SPECIAL INSPECTIONS PER CHAPTER 17OF THE KY. BUILDING CODE
SEISMIC - STRUCTURAL STEEL
HELICAL PILE FOUNDATION
WIND - WIND RESISTING COMPONENTS
1705.8
1705.9
1705.10.1
1705.10.3
1705.11.1
1705.7
CAST IN PLACE DEEP FOUNDATIONS
WIND - STRUCTURAL WOOD
DRIVEN DEEP FOUNDATIONS
SECTION
1704.2.5
1705.2
1705.3
1705.4
1705.5
1705.6
ITEM
STEEL
CONCRETE
MASONRY
WOOD
SOILS
FABRICATORS
X
X
X
X
X
X
NONE
NONE
NONE
NONE
NONE
REQUIRED?
NO
X
YES
REMARKS
NONE
NONE
NONE
SEISMIC- ARCHITECTURAL COMPONENTS-1705.11.5 X SEISMIC DESIGN CATEGORY "C"
SEISMIC- MECHANICAL AND ELECTRICAL COMPONENTS1705.11.6 X SEISMIC DESIGN CATEGORY "C"
SEISMIC- STRUCTURAL WOOD1705.11.2 X NONE
SEISMIC- COLD FORMED STEEL FRAMING1705.11.3 X NONE
NONE
N/A
1705.10.2 WIND - COLD FORMED STEEL FRAMING X NONE
NONE
INTERIOR/EXTERIOR NON-LOAD BEARING WALLS
AND VENEER IN STRUCTURES
NONE
IN ADDITION TO OTHER TESTS AND INSPECTIONS REQUIRED TO BE PROVIDED BY THE CONTRACTOR IN THE SPECIFICATIONS,THE OWNER SHALL PROVIDE THE SERVICES OF QUALIFIED THIRD-PARTY INSPECTORS TO PERFORM ALL REQUIRED SPECIALINSPECTIONS AS FOLLOWS: (INTERIOR RENOVATION; NONE REQUIRED)
DESIGNATED SEISMIC SYSTEMS1705.11.4 X NONE
1704.5.1 STRUCTURAL OBSERVATION FOR SEISMIC REQUIREMENTS X SEISMIC DESIGN CATEGORY "C"
1704.5.2 STRUCTURAL OBSERVATION FOR WIND REQUIREMENTS X Vasd = 89 MPH
SEISMIC- STORAGE RACKS AND ACCESS FLOORS1705.11.7 X ALL LESS THAN 8'-0" IN HEIGHT
SPRAYED FIREPROOFING1705.13 X NONE
FIREPROOFING1705.14 X NONE
EIFS1705.15 NONE
FIRE RESISTANT PENETRATIONS & JOINTS1705.16 X NONE
SMOKE CONTROL1705.17 X NONE
X
X
X
X
X
X
BLUEGRASSAIRPORT
PROJECTJOBSITE
60
MA
N O
WA
R B
LVD
60
MAN O W
AR BLVD
VERSAILLES RD
VERSAILLES RD
DRAWING INDEX VICINITY MAP
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
- S
CB
PR
OJE
CT
NO
. 1508
SHERMAN CARTER BARNHARTARCHITECTS, PLLC
2405 HARRODSBURG ROADLEXINGTON, KY 40504-3329
PHONE: 859.224.1351FAX: 859.224.8446
www.scbarchitects.com
10/1
8/2
017 2
:46:1
4 P
M
1508
BLU
E G
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
BLUE GRASS AIRPORT
BLUE GRASS AIRPORT CUSTOMSFACILITY RENOVATION
MECHANICAL/ELECTRICAL ENGINEER
CMTA2429 MEMBERS WAYLEXINGTON, KY 40504P (859) 253-0892 F (859) 231-8157
N0.1 ABBREVIATIONS, SYMBOL LEGEND, GENERAL NOTES, PARTITION TYPES ANDCODE INFORMATION
A1.1 DEMOLITION AND NEW WORK FLOOR PLANS
A1.2 DOOR SCHEDULE, DOOR AND FRAME ELEVATIONS, CEILING PLAN AND DETAILS
A1.3 SIGNAGE SCHEDULE AND ELEVATIONS AND CASEWORK DETAILS
ARCHITECTURAL
PLUMBING
P1.0 PLUMBING LEGENDP2.0 PLUMBING - FIRST FLOOR
MECHANICAL
M1.0 MECHANICAL LEGENDM2.0 DEMOLITION - FIRST FLOOR AIR DISTRIBUTIONM3.0 AIR DISTRIBUTION - FIRST FLOOR
ELECTRICAL
E1.0 ELECTRICAL LEGENDE2.0 DEMOLITION - FIRST FLOOR ELECTRICALE3.0 LIGHTING - FIRST FLOORE4.0 POWER - FIRST FLOORE5.0 SYSTEMS - FIRST FLOORE6.0 PANEL/FIXTURE SCHEDULES
FOR
OCTOBER 20, 2017
4000 TERMINAL DRIVELEXINGTON, KENTUCKY
CONSTRUCTION DOCUMENTS
LEXINGTON, KENTUCKY
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ABBREVIATIONS
ACT ACTUAL LOC LOCATION
SPEC(S). SPECIFICATIONS
KENTUCKY BUILDING CODE
YYD
HD WD HARDWOODTOS
HEIGHT
HOLLOW
HORSEPOWER
HORIZONTAL
HOLLOW METAL
HEXAGONAL
HEATER
INVERT
JOINT
JOIST
JUNCTION BOX
INTERIOR
INSULATION
INSIDE FACE
INSIDE DIAMETER
HOT WATER, HARD WHITE
INCLUDED
HEATING
HEX
HT.
HM OR H.M.
HORIZ.
HP
HOL
HTR
HW
IID
IF
INSUL.
INT
INV
JJB
INCL
JT
KBC
K
JST.
HTG
TS
U
TOW
TYP.
UG
UL
U.N.O.
UNFIN.
VVAC
VERT.
VB
VCT
V.I.F.
W
W
X
W.R.
X
GAUGE
GRADE
GROUND
HIGH
HARDWARE
HEADER
HANDICAPPED
HARD BOARD
HOLLOW CORE
GYPSUM
GLAZED STRUCTURAL TILE
GLUE-LAMINATED
GLASS, GLAZING
GROUND FAULT INTERRUPT
GALVANIZED IRON
GROUND FACE CONC. MAS. UNIT
GENERATOR
GRAB BAR
GALVANIZED
HOSE BIB
HARDENED
FIELD VERIFY
GA.
GALV.
GB
GI
GFI
GEN
GF CMU
GND
GR
GYP.
GST
GLUE LAM
GL
H
HARD
HB
HD BD
HC
HDR
HC
HDWE
H
G
F.V.SPM
STL.
STD
STA
S.S.
SYMM
SUSP.
STRUCT.
STOR.
TT
TB
TC
TCE
TDS
TEL
TFE
THK
T & G
T.O.
TOC
TOIL
THRESH
TOM
SQ.
YARD
TOP OF STEEL
TACK STRIP,
TYPICAL
TOP OF WALL
STRUCTURAL STEEL TUBING
UNFINISHED
VACUUM
VERTICAL
WIDE
BY
WATER RESISTANT
VERIFY IN FIELD
VINYL COMPOSITION TILE
VAPOR BARRIER
UNLESS NOTED OTHERWISE
UNDERWRITERS LABORATORY
UNDERGROUND
SINGLE-PLY MEMBRANE
STATION
STANDARD
STEEL
STORAGE
STRUCTURAL
SUSPENDED
TACKBOARD
TELEPHONE
TOP OF
TOILET
THRESHOLD
TOP OF CONCRETE
THICK, THICKNESS
TONGUE AND GROOVE
TOP OF FOOTING ELEVATION
TURNED DOWN SLAB
TOP OF CURB ELEVATION
TOP OF CURB
TREAD, THICK
STAINLESS STEEL
SYMMETRICAL
TOP OF MASONRY
SQUARE
POLY CARB
R. OR RAD.
ROW OR R/W
PERIMCSG CASING
ENT ENTRANCE
(SEE MECH DWGS)
EQUIVALENT
EQUAL
EASEMENT
EACH WAY
ELECTRIC WATER COOLER
EXISTING
FURRING
FOOTING
FIRE RETARDANT TREATED
FLEXIBLE
FLASHING
FLOOR
FINISH, FINISHED
FULL HEIGHT
FINISHED FLOOR ELEVATION
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FOUNDATION
FLOOR DRAIN (SEE MECH DWGS)
FIRE CODE
FABRICATE
EXPANSION
EXTERIOR
EQ.
EW
EXIST. OR EX.
EWC
ESMT
EQUIV
FC
FD
F
EXT.
EXP.
FAB
FE
FIN.
FL.
FH
FDN.
FEC
F.F.E.
FLASH
FRT
FTG.
FURR.
FLEX
REF
REBAR
RECIRC
RD
REINF.
REQ'D.
RH
R.O.
RESIL
RET.
REF.
S
RRT
SEP
SCHD.
SECT
SC
SIM.
SHT.
SHEATH
SPA
S.M.
SF
CULVERT
CUBIC
COUNTERSINK
ENCLOSURE
EMERGENCY
ELECTRIC, ELECTRICAL
ELEVATION
EXPANSION JOINT
EACH
DRAWING(S)
DOWNSPOUT
DITTO
DOWN
DIMENSION
DIAMETER
DRINKING FOUNTAIN
DETAIL
DEPRESSED
DOUBLE
CUBIC YARD
COLD WATER, CLOCKWISE
CU
CTSK
CULV
CW
CY
DDBL.
DEP
DET.
DF
DIA.
DIM.
DN.
DO
DS
DWG.(S)
EEA.
EJ
EL. OR ELEV.
ELEC
EMER
ENCL
PH
PERP.
PF CMU
PLAS
POL
PLYWD.
PLUMB
PSMB
PR.
PROJ.
PVC
PWG
PVMT
P.T.
Q.T.
Q
+/-
PREFAB.
R.
RCP
R
C
INSTALLED
CONDENSATE
(SAME MEANING AS OC)
CONTRACTOR FURNISHED AND
COLD ROLLED
CORRUGATED
CONTRACTOR
CONTINUOUS
CONSTRUCTION
CONDITION, CONDENSER,
CONCRETE
COLUMN
CONCRETE MASONRY UNIT
CLEAR
CLOSET
CEILING
CONTROL JOINT
CAST IRON
CHANNEL
CUBIC FEET
CERAMIC TILE
CEMENT
CENTER TO CENTER
CATCH BASIN, CHALKBOARD
CABINET
CB
CAB.
C/C
CF
CFI
CI
CJ
C.T.
CHAN
CEM
CLOS
CLR.
CMU
COL
CONC.
COND
CONST.
CR
CONT.
CONTR
CORRUG
CLG.
PART
PART. BD.
PASS
P/C
PERF
PC
P
NIC
NET
NO. OR #
NTS
O.C.
O.D.
O.F.
O
OF-CI
OH
OPNG.
OPP.
OFI
NOM
BOTTOM OF
BOTTOM
BEAM
BLOCKING
BLOCK
BITUMINOUS
BEVELED
BETWEEN
BOARD
AUTOMATIC
ASSEMBLY
APPROXIMATE
ACCESS PANEL
ANCHOR
ALUMINUM
AIR HANDLING UNIT
AGGREGATE
ABOVE FINISH FLOOR
ADHESIVE
ADJUST, ADJUSTABLE
AMERICANS WITH DISABILITIES
BUILT UP ROOFING
ADA
ADJ.
ADH.
A.F.F.
AGG.
AHU
ALUM.
ANCH.
BBD.
APPROX.
ASSY
AUTO
BIT.
BM.
B.O.
BEV.
BLK.
BLKG.
BOT. OR BTM.
BTWN.
AP
ACT
BUR
LTWT
MAS.
MATL.
MAX.
M
MC
MDO
MECH.
MTL.
MFR.
MH
MED.
MB
MISC.
M.O.
MTD.
MTG.
MULL.
MT.
ML & P
NNA
MIN.
LT
PERIMETER
RECIRCULATE
ROOF DRAIN
REINFORCING
REQUIRED
RESILIENT
SECTION
SCHEDULE
SOLID CORE
SHEATHING
SHEET
SIMILAR
SPACE(S)
SHEET METAL
SEPARATE, SEPARATION
RIGHT OF WAY
ROUGH OPENING
RIGHT HAND, ROUND HEAD
RETAINING, RETURN
REINFORCE, REINFORCED,
REFRIGERATOR
REFERENCE, REFER
REINFORCING BAR
SQUARE FEET, SAND FILL
RAISED RADIAL TILE
PLASTER
PHASE
POLISHED
PLYWOOD
PLUMBING
PAIR
PAVEMENT
QUARRY TILE
PENCIL SHARPENER BLOCK
PLUS OR MINUS
POLISHED WIRE GLASS
POLYVINYL CHLORIDE
PRESSURE TREATED
PROJECT, PROJECTED
PREFABRICATED
POLYCARBONATE SHEET
PREFACED CONC. MAS. UNIT
PERPENDICULAR
RADIUS
REINFORCED CONCRETE PIPE
RISER, RADIUS
PASSAGE
PARTITION
PERFORATED
PRECAST
POURED CONCRETE
PARTICLE BOARD
REQUIRED
NUMBER
NOT IN CONTRACT
MEANS EXACT DIMENSION
INSTALLED
CONTRACTOR INSTALLED
OPPOSITE
OPENING
OVERHEAD
OWNER FURNISHED,
OWNER FURNISHED AND
OUTSIDE FACE
OUTSIDE DIAMETER
ON CENTER
NOT TO SCALE
NOMINAL
METAL
MULLION
MOUNT
LIGHT
MARKER BOARD
NOT APPLICABLE
MOUNTING
MOUNTED
MASONRY OPENING
METAL LATH AND PLASTER
MISCELLANEOUS
MINIMUM, MINUTE
MANHOLE
MANUFACTURER
MEDIUM, MEDICINE
MECHANICAL
MEDIUM DENSITY OVERLAY
MISCELLANEOUS CHANNEL
MAXIMUM
MATERIAL
MASONRY
LIGHTWEIGHT
ACOUSTICAL
AIR CONDITIONING
ANCHOR BOLT
AT
&
@
AB
A/C
ACOUS
AND
A LL
LAM.
LH
LLV
LF
LONG LEG VERTICAL
LEFT HAND
LIGHT FIXTURE, LINEAR FEET
LAMINATE
ANGLE, LONG
BEARINGBRG. OR BRNG.
O.H. OPPOSITE HAND
WWF WELDED WIRE FABRIC
1. DEMOLITION REFERENCE NOTES FOR THIS PROJECT ARE INTENDED TO GENERALLY IDENTIFY THE SELECTIVE REMOVALOF EXISTING ITEMS AT LOCATIONS WHERE REQUIRED BUT, SHALL IN NO WAY RELIEVE THE CONTRACTOR OF THE FULLRESPONSIBILITY FOR EXAMINING AND VERIFYING THE FULL EXTENT OF EXISTING CONDITIONSPRIOR TO BIDDING THE PROJECT.
2. THE INTENT OF THE DEMOLITION NOTES IS TO PROVIDE A GENERAL OUTLINE FOR THE CONTRACTOR OF ITEMS TO BEREMOVED AND TO ALLOW FOR THE NEW CONSTRUCTION AS OUTLINED ELSEWHERE IN THE CONTRACT DOCUMENTS.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION AND REMOVAL OF ITEMS TO ALLOW FOR NEWCONSTRUCTION SHOWN OR NOT SHOWN ON DEMOLITION PLANS AS MAY BE REQUIRED.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PATCHING AND REPAIRING DUE TO DEMOLITION AND/OR REMOVAL OFEQUIPMENT TO CREATE A FLUSH, SMOOTH SURFACE PROPERLY PREPARED TO RECEIVE NEW FINISHES AS INDICATED.
4. WALLS AND SPACES BEHIND EXTERIOR FINISHES OR PARTIALLY REMOVED WALLS/ROOFS, ETC. SHALL BEPROTECTED FROM EXPOSURE TO WEATHER BY THE CONTRACTOR. WALLS/ROOFS, ETC. SHALL BE PROTECTED.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGED WALLS, ROOFS, EQUIPMENT, ETC. CAUSED BY THISDEMOLITION OR WEATHER EXPOSURE OF ITEMS THAT ARE TO REMAIN.
5. THE OWNER SHALL REMOVE AND ABATE ANY HAZARDOUS MATERIALS ENCOUNTERED. CONTRACTOR TO COORDINATEREMOVAL WITH OWNER.
6. REFER TO MECHANICAL AND/OR ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS PERTAINING TOTHE REMOVAL, RELOCATION AND/OR MODIFICATION OF ITEMS RELATED TO EXISTING MECHANICAL AND ELECTRICAL SYSTEMS.
7. SHOULD THE CONTRACTOR ENCOUNTER ANY MATERIALS DURING SELECTIVE DEMOLITION AND NEW WORK WHICH ARESUSPECTED BY THE CONTRACTOR TO BE OF AN UNKNOWN OR QUESTIONABLE COMPOSITION WITH RESPECT TOCONTAINING CONTAMINANTS WHICH MAY BE HAZARDOUS TO HUMAN HEALTH, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE OWNER OF SUCH FINDINGS.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER DISPOSAL OF ALL DEMOLISHED MATERIALS. ALL REMOVEDMATERIALS SHALL BE LEGALLY DISPOSED OF, UNLESS NOTED AS SALVAGED OR "RETURNED TO OWNER".
9. INFORMATION AND DRAWINGS INCLUDED IN THESE CONTRACT DOCUMENTS PERTAINING TO EXISTING CONSTRUCTION HAVEBEEN OBTAINED FROM FIELD INVESTICATIONS. THIS INFORMATION IS INCLUDED HEREIN WITH THE INTENT TO PROVIDE THECONTRACTOR WITH A BASIC UNDERSTANDING OF EXISTING CONDITIONS. ACTUAL CONDITIONS AND DIMENSIONS MAY VARYFROM THOSE INDICATED AND REQUIRE FIELD VERIFICATION.
10. MULTIPLE AREAS IN THE EXISTING BUILDING WILL HAVE MPE WORK AND REQUIRE SELECTIVE DEMOLITION. COORDINATEDEMOLITION WITH M/E DOCUMENTS.
11. REFER TO MPE DRAWINGS FOR NEW WORK WHICH MAY REQUIRE DEMOLITION WORK IN ADDITION TO ITEMS NOTED ON THEARCHITECTURAL DRAWINGS ALL SUCH WORK SHALL BE PERFORMED BY THE CONTRACTOR.
12. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS, MEASURES, ETC. REQUIRED TO COLLECT/DIVERT RAIN WATERFROM BUILDING AND ROOF DURING DEMOLITION AND INSTALLATION OF NEW WORK.
13. GENERAL CONTRACTOR TO DEMOLISH ALL LIGHTS PER ELECTRICAL DRAWINGS. MERCURY LIGHTS AND PCB LADEN BALLASTARE TO BE DISPOSED OF PROPERLY INTO AN EPA APPROVED LANDFILL.
14. SELECTIVELY DEMOLISH EXISTING CONCRETE SLABS AS REQUIRED FOR INSTALLATION OF SYSTEMS ANDUTILITIES ETC. REFER TO ARCHITECTURAL AND MPE DRAWINGS.
GENERAL DEMOLITION NOTES
1. IN THE EXISTING BUILDING, IT IS POSSIBLE HAZARDOUS MATERIALS MAY EXIST, INCLUDING, BUT NOT LIMITED TO ASBESTOSPRODUCTS. POLYCHLORINATED BIPHENYL (PCB) AND OTHER TOXIC SUBSTANCES. IF ANY WORK PERSON ENCOUNTERS ANYMATERIAL WHICH THEY SUSPECT MIGHT BE HAZARDOUS OR TOXIC, THEY SHALL IMMEDIATELY ADVISE THE OWNER. THECONTRACTOR SHALL TAKE IMMEDIATE AND APPROPRIATE ACTION TO PROTECT THE BUILDING USERS AND WORKERS INACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS, CODES AND REGULATIONS. THE ARCHITECT AND ARCHITECT'SCONSULTANTS SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY, PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF OREXPOSURE OF PERSONS TO HAZARDOUS MATERIALS IN ANY FORM AT THE PROJECT SITE, INCLUDING BUT NOT LIMITED TOASBESTOS, ASBESTOS PRODUCTS, POLYCHLORINATED BIPHENYL (PCB) OR OTHER TOXIC SUBSTANCES.
2. THE CONTRACTOR IS HEREBY ADVISED THAT SHERMAN-CARTER-BARNHART, PLLC IS NOT A DESIGN PROFESSIONAL IN THEDETERMINATION OF THE PRESENCE OF HAZARDOUS MATERIALS, NOR IS SHERMAN-CARTER-BARNHART, PLLC A DESIGNPROFESSIONAL INVOLVED IN MAKING RECOMMENDATIONS REGARDING THE TESTING, REMOVAL, ENCAPSULATION OROTHER CORRECTIVE MEASURES PERTAINING TO HAZARDOUS MATERIALS.
3. IF THE WORK WHICH IS TO BE PERFORMED UNDER THE CONTRACT INTERFACES IN ANY WAY WITH THE EXISTINGCOMPONENTS WHICH CONTAIN HAZARDOUS MATERIALS, IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THEOWNER REGARDING THE PROPER MEANS AND METHODS TO BE UTILIZED IN DEALINGWITH HAZARDOUS MATERIALS.
4. BY EXECUTION OF THE CONTRACT FOR CONSTRUCTION, THE CONTRACTOR HEREBY AGREES TO BRING NO CLAIM FORNEGLIGENCE, BREACH OF CONTRACT, INDEMNITY OR OTHERWISE AGAINST THE ARCHITECT, HIS PRINCIPALS, EMPLOYEES,AGENTS OR CONSULTANTS IF SUCH A CLAIM IN ANY WAY WOULD INVOLVE THE INVESTIGATION OF OR REMEDIAL WORKRELATED TO HAZARDOUS MATERIALS IN THE PROJECT.
5. BY EXECUTION OF THE CONTRACT FOR CONSTRUCTION, THE CONTRACTOR FURTHER AGREES TO DEFEND, INDEMNIFYAND HOLD THE ARCHITECT, HIS PRINCIPALS, EMPLOYEES, AGENTS AND CONSULTANTS HARMLESS FROM ANY SUCHASBESTOS OR OTHER HAZARDOUS MATERIALS RELATED CLAIMS THAT MAY BE BROUGHT BY THE CONTRACTOR'SSUBCONTRACTORS, SUPPLIERS OR OTHER THIRD PARTIES WHO MAY BE ACTING UNDER THE DIRECTION OF THECONTRACTOR PURSUANT TO THIS PROJECT.
HAZARDOUS MATERIALS NOTES
G1 (NIC) MEANS NOT IN CONTRACT. TO BE PROVIDED BY OWNER AND INSTALLED BY OWNER.
G2 DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS.
G3 ALL DIMENSIONS SHOWN ARE TO FACE OF METAL STUDS OR CENTERLINE OF STRUCTURE.
G4 ALL CONCEALED WOOD FRAMING AND PLYWOOD SHALL BE FIRE-RETARDANT TREATED (FRT) EXCEPT THAT NON-F.R.T.BLOCKING, NAILERS AND FURRING MAY BE USED WHERE INSTALLED IN ACCORDANCE WITH KBC CHAPTER 8(INCLUDING DIMENSIONAL WOOD BLOCKING, FIRE BLOCKING, REQUIREMENTS, ETC.). WOOD BLOCKING INSTALLED INACCORDANCE WITH KBC SECTION 603, FOR HANDRAILS, MILLWORK, CABINETS, WINDOWS AND DOORS ISNOT REQUIRED TO BE F.R.T. AT COPINGS AND ROOFING TERMINATIONS ALL BLOCKING SHALL BE PRESSURE TREATED(PT). WHERE WOOD BLOCKING IS IN CONTACT WITH CONCRETE, SUCH BLOCKING SHALL BEPRESSURE TREATED.
G5 ALL CHANGES IN FLOOR FINISHES SHALL OCCUR AT DOOR THRESHOLDS - TYPICAL, U.N.O.
G6 ALL CONTRACTORS SHALL REVIEW DWGS FOR MATERIALS AND MANUFACTURER'S MODEL NUMBERS LISTED ON DWGS.
G7 CONTACT BETWEEN DISSIMILAR METALS SHALL BE SEPARATED WITH BUTYL TAPE, OR OTHER APPROVED MEANS TOPREVENT GALVANIC CORROSION.
G8 CONTRACTOR SHALL PROVIDE ALL CONCEALED BLOCKING REQUIRED FOR ATTACHMENT AND SUPPORT OF EQUIPMENT,FIXTURES, WINDOWS, ETC.
G9 GYPSUM CEILING BOARD SHALL BE USED AT ALL HORIZONTAL APPLICATIONS OF GYPSUM BOARD.
G10 ALL EXPOSED CORNERS AND EDGES OF GYPSUM BOARD SHALL BE FINISHED WITH CORNER BEAD OR J-BEAD,RESPECTIVELY.
G11 PARTITIONS TYPES ARE TO MAINTAIN THEIR RESPECTIVE SEPARATION/RATING (IF ANY) FULL HEIGHT. ALL HVAC,ELECTRICAL, PLUMBING PENETRATIONS ARE TO BE SEALED/ SAFED/ DAMPERED TO COMPLY WITH LOCAL CODES.
G12 CONTRACTOR SHALL VERIFY ALL ROUGH OPENING SIZES FOR WINDOWS AND DOORS AND COORDINATE ANY REQUIREDADJUSTMENTS WITH THE ARCHITECT.
G13 SYMBOLS THAT REPRESENT MPE ITEMS ON ARCHITECTURAL DRAWINGS ARE FOR GRAPHIC PURPOSES ONLY. REFER TOMPE DOCUMENTS FOR SPECIFIC INFORMATION. SYMBOLS THAT REPRESENT STRUCTURAL ITEMS ON ARCHITECTURALDRAWINGS ARE FOR GRAPHIC PURPOSES ONLY.
G14 ALL WOOD BLOCKING, NAILERS, SILL PLATES, ETC. IN CONTACT WITH SLABS-ON-GRADE OR CONCRETE SHALL BEPRESSURE-PRESERVATIVE TREATED (P.T.). REFER TO THE DRAWINGS FOR OTHER LOCATIONS WHERE P.T. WOOD ISREQUIRED.
G15 ALL P.T. WOOD COMPONENTS SHALL BE SEPARATED FROM CONTACT WITH ADJACENT METALS WITH PERMANENTLYAFFIXED NO. 15 FELT, SELF-ADHERING ELASTOMERIC MEMBRANE, OR OTHER SUCH PERMANENT NON-CORROSIVESEPARATION MATERIAL.
G16 ALL ANCHORS, FASTENERS, ETC. IN CONTACT WITH P.T. WOOD COMPONENTS SHALL BE STAINLESS STEEL OR G-90 (MIN.)HOT-DIPPED GALVANIZED.
GENERAL NOTES
P3CENTERLINE OF STRUCTURAL STEEL, UNLESS NOTED OTHERWISE.
P4UNLESS NOTED OTHERWISE. REFER TO ROOM FINISH GROUPS.
P5
P6
CONNECTION AND ATTACHMENT/ BRACING OF NON-LOAD BEARING
INTERIOR PARTITION WALL TO STRUCTURE/ DECK ABOVE.
P7WATER RESISTANT GYPSUM BOARD TO BE INSTALLED.
P8BRACED TO UNDERSIDE OF ROOF FRAMING AT 8'-0" O.C. MAX. U.N.O.
ALL DIMENSIONS ARE TO FACE OF STUDS OR TO
INTERIOR GYPSUM BOARD EXPOSED TO VIEW SHALL BE PAINTED
REFER TO ROOM FINISH GROUPS FOR BASE CONDITION.
REFER TO PARTITION DETAILS ON SHEET A1.2 FOR SPECIFIC
WHERE GYPSUM ASSEMBLIES ARE SPECIFIED AT WET WALL LOCATIONS,
METAL STUD FRAMED PARTITIONS, SOFFITS, ETC. TO BE LATERALLY
0'-0"
INDICATES HEIGHT A.F.F. OF SCHEDULED WALL
PARTITION TYPE, REFER TO SCHEDULE, THIS SHEET. ALL WALLS TO BE EXTENDEDFULL HEIGHT TO UNDERSIDE OF EXISTING ROOF INSULATION ABOVE, U.N.O. REFERTO TYPICAL DETAIL 11/A1.2.
P1
P2
FIBER REINFORCED GYPSUM BOARD TO A HEIGHT OF 8'-0" A.F.F.
WITH REGULAR 5/8" GYP. BD. ABOVE. FIBER REINFORCED GYPSUM BOARD MAYBE USED FULL HEIGHT AT CONTRACTOR'S OPTION.
ALL INTERIOR GYPSUM PARTITIONS SHALL HAVE 5/8"
PARTITION TYPEGENERAL NOTES
WALL PARTITION SCHEDULE
5/8" GYPSUM BOARD /3 5/8" METAL STUDS @ 16" O.C. /1 1/2" MINERAL WOOL BATTINSULATION /1/2" GYPSUM BOARD /1/2" GYPSUM BOARD /
1STC 50
5/8" GYPSUM BOARD /3 5/8" METAL STUDS @ 16" O.C. /3" MINERAL WOOL BATTINSULATION /5/8" GYPSUM BOARD /
2STC 45
2A SAME AS TYPE 2OMIT INSULATION
5/8" GYPSUM BOARD /1 1/2" FURRING CHANNELS @24" O.C. VERT. /
3 ADJACENT WALLSUBSTRATE
3A5/8" GYPSUM BOARD /9 GAUGE EXPANDED METALREINFORCING /INSTALL SUPPLEMENTAL3 5/8" METAL FRAMING ASREQUIRED TO ATTACH TOEXISTING METAL BUILDINGGIRT SYSTEM. MIN. 24" O.C.
8" METAL STUDS @ 16" O.C. /8" MINERAL WOOL BATTINSULATION WITH CROSS TIESTO HOLD INSULATION /EXTERIOR METAL FINSH PANEL
43B5/8" GYPSUM BOARD /INSTALL SUPPLEMENTAL3 5/8" METAL FRAMING ASREQUIRED TO ATTACH TOEXISTING METAL BUILDINGGIRT SYSTEM. MIN. 24" O.C.
1A SAME AS TYPE 1 W/ 9 GAUGEEXPANDED METAL REINFORCINGBEHIND THE 5/8" GYPSUM BOARD
ROOM FINISH GROUPS
1 ANTI-STATIC RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENT COVE BASEGYPSUM BOARD CEILING (PAINT) ON SUSPENDED METALFRAMING WITH 9 GAUGE EXPANDED METAL REINFORCING
FLOOR:WALLS:BASE:CEILING:
2 RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENT COVE BASEGYPSUM BOARD CEILING (PAINT) ON SUSPENDED METALFRAMING (PROVIDE 9 GAUGE EXPANDED METALREINFORCING AT DETENTION CORRIDOR 103)
FLOOR:WALLS:BASE:CEILING:
3 RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENT COVE BASESUSPENDED ACOUSTIC TILE
FLOOR:WALLS:BASE:CEILING:
4 ANTI-STATIC RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENTSUSPENDED ACOUSTICAL TILE
FLOOR:WALLS:BASE:CEILING:
5 EPOXY RESINGYPSUM BOARD (PAINT)4” EPOXY RESINGYPSUM BOARD CEILING (PAINT) ON SUSPENDEDMETAL FRAMING WITH 9 GAUGE METAL REINFORCING
FLOOR:WALLS:BASE:CEILING:
6 CARPET TILEGYPSUM BOARD (PAINT)4” RESILIENT BASESUSPENDED ACOUSTICAL TILE
FLOOR:WALLS:BASE:CEILING:
7 EPOXY RESINGYPSUM BOARD (PAINT)4” EPOXY RESINSUSPENDED ACOUSTICAL TILE
FLOOR:WALLS:BASE:CEILING:
8 CARPET TILEGYPSUM BOARD (PAINT)4" RESILIENT BASEGYPSUM BOARD CEILING (PAINT)ON SUSPENDED METAL FRAMING WITH 9 GAUGEEXPANDED METAL REINFORCING
FLOOR:WALLS:BASE:CEILING:
GENERAL NOTES:
1. WHERE MORE THAN ONE FINISH IS LISTED REFER TO PLANS, SECTIONS, AND DETAILS.2. REFER TO TYPICAL BASE DETAIL, THIS SHEET.3. REFER TO TYPICAL FLOOR TRANSITION / THRESHOLD DETAILS, SHEET A1.2.4. REFER TO REFLECTED CEILING PLAN, SHEETS A1.2 FOR CEILING INFORMATION.5. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION AT CEILINGS.
EPOXY RESIN FLOORAND INTEGRAL BASE
REFER TOPLANS
1/2"
4"
SCHLUTER SCHIENE AE 80 STRIP
TILE WHERE APPLICABLE
WALL BASE, REFER TOROOM FINISH GROUPS
(CL
OF
HA
ND
LE)
4'-0
" A
FF
SEMI-RECESSED FIREEXTINGUISHER CABINET(FEC) REFER TO SPECS
5
N0.1
(CL
OF
HA
ND
LE)
4'-0
" A
FF
2x WOOD BLOCKINGAS REQ'D
SEMI-RECESSEDFIRE EXTINGUISHERCABINET (FEC)
CONT SEALANT ATPERIMETER OF CABINET
STANDARDCABINETEXTERIOR TRIM
ALL WORK PERTAINING TOFIRE EXTINGUISHERS SHALLBE DONE IN ACCORDANCEWITH NFPA 10
* REFER TO FLOOR PLAN
GENERAL
CODE: KENTUCKY BUILDING CODE 2013 4TH EDITION
USE GROUP: UNSEPARATED MIXED USE - EXISTING S-1 (STORAGE) AND EXISTING B (OFFICE SUITE)
CONSTRUCTION TYPE: EXISTING 2B
FIRE PROTECTION: EXISTING UNSPRINKLERED
ALLOWABLE BUILDING HEIGHT AND AREA (EXISTING)
S-1 IS MOST RESTRICTIVE
ALLOWABLE AREA (TABLE 503): 17,500 GROSS SF
EXISTING AREA (S-1 STORAGE): 8,537 GROSS SF
EXPANDED AREA (B OFFICE SUITE): 2,266 GROSS SF
TOTAL EXISTING AREA: 10,803 GROSS SF
CALCULATED OCCUPANT LOAD: 2,266 GROSS SF / 100 SF PER OCC. (B OCCUPANCY) = 23 OCCUPANTS
ALLOWABLE HEIGHT: 2 STORIES - 55'-0"
EXISTING HEIGHT: 1 STORY - 19'-0"±
CODE INFORMATION
CODE KEY PLAN
EXISTING STORAGEBUILDING(S-1) 8,537 SFNO WORK
CA
NO
PY
CA
NO
PY
EXISTING OFFICESUITE (B) 1,143 SF
OFFICE SUITEEXPANSION (B) 1,123 SF
TOTA
L A
RE
A O
FIM
PA
CT
(B) 2
,266
SF
INSTALL CONSTRUCTIONFENCE
PROVIDE 6" THICK REDSTRIPED BOX WITH 6" ARIELLETTERING AS INDICATED
CBP SecurityArea
CBP SecurityArea
CB
P S
ecur
ityA
rea
CB
P S
ecurityA
rea
EXISTING CONCRETEAIRFIELD APRON
104' - 4"
108'
- 8"
43' - 5"
10'-0" ±
30'-1
" ±
EXISTING BUILDING
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
10/1
8/2
017 2
:46:2
6 P
M
N0.1
MM
10/20/2017
1508
JSS, BKL
AB
BR
EV
IAT
ION
S, S
YM
BO
LL
EG
EN
D, G
EN
ER
AL
NO
TE
S,
PA
RT
ITIO
N T
YP
ES
AN
D C
OD
EIN
FO
RM
AT
ION
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NLE
XIN
GT
ON
, K
EN
TU
CK
Y
1508
BLU
E G
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
3" = 1'-0"2
TYP. RESIN BASE DETAIL
1 1/2" = 1'-0"3
TYP. BASE DETAIL
3/4" = 1'-0"4
TYP. FEC ELEVATION
3/4" = 1'-0"5
FEC SECTION
1" = 20'-0"1
SITE PLAN TRUENORTH
PLANNORTH
No. Description Date
DN
DN
NEW WORK KEYNOTESX
SYMBOLS LEGEND
WALL TYPE(SHEET N0.1)
NEW WORK KEY NOTES(SHEET A1.1)
ROOM FINISH GROUPS(SHEET N0.1)
ROOM NUMBER
#
#
RFG101
Name
EXISTING WALL / CONSTRUCTIONTO REMAIN
EXISTING CONSTRUCTION TO BE REMOVED -SEE SELECTIVE DEMOLITION NOTES
DEMOLITION KEY NOTE(SHEET A1.1)
#
NEW CONSTRUCTION
SIGN TYPE(SHEET A1.3)
CEILING KEY NOTE(SHEET A1.2)# #
RFG108A
PRE-PROCESSINGPASSENGER
WAITING
3
RFG110
PROCESSING
4
RFG101
CBP GENERALOFFICE
6
RFG105
INTERVIEW
8
RFG104
SEARCH
5
RFG112
EXISTING MENSTOILET
2
113
EXISTINGWOMENS TOILET
115
EXISTING JANITOR
114
EXIST.ELECTRICAL
RFG103
DETENTIONCORRIDOR
2
RFG101A
CLOSET
6
7
3 5/
8"20
'-10
1/8"
3 5/
8"
3 5/8" 11'-7" ± 3 5/8" 11'-6" 3 5/8" 7'-9 1/8" 3 5/8" 13'-2" 3 5/8" 8'-6" 3 5/8" 8'-5 3/8" 3 5/8"
10'-0
"
3 5/
8"
4'-1
0 3/
8"
3 5/
8"
15'-6
" ±
1A
3A
1A
4
1A
1A
1
3
4
3B
3B
3B
INFILL1A
1A
3A
INFILL
2
2
RFG107
STORAGE
2
RFG106
LAN/TELCO
12A
2A
3
3B
2A
4
INFILL
1A
7'-0
"3
5/8"
1'-4
5/8
"
TO FIN.1'-3"
RFG109
TOILET
7
3B 2A
EXIST.SAFE
2
3 3
9
5
6
2'-1
"3 3/4" 7'-9"
4'-6 3/4" 1'-10"
1'-3 5/8"
3 5/8" 10'-0" 2'-10" 3'-0" 10'-0"8
CHASE
COPIER
9
9
2A
4'-4 9/16"
3 5/8"
12'-4"
4'-8
"
INFILL
4
RFG111
EXIT VESTIBULE
3
2
2A
109
107 106
103
105 104
101
101A
110
111
108
2
2
1
11 3
/4"
1'-0
"3
5/8"
4"
10'-4"
10'-4" 3
10'-4"3B3B3B
10'-4"
10'-4"
10'-4"
4
9'-4"3A3A9'-4"
3A9'-4"
10'-4"
3A3B 10'-4"
10'-4"
10 10 10 10
3A3A9'-4"
3A
9 9
10'-4"
10
10
2'-0"
1'-3
"
9'-4"
9
2A 10'-4"
2'-3
3/8
"
30X34X24
B2522
FOR REF
OPEN BLW.
30X24X14
W2052
W30X24X14
W9330WALL
BASE
REF BLW.(N.I.C.)
FILLER FOR 25"OPENING FORUNDERCOUNTER REF.
4'-8 3/16" 5'-2"
2'-3 3/16" 2'-5"
1'-0" 3'-4"4'-6"
1'-0" 3'-4"
1'-8 1/2"
R.O.
4'-4" 1'-8 1/2"
4'-6
"3'
-4"
R.O
. - F
.V.
3'-4
"
R.O
. - F
.V.
3'-4
"
R.O
. - F
.V.
8'-0
"
R.O
. - F
.V.
8'-0
"
7'-0
"
3'-4" 1'-2"
8" 3'-4"
A
1'-7" TO FIN.
C
X
ABOVEDOOR F
HUNGFROMCEILINGABOVE
D
HUNG FROMCEILING ABOVE
E
L
G H
HUNGFROMCEILINGABOVE
O
I
WK
N
M
Q
P S T
R
11
109A
12
12
12
11
X
V
V
U
RFG108B
POST-PROCESSINGPASSENGER
WAITING
3
3B10'-4"
EQ
EQ
16
18
12
12
12
12
D
HUNG FROMCEILING ABOVE
12
16
3A9'-4"
9
20
20
20
20
1717
13
1717
EQ EQ
FEC
15
15
15
14
13
13
1
1
1
1717
17
2A
16
4
A1.1
3B 9'-4"
17
17
9'-4"
9'-4"
1 23
4
5
6
7
8
9
19
9'-4"
2'-0" 1'-7 1/4"
2'-1
5/8
"1'
-2"
3B
3B3B 3B3B
3B
3'-0"
10
DEMOLISH WALL TO MINIMUM 4"BELOW EXISTING SLAB. INFILLSLAB WITH NEW CONCRETE FLUSHWITH ADJACENT SLABS. PREPARETO RECEIVE NEW FLOOR FINISHES.
DEMOLISH EXISTING WALLFINISHES AS REQUIREDFOR INSTALLATION OFNEW FEC.
10'-4"
TYP.TYP.
9
TYP.
9
TYP.
17
21
A1.28
A1.29
@METAL
@BRICK
TYP. @INFILL
1
ABV. &BLW.
21
14
J
RETURN GYPSUMBOARD TO FRAME.
JKQ
23
ADA
2
2
1
2
2
4
4
1
2
2
2
2
4
4
5
3
7
5
4
3
8
1010
7
4
3
3
9
9
44
7
5
7
53
3
9
7
5
6
3 3
2
2
1
2
2
4
4
1
2
22
3
7'-2" R.O.
47
3
15
12
12
12 12
11
5
5
11
14141414
16
14
2
3
16 16 16 16 16
3
14
16
7
17
5
18
13
17
17
17
18
18
19
7
7
12
3
13
20
SELECTIVE DEMOLITIONKEYNOTES
GENERAL NEW WORKNOTES
1. REFER TO MECH./ELEC. DRAWINGS FOR SPECIFIC NOTES REGARDING MECH/ELECITEMS NOT SHOWN ON THIS SHEET.
2. REFER TO SHEET N0.1 FOR GENERAL NOTES AND PARTITION TYPES.
CASEWORK NOTES
TYPICAL WALL AND BASE CASEWORK MODELNUMBERS SHOWN ARE TMI SYSTEMSDESIGN CORP. (PHONE NO. 1-800-456-6716)AND REPRESENT THE LEVEL OF QUALITYREQUIRED AND SHALL BE USED AS THEBASIS FOR EQUAL PRODUCTS. HEIGHTINDICATED IS TO TOP OF COUNTERTOP.
MODEL #
## - ## - ##WIDTH DEPTH
HEIGHT
TMI LEGEND:
1. MOUNT ALL CASEWORK PER ADA GUIDELINES.
2. PROVIDE FINISHED END PANELS AT ALL EXPOSED LOCATIONS.
3. PROVIDE 4" BACK AND SIDE SPLASH AT ALL WALL LOCATIONS.
4. ALL CABINETS AND BASES SHALL HAVE LOCKS ON DOORS AND DRAWERS.
5. ALL BASE CABINETS AND DRAWER CABINETS SHALL HAVE COUNTER TOPS.
6. PROVIDE INFILL PANELS AS REQUIRED TO CONCEAL VOIDS AT ALL CABINETS.
7. MOUNT TOP OF WALL CABINETS AT 7'-0" A.F.F., UNLESS NOTED OTHERWISE.
8. PROVIDE CONT. WD. BLOCKING AT WALL LOCATIONS FOR MOUNTING OF CASEWORK.
9. PROVIDE WD. BLOCKING AS NEEDED TO SUPPORT COUNTER TOP. COORD. W/ UNDERCOUNTER EQUIPMENT.
10. PLUMBING PIPES TO RUN BELOW CASEWORK AS SHOWN ON MECH DWGS.
XXXXX
GENERAL DEMOLITIONNOTES
REFER TO N0.1 FOR HAZARDOUS MATERIALNOTES AND GENERAL DEMOLITION NOTES.
PROJECTIONS
ADA WATER CLOSETREQUIREMENTS.
(SEE FIGURES 604.7PER ICC/ANSI
A117.1-2009 FORFURTHER
INFORMATION)
5
1'-0" 3'-6"
MAX MIN
6
7
3'-4"℄
1'-6
"3'
-4"
CL
2'-1
0"
9"
MAX
1'-3
" M
IN
CL
CLCL
CL
CL
GENERAL TOILET ACCESSORY NOTES:
TOILET ACCESSORY SCHEDULE
SANITARY NAPKIN DISPOSAL
18"L S.S. GRAB BAR (VERTICAL)
42"L S.S. GRAB BAR
26" A.F.F. TO TOP
34" A.F.F. TO CENTER
39" A.F.F. TO BOTTOM
36"L S.S. GRAB BAR 34" A.F.F. TO CENTER
DOUBLE ROLL TOILET TISSUE HOLDER 19" A.F.F. TO CENTER
MTG. HT.ACCESSORY
WALL PLATE MIRROR (24" WIDE) 40" A.F.F. TO BOTTOM.
HEAVY DUTY COAT HOOK 48" A.F.F. TO CENTER
SOAP DISPENSER (WALL MOUNTED) 48" A.F.F. TO OPERATOR
MODEL
REFER TO SPEC (REFER TO 4/A1.2)
BOBRICK B-2116
BOBRICK B-2111
BOBRICK B-270
BOBRICK B-2840
1. PROVIDE SOLID WOOD BLOCKING AS REQUIRED FOR SUPPORT OF ALL ACCESSORIES REGARDLESS IF GENERAL CONTRACTOR OR OWNER PROVIDED.
2. UNLESS NOTED OTHERWISE, MODEL NUMBERS IN SPECIFICATIONS DENOTE TOILET ACCESSORY PRODUCTS OFFERED BYBOBRICK WASHROOM EQUIPMENT, INC. AND REPRESENT THE LEVEL OF QUALITY REQUIRED.
3. ALL ACCESSORIES (EXCEPT #7) SHALL BE LOCATED HORIZONTALLY AND MOUNTED TO SPECIFIC POINTS A.F.F. IN ACCORDANCE WITH ALL APPLICABLEREQUIREMENTS OF THE "AMERICANS WITH DISABILITIES ACT" (A.D.A.). ITEM #7 IS TO BE MOUNTED VERTICALLY (REFER TO 3/A1.1 FOR TYPICAL GRABBAR MOUNTING LAYOUT AT TOILETS).
4. REFER TO MECHANICAL, PLUMBING, ELECTRICAL DRAWINGS, AND SPECIFICATIONS FOR PLUMBING FIXTURES AND CONTROLS. ALL EXPOSED PIPING ATHANDICAPPED LAVATORIES MUST BE INSULATED AND COVERED WITH RIGID JACKET.
5. COORDINATE FINAL PLACEMENT OF ACCESSORIES WITH ADJACENT CONSTRUCTION OR OTHER ACCESSORIES TO CONFIRM MOUNTING HEIGHTS.
6. WHERE ADJACENT TO WALLS, CENTERLINES OF ALL TOILETS ARE 1'-6" FROM FINISH FACE OF ADJACENT WALLS.
7. GRAB BARS ARE TO BE DETENTION GRADE CONSTRUCTION WITH TAMPER PROOF FASTENERS. REFER TO DETENTION FURNITURE SPEC.
-
1
2
3
4
5
6
7
8
9 PAPER TOWEL DISPENSER/TRASH RECEPTACLE 48" A.F.F. TO SLOT GEORGIA-PACIFIC 59466/59491 (RECESSED)
REFER TO SPEC (REFER TO 4/A1.2)
REFER TO SPEC (REFER TO 4/A1.2)
BOBRICK B-290 2436
10 FOLDING CHANGING STATION (SURFACE MOUNTED) 34"TO TOP (WHEN FOLDED) AMERA PRODUCTS, INC MODEL 100-SS-SM
FOR WALL TYPE SEEFLOOR PLAN.
INTEGRAL COVED P. LAM.BACKSPLASH, SEALANTCONT. WHERE MEETSWALL (SIDE SPLASH, ENDS)
PLAS. LAM. ON 3/4"PLYWD W/ CHAMFEREDEDGES ON CON'T. 2x4WD. FRAMING FRONTAND BACK
KICKERS AND CLEATS -PLAS. LAM. ON 3/4"PLYWOOD (NOT ONCASEWORK)
NOTE: BRACKET SUPPORTS,SPACED AS REQ'D. TOSUPPORT COUNTER TOPWITHOUT SAG, 42" MAX. O.C.
CLEARANCEPER ANSI/ADASTANDARDS
BASE - REFER TO ROOMFINISH GROUPS
BACKSPLASH TO MATCHADJACENT CASEWORK INHEIGHT AND COLOR
1 1/
2"1
1/2"
1 1/
2"1'
-7 1
/2"
7"
-
GROMMET@ 36" O.C.
2 1/2" Ø CUTOUT ATALL INTERMEDIATESUPPORTS.
REFER TO PLANS
2'-7
"
2'-0" U.N.O.
4"
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
FIN
AL D
OC
UM
EN
TS
10/1
8/2
017 2
:46:1
9 P
M
A1.1
MM
10/20/2017
1508
JSS, BKL
DE
MO
LIT
ION
AN
D N
EW
WO
RK
FL
OO
R P
LA
NS
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NLE
XIN
GT
ON
, K
EN
TU
CK
Y
1508
BLU
E G
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
1 (4 POST) 18" DEEP BY 48" LONG HEAVY DUTY ADJUSTABLE METAL SHELVING UNITS.REFER TO SPECS.
2 INTERVIEW TABLE SECURED TO CONCRETE SLAB W/ DURESS BUTTON. REFER TO SPECS.
3 SLED BASE SIDE CHAIR SECURED TO CONCRETE SLAB. REFER TO SPECS.
4 PROCESSING PODIUM. REFER TO DETAILS ON SHEET A1.3.
5 STEEL BENCH SECURED TO CONCRETE SLAB. REFER TO SPECS.
6 EXAMINATION TABLE SECURED TO CONCRETE SLAB. REFER TO SPECS.
7 PUBLIC TRANSACTION WINDOW/TRAY. REFER TO SPECS.
8 VINYL COATED SHELF WITH INTEGRAL CLOTHES HANGER ROD @ 8'-0". REFER TO SPECS.
9 FURNITURE BY OWNER. (N.I.C.)
10 EXISTING STEEL COLUMN TO REMAIN. PREP FOR NEW WORK.
11 WINDOW TO RECEIVE HORIZONTAL MINI BLIND. REFER TO SPECS.
12 DOOR TO RECEIVE CARD READER. REFER TO HARDWARE SPECIFICATIONS AND MEPDRAWINGS.
13 LINE OF FLOORING TRANSITION.
14 WATER FOUNTAIN. REFER TO MEP DRAWINGS.
15 DASHED LINE INDICATES PAINTED 3/4" FIRE RATED PLYWOOD FULL HEIGHT TO BOTTOMOF CEILING OVER GYPSUM BOARD.
16 DURESS BUTTON. REFER TO MEP DOCUMENTS.
17 PROVIDE WALL CORNER GUARD. REFER TO SPECS.
18 BAGGAGE EXAMINATION TABLE. REFER TO SPECS.
19 PISTOL LOCKER. FINALIZE LOCATION IN FIELD WITH OWNER. REFER TO SPEC.
20 EXISTING DOOR TO REMAIN.
21 EYEWASH. REFER TO MEP DRAWINGS.
22 REINSTALL SALVAGED RESTROOM SIGN.
23 PROVIDE DOOR RELEASE CARD READERS FOR DOORS 108 AND 110. REFER TO MEP ANDHARDWARE SPECS.
TRUENORTH
PLANNORTH
1/4" = 1'-0"2
NEW WORK FLOOR PLAN
1/4" = 1'-0"1
DEMOLITION FLOOR PLAN
1 SALVAGE EXISTING OVERHEAD DOORS IN THEIR ENTIRITY INCLUDING TRACKS,MOTORS, CONTROLS, ETC. TURN OVER TO OWNER.
2 DEMOLISH EXISTING BOLLARD IN ITS ENTIRETY. PATCH INTERIOR/EXTERIOR SLABWITH MATCHING FINISH.
3 DEMOLISH EXISTING WALL FULL HEIGHT. U.N.O. PREPARE SUBSTRATE FOR NEWWORK.
4 DEMOLISH EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY, INCLUDINGELECTRIFIED HARDWARE. PREPARE FOR NEW WORK.
5 DEMOLISH EXISTING FLOOR AND BASE FINISHES IN THEIR ENTIRETY INCLUDINGADHESIVES. PREPARE SUBSTRATE FOR NEW WORK.
6 DEMOLISH 8'-0"± HIGH PLYWOOD AROUND PERIMETER OF ROOM.
7 DEMOLISH EXISTING SUSPENDED CEILING AND SOFFITS IN THEIR ENTIRETY.
8 DEMOLISH CABINETS AND SINK/REFRIGERATOR.
9 SALVAGE EXISTING OFFICE PARTITION AND DESK. TURN OVER TO OWNER.
10 SALVAGE EXISTING STAINLESS STEEL BENCH AND TABLE. TURN OVER TO OWNER.
11 EXISTING TOILET PARTITION TO REMAIN. REMOVE AND REINSTALL AS REQUIREDFOR INSTALLATION OF NEW WORK.
12 EXISTING PLUMBING FIXTURES TO REMAIN.
13 REMOVE AND REINSTALL WALL MOUNTED TOILET ACCESSORIES. RELOCATE ASREQUIRED FOR NEW CONSTRUCTION.
14 EXISTING COLUMN AND BASE PAD TO REMAIN.
15 RELOCATE EXISTING WATER FOUNTAIN TO ACCOMMODATE NEW WORK. REFER TOMEP.
16 DEMOLISH EXISTING GYPSUM BOARD FINISH FULL HEIGHT ON EXTERIOR / PARTYWALL. FRAMING TO REMAIN.
17 EXISTING DOOR AND FRAME TO REMAIN.
18 NO ARCHITECTURAL WORK REQUIRED.
19 DEMOLISH FLOOR TILE TO EXTENTS SHOWN.
20 SALVAGE EXISTING RESTROOM SIGNAGE FOR REINSTALL
1/2" = 1'-0"3
TYP. ADA GRAB BAR LAYOUT
1" = 1'-0"4
ADA COUNTER
No. Description Date
GENERAL NOTES:1. REFER TO TYPICAL HEAD AND JAMB DETAILS ON SHEETS A1.2 AND ALUM. FRAME
ELEVATIONS ON A1.2.
2. INSTALL 2x BLOCKING BETWEEN STUDS FOR WALL MOUNTED DOOR STOPS IN STUD PARTITIONS.
3. ALL HOLLOW METAL DOORS AND FRAMES SHALL BE PAINTED PER THE SPECIFICATIONS.
HOLLOW METAL FRAME NOTES:1. PROVIDE REINFORCING 12 GA. CHANNEL IN FRAME HEAD AT ALL
H.M. FRAMES WHERE TOTAL FRAME WIDTH IS GREATER THAN 4'-0".
2. PROVIDE 11 - GA x 2" WIDE STRAPS AT 8" O.C. IN H.M. FRAME HEADS GREATER THAN 2" IN HEIGHT, TYPICAL.
3. LINTEL BEAM LENGTH SHALL BE M.O. PLUS 16" LONG (MIN 8" BEARING AT EACH END UNLESS NOTEDOTHERWISE). LINTEL PLATE LENGTH SHALL BE M.O. LESS 1/4" LONG (1/8" AT EACH END MAX.). REFER TOSTRUCTURAL DRAWINGS FOR LINTEL INFORMATION.
4. WHERE GLAZING IS SHOWN, THE FRAME FABRICATOR SHALL PRE-DRILL STOPS AND FRAME TO RECEIVEMOUNTING SCREWS. VERIFY LOCATIONS AND DEPTH OF GLAZING MATERIAL,EQUAL SPACE SCREWS.
5. UNLESS NOTED OTHERWISE, THE HINGE SIDE OF H.M. FRAME AT GYP. AND MTL. STUD WALLS SHALL BE INSTALLED 4" FROM ADJ. WALLS.
6. ALL EXTERIOR HOLLOW METAL FRAMES SHALL BE GALVANIZED, 14 GA.
7. CUT HOLE IN FRAME IN EXISTING OPENING TO GROUT FRAME SOLID. WELD IN NEW FILLERPLATE FLUSH. GRIND SMOOTH AND PREP FOR PAINTING.
DOOR AND FRAME NOTES:
DOOR NOTES:1. UNDERCUT AT NON-RATED S.C. WOOD DOORS 1/2" FROM BOTTOM OF DOOR TO SCHEDULED FLOOR FINISH.
2. UNDERCUT AT EXTERIOR DOORS 1/8" MAX. FROM BOTTOM OF DOOR TO TOP OFTHRESHOLD, WEATHER STRIP MUST CLOSE TIGHTLY AGAINST THRESHOLD.
3. ALL EXTERIOR HOLLOW METAL DOORS BE GALVANIZED AND HAVE FLUSH CLOSURECAPS16 GA. WELD CONT. TOP AND BOTTOM.
4. PROVIDE THRESHOLDS AS REQUIRED AT DOORS. SEE THIS SHEET TYPICALTHRESHOLD DETAILS AND FLOOR FINISHES.
GLASS AND GLAZING NOTES:1. PROVIDE FULLY TEMPERED (FT) GLASS WHERE INDICATED ON SCHEDULE AND/OR
SHOWN ON DOOR AND FRAME TYPES, OR AS REQ'D BY CODE.
2. ALL GLAZING AND GLAZING STOPS IN H.M. FRAMES ARE TO BE INSTALLED AT SECURESIDE OF INTERIOR FRAMES AND INTERIOR SIDE OF ALL EXTERIOR FRAMES.
HARDWARE NOTES:1. PROVIDE AND INSTALL ALL HARDWARE IN ACCORDANCE WITH ANSI A117.1 - 2009.
REMARKS:1. CARD READER. REFER TO HARDWARE SPECIFICATIONS AND MEP DRAWINGS.
2. PROVIDE TINTED GLASS IN DOOR AND FRAME.
3. PROVIDE LAMINATED GLASS IN DOOR FRAME.
4. FIELD VERIFY EXISTING OPENING SIZE. FABRICATE DOOR AND FRAME TO FIT.
5. DELAYED EGRESS HARDWARE. REFER TO SPECIFICATIONS.
6. PROVIDE DOOR RELEASE CARD READER AT BAGGAGE PODIUM. COORDINATE WITH MEP ANDDOOR HARDWARE.
3
9'-0"
3
9'-0"
3
9'-0"
3
9'-0"
2
9'-0"
1
10'-0"
1
9'-0"
1
10'-0"
1
9'-0"
5
8
5 5
5
5
4
8'-8"
F.V.
2'-6"
MODIFY EXISTINGSUSPEDED CEILINGFOR NEW WORK
7
6
6
6
1
9'-0"
6
12
A1.2
REFLECTED CEILINGPLAN KEY NOTES
GENERAL CEILING NOTES
2' x 2' SUSPENDED ACOUSTICAL CEILING.NO ACOUSTICAL TILE SLIVERS LESS THAN 6".
INTERIOR SUSPENDED GYP. BD.SOFFITS OR CEILINGS, PAINT U.N.O.REFER TO REFERENCED DETAILS.
1. = KEYNOTES
2. SEE M/E/P DRAWINGS FOR LIGHTING FIXTURE TYPE, SIZE, AND OTHER REQUIREMENTS.
3. REFER TO FLOOR PLANS AND PARTITION NOTES FOR LOCATIONS OF FULL HEIGHTWALLS.
4. GYPSUM CEILING BOARD SHALL BE USED AT ALL GYPSUM APPLICATIONS.
REFLECTED CEILING LEGEND
#
#
1. SUSPENDED ACOUSTICAL 2'X2' CEILING TILE.
2. SUSPENDED GYP. BOARD CEILING (PAINT) ON SUSPENSION SYSTEM. PROVIDE SEALANTSOFT JOINT AT PERIMETER OF ROOM.
3. SUSPENDED GYP. BOARD CEILING (PAINT) ON SUSPENSION SYSTEM WITH 9 GAUGE METALREINFORCING. PROVIDE SEALANT SOFT JOINT AT PERIMETER OF ROOM.
4. GYP. BOARD SOFFIT, REFER TO SOFFIT DETAILS. (PAINT)
5. NO WORK. EXISTING TO REMAIN. U.N.O.
6. CEILING MOUNTED SIGN. REFER TO SIGNAGE INFORMATION
7. NO ARCHITECTURAL WORK REQUIRED.
8. PAINT EXISTING GYPSUM CEILING BOARD TO REMAIN.
GLASS (AS SCHEDULED)
GLASS STOP, REFER TO SCHED.FOR GLAZING LOCATIONS
PAINTED H.M. DRYWALLFRAME, PROVIDE ADJUSTABLECOMPRESSION ANCHOR ATEACH JAMB
CONT. SEALANT AROUNDFRAME, TYP. AT BOTH SIDES
PROVIDE DOUBLE STUDSAT EACH JAMB (TYP.)
REFER TO PLANS
2"
*
1/2"
1/2"
5 7/
8" T
YP
.6
1/4"
FO
R W
ALL
TY
PE
"1"
U.N.O.
4" MIN.
ADJACENT WALL WHEREAPPLICABLE
H.M. FRAME (PAINT)
SEALANT CONT. AROUND FRAME,TYP. AT BOTH SIDES
GLASS, REFER TO FRAMEELEVATIONS
GLASS STOP CONT. ONSECURE SIDE OF FRAME
REFER TO ROOM FINISH GROUPSFOR BASE AND FLOOR FINISH
10"
TYPE "1"
5 7/8" TYP.6 1/4" WALL
EXIST. CONC.FLOOR SLAB
GLASS (AS SCHEDULED)
GLASS STOP, REFER TO SCHED.FOR GLAZING LOCATIONS
H.M. DRYWALL FRAME (PAINT)
CONT. SEALANT AROUNDFRAME, TYP. AT BOTH SIDES
PROVIDE 6" STUD BOXBEAM AT HEAD, TYP.
REFER TOPLANS
2"
*
1/2"1/2"
5 7/8" TYP.6 1/4" FOR WALL TYPE "1"
3"
FIE
LD V
ER
IFY
1'-0
5/8
"
BACKER ROD AND SEALANT,CONT. (BOTH SIDES)
ALUM. STOREFRONT SYSTEM. REFERTO ALUM. FRAME ELEVATIONS ANDPLANS (PROVIDE SHIMS AS REQ'D.)
'LC' TRIM AND SEALANT, CONT. METAL CORNER BEAD, CONT.
NEW PRE-FIN. S.M. PERIMETERTRIM AROUND EXIST. OPENING.FASTEN TO EXIST. CONSTRUCTION
EXIST. CONST. TO REMAIN(SHOWN SHADED)
3B
EXIST. METAL PANEL SYSTEM
FILL SHIM VOIDS WITH LOWEXPANSION SPRAY FOAM.PROVIDE RIGID INSULATIONINSERTS IN FRAME ATPERIMETER.
BACKER ROD AND SEALANT,CONT. (BOTH SIDES)
ALUM. STOREFRONT SYSTEM.REFER TO ALUM. FRAMEELEVATIONS AND PLANS(PROVIDE SHIMS AS REQ'D.)
'LC' TRIM AND SEALANT, CONT.
METAL CORNER BEAD, CONT.
NEW PRE-FIN. S.M. PERIMETERTRIM AROUND EXIST. OPENING.FASTEN TO EXIST. CONSTRUCTION
EXIST. CONST. TO REMAIN(SHOWN SHADED)
EXISTING THIN BRICK SYSTEM
PROVIDE SUPPLEMENTAL FRAMING TOSUPPORT SHEATHING AS REQUIRED
3B
FILL SHIM VOIDS WITH LOWEXPANSION SPRAY FOAM.PROVIDE RIGID INSULATIONINSERTS IN FRAME ATPERIMETER.
NEW PRE-FIN. S.M. ANCHOR TO NEW ANDEXIST. METAL STUDS AND METAL PANELS.PROVIDE BACKER ROD AND SEALANT AT JOINT EXIST. CONST. TO REMAIN
(SHOWN SHADED)
4 INFILL
3B3B
GYPSUM CONTROL JOINT
NEW PRE-FIN. S.M. TRIM BELOW.MATCH EXISTING IS SHAPE ANDCOLOR
EXIST. S.M. TRIM BELOW
EXIST. CONST. TO REMAIN(SHOWN SHADED)
SELF-ADHERED GRANULAR UNDERLAYMENTOVER 5/8" EXTERIOR GRADE GYPSUMSHEATHING. FIELD VERIFY TO MATCHEXISTING. PROVIDE SUPPLEMENTAL FRAMINGTO SUPPORT SHEATHING AS REQUIRED
NEW PRE-FIN. S.M. ANCHOR TO NEW ANDEXIST. METAL STUDS AND METAL PANELS.PROVIDE BACKER ROD AND SEALANT AT JOINT
THIN BRICK TO MATCH EXIST. FACE BRICK OVERLOXON METAL REINFORCED PANEL OR EQ.(EXTEND FASTENERS INTO METAL FRAMING)
4INFILL
3B3B
EXISTING THIN BRICK SYSTEM
GYPSUM CONTROL JOINT
RE
FER
TO
SC
HE
DU
LE
TYP
.
3'-4
"
SCHEDULE
REFER TO
PANICHARDWAREWHEREAPPLICABLE,TYP.
F
RE
FER
TO
SC
HE
DU
LE
SCHEDULE
REFER TO
5" 5"
7"
10"
2'-3
"6"
FG
LINE OF
FINISH FLOOR
LINE OF
FINISH FLOOR
2"
3'-0" ±2"
10"
1' -
10"
2"4'
- 2"
±2"
3'-4" ±
10"
1' -
10"
2"4'
- 2"
±2"
2' -
8"2"
8'-0" ±
2
2"
2'-5"
2"
2'-6" ±
2"
2'-5"
2"
1
7'-2
" ±
10'-0
" ±
6
A1.2
7
A1.2
MTL. PANELMATCH EXIST.
THIN BRICKMATCH EXIST.
5
A1.2
6
A1.2
7
A1.2
MTL. PANELMATCH EXIST.
THIN BRICKMATCH EXIST.
5
A1.2
10
A1.2
10
A1.2
2"
SCHEDULE
REFER TO 2"
RE
FER
TO
SC
HE
DU
LE2"
LINE OF
FINISH FLOOR1
2"
SCHEDULE
REFER TO
2"
1'-0"2"
10"
1' -
10"
2"4'
- 2"
2"
4'-6"
2"
SCHEDULE
REFER TO
2"
1'-8"2"1'-8"2"
10"
1' -
10"
2"4'
- 2"
2"
7'-0"
2 34
A1.2
4
A1.2
B.O
. CLN
GS
EE
CLN
G P
LAN
B.O
. SO
FFIT
SE
E C
LG P
LAN
B.O
. CLN
GS
EE
CLN
G P
LAN
MTL. CORNER BEAD.TYP. BOTH SIDES
5/8" GYP. CLG. BD. (PAINT)ON 3 5/8" MTL. STUDS @16" O.C. CONT. ANCHOR TOSTRUCT. ABOVE
SUSP. ACOUST. CLG.
SUSP. ACOUST. CLG.
REFER TO CLG. PLAN
TYP
.
6"
LINE OF EXISTING ROOFINSULATION
BRACE PARTITIONS BACKTO ROOF STRUCTURE AT8' O.C. MIN.
EXISTING ROOF STRUCT
6" MTL. STUDS MIN. @ 16"O.C. CONT. ANCHOR TOEXIST. ROOF STRUCT.PROVIDE SIZE AND GUAGEAS REQUIRED TO SUPPORTSOFFIT AND SPAN BETWEENROOF STRUCTURALMEMBERS.
AT ROOF BATT INSULATION, FILL VOIDS SOLIDW/ BATT INSUL. BACKER ROD AND SEALANTBOTH SIDES
GYP. BD. EACH FACE ONMTL. STUDS @ 16" O.C. NOFINISH REQ'D. ON GYP. BD.ABOVE FIN. CLG. SEAL ANDTAPE JOINTS
SOUND BATT INSUL.
HOLD PARTITION 1/2"BELOW EXISTING ROOFINSULATION
LINE OF EXISTING ROOFINSULATION
REFER TOPLANS
1/2"
BRACE PARTITIONS BACKTO ROOF STRUCTURE AT8' O.C. MIN.
EXISTING ROOF STRUCT
EL.: 112'-9"± MIN.
EL.: 113'-3"± MAX.
B.O. STRUCTURE
1/8"
MA
X
EQ.EQ.
EQ.EQ.
EQ.EQ.
TYP. TRANSITION/ THRESHOLDDETAIL CONDITIONS
TYPICAL EXTERIOR DOOR
1/2
"
SEALANT
MAX.1/2" HT.
SCHEDULED FLOOR
SCHEDULED DOOR
FINISH
21
43
CONCRETE
RESILIENT REDUCER STRIP
DOOR
DOOR
CARPET
GENERAL NOTES:
1. REFER TO ROOM FINISH GROUPS AND FLOOR PLANS FOR FINISHES. IT IS THE CONTRACTOR'S RESPONSIBILITY TO MAKE SURE THE PROPER THRESHOLD IS USED.
2. PROVIDE RESILIENT TRANSITION STRIPS OR REDUCERS BETWEEN ALL DIFFERING FLOOR FINISH MATERIALS IE CARPET TO TILE.
3. PROVIDE STRIP OR REDUCER PROFILE AS RECOMMENDED BY MANUFACTURER FOR APPLICATION.
RESILIENT TILE
METAL THRESHOLD INSTALL INCONT. BED OF SEALANT
RESILIENT TILE ORTERRAZO, REFER TO R.F.G.
ALUMINUM REDUCER STRIP
DOOR
EPOXY RESINRESILIENT TILE
RESILIENT TRANSITIONSTRIP CARPETREDUCER STRIP
3"
FIELD VERIFY
1'-0 5/8"
3B
BACKER ROD AND SEALANT,CONT. (BOTH SIDES)
NEW PRE-FIN. S.M.PERIMETER TRIM AROUNDEXIST. OPENING. FASTENTO EXIST. CONSTRUCTION
EXIST. CONST. TO REMAIN(SHOWN SHADED)
EXIST. METALPANEL SYSTEM
ALUM. STOREFRONT SYSTEM.REFER TO ALUM. FRAMEELEVATIONS AND PLANS(PROVIDE SHIMS AS REQ'D.)
'LC' TRIM AND SEALANT, CONT.
METAL CORNER BEAD, CONT.
NEW PRE-FIN. S.M. FLASHINGWITH DRIP EDGE. EXTENDUNDER FRAME HEAD
FILL SHIM VOIDS WITH LOWEXPANSION SPRAY FOAM.PROVIDE RIGID INSULATIONINSERTS IN FRAME AT PERIMETER.
FILL FRAME W/ RIGIDINSUL. INSERTS
EXISTING FLOOR SLAB
CONT. SEALANT AROUNDFRAME, TYP. AT BOTH SIDES
PRE-FIN ALUM. STOREFRONTSYSTEM, REFER TO ALUM. FRAMEELEVATIONS AND PLANS. PROVIDEWD. SHIM AS REQUIRED
FACE OF WALL BEYOND
PROVIDE PRE-FIN.EXTRUDED ALUM. FLUSHINFILL TO MATCH FRAME
FINISH FLOOR, REFER TOROOM FINISH GROUPSAND FLOOR PLANS
10"
3" 4 1/2"
PRE-FIN. ALUM. SUB SILL,SET IN BED OF SEALANT.FINISH TO MATCH FRAME (@EXTERIOR LOCATIONS)
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
FIN
AL D
OC
UM
EN
TS
10/1
8/2
017 2
:46:2
2 P
M
A1.2
MM
10/20/2017
1508
JSS, BKL
DO
OR
SC
HE
DU
LE
, D
OO
R A
ND
FR
AM
E E
LE
VA
TIO
NS
, C
EIL
ING
PL
AN
AN
D D
ET
AIL
S
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NLE
XIN
GT
ON
, K
EN
TU
CK
Y
1508
BLU
E G
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
DOOR SCHEDULE
NO.
DOOR FRAME
HE
AD
JA
MB
FIR
E R
AT
ING
CLO
SE
R D
EG
.
RemarksNO
. LE
AV
ES
LE
AF
WID
TH
HT
.
MA
TL.
TY
PE
GLA
ZIN
G
MA
TL.
TYPE GLA
ZIN
G
101 1 3'-0" 7'-0" SCWD FG 1/4" H.M. 2 1/4" 2/A1.2 3/A1.2 - 105° 1, 2
101A 1 3'-0" 7'-0" SCWD. F - H.M. 1 - 2/A1.2 3/A1.2 - -
103 1 3'-0" 7'-0" SCWD. F - H.M. 1 - 2/A1.2 3/A1.2 - 90° 1, 3
104 1 3'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - -
105 1 3'-0" 7'-0" SCWD F - H.M. 3 1/4" 2/A1.2 3/A1.2 - - 3
106 1 3'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - 90° 1
107 1 4'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - 105°
108 1 3'-0" 7'-0" H.M. FG 1" INSUL. H.M. 1 - 5/A1.2 SIM. 6&7/A1.2SIM.
- 105° 1, 4, 6
109 1 3'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - -
109A 1 1'-0" 7'-0" H.M. F H.M. 1 - 2/A1.2 3/A1.2 - -
110 1 3'-0" 7'-0" H.M. FG 1/4" H.M. 1 - 2/A1.2 SIM. 3/A1.2 SIM. - 90° 1, 5, 6
111 1 3'-0" 7'-0" H.M. F - H.M. 1 - 2/A1.2 3/A1.2 - 105°
1/4" = 1'-0"1
NEW WORK CEILING PLAN
1 1/2" = 1'-0"3
TYPICAL H.M. JAMB @ MTL. STUD
1 1/2" = 1'-0"4
TYPICAL H.M. SILL DETAIL
1 1/2" = 1'-0"2
TYPICAL H.M. HEAD @ MTL. STUD
1 1/2" = 1'-0"6
ALUM. JAMB @ EXIST. EXT. OPENINGAT MTL. PANEL (H.M. SIM.)
1 1/2" = 1'-0"7
ALUM. JAMB @ EXIST. EXT.OPENING AT BRICK (H.M. SIM.)
1 1/2" = 1'-0"8
METAL PANEL INFILL @ EXIST.EXT. OPENING
1 1/2" = 1'-0"9
INFILL @ EXIST. EXT. OPENING
DOOR TYPES1/4" = 1'-0"
HOLLOW METAL FRAME TYPES1/4" = 1'-0"
ALUMINUM STORE FRONT FRAME TYPES1/4" = 1'-0"
DOOR DIMENSIONS: DIMENSIONS NOTED ARE MINIMUM SIZES TOFACILITATE AND/OR CONCEAL PROJECT SPECIFIC HARDWARE, MFR.STANDARD DIMENSIONS WHICH NOMINALLY EXCEED THE MINIMUMS AREACCEPTABLE SUBJECT TO ARCHITECT REVIEW.GLAZING NOTE: DIMENSIONS TO GLAZING EDGE NOTED ARE TO OUTMOSTEDGE AND DO NOT INCLUDE GLAZING TRIM.DENOTES TEMPERED GLASS
ALL EXTERIOR GLAZING SHALL BE 1" INSULATED U.N.O.DENOTES TEMPERED GLASS
ALL EXTERIOR GLAZING SHALL BE 1" INSULATED U.N.O.DENOTES TEMPERED GLASS
1 1/2" = 1'-0"12
TYP. SOFFIT DETAIL
1 1/2" = 1'-0"11
TYPICAL TOP OF WALL DETAIL
1 1/2" = 1'-0"5
ALUM. HEAD @ EXIST. EXT. OPENINGAT MTL. PANEL (H.M. SIM.)
1 1/2" = 1'-0"10
ALUM SILL DETAIL
No. Description Date
CBP FORMS COUNTER
ROOM NAMEFUNCTION/LOCATION
NOT USED
RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY (ON EXTERIOR OF DOOR 108)
PASSENGER WAITING AREA (ON WALL OR HUNG FROM CEILING)
1 FULL SET OF AIRPORT STATUTORY SIGNS (TOTAL 10 SIGNS) (ON EAST WALL OF ROOM 108A)
AT ENTRY TO WAITING - HUNG FROM CEILING : WELCOME SIGN
DHS SEAL FOR PROCESSING PODIUM
CBP PROCESSING AREA (HUNG ABOVE PODIUM WITH IMMIGRATION AND BAGGAGE AIGA ICONS)
1 FULL SET OF STATUTORY SIGNS (TOTAL 10 SIGNS) (ON NORTH WALL OF ROOM 110)
EXIT FROM PROCESSING - "THANK YOU FOR YOUR COOPERATION" (ON WALL AT DOORS 108 & 110)
RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY (ON EXTERIOR OF DOORS 110 & 106)
UNISEX RESTROOM (ON WALL AT DOOR 109); BRAILLE REQUIRED
AUTHORIZED PERSONNEL ONLY (ON DOOR 101)
CBP OFFICE (ON WALL AT DOOR 101); BRAILLE REQUIRED
STORAGE ROOM (ON WALL AT DOOR 107); BRAILLE REQUIRED
LAN ROOM (ON WALL AT DOOR 106); BRAILLE REQUIRED
AUTHORIZED PERSONNEL ONLY (ON DOORS 103 & 107)
108A
ROOMNO.X
TYPE
-
108A
108A/108B
108A
110
110
110
108A/110
106/111
109
101
107
106
103/107
101
SELECTED STATUTORY SIGNS (ON WALL IN DETENTION SUITE)103
INTERVIEW ROOM (ON WALL AT DOOR 105); BRAILLE REQUIRED105
SEARCH ROOM (ON WALL AT DOOR 104); BRAILLE REQUIRED104
EXTERIOR IDENTITY SIGNAGE - ON WALL AT ENTRANCE TO GAF - AT BOTH LANDSIDE AND AIRSIDE ENTRANCES12" DIA. SEAL WITH 4" TALL LETTERS - PANEL SIGN STYLE
A
B
C
D
E
F
G
H
I
J
K
L
M
O
P
Q
N
R
S
T
X
8" X 11.5"
SIZEREQUIRED
-
6" X 36"
12" X 36"
15" DIAMETER
CBP FORMS COUNTER
GENERAL COMMENTSFINISH - TEXT - DESCRIPTION
-
RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY
PASSENGER WAITING AREA
1 FULL SET OF AIRPORT STATUTORY SIGNS (TOTAL 10 SIGNS)
WELCOME TO THE UNITED STATES. PLEASE HAVE YOUR DOCUMENTS READY TO PRESENT TO A CBP OFFICER
CBP PROCESSING AREA - 1 DHS SEAL ON FACE OF PROCESSING PODIUM
CBP PROCESSING AREA
CBP PROCESSING AREA - 1 FULL SET OF STATUTORY SIGNS (TOTAL 10 SIGNS)
THANK YOU FOR YOUR COOPERATION
RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY
TOILET
AUTHORIZED PERSONNEL ONLY
101 CBP OFFICE
107 STORAGE
106 LAN ROOM
AUTHORIZED PERSONNEL ONLY
SELECTED STATUTORY SIGNS: (1) ASSAULTING AN OFFICER OR EMPLOYEE OF THE UNITED STATES; (2) SEARCHAND DETENTION OF PERSONS, MERCHANDISE AND CONVEYANCES; (3) EXPLOSIVES, FIREARMS AND WEAPONSARE PROHIBITED; (4) ILLEGAL DRUGS; (5) CURRENCY AND MONETARY INSTRUMENTS; (TOTAL 5 SIGNS)
105 INTERVIEW ROOM
104 SEARCH ROOM
DHS SEAL: U.S. CUSTOMS ANDBORDER PROTECTION-------------------------------------BLUE GRASS AIRPORT
PROVIDEDBY
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
CONTRACTOR
-
CBP
CBP
CBP
CBP
CBP
CBP
CBP
CBP
1
QUANTITYREQUIRED
-
1
2
1
1
1 FULL SETS
1
1 FULL SET
2
2
1
1
1
1
1
1
1 EACH
1
1
2
11" X 17"
11" X 17"
11" X 17"
11" X 17"
11" X 17"
11" X 17"
11" X 17"
6" X 36"
SIGNAGE SCHEDULE
8" X 11.5"
8" X 11.5"
8" X 11.5"
8" X 11.5"
8" X 11.5"
8" X 11.5"
8" X 11.5"
UNISEX RESTROOM (ON WALL AT DOOR 109); BRAILLE REQUIRED109
SEE PLAN; BRAILLE REQUIREDSEE PLAN
U
V
BABY CHANGING STATION
EXIT
CONTRACTOR
CONTRACTOR
1
1
8" X 11.5"
8" X 8"
108A/108B
2.06' H X 7.89' L
15 SECOND DELAYED EGRESS (ON WALL AT DOOR 110); BRAILLE REQUIRED110W 1 8" X 11.5" CARD REQUIRED FOR EXIT OR ALARMED EXIT. PUSH BAR UNTIL THE ALARM SOUNDS. DOOR CAN BE OPENED IN15 SECONDS.
CONTRACTOR
EXIT
VSIGN DETAIL3" = 1'-0" D
LSIGN DETAIL3" = 1'-0"
6" P
ICTO
GR
AM
FIE
LD (T
YP
.)
PICTOGRAM LOCATION(RAISED 1/32" FROMSURFACE OF SIGN)
RAISED LETTERS ONSIGN FACE
GRADE 2 BRAILLE
11 1
/2"
U
BABY CHANGING STATION
6" P
ICTO
GR
AM
FIE
LD (T
YP
.)
RAISED LETTERS ONSIGN FACE
GRADE 2 BRAILLE
11 1
/2"
SIGN DETAIL3" = 1'-0"
Message
100*
NSIGN DETAIL3" = 1'-0"
RAISED LETTERS ONSIGN FACE
RAISED NUMBERSON SIGN FACE
GRADE 2 BRAILLE
RAISED LETTERS ONSIGN FACE
GRADE 2 BRAILLE
ACRYLIC SIGN PANELACRYLIC SIGN PANELACRYLIC SIGN PANEL
ACRYLIC SIGN PANEL
SIGN DETAIL3" = 1'-0"
ACRYLIC SIGN PANEL
TOILET
8" 8"
Message
ASIGN DETAIL3" = 1'-0"
RAISED LETTERS ONSIGN FACE
GRADE 2 BRAILLE
ACRYLIC SIGN PANEL
J
Message 3" FLUSH LETTERSON SIGN FACE
8"
11 1
/2"
8"
11 1
/2"
REFER TO SIGNAGE SCHED.
RE
FER
TO
SIG
NA
GE
SC
HE
D.
F H
O P S T
8"
8"
W
HANG FROM CEILING GRID WITH STAINLESS STEEL AIRCRAFT CABLE SYSTEM
SIGNAGE GENERAL NOTES1. WHERE ROOM SIGNS ARE AT GLASS WALL PROVIDE SOLID PANEL ON OPPOSITE SIDE OF
SIGN ON GLASS.
2. CHARACTERS SHOWN ON THIS SHEET ARE COMPUTER GENERATED. SPACING OFCHARACTERS IS NOT ACCURATE. CORRECT "VISUAL" SPACING IS THE RESPONSIBILITYOF THE MFR.
3. PICTOGRAMS ARE SHOWN HEREIN FOR INFORMATION AND INTENT ONLY. MECHANICAL,CAMERA - READY ARTWORK SHALL BE SUPPLIED BY THE SIGNAGE CONTRACTOR.
4. COLORS OF PANEL SIGNS TO BE SELECTED BY ARCHITECT.
5. UNLESS OTHERWISE NOTED, ALL SIGNS TO BE MOUNTED BESIDE DOORS AT 4'-0" A.F.F.TO BOTTOM OF SIGN AND 2" FROM EDGE OF DOOR FRAME ON THE LATCH SIDE. WHERETHERE IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR, INCLUDING AT DOUBLELEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. MOUNTINGLOCATION FOR SUCH SIGNAGE SHALL BE SO THAT A PERSON MAY APPROACH WITHIN 3IN OF SIGNAGE WITHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHINTHE SWING OF A DOOR. THE ARCHITECT SHALL BE CONSULTED BEFORE PLACEMENT OFSIGNAGE FOR LEFTHAND AND RIGHTHAND ORIENTATION OF SIGNS.
6. * = THREE CHARACTER NUMBER TO BE SUPPLIED BY ARCHITECT/OWNER.
7. ALL SIGNAGE SHALL MEET REQUIREMENTS OF ADAAG OF THE AMERICANS WITHDISABILITIES ACT (ADA) AND ICC (ANSI) A117.1-2009.
8. MESSAGE (COPY) TO BE DETERMINED BY ARCHITECT/OWNER.
9. SIGNAGE INDICATED TO BE PROVIDED BY CBP IS TO BE PURCHASED BY CONTRACTORTHROUGH U.S. CUSTOMS AND BOARDER PATROL AND INSTALLED BY CONTRACTOR.SIGNAGE INDICATED TO BE PROVIDED BY CONTRACOTR IS TO BE FABRICATED, SUPPLIEDAND INSTALLED BY CONTRACTOR AS INDICATED IN SPEC. AND DRAWINGS.
10. "CBP" REFERS TO UNITED STATES CUSTOMS AND BORDER PROTECTION AGENCY.
11. "GAF" REFERS TO THIS PROJECT / GENERAL AVIATION FACILITY
3"3"
3'-0
"4"
3'-1
0"
4'-0" 3'-0"
3/4"
3/4" 3/4"
DHS SEAL - REFER TOSIGNAGE SCHEDULE
FINGERPRINT READER (N.I.C.)
PLASTIC LAMINATE COLOR A
PLASTIC LAMINATE COLOR B
PLASTIC LAMINATE COLOR C
PLASTIC LAMINATE COLOR B
2'-1
0"
2 1/4" 3/4"
3" 1'-4 1/2" 1'-4 1/2" 3" 1'-9" 1'-9" 3"
4'-0"
1'-0
"2'
-10"
3'-1
0"
3/4" 3/4"
6
A1.3
5
A1.3
FINGERPRINT READER (N.I.C.)
DURRESS ALARM. TETHERTO FLOOR OUTLET
CYLINDERLOCKS
RECESSEDSTAINLESS STEELPULLS
PLASTIC LAMINATE COLOR A
PLASTIC LAMINATECOLOR B
PLASTIC LAMINATECOLOR A
NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.
INTERCOM CABINET WITHPIVOT SLIDING DOOR
PLASTIC LAMINATECOLOR C
CYLINDERLOCKS
RECESSEDSTAINLESS STEELPULLS
3/4" 2 1/4"
3'-0"
7
A1.3
3" 3"
4"
3"
1"3"
10 1/4"
1'-0"
2'-1
0"1'
-0"
OUTLET SWITCH. TETHERTO FLOOR OUTLET
PROVIDE CPUEXHAUST FAN
PLASTIC LAMINATEDRAWERS, ERFER TO SPEC.
8"
DATA/POWER OUTLETS. CONCEALEDFLEX CONDUIT FROM FLOOR. TETHERTO FLOOR OUTLETS
PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF
PLASTIC LAMINATE ON 3/4"PLYWOOD VENTED DOOR
NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.
PLASTIC LAMINATE 3/4"PLYWOOD FRAME
PLASTIC LAMINATE 3/4" PLYWOODTOE KICKS ON 2X WOOD BLOCKING
PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A) WITH RADIUSSEDEGDE ON 1X WOOD FRAMING
PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A)
PLASTIC LAMINATECOLOR B
PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF
1 1/
2"
1/8"
4 1/
4"
1/4"
4 1/
4"
1/4"
1'-7
3/8
"
1'-0"
1'-8"
GROMMET TOLOW COUNTER
4"
1'-0
"2'
-10"
3"3"
1'-3"
2'-9"
3"3"
3" 3"
PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF
PLASTIC LAMINATE ON3/4" PLYWOOD NON-VENTED DOOR
PLASTIC LAMINATE 3/4"PLYWOOD DIVIDER PANELBEYOND
TASK LIGHT, COORDINATEPOWER CONNECTIONWITH ELECTRICAL.
INTERCOM CABINET WITHPIVOT SLIDING DOOR
NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.
PLASTIC LAMINATE 3/4"PLYWOOD FRAME
PLASTIC LAMINATE 3/4" PLYWOODTOE KICKS ON 2X WOOD BLOCKING
SEALANT, CONT.
PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A) WITH RADIUSSEDEGDE ON 1X WOOD FRAMING
PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A)
PLASTIC LAMINATECOLOR B
1 1/
2"8"
1'-8
1/2
"
4 3/4"
1'-8"
4"
2'-1
0"
3" 3"
PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF
PLASTIC LAMINATE ON3/4" PLYWOOD NON-VENTED DOOR
PLASTIC LAMINATE 3/4"PLYWOOD DIVIDER PANELBEYOND
NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.
PLASTIC LAMINATE 3/4"PLYWOOD FRAME
PLASTIC LAMINATE 3/4" PLYWOODTOE KICKS ON 2X WOOD BLOCKING
SEALANT, CONT.
PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A) WITH RADIUSSEDEGDE ON 1X WOOD FRAMING
1/8"
2'-4
3/8
"
1'-8"
2'-9"
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
10/1
8/2
017 2
:46:2
4 P
M
A1.3
MM
10/20/2017
1508
JSS, BKL
SIG
NA
GE
SC
HE
DU
LE
AN
DE
LE
VA
TIO
NS
AN
D C
AS
EW
OR
KD
ET
AIL
S
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NLE
XIN
GT
ON
, K
EN
TU
CK
Y
1508
BLU
E G
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
1 1/2" = 1'-0"3
PROCESSING PODIUM ELEVATION - FRONT
1 1/2" = 1'-0"4
PROCESSING PODIUM ELEVATION - BACK
1 1/2" = 1'-0"5
PROCESSING PODIUM SECTION
1 1/2" = 1'-0"6
PROCESSING PODIUM SECTION
1 1/2" = 1'-0"7
PROCESSING PODIUM SECTION
No. Description Date
VT
E(NAME)
ABAN(NAME)
FD-#
P-#
SAN
BALANCING VALVE
BALL VALVE
CHECK VALVE
THERMOMETER
DOUBLE CHECK VALVE ASSEMBLY
PIPING UNION
PETE'S PLUG
POINT OF CONNECTION
LIMIT OF DEMOLITION
PIPE ELBOW TURNING UP/TURNING DOWN
PIPE TEE TURNING UP/TURNING DOWN
ABOVE FINISHED FLOOR
ABOVE FINISHED ROOFAFR
AFF
DOMESTIC COLD WATERCW
FREEZE PROOF WALL HYDRANTFPWH
HOSE BIBBHB
DOMESTIC HOT WATERHW
INSIDE DIMENSIONID
IN ACCORDANCE WITHIAW
INVERT ELEVATIONIE
NOT TO SCALENTS
NOT IN CONTRACTNIC
NORMALLY OPENNO
NORMALLY CLOSEDNC
OUTSIDE DIMENSIONOD
OPEN RECEPTACLEOR
TOP ELEVATIONTE
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
VENT PIPING
EXISTING PIPING (THIN LINE)
ABANDONED EXISTING PIPING (THIN LINE)
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER SUPPLY
DOMESTIC RECIRCULATING HOT WATER
CLEANOUT IN CEILING SPACE
FLOOR CLEANOUT
EXTERIOR CLEANOUT
SYMBOLS & ABBREVIATIONS
CAST IRONC.I.
DOWNDN
OVERFLOW ROOF LEADERORL
POUNDS PER SQUARE INCHPSI
DOMESTIC RECIRCULATING HOT WATERRHW
SANITARY RISERSR
THRUST BLOCKTB
TRAP PRIMERTP
VENT THRU ROOFVTR
OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI
OWNER FURNISHED, OWNER INSTALLEDOFOI
CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI
CO
CO
ECO
FLOOR DRAIN DESIGNATOR
PLUMBING FIXTURE DESIGNATOR
XXX
XEQUIPMENT TAG DESIGNATOR
STRAINER
X TAGGED NOTE DESIGNATOR
X REVISION DESIGNATOR
SAFETY RELIEF VALVE
SAFETY RELIEF VALVE
TS
TEMPERATURE SENSOR
HOSE BIB
SANITARY WASTE PIPING
4" SAN
P2
4" E(SAN)
2" SAN
2" VT
4" VT
4"
VT
4"
VT
4" SAN
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:2
5 P
M
P1.0
KRM
09/25/2017
1508/XACO16
CMR
PL
UM
BIN
G L
EG
EN
D
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
PLUMBING GENERAL NOTES• COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, ETC., WITH ALL
CASEWORK EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC., PRIORTO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALLBE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THECONTRACTOR.
• THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE COURSE OFTHEIR WORK SO AS TO INSURE THAT THEY DO NOT INTERRUPT ANYEXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULARATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS ANDELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC., OF EACHUNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BEPERFORMED IN ACCORD WITH ALL FEDERAL, STATE AND/OR LOCALRULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE APPLICABLEMUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THEMOST STRINGENT REQUIREMENT SHALL APPLY.
• WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER ORGYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE RESPONSIBLEFOR REMOVAL AND REINSTALLATION (OR REPLACEMENT, IF DAMAGED)OF ALL CEILING OR TILE AND GRID MEMBERS NECESSARY TO PERFORMHIS WORK. NEW TILE AND GRID SHALL MATCH THE SURROUNDINGAREAS. ALL PATCHING WORK SHALL MATCH ADJACENT SURFACES.
• ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM THEWORK OF OTHER TRADES, WHETHER EXISTING OR NEW.
• PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR (TOOWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC., THAT ARE TOREMAIN IF DAMAGED DURING CONSTRUCTION. REPAIRS SHALL MATCHADJACENT SURFACES TO THE SATISFACTION OF THE ARCHITECT ANDOWNER.
• OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAYAPPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL,FEDERAL, MUNICIPALITY, UTILITY COMPANY, COMMONWEALTH OFKENTUCKY, ETC.)
• CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING WORK DURINGDEMOLITION. IF ITEMS ARE UNCOVERED DURING DEMOLITION THENFIELD VERIFY THE USE OF THE ITEMS AND PLAN AN ALTERNATE ROUTETO RUN THESE ITEMS. THEN CONTACT THE ENGINEERS TO REVIEW THEROUTING.
• WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE ALLEXISTING CONDUITS, WATER, HYDRONIC, ETC. SHALL BE LOWERED TOBE BELOW FULL THICKNESS OF FIRE PROOFING WITH NO INTERFERENCE.
• ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES SHALL BEAPPROPRIATELY FIRE STOPPED PER AN APPROVED U.L. LISTEDSTANDARD. CONTRACTOR SHALL PAY PARTICULAR ATTENTION TOINSULATED PIPING PENETRATIONS.
• ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE BUILDING SHALLBE SCHEDULED 2 WEEKS IN ADVANCE, AND SHALL COMPLY WITHINTERIM LIFE SAFETY MEASURES.
• ALL PIPING IN ROOMS WITH CEILINGS SHALL BE ABOVE CEILING EXCEPTAS NOTED.
• IN ACCORDANCE WITH K.R.S. ALL PLUMBING WORK SHALL BECONSTRUCTED IN COMPLIANCE WITH PLANS APPROVED BY ANDBEARING THE APPROVAL STAMP OF THE KENTUCKY DIVISION OFPLUMBING AND/OR THE DIVISION OF WATER. THE CONTRACTOR SHALLNOT BEGIN WORK UNTIL HE HAS RECEIVED SUCH APPROVED PLANS.
• LOCATIONS OF PIPING AND EQUIPMENT ARE APPROXIMATE ANDSUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT SCALE THEDRAWINGS.
• ALL OFFSETS IN PIPING ARE NOT NECESSARILY SHOWN. PROVIDEADDITIONAL OFFSETS WHERE NECESSARY.
• THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES OROTHER COSTS THAT ANY UTILITY COMPANY MAY REQUIRE TO COMPLETETHEIR WORK. (GAS, SEWER, WATER, ETC.).
• INSTALL ALL PIPING AND EQUIPMENT IN STRICT ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTION. IF IN CONFLICT WITHTHE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THEENGINEERS PRIOR TO INSTALLATION FOR CLARIFICATION. PROVIDERECOMMENDED ACCESS AND SERVICE CLEARANCES FOR ALLEQUIPMENT.
• SEAL AIRTIGHT AROUND ALL PIPING PENETRATIONS THROUGH WALLS,FLOORS AND ROOF. PROVIDE FIRE STOPPING IN FIRE PARTITION.
• THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTINGEQUIPMENT APPURTENANCES, ETC., THAT CONFLICT WITH NEW WORK.
• WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICTWITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEERS BEFOREINSTALLATION. REFER ALSO TO ARCHITECTURAL WALL INTERIOR ANDEXTERIOR WALL ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OFTHESE DOCUMENTS.
• ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCINGEQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN ANAPPROVED MANNER. NOISY OR STRUCTURALLY DAMAGINGINSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED ATTHE INSTALLING CONTRACTOR'S EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BETHAT OF THE ENGINEER.
• DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOREQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE THERESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANYPROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHERAPPROVED BY THE ENGINEERS OR NOT, SHALL BE THE RESPONSIBILITYOF THE PURCHASER.
• VALVES, BALANCING DAMPERS OR ANY MECHANICAL/ELECTRICAL ITEMREQUIRING ACCESS SHALL NOT BE LOCATED ABOVE A HARD CEILING. IFTHIS IS NOT POSSIBLE, THEN AN APPROPRIATELY SIZED ACCESS DOORSHALL BE PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE ANDADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE LOCATEDAN UNREASONABLE DISTANCE ABOVE THE CEILINGS. IN GENERAL ALLSUCH ITEMS UNLESS INDICATED OTHERWISE SHALL BE MOUNTED SIX TOTWELVE INCHES ABOVE THE CEILING. IF IN DOUBT, CONTACT ENGINEERPRIOR TO INSTALLING.
• ALL MANHOLES, VAULTS AND SIMILAR UNDERGROUND STRUCTURESSHALL HAVE THE TOP ELEVATION SET FLUSH WITH FINISHED GRADEUNLESS SPECIFICALLY NOTED OTHERWISE.
• WHEN RUNNING ANY TYPE OF PIPING BELOW A FOOTER, OR IN THE ZONEOF INFLUENCE THE PIPING SHALL BE BACKFILLED WITH CEMENTITIOUSFLOWABLE FILL PER SPECIFICATIONS. WHENEVER POSSIBLE, LOCATEPIPING OUTSIDE OF THE ZONE OF INFLUENCE. THE ZONE OF INFLUENCEIS THE AREA UNDER THE FOOTER WITHIN A 45 DEGREE ANGLEPROJECTING DOWN FROM THE BOTTOM EDGE OF THE FOOTER OF ALLSIDES OF THE FOOTER. ADDITIONALLY, GREASE TRAPS, MANHOLES,VAULTS AND OTHER UNDERGROUND STRUCTURES SHALL BE HELD AWAYFROM BUILDING WALLS FAR ENOUGH TO BE OUTSIDE OF THE ZONE OFINFLUENCE.
• THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND 2009 IECC.
• WORK IN CONFINED AREAS SHALL BE IN ACCORDANCE WITH THEOWNER'S SAFETY POLICY REQUIREMENTS.
PLUMBING FIXTURE SCHEDULE
FIXTURE TAG DESCRIPTION CW HW VENT WASTE
P-1 WATER CLOSET - FLOOR MOUNTED - MANUAL FLUSH VALVE - ADA COMPLIANT : VITREOUS CHINA, 18" HIGHELONGATED BOWL, SIPHON JET, 11/2" TOP SPUD INLET, CHINA BOLT CAPS AND WHITE OPEN FRONT PLASTIC SEATWITH SELF-SUSTAINING CHECK HINGES. PROVIDE MANUAL 1.6 GPF FLUSH VALVE WITH HANDLE AT A MAXIMUM OF31" AFF.
1-1/2" - 2" 4"
P-2 LAVATORY - WALL HUNG W/ SINGLE LEVER FAUCET - ADA COMPLIANT : VITREOUS CHINA, 20"X18" WALL HUNGLAVATORY WITH 4" FAUCET CENTERS, CONCEALED ARMS AND 4" HIGH BACKSPLASH. PROVIDE WITH A 0.5 GPMSINGLE LEVER FAUCET, CHROME PLATED 3/8" SUPPLIES WITH STOPS, GRID DRAIN, A KENTUCKY CODE P-TRAP,TAILPIECE AND ESCUTCHEONS. MOUNT LAVATORY AT A HEIGHT LEAVING A CLEARANCE OF AT LEAST 29" FROMTHE FLOOR TO THE APRON AND THE RIM AT A MAXIMUM OF 34" AFF. PROVIDE ON THE EXPOSED WASTE PIPE ANDWATER SUPPLY LINES A TRAP-WRAP INSULATION KIT WITH A VINYL AND PLASTIC COVERING.
1/2" 1/2" 2" 2"
P-3 SINGLE COMPARTMENT SINK : SINGLE COMPARTMENT STAINLESS STEEL SINK, 19"X21" O.D., 14"X18" I.D., 61/2"DEEP, 18 GAUGE, WITH 8" CENTERS. PROVIDE WITH 8" RIGID SPOUT GOOSENECK FAUCET WITH 4" WRIST BLADECONTROL HANDLES, REAR CENTERED CRUMB CUP STRAINER DRAIN, 3/8" ANGLE SUPPLIES WITH STOPS,KENTUCKY CODE P-TRAP, TAILPIECE AND ESCUTCHEONS.
1/2 1/2" 2" 2"
P-4 ELECTRIC WATER COOLER - BI LEVEL - ADA COMPLIANT : BI-LEVEL BARRIER FREE WATER COOLER WITH SINGLECOMPRESSOR, WATER SUPPLY, DRAIN AND ELECTRICAL CONNECTION. 8.0 GPH OF 50°F WATER AT 90°F AMBIENTAND 80°F INLET WATER, 18.8 GAUGE STAINLESS STEEL BASIN, 1/5 HP COMPRESSOR, 115V/1PH, SURFACEMOUNTED TO THE WALL WITH CHILLER BELOW BOWL AND SIDE AND FRONT PUSH BAR OPERATORS. MOUNT SOTHE BOTTOM OF THE LOWER COOLER IS AT 9" MINIMUM AFF WITH A CLEARANCE OF 27" MINIMUM FROM THEBOTTOM OF THE APRON OF THE BOWL TO THE FINISHED FLOOR. THE DIMENSION TO THE CENTERLINE OF THELOWER COOLER BUBBLER SHALL BE 35".
1/2" - 2" 2"
P-5 EMERGENCY EYE/FACE WASH STATION : GUARDIAN G1724 OR EQUAL EYE/FACE WASH WITH FOUR GS PLUS SPRAYHEADS, STAINLESS STEEL BOWL AND STAY-OPEN BALL VALVE. EACH SPRAY HEAD SHALL HAVE A REMOVABLE ABSPLASTIC SPRAY COVER, RETICULATED POLYURETHANE FILTER, SELF-REGULATING FLOW CONTROL AND INTEGRAL"FLIP-TOP" DUST COVER.PROVIDE WITH LEONARD TA-300-STSTL-REC OR EQUAL EMERGENCY MIXING VALVE TO PROVIDE TEPID WATER TOEYE/FACE WASH UNIT. ASSEMBLY SHALL INCLUDE 1/2" INLETS CHECK AND STOP VALVES AND 1/2" OUTLET. MIXINGVALVE SHALL BE MOUNTED IN A RECESSED STAINLESS STEEL CABINET WITH LOCKING DOOR.
1/2" 1/2" - -
PLUMBING DEMOLITION NOTES• THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR
AREAS IN WHICH THE CEILING IS REMAINING. THE CONTRACTOR ISRESPONSIBLE FOR REMOVING THE EXISTING CEILING AS REQUIRED ANDREINSTALLATION. TEMPORARILY SUPPORT LIGHTS, DIFFUSERS, CEILINGETC. REPLACE BROKEN CEILING TILES WITH NEW AT NO ADDITIONALCOST TO OWNER. FIELED VERIFY EXACT REQUIREMENTS.
• ALL OUTAGES SHALL BE SCHEDULED THROUGH THE PROJECTREPRESENTATIVE FOR PROPER COORDINATION. A REQUEST FOR ANOUTAGE SHALL BE SUBMITTED IN WRITING A MINIMUM OF TWO WEEKS INADVANCE.
• ALL WALLS AND FLOOR SLABS SHALL BE REPAIRED TO MATCH EXISTINGAND TO A LIKE NEW CONDITION. ALL RATED WALLS AND FLOOR SLABSSHALL BE PATCHED AND REPAIRED TO MAINTAIN RATING.
• ALL EXISTING BUILDING FINISHES SHALL BE PROTECTED DURING THEDEMOLITION PHASE.
• HEAVY DASHED LINES INDICATE ITEMS FOR REMOVAL (U.O.N) AND LIGHTSOLID LINES INDICATE EXISTING ITEMS TO REMAIN.
• COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATEDFOR DEMOLITION) WITH THE OWNER.
PHASING NOTES• THIS PROJECT INTERFACES EXTENSIVELY WITH EXISTING BUILDING
SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOCOORDINATE AND PHASE ALL TIE-INS AND INTERRUPTIONS OF EXISTINGSERVICES TO MINIMIZE OR ELIMINATE DOWNTIME. AS AN EXAMPLE,MAIN GAS SERVICE, WATER SERVICE, ELECTRICAL SERVICE, HVACSERVICES, ETC., WILL BE AFFECTED AND REPLACED OR MOVED DURINGTHIS PROJECT. THE CONTRACTOR SHALL INSTALL ALL NEW SERVICESAND EQUIPMENT AND HAVE THEM TESTED AND FULLY AND RELIABLYFUNCTIONAL PRIOR TO INTERRUPTING, RELOCATING OR REMOVING ANYEXISTING SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITYTO BARE ANY AND ALL COSTS ASSOCIATED WITH THIS PHASING,INCLUDING TEMPORARY SERVICES, TEMPORARY RELOCATION, PREMIUMTIME WORK, ETC. CONTRACTOR SHALL COORDINATE ALL SAID WORKWITH THE OWNER AND APPLICABLE UTILITIES PER THE CONTRACTDOCUMENTS.
1SANITARY WASTE AND VENT RISER
ECO
P-2
P-4
P-5
P-3
TAGGED NOTES
P2 4" VENT THRU ROOF. SEAL ROOF PENETRATION WATER TIGHT.
P-1
No. Description Date
DN
DN
P1
E(WH)
3/4" E(HW)
1 1/2" E(CW)
2" E(SAN)
1 1/2" E(CW)
3/4" E(HW)
P5
P-1
P-2
P-5
P-4
P-3
4" SAN
3/4
" C
W
3/4
" H
W
2" VT
4"
VT
P2
ECO
3/4
" C
W
3/4" HW
1 1/2" CW
1 1
/2"
CW
3/4
" H
W
E(WH)
3/4" E(HW)
1 1/2" E(CW)
4"
E(S
AN
)
4"
SA
N
4"
SA
N
P4
P4
P6
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:2
7 P
M
P2.0
KRM
09/25/2017
1508/XACO16
CMR
PL
UM
BIN
G -
FIR
ST
FL
OO
R
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
1/4" = 1'-0"1
DEMO - PLUMBING - FIRST FLOOR
1/4" = 1'-0"2
PLUMBING - FIRST FLOOR
TAGGED NOTES
P1 DEMO EXISTING SINK AND UNDER COUNTER PUMP.
P2 4" VENT THRU ROOF. SEAL ROOF PENETRATION WATER TIGHT.
P4 PATCH AND REPAIR ASPHALT AND CONCRETE PER ARCHITECTURAL REQUIREMENTS.
P5 SALVAGE EXISTING DRINKING FOUNTAIN.
P6 RELOCATE EXISTING DRINKING FOUNTAIN. CONNECT TO EXISTING WATER AND WASTESUPPLY LINES.
TRUENORTH
PLANNORTH
No. Description Date
EA
EA
RA
SA
EA
OA
TA
CD
FD
SD
FSD
E(NAME)
ABAN(NAME)
RF
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
EA AIR DUCT TURNING UP
EA AIR DUCT TURNING DOWN
FLEXIBLE DUCT
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
OUTSIDE AIR DUCT
TRANSFER AIR DUCT
CONDENSATE DRAIN
FIRE DAMPER
SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPER
POINT OF CONNECTION
LIMIT OF DEMOLITION
VOLUME DAMPER
PIPE ELBOW TURNING UP/TURNING DOWN
PIPE TEE TURNING UP/TURNING DOWN
ABOVE FINISHED FLOOR
ABOVE FINISHED ROOFAFR
AFF
CONDENSATE DRAINCD
CAST IRONC.I.
DOWNDN
FIRE DAMPERFD
INSIDE DIMENSIONID
NORMALLY CLOSEDNC
NORMALLY OPENNO
NORMALLY OPENNO
NOT IN CONTRACTNIC
NOT TO SCALENTS
OUTSIDE DIMENSIONOD
CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI
OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI
OWNER FURNISHED, OWNER INSTALLEDOFOI
OPEN RECEPTACLEOR
POUNDS PER SQUARE INCHPSI
SMOKE DAMPERSD
THRUST BLOCKTB
TOP ELEVATIONTE
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
VARIABLE FREQUENCY DRIVEVFD
REFRIGERANT PIPING
SYMBOLS & ABBREVIATIONS
XXX
XEQUIPMENT TAG DESIGNATOR
X TAGGED NOTE DESIGNATOR
X REVISION DESIGNATOR
EXISTING PIPING (THIN LINE)
ABANDONED EXISTING PIPING (THIN LINE)
EXISTING DUCT OR PIPING TO BE REMOVED
CEILING
NOTES:
1. SUPPORT DUCTWORK, DIFFUSERS, ETC. INDEPENDANTLY OFCEILING SYSTEM
2. PROVIDE VOLUME DAMPERS IN ALL BRANCH DUCTS TO GRILLES,REGISTERS, AND DIFFUSERS, INCLUDING RECTANGULAR BRANCHDUCTS.
EXTERNAL INSULATION(WHERE REQUIRED-SEESPECIFICATIONS)
2'' EXTENSION ANDLOCKING QUADRANTOPERATOR
REFER TO SPECS FOR DUCTSEALANT REQUIREMENTS ATFITTING, JOINTS, ETC.
PROVIDE TRANSITION WHEREREQUIRED. PAINT ALL SHEETMETAL (VISIBLE THROUGHGRILLE) PER SPECIFICATIONS.
THE MAX. LENGTH OFFLEX DUCTWORK SHALLNOT EXCEED 6'-0".
CONNECT WITH A MIN. OF THREESCREWS SPACED A MAX. OF 6'' APART.DUCT SHALL BE SECURED WITH PANDUITTYPE STRIP AND A MIN. OF 2 COMPLETEWRAPS OF DUCT TAPE.
RIGID ROUND DUCT. (LENGTH AS REQUIRED)
ROUND VOLUME DAMPER. (REFER TOSPECS) DO NOT PROVIDE VOLUME DAMPERABOVE HARD CEILINGS.
FLEXMASTER OREQUAL BELLMOUTHSPIN-IN COLLARFITTING.
RECTANGULAR MAINDUCT. (SEE SPECFOR INSULATION)
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:2
2 P
M
M1.0
KRM
09/25/2017
1508/XACO16
CMR
ME
CH
AN
ICA
L L
EG
EN
D
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
MECHANICAL GENERAL NOTES• COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, ETC., WITH ALL
CASEWORK EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC., PRIORTO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALLBE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THECONTRACTOR.
• THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE COURSE OFTHEIR WORK SO AS TO INSURE THAT THEY DO NOT INTERRUPT ANYEXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULARATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS ANDELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC., OF EACHUNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BEPERFORMED IN ACCORD WITH ALL FEDERAL, STATE AND/OR LOCALRULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE APPLICABLEMUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THEMOST STRINGENT REQUIREMENT SHALL APPLY.
• WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER ORGYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE RESPONSIBLEFOR REMOVAL AND REINSTALLATION (OR REPLACEMENT, IF DAMAGED)OF ALL CEILING OR TILE AND GRID MEMBERS NECESSARY TO PERFORMHIS WORK. NEW TILE AND GRID SHALL MATCH THE SURROUNDINGAREAS. ALL PATCHING WORK SHALL MATCH ADJACENT SURFACES.
• ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM THEWORK OF OTHER TRADES, WHETHER EXISTING OR NEW.
• PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR (TOOWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC., THAT ARE TOREMAIN IF DAMAGED DURING CONSTRUCTION. REPAIRS SHALL MATCHADJACENT SURFACES TO THE SATISFACTION OF THE ARCHITECT ANDOWNER.
• OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAYAPPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL,FEDERAL, MUNICIPALITY, UTILITY COMPANY, COMMONWEALTH OFKENTUCKY, ETC.)
• CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING, HVAC ANDELECTRICAL WORK DURING DEMOLITION. IF ITEMS ARE UNCOVEREDDURING DEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS ANDPLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THEN CONTACT THEENGINEERS TO REVIEW THE ROUTING.
• WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE ALLEXISTING CONDUITS, WATER, HYDRONIC, ETC. SHALL BE LOWERED TOBE BELOW FULL THICKNESS OF FIRE PROOFING WITH NO INTERFERENCE.
• ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES SHALL BEAPPROPRIATELY FIRE STOPPED PER AN APPROVED U.L. LISTEDSTANDARD. CONTRACTOR SHALL PAY PARTICULAR ATTENTION TOINSULATED PIPING PENETRATIONS.
• ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE BUILDING SHALLBE SCHEDULED 2 WEEKS IN ADVANCE, AND SHALL COMPLY WITHINTERIM LIFE SAFETY MEASURES.
• ALL DUCTWORK, PIPING, CONDUITS, ETC. IN ROOMS WITH CEILINGSSHALL BE ABOVE CEILING EXCEPT AS NOTED.
• LOCATIONS OF PIPING, DUCTS AND EQUIPMENT ARE APPROXIMATE ANDSUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT SCALE THEDRAWINGS.
• ALL OFFSETS IN DUCTS AND PIPING ARE NOT NECESSARILY SHOWN.PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.
• COORDINATE ALL HVAC WORK WITH ELECTRICAL, PLUMBING AND OTHERTRADES TO AVOID INTERFERENCE WITH PIPING, DUCTS, CONDUIT ANDOTHER EQUIPMENT.
• INSTALL ALL PIPING, DUCTWORK AND EQUIPMENT IN STRICTACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTION. IF INCONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS,ADVISE THE ENGINEERS PRIOR TO INSTALLATION FOR CLARIFICATION.PROVIDE RECOMMENDED ACCESS AND SERVICE CLEARANCES FOR ALLEQUIPMENT.
• SEAL AIRTIGHT AROUND ALL DUCTS AND PIPING PENETRATIONSTHROUGH WALLS, FLOORS AND ROOF. PROVIDE FIRE STOPPING IN FIREPARTITION.
• SEAL ALL NEW DUCTWORK JOINTS WITH UNITED MCGILL, IRONGRIP 6O1OR EQUAL WATER BASED SEALANT.
• ALL MOTOR DRIVEN EQUIPMENT SHALL BE INSTALLED WITH FLEXIBLECONNECTIONS TO DUCTWORK, PIPING, ETC., UNLESS OTHERWISENOTED.
• THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTINGEQUIPMENT APPURTENANCES, ETC., THAT CONFLICT WITH NEW WORK.
• WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICTWITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEERS BEFOREINSTALLATION. REFER ALSO TO ARCHITECTURAL WALL INTERIOR ANDEXTERIOR WALL ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OFTHESE DOCUMENTS.
• DOUBLE WIDTH TURNING VANES SHALL BE INSTALLED IN ALL SUPPLY,RETURN, AND EXHAUST DUCTWORK ELBOWS.
• ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCINGEQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN ANAPPROVED MANNER. NOISY OR STRUCTURALLY DAMAGINGINSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED ATTHE INSTALLING CONTRACTOR'S EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BETHAT OF THE ENGINEER.
• DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOREQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE THERESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANYPROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHERAPPROVED BY THE ENGINEERS OR NOT, SHALL BE THE RESPONSIBILITYOF THE PURCHASER.
• VALVES, BALANCING DAMPERS OR ANY MECHANICAL/ELECTRICAL ITEMREQUIRING ACCESS SHALL NOT BE LOCATED ABOVE A HARD CEILING. IFTHIS IS NOT POSSIBLE, THEN AN APPROPRIATELY SIZED ACCESS DOORSHALL BE PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE ANDADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE LOCATEDAN UNREASONABLE DISTANCE ABOVE THE CEILINGS. IN GENERAL ALLSUCH ITEMS UNLESS INDICATED OTHERWISE SHALL BE MOUNTED SIX TOTWELVE INCHES ABOVE THE CEILING. IF IN DOUBT, CONTACT ENGINEERPRIOR TO INSTALLING.
• ALL MANHOLES, VAULTS AND SIMILAR UNDERGROUND STRUCTURESSHALL HAVE THE TOP ELEVATION SET FLUSH WITH FINISHED GRADEUNLESS SPECIFICALLY NOTED OTHERWISE.
• WHEN RUNNING ANY TYPE OF PIPING BELOW A FOOTER, OR IN THE ZONEOF INFLUENCE THE PIPING SHALL BE BACKFILLED WITH CEMENTITIOUSFLOWABLE FILL PER SPECIFICATIONS. WHENEVER POSSIBLE, LOCATEPIPING OUTSIDE OF THE ZONE OF INFLUENCE. THE ZONE OF INFLUENCEIS THE AREA UNDER THE FOOTER WITHIN A 45 DEGREE ANGLEPROJECTING DOWN FROM THE BOTTOM EDGE OF THE FOOTER OF ALLSIDES OF THE FOOTER. ADDITIONALLY, GREASE TRAPS, MANHOLES,VAULTS AND OTHER UNDERGROUND STRUCTURES SHALL BE HELD AWAYFROM BUILDING WALLS FAR ENOUGH TO BE OUTSIDE OF THE ZONE OFINFLUENCE.
• THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND 2009 IECC.
• WORK IN CONFINED AREAS SHALL BE IN ACCORDANCE WITH THEOWNER'S SAFETY POLICY REQUIREMENTS.
PHASING NOTES• THIS PROJECT INTERFACES EXTENSIVELY WITH EXISTING BUILDING
SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOCOORDINATE AND PHASE ALL TIE-INS AND INTERRUPTIONS OF EXISTINGSERVICES TO MINIMIZE OR ELIMINATE DOWNTIME. AS AN EXAMPLE,MAIN GAS SERVICE, WATER SERVICE, ELECTRICAL SERVICE, HVACSERVICES, ETC., WILL BE AFFECTED AND REPLACED OR MOVED DURINGTHIS PROJECT. THE CONTRACTOR SHALL INSTALL ALL NEW SERVICESAND EQUIPMENT AND HAVE THEM TESTED AND FULLY AND RELIABLYFUNCTIONAL PRIOR TO INTERRUPTING, RELOCATING OR REMOVING ANYEXISTING SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITYTO BARE ANY AND ALL COSTS ASSOCIATED WITH THIS PHASING,INCLUDING TEMPORARY SERVICES, TEMPORARY RELOCATION, PREMIUMTIME WORK, ETC. CONTRACTOR SHALL COORDINATE ALL SAID WORKWITH THE OWNER AND APPLICABLE UTILITIES PER THE CONTRACTDOCUMENTS.
MECHANICAL DEMOLITION NOTES• THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR
AREAS IN WHICH THE CEILING IS REMAINING. THE CONTRACTOR ISRESPONSIBLE FOR REMOVING THE EXISTING CEILING AS REQUIRED ANDREINSTALLATION. TEMPORARILY SUPPORT LIGHTS, DIFFUSERS, CEILINGETC. REPLACE BROKEN CEILING TILES WITH NEW AT NO ADDITIONALCOST TO OWNER. FIELED VERIFY EXACT REQUIREMENTS.
• ALL OUTAGES SHALL BE SCHEDULED THROUGH THE PROJECTREPRESENTATIVE FOR PROPER COORDINATION. A REQUEST FOR ANOUTAGE SHALL BE SUBMITTED IN WRITING A MINIMUM OF TWO WEEKS INADVANCE.
• ALL WALLS AND FLOOR SLABS SHALL BE REPAIRED TO MATCH EXISTINGAND TO A LIKE NEW CONDITION. ALL RATED WALLS AND FLOOR SLABSSHALL BE PATCHED AND REPAIRED TO MAINTAIN RATING.
• ALL EXISTING BUILDING FINISHES SHALL BE PROTECTED DURING THEDEMOLITION PHASE.
• HEAVY DASHED LINES INDICATE ITEMS FOR REMOVAL (U.O.N) AND LIGHTSOLID LINES INDICATE EXISTING ITEMS TO REMAIN.
• COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATEDFOR DEMOLITION) WITH THE OWNER.
SPLIT SYSTEM INDOOR UNIT SCHEDULE
MARK MANUF. MODEL #
DIMENSIONS (IN.) WEIGHT(LBS)
AIRFLOW(CFM)
ELECTRICAL
REMARKS LENGTH WIDTH HEIGHT VOLTAGE PHASE
SS-1 DAIKIN FTX09 2'-7" 9" 1'-0" 18 300 208 V 1 1,2,3,4,5,6
SPLIT SYSTEM OUTDOOR UNIT SCHEDULE
MARK MANUF. MODEL #
DIMENSIONS (IN.)
WEIGHT(LBS)
TOTALCOOLING
(MBH)
SENSIBLECOOLING
(MBH)
HEATINGCAPACITY
(MBH)MINIMUM
SEER
ELECTRICAL
REMARKS LENGTH WIDTH HEIGHT MCAMOC
P VOLTAGE PHASE
CU-1 DAIKIN RX09 2'-3" 1'-0" 1'-10" 60 9.0 9.0 10.0 19 12 A 15 208 V 1 1,2,3,4,5,6,7
EXHAUST FAN SCHEDULE
MARK MANUFACTURER MODEL # SERVICE TYPE CFME.S.P.("WG) RPM HP VOLTAGE PHASE STARTER DRIVE DISCONNECT
MAXSONES MAX DBA WEIGHT REMARKS
EF-1 GREENHECK SQ-90 DETENTIONAREA
INLINE 260 0.50 1725 0.1 120 V 1 YES DIRECT YES 8.8 57 60 1,2
EF-2 GREENHECK SQ-97 RESTROOMEXHAUST
INLINE 100 0.50 1725 0.25 120 V 1 YES DIRECT YES 8.6 56 60 1,2
REGISTERS, GRILLES, AND DIFFUSERS SCHEDULE
MARK MANUFACTURER MODEL TYPE GRILLE SIZE PANEL SIZEINLET DUCT
SIZEBRANCH DUCT
SIZE CFM P.D.NOISE
CRITERIATHROW
PATTERN REMARKS
350FL ALUMININUM SIDEWALL GRILLE 10"X8" - 10"X8" 10"x8" 0-200 .05 25 - 1,2
E-1 TITUS 50F ALUMINUM 1/2" EGG CRATE 12"x12" 12"x12" - 6" DIA. 0-100 .05 25 - 1,2
E-2 TITUS SG-PRA ALUMINUM SECURITY GRILLE 12"x12" 12"x12" - 6" DIA. 0-100 .05 25 - 1,2,4
L-2
R-1 TITUS 50F ALUMINUM 1/2" EGG CRATE 22"x22" 24"x24" - 8" DIA. 101-225 .05 25 - 1,2
R-2 TITUS 50F ALUMINUM 1/2" EGG CRATE 22"x22" 24"x24" - 12" DIA 401-600 .05 25 - 1,2
S-1 TITUS OMNI-AA ALUMINUM ADJUSTABLE SQUARE DIFFUSER 12"x12" 12"x12" 6" DIA. 6" DIA. 0-100 .05 25 4-WAY 1,2,3
S-2 TITUS OMNI-AA ALUMINUM ADJUSTABLE SQUARE DIFFUSER 15"x15" 24"x24" 8" DIA. 8" DIA. 101-225 .05 25 4-WAY 1,2,3
S-3 TITUS OMNI-AA ALUMINUM ADJUSTABLE SQUARE DIFFUSER 18"x18" 24"x24" 10" DIA. 10" DIA. 226-400 .05 25 4-WAY 1,2,3
S-4 TITUS SG-PRA ALUMINUM SECURITY GRILLE 12"x12" 12"x12" 6" DIA. 6" DIA. 0-100 .05 25 4-WAY 1,2,3,4,5
REMARKS:
1. MAINTAIN MANUFACTURER'S CLEARANCES.2. PROVIDE INTERNAL CONDENSATE PUMP.3. SIZE ALL REFRIGERANT PIPING PER MANUFACTURER'S INSTRUCTIONS. REVIEW PIPING RUNS WITH MANUFACTURER.PROVIDE ALL COMPONENETS NECESSARY FOR PROPER OPERATION. R-410 REFRISGERANT.4. ELECTRICAL CONNECTION SHALL BE PROVIDED WITH OUTDOOR UNIT.5. PROVIDE WITH WIRED THERMOSTAT.6. ACCEPTABLE MANUFACTURERS INCLUDE DAIKIN, PANASONIC, OR LG.
REMARKS:
1. MAINTAIN MANUFACTURER'S CLEARANCES.2. HEAT CAPACITY IS BASED ON 70 DB INDOOR AIR TEMPERATURE. COOLING CAPACITY IS BASED ON 80 DB/67 WB INDOOR AIR TEMPERATURE AND95 DB AMBIENT.3. PROVIDE SINGLE POINT ELECTRICAL CONNECTION FOR INDOOR AND OUTDOOR UNIT.4. PROVIDE LOW AMBIENT COOLING TO 0 DEGREES.5. SIZE ALL REFRIGERANT PIPING PER MANUFACTURER'S INSTRUCTIONS. REVIEW PIPING RUNS WITH MANUFACTURER. PROVIDE ALL COMPONENTSNECESSARY FOR PROPER OPERATION. R-410 REFRIGERANT.6. ACCEPTABLE MANUFACTURERS INCLUDE DAIKIN, PANASONIC, OR LG.
LOUVER SCHEDULE
MARK MANUFACTURER MODEL # SERVICE CFMLENGTH
(IN)HEIGHT
(IN) FREE AREAVELOCITY
(FPM)APD (IN.
WG.) REMARKS
L-1 RUSKIN ELF375DX RESTROOMEXHAUST
100 10 8 0.20 SF 500 FPM 0.10 1,2,3
L-2 RUSKIN ELF375DX DETENTIONAREA
260 12 12 0.33 SF 680 FPM 0.10 1,2,3
REMARKS:
1. PROVIDE WITH BIRDSCREEN.2. COLOR TO BE SELECTED BY ARCHITECT.3. ACCEPTABLE MANUFACTURERS INCLUDE RUSKIN, PENN, OR GREENHECK.
REMARKS:
1. PROVIDE FACTORY MOUNTED DISCONNECT.2. ACCEPTABLE MANUFACTURERS INCLUDE TWIN CITY, CAPTIVEAIRE, OR GREENHECK.
REMARKS:
1. COLOR TO BE SELECTED BY ARCHITECT.2. COORDINATE MOUNTING TYPE (LAY-IN, GYP BOARD, ETC.) WITH ARCHITECTURAL DRAWINGS.3. PROVIDE AIR ADJUSTER FLAPS/AIR PATTERN DEFLECTORS.4. PROVIDE WITH TAMPER PROOF SCREWS.5. PROVIDE WITH FACE OPERATED DAMPER ACCESSORY.
1/8" = 1'-0"1
TYPICAL ROUND SUPPLY BRANCH DUCTDETAIL
No. Description Date
DN
DN
E(AHU)
E(AHU)
E(SA)
E(SA) E(SA)
A1
A1 A1
A1 A1
A1 A1 A1 A1
A2
A2
E(OA)
E(CU-2) E(CU-2) E(CU-2) E(CU-2)
G
RF
RF
RF
OA
E(SA)
A13
A13
A5 A5 A5
A5
A5
A5
A5
A2 A2 A2 A2
A15
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:2
3 P
M
M2.0
KRM
09/25/2017
1508/XACO16
CMR
DE
MO
- F
IRS
T F
LO
OR
AIR
DIS
TR
IBU
TIO
N
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
1/4" = 1'-0"1
DEMOLITION MECHANICAL FLOOR PLAN
TAGGED NOTES
A1 REMOVE EXISTING DIFFUSER AND BRANCH DUCT. CAP AND PATCH MAIN DUCT SHEETMETAL AND INSULATION.
A2 EXISTING EQUIPMENT TO REMAIN.
A5 REMOVE EXISTING GRILLE.
A13 EXISTING INTAKE LOUVER TO REMAIN.
A15 SALVAGE EXISTING GRILLES AND DUCTWORK IN THIS AREA.
TRUENORTH
PLANNORTH
No. Description Date
DN
DN
PROCESSING
110
PRE-PROCESSING PASSENGERWAITING
108
TOILET
109
STORAGE
107
LAN/TELCO
106
INTERVIEW
105
SEARCH
104
EXIT VESTIBULE
111
EXISTING STAFF TOILET
-
EXISTING STAFF TOILET
-
EXISTING PUBLIC TOILET
-
EXIST. ELECTRICAL
-
EXISTING JANITOR
-
CBP GENERAL OFFICE
101
DETENTION CORRIDOR
103
E-2
75
E-2
100
S-4
75
S-4
75
E(CU-2) E(CU-2) E(CU-2) E(CU-2)
E(AHU)
E(AHU)
S-4
50
10"x8" EA
S-1
35
S-2
200
S-2
200
S-2
200
S-2
175
S-3
275
S-3
275
S-2
200SS-1
E(SA)
24 30 24 60
E(OA)
G
RF
3/4" CDRF
R-2
600
R-2
550
R-1
200
R-1
200
E-2
50
T
TT
CU-1
E(OA)
12"x12" RA
E(SA)
A4
A4A4
A4 A4
A4
A4
A4
A4
A4
A4
E(SA)E(SA) 12"x
14"
RA
A10
A9
A8
A6
A11
EF-2
L-1
E-1
7510"x8" EA
10"x8" EA
10"x
8"
EA
L-2
10'-0"
A14
A16
3/4" CDRF
10"x8" EA
EF-1
POST-PROCESSING PASSENGERWAITING
113
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:2
4 P
M
M3.0
KRM
09/25/2017
1508/XACO16
CMR
AIR
DIS
TR
IBU
TIO
N -
FIR
ST
FL
OO
R
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
TAGGED NOTES
A4 CONNECT TO EXISTING DUCT.
A6 EXTEND CONCRETE PAD FOR CONDENSING UNIT.
A8 SPILL CONDENSATE TO GRADE. PIPE SHALLPENETRATE EXTERIOR WALL AT 1'-0'' ABOVEFINISHED GRADE AND ELBOW DOWN. SEALPENETRATION WALL PENETRATION AIRTIGHT.
A9 SIZE REFRIGERANT PIPING PER MANUFACTURERSREQUIREMENTS.
A10 BALANCE TO 100 CFM OA.
A11 BALANCE TO 150 CFM OA.
A14 EXHAUST LOUVER SHALL BE A MINIMUM OF 10'-0"FROM INTAKE LOUVER.
A16 REINSTALL AND RECONNECT SALVAGED GRILLES INTHIS AREA.
DIFFUSER RUNOUT SCHEDULEMARK BRANCH DUCT SIZE
E-1 6" DIA.
E-2 6" DIA.
R-1 8" DIA.
R-2 12" DIA
S-1 6" DIA.
S-2 8" DIA.
S-3 10" DIA.
S-4 6" DIA.
TRUENORTH
PLANNORTH
No. Description Date
C
SD
SD
BL
P
UON
E, EM
CFOI
OFOI
CFCI
OFCI
T
C/S
J
DESCRIPTION
DP
S
S
X
S
S 3
S D
S K
PC
S
S 4
S
U
SL
N
OS
OS
S PL
IL
GROUND FAULT PROTECTED DUPLEX WITHWEATHER-PROOF "WHILE IN USE" TYPE DIE-CASTMETAL COVERPLATE WITH LOCKABLE ENCLOSUREAT OUTLET - SEE SPECIFICATIONS
WP
ER
DUPLEX FOR ELECTRIC WATER COOLER: PROVIDEREMOTE, READILY ACCESSIBLE GFI DEVICE AT 48"ADJACENT TO WATER COOLER, COORDINATE EXACTLOCATION WITH PLUMBING CONTRACTOR TO CONCEALOUTLET BEHIND COOLER
EWC
AUDIO/VIDEO INTERCOM STATION: MASTER WITHSELECTIVE DOOR CONTROLS, POWER SUPPLIES & DOORRELAY CONTACTS AS REQUIRED FOR OPERATION OF ANYDOOR IN THE SYSTEM AND VIEWING OF ANY AUDIO/VIDEOINTERCOM REMOTE ON THE SYSTEM. AIPHONE#AX-MVW/DESK STAND - COLOR BY ARCHITECT.
SAME AS ''IM'' EXCEPT WALL MOUNTED W
DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATORSTATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR''EMERGENCY RELEASE'' OPERATOR STATIONS ASREQUIRED.
DOOR RELEASE CARD READER STATION. PROVIDE ANYADDITIONAL ROUGH-IN FOR ''EMERGENCY RELEASE''OPERATOR STATIONS AS REQUIRED.
AUTOMATIC DOOR CONNECTION (MAY ALSO HAVEELECTRIC STRIKE/MAG-LOCK/ELECTRIFIED PANICCONNECTION - SEE ARCHITECTURAL HARDWARESPECIFICATIONS)
FLOORBOX, COMBINATION POWER AND LOWVOLTAGE, REFER TO FLOORBOX SCHEDULE
B
SS
KEYED, LOCKED PULL STATION : DOUBLE ACTION.STATION SHALL ONLY BE OPERABLE VIA KEY INPOSSESSION OF STAFF.
CDCARBON MONOXIDE DUCT DETECTOR
POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES
SAME AS ''CR'' EXCEPT MULLION MOUNT M
SLASH THROUGH ANY DEVICE INDICATES MOUNTINGABOVE COUNTERTOP 4" ABOVE BACKSPLASH
OVERHEAD PROJECTOR: PROVIDE DUPLEXRECEPTACLE, ONE DATA, HDMI, 3.5mm AUDIO, ANDVGA OUTLET ON (3) PLATES
CCTV CAMERA: CEILING MOUNT DOME
WP
''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE WITHONE DUPLEX RECEPTACLE ON BOTH SIDES
AUDIO/VIDEO INTERCOM STATION: REMOTE WITHFLUSH-MTD S.S. ENCLOSURE. AIPHONE #AX-DVF.
S VS
VS
LV
PILOT LIGHT SWITCH (ILLUMINATED WHEN LOAD IS ON)
ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATEDWHEN LOAD IS OFF)
EMERGENCY AUTOMATIC TRANSFER SWITCH FORLIGHTING CONTROLS (REFER TO DETAIL)
FILLED CENTER BAR INDICATES INTEGRAL GROUNDFAULT PROTECTION (GFCI)
GANG RECEPTACLE IN COMBINATION WITH SWITCH(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)
NON-REVERSING MOTOR STARTER SNAP SWITCH
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
FLUSH MOUNTED REMOTE ALARM INDICATINGSTATION/TEST SWITCH
CONNECTION TO SPRINKLER TAMPER SWITCHWITH ADDRESSABLE MODULE
CONNECTION TO SPRINKLER FLOWSWITCH WITH ADDRESSABLE MODULE
PHOTO-ELECTRIC SMOKE DETECTOR FORPATIENT ROOM MONITORING (SEE RISER)
PHOTO-ELECTRIC SMOKE DETECTOR
MAIN CONTROL PANEL CENTRAL PROCESSING UNIT (CPU)
DOOR ALARM/POSITION SWITCH
DOOR POWER SUPPLY
DOOR DELAYED EGRESS/ELECTRIFIED PANIC MECHANISM
TELEVISION SYSTEM OUTLET WITH DUPLEX RECEPTACLE,COORDINATE LOCATION WITH WALL BRACKET WHEREAPPLICABLE
SURGICAL LIGHT INTENSITY CONTROL
LIGHT SWITCH: LOW VOLTAGE
AS NOTED
AS NOTED
LIGHT SWITCH FOR UNDER-CABINET LIGHTS
6'-6'' TOTOP
48" TOLEVER
48" TOLEVER
PULL STATION : DOUBLE ACTION
AUDIO-ONLY NOTIFICATION APPLIANCE
VISUAL-ONLY NOTIFICATION APPLIANCE
AUDIO/VISUAL NOTIFICATION APPLIANCE
BELL / LIGHT
BELL ONLY
HEAT DETECTOR
CARBON MONOXIDE ALARM: SINGLE STATIONW/SOUNDER BASE
CARBON MONOXIDE AUDIO/VISUAL NOTIFICATIONAPPLIANCE
DOOR HOLDER : WALL TYPE
DOOR HOLDER : CLOSURE TYPE
DUCT SMOKE DETECTOR
PRESSURE SWITCH
REMOTE L.C.D. FIRE ALARM ANNUNCIATOR
POST INDICATOR VALVE
ISOLATION MODULE
H.V.A.C. SMOKE DAMPER CONNECTION
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
SURFACE PLUG-MOLD
SPECIAL OUTLETS
HD
ABV CLG
CM
F
DH
ABV DOOR DH
ABV CLG DD
FS
TS
PS
4'-0''
I
ZONE ADDRESSABLE MODULE Z
SM
ABBREVIATIONS
DESCRIPTION
XLSL
, ,
STRIP FIXTURE
CROSS-HATCHING INDICATES LIGHT IS POWEREDFROM THE EMERGENCY-CRITICAL BRANCH
PARALLEL-HATCHING INDICATES LIGHT ISPOWERED FROM THE EMERGENCY-LIFE SAFETYBRANCH
PANEL FURNITURE
POWER OUTLETS
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE-SAFETY TYPE, TAMPER-RESISTANT
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
JUNCTION BOX, CEILING OR WALL
VOLTAGE/1PH RECEPTACLE, AS NOTED
VOLTAGE/3PH RECEPTACLE, AS NOTED
SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)
EXAM LIGHT SWITCH
NIGHT LIGHT SWITCH WITH CONSTANTLY ILLUMINATEDHANDLE
LINE VOLTAGE DIMMER SWITCH
LINE VOLTAGE THREE-WAY SWITCH
LINE VOLTAGE FOUR-WAY SWITCH
KEYED SWITCH
OCCUPANCY OR VACANCY SENSOR SWITCH
OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT
LOW VOLTAGE MOMENTARY SWITCH
PHOTO-CELL AS NOTED
SURGICAL/EXAM LIGHT
EXIT LIGHT (CEILING, END, WALL MOUNT)
LIGHTING
REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURESPECIFICATIONS, MOUNTING HEIGHTS, ETC.
SPECIAL VIDEO SYSTEM SIGNAL INPUT
SECURITY PANIC ALARM
SECURITY INTERCOM
SECURITY ACCESS CONTROL
SECURITY CCTV VIDEO SURVEILLANCE
PANIC ALARM BUTTON
PANIC ALARM ANNUNCIATOR
PANIC ALARM POWER SUPPLY CABINET
DOOR RELEASE KEYSWITCH STATION
DOOR RELEASE KEYPAD STATION
MOTION SENSOR DOOR CONTROL
REMOTE DOOR RELEASE PUSH-BUTTON
CCTV CAMERA: WALL MOUNT DOME
CCTV POWER SUPPLIES/CONTROL PANEL 4'-0''
4'-0''
DOORFRAME
ABV DOOR
8" ACT
DESCRIPTION
WALL, CLG
80"
CLG
CLG
CLG
WALL
54"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
1'-6"
1'-6"
1'-6"
1'-6"
4'-0"
1'-6"
1'-6"
ON CNTR.
2'-2"
CLG
AS NOTED
4'-0''
4'-0''
18''
4'-0''
4'-0''
CLG
4'-0''
6'-0''
4'-0''
4'-0''
CEIL.
CLG
7'-0"
S
CLG
S
FLOOR
S
S
S M
TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION
TELEVISION
4'-0" TV-HE
DR
AW
ING
SY
MB
OL
AMBER STROBE 80''
,
SURFACE OR SUSPENDED CEILING FIXTURE (SLASHINDICATES RECESSED)
POLE MOUNTED AREA LIGHT
, ,
,
,
EMERGENCY BATTERY WALL-PACK
WALL MOUNT FIXTURE ,
FLOODLIGHT
V
A
F
F K
F
GRAPHICS DISPLAY TERMINAL
RI
INDICATES VANDAL-PROOF POLYCARBONATE COVER,VANDAL PROOF COVERS SHALL BE UL LISTED FOR USEWITH THE SPECIFIC DEVICE THEY ARE PROTECTING
PC
80"
CLG
WALL
WALL
7'-6''
FIREMAN'S PHONE JACK FP
ADDRESSABLE RELAY MODULE R
WALL
ACCESS CONTROL POWER SUPPLIES/CONTROL PANEL 4'-0''
4'-0''
ABV CLG
ELECTRIC STRIKE AT LATCH
MAGNETIC LOCK(S) ABV DOOR
INDICATES EXTERIOR CAMERA RATED FORCONDITIONS, WET LOCATION LISTED, WITHAUXILLARY HEATER
PTZINDICATES CAMERA WITH PAN/TILT/ZOOM FUNCTION
FLOORBOX, POWER ONLY, AS SCHEDULED FLOOR
FIRE RATED POKE THOUGH FLOOR BOX, COORDINATEEXACT COVER REQUIREMENTS WITH ARCHITECTURALFINISHES, DEVICES AS SCHEDULED
DESCRIPTION
K
DB
DB
WP
DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETEWITH TRANSFORMER (MOUNT ABOVE CEILING INCORRIDOR NEAR PUSH-BUTTON) AND ALL ACCESSORIES,POWER FROM NEAREST AVAILABLE 120V NORMAL POWERGENERAL RECEPTACLE CIRCUIT, NUTONE OR EQUAL
DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDECONNECTION TO PUSHBUTTON STATION IN AREA.COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER, ETC.)DESIRED WITH OwNER/ARCHITECT, NUTONE OR EQUAL
PLUMBING FIXTURE ELECTRIC EYE TRANSFORMERCONNECTION. TRANSFORMER SHALL BE 120V-24V.MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAMETYPE AS/IF NEEDED
PROVIDE CONNECTION TO HAND DRYER (SEEARCHITECTURAL SPECIFICATIONS)
VERIFY WITHARCHITECT
WGWIREGUARD - PROVIDE MANUFACTURER'S SPECIFICGUARD FOR DEVICE NOTED
BOX ON ANY DEVICE INDICATES SURFACE MOUNTEDBACKBOX/WIREMOLD
CONDUIT CONCEALED IN WALLS OR IN CEILINGSPACE: ARROW(S) INDICATE(S) HOME RUN & # OFCIRCUITS: HASHMARKS INDICATE # OFCONDUCTORS. DASHED LINE INDICATESCONDUIT BELOW FLOOR.
WIREWAY WITH REMOVABLE COVER (SIZE AS NOTED)
PANELBOARD, SURFACE OR FLUSH MOUNTED,HATCHING INDICATES EMERGENCY
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
MECHANICAL EQUIPMENT DESIGNATOR(SEE MECH. SCHEDULES)
EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)
KITCHEN EQUIPMENT OUTLET COUPLING CONNECTION(SEE DETAIL)
AS SHOWN
AS SHOWN
AS NOTED
AS SHOWN
MISCELLANEOUS
DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC COMBINATION STARTER
ENCLOSED FLUSH MTD. CIRCUIT BREAKER
WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOROUTDOORS.
TRENCH DUCT (SIZE AS NOTED)
PUSHBUTTON STATION
FLEXIBLE CONDUIT
TRANSFORMER
TAGGED NOTE
REVISION TAG
WIRE BASKET CABLE TRAY, SIZE AS NOTED
LOW VOLTAGE CABLE PATH
5'-0"
5'-0"
5'-0"
5'-0"
4'-0"
4'-0''
7'-6''
6'-6'' TO TOP
XPEXPLOSION PROOF - PROVIDE WIRING METHODS,ENCLOSURES, RATINGS, ETC. AS SUITABLE FORHAZARDOUS LOCATION.
SURGE PROTECTION DEVICE
GENERATOR ANNUNCIATOR PANEL - SEE SPECIFICATIONS 4'-0''
THERMOSTAT PROVIDED BY MECHANICAL CONTRACTOR,ELECTRICAL CONTRACTOR SHALL PROVIDE BACK-BOXCONDUIT STUB-UP, REFER TO MECHANICAL DRAWINGSFOR LOCATIONS
PANEL FURNITURE DUPLEX RECEPTACLE. PROVIDE ALLWIRING AS REQUIRED, COORDINATE EXACTINSTALLATION REQUIREMENTS AND LOCATIONS WITHOWNER'S PANEL FURNITURE VENDOR
PANEL FURNITURE DATA/VOICE OUTLET. PROVIDE ALLWIRING AS REQUIRED, COORDINATE EXACTINSTALLATION REQUIREMENTS AND LOCATIONS WITHOWNER'S PANEL FURNITURE VENDOR
POWER CONNECTION TO PANEL FURNITURE,PROVIDE SEAL-TIGHT CONDUIT CONNECTION FROMRECESSED WALL BOX TO PANEL FURNITURE,PROVIDE FINAL CONNECTIONS TO PANEL FURNITUREAS REQUIRED BY PANEL FURNITURE VENDOR
1'-6"
COMBINATION POWER AND LOW VOLTAGE CONNECTIONTO PANEL FURNITURE, PROVIDE SEAL-TIGHT CONDUITCONNECTION FROM RECESSED WALL BOX TO PANELFURNITURE, PROVIDE FINAL CONNECTIONS TO PANELFURNITURE AS REQUIRED BY PANEL FURNITUREVENDOR
PPPOWER POLE AS NOTED
,
SECURITY INTRUSION DETECTION
MOTION DETECTOR CLG
MOTION DETECTOR KEYPAD CONTROLLER 4'-0''
SECURITY SYSTEM HEAD END 4'-0''
LIGHTING CONTROL SWITCHES
MOMENTARY CONTACT SWITCH
HAND-OFF-AUTO 3-POSTION SWITCH
TIMER SWITCH
S MC
S HOA
S T
4'-0"
4'-0"
4'-0"
M
SV
S
S
V
1'-6''
4'-0''PAGING SYSTEM AMPLIFIER/TUNER CABINET
PAGING MICROPHONE
WALL VOLUME CONTROL
PAGING SPEAKER: WALL
PAGING SPEAKER W/ VOLUME CONTROL
PAGING SPEAKER: CEILING CLG
CLG
8'-0"
4'-0"
OVERHEAD PAGING
VANDAL PROOF / WEATHERPROOF WALL MOUNTEDPAGING SPEAKER. QUAM VP1
EXTERIOR VANDAL PROOF / WEATHERPROOF WALLMOUNTED PAGING SPEAKER, SHALL BE PAINTEDCOLOR SELECTED BY ARCHITECT/OWNER. QUAM VP6
RECESSED WALL MOUNTED PAGING SPEAKERDUKANE 5A606 SPEAKER. ATLAS 417-8WD
WALL MOUNTED PAGING HORN
CALL INITIATION STATION
LCD WALL DISPLAY
8'-0"
9'-0"
SEEFLOORPLANS
SEEFLOORPLANS
44"
S
H
S
S
C
LD
R
EXT.
FIRE ALARM
WP
PUSH-TO-EXIT BUTTON 4'-0''
SURFACE WIRE-MOLD
PE
PA
MK
MD
SEC-M
GEN-A
SPD
J
J
ML
ES
SEC-A
GDT
AS
NAC
CC
CC
CR
RR
DP
DA
IM
KP
IR
KS
MS
PP
CR
DS
AD
IM
PIV
FAA
FACP
SEC-P
PA
PB
SEC-C
J
T
FP
DR
AW
ING
SY
MB
OL
DR
AW
ING
SY
MB
OL
MO
UN
TIN
GH
EIG
HT
(T
OC
EN
TE
R O
FB
OX
)
DR
AW
ING
SY
MB
OL
AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED
AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED
EQUIP-1
PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYESENSOR CONNECTION. COORDINATE EXACTCONNECTION REQUIREMENTS WITH MANUFACTURER.
GROUND
NEUTRAL
PHASE
FIREMAN'S KNOX BOX CONNECTION KB
REMOTE FIRE ALARM ANNUNCIATOR W/ MICROPHONE 54" FAAM
WALL, CLG
WALL, CLG V
A
F,
,
,
CM
INDICATES CHIME AUDIBLE NOTIFACTION CH
DEVICE USED FOR ELEVATOR CONTROL EL
FIRE ALARM CONTROL EXTENDER EXT
4'-6''
TRANSPONDER CABINET 4'-0'' TRAN
BE , BRPROJECTED BEAM SMOKE DETECTOR; EMITTER(BE) AND RECEIVER (BR)
FLOOR
AV
AUDIO/VISUAL SYSTEM OUTLET WITH DUPLEXRECEPTACLE, REFER TO ASSOCIATED DETAIL FORADDITIONAL INFORMATION
1'-6"
COMBINATION POWER AND DATA OUTLET LOCATION,REFER TO ASSOCIATED DETAIL FOR ADDITIONALINFORMATION
1'-6"
COMBINATION POWER AND DATA OUTLET LOCATION,GFCI DUPLEX RECEPTACLE, REFER TO ASSOCIATEDDETAIL FOR ADDITIONAL INFORMATION
1'-6"
1'-6"FF
,
,
DEAD FRONT GFCI DEVICE, LABEL AND INSTALL INREADILY ACCESSIBLE LOCATION
FILLED OUTER BARS INDICATES INTEGRAL INTEGRALUSB OUTLETS IN ADDITION TO POWER RECEPTACLES
1'-6"
, J
VARIABLE FREQUENCY DRIVE 5'-0"
CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROMSTUB UP CONDUIT
MOTOR CONNECTION, REFER TO EQUIPMENTCONNECTION SCHEDULE
DUPLEX RECEPTACLE, CEILING MOUNTED CLG
CONDUIT UP
CONDUIT DOWN
GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''
WIREGUARD - PROVIDE MANUFACTURER'S SPECIFICGUARD FOR DEVICE NOTED
PAY
#D/#V
#D
INTERMEDIATE DISTRIBUTION FRAME - REFERENCEDATA SYSTEM SCHEMATICS AND DETAILS FORADDITIONAL REQUIREMENTS
MAIN DISTRIBUTION FRAME - REFERENCE DATA SYSTEMSCHEMATICS AND DETAILS FOR ADDITIONALREQUIREMENTS
WIRELESS ACCESS POINT OUTLET WITH PROVISIONSFOR (1 DATA OUTLET FOR ANTENNA. PROVIDE ACOMPLETE DATA OUTLET WITH FACEPLATE ABOVECEILING, MOUNTED AT AN ACCESSIBLE HEIGHT NO MORETHAN 24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A20' COIL OF CABLE AHEAD OF THE OUTLET FORADJUSTMENT OF FINAL OUTLET LOCATION. THECONTRACTOR SHALL COORDINATE EXACT LOCATIONSWITH THE OWNER AND ADJUST OUTLET LOCATIONS ATSUBSTANTIAL COMPLETION TO ACCOMMODATE OWNER'SWAP LOCATIONS.
TELECOMMUNICATIONS SYSTEM BACKBOARD. PROVIDE96''H x 3/4''D FIRE-RETARDENT PLYWOOD BACKBOARDWITH TWO (2) COATS OF NON-C0NDUCTIVE, FIRE-RETARDANT LIGHT GRAY PAINT, #3/0 TO GROUND BAR ATMAIN SERVICE SWITCHBOARD, 30-PT GROUND BAR AND A6'-0'', #3 AWG PIGTAIL AT BACKBOARD. INSTALL BOARD AT2' AFF. (LENGTH OF BOARD AS INDICATED ON FLOORPLAN)
WAP
DATA OUTLET : NUMBER BESIDE OUTLET INDICATESNUMBER OF DATA JACKS
VOICE OUTLET : NUMBER BESIDE OUTLET INDICATESNUMBER OF VOICE JACKS
COMBINATION OUTLET : NUMBER BESIDE OUTLETINDICATES NUMBER OF DATA/VOICE JACKS
TELEMETRY ANTENNA
RF TRACKER ANTENNA
DATA / VOICE
AS REQ'D.OUTLET (VOICE ONLY) : PAYPHONE TYPE
1'-6"
1'-6"
1'-6"
CLG
CLG
#V
MDF
IDF
TEL
SLASH THROUGH ANY DEVICE INDICATES MOUNTINGABOVE COUNTERTOP 4" ABOVE BACKSPLASH
,
#D
,
#V
,
#D/#V
S 1LINE VOLTAGE SWITCH 4'-0"
CLG
MO
UN
TIN
GH
EIG
HT
(T
OC
EN
TE
R O
FB
OX
)
MO
UN
TIN
GH
EIG
HT
(T
OC
EN
TE
R O
FB
OX
)
MO
UN
TIN
GH
EIG
HT
(T
OC
EN
TE
R O
FB
OX
)
DESCRIPTION
CA
BL
ING
/CO
ND
UC
TO
RS
- O
F O
I
CA
BL
ING
/CO
ND
UC
TO
RS
- O
F C
I
CA
BLIN
G/C
ON
DU
CT
OR
S -
C F
C I
ITE
M U
SE
D O
N P
RO
JE
CT
DE
VIC
ES
- O
F C
I
DE
VIC
ES
- C
F C
I
SYSTEM DE
VIC
ES
- O
F O
I
SECURITY: PANIC ALARM (VENDOR ALLOWANCE)
SECURITY: ACCESS CONTROL (VENDOR ALLOWANCE)
SECURITY: INTERCOM (VENDOR ALLOWANCE)
SECURITY: CCTV (VENDOR ALLOWANCE)
SYSTEMRESPONSIBILITYMATRIX
FIRE ALARM
TELEVISION
DATA PROCESSING
TELEPHONE
SYSTEM RESPONSIBILITY GENERAL NOTES:
A. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TOVENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGSSHALL BE INCLUDED BY THE CONTRACTOR.
B. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESSCONTROL DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.
C. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACTINSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OFALL SYSTEMS PRIOR TO CONSTRUCTION.
D. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS,CONTRACTOR SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TOCABLE PATHS AS REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS ATCABINETS/ON BACKBOARDS AS REQUIRED. COORDINATE EXACTREQUIREMENTS WITH APPROPRIATE VENDORS PRIOR TO CONSTRUCTION.
E. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALLSYSTEMS INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION,GROUNDING, TESTING, LABELING, ETC.
F. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEMCOMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THECONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TOBID. ALL SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BEFULLY COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORSSHALL COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR TOBID. NEW COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMSWHERE POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BECOORDINATED WITH THE OWNER PRIOR TO ORDERING. ALL PROGRAMMINGSHALL BE INCLUDED AS REQUIRED BY THE OWNER. PROVIDE 4 HOURS OFTRAINING FOR EACH SYSTEM.
SECURITY: PANIC ALARM
SECURITY: ACCESSCONTROL
SECURITY: INTERCOM
SECURITY: CCTV
FIRE ALARM
SYSTEM COMPANY CONTACT
SIMPLEX
MATRIX SYSTEMSINC.
MATRIX SYSTEMSINC.
MATRIX SYSTEMSINC.
MATRIX SYSTEMSINC.
DANNY CALIA859-294-7233
JEFF STOUT844-593-6879
JEFF STOUT844-593-6879
JEFF STOUT844-593-6879
JEFF STOUT844-593-6879
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:1
6 P
M
E1.0
AKP
09/25/2017
1508/XACO16
WRS
EL
EC
TR
ICA
L L
EG
EN
D
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
ELECTRICAL GENERAL NOTES• EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO
THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITHSPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT WITH ANY OTHER BUILDINGSSYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.
• ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THECONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE UNDERSTANDING OF THEPROJECT REQUIREMENTS.
• WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES. INCLUDINGBUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.
• CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATEAND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TOELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
• ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED.ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.
• INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THECOLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.
• ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOWCLARIFICATION BY WRITTEN ADDENDUM.
• WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENTREQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.
• DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND MUST BESUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.
• OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT.(CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).
• MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO.MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.
• INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS ANDDIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER PRIOR TOINSTALLATION FOR CLARIFICATION.
• DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE RATING. NOINSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.
• THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE,FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.
• ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOTMEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THEACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER
• ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATEOF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY PERIODS FOREQUIPMENT ARE SPECIFIED.
• UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OREXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENTSURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.
• WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKESUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY.COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND ARCHITECT.
• THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THEUTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).
• COORDINATE WITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEWORK DETAILS FOR LOCATION OF ADDITIONALRECEPTACLES, UTILITY OUTLETS, ELECTRICAL DEVICES, ETC.
• CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2'DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.
• ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROMSURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BESATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE ENGINEER.
• CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.
• PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT
• DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THERESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION,WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.
• THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THISCONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORKOF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANYSUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.
• WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THEENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS,CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.
• WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD ORPRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TOMAINTAIN CEILING RATINGS.
• COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHENEQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATEDSHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE CONTRACTOR(S).
• ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OROTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOTACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE ENGINEER IN WRITING.
• ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE ORMULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.
• NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E.VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.
• ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DONOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THISPRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACHUNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATEAND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED INACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOSTSTRINGENT REQUIREMENT SHALL APPLY.
• ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE.DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN PERMISSION FROM THEENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.
• WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLECONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.
• REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETSAND EQUIPMENT. IF IN DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.
• FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONSPROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER PRIOR TOROUGHING-IN ANY WORK.
• AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FORSEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARYCONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE.
• THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTINGAND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.
• ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF INDOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.
• INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITYCOMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. ASCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TOAVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANYANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGERNOTIFICATION PERIOD, SO PROVIDE.
• WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAMEWALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND TRANSMISSION FROMROOM TO ROOM.
• JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL.LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH SPECIFICATIONS, WHICHEVERIS MORE STRINGENT.
• ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONALELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OFLOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVINGJURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT SHALL APPLY.
• DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONEDDRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.
• NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTERHOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.
• ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THEOWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.
• REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. WORK SHALL BE COMPLETED IN PHASES PER THEPHASING PLAN AND AS COORDINATED WITH OWNER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTALINSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS REQUIRED BY OWNER TO ACCOMPLISH THEPHASING PLAN.
12" = 1'-0"1
ELECTRICAL LEGENDNo. Description Date
DN
DN
J
J
FF
F
F
FF J
J J J J
CR
F
S
S
KP
KP
CR
KP
KP
.
GFI
.
GFI
.
GFI
.
3
.
3
.
GFI
.
MC
.
MC
.
EPB
.
EPB
.
MC
X4
X4
X4
X6
X5
X7
X8
X16
X3
X16
X13
X3
X3
X15X15X15X15
X3
X3
X9
X9
X11
X12
X10
X2
X17
X17
X3
X3X2 X1
X17
X17
X14
X14
X14
X15
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:1
7 P
M
E2.0
AKP
09/25/2017
1508/XACO16
WRS
DE
MO
- F
IRS
T F
LO
OR
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
GENERAL NOTES (DEMOLITION):
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINESINDICATE EXISTING ITEMS TO REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITSTHAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHENDEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THEDRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OREQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON THE CIRCUITS SHALLREMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUITBREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BELABELED AS SPARES IN THEIR PANELS. PROVIDE NEW TYPEWRITTENDIRECTORIES FOR ALL PANELS AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THISDRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY AREDIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTINGCONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL.THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATEDHEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTIONTHAT THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HEPROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FORDEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH ANDREPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES ARESHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW FINISHES -SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FORDEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO OWNER ATTHEIR OPTION.
F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/ORRELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATEDWITH THEIR EQUIPMENT.
G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTIONBARRIERS AS REQUIRED.
H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGSAS REQUIRED WHERE DEVICES ARE BEING REMOVED OR INSTALLED.
I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLECEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NECREQUIREMENTS.
J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALLBE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENTSHOWN ON PLANS.
K. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OFBUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT ANDAS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BERESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTENINSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER ASREQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL ANDENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.
L. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORKPLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEWLOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.
M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALLBE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND INSERTSLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES ORNUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE DETAILEDAND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL ROOMNUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSEDBREAKERS SHALL BE IN OFF POSITION.
TAGGED NOTES
X1 EXISTING PANEL PP5. PANEL TO BE REMOVED AND RELOCATED . SALVAGEEXISTING FEEDER. PANEL IS 120/240 VOLT, RATED AT 100 AMPS.
X2 EXISTING MATRIX SYSTEM ACCESS CONTROL PANEL TO TO BE SALVAGED ANDREINSTALLED AT NEW LOCATION.
X3 EXISTING FIRE ALARM DEVICE TO BE SALVAGED AND REUSED IN EXPANDEDSIMPLEX SYSTEM.
X4 MOMENTARY CONTACT SWITCH TO BE REMOVED.
X5 EXISTING PANEL PP2 TO REMAIN.
X6 EXISTING PANEL PP3 TO REMAIN.
X7 EXISTING TELECOMMUNICATION BACKBOARD AND SERVICE ENTRANCE.SERVICE TO REMAIN.
X8 EXISTING SIMPLEX FIRE ALARM CONTROL PANEL (FACP) 4010 TO BE EXPANDEDAS NEEDED FOR AREA OFRENOVATION.
X9 EXISTING EMERGENCY PUSH BUTTON TO BE SALVAGED AND REUSED.
X10 EXISTING PANELS TO BE REMOVED AND RELOCATED. SALVAGE EXISTINGFEEDER. PANEL IS 120/240 VOLT, RATED AT 100 AMPS.
X11 EXISTING IT SERVER TO BE RELOCATED. PROVIDE NETWORK CONNECTIONS TONEW LAN/TELCO ROOM.
X12 EXISTING EIGHT (8) CAT 5E NETWORK CONNECTIONS. CABLES TO BE REMOVED.
X13 EXISTING WATER HEATER WITH ELECTRICAL CONNECTIONS TO REMAIN. REFEEDAS NEEDED.
X14 EXISTING EMERGENCY EGRESS REMOTE HEAD TO REMAIN AND REFEED VIANEW INVERTER POWER SUPPLY
X15 EXISTING MECHANICAL UNIT TO REMAIN. MAINTAIN POWER AS NEEDED.
X16 EXISTING FIRE ALARM DEVICE EXISTING TO REMAIN. MAINTAIN OPERATION.
X17 EXISTING ACCESS CONTROL READER/KEYPAD TO BE REMOVED. REVISE ACCESSCONTROL PROGRAMMING TO REFLECT REMOVAL OF DEVICES.
1/4" = 1'-0"1
DEMO - FIRST FLOOR
TRUENORTH
PLANNORTH
No. Description Date
LR
LR
LR
LR OS
OSOSOS
LR
PROCESSING
110
CBP GENERAL OFFICE
101
EXIT VESTIBULE
111
EXISTING PUBLIC TOILET
-
EXISTING STAFF TOILET
-
EXIST. ELECTRICAL
-
EXISTING JANITOR
-
DETENTION CORRIDOR
103
SEARCH
104
INTERVIEW
105
LAN/TELCO
106
STORAGE
107
PRE-PROCESSING PASSENGERWAITING
108
TOILET
109
R1 R1 R1
R1R1R1 R1
R1
R1E
R1 R1
S1E S1
S1S1
VR2E
VR2
VR1E
VR1
R1 R1
R1
R1R1
R1E
R1
R1E
R2R2E
.OS
.OS
R1 R1 R1 R1
.OS
R1
X1
.3
.OS
X2
L2
X1
L1
L1
.LVD
.LVD
.LVD3
.LVD3
a a a a
a
aa
aa
aa
a
bb
b
b
a
b
R1
S2
U1
L5
R1
b
-16PP2
L3 L3
L4
.LVD3
L7
L7
L1
L7
L6
.LVD3
.LVD3.LVD3a b
L4
PP2PP5
L4
L2
-18PP2
U1
U1
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:1
8 P
M
E3.0
AKP
09/25/2017
1508/XACO16
WRS
LIG
HT
ING
- F
IRS
T F
LO
OR
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
1/4" = 1'-0"1
LIGHTING - FIRST FLOOR
GENERAL NOTES (LIGHTING):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL ANDCEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, ASINDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCHCIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDEDWITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRALCONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IFADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSEINDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYINGCONDUCTORS PER N.E.C. #310.15(B)(3), AND UPSIZE CONDUIT ASREQUIRED PER N.E.C. #300.17 AND ANNEX C. MULTIWIRE BRANCHCIRCUITS AS DEFINED IN N.E.C #100 / 210.4 (CIRCUITS SHARING A COMMONNEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVELABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVEEMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. ALSO,MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.
D. LOCATE CHAIN-HUNG INDUSTRIAL FIXTURES IN MECHANICAL ROOMS TOAVOID DUCTWORK AND PIPING, TO MAXIMIZE AVAILABLE LIGHT. SPACEAROUND EQUIPMENT, AIR HANDLERS, ETC. TO PROVIDE ADEQUATELIGHTING TO ALL AREAS OF ROOM. PROVIDE ADDITIONAL FIXTURES OFSAME TYPE AS NEEDED TO FULFILL THIS REQUIREMENT.
E. LOCATE EXIT SIGNS FOR MAXIMUM VIEWING AREA TO IDENTIFY EGRESSPATHS AS INDICATED ON PLANS. COORDINATE LOCATIONS SUCH THATARCHITECTURAL FEATURES OR EQUIPMENT FROM OTHER TRADES DONOT OBSTRUCT VIEW.
F. WHERE EXIT SIGNS OR EMERGENCY BATTERY PACKS ARE PROVIDED,THEY SHALL BE CONNECTED TO AN UNSWITCHED LINE.
G. LUMINAIRES INDICATED WITH MULTI-LEVEL SWITCHING SHALL HAVESIMILAR LAMPS CONTROLLED TOGETHER, I.E. INBOARD AND OUTBOARDLAMPS OR RIGHT AND LEFT HAND LAMPS.
H. ALL LIGHTING FIXTURE LENSES, PARABOLIC LOUVERS, DOWNLIGHTINGALZAK CONES AND "PARACUBE" LOUVERS SHALL BE HANDLED WITHCOTTON GLOVES DURING INSTALLATION AND LAMPING TO AVOIDFINGERPRINTS OR DIRT DEPOSITS. IT IS PREFERRED THAT FIXTURES BESHIPPED AND INSTALLED WITH CLEAR PLASTIC BAGS TO PROTECTLOUVERS. AT CLOSE OF PROJECT, AND AFTER CONSTRUCTION AIRFILTERS ARE CHANGED, REMOVE BAGS. ANY LOUVER OR CONE SHOWINGDIRT OR FINGER PRINTS SHALL BE CLEANED WITH SOLVENTRECOMMENDED BY THE MANUFACTURER, OR REPLACED AS NECESSARYIN ORDER TO TURN OVER TO THE OWNER NEW FIXTURES AT OCCUPANCY.
I. RECESSED LUMINAIRES SHALL BE SECURED SUCH THAT THE FORCEREQUIRED INSERTING LAMPS, TRIMS, LENSES, LOUVERS, OR DOORFRAMES DOES NOT SHIFT HOUSING. ALL TRIMS SHALL BE COMPLETELYFLUSH WITH FINISHED CEILINGS AT COMPLETION OF CONSTRUCTION.
J. CONTRACTOR SHALL PROVIDE UNSWITCHED CONDUCTOR TO ALL EXITSIGNS, EMERGENCY INVERTER BATTERY PACKS, AND NIGHT LIGHTS ASREQUIRED.
TAGGED NOTES
L1 EXISTING ROOM LIGHT FIXTURES AND CONTROLS REMAIN AND RECIRCUITED.
L2 LIGHTING CONTROL RELAY WITH NETWORK INTERFACE. RELAYS TO PROVIDEAUTOMATIC LIGHTING CONTROL VIA PROGRAMMABLE TIMECLOCK SCHEDULE.
L3 LIGHT CONTROL SWITCH TO BE VANDAL PROOF (INSTITUTION GRADE).
L4 LIGHTING CONTROL RELAY FOR LOCAL LIGHTING CONTROL(SWITCH/OCCUPANCY SENSOR).
L5 PROVIDE WALL MOUNTED "IN USE" LIGHT TO ILLUMINATE UPON LIGHT CONTROLON STATUS IN ROOMS 103, 104, AND 105. LIGHT TO BE LASERMET SLIM JIM THINPROFILE LED "ROOM IN USE" SIGN OR EQUAL.
L6 REPLACE EXISTING EXIT SIGN WITH TYPE X1.
L7 NEW LIGHTING CONTROL SWITCH. CIRCUIT TO EXISTING FIXTURES.
TRUENORTH
PLANNORTH
No. Description Date
DN
DN
J
J
J
J
PROCESSING
110
CBP GENERAL OFFICE
101
EXIT VESTIBULE
111
EXISTING PUBLIC TOILET
-
EXISTING STAFF TOILET
-
EXIST. ELECTRICAL
-
EXISTING JANITOR
-
DETENTION CORRIDOR
103
SEARCH
104
INTERVIEW
105
LAN/TELCO
106
STORAGE
107
TOILET
109
.
GFI
.
GFI
.
GFI .
GFI
.
GFI
E2
NEMA 14-20
.
GFI
.
GFI.
M
E1
E1
.
M
E5
.
PRE-PROCESSING PASSENGERWAITING
108
PP2
-17PP2
.
GFI
-4PP2
-3PP2
-2PP2
E6
EF-2
SS-1
.
M
-1PP5
-7PP2
-8PP2
-11PP2
-10PP2
-12PP2
-13PP2
-14PP2
-2PP5
-1PP2
.
GFI
.
MCU-1-4,6PP5
.
MEF-1
-3PP5
PP5
-5PP2
E3E4
E7
E7
-6PP2
-15PP2
E1
E8
E5
-9PP2
E9
E9
-19PP2
S18S19
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:1
9 P
M
E4.0
AKP
09/25/2017
1508/XACO16
WRS
PO
WE
R -
FIR
ST
FL
OO
R
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
1/4" = 1'-0"1
POWER - FIRST FLOOR
GENERAL NOTES (POWER):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL ANDCEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, ASINDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3)BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BEPROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATEDNEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING.IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITHTHOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENTCARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT ASREQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITSAS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A COMMON NEUTRALCONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEARADHESIVE LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES,ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CAREAREAS. MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUITNUMBER.
D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCHAS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM SHALL BEMARKED IN ACCORDANCE WITH NEC 406.3(E).
E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTSSHALL BE COORDINATED WITH MECHANICAL AND PLUMBINGCONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE ISMAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIREDCLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESEAREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENTNAMEPLATES OR ACCESS PANELS OR THROUGHACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHERTRADES.
TAGGED NOTES
E1 EXISTING ROOM TO REMAIN. MAINTAIN POWER TO EQUIPMENT LOCATED ATTHESE LOCATIONS.
E2 DISCONNECT TO BE PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATEINSTALLATION WITH MECHANICAL CONTRACTOR.
E3 RELOCATED PANEL PP2. REWORK FEEDER TO LOCATION SHOWN.
E4 RELOCATED PANEL PP5. REWORK FEEDER TO LOCATION SHOWN.
E5 PROVIDE NEW RECESSED FLOOR BOX WITH QUAD RECEPTACLE AT PODIUM.
E6 RECEPTACLE DEDICATED FOR MICROWAVE ONLY.
E7 RECEPTACLES AT LOCATIONS SHOWN ARE TO BE TAMPER PROOF(INSTITUTIONAL) TYPE.
E8 POWER FOR TRANSACTION WINDOW.
E9 POWER CONNECT PROVIDED WITH OUTDOOR UNIT.
S18 ALL CCTV SIGNALS TO HOMERUN TO LAN/TELCO ROOM. SECURITY VENDOR TOPROVIDE NETWORK VIDEO RECORDER WITH 45 DAY BACKUP. CBP OFFICE TOHAVE SELECT REVIEW/MONITOR PERMISSIONS AND CBP TO HAVEADMINISTRATIVE PERMISSIONS.
S19 PROVIDE LOCAL VIDEO MONITORING AND CONTROL STATION. COORDINATEWITH SECURITY VENDOR AND CBP.
TRUENORTH
PLANNORTH
No. Description Date
DN
DN
F
S
CC
CC
CR
CC
CC
CC CC
PB
PB
F
F
F
V
V
V
SD
SD
SD
SD
F
SD
SD
WAP
SD
SD
S
SD
SD
WAP
SD
SD
FF
CC
CR
CC
CC
CC
CC
CR
PB
CR PB
MD
MD
MD
MK
MD
ES
M
MK
MD
DA
DA
DA
A
CR
RR
RR
CR
ES
CC
MDMD
MDMD
M
PA PA
IM
MD
PA
M
CR
IR
MD
ES
ES
CR
CR
KP
PE
CR
ES
CBP GENERAL OFFICE
101
PROCESSING
110
STORAGE
107
LAN/TELCO
106 INTERVIEW
105
SEARCH
104
TOILET
109
PRE-PROCESSING PASSENGERWAITING
108
EXISTING PUBLIC TOILET
-
EXIT VESTIBULE
111
EXIST. ELECTRICAL
-
EXISTING JANITOR
-
EXISTING STAFF TOILET
-
.
2D
S1
.
LCD
S3
S2
DETENTION CORRIDOR
103
.
2D
.
2D
S4
.
2D
.
2D
.
2D
S5
S9
S4
S2
S8
S11
4D
S10
S7
S6
m
m
.
2D
.
2D
m
S14
S16
S19
S12
S17
S13
.
2D
S16
S7
S20
S21
ACPS22
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:1
9 P
M
E5.0
AKP
09/25/2017
1508/XACO16
WRS
SY
ST
EM
S -
FIR
ST
FL
OO
R
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S
1/4" = 1'-0"1
SYSTEMS - FIRST FLOOR
GENERAL NOTES (SYSTEMS):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, ANDCASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILINGMOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATEDON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITSPER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH ADEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORSSHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORSARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTORSHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C.MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITSSHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVELABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVEEMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARKINSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.
D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND SHEET)AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF EACH SYSTEM.
E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO THENEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS). REFER TOCABLING PATH INSTALLATION DETAIL FOR ADDITIONAL REQUIREMENTS.
F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT BLUEFOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH. PROVIDE PULLSTRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM CABLING INSTALLATION.
TAGGED NOTES
S1 FIXED CCTV INTERVIEW CAMERA WITH WIDE-ANGLE LENS. HOMERUN NETWORKCABLE TO LAN/TELCO ROOM 106 RACK. CAMERA TO INCLUDE MICROPHONE WITHAUDIO RECORDING.
S2 RECESSED DURESS ALARM BUTTON CONCEALED UNDER TABLE. CONNECT TOCCC AND/OR OTHER DBP DESIGNATED LOCATION
S3 INTERVIEW CAMERA MONITOR.
S4 SMOKE DETECTOR IN SEARCH AND INTERVIEW ROOM TO HAVE INSTITUTIONALRATED COVER (SHROUD).
S5 LAN/TELCO ROOM IS TO BE SHIELDED. COORDINATE ROOM PENETRATION ANDPROVIDE UNIQUE GROUND.
S6 PROVIDE AUDIO/VISUAL DURESS ALARM INDICATOR OVER DOOR.
S7 DETENTION GRADE MICROPHONE, CEILING MOUNTED TO BE PROVIDED BYSECURITY VENDOR. PROVIDE SINGLE GANG BACKBOX WITH 3/4" CONDUIT TOSECURITY HEADEND. AUDIO/VIDEO TO BE RECORDED VIA NETWORKED VIDEORECORDER.
S8 NEW RECESS FLOOR BOX TO INCLUDE (4) DATA CONNECTIONS ANDMICROPHONE AND CAMERA SYSTEM CABLING WITH INTERFACE TO SECURITYSYSTEM.
S9 REUSE EXISTING ACCESS CONTROL KEYPAD AT LOCATION SHOWN.
S10 DOOR TO HAVE REMOTE RELEASE FROM PROCESSING 110 PODIUM. SEE NOTES11.
S11 PROVIDE REMOTE RELEASE CARD READER FOR EXIT VESTIBULE 111 DOOR.
S12 ACCESS CONTROL SYSTEM IS TO BE EXPANSION OF EXISTING FACILITY SYSTEM.ACCESS CONTROL TO BE BY SECURITY VENDOR (MATRIX SYSTEMS).COORDINATE ALL RACEWAY, POWER, CABLING INSTALLATION, AND OPERATIONWITH VENDOR.
S13 KEYPAD TO DISABLE LAN/TELCO INTRUSION DEVICES ONLY. CODE ENTEREDSHUTS OFF MOTION DETECTION AND DOOR ALARMS WITHIN A 60 SECONDWINDOW.
S14 SECURITY SYSTEM IS TO BE MONITORED BY AIRPORT SECURITY. COORDINATEMONITORING METHOD WITH CBP AND SEGREGATE ALARMS AND DEVICESACCORDINGLY.
S16 REMOTE INTERCOM STATION WITH NETWORK CONNECTION. CONNECT TOMASTER INTERCOM LOCATED IN CBP GENERAL OFFICE 101.
S17 INTERCOM MASTER STATION TO BE LOCATED NEAR TRANSACTION WINDOW.
S19 PROVIDE LOCAL VIDEO MONITORING AND CONTROL STATION. COORDINATEWITH SECURITY VENDOR AND CBP.
S20 PROVIDE REMOTE RELEASE CARD READER FOR DOOR 108.
S21 WIRE MESH NEEDS TO ALSO BE PLACED ON THE CEILING IN THE SEARCH ROOM.
S22 ACCESS CONTROL PANEL
TRUENORTH
PLANNORTH
No. Description Date
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MODEL LUMENS WATTAGE VOLTAGE
FIXTURE DESCRIPTION MANUFACTURER AND SERIES MODELTRUE LUMEN
OUTPUTTOTAL WATTAGE VOLTAGE MOUNT ORDERING INFORMATION
R1
RECESSED 2' X 4' LED VOLUMETRIC TROFFER WITH CURVED, LINEAR LENS.2-3/8” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL
REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACTRESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR WITH POLYMER
LIGHT DIFFUSING FILM, INTEGRAL 89% EFFICIENT LOW INRUSH MULTI-VOLT0-10V DIMMABLE DRIVER, 4000 KELVIN 82 CRI LED ARRAY PRODUCING 4800
DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS
LITHONIA 2BLT4 OR EQUAL 5,117 45 120V CEIL. 2BLT4-48L-ADSM-LP840
R1E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2BLT4 OR EQUAL 5,117 45 120V CEIL. 2BLT4-48L-ADSM-LP840
R2
RECESSED 2' X 4' LED VOLUMETRIC TROFFER WITH CURVED, LINEAR LENS.2-3/8” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL
REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACTRESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR WITH POLYMER
LIGHT DIFFUSING FILM, INTEGRAL 89% EFFICIENT LOW INRUSH MULTI-VOLT0-10V DIMMABLE DRIVER, 4000 KELVIN 82 CRI LED ARRAY PRODUCING 6000
DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS
LITHONIA 2BLT4 OR EQUAL 6,163.60 52.95 120V CEIL. 2BLT4-60L-ADSM-LP840
R2E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2BLT4 OR EQUAL 6,163.60 52.95 120V CEIL. 2BLT4-60L-ADSM-LP840
VR1
SURFACE MOUNTED 2' X 4' LED VANDAL RESISTANT, DAMP LOCATION LEDTROFFER. 20-GAUGE COLD ROLLED STEEL DOOR FRAME,
TAMPER-RESISTANT FASTNERS AND POLYCARBONATE LENS. 18 GUAGESWING ARMS. UNPAINTED GALVANIZED STEEL. 4000KELVIN, 80 CRI WITH 5000DELIEVERED LUMENS. LONG LIFE LED'S, HIGH-EFFICIENCY DRIVERS. LUMEN
MAINTENANCE OF L80/60,000 HOURS, L70 RATED LIFE OF 100,000 HOURS.
LITHONIA 2VRTL OR EQUAL 4,388.60 38.70 120V CEIL. 2VRTL-XX-L48-5000LM-APFL-40K-XX-APFL-XX-40K-80CRI
VR1E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2VRTL OR EQUAL 4,388.60 38.70 120V CEIL. 2VRTL-XX-L48-5000LM-APFL-40K-XX-APFL-XX-40K-80CRI
VR2
SURFACE MOUNTED 2' X 4' LED VANDAL RESISTANT, DAMP LOCATION LEDTROFFER. 20-GAUGE COLD ROLLED STEEL DOOR FRAME,
TAMPER-RESISTANT FASTNERS AND POLYCARBONATE LENS. 18 GUAGESWING ARMS. UNPAINTED GALVANIZED STEEL. 4000 KELVIN, 80 CRI WITH 7000
DELIVERED LUMENS. LONG LIFE LED'S, HIGH-EFFICIENCY DRIVERS. LUMENMAINTENANCE OF L80/60,000 HOURS, L70 RATED LIFE OF 100,000 HOURS.
LITHONIA 2VRTL OR EQUAL 6,449.30 58.50 120V CEIL. 2VRTL-XX-L48-7000LM-APFL-40K-XX-APFL-XX-40K-80CRI
VR2E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2VRTL OR EQUAL 6,449.30 58.50 120V CEIL. 2VRTL-XX-L48-7000LM-APFL-40K-XX-APFL-XX-40K-80CRI
I1
SUSPENDED MOUNTED LED STRIP LIGHT WITH 20 GAUGE STEEL HOUSING,HIGH GLOSS BAKED WHITE ENAMEL FINISH, REPLACEABLE MEDIUM DIFFUSE
ACRYLIC LENS, HIGH OUTPUT LEDS ON TWO LAYER CIRCUIT BOARD,ELECTRONIC LED DRIVER. 5000 KELVIN, 90 CRI WITH 2000 DELIVERED
LUMENS, 80 CRI, 85% OUTPUT AT 44,000 HOURS, CSA LISTED FOR DAMPLOCATIONS.
LITHONIA ZL2N OR EQUAL 2,000.00 32.40 120V STRIP ZL2N L48 2000LM MDD MVOLT 40K 90CRI WH
I1E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA ZL2N OR EQUAL 2,000.00 32.40 120V STRIP ZL2N L48 2000LM MDD MVOLT 40K 90CRI WH
I2
SUSPENDED MOUNTED LED STRIP LIGHT WITH 20 GAUGE STEEL HOUSING,HIGH GLOSS BAKED WHITE ENAMEL FINISH, REPLACEABLE MEDIUM DIFFUSE
ACRYLIC LENS, HIGH OUTPUT LEDS ON TWO LAYER CIRCUIT BOARD,ELECTRONIC LED DRIVER. 5000 KELVIN, 90 CRI WITH 3000 DELIVERED
LUMENS, 80 CRI, 85% OUTPUT AT 44,000 HOURS, CSA LISTED FOR DAMPLOCATIONS.
LITHONIA ZL2N OR EQUAL 2,894.80 33.20 120V STRIP ZL2N L48 3000LM MDD MVOLT 40K 90CRI WH
X1
CEILING MOUNTED, TWIN HEAD, INTERIOR EGREESS LIGHT. CONSTRUCTEDOF UV-STABILIZED THERMOPLASTIC WHICH IS CORROSION-RESISTANT WITHA UL94V-0 FLAME RATING. 12 SERIES PARALLEL WHITE LED'S PER HEAD WITH
A 10 YEAR LED LAMP LIFE.
LITHONIA ECR LED M6 OR EQUALOSHA LUMENSTANDARD
1.50 277V CEIL. ECR-LED-HO-M6-78423184561
X2
CEILING MOUNTED VANDAL RESISTANT EXIST SIGN. CONTRUCTED OF CASTALUMINUM - RUGGED, LOW-PROFILE HOUSING IS .250" TO .525" THICK.
CONTAINS UC-STABLE POLY CARBONATE COVER THAT IS .130" THICK. COVERIS SECURED WITH FOUR STAINLESS STEEL, TORX T20 TAMPERPROOF SCREW
WITH CENTER PIN. 10 YEAR LED LAMP LIFE.
LITHONIA LV OR EQUALOSHA LUMENSTANDARD
2.30 277V CEIL. LV-S-W-1-R-120/277
U1THIN PROFILE BACKLIT LED SIGN. IT MEASURES 11mm THICK AND REQUIRESNO ADDITIONAL POWER SUPPLY OR TRANSFORMER AND FITS TO EXISTING
MAINS POWER SINGLE OR TWIN SOCKET BACKBOXES.LASERMET SLIM JIM OR EQUAL
OSHA LUMENSTANDARD
4.60 277V WALL LEDS-SJ-R-RIU
NOTES:1. LAMP AND BALLAST COMBINATION TO HAVE FIVE YEAR WARRANTY FROM THE FIXTURE MANUFACTURER. FURNISH WITH WARRANTY CERTIFICATES.
2. FIXTURE TO BE CIRCUITED TO NEAREST UNSWITCHED EMERGENCY POWER CIRCUIT.* ALL FIXTURES SHALL BE PRE-LAMPED FROM THE
MANUFACTURER** POINT-BY-POINT CALCULATIONS FOR THE CLASSROOMS, MEDIA CENTER, CAFETERIA, GYMNASIUM AND SITE ARE REQUIRED. MANUFACTURERS WISHING TO BID THIS PROJECT MUST SUBMIT ORIGINAL FIXTURE BROCHURES, AND ELECTRONIC FILE (VISUAL OR AGI32) POINT-BY-POINT
CALCULATIONS, TEN (10) DAYS PRIOR TO BID FOR WRITTEN APPROVAL.
COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC
JOB NO.
DATE
DRAWN
CHECKED
REVISIONS
SHEET
LE
XIN
GT
ON
, K
Y
10/1
9/2
017 2
:39:2
0 P
M
E6.0
AKP
09/25/2017
1508/XACO16
WRS
PA
NE
L/F
IXT
UR
E S
CH
ED
UL
ES
BL
UE
GR
AS
S A
IRP
OR
TC
US
TO
MS
FA
CIL
ITY
RE
NO
VA
TIO
NS
1508/X
AC
O16
BLU
EG
RA
SS
AIR
PO
RT
CU
ST
OM
S F
AC
ILIT
Y R
EN
OV
AT
ION
S No. Description Date
CIRCUIT #15 TO BE A GFI BREAKER.
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
TOTAL ESTIMATED DEMAND CURRENT: 29 A
REC 8820 VA 100.00% 8820 VA TOTAL CONNECTED CURRENT: 29 A
LTNG 1512 VA 100.00% 1512 VA TOTAL ESTIMATED DEMAND: 10532 VA
EQUIP 200 VA 100.00% 200 VA TOTAL CONNECTED LOAD: 10532 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 37 A 28 A 24 A
TOTAL LOAD (kVA): 4.3 kVA 3.3 kVA 2.9 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
REC PROCESSING FLOOR BOX 12 12 3/4" 20 1 19 0.4 20
REC 109, DRINKING FOUNTAINS 12 12 3/4" 20 1 17 0.5 0.5 18 1 20 3/4" 12 12 LTNG 101, 103, 104, 105
GFI BREAKER 12 12 3/4" 20 1 15 0.5 1.0 16 1 20 3/4" 12 12 LTNG 106, 107, 108, 109, 110
REC CBP GEN OFFICE 101 12 12 3/4" 20 1 13 0.7 0.7 14 1 20 3/4" 12 12 REC 101, 111
REC LAN/TELCO 106 12 12 3/4" 20 1 11 0.7 0.4 12 1 20 3/4" 12 12 REC 103, 105
REC 107, 108 12 12 3/4" 20 1 9 0.9 0.5 10 1 20 3/4" 12 12 REC LAN/TELCO 106
REC PROCESSING 110 12 12 3/4" 20 1 7 0.7 0.5 8 1 20 3/4" 12 12 REC PROCESSING 110
REC PROCESSING FLOOR BOX 12 12 3/4" 20 1 5 0.4 0.4 6 1 20 3/4" 12 12 REC DED TV 101
REC CBP GEN OFFICE 101 12 12 3/4" 20 1 3 0.2 0.2 4 1 20 3/4" 12 12 REC DED MICROWAVE 101
REC PRE-PROCESSING 108 12 12 3/4" 20 1 1 1.1 0.2 2 1 20 3/4" 12 12 REC 101
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM:
VOLTAGE: 208Y/120V,3P,4W SPD: LOCATION: STORAGE 107
PANEL: PP2 MAINS TYPE: AIC RATING:
PANELBOARD AND WIRING SCHEDULE kAIC VALUE:
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
TOTAL ESTIMATED DEMAND CURRENT: 8 A
TOTAL CONNECTED CURRENT: 8 A
TOTAL ESTIMATED DEMAND: 3000 VA
EQUIP 3000 VA 100.00% 3000 VA TOTAL CONNECTED LOAD: 3000 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 13 A 9 A 4 A
TOTAL LOAD (kVA): 1.5 kVA 1.0 kVA 0.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 0.5 6
EQUIP EF-1 108 12 12 3/4" 20 1 3 0.5 0.5 42 15 3/4" 12 12 EQUIP CU-1
EQUIP EF-2 RM 109 12 12 3/4" 20 1 1 0.5 1.0 2 1 20 3/4" 12 12 EQUIP DISPOSAL 101
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM:
VOLTAGE: 208Y/120V,3P,4W SPD: LOCATION: STORAGE 107
PANEL: PP5 MAINS TYPE: AIC RATING:
PANELBOARD AND WIRING SCHEDULE kAIC VALUE: