, ACW400W, ACW800P, ACW800WPlease contact your WEG representative offce for availability of other trip units.

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-110

AcW SERIES

Internal accessories

Auxiliary contact

AcW oN oFF TRIP

Auxiliary contact AXc1

AXa1AXc1

AXa1

AXb1 AXb1

Suitable for catalog Number List Price Multiplier Symbol

ACW125...800 AX AcW 125-800 $103.00 Z10

Suitable for catalog Number List Price Multiplier Symbol

ACW125…800 AL AcW 125-800 $103.00 Z10

ACW ON OFF TRIP

Alarm contact ALc1Ala1

ALc1Ala1

ALb1 ALb1

The auxiliary contact block contains one set of form ‘C’ contacts. This contact indicates remote circuit-breaker status “ON” and “OFF”.

Alarm contactAlarm contact offers provisions for audio and visual indication of a tripped breaker due to overload, short-circuit, shunt trip or under voltage release conditions. The contact opens when the circuit breaker is reset.

Suitable for Rated voltage catalog Number List Price Multiplier Symbol

ACW125…800

12VDC ShT c02 AcW 125-800 $235.00 Z10

24VAC/DC ShT E26 AcW 125-800 $235.00 Z10

48VAC/DC ShT E27 AcW 125-800 $235.00 Z10

110-130VAC/DC ShT E10 AcW 125-800 $235.00 Z10

220-240VAC/250VDC ShT E14 AcW125-800 $235.00 Z10

380-500VAC ShT E52 AcW125-800 $235.00 Z10

Shunt releaseThe shunt release opens the breaker in response to an externally voltage signal.

Range of operational voltage: 0.7…1.1xUnFrequency: 45…65Hz

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-111

AcW

SER

IES

Under voltage release

Suitable for Rated voltage catalog Number List Price Multiplier Symbol

ACW125…800

24VAC/DC uVT E26 AcW 125-800 $235.00 Z10

48VAC/DC uVT E27 AcW 125-800 $235.00 Z10

110-130VAC/DC uVT E10 AcW 125-800 $235.00 Z10

220-240VAC/250VDC uVT E14 AcW 125-800 $235.00 Z10

380-440VAC uVT E53 AcW 125-800 $235.00 Z10

440-480VAC uVT E54 AcW 125-800 $235.00 Z10

The under voltage release automatically opens a circuit breaker when voltage drops to a value ranging between 35% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be reset until the voltage returns to 85% of line voltage.

Range of voltage trip: 0.35…0.7xUnMCCB reset voltage: 0.85xUn (exceed)Frequency: 45…65Hz

Configuration of internal accessories

Internal accessories

Phase (side) Accessory AcW125 AcW250 AcW400 AcW800

R (left)AX 0 1 3 3AL 1 1 0 0

SHT or UVT 1 1 1 1

T (right)AX 2 1 0 0AL 0 0 1 2

Possible configuration of internal accessories

ACW125 ACW250 ACW400 ACW800

AX AX

SHT/UVT

AL

AX AX

SHT/UVT

ALAX AX AX

SHT/UVT

AL

SHT/UVT

AL ALAX AX AX

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-112

AcW SERIES

Rotary handle

External accessories

The through-the-door rotary handle operating mechanism is available in NEMA 3(R), 12 and 4X versions. Units are offered either complete (rotary handle + operating mechanism + shaft 12”) or as seperate components (different shaft sizes sold separately). Lockable in OFF position.

Suitable for catalog Number List Price Multiplier SymbolRotary handle + mechanism + shaft 12“ (uL Type 1, 3(R), 12)

ACW125 Ehu 12 AcW 125 $254.00 Z10ACW250 Ehu 12 AcW 250 $275.00 Z10ACW400 Ehu 12 AcW 400 $336.00 Z10ACW800 Ehu 12 AcW 800 $449.00 Z10

Rotary handle + mechanism + shaft 12“ (uL Type 4X)ACW125 EhX 12 AcW 125 $331.00 Z10ACW250 EhX 12 AcW 250 $352.00 Z10ACW400 EhX 12 AcW 400 $422.00 Z10ACW800 EhX 12 AcW 800 $586.00 Z10

Suitable for catalog Number List Price Multiplier SymbolRotary handle + mechanism (without shaft) (uL Type 1, 3(R), 12)

ACW125 Ehu AcW 125 $221.00 Z10ACW250 Ehu AcW 250 $239.00 Z10ACW400 Ehu AcW 400 $305.00 Z10ACW800 Ehu AcW 800 $427.00 Z10

Rotary handle + mechanism (without shaft) (uL Type 4X) ACW125 EhX AcW 125 $305.00 Z10ACW250 EhX AcW 250 $322.00 Z10ACW400 EhX AcW 400 $398.00 Z10ACW800 EhX AcW 800 $575.00 Z10

16” shaft for rotary handleACW125…800 ES 16 AcW 125-800 $53.00 Z10

24” shaft for rotary handleACW125…800 ES 24 AcW 125-800 $71.00 Z10

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-113

AcW

SER

IES

Flange handle

External accessories

The flange disconnect handle is available in NEMA 3(R), 12 and 4X versions. Flexible cables are available in four different sizes (36”, 48”, 60”, 72”) and are ordered separately. Lockable in OFF position.

Suitable for catalog Number List Price Multiplier SymbolFlange handle + mechanism (without flexible cable) (uL Type 1, 3(R), 12)

ACW125 Fhu AcW 125 $365.00 Z10ACW250 Fhu AcW 250 $410.00 Z10ACW400 Fhu AcW 400 $480.00 Z10ACW800 Fhu AcW 800 $551.00 Z10

Flange handle + mechanism (without flexible cable) (uL Type 4X)ACW125 FhX AcW 125 $458.00 Z10ACW250 FhX AcW 250 $526.00 Z10ACW400 FhX AcW 400 $594.00 Z10ACW800 FhX AcW 800 $656.00 Z10

Suitable for catalog Number List Price Multiplier SymbolFlexible cable

cable 36”ACW125…250 Fc 36 AcW 125-250 $146.00 Z10ACW400…800 Fc 36 AcW 400-800 $155.00 Z10

cable 48”ACW125…250 Fc 48 AcW 125-250 $169.00 Z10ACW400…800 Fc 48 AcW 400-800 $179.00 Z10

cable 60”ACW125…250 Fc 60 AcW 125-250 $188.00 Z10ACW400…800 Fc 60 AcW 400-800 $198.00 Z10

cable 72”ACW125…250 Fc 72 AcW 125-250 $208.00 Z10ACW400…800 Fc 72 AcW 400-800 $227.00 Z10

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-114

AcW SERIES

Pad lock

Handle lock

External accessories

T ad lock allows the handle to be locked in the “OFF” on. Maximum three padlocks with shackle diameters ng from 0.2 to 0.3in (5 to 8mm) may be used. (Padlocks

ot supplied)ng in the “OFF” position guarantee isolation required per UL 489.

The handle lock allows the handle to be locked in the “ON” and “OFF” positions. Maximum three padlocks with shackle diameters ranging from 0.2 to 0.3inch (5 to 8mm) may be used.(Padlocks are not supplied)Locking in the “OFF” position guarantee isolation required per UL 489.

Suitable for catalog Number List Price Multiplier Symbol

ACW125 PL AcW 125 $59.00 Z10

ACW250 PL AcW 250 $65.00 Z10

ACW400 PL AcW 400 $78.00 Z10

ACW800 PL AcW 800 $90.00 Z10

Suitable for catalog Number List Price Multiplier Symbol

ACW125 hL AcW 125 $95.00 Z10

ACW250 hL AcW 250 $101.00 Z10

ACW400 hL AcW 400 $158.00 Z10

ACW800 hL AcW 800 $165.00 Z10

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-115

AcW

SER

IES

Wiring terminal (Lugs)

Mechanical interlock

External accessories

The mechanical interlock can be applied on the front of two breakers mounted side by side and prevents simultaneous closing of the two breakers. Interlock is assembled directly to the front cover of the breakers. The interlocking plate allows installation of a padlock to maintain the position. The operator can lock out either one or both breakers in the “OFF” position. (Padlocks are not supplied)

Suitable for catalog Number List Price Multiplier Symbol

ACW125 MIT AcW 125 $338.00 Z10

ACW250 MIT AcW 250 $377.00 Z10

ACW400 MIT AcW 400 $413.00 Z10

ACW800 MIT AcW 800 $440.00 Z10

Suitable for catalog Number List Price Multiplier Symbol Set with 3 pieces

ACW125 LW1 3P AcW 125 $48.00 Z10ACW250 LW2 3P AcW 250 $81.00 Z10

Set with 15 piecesACW125 LW1 15P AcW 125 $168.00 Z10ACW250 LW2 15P AcW 250 $283.00 Z10

Line and Load terminals provide the means for connecting the circuit breaker to the power source and the load. Each breaker accepts up to 6 lugs (a set of 3 units for the line terminals and another set of 3 units for the load terminals); Each lug is suitable for either line or load terminals.

Locked in OFF position

Locked in OFF position

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-116

AcW SERIES

Technical Data

Models AcW125 AcW250Frame size 125 250Rated current – In @ 40ºC A 15, 20, 30, 40, 50, 60, 80, 100, 125 150, 160, 175, 200, 225, 250No. of poles 3 3Rated operational voltage - Ue VAC 600 600uL interrupting rating - Icu kA P W P W120VAC 50 100 - -240VAC 50 100 50 100480VAC 35 65 35 65600VAC 10 14 10 18Reference standard UL 489 UL 489Trip unit (Thermal-magnetic)Fixed thermal, fixed magnetic FTU Yes YesAdjustable thermal, fixed magnetic FMU Yes YesAdjustable thermal, adjustable magnetic ATU No YesAccessoriesAuxiliary contact (AX) Yes YesAlarm contact (AL) Yes YesShunt release (SHT) Yes YesUnder voltage (UVT) Yes YesRotary handle Yes YesFlange handle Yes YesLocking devices (pad and handle lock) Yes YesMechanical interlock block Yes YesWiring terminals Yes YesMechanical life operations 4,000 4,000Electrical life @ 600VAC operations 4,000 4,000Weight Lbs/kg 2.65/1.2 2.65/1.2Dimensions (width x height x depth) in/mm 3.54x6.46x3.39/90x164x86 4.13x7.01x3.39/105x178x86

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-117

AcW

SER

IES

Auxiliary contact (AX) & Alarm contact (AL)

Conventional thermal current (Ith) 5A

Rated operational current (Ie) 50/60Hz

[V] Resistive Load Inductive Load120Vac 5 3240Vac 3 2480Vac 2 1.5

Terminal tigheting torque [lb.in (N/m)] 7 (0.8)

Shunt Release

Power consumption

[V] Consumption[VA] [mA]

24Vac 0.58 2448Vac 1.22 25

110-130Vac 1.36 10.5220-240Vac 1.8 7.5380-500Vac 1.15 2.3

Maximum opening time [msec] 50Terminal tigheting torque [lb.in (N/m)] 7 (0.8)

undervoltage Release

Drop-out voltage [% of Vn] 0.35 - 0.7 x VnReset voltage [% of Vn] 0.85 x Vn

Power consumption

[V] Consumption[VA] [mA]

24Vac 0.64 2748Vac 1.09 23

110-130Vac 0.73 5.8220-240Vac 1.21 5.4380-500Vac 1.68 3.5

Maximum opening time [msec] 50

Terminal tigheting torque [lb.in (N/m)] 7 (0.8)

Models ACW400 ACW800Frame size 400 800Rated current – In @ 40ºC A 300, 350, 400 500, 600, 700, 800No. of poles 3 3Rated operational voltage - Ue VAC 600 600uL interrupting rating - Icu P W P W120VAC - - - -240VAC 50 100 50 100480VAC 35 65 35 65600VAC 14 20 18 25Reference standard UL 489 UL 489Trip unit (Thermal-magnetic)Fixed thermal, fixed magnetic FTU Yes YesAdjustable thermal, fixed magnetic FMU Yes YesAdjustable thermal, adjustable magnetic ATU Yes YesAccessoriesAuxiliary contact (AX) Yes YesAlarm contact (AL) Yes YesShunt release (SHT) Yes YesUnder voltage (UVT) Yes YesRotary handle Yes YesFlange handle Yes YesLocking devices (pad and handle lock) Yes YesMechanical interlock block Yes YesWiring terminals Standard StandardMechanical life operations 5,000 3,000Electrical life @ 600VAC operations 1,000 500Weight Lbs/kg 12.57/5.7 29.98/13.6Dimensions (width x height x depth) in/mm 5.51x11.50x4.33/140x292x110 8.27x16.85x5.31/210x428x135

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-118

AcW SERIES

Screw and connection

Screw mounting

Connecting terminal and conductor

AcW125 AcW250 AcW400 AcW800

Screw for mounting

4EA(NO.8-32 UNC-2A, L100)

4EA(NO.10-24 UNC-2A, L120)

4EA(1/4”-20 UNC2A, L140)

Screw for connection of

terminals6EA(M5×L16) 6EA(M8×L20)

N.A. N.A.

Torque: Max 78kgf·cm

67.7lbf·in

Torque: Max 197kgf·cm

170lbf·inN.A. N.A.

Terminal (mm) Conductor (mm)

AcW125

Max 78kgf·cm

AcW250

Max 147kgf·cm

18

8

23

22

M5x16

20

28

22

M8x20

>8>8

1025

21

2510

Note: ACW400 and ACW800 are supplied with lugs.

Note: ACW400 and ACW800 are supplied with lugs.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-119

AcW

SER

IES

Mccb Rating(A)

Fixed Mccb (thermal-magnetic trip unit)

50°F 68°F 86°F 104°F 122°F 140°F 158°F 176°F10°c 20°c 30°c 40°c 50°c 60°c 70°c 80°c

AcW125

15 15 15 15 15 15 14 13 1220 20 20 20 20 19 19 18 16

30 30 30 30 30 29 28 26 24

40 40 40 40 40 39 38 35 3350 50 50 50 50 48 47 44 4160 60 60 60 60 58 56 53 4980 80 80 80 80 78 75 71 66100 100 100 100 100 97 94 88 82125 125 125 125 125 121 117 110 103

AcW250

150 150 150 150 150 145 140 131 121160 160 160 160 160 155 150 141 131175 175 175 175 175 170 165 156 145200 200 200 200 200 194 188 176 164225 225 225 225 225 219 213 201 189250 250 250 250 250 242 234 220 205

AcW400300 300 300 300 300 291 281 264 246350 350 350 350 350 341 331 314 296400 400 400 400 400 388 375 353 328

AcW800

500 500 500 500 500 484 469 441 410600 600 600 600 600 580 571 525 487700 700 700 700 700 680 661 625 587800 800 800 800 800 775 750 705 656

A derating of the rated operational current for ACW series is necessary if the ambient temperature is greater than 40oC (+104oF), because the overload-protection characteristics are slightly modified.

Frame TypeWire Range

"conductor "Number of Tightening Torquecross-section" conductors" [lb.in.]

AcW12514 - 8 AWG 1 606 - 1/0 AWG 1 90

AcW250

1 AWG 1 1501/0 - 2/0 AWG 1 1803/0 - 4/0 AWG 1 250

250 - 300 kcmil 1 Tightening Torque 325

AcW400250 - 400 kcmil 1 325

500 kcmil 1 3753/0 AWG up to 2 250

AcW800 (500 and 600A) 250 - 500 kcmil up to 2 375

AcW800 (800A)250 - 400 kcmil up to 3 375

500 kcmil up to 2 375

Terminal size acceptability and terminal torque

Temperature derating

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-120

AcW SERIES

Cascading protection

Power supply 240V

branch breakerMain breaker AcW125P AcW125W AcW250P AcW250W

Rated breaking capacity (kArms) 50 100 50 100

AcW125P 50 - 75 - 75AcW125W 100 - - - -AcW250P 50 - - - 75AcW250W 100 - - - -AcW400P 50 - - - -AcW400W 100 - - - -AcW800P 50 - - - -AcW800W 100 - - - -

branch breakerMain breaker AcW400P AcW400W AcW800P AcW800W

Rated breaking capacity (kArms) 50 100 50 100

AcW125P 50 - 75 - 75AcW125W 100 - - - -AcW250P 50 - 75 - 75AcW250W 100 - - - -AcW400P 50 - 75 - 75AcW400W 100 - - - -AcW800P 50 - - - 75AcW800W 100 - - - -

Power supply 480V

branch breakerMain breaker AcW125P AcW125W AcW250P AcW250W

Rated breaking capacity (kArms) 35 65 35 65

AcW125P 35 - 50 - 50AcW125W 65 - - - -AcW250P 35 - - - 50AcW250W 65 - - - -AcW400P 35 - - - -AcW400W 65 - - - -AcW800P 35 - - - -AcW800W 65 - - - -

branch breakerMain breaker AcW400P AcW400W AcW800P AcW800W

Rated breaking capacity (kArms) 35 65 35 65

AcW125P 35 - 50 - 50AcW125W 65 - - - -AcW250P 35 - 50 - 50AcW250W 65 - - - -AcW400P 35 - 50 - 50AcW400W 65 - - - -AcW800P 35 - - - 50AcW800W 65 - - - -

This is an economical approach to the use of circuit protective devices, whereby only the main (upstream) breaker has adequate interrupting capacity for the maximum available fault current. Downstream circuit breakers cannot handle this maximum fault current and rely on the opening of the upstream breaker for protection.

The advantage of this approach is that it facilitates the use of downstream low cost, low fault level breakers, thereby offering savings in both the cost and size of equipment. These ratings, however, are applicable only when the series-connected devices have been investigated by UL in combination with the end-use equipment and the equipmentin which these devices are used is marked with the series-connected rating.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-121

AcW

SER

IES

Power supply 600V

branch breakerMain breaker AcW125P AcW125W AcW250P AcW250W

Rated breaking capacity (kArms) 10 14 10 18

AcW125P 10 - 12 - 14AcW125W 14 - - - 16AcW250P 10 - - - 14AcW250W 18 - - - -AcW400P 14 - - - -AcW400W 20 - - - -AcW800P 18 - - - -AcW800W 25 - - - -

Branch breakerMain breaker ACW400P ACW400W ACW800P ACW800W

Rated breaking capacity (kArms) 14 20 18 25

AcW125P 10 12 15 14 17AcW125W 14 - 17 16 19AcW250P 10 12 15 14 17AcW250W 18 - 19 - 21AcW400P 14 - 17 16 19AcW400W 20 - - - 22AcW800P 18 - - - 21AcW800W 25 - - - -

Cascading protection

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-122

AcW SERIES

Selectivity (Coordination tables)

branch breaker

Main breaker AcW125P/W AcW250P/W

Rating (A)Trip units – Thermal magnetic Trip units – Thermal magnetic

15 20 30 40 50 60 80 100 125 150 160 175 200 225

ACW

P

Trip units – thermal magnetic

15 0.5kA 0.5kA 0.5kA 0.63kA 0.8kA 2kA 2kA 2kA T T T20 0.5kA 0.5kA 0.63kA 0.8kA 2kA 2kA 2kA T T T30 0.5kA 0.63kA 0.8kA 2kA 2kA 2kA T T T40 0.63kA 0.8kA 2kA 2kA 2kA T T T50 0.63kA 0.8kA 2kA 2kA 2kA T T T60 0.8kA 2kA 2kA 2kA T T T80 1.25kA 2kA 2kA T T T100 1.6kA 1.6kA T T T125 1.25kA 1.25kA 4kA 4kA

W

15 0.5kA 0.5kA 0.5kA 0.63kA 0.8kA 2kA T T T T T20 0.5kA 0.5kA 0.63kA 0.8kA 2kA T T T T T30 0.5kA 0.63kA 0.8kA 2kA 50kA 50kA 50kA 50kA 50kA40 0.63kA 0.8kA 2kA 50kA 50kA 50kA 50kA 50kA50 0.63kA 0.8kA 2kA 50kA 50kA 50kA 50kA 50kA60 0.8kA 2kA 50kA 50kA 50kA 50kA 50kA80 50kA 50kA 50kA 50kA 50kA

100 50kA 50kA 50kA 50kA 50kA125 1.25kA 1.25kA 1.25kA 4kA 4kA

ACW

P

Trip units – thermal magnetic

150160175200225250

W

150 1.25kA160175200225250

Note: T means Total Selectivity.

Definition of selectivity is given by the IEC 60947-1. "Trip selectivity is the coordination between the operating char-acteristics of two or more overcurrent protection devices, so that when an overcurrent within established limits oc-curs, the device intended to operate within those limits trips whereas the others do not trip".The definitions of total selectivity and partial selectivity are, on the other hand, given in Part 2 of the same Standard IEC 60947-2 "Low voltage Equipment - Part 2: Circuit-breakers"

"Total selectivity"Overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load-side protection device carries out the protection without making the other device trip."

"Partial selectivity"Overcurrent selectivity where, in the presence of two protection devices against overcurrent in series, the load-side protection device carries out the protection up to a given level of overcurrent, without making the other device trip."

Selection of proper protection system is fundamental to guarantee correct economical and functional service of the whole installation and to reduce the problems caused by abnormal service conditions or actual faults to a minimum.

ExampleThe following two circuit-breakers are considered: - Main breaker ACW250W-175-3 (Icu = 65kA)- Branch breaker ACW125W-20-3 (Icu = 65kA)Extracting the data from the table above, it can be seen that there is total selectivity (T) between these circuit-breakers. In other words, there is selectivity up to 65kA (the lower of the two values).

Now the following two circuit-breakers are considered:- Main breaker ACW250W-175-3 (Icu = 65kA)- Branch breaker ACW125W-30-3 (Icu = 65kA)Extracting the data from the table above, it can be seen that the selectivity value is 50kA between the two circuit-breakers. This means that, if the maximum prospective short-circuit current on the load-side of the ACW125W-30-3 circuit-breaker is less than 50kA, there will be total selectivity, whereas if the short-circuit current has a higher value, there will be partial selectivity (non-tripping of the supply-side cir-cuit-breaker is not guaranteed).

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-123

AcW

SER

IES

Trip curves

ACW125 – FTU & FMU (15…125A)

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-124

AcW SERIES

ACW250 – FTU & FMU (128…250A)

Trip curves

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-125

AcW

SER

IES

ACW250 – ATU (128…250A)

Trip curves

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-126

AcW SERIES

ACW400 – FTU & FMU (240…400A)

Trip curves

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-127

AcW

SER

IES

ACW400 – ATU (240…400A)

Trip curves

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-128

AcW SERIES

ACW800 – FTU & FMU 400…800A)

Trip curves

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-129

AcW

SER

IES

ACW800 – ATU (400…800A)

Trip curves

Min

ute

Ope

ratin

g tim

e

Sec

ond

X Rated Current In (I/Ir)

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-130

AcW SERIES

Current-limiting curves @ 240V

Characteristics curves - Current limiting

The following curves show circuit breaker current-limiting characteristics. The rms of the prospective symmetrical short-circuit current is indicated on the abscissa of the diagram, whereas the peak short-circuit current value is indicated on the ordinates. The current-limiting effect can be visualized by comparing, at the same symmetrical short-circuit current value, the corresponding peak value at the prospective short-circuit current with the limited peak value. In correspondence to a short-circuit of 40kA@480V, the ACW125W circuit breaker would limit the peak value to approximately 16kA@480V.

ACW800

ACW400

W

WP

P

W

P

P

W

ACW250

ACW125

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-131

AcW

SER

IES

Current-limiting curves @ 480V

Characteristics curves - Current limiting

Available short circuit current (kArms)

Max

imum

pea

k le

t-th

roug

h cu

rren

t (kA

)

P

W

P

W

W

WP

P

ACW800

ACW400

ACW250

ACW125

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-132

AcW SERIES

Current-limiting curves @600V

Characteristics curves - Current limiting

ACW800

W

P

ACW400

W

P

W

ACW250

P

W

P

ACW125

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-133

AcW

SER

IES

Let-through energy curves @240V

Characteristics curves - Let-through energy

Max

imum

let-

thro

ugh

l²t (A

²s)

Available short circuit current (kArms)

The prospective symmetrical short-circuit current is indicated on the abscissa of the diagram, whereas the ordinates show the specific let through energy values expressed in A2s. In correspondence to a short-cir-cuit of 65kA@480V, the ACW125W circuit breaker lets through a value of I2t approximately to 400kA2s.

W

ACW800

ACW400

W

W

W

P

P

P

P

ACW250

ACW125

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-134

AcW SERIES

Let-through energy curves @ 480V

Characteristics curves - Let-through energyM

axim

um le

t-th

roug

h l²t

(A²s

)

ACW800

ACW400

ACW250

ACW125

W

W

P

P

P

P

W

W

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-135

AcW

SER

IES

Let-through energy curves @ 600V

Characteristics curves - Let-through energy

ACW800

ACW400

ACW250

ACW125

W

P

P

W

P

P

W

W

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-136

AcW SERIES

ACW125

Dimensions - inch (mm)

ACW250

Drillingtemplate

Drillingtemplate

Front viewcut-out

Front viewcut-out

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-137

AcW

SER

IES

ACW400

ACW800

Dimensions - inch (mm)

Drillingtemplate

Drillingtemplate

Front viewcut-out

Front viewcut-out

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-138

AcW SERIES

14.5 (368.3)

14.5(368.3) - 12” shaft18.5(470) - 16” shaft26.5(673.1) - 24” shaft

Panel drilling Way of installation

Dimensions - inch (mm)

Extended rotary handle - ACW125

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-139

AcW

SER

IES

Panel drilling Way of installation

Dimensions - inch (mm)

Extended rotary handle - ACW250

14.54 (369.3)

14.54 (369.3) -12” shaft18.54 (471) - 16” shaft26.54 (674.1) - 24” shaft

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-140

AcW SERIES

15.93 (404.6) -12” shaft19.93 (506) - 16” shaft27.93 (709.4) -24” shaft

Panel drilling Way of installation

Dimensions - inch (mm)

Extended rotary handle - ACW400

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-141

AcW

SER

IES

Panel drilling Way of installation

Dimensions - inch (mm)

Extended rotary handle - ACW800

17.42 (442.5) - 12” shaft21.42 (541.2) - 16” shaft29.42 (747.32) - 24” shaft

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-142

AcW SERIES

Dimensions - inch (mm)

Flange Handle ACW125

Panel drilling Way of installation

Table 1 Maximum "E" Dimension

Enclosure Depth 60” cable 72” cable

10 25 30

12 24 29

16 23 28

18 22 27

20 21 26

24 20 25

30 19 24

36 18 23

Table 2 Maximum "F" Dimension

Enclosure Depth

60” cable 72” cable

Up Down Up Down

10 17 31 20 34

12 17 31 19 33

16 17 28 19 30

18 17 28 19 30

20 16 26 18 28

24 14 26 16 28

30 11 24 13 26

36 6 21 8 22

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-143

AcW

SER

IES

Dimensions - inch (mm)

Flange Handle ACW250

Panel drilling Way of installation

Table 1 Maximum "E" Dimension

Enclosure Depth 60” cable 72” cable

10 25 30

12 24 29

16 23 28

18 22 27

20 21 26

24 20 25

30 19 24

36 18 23

Table 2 Maximum "F" Dimension

Enclosure Depth

60” cable 72” cable

Up Down Up Down

10 17 31 20 34

12 17 31 19 33

16 17 28 19 30

18 17 28 19 30

20 16 26 18 28

24 14 26 16 28

30 11 24 13 26

36 6 21 8 22

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-144

AcW SERIES

Dimensions - inch (mm)

Flange Handle ACW400

Panel drilling Way of installation

Table 1 Maximum "E" Dimension

Enclosure Depth 60” cable 72” cable

10 25 30

12 24 29

16 23 28

18 22 27

20 21 26

24 20 25

30 19 24

36 18 23

Table 2 Maximum "F" Dimension

Enclosure Depth

60” cable 72” cable

Up Down Up Down

10 17 31 20 34

12 17 31 19 33

16 17 28 19 30

18 17 28 19 30

20 16 26 18 28

24 14 26 16 28

30 11 24 13 26

36 6 21 8 22

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-145

AcW

SER

IES

Dimensions - inch (mm)

Flange Handle ACW800

Panel drilling Way of installation

Table 1 Maximum "E" Dimension

Enclosure Depth 60” cable 72” cable

10 25 30

12 24 29

16 23 28

18 22 27

20 21 26

24 20 25

30 19 24

36 18 23

Table 2 Maximum "F" Dimension

Enclosure Depth

60” cable 72” cable

Up Down Up Down

10 17 31 20 34

12 17 31 19 33

16 17 28 19 30

18 17 28 19 30

20 16 26 18 28

24 14 26 16 28

30 11 24 13 26

36 6 21 8 22

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-146

AcW SERIES

Dimensions - inch (mm)

Mechanical interlocking device - MIT

Mechanical interlocking device - Mounting dimension for MIT

A (inch) B (inch)

ACW125 3.267 3.385

ACW250 4.015 3.385

ACW400 6.614 4.330

ACW800 7.193 5.314

3 Pole MCCB C(inch) D(inch) E(inch)

ACW125 4.212 3.543 1.181

ACW250 4.921 4.133 1.377

ACW400 7.874 5.490 1.830

ACW800 10.944 8.267 2.755

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-147

MPW

SER

IES

Manual Motor Protectors

MPW SeriesOperation and Protection of Motors up to 100AOutstanding DesignWEG Manual Motor Protectors are the state-of-the-art products available for worldwide market. With the latest technology and design, you’ll find how easy is to save panel space and to face almost any application in motor control. Built in a very compact frame size, WEG’s Manual Motor Protectors combine, motor control, disconnect means short-circuit and motor overload protections in just one component.

These devices include pushbutton operators or a three-position rotary ON-TRIP-OFF handle, which can be padlocked in the OFF position.

WEG Manual Motor Protectors are designed for DIN rail mounting, while lugs for direct panel mounting are also available as an accessory.

Even Better PerformanceMotor protectors include some of the same features you can find in WEG’s RW bimetal overload relays, such as Class 10 protection, ambient temperature compensation and phase failure sensitivity, which give you all the protection your motors need. For short circuit protection, the magnetic device trips at 13 times the maximum FLA of the component.

When using WEG’s contactors connected with the MPW series, you can provide a remote control either using pushbuttons or any other remote control device. Manual Motor Protectors can handle a wide range of applications, not only three phase motor control but single phase and DC motors as well.

A product for the world Motor protectors are designed for use according to international standards, making them suitable for applications all over the world. Because of the multiple approvals WEG’s Manual Motor Protectors can be used for many different applications. IEC standards recognize MPW series as a Circuit Breaker. According to this, different functions are available:

g Motor Circuit Protectiong Manual Disconnectg Main Switchg Emergency Disconnect

So, if you export your motor control panels outside the U.S. and Canada, the MPW series are your right choice. Also, UL508 has MPW series listed as Motor Controller, allowing them to be used in several different configurations:

g Manual Motor Starter, g Combination Starter,g Group Motor Installations,g Motor Disconnect Applications

So, if you use your motor control panels inside the U.S. and Canada, the MPW series are still your right choice.

Certifications

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-148

MPW

SERIES

Controls Manual Motor Protectors - MPW Series

Adjustableoverload Release(acc. to motor’s FL A)

Fixed Short-circuit Release13 x In

Test TripSwitch

Temperaturecompensation(-4 to +140F)

Rotary handleLockable in off-position

Phase-loss Sensitivity

handle withTrip PositionIndication

Standard Features g High short-circuit interrupting rating – up to 50kA @ 480Vg Current limiting short-circuit protectiong Thermal overload protection Class 10g Phase loss sensitivity protectiong Ambient temperature compensation -4ºF +140ºF (-20ºC +60ºC)g Lockable rotary handle mechanism for disconnectg Visual indication of ON-TRIP-OFF statusg 35mm DIN-rail mountingg Snap-in accessoriesg Finger safe protected terminalsg Rated for DC applicationsg Test trip featureg Coordination type 2 per IEC60947-4-1 and UL508E, with WEG’s CWM contactorsg Manual Motor Startersg Group motor installations (per NEC Article 430)g Multi-motor starter applicationsg Suitable for motor disconnect applicationsg UL Type-E self protected combination starter

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-149

MPW

SER

IES

WEG‘s Self Protected Combination Type-E Motor Controller with Unmatched Features and BenefitsCombination starters are the most common type of packaged motor

controllers. They are called combination because of their construction

and combined functions required by the US National Electric Code (NEC):

Motor Disconnect, Motor Branch Circuit Protection, Motor Controller and

Motor Overload Protection. UL1 currently recognizes six different types

of combination starters that meet the requirements of a motor branch

circuit.

Constructions Types A through D are traditional starters that use either

a listed disconnect switch and fuses or a listed circuit breakers as the

disconnect means and for short circuit protection. Each type uses a

separate UL 508 listed motor controller and overload relay. Recently

revisions on UL508 introduced the Type E and Type F starters.

Type E starter is a self-protected combination motor controller that

combines in a single device all the required functions of a combination

starter and eliminates any additional requirements for upstream fuses

or circuit breakers. These starters clear faults within their rating without

sustaining damage to themselves or the rest of the system, being able

to get back into operation. There are two arrangements for a Type E

starter: manual (as stand-alone) and associated with a contactor. Both

are submitted to the same tests sequences.

Type F starter consists of a listed manual Type E combined with a UL508

listed contactor. The difference between the two types is related to the

absence of self-protected characteristic; hence, Type F has softened

tests sequences allowing damages on the contactor after a fault.

Tests performed in order to fulfill the Type E requirements are

considered the hardest in UL508, including short-circuit and endurance

tests on the same sample. As a comparison, UL Type E exceeds the

requirements for Type F and IEC60947-4-1 Coordination type 2.

WEG’s self-protected combination Type E combines all of these functions

within a single product for a manual operation or within a set of two

products (with a listed contactor) for a remote operation. Both options

must be associated with the accessories Line Side Terminal (LST25)

and Tripping Signaling Block (TSB-22) to accomplish UL508/UL489

requirements for spacing (clearance and creepage) and short-circuit

indication.

They are recommended for a wide range of applications where full

voltage combination starters are required. Some examples are: Pumps,

Industrial Washing Machines, Compressors, Blowers, Cutting Machines,

Conveyors, Lumber Processing and many others.

The Manual Type E Starter is a stand-alone product – MPW series –

that ranges from fractional up to 75Hp@460V motors (0.16 to 100A)

with up to 100KA@480V and 50KA@600V interrupting short-circuit

capability. Together with some accessories that complete this product

line, the MPW series are a compact and reliable solution for starting and

protecting motors.

WEG also offers an option for a remote Type E & F Starter, combining

the MPW series (as a manual type E) together with a contactor from

CWM Series. As this version undergoes the same tests, it has the same

horse power ratings and short-circuit capabilities as the manual Type E.

However, it provides remote operation and controlling of the application

through the contactor’s coil.

In addition to its popular line of UL enclosed starters, WEG is also

providing a NEMA 4X (IP65) enclosed Type E & F Starter – ESWE &

ESWF – featuring as standard a handle for disconnect means through

the door and a contactor for remote operation. Provisions for control

circuit transformer installation as well as pilot lights are also included.

UL Combination Starter Type

UL 489 Inverse Time CircuitBreaker

UL 508 Manual Self-protected Combination Controller

UL 508 Magnetic orSolid State Controller

UL 508 Manual Self-Protected Combination

Controller

UL 508 Magnetic or Solid State

Controller

UL 508 MotorOverload Relay

UL 489 Instantaneous Trip Circuit Breaker

UL 508 Self-protected Combination Controller

UL 248 Fuses

UL 98 ManualDisconnect

UL 508 MotorShort Circuit

Protector

A

B

C

D

E

F

Branch CircuitProtection

Disconnected Motor Controller

Device Used for Component Function

Motor OL Relay

TYPES A - d coMbINATIoN STARTERS TYPES E & F coMbINATIoN STARTERS

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-150

MPW

SERIES

Controls Manual Motor Protectors - MPW SeriesN OL

OTO T T P S

- 3 - U00416MPW

MANUAL MOTOR PROTECTOR SERIES:

MPW: Manual Motor Protectors POWER POLE:

3: 3 NO Power Poles

FRAME SIZE:

16: to use with CWC07…025 & CWM9…CWM1825: to use with CWC07…025 & CWM9…40 65: to use with CWM50…80 100: to use with CWM95…105

OVERLOAD SETTING CURRENT:

MPW16 C016: 0.10 ... 0.16A ... U016: 10 … 16A

MPW25 C016: 0.10 ... 0.16A ... U032: 25 … 32A

For more details refer to selection table for each frame size

MPW65 U016: 10 … 16A ... U065: 50 ... 65A

MPW100 U075: 55 … 75A ... U100: 80 ... 100A

Catalog part number composition

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-151

MPW

SER

IES

Controls Manual Motor Protectors - Overview

MPW16 MPW25

Gene

ral T

echn

ical

dat

a

Maximum Rated current Imax(Iu) 16A 32A

Maximum horsepower rating at 460Vac 60hz 10Hp 20HpNumber of poles 3 3

Short-circuit release 13 x lu max 13 x lu max

Rated operational Voltage ue 600V 600V

Rated Frequency 50/60Hz 50/60HzTripping Test Yes Yesoverload Protection Yes YesPhase failure sensitivity Yes YesTripping Indication Yes YesTripping class 10 10Mechanical life Number of operations 100,000 100,000Electrical life Number of operations 100,000 100,000Temperature compensation -4...+140ºF -4...+140ºFType of protection Thermomagnetic Thermomagnetic

overload setting

Ir(A)

Catalog number Catalog number

0.1...0.16 MPW16-3-C016 MPW25-3-C0160.16...0.25 MPW16-3-C025 MPW25-3-C0250.25...0.4 MPW16-3-D004 MPW25-3-D0040.4...0.63 MPW16-3-C063 MPW25-3-C0630.63...1 MPW16-3-U001 MPW25-3-U0011...1.6 MPW16-3-D016 MPW25-3-D016

1.6...2.5 MPW16-3-D025 MPW25-3-D0252.5...4 MPW16-3-U004 MPW25-3-U0044...6.3 MPW16-3-D063 MPW25-3-D063

6.3...10 MPW16-3-U010 MPW25-3-U01010...16 MPW16-3-U016 MPW25-3-U01616...20

-

MPW25-3-U02020...25 MPW25-3-U02525...32 MPW25-3-U03232...40

-

40...5050...6555...7570...9080...100

All functions in just one component:g Disconnect meansg Short circuit protectiong Motor controlg Overload protection

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-152

MPW

SERIES

MPW65 MPW100

Gene

ral T

echn

ical

dat

a

Maximum Rated current Imax(Iu) 65A 100A

Maximum horsepower rating at 460Vac 60hz 50Hp 75HpNumber of poles 3 3

Short-circuit release 13 x lu max 13 x lu max

Rated operational Voltage ue 600V 600V

Rated Frequency 50/60Hz 50/60HzTripping Test Yes Yesoverload Protection Yes YesPhase failure sensitivity Yes YesTripping Indication Yes YesTripping class 10 10Mechanical life Number of operations 50,000 50,000Electrical life Number of operations 25,000 25,000Temperature compensation -4...+140ºF -4...+140ºFType of protection Thermomagnetic Thermomagnetic

Overload Fitting

Ir(A)

Catalog Number Catalog Number

0.1...0.16

-

-

0.16...0.250.25...0.40.4...0.630.63...11...1.6

1.6...2.52.5...44...6.36.3...1010...1616...2020...2525...3232...40 MPW65-3-U04040...50 MPW65-3-U05050...65 MPW65-3-U06555...75

-MPW100-3-U075

70...90 MPW100-3-U09080...100 MPW100-3-U100

Controls Manual Motor Protectors - OverviewDesigned for DIN rail mounting, lugs for direct panel mounting are also available as accessory.

MPW Manual Motor Protectors are available in four models: MPW16/MPW25 (45mm), MPW65 (54mm) and MPW100 (70mm) and designed for use according to international standards, making them suitable for applications all over the world.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-153

MPW

SER

IES

1. MPW16 Manual Motor Protector - MPW16 Series

2 FTbbS Three Phase Line Side Feeder Terminal

3. bbS Three Phase Busbars

4. PLMP Push-in Lugs for panel mounting

5. AcbS Auxiliary Contact Block Side-Mounting

6. uRMP/SRMP Undervoltage Release / Shunt Release

7. AcbF Auxiliary Contact Block Front-Mounting

8. EccMP-c016 Connection Link (MPW16 to + CWC07...16)

9. cWc 07, 09, 012, 016, Miniature Contactors

10. PE66GN IP66 Non Metallic Insulated Enclosure

11. Printed Circuit Board Connector for Power Terminals

12. Printed Circuit Board Connector front Auxiliary Contact Block

13. ScMP Scale Cover

Controls Manual Motor Protectors - MPW Series

MPW16 - Overview

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-154

MPW

SERIES

Controls Manual Motor Protectors - MPW Series

MPW16 - Product Selection

g Suitable for manual motor controller and group installationg Built-in protection: disconnect means, short circuit protection, motor control and overload protectiong Short circuit interrupting capacity up to 50kA@480Vac (10kA@600Vac)g Fixed short circuit release 13 x lug Phase loss sensivityg Ambient temperature compensation -40...+1400F (-20...+600C)

Maximum uL horsepowerThermal Setting

Short-circuit interruption

capacity catalog NumberList

PriceMultiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V [A] 480V 600V

- - - - - - 0.10 - 0.16 50kA 10kA MPW16-3-c016 $97 Z4

- - - - - - 0.16 - 0.25 50kA 10kA MPW16-3-c025 $97 Z4

- - - - - 0.25 - 0.40 50kA 10kA MPW16-3-d004 $97 Z4

- - - - - - 0.40 - 0.63 50kA 10kA MPW16-3-c063 $105 Z4

- - - - - 1/2 0.63 - 1.0 50kA 10kA MPW16-3-u001 $105 Z4

- 1/10 - - 3/4 3/4 1.0 - 1.6 50kA 10kA MPW16-3-d016 $105 Z4

- 1/6 1/2 1/2 1 1 1/2 1.6 - 2.5 50kA 10kA MPW16-3-d025 $105 Z4

1/8 1/3 3/4 3/4 2 3 2.5 - 4.0 50kA 10kA MPW16-3-u004 $105 Z4

1/4 1/2 1 1 1/2 3 5 4.0 - 6.3 50kA 10kA MPW16-3-d063 $105 Z4

1/2 1 1/2 2 3 5 7 1/2 6.3 - 10 50kA 5kA MPW16-3-u010 $105 Z4

1 2 3 5 10 10 10 - 16 30kA 5kA MPW16-3-u016 $105 Z4

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-155

MPW

SER

IES

Controls Manual Motor Protectors - MPW Series

description catalog Number List PriceMultiplier Symbol

Auxiliary contact blocks

1NO&1NC auxiliary contact block front mounting - 250Vmax. AcbF-11 $20 Z4

1NO&1NC auxiliary contact block left side mounting - 600Vmax. AcbS-11 $22 Z4

2NO Auxiliary contact block left side mounting - 600Vmax. AcbS-20 $22 Z4

2NC Auxiliary contact block left side mounting - 600Vmax. AcbS-02 $22 Z4

Link Modules

Mechanical and electrical link module for CWC07 to CWC016 miniature contactor series EccMP-c016 $20 Z4

Mechanical and electrical link module for CWC025 miniature contactor series EccMP-c025 $20 Z4

Accessories for Group Motor Installation 1

Three Phase Line Side Feeder Terminal FTbbS $35 Z4

Bus bar system 45mm (for 2 MPW without side mounting auxiliary contacts) bbS45-2 $32 Z4

Bus bar system 45mm (for 3 MPW without side mounting auxiliary contacts) bbS45-3 $35 Z4

Bus bar system 45mm (for 4 MPW without side mounting auxiliary contacts) bbS45-4 $45 Z4

Bus bar system 45mm (for 5 MPW without side mounting auxiliary contacts) bbS45-5 $60 Z4

Bus bar system 54mm (for 2 MPW with side mounting auxiliary contacts) bbS54-2 $32 Z4

Bus bar system 54mm (for 3 MPW with side mounting auxiliary contacts) bbS54-3 $35 Z4

Bus bar system 54mm (for 4 MPW with side mounting auxiliary contacts) bbS54-4 $45 Z4

Bus bar system 54mm (for 5 MPW with side mounting auxiliary contacts) bbS54-5 $60 Z4

Shroud for unused terminals of BBS bars cSd $10 2 Z4

under Voltage and Shunt block Releases

Shunt release block right side mounting - 20-24V 50/60Hz SRMP d51 $56 Z4

Shunt release block right side mounting - 100-127V 50/60Hz SRMP d59 $56 Z4

Shunt release block right side mounting - 200-240V 50/60Hz SRMP d65 $56 Z4

Under voltage release block right side mounting - 24V 60Hz uRMP V05 $56 Z4

Under voltage release block right side mounting - 120V 60Hz uRMP V18 $56 Z4

Under voltage release block right side mounting - 208V 60Hz uRMP V23 $56 Z4

Under voltage release block right side mounting - 240V 60Hz uRMP V30 $56 Z4

Under voltage release block right side mounting - 480V 60Hz uRMP V47 $56 Z4

IEc Enclosures

IEC IP66 enclosure (non-UL) PE66GN $45 Z4

other Accessories

Scale cover protection for the current range adjustment - package with 5 units ScMP $5 Z4

Lugs for panel mounting - package with 2 pieces (one MPW mounting) PLMP $0.50 Z4

Accessories for MPW16 - Summary

Notes: 1 Maximum Amps of each Bus bar system (BBS) must not be exceeded by adding multiple MPW. Bus bar capacity is 63Amps. 2 Unit list price. Product sold in multiples of 5 units.

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-156

MPW

SERIES

Controls Manual Motor Protectors - MPW Series

MPW25

12

13

1

1

1

18

16

1910

17

9

1

7

8

155

6

2 3

4

4

21

22

20

23

14

11

1

24

1. MPW25 Manual motor protector – MPW25 Series 2. FTbbS Three-phase line side feeder terminal3. bbS Three-phase busbars4. PLMP Push-in-lugs for panel mounting5. AcbS Auxiliary contact block side mounting6. uRMP/SRMP Undervoltage release / Shunt release 7. AcbF Auxiliary contact block front mounting8. RMMP NEMA 1 through-the-door interlocked handle9. EccMP-25 Connector link (MPW25 + CWM9...25)10. cWM 9, 12, 18, 25 Contactors 11. MRX NEMA 4 through-the-door interlocked handle12. FME55 Front plate panel mounting (non-UL)13. PE55GN IP55 Non Metallic enclosure for MPW25 (standard)

14. LPE55GN IP55 Non Metallic enclosure for MPW25 (wide)15. TSb-22 Trip signaling block for Type E/F construction16. EccMP-32 Connector link (MPW25 + CWM32...40)17. cWM 32, 40 Contactors18. EccMP-c025 Connector link (MPW25 + CWC025)19. cWc025 Miniature contactor20. LST25 Line side terminal for Type E/F construction21. EccMP-c0 Connector link (MPW25 + CWC07...16)22. cWc 07, 09, 012, 016 Miniature contactors23. cLT25 Current limiter24. ScMP Scale cover

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-157

MPW

SER

IES

MPW25 - Product Selection

Maximum uL horsepowerThermal Setting

Short-circuit Ratings for Group Installation catalog Number

List Price

Multiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V [A] 480V 600V

- - - - - - 0.10 - 0.16 50kA 25kA MPW25-3-c016 $116 Z4

- - - - - - 0.16 - 0.25 50kA 25kA MPW25-3-c025 $116 Z4

- - - - - - 0.25 - 0.40 50kA 25kA MPW25-3-d004 $116 Z4

- - - - - 1/4 0.40 - 0.63 50kA 25kA MPW25-3-c063 $137 Z4

- - - - 1/2 1/2 0.63 - 1.0 50kA 25kA MPW25-3-u001 $137 Z4

- 1/10 1/4 1/3 3/4 1 1.0 - 1.6 50kA 25kA MPW25-3-d016 $137 Z4

- 1/6 1/2 1/2 1 1/2 1 1/2 1.6 - 2.5 50kA 25kA MPW25-3-d025 $137 Z4

1/8 1/3 3/4 1 2 3 2.5 - 4.0 50kA 25kA MPW25-3-u004 $137 Z4

1/4 3/4 1 1/2 1 1/2 3 5 4.0 - 6.3 50kA 25kA MPW25-3-d063 $137 Z4

1/2 1 1/2 3 3 5 7 1/2 6.3 - 10 50kA 25kA MPW25-3-u010 $137 Z4

1 3 5 5 10 15 10 - 16 50kA 25kA MPW25-3-u016 $150 Z4

1 1/2 3 5 7 1/2 15 15 16 - 20 50kA 25kA MPW25-3-u020 $150 Z4

2 3 7 1/2 7 1/2 15 20 20 - 25 50kA 25kA MPW25-3-u025 $150 Z4

- 5 10 10 20 25 25 - 32 42kA 25kA MPW25-3-u032 $190 Z4

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.

Controls

Manual Motor Protectors - MPW Series

g Suitable for manual motor controller, group installation, tap conductor and combination starters* type E & type Fg Built-in protection: disconnect means, short-circuit protection, motor control and overload protectiong Short-circuit interrupting capacity up to 50kA@480Vac (25kA@600Vac)g Fixed short-circuit release 13 x Iug Phase loss sensitivityg Ambient temperature compensation -4…+140ºF (-20…+60ºC)

* When associated with line side terminal LST25 and trip indicator TSB-22

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-158

MPW

SERIES

Controls

Manual Motor Protectors - MPW Series

MPW25 with current Limiter - Product Selection

g Suitable for manual motor controller, group installation, tap conductor and combination starters* type E & type Fg Built-in protection: disconnect means, short-circuit protection, motor control and overload protectiong Short-circuit interrupting capacity up to 100kA@480Vac (50kA@600Vac)g Fixed short-circuit release 13 x Iug Phase loss sensitivityg Ambient temperature compensation -4…+140ºF (-20…+60ºC)

Maximum uL horsepowerThermal Setting

Short-circuit interruption

capacity

Individual component catalog Number1

Multiplier Symbol

Single Phase Three Phasecatalog Number

List Price

catalog Number

List Price

115V 230V 200V 230V 460V 575V [A] 480V 600V

- - - - - - 0.10 - 0.16 100kA 50kA MPW25-3-c016 $116 cLT25 $100 Z4

- - - - - - 0.16 - 0.25 100kA 50kA MPW25-3-c025 $116 cLT25 $100 Z4

- - - - - - 0.25 - 0.40 100kA 50kA MPW25-3-d004 $116 cLT25 $100 Z4

- - - - - 1/4 0.40 - 0.63 100kA 50kA MPW25-3-c063 $137 cLT25 $100 Z4

- - - - 1/2 1/2 0.63 - 1.0 100kA 50kA MPW25-3-u001 $137 cLT25 $100 Z4

- 1/10 1/4 1/3 3/4 1 1.0 - 1.6 100kA 50kA MPW25-3-d016 $137 cLT25 $100 Z4

- 1/6 1/2 1/2 1 1/2 1 1/2 1.6 - 2.5 100kA 50kA MPW25-3-d025 $137 cLT25 $100 Z4

1/8 1/3 3/4 1 2 3 2.5 - 4.0 100kA 50kA MPW25-3-u004 $137 cLT25 $100 Z4

1/4 3/4 1 1/2 1 1/2 3 5 4.0 - 6.3 100kA 50kA MPW25-3-d063 $137 cLT25 $100 Z4

1/2 1 1/2 3 3 5 7 1/2 6.3 - 10 100kA 50kA MPW25-3-u010 $137 cLT25 $100 Z4

1 3 5 5 10 15 10 - 16 100kA 50kA MPW25-3-u016 $150 cLT25 $100 Z4

1 1/2 3 5 7 1/2 15 15 16 - 20 100kA 50kA MPW25-3-u020 $150 cLT25 $100 Z4

2 3 7 1/2 7 1/2 15 20 20 - 25 100kA 50kA MPW25-3-u025 $150 cLT25 $100 Z4

- 5 10 10 20 25 25 - 32 100kA 50kA MPW25-3-u032 $190 cLT25 $100 Z4

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.

1 Individual Component Catalog Numbers are ordered separately.

* When associated with line side terminal LST25 and trip indicator TSB-22

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-159

MPW

SER

IES

Controls

Manual Motor Protectors - MPW Series

Accessories for MPW25 - Summary

description catalog NumberList

PriceMultiplier Symbol

Auxiliary contact blocks 1NO&1NC auxiliary contact block front mounting - 250Vmax. AcbF-11 $20 Z4 1NO&1NC auxiliary contact block left side mounting - 600Vmax. AcbS-11 $22 Z4 2NO Auxiliary contact block left side mounting - 600Vmax. AcbS-20 $22 Z4 2NC Auxiliary contact block left side mounting - 600Vmax. AcbS-02 $22 Z4 Accessories for combination Type-E construction Line power terminal LST25 $38 Z4 Trip Signaling and Alarm Contact Block (1NO&1NC for Short-circuit and 1NO&1NC for Overload) TSb-22 $38 Z4 current Limiter Current Limiter cLT25 $100 Z4 Link Modules Mechanical and electrical link module for CWC07 to CWC016 miniature contactor series EccMP-c0 $20 Z4 Mechanical and electrical link module for CWM9…CWM25 contactor series EccMP-25 $20 Z4 Mechanical and electrical link module for CWM32…CWM40 contactor series EccMP-32 $25 Z4 Accessories for Group Motor Installation 1

Income power terminal for bus bar system FTbbS $35 Z4 Bus bar system 45mm (for 2 MPW without side mounting auxiliary contacts) bbS45-2 $32 Z4 Bus bar system 45mm (for 3 MPW without side mounting auxiliary contacts) bbS45-3 $35 Z4 Bus bar system 45mm (for 4 MPW without side mounting auxiliary contacts) bbS45-4 $45 Z4 Bus bar system 45mm (for 5 MPW without side mounting auxiliary contacts) bbS45-5 $60 Z4 Bus bar system 54mm (for 2 MPW with side mounting auxiliary contacts) bbS54-2 $32 Z4 Bus bar system 54mm (for 3 MPW with side mounting auxiliary contacts) bbS54-3 $35 Z4 Bus bar system 54mm (for 4 MPW with side mounting auxiliary contacts) bbS54-4 $45 Z4 Bus bar system 54mm (for 5 MPW with side mounting auxiliary contacts) bbS54-5 $60 Z4 Shroud for unused terminals of BBS bars cSd $102 Z4 Through-the-door Rotary Mechanisms Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 130mm shaft RMMP-130 $60 Z4 Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 130mm shaft RMMP-130-E $60 Z4 Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 330mm shaft RMMP-330 $70 Z4 Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 330mm shaft RMMP-330-E $70 Z4 Rotary NEMA 4X Through the Door Mechanism - gray/black handle with 130mm shaft MRX-130 $105 Z4 Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 130mm shaft MRX-130-E $105 Z4 Rotary NEMA 4X Through the Door Mechanism - gray/black handle with 330mm shaft MRX-330 $115 Z4 Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 330mm shaft MRX-330-E $115 Z4 under Voltage and Shunt block Releases Shunt release block right side mounting - 20-24V 50/60Hz SRMP d51 $56 Z4 Shunt release block right side mounting - 100-127V 50/60Hz SRMP d59 $56 Z4 Shunt release block right side mounting - 200-240V 50/60Hz SRMP d65 $56 Z4 Under voltage release block right side mounting - 24V 60Hz uRMP V05 $56 Z4 Under voltage release block right side mounting - 120V 60Hz uRMP V18 $56 Z4 Under voltage release block right side mounting - 208V 60Hz uRMP V23 $56 Z4 Under voltage release block right side mounting - 240V 60Hz uRMP V30 $56 Z4 Under voltage release block right side mounting - 480V 60Hz uRMP V47 $56 Z4 Mounting adapter Mounting adapter for a D.O.L. assembly with MPW25 and CWM contactors series MA45doL $40 Z4 Mounting adapter for a REVERSING assembly with MPW25 and CWM contactors series MA90RVS $50 Z4 Mounting adapter for a STAR-DELTA assembly with MPW25 and CWM contactors series MA90SdS $50 Z4 IEc Enclosures IEC IP55 enclosure yellow/red handle (non-UL) PE55GN-E $45 Z4 IEC IP55 enclosure + lateral auxiliary device yellow/red handle (non-UL) LPE55GN-E $55 Z4 IEC IP55 enclosure gray/black handle (non-UL) PE55GN $45 Z4 IEC IP55 enclosure + lateral auxiliary device gray/black handle (non-UL) LPE55GN $55 Z4 other Accessories Scale cover protection for the current range adjustment - package with 5 units ScMP $5 Z4 Lugs for panel mounting - package with 2 pieces (one MPW mounting) PLMP $0.50 Z4

Notes: 1 Maximum Amps of each Bus bar system (BBS) must not be exceeded by adding multiple MPW. Bus bar capacity is 63Amps. 2 Unit list price. Product sold in multiples of 5 units.

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-160

MPW

SERIES

Controls

Manual Motor Protectors - MPW Series

MPW65 - Overview

1

5

6

2

2

3

4

7

8

9

1 MPW65 Manual motor protector – MPW65 Series

2 PLMP Push-in-lugs for panel mounting

3 AcbS Auxiliary contact block side mounting

4 uRMP/SRMP Undervoltage release / Shunt release

5 AcbF Auxiliary contact block front mounting

6 TSb-22 Trip signaling block for Type E/F construction

7 MRX65 NEMA 4 through-the-door interlocked handle

8 RMMP65 NEMA 1 through-the-door interlocked handle

9 ScMP Scale cover

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-161

MPW

SER

IES

Maximum uL horsepower Thermal Setting

Short-circuit inter-ruption capacity catalog Number List Price

Multiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V [A] 480V 600V

3 7 1/2 - 15 25 30 32 ... 40 35kA 10kA MPW65-3-u040 $380 Z4

- 10 15 15 30 40 40 ... 50 35kA 10kA MPW65-3-u050 $380 Z4

5 10 20 20 50 60 50 ... 65 35kA 10kA MPW65-3-u065 $380 Z4

Maximum uL horsepower Thermal Setting

Short-circuit inter-ruption capacity catalog Number List Price

Multiplier Symbol

Single Phase Three Phase

115V 230V 200V 230V 460V 575V [A] 480V 600V

5 15 20 25 50 60 55 ... 75 50kA 10kA MPW100-3-u075 $460 Z4

7 1/2 20 25 30 60 75 70 ... 90 50kA 10kA MPW100-3-u090 $530 Z4

10 20 30 30 75 100 80 ... 100 50kA 10kA MPW100-3-u100 $530 Z4

Controls

Manual Motor Protectors - MPW Series

MPW65 - Product Selection

g Suitable for manual motor controller, group installation, tap conductor and combination starters1 type E & type Fg Built-in protection: disconnect means, short-circuit protection, motor control and overload protectiong Short-circuit interrupting capacity up to 35kA@480Vac (10kA@600Vac)g Fixed short-circuit release 13 x Iug Phase loss sensitivityg Ambient temperature compensation -4…+140ºF (-20…+60ºC)

MPW100 - Product Selection

g Suitable for manual motor controller, group installation, tap conductor and combination starters2 type E & type Fg Built-in protection: disconnect means, short-circuit protection, motor control and overload protectiong Short-circuit interrupting capacity up to 50kA@480Vac (10kA@600Vac)g Fixed short-circuit release 13 x Iug Phase loss sensitivityg Ambient temperature compensation -4…+140ºF (-20…+60ºC)

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection1 When associated with line side terminal (LST65) and Trip indicator (TSB-22)

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.2 When associated with line side terminal (IB MPW100) and Trip indicator (TSB SC-11 MPW100)

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-162

MPW

SERIES

description catalog Number List Price Multiplier Symbol

Auxiliary contact blocks 1NO&1NC auxiliary contact block front mounting - 250Vmax. AcbF-11 $20 Z4 1NO&1NC auxiliary contact block left side mounting - 600Vmax. AcbS-11 $22 Z4 2NO Auxiliary contact block left side mounting - 600Vmax. AcbS-20 $22 Z4 2NC Auxiliary contact block left side mounting - 600Vmax. AcbS-02 $22 Z4 Accessories for combination Type-E construction Line power terminal (for MPW65-3-U040 to MPW65-3-U065) LST65 $75 Z4 Trip Signaling and Alarm Contact Block (1NO&1NC for Short-circuit and 1NO&1NC for Overload) TSb-22 $38 Z4 Through-the-door Rotary Mechanisms Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 130mm shaft RMMP65-130 $80 Z4 Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 130mm shaft RMMP65-130-E $80 Z4 Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 330mm shaft RMMP65-330 $90 Z4 Rotary NEMA 1 Through the Door Mechanism - yellow/red handle with 330mm shaft RMMP65-330-E $90 Z4 Rotary NEMA 4X Through the Door Mechanism - black/red handle with 130mm shaft MRX65-130 $120 Z4 Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 130mm shaft MRX65-130-E $120 Z4 Rotary NEMA 4X Through the Door Mechanism - black/red handle with 330mm shaft MRX65-330 $130 Z4 Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 330mm shaft MRX65-330-E $130 Z4 under Voltage and Shunt block Releases Shunt release block right side mounting - 20-24V 50/60Hz SRMP d51 $56 Z4 Shunt release block right side mounting - 100-127V 50/60Hz SRMP d59 $56 Z4 Shunt release block right side mounting - 200-240V 50/60Hz SRMP d65 $56 Z4 Under voltage release block right side mounting - 24V 60Hz uRMP V05 $56 Z4 Under voltage release block right side mounting - 120V 60Hz uRMP V18 $56 Z4 Under voltage release block right side mounting - 208V 60Hz uRMP V23 $56 Z4 Under voltage release block right side mounting - 240V 60Hz uRMP V30 $56 Z4 Under voltage release block right side mounting - 480V 60Hz uRMP V47 $56 Z4 other Accessories Scale cover protection for the current range adjustment - package with 5 units ScMP $5 Z4 Lugs for panel mounting - package with 2 pieces (one MPW mounting) PLMP $0.50 Z4

description catalog Number List Price Multiplier Symbol

Auxiliary contact blocks 1NO&1NC auxiliary contact block front mounting - 250Vmax. AcbF-11 MPW100 $20 Z4 1NO&1NC auxiliary contact block left side mounting - 600Vmax. AcbS-11 MPW100 $221 Z4 2NO Auxiliary contact block left side mounting - 600Vmax. AcbS-20 MPW100 $221 Z4 2NC Auxiliary contact block left side mounting - 600Vmax. AcbS-02 MPW100 $221 Z4 Accessories for combination Type-E construction Insulators Ib MPW100 $30 Z4 Trip Signaling and Alarm Contact Block (1NO&1NC for Short-circuit and Overload) TSb-11 MPW100 $381 Z4 Through-the-door Rotary Mechanisms Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 115mm shaft MR MPW100-115 $80 Z4 Rotary NEMA 1 Through the Door Mechanism - gray/black handle with 315mm shaft MR MPW100-315 $90 Z4 Rotary NEMA 4X Through the Door Mechanism - gray/black handle with 130mm shaft MRX100-130 $130 Z4 Rotary NEMA 4X Through the Door Mechanism - yellow/red handle with 130mm shaft MRX100-130E $130 Z4 under Voltage and Shunt block Releases Shunt release block right side mounting - 120V 50/60Hz SRMP V18 MPW100 $56 Z4 Shunt release block right side mounting - 240-260V 60Hz SRMP V33 MPW100 $56 Z4 Under voltage release block right side mounting - 120V 60Hz uRMP V18 MPW100 $56 Z4 Under voltage release block right side mounting - 240V 60Hz uRMP V33 MPW100 $56 Z4 Under voltage release block right side mounting - 460V 60Hz uRMP V43 MPW100 $56 Z4

Controls

Manual Motor Protectors - MPW Series

Accessories for MPW65 - Summary

Accessories for MPW100 - Summary

Notes: 1 Unit list price. Product sold in multiples of 2 units.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-163

MPW

SER

IES

WEG‘s Self Protected Combination Type-E Motor Controller with Unmatched Features and BenefitsCombination starters are the most common type of packaged motor

controllers. They are called combination because of their construction

and combined functions required by the US National Electric Code

(NEC): Motor Disconnect, Motor Branch Circuit Protection, Motor

Controller and Motor Overload Protection. UL1 currently recognizes

six different types of combination starters that meet the requirements

of a motor branch circuit.

Constructions Types A through D are traditional starters that use either

a listed disconnect switch and fuses or a listed circuit breakers as the

disconnect means and for short circuit protection. Each type uses a

separate UL 508 listed motor controller and overload relay. Recently

revisions on UL508 introduced the Type E and Type F starters.

Type E starter is a self-protected combination motor controller that

combines in a single device all the required functions of a combination

starter and eliminates any additional requirements for upstream

fuses or circuit breakers. These starters clear faults within their rating

without sustaining damage to themselves or the rest of the system,

being able to get back into operation. There are two arrangements

for a Type E starter: manual (as stand-alone) and associated with a

contactor. Both are submitted to the same tests sequences.

Type F starter consists of a listed manual Type E combined with

a UL508 listed contactor. The difference between the two types is

related to the absence of self-protected characteristic; hence, Type

F has softened tests sequences allowing damages on the contactor

after a fault.

Tests performed in order to fulfill the Type E requirements are

considered the hardest in UL508, including short-circuit and

endurance tests on the same sample. As a comparison, UL

Type E exceeds the requirements for Type F and IEC60947-4-1

Coordination type 2.

WEG’s self-protected combination Type E combines all of these

functions within a single product for a manual operation or within a set

of two products (with a listed contactor) for a remote operation. Both

options must be associated with the accessories Line Side Terminal

(LST25) and Tripping Signaling Block (TSB-22) to accomplish UL508/

UL489 requirements for spacing (clearance and creepage) and short-

circuit indication.

They are recommended for a wide range of applications where

full voltage combination starters are required. Some examples are:

Pumps, Industrial Washing Machines, Compressors, Blowers, Cutting

Machines, Conveyors, Lumber Processing and many others.

The Manual Type E Starter is a stand-alone product – MPW series

– that ranges from fractional up to 75Hp@460V motors (0.16 to

100A) with up to 100KA@480V and 50KA@600V interrupting short-

circuit capability. Together with some accessories that complete this

product line, the MPW series are a compact and reliable solution for

starting and protecting motors.

WEG also offers an option for a remote Type E & F Starter, combining

the MPW series (as a manual type E) together with a contactor

from CWM Series. As this version undergoes the same tests, it

has the same horse power ratings and short-circuit capabilities

as the manual Type E. However, it provides remote operation and

controlling of the application through the contactor’s coil.

In addition to its popular line of UL enclosed starters, WEG is also

providing a NEMA 4X (IP65) enclosed Type E & F Starter – ESWE

& ESWF – featuring as standard a handle for disconnect means

through the door and a contactor for remote operation. Provisions

for control circuit transformer installation as well as pilot lights are

also included.

UL Combination Starter Type

UL 489 Inverse Time CircuitBreaker

UL 508 Manual Self-protected Combination Controller

UL 508 Magnetic orSolid State Controller

UL 508 Manual Self-Protected Combination

Controller

UL 508 Magnetic or Solid State

Controller

UL 508 MotorOverload Relay

UL 489 Instantaneous Trip Circuit Breaker

UL 508 Self-protected Combination Controller

UL 248 Fuses

UL 98 ManualDisconnect

UL 508 MotorShort Circuit

Protector

A

B

C

D

E

F

Branch CircuitProtection

Disconnected Motor Controller

Device Used for Component Function

Motor OL Relay

TYPES A - d coMbINATIoN STARTERS TYPES E & F coMbINATIoN STARTERS

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-164

www.weg.net

Controls

Manual Motor Protectors - MPW SeriesManual Self-Protected Combination Motor Controller Type-Eg No need of upstream protective devices such as UL489 MCCB or UL248 fuses

g Built-in protections: disconnect means, short-circuit protection, motor control and overload protection

g Short-circuit interrupting capacity up to 100kA@480Vac (50kA@600Vac)

g Compact combination starter

g Phase loss sensitivity

g Ambient temperature compensation -4…+140ºF (-20…+60ºC)

Maximum uL horsepowerThermalSetting

Short-circuit

Interruption capacity

Individual component catalog Number1

Single Phase Three Phase Manual Motor Protector

Line Side Terminal

Tripping IndicatorList

PriceMultiplierSymbol

115V 230V 200V 230V 460V 575V [A] 480V

- - - - - - 0.10 - 0.16 50kA MPW25-3-c016 LST25 TSb-22$192

Z4

- - - - - - 0.16 - 0.25 50kA MPW25-3-c025 LST25 TSb-22- - - - - - 0.25 - 0.40 50kA MPW25-3-d004 LST25 TSb-22- - - - - 1/4 0.40 - 0.63 50kA MPW25-3-c063 LST25 TSb-22

$213

- - - - 1/2 1/2 0.63 - 1.0 50kA MPW25-3-u001 LST25 TSb-22- 1/10 1/4 1/3 3/4 1 1.0 - 1.6 50kA MPW25-3-d016 LST25 TSb-22- 1/6 1/2 1/2 1 1/2 1 1/2 1.6 - 2.5 50kA MPW25-3-d025 LST25 TSb-22

1/8 1/3 3/4 1 2 3 2.5 - 4.0 50kA MPW25-3-u004 LST25 TSb-221/4 3/4 1 1/2 1 1/2 3 5 4.0 - 6.3 50kA MPW25-3-d063 LST25 TSb-221/2 1 1/2 3 3 5 7 1/2 6.3 - 10 50kA MPW25-3-u010 LST25 TSb-221 3 5 5 10 15 10 - 16 50kA MPW25-3-u016 LST25 TSb-22

$2261 1/2 3 5 7 1/2 15 15 16 - 20 50kA MPW25-3-u020 LST25 TSb-222 3 7 1/2 7 1/2 15 20 20 - 25 50kA MPW25-3-u025 LST25 TSb-22- 5 10 10 20 25 25 - 32 42kA MPW25-3-u032 LST25 TSb-22 $2643 7 1/2 - 15 25 30 32 ... 40 35kA MPW65-3-u040 LST65 TSb-22

$483- 10 15 15 30 40 40 ... 50 35kA MPW65-3-u050 LST65 TSb-225 10 20 20 50 60 50 ... 65 35kA MPW65-3-u065 LST65 TSb-225 15 20 25 50 60 55 ... 75 50kA MPW100-3-u075 Ib MPW100 TSb Sc-11 MPW100 $526

7 1/2 20 25 30 60 75 70 ... 90 50kA MPW100-3-u090 Ib MPW100 TSb Sc-11 MPW100$596

10 20 30 30 75 100 80 ... 100 50kA MPW100-3-u100 Ib MPW100 TSb Sc-11 MPW100

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.1 Individual Component Catalog Numbers are ordered separately. Multiplier Symbol Z4.

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.1 Individual Component Catalog Numbers are ordered separately. Multiplier Symbol Z4.

High Interruption Capacity

Extra High Interruption Capacity

Maximum uL horsepowerThermal Setting

Short-circuit

Interruption capacity

Individual component catalog Number1

Single Phase Three Phase Manual Motor Protector

current Limiter

Line Side Terminal

Tripping Indicator

List Price

MultiplierSymbol

115V 230V 200V 230V 460V 575V [A] 480V- - - - - - 0.10 - 0.16 100kA MPW25-3-c016 cLT25 LST25 TSb-22

$292

Z4

- - - - - - 0.16 - 0.25 100kA MPW25-3-c025 cLT25 LST25 TSb-22- - - - - - 0.25 - 0.40 100kA MPW25-3-d004 cLT25 LST25 TSb-22- - - - - 1/4 0.40 - 0.63 100kA MPW25-3-c063 cLT25 LST25 TSb-22

$313

- - - - 1/2 1/2 0.63 - 1.0 100kA MPW25-3-u001 cLT25 LST25 TSb-22- 1/10 1/4 1/3 3/4 1 1.0 - 1.6 100kA MPW25-3-d016 cLT25 LST25 TSb-22- 1/6 1/2 1/2 1 1/2 1 1/2 1.6 - 2.5 100kA MPW25-3-d025 cLT25 LST25 TSb-22

1/8 1/3 3/4 1 2 3 2.5 - 4.0 100kA MPW25-3-u004 cLT25 LST25 TSb-221/4 3/4 1 1/2 1 1/2 3 5 4.0 - 6.3 100kA MPW25-3-d063 cLT25 LST25 TSb-221/2 1 1/2 3 3 5 7 1/2 6.3 - 10 100kA MPW25-3-u010 cLT25 LST25 TSb-221 3 5 5 10 15 10 - 16 100kA MPW25-3-u016 cLT25 LST25 TSb-22

$3361 1/2 3 5 7 1/2 15 15 16 - 20 100kA MPW25-3-u020 cLT25 LST25 TSb-222 3 7 1/2 7 1/2 15 20 20 - 25 100kA MPW25-3-u025 cLT25 LST25 TSb-22- 5 10 10 20 25 25 - 32 100kA MPW25-3-u032 cLT25 LST25 TSb-22 $364

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-165

MPW

SER

IES

Controls

Manual Motor Protectors - MPW Series

Combination Motor Controller Type-F

g No need of upstream protective devices such as UL489 MCCB or UL248 fuses

g Built-in protections: disconnect means, short-circuit protection, motor control and overload protection

g Short-circuit interrupting capacity up to 100kA@480Vac (50kA@600Vac)

g Compact combination starter

g Phase loss sensitivity

g Ambient temperature compensation -4…+140ºF (-20…+60ºC)

g Remote operation

high interruption capacity

Maximum uL horsepowerThermal Setting

Short-circuit Interruption

capacity

Individual component catalog Number1

Single Phase Three Phase Manual Motor Protector

Line Side Terminal

Tripping Indicator

ListPrice2 contactor3 List

Price3

115V 230V 200V 230V 460V 575V [A] 480V- - - - - - 0.10 - 0.16 50kA MPW25-3-c016 LST25 TSb-22

$192cWM9

$72

- - - - - - 0.16 - 0.25 50kA MPW25-3-c025 LST25 TSb-22 cWM9- - - - - - 0.25 - 0.40 50kA MPW25-3-d004 LST25 TSb-22 cWM9- - - - - 1/4 0.40 - 0.63 50kA MPW25-3-c063 LST25 TSb-22

$213

cWM9- - - - 1/2 1/2 0.63 - 1.0 50kA MPW25-3-u001 LST25 TSb-22 cWM9- 1/10 1/4 1/3 3/4 1 1.0 - 1.6 50kA MPW25-3-d016 LST25 TSb-22 cWM9- 1/6 1/2 1/2 1 1/2 1 1/2 1.6 - 2.5 50kA MPW25-3-d025 LST25 TSb-22 cWM9

1/8 1/3 3/4 1 2 3 2.5 - 4.0 50kA MPW25-3-u004 LST25 TSb-22 cWM91/4 3/4 1 1/2 1 1/2 3 5 4.0 - 6.3 50kA MPW25-3-d063 LST25 TSb-22 cWM91/2 1 1/2 3 3 5 7 1/2 6.3 - 10 50kA MPW25-3-u010 LST25 TSb-22 cWM91 3 5 5 10 15 10 - 16 50kA MPW25-3-u016 LST25 TSb-22

$226cWM18 $103

1 1/2 3 5 7 1/2 15 15 16 - 20 50kA MPW25-3-u020 LST25 TSb-22 cWM25 $1182 3 7 1/2 7 1/2 15 20 20 - 25 50kA MPW25-3-u025 LST25 TSb-22 cWM32 $140- 5 10 10 20 25 25 - 32 42kA MPW25-3-u032 LST25 TSb-22 $264 cWM40 $1643 7 1/2 - 15 25 30 32 ... 40 30kA MPW65-3-u040 LST65 TSb-22

$483cWM50 $190

- 10 15 15 30 40 40 ... 50 30kA MPW65-3-u050 LST65 TSb-22 cWM65 $2155 10 20 20 50 60 50 ... 65 30kA MPW65-3-u065 LST65 TSb-22 cWM80 $2615 15 20 25 50 60 55 ... 75 50kA MPW100-3-u075 Ib MPW100 TSb Sc-11 MPW100 $526 cWM95

$2947 1/2 20 25 30 60 75 70 ... 90 50kA MPW100-3-u090 Ib MPW100 TSb Sc-11 MPW100

$596cWM95

10 20 30 30 75 100 80 ... 100 50kA MPW100-3-u100 Ib MPW100 TSb Sc-11 MPW100 cWM105 $393Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.¹ Individual Component Catalog Numbers are ordered separately. 2 Multiplier Symbol Z43 Multiplier Symbol Z14 For Link Module, see accessories

Extra-high interruption capacity

Maximum uL horsepowerThermal Setting

Short-circuit Interruption

capacity

Individual component catalog Number1

Single Phase

Three Phase Manual Motor Protector

current Limiter

Line Side

Terminal

Tripping Indicator

ListPrice2 contactor3 List

Price3

115V 230V 200V 230V 460V 575V [A] 480V- - - - - - 0.10 - 0.16 100kA MPW25-3-c016 cLT25 LST25 TSb-22

$292cWM9

$72

- - - - - - 0.16 - 0.25 100kA MPW25-3-c025 cLT25 LST25 TSb-22 cWM9- - - - - - 0.25 - 0.40 100kA MPW25-3-d004 cLT25 LST25 TSb-22 cWM9- - - - - 1/4 0.40 - 0.63 100kA MPW25-3-c063 cLT25 LST25 TSb-22

$313

cWM9- - - - 1/2 1/2 0.63 - 1.0 100kA MPW25-3-u001 cLT25 LST25 TSb-22 cWM9- 1/10 1/4 1/3 3/4 1 1.0 - 1.6 100kA MPW25-3-d016 cLT25 LST25 TSb-22 cWM9- 1/6 1/2 1/2 1 1/2 1 1/2 1.6 - 2.5 100kA MPW25-3-d025 cLT25 LST25 TSb-22 cWM9

1/8 1/3 3/4 1 2 3 2.5 - 4.0 100kA MPW25-3-u004 cLT25 LST25 TSb-22 cWM91/4 3/4 1 1/2 1 1/2 3 5 4.0 - 6.3 100kA MPW25-3-d063 cLT25 LST25 TSb-22 cWM91/2 1 1/2 3 3 5 7 1/2 6.3 - 10 100kA MPW25-3-u010 cLT25 LST25 TSb-22 cWM91 3 5 5 10 15 10 - 16 100kA MPW25-3-u016 cLT25 LST25 TSb-22

$336cWM18 $103

1 1/2 3 5 7 1/2 15 15 16 - 20 100kA MPW25-3-u020 cLT25 LST25 TSb-22 cWM25 $1182 3 7 1/2 7 1/2 15 20 20 - 25 100kA MPW25-3-u025 cLT25 LST25 TSb-22 cWM32 $140- 5 10 10 20 25 25 - 32 100kA MPW25-3-u032 cLT25 LST25 TSb-22 $364 cWM40 $164

Note: Horsepower ratings shown in the table are for reference only. Please refer to the Full Load Amps of the Motor for final selection.¹ Individual Component Catalog Numbers are ordered separately. 2 Multiplier Symbol Z43 Multiplier Symbol Z1

(4)

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-166

MPW

SERIES

For use withAuxiliary contacts

catalog Number ListPrice

MultiplierSymbolNo Nc

MPW16MPW25MPW65

1

1 1

AcbF-11 $20 Z4

MPW100 AcbF-11 MPW100 $20 Z4

For use withAuxiliary contacts

catalog Number ListPrice

MultiplierSymbolNo Nc

MPW16MPW25MPW65

1)

1 1 AcbS-11

$22 Z42 - AcbS-20

- 2 AcbS-02

MPW100

1 1 AcbS-11 MPW100

$222 Z42 - AcbS-20 MPW100

- 2 AcbS-02 MPW100

Front Mounting Auxiliary Contact Block - ACBF

Left side Auxiliary Contact Block - ACBS

Note: 1 The following accessories can be assembled at the same time: 1 ACBF + 1 URMP/SRMP + 1 TSB-22 or 1 ACBS + 1 URMP/SRMP + 1 TSB-22 2 Unit list price. Product sold in multiples of 2 units

Controls

Manual Motor Protectors - Accessories

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-167

MPW

SER

IES

Controls

Manual Motor Protectors - Accessories

For use with description catalog Number List Price

MultiplierSymbol

MPW25MPW65

1)

-Equipped with 2 auxiliary contacts (1NO + 1NC) for overload trip signalling and 2 other auxiliary contacts (1NO + 1NC) for short-circuit trip signalling.

- To reset the MPW after a short-circuit, the blue flag must be manually reset after the cause of the failure has been solved.

- Left side auxiliary contacts can be assembled together with the trip signalling block.

- Left side assembly only

TSb-22 $38 Z4

MPW100

- Equipped with 2 auxiliary contacts (1NO + 1NC) for short-circuit trip signalling.

- Left side assembly only

TSb Sc-11 MPW100 $382 Z4

Trip Signalling Block - TSB-22

Undervoltage Release - URMP

For use with Voltage catalog Number List Price

MultiplierSymbol

MPW16MPW25MPW65

1)

208V 60Hz24V 50/60Hz400-415V 50Hz / 480V 60Hz110V 50Hz / 120V 60Hz240V 60Hz

uRMP V23uRMP d02uRMP V47uRMP V18uRMP V30

$56 Z4

MPW100

Note: - Operating voltage > 0,85 x Ue- Non operating voltage 0,35...0,7 x Ue

110V 50Hz / 120V 60Hz220-230V 50Hz / 240V 60Hz380-400V 50Hz / 460V 60Hz

uRMP V18 MPW100uRMP V33 MPW100uRMP V43 MPW100

$56 Z4

Note: 1 The following accessories can be assembled at the same time: 1 ACBF + 1 URMP/SRMP + 1 TSB-22 or 1 ACBS + 1 URMP/SRMP + 1 TSB-22 2 Unit list price. Product sold in multiples of 2 units

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-168

MPW

SERIES

Shunt Release - SRMP

Controls

Manual Motor Protectors - Accessories

Link modules for manual motor protector assembly + contactors – ECCMP

For use with Voltage catalog Number List Price

MultiplierSymbol

MPW16MPW25MPW65

1)

20-24V 50/60Hz100-127V 50/60Hz200-240V 50/60Hz

SRMP d51SRMP d59SRMP d65 $56 Z4

MPW100 Note: - Operating voltage > 0.7 x Ue 110V 50Hz / 120V 60Hz220-230V 50Hz / 240-260V 60Hz

SRMP V18 MPW100SRMP V33 MPW100 $56 Z4

For use with description contactorscatalog Number

List Price

MultiplierSymbol

MPW16- For direct connection (electrical and mechanical) of motor circuit

breakers to contactors.Note:

- Not applicable to CWM contactors with DC coils.

CWC07…16CWC025

EccMP-c016EccMP-c025

$20 Z4

MPW25CWC07…16CWM9…25CWM32...40

EccMP-c0EccMP-25EccMP-32

Note: 1) The following accessories can be coupled at the same time: 1 ACBF + 1 URMP/SRMP + 1 TSB or 1 ACBS + 1 URMP/SRMP + 1 TSB

For use with Illustrative picture description Terminals handle colorcatalog Number

ListPrice

MultiplierSymbol

MPW16

- Degree of protection: IP66- Two cable entry knockouts, top and bottom - Allows installing: MPW16 + ACBF11/PL lamps + ACBS

With neutral and ground terminals

- PE66GN $45

Z4

MPW25

- Degree of protection: IP55- Allows installing: MPW25 + ACBF11/PL lamps + ACBS - Two cable entry knockouts, top and bottom - Handle can be locked with up to 3 padlocks at OFF position.

With neutral and ground terminals

Black PE55GN $45

Red with yellow background

PE55GNE $45 Z4

Standard IEC Enclosure - PE

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-169

MPW

SER

IES

Through-the-door Rotary Handle - RMMP and MRX

Controls

Manual Motor Protectors - Accessories

For use with Illustrative picture description handle color

catalog Number

PriceList

MultiplierSymbol

MPW25- Degree of protection IP55/NEMA1;

- Shows MPW position “I”(ON) or

“O”(OFF);

- Panel door can only be opened in OFF position;

- Adjustable shaft length. There are 2 standard shaft sizes: 130-

155mm (Model 130) and 330-355mm (Model 330). To

assemble the handle on the MPW the shaft must have a length

of at least 80mm;

- Up to 3 padlocks can be used in the OFF position. This blocks

MPW operation and panel door opening;

- Handle can be mounted on panels with thickness of 1 to 5mm;

- Handle can be assembled even with MPW turned in 90º position

Gray/Black

RMMP-130 $60

Z4

RMMP-330 $70

Red/Yellow

RMMP-130E $60

RMMP-330E $70

MPW65

Gray/Black

RMMP65-130 $60

RMMP65-330 $70

Red/Yellow

RMMP65-130E $60

RMMP65-330E $70

MPW100

- Degree of protection NEMA1;

- Shows MPW position “I”(ON) or “O”(OFF);

- Panel door can be opened at ON position (thermometry) by

defeating mechanism;

- Adjustable shaft length. There are 2 standard shaft sizes:

115mm (Model 115) and 315mm (Model 315). To assemble the

handle to the MPW, the shaft must have a min. length of at least

80mm;

- Up to 3 padlocks can be used in the OFF position. This blocks

the MPW operation and opens panel door.

Gray/Black

MR MPW100-115 $80

Gray/Black

MR MPW100-315 $90

MPW25 - Panel door can be opened in ON position (thermometry) by

defeating mechanism.

- Degree of protection: IP65/Nema 4X

- Shows MPW position “I”(ON) or “O”(OFF)

- Adjustable shaft length. There are 2 standard shaft sizes: 130-

155mm (Model 130) and 330-355mm (Model 330). To

assemble the handle ON the MPW the shaft must have a length

of at least 80mm

- Up to 3 padlocks can be used in the OFF position. This blocks

MPW operation and opens panel door. Handle can be mounted

on panels with thickness of 1 to 5mm

Gray/Black

MRX-130 $105MRX-330 $115

Red/Yellow

MRX-130E $105MRX-330E $115

MPW65

Gray/Black

MRX65-130 $120MRX65-330 $130

Red/Yellow

MRX65-130E $120MRX65-330E $130

MPW100

Gray/Black MRX100-130-E $130

Red/Yellow MRX100-130-E $130

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-170

MPW

SERIES

Controls

Manual Motor Protectors - Accessories

Large IEC Enclosure - LPE55

Manual Motor Protector mounting adapter - MA

For use with description contactors catalogNumber

ListPrice

MultiplierSymbol

MPW25

Used for direct on line starters

45mm width

CWC07...25CWM9…CWM25 MA45doL $40

Z4MPW25

Used for rever-sing starters

90mm width

2 x CWC07...252x CWM9...CWM25 MA90RVS $50

MPW25

Used for star-delta motor

starters

90mm width

2 x CWC07...252x CWM9…CWM25 MA90SdS $50

For use with description Terminals handle color

catalogNumber

ListPrice

MultiplierSymbol

MPW25

- Degree of protection: IP55- For use with MPW25 + URMP/ SRMP + ACBF11 + ACBS + PL lamps- Two cable entry knockouts. top and bottom - Handle can be locked with up to 3 padlocks at OFF position.

With neutral and ground terminals

Black LPE55GN

$55 Z4

Red with yellow

backgroundLPE55GN-E

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-171

MPW

SER

IES

Controls

Manual Motor Protectors - Accessories

Three-phase feeder terminal – FTBBS and LST25

Three-phase feeder terminals for MPW without side auxiliary contacts – BBS45

For use with description catalogNumber

List Price

MultiplierSymbol

MPW16MPW25

- For feeding the feeder terminals;- Rated insulation voltage: 690VAC;- Ie: 63A;- Terminals: 6-25mm2 rigid wire and 6-16mm2 flexible wire with terminal.

FTbbS $35 Z4

MPW25

- Block module for “ Type E“ Combination motor Controller” in accordance with UL (LST25+MPW+TSB-22);- Rated insulation voltage: 690VAC; - Ie: 63A.- Terminals: 8-20AWG.

LST25 $30 Z4

For use with description Numbers of MPW

catalogNumber

List Price

MultiplierSymbol

MPW16MPW25

- For parallel blocking of side-by-side mounted MPW, without side auxiliary contacts; - - Enables the use of frontal auxiliary contact block ACBF-11; - Ue: 690VAC;- Ie: 63A.

2 bbS45-2 $32

Z4 3 bbS45-3 $35

4 bbS45-4 $45

5 bbS45-5 $60

Insulators - IB

For use with description catalog Number List Price

MultiplierSymbol

MPW100Insulators for increasing cree-page distance and clearances according to UL requirements.

Ib MPW100 $30 Z4

Three-phase feeder terminals for MPW with side auxiliary contacts – BBS54

For use with descriptionNumbers of MPW

catalogNumber

List Price

MultiplierSymbol

MPW16/MPW25

- For parallel blocking of side-by-side mounted MPW; - Enables the use of frontal auxiliary contact block ACBF-11 and side auxiliary contact block ACBS;- Ue: 690VAC;- Ie: 63A.

2 bbS54-2 $32

Z43 bbS54-3 $35

4 bbS54-4 $45

5 bbS54-5 $60

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-172

MPW

SERIES

Controls

Manual Motor Protectors - Accessories

Shround for unused terminals – CSD

Scale Cover - SCMP

Push-in-lugs - PLMP

For use with descriptioncatalogNumber

List Price

MultiplierSymbol

bbS45 and bbS54

Protection against direct contact on unused terminals on energized BBS45 and BBS54 three-phase feeder terminals.

cSd $101 Z4

For use with descriptioncatalogNumber

List Price

MultiplierSymbol

MPW16MPW25MPW65

Protects the current adjustment dial against direct contact while enabling the set current to be viewed.

ScMP $5 Z4

For use with descriptioncatalogNumber

List Price

MultiplierSymbol

MPW16MPW25MPW65

For direct assembly of motor protective circuit breaker onto any surface using screws.

PLMP $0.50 Z4

Current Limiter - CLT25

For use with descriptioncatalogNumber

List Price

MultiplierSymbol

MPW25

- For protecting electrical circuits where extra high short-circuit breaking capacity is required:

100kA @ 480VAC;

Note: This accessory must be used together with a MPW motor protector.

cLT25 $100 Z4

Notes: 1 Unit list price. Product sold in multiples of 5 units.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-173

MPW

SER

IES

Controls

Manual Motor Protectors - MPW16 Technical Data

TYPE MPW16-3-c016

MPW16-3-c025

MPW16-3-d004

MPW16-3-c063

MPW16-3-u001

MPW16-3-d016

MPW16-3-d025

Standards Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Current Setting Range [A] 0.10 - 0.16 0.16 - 0.25 0.25 - 0.40 0.40 - 0.63 0.63 - 1.0 1.0 - 1.6 1.6 - 2.5Rated Thermal Current Ith [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5Rated Insulation Voltage UiAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Operating Voltage UeAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Impulse Voltage UimpAcc. IEC60947-1 [kV] 6Rated Operating Frequency [Hz] 50/60Overvoltage Category IIIPollution Degree 3Utilization CategoryIEC 60947-2 (Motor Protector) AIEC 60947-4-1 (Motor Starter) AC-3LifespanMechanical [ops.] 100,000Electrical (Ie max.) [ops.] 100,000Switching Rate (motor starts) AC-3 [ops/hr] 15Ambient TemperatureStorage [oC (oF)] -50 to +80 (-58 to +176)Operating [oC (oF)] -20 to +60 (-4 to +140)Ambient Temperature Compensation [oC (oF)] -20 to +60 (-4 to +140)Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30AltitudeUp to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page B-194Degree of protection IP20Resistance to ShockAcc. IEC 60068-2-27 [g] 15Resistance to Vibration IEC 68-2Protection against direct contactAcc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proofPhase Failure Sensitivity Protection YesOverload Protection Characteristics x Iu [A] 0.6 - 1Magnetic Release x Iu [A] 13Overload Trip Class 10Total Power Loss PvAt rated load operating temperature [W] 6 6 6 6 6 6 6Weight [kg] 0.30

[lb] 0.70Type of Terminal Flat TypeScrew Driver Philips #2Terminal CapacitySolid - Stranded [mm2] [AWG] Refer to table on page B-193Tightening Torque N.m) lb.in 1.2 - 1.7 (11 - 16)Mounting Position Any Position

General Ratings

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-174

MPW

SERIES

Controls

Manual Motor Protectors - MPW16 Technical DataGeneral Ratings

TYPE MPW16-3-u004

MPW16-3-d063

MPW16-3-u010

MPW16-3-u016

Standards Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA

C.22.2/14; VDE 0660/102

Current Setting Range [A] 2.5 - 4.0 4.0 - 6.3 6.3 - 10 10 - 16

Rated Thermal Current Ith [A] 4.0 6.3 10 16

Rated Insulation Voltage Ui

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Operating Voltage Ue

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Impulse Voltage Uimp

Acc. IEC60947-1 [kV] 6

Rated Operating Frequency [Hz] 50/60

Overvoltage Category III

Pollution Degree 3

Utilization Category

IEC 60947-2 (Motor Protector) A

IEC 60947-4-1 (Motor Starter) AC-3

Lifespan

Mechanical [ops.] 100,000

Electrical (Ie max.) [ops.] 100,000

Switching Rate (motor starts) AC-3 [ops/hr] 15

Ambient Temperature

Storage [oC (oF)] -50 to +80 (-58 to +176)

Operating [oC (oF)] -20 to +60 (-4 to +140)

Ambient Temperature Compensation [oC (oF)] -20 to +60 (-4 to +140)

Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30

Altitude

Up to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page B-194

Degree of protection IP20

Resistance to Shock

Acc. IEC 60068-2-27 [g] 15

Resistance to Vibration IEC 68-2

Protection against direct contact

Acc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proof

Phase Failure Sensitivity Protection YesOverload Protection Characteristics x Iu [A] 0.6 - 1Magnetic Release x Iu [A] 12Overload Trip Class 10Total Power Loss PvAt rated load operating temperature [W] 6 6 6 6Weight [kg] 0.3

[lb] 0.7Type of Terminal Flat TypeScrew Driver Philips #2Terminal CapacitySolid - Stranded [mm2] [AWG] Refer to table on page B-193Tightening Torque N.m) lb.in 1.2 - 1.7 (11 - 16)Mounting Position Any Position

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-175

MPW

SER

IES

Power Contact Ratings

Controls Manual Motor Protectors - MPW16 Technical Data

TYPEuL/cSA dATA

MPW16-3-c016

MPW16-3-c025

MPW16-3-c040

MPW16-3-c063

MPW16-3-c100

MPW16-3-c160

MPW16-3-c250

Rated Operational Current Ie

[A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5

Magnetic Release Current

[A] 2 3 5 8 13 21 33

Max. Short Circuit Current

480V [kA] 50

600V [kA] 10

Motor Load, 1-phase

115V [HP] - - - - - - -

230V [HP] - - - - - 1/10 1/6

Motor Load, 3-phase

200V [HP] - - - - - 1/4 1/2

230V [HP] - - - - - 1/3 1/2

460V [HP] - - - - 1/2 3/4 1 1/2

575V [HP] - - - 1/4 1/2 1 1 1/2

Max. Rated Current of Protection Devicefor Group Installation

Fuse or MCCB

[A] 125 125 125 125 125 125 125

IEc dATA

Rated Operational Current Ie

[A] 0.16 0.25 0.4 0.63 1 1.6 2.5

Magnetic Release Current

[A] 2 3 5 8 13 21 33

Back-Up Fuses

gL/gG 220/240V [A] - - - - - - -

380/400V [A] - - - - - - -

415/440V [A] - - - - - - -

500V [A] - - - - - - -

660/690V [A] - - - - - - 25

Ultimate Short Circuit Breaking Capacity

Icu 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 100 100 100 100 100 100 100

415/440V [kA] 100 100 100 100 100 100 100

500V [kA] 100 100 100 100 100 100 100

660/690V [kA] 100 100 100 100 100 100 8

Rated Service Short Circuit Breaking Capacity

Ics 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 100 100 100 100 100 100 100

415/440V [kA] 100 100 100 100 100 100 100

500V [kA] 100 100 100 100 100 100 100

660/690V [kA] 100 100 100 100 100 100 8

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-176

MPW

SERIES

Power Contact Ratings

Controls Manual Motor Protectors - MPW16 Technical Data

TYPE MPW16-3-u004 MPW16-3-d063 MPW16-3-u010 MPW16-3-u016

uL/cSA dATA

Rated Operational Current Ie [A] 4.0 6.3 10 16

Magnetic Release Current [A] 52 82 130 208

Max. Short Circuit Current

480V [kA] 50 50 50 30

600V [kA] 10 10 5 5

Motor Load, 1-phase

115V [HP] 1/8 1/4 1/2 1

230V [HP] 1/3 3/4 1 1/2 3

Motor Load, 3-phase

200V [HP] 3/4 1 1/2 3 5

230V [HP] 1 1 1/2 3 5

460V [HP] 2 5 7 1/2 10

575V [HP] 3 5 10 15

Max. Rated Current of Protection Device for Group Installation

Fuse or MCCB

[A] 125 125 125 160

IEc dATA

Rated Operational Current Ie [A] 4 6.3 10 16

Magnetic Release Current [A] 52 82 130 208

Back-Up Fuses

gL/gG 220/240V [A] - - - -

380/400V [A] - - 100 100

415/440V [A] - - 80 80

500V [A] - - 63 80

660/690V [A] 35 50 50 63

Ultimate Short Circuit Breaking Capacity

Icu 220/240V [kA] 100 100 100 100

380/400V [kA] 100 100 50 10

415/440V [kA] 100 100 50 10

500V [kA] 100 100 10 10

660/690V [kA] 8 8 5 4

Rated Service Short Circuit Breaking Capacity

Ics 220/240V [kA] 100 100 100 100

380/400V [kA] 100 100 10 10

415/440V [kA] 100 100 10 10

500V [kA] 100 100 10 10

660/690V [kA] 8 8 5 3

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-177

MPW

SER

IES

General Ratings

Controls Manual Motor Protectors - MPW25 Technical Data

TYPE MPW25-3-c016

MPW25-3-c025

MPW25-3-d004

MPW25-3-c063

MPW25-3-u001

MPW25-3-d016

MPW25-3-d025

Standards Devices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1,

Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102Current Setting Range [A] 0.10 - 0.16 0.16 - 0.25 0.25 - 0.40 0.40 - 0.63 0.63 - 1.0 1.0 - 1.6 1.6 - 2.5Rated Thermal Current Ith [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5Rated Insulation Voltage UiAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Operating Voltage UeAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Impulse Voltage UimpAcc. IEC60947-1 [kV] 6Rated Operating Frequency [Hz] 50/60Overvoltage Category IIIPollution Degree 3Utilization CategoryIEC 60947-2 (Motor Protector) AIEC 60947-4-1 (Motor Starter) AC-3LifespanMechanical [ops.] 100,000Electrical (Ie max.) [ops.] 100,000Switching Rate (motor starts) AC-3 [ops/hr] 15Ambient TemperatureStorage [oC (oF)] -50 to +80 (-58 to +176)Operating [oC (oF)] -20 to +60 (-4 to +140)Ambient Temperature Compensation [oC (oF)] -20 to +60 (-4 to +140)Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30AltitudeUp to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page B-194Degree of protection IP20Resistance to ShockAcc. IEC 60068-2-27 [g] 15Resistance to Vibration IEC 68-2Protection against direct contactAcc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proofPhase Failure Sensitivity Protection YesOverload Protection Characteristics x Iu [A] 0.6 - 1Magnetic Release x Iu [A] 13Overload Trip Class 10Total Power Loss PvAt rated load operating temperature [W] 6 6 6 6 6 6 6Weight [kg] 0.32

[lb] 0.71Type of Terminal Flat TypeScrew Driver Philips #2Terminal Capacity

Solid - Stranded [mm2] [AWG] Refer to table on page B-193

Tightening Torque N.m) lb.in 1.2 - 1.7 (11 - 16)

Mounting Position Any Position

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-178

MPW

SERIES

General Ratings

Controls Manual Motor Protectors - MPW25 Technical Data

TYPEMPW25-3-u004

MPW25-3-d063

MPW25-3-u010

MPW25-3-u016

MPW25-3-u020

MPW25-3-u025

MPW25-3-u032

StandardsDevices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN

60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Current Setting Range [A] 2.5 - 4.0 4.0 - 6.3 6.3 - 10 10 - 16 16 - 20 20 - 25 25 - 32Rated Thermal Current Ith [A] 4.0 6.3 10 16 20 25 32Rated Insulation Voltage UiAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Operating Voltage UeAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Impulse Voltage UimpAcc. IEC60947-1 [kV] 6Rated Operating Frequency [Hz] 50/60Overvoltage Category IIIPollution Degree 3Utilization CategoryIEC 60947-2 (Motor Protector) AIEC 60947-4-1 (Motor Starter) AC-3LifespanMechanical [ops.] 100,000Electrical (Ie max.) [ops.] 100,000Switching Rate (motor starts) AC-3 [ops/hr] 15Ambient Temperature

Storage[oC (oF)]

-50 to +80 (-58 to +176)

Operating[oC (oF)]

-20 to +60 (-4 to +140)

Ambient Temperature Compensation[oC (oF)]

-20 to +60 (-4 to +140)

Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30AltitudeUp to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page B-194Degree of protection IP20Resistance to Shock Acc. IEC 60068-2-27 [g] 15Resistance to Vibration IEC 68-2Protection against direct contactAcc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proofPhase Failure Sensitivity Protection YesOverload Protection Characteristics x Iu [A] 0.6 - 1Magnetic Release x Iu [A] 13Overload Trip Class 10Total Power Loss PvAt rated load operating temperature [W] 6 6 6 6 8 8 8Weight [kg] 0.32

[lb] 0.71Type of Terminal Flat TypeScrew Driver Philips #2Terminal CapacitySolid - Stranded [mm2] [AWG] Refer to table on page B-193

Tightening Torque N.m) lb.in 1.2 - 1.7 (11 - 16)

Mounting Position Any Position

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-179

MPW

SER

IES

Power Contact Ratings

Controls Manual Motor Protectors - MPW25 Technical Data

TYPE MPW25-3-c016

MPW25-3-c025

MPW25-3-c040

MPW25-3-c063

MPW25-3-u001

MPW25-3-d016

MPW25-3-d025

uL/cSA dATA

Rated Operational Current Ie [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5

Magnetic Release Current [A] 2 3 5 8 13 21 33

Max. Short Circuit Current

without CLT25

480V [kA] 50

600V [kA] 25

with CLT25

480V [kA] 100

600V [kA] 50

Motor Load, 1-phase

115V [HP] - - - - - - -

230V [HP] - - - - - 1/10 1/6

Motor Load, 3-phase

200V [HP] - - - - - 1/4 1/2

230V [HP] - - - - - 1/3 1/2

460V [HP] - - - - 1/2 3/4 1 1/2

575V [HP] - - - 1/4 1/2 1 1 1/2

Max. Rated Current of Protection Device for Group Installation

Fuse or MCCB [A] 125 125 125 125 125 125 125

IEc dATA

Rated Operational Current Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5

Magnetic Release Current [A] 2 3 5 8 13 21 33

Back-Up Fuses

gL/gG 220/240V [A] - - - - - - -

380/400V [A] - - - - - - -

415/440V [A] - - - - - - -

500V [A] - - - - - - -

660/690V [A] - - - - - - 25

Ultimate Short Circuit Breaking Capacity

Icu 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 100 100 100 100 100 100 100

415/440V [kA] 100 100 100 100 100 100 100

500V [kA] 100 100 100 100 100 100 100

660/690V [kA] 100 100 100 100 100 100 8

Rated Service Short Circuit Breaking Capacity

Ics 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 100 100 100 100 100 100 100

415/440V [kA] 100 100 100 100 100 100 100

500V [kA] 100 100 100 100 100 100 100

660/690V [kA] 100 100 100 100 100 100 8

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-180

MPW

SERIES

Power Contact Ratings

Controls Manual Motor Protectors - MPW25 Technical Data

TYPE MPW25-3-u004

MPW25-3-d063

MPW25-3-u010

MPW25-3-u016

MPW25-3-u020

MPW25-3-u025

MPW25-3-u032

uL/cSA dATA

Rated Operational Current Ie [A] 4.0 6.3 10 16 20 25 32

Magnetic Release Current [A] 52 82 130 208 260 325 416

Max. Short Circuit Current

without CLT25

480V [kA] 50 42

600V [kA] 25 25

with CLT25

480V [kA] 100

600V [kA] 50

Motor Load, 1-phase

115V [HP] 1/8 1/4 1/2 1 1 1/2 2 -

230V [HP] 1/3 3/4 1 1/2 3 3 3 5

Motor Load, 3-phase

200V [HP] 3/4 1 1/2 3 5 5 7 1/2 10

230V [HP] 1 1 1/2 3 5 7 1/2 7 1/2 10

460V [HP] 2 5 7 1/2 10 15 15 20

575V [HP] 3 5 10 15 20 20 25

Max. Rated Current of Protection Device for Group Installation

Fuse or MCCB

[A] 125 125 125 160 250 250 300

IEc dATA

Rated Operational Current Ie [A] 4 6.3 10 16 20 25 32

Magnetic Release Current [A] 52 82 130 208 260 325 416

Back-Up Fuses

gL/gG 220/240V [A] - - - - - - -

380/400V [A] - - - 100 125 125 125

415/440V [A] - - 80 80 80 100 100

500V [A] - - 63 80 80 80 80

660/690V [A] 35 50 50 63 63 63 63

Ultimate Short Circuit Breaking Capacity

Icu 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 100 100 100 50 50 50 50

415/440V [kA] 100 100 50 50 50 50 25

500V [kA] 100 100 42 10 10 10 10

660/690V [kA] 8 8 8 5 5 5 5

Rated Service Short Circuit Breaking Capacity

Ics 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 100 100 100 25 25 25 25

415/440V [kA] 100 100 25 15 15 15 15

500V [kA] 100 100 21 8 8 8 8

660/690V [kA] 8 8 8 5 5 5 5

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-181

MPW

SER

IES

General Rating

Controls Manual Motor Protectors - MPW65 Technical Data

TYPE MPW65-3-u016

MPW65-3-u020

MPW65-3-u025

MPW65-3-u032

MPW65-3-u040

MPW65-3-u050

MPW65-3-u065

StandardsDevices according to International Standards IEC 60947-1 / 60947-4-1, European Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Current Setting Range [A] 10 - 16 16 - 20 20 - 25 25 - 32 32 - 40 40 - 50 50 - 65

Rated Thermal Current Ith [A] 16 20 25.00 32 40.0 50 65

Rated Insulation Voltage Ui

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Operating Voltage Ue

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Impulse Voltage Uimp

Acc. IEC60947-1 [kV] 6

Rated Operating Frequency [Hz] 50/60

Overvoltage Category III

Pollution Degree 3

Utilization Category

IEC 60947-2 (Motor Protector) A

IEC 60947-4-1 (Motor Starter) AC-3

Lifespan

Mechanical [ops.] 50,000

Electrical (Ie max.) [ops.] 25,000

Switching Rate (motor starts) AC-3 [ops/hr] 15

Ambient Temperature

Storage [oC (oF)] -50 to +80 (-58 to +176)

Operating [oC (oF)] -20 to +60 (-4 to +140)

Ambient Temperature Compensation [oC (oF)] -20 to +60 (-4 to +140)

Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30

Altitude

Up to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page B-194

Degree of protection IP20

Resistance to Shock

Acc. IEC 60068-2-27 [g] 15

Resistance to Vibration IEC 68-2

Protection against direct contact

Acc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proof

Phase Failure Sensitivity Protection Yes

Overload Protection Characteristics x Iu [A] 0.6 - 1

Magnetic Release x Iu [A] 13

Overload Trip Class 10

Total Power Loss Pv

At rated load operating temperature [W] 8 8 8 8 8 8 8

Weight [kg] 0.60

[lb] 1.42

Type of Terminal Flat Type

Screw Driver Allen #4

Terminal Capacity

Solid - Stranded [mm2] [AWG] Refer to table on page B-193

Tightening Torque N.m) lb.in 1.2 - 1.7 (11 - 16)

Mounting Position Any Position

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-182

MPW

SERIES

Power Contact Ratings

Controls Manual Motor Protectors - MPW65 Technical Data

TYPE MPW65-3-u016

MPW65-3-u020

MPW65-3-u025

MPW65-3-u032

MPW65-3-u040

MPW65-3-u050

MPW65-3-u065

uL/cSA dATA

Rated Operational Current Ie [A] 16 20 25 32 40 50 65

Magnetic Release Current [A] 208 260 325 416 520 650 845

Max. Short Circuit Current

480V [kA] 50 35

600V [kA] 30 10

Motor Load, 1-phase

115V [HP] 3 - 5

230V [HP] 71/2 10 10

Motor Load, 3-phase

200V [HP] - 15 20

230V [HP] 15 15 20

460V [HP] 25 30 50

575V [HP] 30 40 60

Max. Rated Current of Protection Device for Group Installation

Fuse or MCCB

[A]

IEc dATA

Rated Operational Current Ie [A] 16 20 25 32 40 50 65

Magnetic Release Current [A] 208 260 325 416 520 650 845

Back-Up Fuses

gL/gG 220/240V [A] - - - - - - -

380/400V [A] 100 125 125 125 160 160 160

415/440V [A] 80 80 80 100 125 125 125

500V [A] 80 80 100 80 100 100 100

660/690V [A] 63 63 63 63 63 80 80

Ultimate Short Circuit Breaking Capacity

Icu 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 50 50 50 50 50 50 50

415/440V [kA] 50 50 50 50 50 50 50

500V [kA] 15 15 15 15 15 15 15

660/690V [kA] 8 8 8 5 5 5 5

Rated Service Short Circuit Breaking Capacity

Ics 220/240V [kA] 100 100 100 100 100 100 100

380/400V [kA] 50 50 50 50 50 50 50

415/440V [kA] 50 50 50 50 50 50 50

500V [kA] 15 15 15 15 10 10 10

660/690V [kA] 8 8 8 5 5 5 5

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-183

MPW

SER

IES

General Contact Ratings

Controls Manual Motor Protectors - MPW100 Technical Data

TYPE MPW100-3-u075 MPW100-3-u090 MPW100-3-u100Standards Devices according to International Standards IEC 60947-1 / 60947-4-1, European

Standards EN 60947-1 / 60947-4-1, Underwriters Laboratories - UL 508; CSA C.22.2/14; VDE 0660/102

Current Setting Range [A] 55 - 75 70 - 90 80 - 100Rated Thermal Current Ith [A] 75 90 100.00Rated Insulation Voltage UiAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Operating Voltage UeAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Impulse Voltage UimpAcc. IEC60947-1 [kV] 6Rated Operating Frequency [Hz] 50/60Overvoltage Category IIIPollution Degree 3Utilization CategoryIEC 60947-2 (Motor Protector) AIEC 60947-4-1 (Motor Starter) AC-3LifespanMechanical [ops.] 50,000Electrical (Ie max.) [ops.] 25,000Switching Rate (motor starts) AC-3 [ops/hr] 15Ambient TemperatureStorage [oC (oF)] -50 to +80 (-58 to +176)Operating [oC (oF)] -20 to +60 (-4 to +140)Ambient Temperature Compensation [oC (oF)] -20 to +60 (-4 to +140)Climatic Proofing IEC 60068-2-3 / IEC 60068-2-30AltitudeUp to 2,000m (6,600ft) Nominal Values (for higher altitudes refer to page B-194Degree of protection IP20Resistance to ShockAcc. IEC 60068-2-27 [g] 15Resistance to Vibration IEC 68-2Protection against direct contactAcc. IEC 536; DIN VDE 0106 Part 100 Finger and back of hand proofPhase Failure Sensitivity Protection YesOverload Protection Characteristics x Iu [A] 0.6 - 1Magnetic Release x Iu [A] 13Overload Trip Class 10Total Power Loss PvAt rated load operating temperature [W] 10 10 10Weight [kg] 1.20

[lb] 3.00Type of Terminal Flat TypeScrew Driver Allen #4Terminal CapacitySolid [mm2] Refer to table on page B-193Stranded [mm2]Solid or Stranded [AWG]Tightening Torque [N.m (lb.

in)]4.0 - 4.6 (35 - 55)

Mounting Position Any Position

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-184

MPW

SERIES

Power Contact Ratings

Controls Manual Motor Protectors - MPW100 Technical Data

TYPE MPW100-3-u075

MPW100-3-u090

MPW100-3-u100

uL/cSA dATA

Rated Operational Current Ie [A] 75 90 100

Magnetic Release Current [A] 975 1170 1300

Max. Short Circuit Current

480V [kA] 50

600V [kA] 10

Motor Load, 1-phase

115V [HP] 5 71/2 10

230V [HP] 15 20 20

Motor Load, 3-phase

200V [HP] 20 25 30

230V [HP] 25 30 30

460V [HP] 50 60 75

575V [HP] 60 75 100

Max. Rated Current of Protection Device for Group Installation

Fuse or MCCB

[A]

IEc dATA

Rated Operational Current Ie [A] 75 90 100

Magnetic Release Current [A] 975 1170 1300

Back-Up Fuses

gL/gG 220/240V [A] - - -

380/400V [A] - - -

415/440V [A] 200 200 200

500V [A] 160 160 160

660/690V [A] 125 160 160

Ultimate Short Circuit Breaking Capacity

Icu 220/240V [kA] 100 100 100

380/400V [kA] 75 75 75

415/440V [kA] 50 50 50

500V [kA] 12 12 12

660/690V [kA] 6 6 6

Rated Service Short Circuit Breaking Capacity

Ics 220/240V [kA] 100 100 100

380/400V [kA] 50 50 50

415/440V [kA] 38 38 38

500V [kA] 9 9 9

660/690V [kA] 6 6 6

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-185

MPW

SER

IES

Auxiliary Contact Block Ratings

Controls Manual Motor Protectors - MPW Technical Data

TYPE AcbF-11

AcbF-11 MPW100

AcbS-11

AcbS-20

AcbS-02

AcbS-11 MPW100

AcbS-20 MPW100

AcbS-02 MPW100

Rated Insulation Voltage Ui

Acc. IEC; VDE 0660 [V] 300 690

Acc. UL; CSA [V] 240 600

Rated Operating Voltage Ue

Acc. IEC; VDE 0660 [V] 250 690

Acc. UL; CSA [V] 240 600

Rated Impulse Voltage Uimp

Acc. IEC60947-1 [kV] 4 6

Overvoltage Category III

Pollution Degree 3

Life Span

Mechanical [ops.] 100,000

Electrical (Ie max.) [ops.] 100,000

Rated Thermal Current Ith [A] 2.5 10

Rated Operating Current Ie

Acc. IEC 60947-5-1 / AC-15 24V [A] 2 6

110-127V [A] 0.5 6

220-240V [A] 0.5 6

380-400V [A] - 3

415-450V [A] - 1

500V [A] - 1

660-690V [A] - 1

Acc. UL; CSA C300 A600

Rated Operating Current Ie

Acc. IEC 60947-5-1 / DC-13 24V [A] 1 2

48V [A] 0.3 0.8

60V [A] 0.15 0.5

110V [A] - 0.5

220V [A] - 0.250.25

440V [A] - 0.10.1

Acc. UL; CSA R300 Q600

Short Circuit rating without welding

gL/gG [A] 10

MCB [A] 6

Type of Terminal Screw Driver

Philips #2

Terminal Capacity

Solid or Stranded [mm2] 1 or 2 x (0.5 to 2.5)

Solid or Stranded [AWG] 1 or 2 x (18 to 14)

Tightening Torque [N.m (lb.in)] 1.0 - 1.25 (8.85 - 11.06)

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-186

MPW

SERIES

Trip Signalling Block

Controls Manual Motor Protectors - MPW Technical Data

TYPE TSb-22 TSb-11 MPW100

Rated Insulation Voltage Ui

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Operating Voltage Ue

Acc. IEC; VDE 0660 [V] 690

Acc. UL; CSA [V] 600

Rated Impulse Voltage Uimp

Acc. IEC60947-1 [kV] 6

Overvoltage Category III

Pollution Degree 3

Life Span

Mechanical [ops.] 100000

Electrical (Ie max.) [ops.] 100000

Rated Thermal Current Ith [A] 10

Rated Operating Current Ie

Acc. IEC 60947-5-1 / AC-15 24V [A] 6

110-127V [A] 6

220-240V [A] 6

380-400V [A] 3

415-450V [A] 3

500V [A] 2

660-690V [A] 1

Acc. UL; CSA A600

Rated Operating Current Ie

Acc. IEC 60947-5-1 / DC-13 24V [A] 2

48V [A] 0.5

60V [A] 0.5

110V [A] 0.5

220V [A] 0.25

440V [A] 0.1

Acc. UL; CSA Q600

Short Circuit rating without welding

gL/gG [A] 6

MCB [A] 6

Type of Terminal Screw Driver Philips #2

Terminal Capacity

Solid or Stranded [mm2] 1 or 2 x (0.5 to 2.5)

Solid or Stranded AWG 1 or 2 x (18 to 14)

Tightening Torque [N.m (lb.in)] 1.0 - 1.25 8.85 - 11.06)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-187

MPW

SER

IES

Shunt Release Block

Controls Manual Motor Protectors - MPW Technical Data

TYPE SRMP SRMP MPW100Rated Insulation Voltage UiAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Operating Voltage UeAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Impulse Voltage UimpAcc. IEC60947-1 [kV] 6Overvoltage Category IIIPollution Degree 3Life SpanMechanical [ops.] 100000Electrical (Ie max.) [ops.] 100000Actuating Voltage x Us [V] 0.7 - 1.1Power ConsumptionPull-In [VA (W)] 20.2 (13) 8.5 (6)Hold [VA (W)] 7.2 (2.4) 3 (1.2)Maximum Opening Time [ms] 20Short Circuit Rating without WeldingFuse gL/gG [A] 10MCB [A] 6Type of Terminal Screw Driver Philips #2Terminal CapacitySolid or Stranded [mm2] 1 or 2 x (0.5 to 2.5)Solid or Stranded AWG 1 or 2 x (18 to 14)Tightening Torque [N.m (lb.in)] 1.0 - 1.25 (8.85 - 11.06)

TYPE uRMP uRMP MPW100Rated Insulation Voltage UiAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Operating Voltage UeAcc. IEC; VDE 0660 [V] 690Acc. UL; CSA [V] 600Rated Impulse Voltage UimpAcc. IEC60947-1 [kV] 6Overvoltage Category IIIPollution Degree 3Life SpanMechanical [ops.] 100000Electrical (Ie max.) [ops.] 100000Pick-Up Voltage x Us [V] 0.85 - 1.1Drop-Out Voltage x Us [V] 0.7 - 0.35Power ConsumptionPull-In [VA (W)] 20.2 (13) 8.5 (6)Hold [VA (W)] 7.2 (2.4) 3 (1.2)Maximum Opening Time [ms] 20Short Circuit Rating without WeldingFuse gL/gG [A] 10MCB [A] 6Type of Terminal Screw Driver Philips #2Terminal CapacitySolid or Stranded [mm2] 1 or 2 x (0.5 to 2.5)Solid or Stranded AWG 1 or 2 x (18 to 14)Tightening Torque [lb. in] 1.0 - 1.25 (8.85 - 11.06)

Under Voltage Release Block

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-188

MPW

SERIES

Time Current Characteristic MPW25 Class 10

Controls Manual Motor Protectors - Characteristics Curves

The tripping characteristic indicates the manual motor protector trip time in relation to the rated current.The curves show average tolerance range values for an ambient temperature of 20ºC (68ºF), starting in cold state. Thermal trip time when working in operating temperature is reduced to around 25% of the listed values. Under normal operating conditions, all 3 manual motor protector phases must be conducting.

MPW16/25/65

Characteristic I2t at 460V - MPW25

3-phase

2-phase

mill

isec

ond

seco

ndm

inut

e

X Adjusted current Ie

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-189

MPW

SER

IES

Notes: 1) Thermal Tripping current: Curve presented for an ambient temperature of 20ºC(68ºF) starting from cold state.

MPW100

Min

ute

Seco

nd

x Adjusted current Ie

Trip ≤ 5 ms

In(r) = 10,4...15,6 x In

Hour

Controls Manual Motor Protectors - Characteristics Curves

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-190

MPW

SERIES

Controls Manual Motor ProtectorsShort Circuit Interruption Capacity UL/CSA for MPW16, MPW25, MPW65, MPW100

Manual Motor controller high capacity

combination Motor controller (Type E/F) high capacity

combination Motor controller (Type E/F)

Extra high capacity

catalog Number

Setting overload Release

(A)

240VAc480VAc

Y/277VAc600VAc

Y/347VAc

Max. Fuse or Mccb

240VAc480VAc

Y/277VAc600VAc

Y/347VAc

Max. Fuse or Mccb

240VAc480VAc

Y/277VAc600VAc

Y/347VAc

Max. Fuse or Mccb

kA kA kA A kA kA kA A kA kA kA A

MPW

16

0.10 - 0.16 50 50 10 125 - - - - - - - -

0.16 - 0.25 50 50 10 125 - - - - - - - -

0.25 - 0.40 50 50 10 125 - - - - - - - -

0.40 - 0.63 50 50 10 125 - - - - - - - -

0.63 - 1.0 50 50 10 125 - - - - - - - -

1.0 - 1.6 50 50 10 125 - - - - - - - -

1.6 - 2.5 50 50 10 125 - - - - - - - -

2.5 - 4.0 50 50 10 125 - - - - - - - -

4.0 - 6.3 50 50 10 125 - - - - - - - -

6.3 - 10 50 50 5 125 - - - - - - - -

10 - 16 30 30 5 160 - - - - - - - -

MPW

25

0.10 - 0.16 50 50 25 125 50 50 25 - 100 100 50 -

0.16 - 0.25 50 50 25 125 50 50 25 - 100 100 50 -

0.25 - 0.40 50 50 25 125 50 50 25 - 100 100 50 -

0.40 - 0.63 50 50 25 125 50 50 25 - 100 100 50 -

0.63 - 1.0 50 50 25 125 50 50 25 - 100 100 50 -

1.0 - 1.6 50 50 25 125 50 50 25 - 100 100 50 -

1.6 - 2.5 50 50 25 125 50 50 25 - 100 100 50 -

2.5 - 4.0 50 50 25 125 50 50 25 - 100 100 50 -

4.0 - 6.3 50 50 25 125 50 50 25 - 100 100 50 -

6.3 - 10 50 50 25 125 50 50 25 - 100 100 50 -

10 - 16 50 50 25 160 50 50 25 - 100 100 50 -

16 - 20 50 50 25 250 50 50 25 - 100 100 50 -

20 - 25 50 50 25 250 50 50 25 - 100 100 50 -

25 - 32 42 42 25 500 42 42 25 - 100 100 50 -

MPW

65

10 ... 16 50 50 30 160 50 50 30 - - - - -

16 ... 20 50 50 30 250 50 50 30 - - - - -

20 ... 25 50 50 30 250 50 50 30 - - - - -

25 ... 32 50 50 30 500 50 50 30 - - - - -

32 ... 40 35 35 10 500 35 35 10 - - - - -

40 ... 50 35 35 10 750 35 35 10 - - - - -

50 ... 65 35 35 10 750 35 35 10 - - - - -

MPW

100 55 ... 75 50 50 10 1250 50 50 10 - - - - -

70 ... 90 50 50 10 1250 50 50 10 - - - - -

80 ... 100 50 50 10 1250 50 50 10 - - - - -

Note: “-” Fuse or MCCB not required.

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-191

MPW

SER

IES

Controls Manual Motor ProtectorsShort-Circuit Interruption Capacity (IEC 60947-2) for MPW16 , MPW25, MPW65, MPW100

catalogNumber

Setting overload Release

(A)

220-230VAc 380-415VAc 440VAc 460-500VAc 630-690VAc

Icu Ics

Max. Fuse

(gL/gG)Icu Ics

Max. Fuse (gL/gG) 1)

Icu Ics

Max. Fuse (gL/gG) 1)

Icu Ics

Max. Fuse (gL/gG) 1)

Icu Ics

Max. Fuse (gL/gG) 1)

kA kA A kA kA A kA kA A kA kA A kA kA A

MPW

16

0.10...0.16 100 100 - 100 100 - 100 100 - 100 100 - 10 10 -

0.16...0.25 100 100 - 100 100 - 100 100 - 100 100 - 10 10 -

0.25...0.4 100 100 - 100 100 - 100 100 - 100 100 - 10 10 -

0.4...0.63 100 100 - 100 100 - 100 100 - 100 100 - 10 10 -

0.63...1 100 100 - 100 100 - 100 100 - 100 100 - 10 10 -

1...1.6 100 100 - 100 100 - 100 100 - 100 100 - 10 10 -

1.6...2.5 100 100 - 100 100 - 100 100 - 100 100 - 8 8 25

2.5...4 100 100 - 100 100 - 100 100 - 100 100 - 8 8 35

4...6.3 100 100 - 100 100 - 100 100 - 100 100 - 8 8 50

6.3...10 100 100 - 50 10 100 50 10 80 10 10 63 5 5 50

10...16 100 100 - 10 10 100 10 10 80 10 10 80 4 3 63

MPW

25

0.10...0.16 100 100 - 100 100 - 100 100 - 100 100 - 100 100 -

0.16...0.25 100 100 - 100 100 - 100 100 - 100 100 - 100 100 -

0.25...0.4 100 100 - 100 100 - 100 100 - 100 100 - 100 100 -

0.4...0.63 100 100 - 100 100 - 100 100 - 100 100 - 100 100 -

0.63...1 100 100 - 100 100 - 100 100 - 100 100 - 100 100 -

1...1.6 100 100 - 100 100 - 100 100 - 100 100 - 100 100 -

1.6...2.5 100 100 - 100 100 - 100 100 - 100 100 - 8 8 25

2.5...4 100 100 - 100 100 - 100 100 - 100 100 - 8 8 32

4...6.3 100 100 - 100 100 - 100 100 - 100 100 - 8 8 50

6.3...10 100 100 - 100 100 - 50 25 80 42 21 63 8 8 50

10...16 100 100 - 50 25 100 50 15 80 10 8 80 5 5 63

16...20 100 100 - 50 25 125 50 15 80 10 8 80 5 5 63

20...25 100 100 - 50 25 125 50 15 100 10 8 80 5 5 63

25...32 100 100 - 50 25 125 25 15 100 10 8 80 5 5 63

MPW

65

10...16 100 100 - 50 50 100 50 50 80 15 15 80 8 8 6316...20 100 100 - 50 50 125 50 50 80 15 15 80 8 8 6320...25 100 100 - 50 50 125 50 50 100 15 15 80 8 8 6325...32 100 100 - 50 50 125 50 50 100 15 15 80 5 5 6332...40 100 100 - 50 50 160 50 50 125 15 10 100 5 5 6340...50 100 100 - 50 50 160 50 50 125 15 10 100 5 5 8050...65 100 100 - 50 50 160 50 50 125 15 10 100 5 5 80

MPW

100 55...75 100 100 - 75 50 - 50 38 200 12 9 160 6 6 125

70...90 100 100 - 75 50 - 50 38 200 12 9 160 6 6 160

80...100 100 100 - 75 50 - 50 38 200 12 9 160 6 6 160

Self protected against short-circuits up to 100kA - Back-up fuse not required 1) Fuse required for greater short-circuit currents.

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-192

MPW

SERIES

Controls Manual Motor ProtectorsShort-Circuit Interruption Capacity (IEC 60947-2) Limiter Function MPW25 + CLT25

Self protected against short-circuits up to 100kA - Back-up fuse not required ♦ Not applicable due to MPW25/already having 100 kA of Icu / Ics in referred ranges.

catalogNumber

Setting Overload Release

(A)

380-415VAC 440VAC 460-500VAC 630-690VAC

Icu Ics

Max. Fuse

(gL/gG)Icu Ics

Max. Fuse

(gL/gG)Icu Ics

Max. Fuse

(gL/gG)Icu Ics

Max. Fuse

(gL/gG)

kA kA A kA kA A kA kA A kA kA A

MPW

25 +

CLT

25

0.10...0.16 ♦ ♦ - ♦ ♦ - ♦ ♦ - ♦ ♦ -0.16...0.25 ♦ ♦ - ♦ ♦ - ♦ ♦ - ♦ ♦ -0.25...0.4 ♦ ♦ - ♦ ♦ - ♦ ♦ - ♦ ♦ -0.4...0.63 ♦ ♦ - ♦ ♦ - ♦ ♦ - ♦ ♦ -0.63...1 ♦ ♦ - ♦ ♦ - ♦ ♦ - ♦ ♦ -1...1.6 ♦ ♦ - ♦ ♦ - ♦ ♦ - ♦ ♦ -

1.6...2.5 ♦ ♦ - ♦ ♦ - ♦ ♦ - 50 50 -2.5...4 ♦ ♦ - ♦ ♦ - ♦ ♦ - 50 50 -4...6.3 ♦ ♦ - ♦ ♦ - ♦ ♦ - 50 50 -

6.3...10 ♦ ♦ - 100 100 - 100 100 - 50 50 -10...16 100 100 - 100 100 - 100 100 - 50 50 -16...20 100 100 - 100 100 - 100 100 - 50 50 -20...25 100 100 - 100 100 - 100 100 - 10 10 -25...32 100 100 - 100 100 - 100 100 - 10 10 -

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-193

MPW

SER

IES

Controls Manual Motor Protectors - MPW Technical DataMain Terminal Capacity

catalog Number Type Number of conductors cross-Section

MPW16 Rigid or flexible cable 1 or 21...4 mm2

18...12 AWG

MPW25 Rigid or flexible cable 1 or 21...2.5 mm2

2.5...6 mm2

14...8 AWG 1)

MPW65

Type 1 conductor connection in upper part only Cross-Section Rigid cable 1...35 mm2

Cable without terminal 1.5...35 mm2

Cable with terminal 1...35 mm2

Flexible cable1.5...35 mm2

16...2 AWGType 1 conductor connection in lower part only Cross-Section

Rigid cable 2.5...35mm2

Cable without terminal 6...35mm2

Cable with terminal 2.5...35mm2

Flexible cable6...35mm2

12...2 AWGType Connection of 2 condutors - Conductor in upper part Cross-Section

Rigid cable 1...35mm2

Cable without terminal 1.5...35mm2

Cable with terminal 1...35mm2

Flexible cable1.5...35mm2

16...2 AWGType Conductor in lower part Cross-Section

Rigid cable 2.5...35mm2

Cable without terminal 6...35mm2

Cable with terminal 2.5...35mm2

Flexible cable6...35mm2

12...2 AWG

MPW100

Type Number of conductors Cross-Section

Rigid cable1

2.5...70 mm2

12...2/0 AWG

22.5...50 mm2

12...1/0 AWG

Flexible cable1

2.5...50 mm2

12...1/0 AWG

22.5...35 mm2

10...2 AWG

Note: 1) 8 AWG for flexible cable only

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-194

MPW

SERIES

Altitude (above sea level) - h

Rated operational voltage ue

current correction factor Iu

h ≤ 2000 m 690 V 1 x Iu2000 < h ≤ 3000 m 550 V 0,96 x Iu3000 < h ≤ 4000 m 480 V 0,93 x Iu4000 < h ≤ 5000 m 420 V 0,90 x Iu

Controls Manual Motor Protectors - MPW Technical Data

Altitude - Correction factorThe MPW manual motor protectors do not undergo any change to their specified performance when applied at an altitude of up to 2000 meters above sea level.However, as the altitude increases, the reduced atmospheric pressure produces decreasing dielectric properties. Therefore, current and voltage correction factors must be applied for altitudes exceeding 2000 meters, as shown in the table on the right.

DC operationThe MPW16, MPW25 and MPW65 motor protective circuit breakers can also be used for operating DC loads. For such operation it is necessary to connect 2 or 3 poles in series.See recommended circuits and their voltage limits in the table on the right.

Time constant t = 5 ms

Short-circuit breaking capacity Icu = 10 kA for all configurations

circuits Max. Vdc Notes

150 VDC

System notgrounded

2 pole series connected

300 VDC

System grounded

2 pole series connected

450 VDC

System grounded

3 pole series connected

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-195

MPW

SER

IES

Controls Manual Motor ProtectorsConnection Diagrams and Typical Cirrcuits

Typical Circuits

ACBF-11 and ACBF 11 MPW100 ACBS-11 and ACBS-11-MPW100 ACBS-20 and ACBS-20-MPW100

ACBS-02 and ACBS-02 MPW100 TSB-22 TSB AT11 MPW100

URMP SRMP

Undervoltage Release URMP Shunt Release SRMP Trip Signalling Block TSB-22

F1

S0...Sn - Push Buttons in the circuit (NC)S0...Sn - Push Buttons in the circuit (NO)S - MPW auxiliary contact

H1 - Short-circuit trip signallingH2 - Overcurrent trip signalling

S

MPW25 + CLT25

Load

Feeder

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-196

MPW

SERIES

Controls Manual Motor Protectors - Dimensions mm (in)

MPW16 + CWC07...16

MPW16 + Accessories Mounting Position

Insulated Enclosure - PE66 (IP66)

45 [1.76]

165

[6.4

9]

175

[6.9

1]

77 [3.03]

DIN rail35 [1 38]

MP

ECCMP C016

CWC07 16

92 [3.62]

7]

83.2 [3.28]

157

[6.1

8]

PG 16PG 16

150.

32 [5

.92]

18 [0.71]45 [1.77]18 [0.71]

9 [0.36]

90 [3.55]

119

[4.6

7]

5 [ 0.19]

30 [1.19]

106

[4.1

6]

ACBS

URMPSRMPTSB

ACBF

97 [3

.84]

DIN ra l35 [1 38]

77 [3.05]

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-197

MPW

SER

IES

Controls Manual Motor Protectors - Dimensions mm (in)

MPW25 + CWC07…16

MPW25 + Accessories Mounting Position

45 [1.76] 98 [3.85]

165

[6.5

0]

DIN rail35 [1.38]

176

[6.9

2]

ECCMP-C0

CWC07...16

18 [0.71]

45 [1.77]

18 [0.71]

9 [0.36]

90 [3.55]

5 [ 0.19]

30 [1.19]

106

[4.1

6]

ACBS

URMPSRMPTSB

ACBF

98 [3

.84]

119

[4.6

7]

98 [3.85]

DIN rail35 [1 38]

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-198

MPW

SERIES

MPW25 + CWC025

MPW25 + CWM9...18

MPW25 + CWM25

45 [1.76]

176

[6.9

4]

165

[6.5

1]

98 [3.84]

DIN rail35 [1 38]

ECCMP C025

CWC025

45 [1 76]97 3 83]

193

[7.6

0]

183

[7.1

9]

4 5 [0 18]

35 [1 38]10 [0

.39]

183

[7.2

0]

5 0 19]

30 [1 18]

DIN ra l35 1 38]

MPW25

ECCMP 25

CWM9 18

45 [1 76]

193

[7.6

0]

183

[7.1

9]

97 [3 83]

CWM25

10 [0

.39]

35 [1 38]

4 5 [0 18]

183

[7.2

0]

5 [ 0 19]

30 [1 18]

ECCMP 25

MPW25

D N rail35 [1 38]

Controls Manual Motor Protectors - Dimensions mm (in)

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-199

MPW

SER

IES

MPW25 + CWM32

Insulated Enclosure - PE55 (IP55) Insulated Enclosure - LPE55 (IP55)

Current limiter - CLT25

183

[7.2

0]

5 [ 0 20]30 [1 18]

200

[7.8

7]

98 3 86]55 [2 17]

ECCMP 32

CWM32

MPW25D N a l35 [1 38]

13 [0

.47]

16.5

[0.6

5]

4 5 [0 18]

79 [3

.11]

128 7 [5 07]109 2 [4 30]

167

[657

Ø4 5 [Ø0 18]

155

[610

92 [3 62]

PG 16PG 16PG 16 PG 16

108 [4 25]

155

[6.1

0]

Ø4 5 [Ø0 18]

109 2 [4 30]128 72 [5 07]

45 [1,772]

CLT25

72 [2,820]

118

[4,6

46]

Ø4 8 Ø0,1

90]

30 [1,193]

61 [2,385]

106

[4,1

60]

Controls Manual Motor Protectors - Dimensions mm (in)

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-200

MPW

SERIES

Accessories: BBS45, BBS54, FTBBS, LST25

Through the Door Rotary Handle - RMMP

Through the Door Rotary Handle - MR MPW25

118

[4.6

5]

19.4 [0.76]97 [3.82]

R20

Ø4 [Ø0.16]MPW25

45 [1.77]

MPW25i

Widthfrom 1.0 to 3.5mm

ACBF

PLMP

ACBSURMPSRMP

97 [3

.82]

9 [0.35] 18 [0.71]72 [2.83]

45°

149 [5.87] 28 to 302

177 a 451

5.5 [0.22]

Connect ng Rod (130 or 330mm)

12.2

[0.4

9]

6.9 [0.28]

Ø16 [Ø0 63]

[5.12 or 13.0]

[1.10 to 11.89]

[.04 to 0.14]

Drilling holes located on door panel

118

[4.6

5]

97 [3 82]Drilling holes located on door panel

MPW25

45 [1 77]

MPW25i

Widthfrom 1 0 to 3 5mm

ACBF

PLMP

ACBSURMPSRMP

97 [3

.82]

9 [0 35] 18 [0 71]

72 [2 83]

149 [5 87] 15 to 280

164 to 429

5 5 [0 22]

Connecting Rod (130 or 330mm)

12.2

[0.4

8]

33 [1 30]

24.5

[0.9

6]

3 2 [0 13]

Ø22.5

[Ø0.8

9]

6 9 [0 27] 20 [0 79]

[6 46 to 16 89]

[5 12 or 13 0]

[0 59 to 11 02]

[0 4 to 0 14]I ON

0 O

FF

Catalog Number BBS45-2 BBS45-3 BBS45-2 BBS45-5

A 85 130 175 220

Catalog Number BBS54-2 BBS54-3 BBS54-2 BBS54-5

B 94 149 202 256

Controls Manual Motor Protectors - Dimensions mm (in)

85 [3 36]

20 [079]

14 [057]

45 [1 77]

13 0 [0 51]

28 1 2]

4 0 95]

40 156

44 [1 7 ]

28 [1.09]

40 [1.57]

25 [1

.00]

51 [2

.01]

B 13 [0 51]

20 [079]

14 [057]

54 2 13]

WEG Automation - Products and Solutions

www.weg.net

Data is subject to change without notice. B-201

MPW

SER

IES

Through the Door Rotary Handle - MRX

Through the Door Rotary Handle - RMMP65

Through the Door Rotary Handle - MRX65

MPW65 + Accessories Mounting Position

213 [8 50]

19 22 [0 77]

125

[5.0

0]

52 60 [2 07]

MPW65MPW6

3 5 [0 14

10 [0 40]

AR2

0

45°

4 [ 0 16]

16 [ 0 64]

241 to 515

28 to 302

Dri ling holes on the door panel

Connecting Rod130 or 330[5 12 or 12 99]

A < 5 0[A < 20]

[9 49 to 20 28]

[1 10 to 11 89]

3 5 [0 14]

10 [0 39]

A

50 7 [2 00]

213 [8 37]

125

[4.9

2]

33 [1 30]

MPW65MPW65i

23.5

[0.9

3]

3 2 [0 13]

4 [ 0 16]24 25 [0 95]

24.2

5 [0

.95]

22 5 [ 0 89]

48 5 [1 91]

48.5

[1.9

1]

Dr lling holes on the door panel

Connecting Rod130 or 330

A < 5 0

261 to 489

48 to 276[1 89 to 10 87]

[5 12 or 12 99]

[10 27 to 19 25]

[A < 20]

9 [0 37]

99 [3 97]

18 0 72] 54 2 16] 18 0 72]

157 [6 27]

125

[5.0

0]

144

[575

]

131

[5.2

4]

30 1 20]

5 0 19]

DIN ra l35 [1 38]

URMPSRMPTSB

ACBS

ACBF

154 2 [6 07] 48 to 276

50 7 [2 00]

97.2

[3.8

3]

11.5

[0.4

5]

7 2 [0 28]

A

3 2 [0 13]

23.5

[0.9

3]

4 [ 0 16]

24 3 [0 95]

24.3

[0.9

5]

48.5

[1.9

1]

48 5 [1 91]

Drilling the panel door

130 or 330

A < 5 0 MPWMPWMPW25t

202 to 430

[5 12 or 13 0]

[7 95 to 16 93]

[A < 19 ]

[1 89 to 10 87]

Controls Manual Motor Protectors - Dimensions mm (in)

www.weg.net

Data is subject to change without notice.1-800-ASK-4WEGB-202

MPW

SERIES

MPW100

Through the Door Coupling Rotary Handle - MR MPW100

Mounting position

35 [1 38]

DIN rail:75 [2 95]

11 MPW100

ACBS

URMPSRMP

MPW100

165

[6.5

0]

70 [2 76] 171 [6.73]

155

[6.1

0]

30 [1.18]

[

0.2

0]

18 [0.71]18 [0.71]

9 [0.35]

106.5 [4.19]

Ø43

53,6

4x Ø3,4

56

4,5

0,9

B

Drilling the panel door

A < 7,6

Reference Code B (mm)

MR MPW100-115min: 220max: 282

MR MPW100-315min: 220max: 482

4 5mm

A < 7 6mm

∅43

B

0,9m