bs5839 fire alarm systems
TRANSCRIPT
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 1/26
BS and Alarm systems for Buildings-Code of practice for system design, installation and servicing
BS 1:2002 Fire detection and Alarm systems forBuildings-
Code of practice for system design, installation and servicing
Due to the on going and continued advances in Fire Alarm System
Technology
and the changes in Building Design and Construction the previous
British Standard 5839:Part 1:1988 had become out of date.
Consequently the Standard taking into account these
advances/changes
made over the years has been revised.
1. GENERAL
BS 5839:Part 1:2002 like its predecessor provides guidance by
recommendations fromthe initial Planning Stage, through the Design, Installation,
Commissioning and
Final Maintenance of Fire Alarm Systems in and around buildings
other than
Domestic Dwellings, these being covered by Part 6 of the Standard.
It should be noted that the Standard does not recommend or identify
whether a
Fire Alarm System need be or should be installed within any given
premises. This
should/must be subject to, in the respect of new buildings, Fire
Precautions Act (1971)
and Building Regulations.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 2/26
Existing Buildings consequently are subject to the Workplace
Regulations and the
subsequent Risk Assessment.
It should be noted that the Standard does not cover Extinguishing/Fire Control Systems,
Voice Alarms (BS5839:Part 8), 999 Public Emergency Call
Systems,
Audible/Visual Way Guidance Systems, Critical Electronic Systems
(BS 6266) or
Fire Alarm Systems covered under NHS Estates Publication HTM
82.
NHS Estates Publication HTM 82 generally calls for the
recommendations of
BS 5839:Part 1 but also contains its own requirements which may
be in variance from
the Standard.
With regard to existing Fire Alarm Systems the new Standard
generally applies toExtensions and Alterations of these system, at least in respects of the
Planning, Design,
Installation, Commissioning, Maintenance and Certification of the
new works. Albeit that
the extended/altered system might not, overall, comply with the
recommendations of the
Standard.
2. CATEGORIES OF SYSTEMBS 5839:Part 1:2002 like the 1988 Standard Categorises Fire Alarm
Systems to satisfy
one, or both, of two principle objectives…
The Protection of Life and The Protection of Property.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 3/26
The 1988 Standard sub-categorized these objectives into the
following levels of
protection;
Life
L1:Automatic Protection Throughout the Premises.
L2:Automatic Protection as L3, but also including Defined areas
of High Risk.
L3:Automatic Protection along Escape Routes and all Rooms
opening onto these
Escape Routes.
M:Manual. (Manual Call Point)
Property
P1:Automatic Protection Throughout the Premises.
P2:Automatic Protection in Defined Areas of High Risk.
The new 2002 Standard has recognized and consequently identified
the need to expand
these categorises further and now include both L4 and L5 in the Lifecategory.
L4:Automatic Protection along Escape Routes.
L5:Automatic Protection in Defined Areas only.
I t should be noted that a very comprehensive and recorded record
of
Risk Assessment should be made if a system is to be designed and
categorized as L5 due to the implication and ramifications of a Fire Alarm
System being installed
for the protection of life with Automatic Detection ONLY
COVERING
DEFINED AREAS!
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 4/26
P1: All areas covered by Automatic Fire Detection.
If Manual Call Points are installed, i.e. Giving the
implication, that at times
the building will/may be occupied consideration must be
given to the provisionof adequate Audible Fire Alarm Sounders to warn the
occupants of an
activation of the Fire Alarm System.
All Systems installed for the Protection of Property must
have means of
remote indicating that the Fire Alarm System has activated.
Usually achievedby means of a Digital Communicator or the alike.
P2: Defined Areas of High Risk covered by Automatic
Fire Detection.
Like a P1 System if Manual Call Points are installed, the
provision of adequate
Audible Fire Alarm Sounders to warn the occupants of an
activation of the
Fire Alarm System must be installed. Plus the provision of remote signalling.
L1: All areas covered by Automatic Fire Detection.
L2: As an L3 System.
i.e. Automatic Fire Detection on Escape Route, Rooms
opening onto
Escape Routes, and including Defined Areas of High Risk.
L3: Automatic Fire Detection on Escape Routes, Rooms
opening
onto Escape Routes.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 5/26
L4: Automatic Fire Detection on Escape Routes.
As well as only covering Escape Routes an L4 System does
not exclude
other Areas of Defined High Risk
L5: Automatic Fire Detection covering only defined
areas of High Risk.
As previously stated a Life System to this category must be
subject to a very
comprehensive and detailed and recorded Risk Assessment
due to the possible
ramifications of this type of system.
M or Manual.
These systems purely rely on possibly the most reliable and
effective
Fire Detection device for the protection of life in existence!
i.e. A Human Being.
Consequently this type of system requires the need of
Manual Call Point
“Break Glass” Units.
3. POSITIONING OF EQUIPMENT
There have been no discernable changes in the new standard
regarding the spacing and
coverage of Automatic Fire Detectors.
Smoke Detectors still can cover an overall area of 100 square
metres. Heat Detectors
like wise with an overall coverage of 50 square metres.
The standard it should be noted now recognizes the use of the newly
developed
CO (Carbon Monoxide) Detectors which it must be said can reduce
the causes of false
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 6/26
alarms, however like wise they may not detect a real fire condition,
thus it is
recommended that they are not used on their own but installed
interleaved with
optical detection.
The only major changes in recommendations for manual call points
is the change
of distance between call points to 45m. A further recommendation
concerns call points
located on stairways or landings. To aid in locating the possible area
of activation the
standards suggest that the call points can either located on theroutes/exits leading to the
Stairways/landings or on the landings. With either method it is
recommended that
the units are always connected to the same detection zone of
adjacent storey.
i.e.
0
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 7/26
4. AUDIBLE ALARM SIGNALS
The 1988 Standard called for a Minimum Alarm Sound Level of
65dB. The revised2002 Standard appreciates that a Sound Pressure Level difference of
2 to 3 dB is
only just perceivable by the human ear. Consequently the new
standard now calls for a
general level of 65dB in open areas with a minimum of 60dB at
specific points of limited
extent within the area.
A level of 60dB is now also acceptable in small enclosed spaces
such as Cellular Offices,
Stairways etc.
The requirement of 75dB at a bed-head is required if the intention is
to rouse a person
from sleep.
The new recommended minimum alarm sound levels must still takeinto account any
background noise which is in excess of 60dB with the requirement
that the Fire Alarm
Audibility Level should be at least 5dB above the Background
Noise.
The maximum Level of 120dB at any normally accessible point
should still not beexceed. If this is not attainable the recommendations require that
any Alarm Sounders
be supplemented with Visual Alarm Signals, such us Xenon
Beacons.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 8/26
Should the protected premise be used for either Public
Entertainment, Retail or Similar
in which any background noise may be caused by Music etc. that is
greater than 80dB,
the new 2002 Standard recommends that in the event of a Alarm
Activation the Music
and alike be automatically muted by the Fire Alarm System.
Both the New and Old Standards recommend that there be at least 2
off individual
Alarm Sounder Circuits within the protected premises, even if only
1 sounder was on
the second circuit. This recommendation allows that in the event of
a Sounder Circuit
Failure that at least an alarm sounder would operate to draw theattention of the building
occupants to a Fire Condition.
Recommendations in the new standard in particular to larger areas
accessible to the
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 9/26
general public (typically areas of 4000sq m or more) or where in
excess of
500 members of the public are present that the Fire Alarm Sounders
within these
areas are distributed or interleaved across 2 or more sounder circuits. These individual
circuits not being contained within the same common cable sheath.
( i.e. Precluding the use of 4 Core Cable)
5. CONTROL EQUIPMENT
BS5839:Part 1:2002 recommends that the Control and Indicating
Equipment used for Fire Alarm Systems, including their associated power supplies
should confirm to the
requirements of EN54 Parts 2 and 4.
(Partly due to some recommendation included within the new
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 10/26
BS5839 Standard,
both parts 2 and 4 of EN54 are under review.)
A fundamental requirement with regard to Fire Alarm Control and
Indicating Equipmentconforming to EN54 is to limit the number of Automatic Devices
(Fire Detectors,
Manual Call Points, Interface Units etc.) controlled by a single
Micro-Processor within
the Control Panel to a Maximum of 512 Devices.
This generally limits Single Conventional non-addressable Fire
Alarm Panels to 16 Zones(larger panels are generally however made up of one or more
interlinking mother boards).
This application however, with regards to Addressable Panels limits
most single control
Panels to 4 Detection Loops.
This limitation can be over come with use of “Networked”Indicator Control Panels
distributing the Fire Alarm system amongst a number of “Sub-
Panels”, these sub-panels
usually being located remote from each other.
The practical use of this type of networked system may reduce the
cabling for the entire
system as the remote panels can be located within specific areas of
the buildings, particularly adjacent to the areas to which the connected detection
loops are protecting.
However there may be some instances, particularly in larger
addressable systems
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 11/26
here the use of Networked Systems may not be practical to achieve
the desired/required
number of detection loops.
BS5839:Part 1:2002 being only a guidance document therefore doesnot preclude the use
of Panels that do not confirm with the requirements of EN54.
Therefore Multi-Loop Panels
manufactured to confirm to the previous standard for panels
BS5839:Part 4:1988
can still be used if desired, subject to agreement between the Client
and the Designer. This
agreed variation must be recorded and noted on the DesignersDesign Certificate for the
system.
A major revision to the standard is the requirement for standby
power supplies. The
1988 standard related standby capacity to the type and occupancy of
the premises protected.
The 2002 standard recommends that sufficient backup capacity can
now be met by:
L Category Systems 24 Hours plus 30 minutes in alarm
should suffice.
P Category Systems should provide for any unoccupied
time of the protected
premise plus 24 hours up to a maximum of 72 hours plus
30 minutes inalarm. Should the 72 hour period expire and fault signal
should be sent to
the connected remote monitoring centre.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 12/26
6. CABLING
Unlike the earlier standard where the use of Non-Fire Rated Cabling
would have been
acceptable for the Detection Circuits and Fire Rated Cables used for
theAlarm Circuits. The 2002 standard recommends the use of Fire
Rated Cables for Critical
Signal Paths, this includes both the Detection and Alarm Circuits.
Even though the
Indicating and Control Equipment is provided with means of a
“Standby Supply”
(i.e. Battery Backup) the normal Electrical Mains Supply to the
equipment is nowconsidered as a Critical Circuit and consequently should be
adequately protected from the
effects of fire.
Cabling for Critical Signal Paths are now categorized to two
standards;
Standard Grade Fire Resisting Cables, generally of the Soft Skinned type,
FP200/Firetuf and
the similar.
Enhanced Grade
Until recently only M.I.C.C. Cable, but now includes both
FP200 Plus
& Firetuf Plus Soft Skinned cables
Standard Cabling in most instances will usually be adequate for a
great majority of installations.
Detection, Alarm Circuits etc.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 13/26
Apart form the previously mentioned FP200 and FireTuf, Fire Rated
Steel Wired
Armoured cable would also be acceptable particularly for external
applications.
Where a buildings Fire Alarm System incorporates a four or more
phased evacuation
procedure, or the building is greater than 30metres in height, or
being identified by a
Fire Risk Assessment or as part of a Fire Engineered solution which
compensates for
shortfalls in building construction than the use of Enhanced cabling
should be used.
The standard recommends the use of Enhanced Grade cabling for
Network
Communication Cables between networked Panels.
However if all the following criteria can be met standard Grade and
Communications
Cables (i.e. Beldon Type Cables etc.) would be acceptable;
1. The Network is configured as a loop; and
2. There is diverse routing of both the incoming and out
going circuits of the
Network Loop; and
3. There will be no loss of communication to any sub-panel
in the event of asingle open or short circuit on the Network Loop.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 14/26
7. REMOTE MONITORING
BS 5839:Part 1:2002 has identified possible inherent faults with the
current methods
of providing Fire Alarm Activations to Remote Monitoring Centres
by means of
Digital Communicators and consequently provides the
recommendations to alleviate theshort comings of current equipment;
All interconnections including the telephone line should be
monitored (usually only
achievable by means of BT Redcare or similar).
Interconnecting cables to be run through areas of low Fire Risk.
Digital communicator Unit located within area of low Fire Risk or
protected by means
of Automatic Fire Detection.
Standby Capacity of any communicator should match that as of the
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 15/26
Fire Alarm System
and should be a minimum of 24 hours. Which would preclude the
use of
security Digital Communicators which only usually have a backup
capacity of 8 hours.
8. FIRE ALARM SYSTEM DESIGN
BS5839:Part 1:2002 has identified, in particular for new Fire Alarm
Systems the need to
manage and limit the numbers of false alarms.
Consequently the revised/updated standard recommends and
emphasizes for a moredetailed roll and resultant responsibility for the designer of new Fire
Alarm System.
The standard as previously stated does not identify the need for a
fire alarm system. This
is the responsibility of the purchaser, be they a Developer or Final
User of a building. This
process will evolve consultation with the Fire Authorities, Building
Control Officers and Insurers.
The decision/consultation process for new buildings would progress
through and with
reference to general compliance to;
FIRE PRECAUTIONS ACT (1971)
BUILDING REGULATION
Which would identify and provide solutions to enable the building
to be issued with the
necessary resultant Fire Certificate.
From this point and for existing buildings this decision/consultation
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 16/26
process would
continue with reference to the "WORK PLACE REGULATIONS"
and the resultant
RISK ASSESSMENT would identify the need (if any) for the
provision of aFire Alarm System.
Upon completion of the decision process the purchaser should be in procession of all
the necessary information to identify the need and category for a fire
alarm system. This
information should then be passed to the Designer whom, with
regard to the
identified Risk and Category of System, provide a suitable design
inline with the
recommendation of the new standard.
The ultimate responsibility for the need and category of the system
solely rest with the
purchaser. However the designer can propose a category should the
situation arise. But
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 17/26
the final decision must be taken by the client/purchaser.
The proposed new Fire Alarm System must take into account all the
findings of the
provided Risk Assessment which has identified the category of thenew system. Vital
importance in the design is the need to identify and
resolve/eliminate any potential causes
of false alarms.
Any variations from the standard should be agreed between the
Designer and the
Purchaser. These if agreed variations should be documented.
Upon completion of the design a signed DESIGN CERTIFICATE
would be submitted
detailing all aspects of the final design including any agreed
variations from the standard.
This Certificate will form an integral part of the proposed system
and must be forwarded
through the entire process from the installation, commissioning andfinal acceptance by
the purchaser.
9. INSTALLATION
BS 5839:Part 1:2002 in keeping with the recommendation about
responsibilities for both
the Purchaser/Client/User as well as the system Designer has also
identified the need for
the Competency and subsequent responsibilities for both theInstallation and
Commissioning Engineers.
The installation engineer(s) responsibility extends to ensuring that
they, as well as any
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 18/26
sub-contracts they use carry out the installation in compliance to
both the new standard
and the designers design.
They also have a responsibility to make the designer aware of any building features that
the designer was not or could not have known which would effect
the design. They
should not however alter the design with out written confirmation
from the designer.
The installers responsibility also extends to ensuring compliance for
installed componentsto both manufactures and the British Standards recommendations.
Consequently any installer engaged in the installation of fire alarm
systems should be fully
conversant with BS 5839:part 1:2002.
The installation and in particular the cabling should be installed to
the requirements of BS 7671 (Wiring Regulations)
Fixing of cables should be as per the manufactures requirement,
generally ensuring that
Metal Fixings are used where necessary (i.e. Stainless Steel Cable
ties when securing
below steel cable trays). Particular attention should be made to the
use of metal fixing
within PVC Trunking, where the trunking forms the only means of support for the Fire
Alarm Cabling installed within.
Cabling installed should meet either Standard or Enhanced Grade
dependent on both the
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 19/26
designers specification and the probable intended routing of the
cables as well as any
system and cabling requirements regarding Earth/Screening
continuity as required by the
manufacture.
As with any electrical or mechanical installation protection and fire
stopping should always be
considered.
As per BS 7671 (Wiring Regulations) all the cabling should be
tested for
insulation resistance. BS 5839:Part 1:2002 recommends that thesetest should always be
carried out to prevent damage to equipment with all equipment
disconnect.
Also it is recommended (which may be at variance with the wiring
regulations) that thes
test be carried out using a Test Instrument set at 500v.
The standard also calls for the mains supply to the Indicator andControl Equipment and
any other relevant supplies associated with the Fire Alarm System
should be tested for
both Earth Continuity and Earth Fault Loop Impedance.
The field wiring and most particularly Loop Wiring to be tested for
Circuit Resistance.
All these test must be recorded for the system final documentation
plus a copy of the
results must also be forwarded to the commissioning engineer.
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 20/26
Once the installation and test are completed the installation engineer
would sign of the
system and provide the next Certificate for the system, the
Installation Certificate.
10. COMMISSIONING
Once the Fire Alarm System has been installed the system should be
set-up and
functionally tested, the commission.
Like the installer the Commissioning Engineer should be competent
with a good
knowledge of Fire Alarm Design, False Alarms and their Avoidanceand
Fire Alarm Installation. The engineer should be able to deal directly
with the
purchaser/client and other interested parties.
To facilitate the commissioning all documentation for the Fire
Alarm System,
System Specification, Design Documents (including a copy of the
Final Design Certificate),consultation documents, Original and the Installers “As Fitted”
Drawings and the installers
Test Records must be made available to the Commission Engineer.
Apart from carrying out any programming of any addressable Fire
Alarm Panels, the
commissioning engineer must ensure that the system is fully
functionally tested.
Call points, Automatic Detectors, Interfaces etc. operate and
indicate correctly, audibility
levels should be measured for sounders and where Voice Alarms are
installed their
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 21/26
intelligibility is satisfactory. Signals required to be transmitted to
“Alarm Receiving Centres” are correctly received. Cause and
Effects of the system
are functionally checked and operate as per the specification. They
should also note anychanges to the building since the original design that may effect the
design and
performance of the system. The engineer would also check that the
installed components,
Manual Call Points, Detectors, Control and Indicating Equipment,
Visual Alarms are
suitable and correctly sited and consequently acceptable to the
relevant clauses of theBritish Standard.
Also recommend by the standard and to be checked by the
Commission Engineer is that
a suitable Zone Plan is displayed.
During the commission the engineer would also inspect and check
the suitability of theMains Supply, Standby Power (i.e. Battery Backup) functions
correctly both on and off
load and has sufficient backup capacity. There is also a
recommendation that the batteries
are labelled with the date of installation.
The engineer would also check that the correct/specified cable has
been installed
(as as far as it is reasonably practical to ascertain), as well as theworkmanship of the
installation.
As far as reasonably practical to ascertain the engineer would also
check for immunity to
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 22/26
false alarms.
Any non-compliances with the design should be noted and the
designer informed.
Upon satisfactory completion of the system commissioning
following a " SOAK TEST"
(during which time the system would be deemed as not operational)
the system would
be signed off by the engineer and a Commissioning Certificate
submitted.
Like both the Design and Installation Certificates all details pursuantto the Design
including any agreed variations from the new standard would be
noted on the
Commission Certificate, all of which should be consistent through
all the Certificates.
11. FIRE ALARM SYSTEM ACCEPTANCE
The final stage of the installation process, not taking into account
the necessary ongoingmaintenance of the system would be the handover of the system to
the
purchaser/client/user.
Arrangements for the handover should include for full training to the
"Users Responsible Person" on the operation of the system and the
provision of
full documentation for the system. Including all the originalconsultation documents,
design documentation, “As Fitted” installation drawings, a system
Log Book,
Maintenance Instructions and the Design, Installation and
Commissioning Certificates to
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 23/26
be handed to the purchaser/client/user.
Once the purchaser/client/user has formally accepted the Fire Alarm
System they will sign
the Final Acceptance Certificate as evidence of their satisfaction of the system.
It should be noted that the new standard has a strong
recommendation that a minimum
and this duration may/should be increased for larger systems that the
new system be
left on a “Soak Test” for at least a week before the system is
certified as being functionaland can consequently be formally handed over to the
purchaser/client/user.
12. FIRE ALARM SYSTEM MAINTENANCE
BS 5839:Part 1:2002 provides recommendations and consequently
suggested
procedures regarding the Maintenance/Servicing of Fire Alarm
Systems.
The new Standard recognizes that modern Fire Alarm Systems may
incorporate a high
degree of monitoring, so that any faults that develop are indicated
automatically, usually
on the Control and Indicating Equipment. These fault indications are
only effective if they
are identified and appropriate action taken.
Consequently a need has been identified that the monitoring of these
systems should be
carried out by the Fire Alarm System Users nominated Responsible
Person, this person
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 24/26
should be some one whom is normally employed within the
protected premises.
The Responsible Person shall ensure that Routine Tests of the Fire
Alarm Systemare carried out. Every week, a Manual Call Point should be operated
during normal
working hours, it should be confirmed that the Control Equipment
functions correctly,
Alarm Sounders Sound and should a link to a Remote Monitoring
Centre be connected
that a signal is correctly received. The weekly test should be carried
out at approximatelythe same time each week with the alarm sounders not operating for
longer than 1 minute.
A different Call point should be tested each week so over a period
all points are tested.
(i.e. 80 Call Points would take 80weeks to test)
Premises provided with means of Standby Power Supplies
(Generator) should be test
Monthly by simulating failure of the normal power supply.
As previous identified provision of a Fire Alarm System both new
buildings would be
subject to a consultation process with reference to:
Fire Precaution Act
Building Regulations
and as well for both new and existing buildings:
Work Place Regulations
resultant Risk Assessment
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 25/26
The Fire Precautions (Workplace) Regulations require that any
equipment and devices
provided in respect of the regulations SHALL be subject to a
suitable system of
maintenance and be maintained in an efficient state, in efficientworking order and in good
repair. Failure to provide this may warrant the user liable for
prosecution.
The Health & Safety (Safety Signs & Signals) Regulations 1996
requires that
Fire Alarm warning system must be provided with a guaranteed
emergency supply inevent of interruption of the normal mains supply, unless the hazard
has thereby been
eliminated. Consequently systems not having a standby power
supply
(i.e. Battery Backup) are no longer legal!
BS5839:Part 1:2002 recommends that maintenance of Fire Alarm
Systems be carriedout by Competent Persons (i.e. Maintenance Organisations).
A Periodic Service Inspections of a period not exceeding six
months, subject to a
Risk Assessment and agreement between all interested parties this
period may be
reduced.
Tests and Checks should include operation of one Manual Call Point
or Detector oneach Circuit, changes that may effect the operation of the system,
signals if connected
to Remote Monitoring Centre.
An annual inspection (over a 12month period) to include a complete
7/15/2019 BS5839 Fire Alarm Systems
http://slidepdf.com/reader/full/bs5839-fire-alarm-systems-563280d1ad37c 26/26
function and
operational test of all equipment connected and interfaced to the Fire
Alarm System,
including all “Cause and Effects”.
Upon satisfactory completion of the Inspection;
All Devices operated correctly
Transmission to Remote Monitoring Centre correctly received
Analogue Levels on Addressable Equipment within acceptable
range
Radio Signal Strength for Radio Equipment within acceptable
rangeCause & Effect programme proved
Standby Power Supply Capacity Satisfactory
a Inspection and Service Certificate would be issued with any
recommendations noted.
During the annual inspection confirmation of the number of false
alarms would be checkedin the Log Book to see if within acceptable limits.