building operator certification level i...• component #1 compressor. the compressor is the heart...
TRANSCRIPT
Building
Operator
Certification –
Level I
A Partnership of the
CUNY Institute for Urban Systems
Building Performance Lab, the
CUNY School of Professional
Studies, and the New York State
Energy Research & Development
Authority
Building Operator Certification Level I (BOCI)
Building Systems: Electrical
CUNY School of Professional Studies
CUNY Building Performance Lab
The BOC
Air Conditioning & Chilled Water
Systems: Lesson 8
Lesson 8 Objectives
• Understand the Vapor Compression Cycle
• Learn about the different systems and the
equipment used to provide cooling in
buildings
– DX
– Heat Pumps
– Chillers
Air Conditioning & Energy Efficiency
• To operate your Air Conditioning at peak efficiency:
-Understand the system
-Understand system components
-Prepare for and provide proper maintenance.
How does an air conditioner cool the air?
• The cooling effect of evaporation is the main process: We often experience
evaporative cooling: for example, water from a spray bottle or perfume sprayed on wrist. As water
is sprayed through the nozzle, the trigger inside pushes the water against the (small) opening,
building up pressure. After the water is squeezed through, it atomizes into a mist/vapor of
thousands of tiny droplets of water. The water has gone from a high pressure (inside the nozzle)
to a relatively low pressure (outside the nozzle). In its newly atomized state, the greater surface
area of the water has an enhanced ability to absorb heat: absorbing heat, it feels cool as it
absorbs heat from whatever it touches.
• Change of State: A refrigerant is gas/vapor at atmospheric pressure. Under high pressure it
will liquify. A refrigerant changes state as it turns from a liquid to vapor. Ice turns to water then to
steam - each is a change of state. Water is 32 dF and ice 32 dF, it takes a lot of energy change
ice into water. When something changes state there is a lot of energy embodied in that process.
To enhance this process refrigerants are said to “boil” at very low temperatures approximately -60
dF, which enhances its ability to remove heat at wide range of temperature.
Notes for Vapor Compression Cycle • Component #1 Compressor. The compressor is the heart of the system and does most of the
mechanical work. The compressors raises the pressure of the refrigerant vapor/gas and moves it
through the system. Now at higher pressure, refrigerant molecules are closer together and they
do not have the same ability to hold heat.
• Component #2 Condenser. The refrigerant enters the condenser as a vapor; as it passes
through heat is removed from it, the molecules slow down and the refrigerant condenses and
turns into a liquid. The condenser acts like a radiator, removing heat from the refrigerant and
transferring it to the atmosphere. In the image, the red dots inside the piping represent vapor; the
solid red represents the liquid refrigerant.
• Component #3 Metering Device or Expansion Valve The dividing point between the high
pressure and low pressure sides of the system. The refrigerant enters at high pressure and
leaves at low pressure in a similar fashion to the spray bottle. The metering device is designed to
maintain a specific rate of flow of refrigerant into the low pressure side of the system.
• Component #4 Evaporator The refrigerant enters the evaporator as an atomized liquid as it
passes through the coil because of the lower pressure it continues to expand and turns into a
vapor which enhances its ability to absorb heat. Because the refrigerant is absorbing heat the coil
becomes cold. This process will cool the air, water, or for that matter, ice cream mix if that's what
is flowing over the evaporator.
Activity: Liquid or Vapor? High or Low Pressure
Is the refrigerant a liquid or vapor here? Is the pressure high or low here?
At the outlet of the compressor: vapor and high pressure
At the outlet of the condenser: liquid and high pressure
At the outlet of the Metering Device: low pressure and an atomized liquid and vapor mixture.
At the outlet of the evaporator: vapor and low pressure
The Vapor-Compression cycle is used in many different configurations and equipment packages, based on direct refrigerant expansion (DX units):
Room unit air conditioners
Split Systems
Packaged Rooftop units
Heat Pumps
V-C Direct Expansion Configurations
DX System Schematic
Heat Pump
Packaged Rooftop Unit & Window Unit
Outside air intake (fixed louver, operable damper)
Return fan
Filter section
Supply fan
Cooling coil
Compressor
Condenser unit
Outside
air
Return
air
Supply
airThis is also a DX Air Conditioning System
Point to Each Part and Ask: What is this?Last Question: Where is the gas-fired heating section? Not Labeled: just to the left of the Cooling Coil
Heat Pump
• Vapor-compression cycle can be reversed
• Used for Heating & Cooling
• A heat pump can work both as an air conditioner (in summer) reversing the cycle (in winter) to heat the building. The reversing valve reverses the direction of refrigerant flow, altering the function of the inside and outside coils.
• Air Source Heat pumps are very popular because of their high efficiency during mild outside air temperatures. They are not as efficient when outdoor temper-atures are extreme: they switch-over to electric resistance heating when the air is just above 32 dF.
AC mode
Heating
Compressor Types: Workhorse of the V-C Cycle
• Positive Displacement Compressors– Reciprocating
– Rotary
– Scroll
– Screw
• Centrifugal Compressor
The Workhorse of the V-C Cycle
Compressor-drives
• Usually electric motor
• Alternative drives
– Steam Turbine
– Gas Turbine
Compressor Drives & Maintenance
Compressor life is dependent on adequate lubrication and maintaining operating pressures within the acceptable range, as recommended by the manufacturer.
Electric Motor
Steam Turbine
Gas Turbine
Refrigerants: Lifeblood of the V-C Cycle
•The properties of a refrigerant is essential to the performance of the V-C cycle, but its composition can have real environmental impacts
•Refrigerants are regulated substances: Chlorine impacts the upper atmosphere and depletes the Ozone layer.
•Building operators should have training and certification in refrigerants.
•Individuals handling refrigerants must be certified through a qualified program to ensure that venting to the atmosphere during service is prevented.
•The Montreal Protocol (1989) is an international Treaty eliminating the production of CFC’s
------------------------------------------------
Freon: A general term used to identify any of a group of partially or completely halogenated
simple hydrocarbons containing fluorine, chlorine or bromine used as refrigerants. R-22 is the most
well-known and used of these refrigerants, currently being phased out.
R-22 Refrigerant: An ozone-depleting, hydro-chloro-fluoro-carbon (HCFC) refrigerant - the
refrigerant of choice for residential heat pump and AC systems for decades. Due to its harmful
environmental effects, production of R-22 and systems that use it are being phased out and will
cease in 2015.
Puron R-410a: An environmentally sound refrigerant not harmful to the earth’s ozone layer
but still a greenhouse has (GHG). Boils at -48dC. Puron refrigerant has been approved by
Environmental Protection Agency as replacement for Freon R-22 and other ozone depleting
refrigerants. Used in both residential and commercial applications.
HFC (R134a) Tetrafluoroethane the new refrigerant, an inert gas. Boils at -15 dF. Used as a
“high-temperature” refrigerant for domestic AC, car AC and for the delivery of pharmaceuticals like
bronchodilators.
Ammonia (NH3) has been used in air conditioning systems before 1930, before Willis Carrier invented his air conditioning system. Anhydrous ammonia boils at -28 dF. Household ammonia is diluted with water and only about a 5 – 10% concentration.
Common Refrigerants
The Absorption Cycle
Cooling generated from a different process; used the same
as the V-C core.
• AC driven by heat, not a motor’s mechanical energy.
• Water and lithium bromide solution refrigerant
• Evaporation, Condensation and re-constitution of lithium
bromide solution driven by heat
• Single-stage and two-stage cycles
– Two stage higher efficiency but needs higher quality
input (e.g. – high pressure steam)
Intro to Larger Cooling Systems
Compressor
Evaporator
Heat
Exchanger
Condenser
Heat
Exchanger
Intro to Larger Cooling Systems• Same V-C core…
• New pieces of Equipment
– The Chiller
– The Heat Exchanger
• Condenser - Heat Rejection
– Cooling tower
– Other Methods
• Evaporator - Chilled Water
Delivery
Same
V-C
Core
Heat
Exchanger
Heat
Exchanger
Cooling
Tower Chilled
Water
Schematic of Typical Chilled Water Systems
• Chillers are designed for large cooling loads
• The Chiller has the 4 Core V-C cycle components, as well the Heat Exchangers in one location
• Shell-and-tube Heat Exchangers HX reject heat & transfer cooling
• Water is pumped from the HXs to cooling towers to reject heat and chilled water for space cooling
• Chillers use centrifugal, reciprocal or rotary screw compressors
• Controls are usually integrated into a building automation system BAS
Chillers and Heat Exchangers HX
V-C Cycle Performance & Diagnostics
• Diagnose using temperature and pressures across the cycle
• Some of the most common defects can be addressed by maintenance:
• Dirty coils
• Blocked air flow
• Low refrigerant charge
Air-Conditioning Performance: There is an expected temperature and pressure at each point in the system for a given refrigerant. Using a table with these specifications, a technician can give the system a check-up and run diagnostics when there is an problem (on next slide)
Refrigerant Pressure-Temperature Table
• Tables and tools read temp and pressure
• Table lists temperature and pressure for each refrigerant
• Used to check refrigerant charge and for diagnostics
• Hand-held instrument reads pressure & temperature with tables built-in
This is the table used for V-C
diagnostics. Each column of
the table is for one
refrigerant. Each
temperature has an
expected corresponding
pressure. This will tell the
technician if you have the
correct refrigerant charge.
Automated diagnostics: Honeywell Service Assistant
Definition: The amount of refrigerant
in a system is measured in pounds of
freon.
This diagnostics tool is attached to
the points of the system and it takes
temperature and pressure readings.
It has the table built in. This makes it
faster and easier to diagnosis
problems with the equipment and
determine if it is operating efficiently.
Refrigerant Charge Effect on the System
This chart shows the effect on efficiency from
under or over charging the equipment.
You can see that an over-charge is as bad for
efficiency as an under-charge.
Each bar shows a
percentage of
systems that have the
wrong charge.
Only 17% have the
correct charge.
If you add up all the
bars = 80% of all AC
systems are under-
charged
Survey by Proctor Engineering
What are some of the common causes of inefficiency when the
system is not properly charged?
Rating Terms for AC Performance
• Coefficient of Performance (COP)
= Refrigeration effect / input - in btu(British Thermal Unit)
1 ton = 12,000 btu 1 kW (1000 Watts) = 3,410 btu 1# LP steam = 1,000 btu
• If it takes one kW produce one ton of cooling; output/input; 1 ton/1kW
• 12,000/3,410 = COP of 3.5
• Energy Efficiency Ratio (EER)
= Btu cooling / input - in watts• If it takes one kW (1000W) produce one ton of cooling,
• 12,000 / 1,000 = EER of 12
• If it takes .5 kW (500W) to produce one ton of cooling
• 12,000 / 500 = EER of 24• If you have an EER of 6 it would take 2kW to produce 1 ton of cooling
• EER of 6 = 12,000/ 2,000W, ie – 2 kW per ton
Notes for Rating Terms for AC Performance
•kW/ton
•1 ton= the amount of power it takes to freeze one ton of ice in 24 hours (or 12,000 Btu/hr or 3517 Watts).
•COP = Q out / Work in. The input is in Btu.
•EER = The Energy Efficiency Ratio (EER) of a particular cooling device is the ratio of output cooling (in Btu/hr) to
input electrical power (in Watts).
•SEER = The Seasonal Energy Efficiency Ratio has the same units of Btu/W·hr, but instead of taken at a single
operating condition, it represents expected overall performance for a typical year's weather in a given location.
•The EER is related to the coefficient of performance (COP) commonly used in thermodynamics: the COP of a
cooling device is unit-less: both the cooling load and the electrical power needed to run the device are measured
using the same units, e.g. watts- a COP is universal and can be used in any system of units. The COP is an
instantaneous measure (a measure of power divided by power), whereas both EER and SEER are averaged over
a duration of time (measures of energy divided by energy). The time duration considered is several hours of
constant conditions for EER, and a full year of typical meteorological and indoor conditions for SEER.
•IPLV is an abbreviation for Integrated Part Load Value. Unlike the EER, however, the IPLV measures the
efficiency of air conditioners under a variety of conditions -- that is, when the unit is operating at part load 25%,
50%, 75% and 100% of capacity and at different temperatures.
_________________________________________________________________________________________
•Formulas for determining energy used by chillers and DX systems
Chillers – The formula for output for chillers (500 is a constant, represents the ability of water to carry heat)
Q = 500 * GPM * ΔT
–DX – The formula for output of DX AC units (1.08 is a constant, represents the ability of air to carry heat)
•Qs=1.08 * CFM * ΔT
Compressor Capacity Control Individual feedback controllers adjust the cooling capacity of each chiller to
maintain a specific chilled water supply temperature.
When cooling load is light, we can reduce compressor work by raising the evaporator temperature (chilled water temperature reset). But what happens at the compressor?
The compressor has to work at part load. What is the best way for it to work at part load? Some ways are more efficient than others.
• Hot Gas By-pass (this is the easiest to do, but the least efficient)
• Unloaders
• Multiple compressor staging
• Inlet Vanes (centrifugal compressors)
• Variable Speed drive control, including variable refrigerant flow
______________________________________
All of the listed items are done to make sure that enough heat gets dumped so that
the chiller can work efficiently. Chillers work best when they have about a 12 d ΔT,
change of temperature or the chilled water between when it enters and leaves the
chiller. All of these help to optimize the system
Condenser - Heat Rejection
Mechanisms
• Air-cooled condenser
– DX Type
• Water-cooled condenser
– Cooling tower
• Evaporative condenser
• Direct-Contact Tower
• Indirect-Contact Tower
– Ground and Water loops
• Used with Heat Pumps
Water cooled condenser
and cooling towerWater cooled condenser
Air cooled condenser Water-cooled Evaporative
condenser cooling tower
Condensers remove the heat from the V-C
cycle. These heat rejection components
augment the condenser and help it dump
the heat more efficiently. Cooling towers
are most commonly used with large
systems
Cooling Towers Reject Condenser Heat
drift
eliminators
condenser water in
cooled water out
wet deck
(fill)
air inlet
heated air out
wet deck
air inlet
closed circuit
to condenser
external water recirc
heated air out
Direct-Contact Tower Indirect-Contact Tower
spray pump
warm
cool
Cooling Tower Operations & Maintenance
Cooling tower maintenance considerations
• Fan speed control and multi-cell sequencing– May be staged, usually two-stage
– Cells may be sequenced
• Blockages – air intakes, drift eliminators, nozzles
• Biological growth, including Legionella
Operating Considerations- Efficiency
Cooling tower temperature reliefIf the required temperature of the cooling tower is difficult to achieve because
of exterior conditions, the tower will use a lot of fan energy. If the chiller is only
at part load and the tower temperature can be raised, this can save energy.
Condenser Heat Recovery
If waste heat from condenser can be diverted from the cooling tower and used
to heat domestic hot water or some other use, this can save energy.
Water-side Economizer (see next slide)
If outside conditions are cool enough the chiller can be
bypassed and the tower can indirectly supply the chilled water.
Legionnaires Disease • Legionnaires disease is an infection of the lungs caused by the Legionella
bacteria, which can be found anywhere untreated water is in contact with air
or soil, such as standing water on rooftops near the fresh air intakes of Air
Handling Units. Legionella bacteria has been found in cooling towers,
humidifiers, and warm water spray or mist, shower heads, fountains and a
variety of other sources.
• Legionnaires disease begins like a cold or the flu and gets worse, damaging
the kidney and lungs.
• Thousands of people are hospitalized in the U.S. each year with
Legionnaires disease: most cases occur in the summer and early fall, but
the disease can occur any time or year.
• People most susceptible to the disease are individuals over 50, especially
those who smoke, abuse alcohol, or have immune system deficiencies.
• Approximately 15% of those who contract Legionnaires disease die.
Water-side Economizer Operation
• Water-side economizer: use the cooling tower alone, bypass the chiller, indirectly supply chilled water
Bypass
chiller
Heat
exchanger
Cool air
Free chilled
water
Chiller Plants and the Chilled Water System
Chilled Water System Configurations
Part load operations – Low delta T
– The amount of cooling required is the load. Systems are designed to handle the maximum
anticipated load. On a mild day, the system will only have part of the load to deal with or “part
load. You might think the system works more efficiently on a mild day, that is not the case.
– Systems are designed to remove a certain amount of heat from the fluid it is circulating. The
amount of heat removed drops the temperature of the fluid. The chiller system we are
looking at is designed for a rise in temperature of 12 dF or a delta T of 12 dF. Different
system configurations are designed to efficiently handle a part load condition or low delta T.
– If the system has a secondary loop, the flow can remain constant in the primary/chiller loop
and the flow in the secondary/building load can be slowed to help more heat dissipate.
These are different ways to design systems and deliver
cooling
The operator must know the Design Intent, the Standard Operating Procedures SOP’s and the reasoning behind them
– Common System Designs – {these are the different system configurations designed to deliver cooling in different ways and to efficiently deal with part load conditions.}
– Constant Volume• the amount of fluid being delivered is always the same, control of cooling to the load
required by the zones is by changing the temperature of the fluid or other controls
– Constant Primary / Variable Secondary & Tertiary• same as above, but the control is done at the secondary systems/loops. The
temperature is varied/reset to meet the load by changing the volume of the flow.
– Variable Primary / Variable Secondary• the volume can be changed at the primary, by taking chillers off line, and by changing
the pump speed at the secondary systems
– Modern Systems• All of the systems above use a constant volume at the chillers.
• Today the volume can be varied by varying the refrigerant flow or varying the speed of the compressor.
• The secondary loop is no longer required regulate the CW temperatures
– Variable Prime Only• the volume can be changed at the primary pumps
Chilled Water Distribution
Chiller Plant Piping Configurations
There are many different
ways to set-up
pumping. Each set of
pumps gives better
control.
– Here are three different
pumping
configurations: the 1st
has one set of pumps -
for a small building.
The 2nd- for a larger
building -has one set of
pumps for the chiller
loop and one set to
circulate the chilled
water to the coils. The
3rd -for multiple
buildings -is similar to
the 2nd but also has a
set of pumps for each
building or wing.
1,000 Ton Plant
2,000 gpm, 12OF dT
Ideal Conditions
Chiller System - Full Load – Ideal ConditionsExiting
temp. 45d
Entering
temp. 57d
No
bypass
2000
GPM
supplied2000
GPM
delivered
1000 Ton
Load
Running
at 500
Tons
Running
at 500
Tons
36
Chiller Performance - Issues
Actual performance is often far from nameplate ratings
Why?
– Low refrigerant charge
– Excess refrigerant charge
– Air entrainment
• air trapped in the water reduces its efficiency
– Oil contamination
– Fouled watersides
• build-up on the heat exchanger from minerals and other impurities in the
water reduces conductivity
– Mechanical or Control Issues
Refrigerant level control
VFD & vortex damper control
– Steam Machines
Turbine Issues, Surface Condenser Vacuum, Wet Steam
1OF change in condenser water CW temp =
1% - 1.5% chiller performance
1OF change in chilled water CHW temp =
.75% - 1% chiller performance
Maintenance and Optimizing
General & Preventive maintenance can significantly improve efficiency!
Clean filters and coils (for good air flow)
Maintain correct refrigerant charge
Thermostat – Check for correct temperatureControls are calibrated
Use time-clocks for end-of-day shut-down
Make sure outside air economizer cycle works properly -have a Functional Test procedure
•Air Distribution System
•Contains: terminal units, air handling units, ducts, dampers, fan, cooling coils.
•Cooling Coil: cools and dehumidifies air.
•The flow of water is controlled to maintain a set-point temperature for air leaving the cooling coil.
After chilled water is produced it needs the distribution system to deliver cooling to the
different zones.
Now the chilled water
can get to work
Chilled Water – Air Distribution System
Review & Reading for Lesson 9
Today’s Class:
• Vapor Compression Cycle & Applications
– Dx, Heat Pumps, Chillers
• Chiller & Chilled Water System Components
– Compressors, Evap/Conds, Cooling Towers
• Chilled Water System Configurations & Issues
– Constant Volume , Constant Primary / Variable Secondary & Tertiary,
Variable Primary
Readings for next class:
• FEMP Section 9.7 (AIR HANDLING SYSTEMS)
• Herzog Chap. 8, pp. 119-136