blue grass airport customs facility · pdf fileblue grass airport customs facility renovation...

16
SPECIAL INSPECTIONS PER CHAPTER 17 OF THE KY. BUILDING CODE SEISMIC - STRUCTURAL STEEL HELICAL PILE FOUNDATION WIND - WIND RESISTING COMPONENTS 1705.8 1705.9 1705.10.1 1705.10.3 1705.11.1 1705.7 CAST IN PLACE DEEP FOUNDATIONS WIND - STRUCTURAL WOOD DRIVEN DEEP FOUNDATIONS SECTION 1704.2.5 1705.2 1705.3 1705.4 1705.5 1705.6 ITEM STEEL CONCRETE MASONRY WOOD SOILS FABRICATORS X X X X X X NONE NONE NONE NONE NONE REQUIRED? NO X YES REMARKS NONE NONE NONE SEISMIC- ARCHITECTURAL COMPONENTS- 1705.11.5 X SEISMIC DESIGN CATEGORY "C" SEISMIC- MECHANICAL AND ELECTRICAL COMPONENTS 1705.11.6 X SEISMIC DESIGN CATEGORY "C" SEISMIC- STRUCTURAL WOOD 1705.11.2 X NONE SEISMIC- COLD FORMED STEEL FRAMING 1705.11.3 X NONE NONE N/A 1705.10.2 WIND - COLD FORMED STEEL FRAMING X NONE NONE INTERIOR/EXTERIOR NON-LOAD BEARING WALLS AND VENEER IN STRUCTURES NONE IN ADDITION TO OTHER TESTS AND INSPECTIONS REQUIRED TO BE PROVIDED BY THE CONTRACTOR IN THE SPECIFICATIONS, THE OWNER SHALL PROVIDE THE SERVICES OF QUALIFIED THIRD-PARTY INSPECTORS TO PERFORM ALL REQUIRED SPECIAL INSPECTIONS AS FOLLOWS: (INTERIOR RENOVATION; NONE REQUIRED) DESIGNATED SEISMIC SYSTEMS 1705.11.4 X NONE 1704.5.1 STRUCTURAL OBSERVATION FOR SEISMIC REQUIREMENTS X SEISMIC DESIGN CATEGORY "C" 1704.5.2 STRUCTURAL OBSERVATION FOR WIND REQUIREMENTS X Vasd = 89 MPH SEISMIC- STORAGE RACKS AND ACCESS FLOORS 1705.11.7 X ALL LESS THAN 8'-0" IN HEIGHT SPRAYED FIREPROOFING 1705.13 X NONE FIREPROOFING 1705.14 X NONE EIFS 1705.15 NONE FIRE RESISTANT PENETRATIONS & JOINTS 1705.16 X NONE SMOKE CONTROL 1705.17 X NONE X X X X X X BLUEGRASS AIRPORT PROJECT JOBSITE 60 MAN O WAR BLVD 60 MAN O WAR BLVD VERSAILLES RD V E R SAI LLE S R D DRAWING INDEX VICINITY MAP BLUEGRASS AIRPORT CUSTOMS FACILITY RENOVATION - SCB PROJECT NO. 1508 SHERMAN CARTER BARNHART ARCHITECTS, PLLC 2405 HARRODSBURG ROAD LEXINGTON, KY 40504-3329 PHONE: 859.224.1351 FAX: 859.224.8446 www.scbarchitects.com 10/18/2017 2:46:14 PM 1508 BLUE GRASS AIRPORT CUSTOMS FACILITY RENOVATION BLUE GRASS AIRPORT BLUE GRASS AIRPORT CUSTOMS FACILITY RENOVATION MECHANICAL/ELECTRICAL ENGINEER CMTA 2429 MEMBERS WAY LEXINGTON, KY 40504 P (859) 253-0892 F (859) 231-8157 N0.1 ABBREVIATIONS, SYMBOL LEGEND, GENERAL NOTES, PARTITION TYPES AND CODE INFORMATION A1.1 DEMOLITION AND NEW WORK FLOOR PLANS A1.2 DOOR SCHEDULE, DOOR AND FRAME ELEVATIONS, CEILING PLAN AND DETAILS A1.3 SIGNAGE SCHEDULE AND ELEVATIONS AND CASEWORK DETAILS ARCHITECTURAL PLUMBING P1.0 PLUMBING LEGEND P2.0 PLUMBING - FIRST FLOOR MECHANICAL M1.0 MECHANICAL LEGEND M2.0 DEMOLITION - FIRST FLOOR AIR DISTRIBUTION M3.0 AIR DISTRIBUTION - FIRST FLOOR ELECTRICAL E1.0 ELECTRICAL LEGEND E2.0 DEMOLITION - FIRST FLOOR ELECTRICAL E3.0 LIGHTING - FIRST FLOOR E4.0 POWER - FIRST FLOOR E5.0 SYSTEMS - FIRST FLOOR E6.0 PANEL/FIXTURE SCHEDULES FOR OCTOBER 20, 2017 4000 TERMINAL DRIVE LEXINGTON, KENTUCKY CONSTRUCTION DOCUMENTS LEXINGTON, KENTUCKY

Upload: dinhnguyet

Post on 30-Mar-2018

219 views

Category:

Documents


3 download

TRANSCRIPT

SPECIAL INSPECTIONS PER CHAPTER 17OF THE KY. BUILDING CODE

SEISMIC - STRUCTURAL STEEL

HELICAL PILE FOUNDATION

WIND - WIND RESISTING COMPONENTS

1705.8

1705.9

1705.10.1

1705.10.3

1705.11.1

1705.7

CAST IN PLACE DEEP FOUNDATIONS

WIND - STRUCTURAL WOOD

DRIVEN DEEP FOUNDATIONS

SECTION

1704.2.5

1705.2

1705.3

1705.4

1705.5

1705.6

ITEM

STEEL

CONCRETE

MASONRY

WOOD

SOILS

FABRICATORS

X

X

X

X

X

X

NONE

NONE

NONE

NONE

NONE

REQUIRED?

NO

X

YES

REMARKS

NONE

NONE

NONE

SEISMIC- ARCHITECTURAL COMPONENTS-1705.11.5 X SEISMIC DESIGN CATEGORY "C"

SEISMIC- MECHANICAL AND ELECTRICAL COMPONENTS1705.11.6 X SEISMIC DESIGN CATEGORY "C"

SEISMIC- STRUCTURAL WOOD1705.11.2 X NONE

SEISMIC- COLD FORMED STEEL FRAMING1705.11.3 X NONE

NONE

N/A

1705.10.2 WIND - COLD FORMED STEEL FRAMING X NONE

NONE

INTERIOR/EXTERIOR NON-LOAD BEARING WALLS

AND VENEER IN STRUCTURES

NONE

IN ADDITION TO OTHER TESTS AND INSPECTIONS REQUIRED TO BE PROVIDED BY THE CONTRACTOR IN THE SPECIFICATIONS,THE OWNER SHALL PROVIDE THE SERVICES OF QUALIFIED THIRD-PARTY INSPECTORS TO PERFORM ALL REQUIRED SPECIALINSPECTIONS AS FOLLOWS: (INTERIOR RENOVATION; NONE REQUIRED)

DESIGNATED SEISMIC SYSTEMS1705.11.4 X NONE

1704.5.1 STRUCTURAL OBSERVATION FOR SEISMIC REQUIREMENTS X SEISMIC DESIGN CATEGORY "C"

1704.5.2 STRUCTURAL OBSERVATION FOR WIND REQUIREMENTS X Vasd = 89 MPH

SEISMIC- STORAGE RACKS AND ACCESS FLOORS1705.11.7 X ALL LESS THAN 8'-0" IN HEIGHT

SPRAYED FIREPROOFING1705.13 X NONE

FIREPROOFING1705.14 X NONE

EIFS1705.15 NONE

FIRE RESISTANT PENETRATIONS & JOINTS1705.16 X NONE

SMOKE CONTROL1705.17 X NONE

X

X

X

X

X

X

BLUEGRASSAIRPORT

PROJECTJOBSITE

60

MA

N O

WA

R B

LVD

60

MAN O W

AR BLVD

VERSAILLES RD

VERSAILLES RD

DRAWING INDEX VICINITY MAP

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

- S

CB

PR

OJE

CT

NO

. 1508

SHERMAN CARTER BARNHARTARCHITECTS, PLLC

2405 HARRODSBURG ROADLEXINGTON, KY 40504-3329

PHONE: 859.224.1351FAX: 859.224.8446

www.scbarchitects.com

10/1

8/2

017 2

:46:1

4 P

M

1508

BLU

E G

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

BLUE GRASS AIRPORT

BLUE GRASS AIRPORT CUSTOMSFACILITY RENOVATION

MECHANICAL/ELECTRICAL ENGINEER

CMTA2429 MEMBERS WAYLEXINGTON, KY 40504P (859) 253-0892 F (859) 231-8157

N0.1 ABBREVIATIONS, SYMBOL LEGEND, GENERAL NOTES, PARTITION TYPES ANDCODE INFORMATION

A1.1 DEMOLITION AND NEW WORK FLOOR PLANS

A1.2 DOOR SCHEDULE, DOOR AND FRAME ELEVATIONS, CEILING PLAN AND DETAILS

A1.3 SIGNAGE SCHEDULE AND ELEVATIONS AND CASEWORK DETAILS

ARCHITECTURAL

PLUMBING

P1.0 PLUMBING LEGENDP2.0 PLUMBING - FIRST FLOOR

MECHANICAL

M1.0 MECHANICAL LEGENDM2.0 DEMOLITION - FIRST FLOOR AIR DISTRIBUTIONM3.0 AIR DISTRIBUTION - FIRST FLOOR

ELECTRICAL

E1.0 ELECTRICAL LEGENDE2.0 DEMOLITION - FIRST FLOOR ELECTRICALE3.0 LIGHTING - FIRST FLOORE4.0 POWER - FIRST FLOORE5.0 SYSTEMS - FIRST FLOORE6.0 PANEL/FIXTURE SCHEDULES

FOR

OCTOBER 20, 2017

4000 TERMINAL DRIVELEXINGTON, KENTUCKY

CONSTRUCTION DOCUMENTS

LEXINGTON, KENTUCKY

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

ABBREVIATIONS

ACT ACTUAL LOC LOCATION

SPEC(S). SPECIFICATIONS

KENTUCKY BUILDING CODE

YYD

HD WD HARDWOODTOS

HEIGHT

HOLLOW

HORSEPOWER

HORIZONTAL

HOLLOW METAL

HEXAGONAL

HEATER

INVERT

JOINT

JOIST

JUNCTION BOX

INTERIOR

INSULATION

INSIDE FACE

INSIDE DIAMETER

HOT WATER, HARD WHITE

INCLUDED

HEATING

HEX

HT.

HM OR H.M.

HORIZ.

HP

HOL

HTR

HW

IID

IF

INSUL.

INT

INV

JJB

INCL

JT

KBC

K

JST.

HTG

TS

U

TOW

TYP.

UG

UL

U.N.O.

UNFIN.

VVAC

VERT.

VB

VCT

V.I.F.

W

W

X

W.R.

X

GAUGE

GRADE

GROUND

HIGH

HARDWARE

HEADER

HANDICAPPED

HARD BOARD

HOLLOW CORE

GYPSUM

GLAZED STRUCTURAL TILE

GLUE-LAMINATED

GLASS, GLAZING

GROUND FAULT INTERRUPT

GALVANIZED IRON

GROUND FACE CONC. MAS. UNIT

GENERATOR

GRAB BAR

GALVANIZED

HOSE BIB

HARDENED

FIELD VERIFY

GA.

GALV.

GB

GI

GFI

GEN

GF CMU

GND

GR

GYP.

GST

GLUE LAM

GL

H

HARD

HB

HD BD

HC

HDR

HC

HDWE

H

G

F.V.SPM

STL.

STD

STA

S.S.

SYMM

SUSP.

STRUCT.

STOR.

TT

TB

TC

TCE

TDS

TEL

TFE

THK

T & G

T.O.

TOC

TOIL

THRESH

TOM

SQ.

YARD

TOP OF STEEL

TACK STRIP,

TYPICAL

TOP OF WALL

STRUCTURAL STEEL TUBING

UNFINISHED

VACUUM

VERTICAL

WIDE

BY

WATER RESISTANT

VERIFY IN FIELD

VINYL COMPOSITION TILE

VAPOR BARRIER

UNLESS NOTED OTHERWISE

UNDERWRITERS LABORATORY

UNDERGROUND

SINGLE-PLY MEMBRANE

STATION

STANDARD

STEEL

STORAGE

STRUCTURAL

SUSPENDED

TACKBOARD

TELEPHONE

TOP OF

TOILET

THRESHOLD

TOP OF CONCRETE

THICK, THICKNESS

TONGUE AND GROOVE

TOP OF FOOTING ELEVATION

TURNED DOWN SLAB

TOP OF CURB ELEVATION

TOP OF CURB

TREAD, THICK

STAINLESS STEEL

SYMMETRICAL

TOP OF MASONRY

SQUARE

POLY CARB

R. OR RAD.

ROW OR R/W

PERIMCSG CASING

ENT ENTRANCE

(SEE MECH DWGS)

EQUIVALENT

EQUAL

EASEMENT

EACH WAY

ELECTRIC WATER COOLER

EXISTING

FURRING

FOOTING

FIRE RETARDANT TREATED

FLEXIBLE

FLASHING

FLOOR

FINISH, FINISHED

FULL HEIGHT

FINISHED FLOOR ELEVATION

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

FOUNDATION

FLOOR DRAIN (SEE MECH DWGS)

FIRE CODE

FABRICATE

EXPANSION

EXTERIOR

EQ.

EW

EXIST. OR EX.

EWC

ESMT

EQUIV

FC

FD

F

EXT.

EXP.

FAB

FE

FIN.

FL.

FH

FDN.

FEC

F.F.E.

FLASH

FRT

FTG.

FURR.

FLEX

REF

REBAR

RECIRC

RD

REINF.

REQ'D.

RH

R.O.

RESIL

RET.

REF.

S

RRT

SEP

SCHD.

SECT

SC

SIM.

SHT.

SHEATH

SPA

S.M.

SF

CULVERT

CUBIC

COUNTERSINK

ENCLOSURE

EMERGENCY

ELECTRIC, ELECTRICAL

ELEVATION

EXPANSION JOINT

EACH

DRAWING(S)

DOWNSPOUT

DITTO

DOWN

DIMENSION

DIAMETER

DRINKING FOUNTAIN

DETAIL

DEPRESSED

DOUBLE

CUBIC YARD

COLD WATER, CLOCKWISE

CU

CTSK

CULV

CW

CY

DDBL.

DEP

DET.

DF

DIA.

DIM.

DN.

DO

DS

DWG.(S)

EEA.

EJ

EL. OR ELEV.

ELEC

EMER

ENCL

PH

PERP.

PF CMU

PLAS

POL

PLYWD.

PLUMB

PSMB

PR.

PROJ.

PVC

PWG

PVMT

P.T.

Q.T.

Q

+/-

PREFAB.

R.

RCP

R

C

INSTALLED

CONDENSATE

(SAME MEANING AS OC)

CONTRACTOR FURNISHED AND

COLD ROLLED

CORRUGATED

CONTRACTOR

CONTINUOUS

CONSTRUCTION

CONDITION, CONDENSER,

CONCRETE

COLUMN

CONCRETE MASONRY UNIT

CLEAR

CLOSET

CEILING

CONTROL JOINT

CAST IRON

CHANNEL

CUBIC FEET

CERAMIC TILE

CEMENT

CENTER TO CENTER

CATCH BASIN, CHALKBOARD

CABINET

CB

CAB.

C/C

CF

CFI

CI

CJ

C.T.

CHAN

CEM

CLOS

CLR.

CMU

COL

CONC.

COND

CONST.

CR

CONT.

CONTR

CORRUG

CLG.

PART

PART. BD.

PASS

P/C

PERF

PC

P

NIC

NET

NO. OR #

NTS

O.C.

O.D.

O.F.

O

OF-CI

OH

OPNG.

OPP.

OFI

NOM

BOTTOM OF

BOTTOM

BEAM

BLOCKING

BLOCK

BITUMINOUS

BEVELED

BETWEEN

BOARD

AUTOMATIC

ASSEMBLY

APPROXIMATE

ACCESS PANEL

ANCHOR

ALUMINUM

AIR HANDLING UNIT

AGGREGATE

ABOVE FINISH FLOOR

ADHESIVE

ADJUST, ADJUSTABLE

AMERICANS WITH DISABILITIES

BUILT UP ROOFING

ADA

ADJ.

ADH.

A.F.F.

AGG.

AHU

ALUM.

ANCH.

BBD.

APPROX.

ASSY

AUTO

BIT.

BM.

B.O.

BEV.

BLK.

BLKG.

BOT. OR BTM.

BTWN.

AP

ACT

BUR

LTWT

MAS.

MATL.

MAX.

M

MC

MDO

MECH.

MTL.

MFR.

MH

MED.

MB

MISC.

M.O.

MTD.

MTG.

MULL.

MT.

ML & P

NNA

MIN.

LT

PERIMETER

RECIRCULATE

ROOF DRAIN

REINFORCING

REQUIRED

RESILIENT

SECTION

SCHEDULE

SOLID CORE

SHEATHING

SHEET

SIMILAR

SPACE(S)

SHEET METAL

SEPARATE, SEPARATION

RIGHT OF WAY

ROUGH OPENING

RIGHT HAND, ROUND HEAD

RETAINING, RETURN

REINFORCE, REINFORCED,

REFRIGERATOR

REFERENCE, REFER

REINFORCING BAR

SQUARE FEET, SAND FILL

RAISED RADIAL TILE

PLASTER

PHASE

POLISHED

PLYWOOD

PLUMBING

PAIR

PAVEMENT

QUARRY TILE

PENCIL SHARPENER BLOCK

PLUS OR MINUS

POLISHED WIRE GLASS

POLYVINYL CHLORIDE

PRESSURE TREATED

PROJECT, PROJECTED

PREFABRICATED

POLYCARBONATE SHEET

PREFACED CONC. MAS. UNIT

PERPENDICULAR

RADIUS

REINFORCED CONCRETE PIPE

RISER, RADIUS

PASSAGE

PARTITION

PERFORATED

PRECAST

POURED CONCRETE

PARTICLE BOARD

REQUIRED

NUMBER

NOT IN CONTRACT

MEANS EXACT DIMENSION

INSTALLED

CONTRACTOR INSTALLED

OPPOSITE

OPENING

OVERHEAD

OWNER FURNISHED,

OWNER FURNISHED AND

OUTSIDE FACE

OUTSIDE DIAMETER

ON CENTER

NOT TO SCALE

NOMINAL

METAL

MULLION

MOUNT

LIGHT

MARKER BOARD

NOT APPLICABLE

MOUNTING

MOUNTED

MASONRY OPENING

METAL LATH AND PLASTER

MISCELLANEOUS

MINIMUM, MINUTE

MANHOLE

MANUFACTURER

MEDIUM, MEDICINE

MECHANICAL

MEDIUM DENSITY OVERLAY

MISCELLANEOUS CHANNEL

MAXIMUM

MATERIAL

MASONRY

LIGHTWEIGHT

ACOUSTICAL

AIR CONDITIONING

ANCHOR BOLT

AT

&

@

AB

A/C

ACOUS

AND

A LL

LAM.

LH

LLV

LF

LONG LEG VERTICAL

LEFT HAND

LIGHT FIXTURE, LINEAR FEET

LAMINATE

ANGLE, LONG

BEARINGBRG. OR BRNG.

O.H. OPPOSITE HAND

WWF WELDED WIRE FABRIC

1. DEMOLITION REFERENCE NOTES FOR THIS PROJECT ARE INTENDED TO GENERALLY IDENTIFY THE SELECTIVE REMOVALOF EXISTING ITEMS AT LOCATIONS WHERE REQUIRED BUT, SHALL IN NO WAY RELIEVE THE CONTRACTOR OF THE FULLRESPONSIBILITY FOR EXAMINING AND VERIFYING THE FULL EXTENT OF EXISTING CONDITIONSPRIOR TO BIDDING THE PROJECT.

2. THE INTENT OF THE DEMOLITION NOTES IS TO PROVIDE A GENERAL OUTLINE FOR THE CONTRACTOR OF ITEMS TO BEREMOVED AND TO ALLOW FOR THE NEW CONSTRUCTION AS OUTLINED ELSEWHERE IN THE CONTRACT DOCUMENTS.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION AND REMOVAL OF ITEMS TO ALLOW FOR NEWCONSTRUCTION SHOWN OR NOT SHOWN ON DEMOLITION PLANS AS MAY BE REQUIRED.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PATCHING AND REPAIRING DUE TO DEMOLITION AND/OR REMOVAL OFEQUIPMENT TO CREATE A FLUSH, SMOOTH SURFACE PROPERLY PREPARED TO RECEIVE NEW FINISHES AS INDICATED.

4. WALLS AND SPACES BEHIND EXTERIOR FINISHES OR PARTIALLY REMOVED WALLS/ROOFS, ETC. SHALL BEPROTECTED FROM EXPOSURE TO WEATHER BY THE CONTRACTOR. WALLS/ROOFS, ETC. SHALL BE PROTECTED.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGED WALLS, ROOFS, EQUIPMENT, ETC. CAUSED BY THISDEMOLITION OR WEATHER EXPOSURE OF ITEMS THAT ARE TO REMAIN.

5. THE OWNER SHALL REMOVE AND ABATE ANY HAZARDOUS MATERIALS ENCOUNTERED. CONTRACTOR TO COORDINATEREMOVAL WITH OWNER.

6. REFER TO MECHANICAL AND/OR ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS PERTAINING TOTHE REMOVAL, RELOCATION AND/OR MODIFICATION OF ITEMS RELATED TO EXISTING MECHANICAL AND ELECTRICAL SYSTEMS.

7. SHOULD THE CONTRACTOR ENCOUNTER ANY MATERIALS DURING SELECTIVE DEMOLITION AND NEW WORK WHICH ARESUSPECTED BY THE CONTRACTOR TO BE OF AN UNKNOWN OR QUESTIONABLE COMPOSITION WITH RESPECT TOCONTAINING CONTAMINANTS WHICH MAY BE HAZARDOUS TO HUMAN HEALTH, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE OWNER OF SUCH FINDINGS.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER DISPOSAL OF ALL DEMOLISHED MATERIALS. ALL REMOVEDMATERIALS SHALL BE LEGALLY DISPOSED OF, UNLESS NOTED AS SALVAGED OR "RETURNED TO OWNER".

9. INFORMATION AND DRAWINGS INCLUDED IN THESE CONTRACT DOCUMENTS PERTAINING TO EXISTING CONSTRUCTION HAVEBEEN OBTAINED FROM FIELD INVESTICATIONS. THIS INFORMATION IS INCLUDED HEREIN WITH THE INTENT TO PROVIDE THECONTRACTOR WITH A BASIC UNDERSTANDING OF EXISTING CONDITIONS. ACTUAL CONDITIONS AND DIMENSIONS MAY VARYFROM THOSE INDICATED AND REQUIRE FIELD VERIFICATION.

10. MULTIPLE AREAS IN THE EXISTING BUILDING WILL HAVE MPE WORK AND REQUIRE SELECTIVE DEMOLITION. COORDINATEDEMOLITION WITH M/E DOCUMENTS.

11. REFER TO MPE DRAWINGS FOR NEW WORK WHICH MAY REQUIRE DEMOLITION WORK IN ADDITION TO ITEMS NOTED ON THEARCHITECTURAL DRAWINGS ALL SUCH WORK SHALL BE PERFORMED BY THE CONTRACTOR.

12. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS, MEASURES, ETC. REQUIRED TO COLLECT/DIVERT RAIN WATERFROM BUILDING AND ROOF DURING DEMOLITION AND INSTALLATION OF NEW WORK.

13. GENERAL CONTRACTOR TO DEMOLISH ALL LIGHTS PER ELECTRICAL DRAWINGS. MERCURY LIGHTS AND PCB LADEN BALLASTARE TO BE DISPOSED OF PROPERLY INTO AN EPA APPROVED LANDFILL.

14. SELECTIVELY DEMOLISH EXISTING CONCRETE SLABS AS REQUIRED FOR INSTALLATION OF SYSTEMS ANDUTILITIES ETC. REFER TO ARCHITECTURAL AND MPE DRAWINGS.

GENERAL DEMOLITION NOTES

1. IN THE EXISTING BUILDING, IT IS POSSIBLE HAZARDOUS MATERIALS MAY EXIST, INCLUDING, BUT NOT LIMITED TO ASBESTOSPRODUCTS. POLYCHLORINATED BIPHENYL (PCB) AND OTHER TOXIC SUBSTANCES. IF ANY WORK PERSON ENCOUNTERS ANYMATERIAL WHICH THEY SUSPECT MIGHT BE HAZARDOUS OR TOXIC, THEY SHALL IMMEDIATELY ADVISE THE OWNER. THECONTRACTOR SHALL TAKE IMMEDIATE AND APPROPRIATE ACTION TO PROTECT THE BUILDING USERS AND WORKERS INACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS, CODES AND REGULATIONS. THE ARCHITECT AND ARCHITECT'SCONSULTANTS SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY, PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF OREXPOSURE OF PERSONS TO HAZARDOUS MATERIALS IN ANY FORM AT THE PROJECT SITE, INCLUDING BUT NOT LIMITED TOASBESTOS, ASBESTOS PRODUCTS, POLYCHLORINATED BIPHENYL (PCB) OR OTHER TOXIC SUBSTANCES.

2. THE CONTRACTOR IS HEREBY ADVISED THAT SHERMAN-CARTER-BARNHART, PLLC IS NOT A DESIGN PROFESSIONAL IN THEDETERMINATION OF THE PRESENCE OF HAZARDOUS MATERIALS, NOR IS SHERMAN-CARTER-BARNHART, PLLC A DESIGNPROFESSIONAL INVOLVED IN MAKING RECOMMENDATIONS REGARDING THE TESTING, REMOVAL, ENCAPSULATION OROTHER CORRECTIVE MEASURES PERTAINING TO HAZARDOUS MATERIALS.

3. IF THE WORK WHICH IS TO BE PERFORMED UNDER THE CONTRACT INTERFACES IN ANY WAY WITH THE EXISTINGCOMPONENTS WHICH CONTAIN HAZARDOUS MATERIALS, IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THEOWNER REGARDING THE PROPER MEANS AND METHODS TO BE UTILIZED IN DEALINGWITH HAZARDOUS MATERIALS.

4. BY EXECUTION OF THE CONTRACT FOR CONSTRUCTION, THE CONTRACTOR HEREBY AGREES TO BRING NO CLAIM FORNEGLIGENCE, BREACH OF CONTRACT, INDEMNITY OR OTHERWISE AGAINST THE ARCHITECT, HIS PRINCIPALS, EMPLOYEES,AGENTS OR CONSULTANTS IF SUCH A CLAIM IN ANY WAY WOULD INVOLVE THE INVESTIGATION OF OR REMEDIAL WORKRELATED TO HAZARDOUS MATERIALS IN THE PROJECT.

5. BY EXECUTION OF THE CONTRACT FOR CONSTRUCTION, THE CONTRACTOR FURTHER AGREES TO DEFEND, INDEMNIFYAND HOLD THE ARCHITECT, HIS PRINCIPALS, EMPLOYEES, AGENTS AND CONSULTANTS HARMLESS FROM ANY SUCHASBESTOS OR OTHER HAZARDOUS MATERIALS RELATED CLAIMS THAT MAY BE BROUGHT BY THE CONTRACTOR'SSUBCONTRACTORS, SUPPLIERS OR OTHER THIRD PARTIES WHO MAY BE ACTING UNDER THE DIRECTION OF THECONTRACTOR PURSUANT TO THIS PROJECT.

HAZARDOUS MATERIALS NOTES

G1 (NIC) MEANS NOT IN CONTRACT. TO BE PROVIDED BY OWNER AND INSTALLED BY OWNER.

G2 DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS.

G3 ALL DIMENSIONS SHOWN ARE TO FACE OF METAL STUDS OR CENTERLINE OF STRUCTURE.

G4 ALL CONCEALED WOOD FRAMING AND PLYWOOD SHALL BE FIRE-RETARDANT TREATED (FRT) EXCEPT THAT NON-F.R.T.BLOCKING, NAILERS AND FURRING MAY BE USED WHERE INSTALLED IN ACCORDANCE WITH KBC CHAPTER 8(INCLUDING DIMENSIONAL WOOD BLOCKING, FIRE BLOCKING, REQUIREMENTS, ETC.). WOOD BLOCKING INSTALLED INACCORDANCE WITH KBC SECTION 603, FOR HANDRAILS, MILLWORK, CABINETS, WINDOWS AND DOORS ISNOT REQUIRED TO BE F.R.T. AT COPINGS AND ROOFING TERMINATIONS ALL BLOCKING SHALL BE PRESSURE TREATED(PT). WHERE WOOD BLOCKING IS IN CONTACT WITH CONCRETE, SUCH BLOCKING SHALL BEPRESSURE TREATED.

G5 ALL CHANGES IN FLOOR FINISHES SHALL OCCUR AT DOOR THRESHOLDS - TYPICAL, U.N.O.

G6 ALL CONTRACTORS SHALL REVIEW DWGS FOR MATERIALS AND MANUFACTURER'S MODEL NUMBERS LISTED ON DWGS.

G7 CONTACT BETWEEN DISSIMILAR METALS SHALL BE SEPARATED WITH BUTYL TAPE, OR OTHER APPROVED MEANS TOPREVENT GALVANIC CORROSION.

G8 CONTRACTOR SHALL PROVIDE ALL CONCEALED BLOCKING REQUIRED FOR ATTACHMENT AND SUPPORT OF EQUIPMENT,FIXTURES, WINDOWS, ETC.

G9 GYPSUM CEILING BOARD SHALL BE USED AT ALL HORIZONTAL APPLICATIONS OF GYPSUM BOARD.

G10 ALL EXPOSED CORNERS AND EDGES OF GYPSUM BOARD SHALL BE FINISHED WITH CORNER BEAD OR J-BEAD,RESPECTIVELY.

G11 PARTITIONS TYPES ARE TO MAINTAIN THEIR RESPECTIVE SEPARATION/RATING (IF ANY) FULL HEIGHT. ALL HVAC,ELECTRICAL, PLUMBING PENETRATIONS ARE TO BE SEALED/ SAFED/ DAMPERED TO COMPLY WITH LOCAL CODES.

G12 CONTRACTOR SHALL VERIFY ALL ROUGH OPENING SIZES FOR WINDOWS AND DOORS AND COORDINATE ANY REQUIREDADJUSTMENTS WITH THE ARCHITECT.

G13 SYMBOLS THAT REPRESENT MPE ITEMS ON ARCHITECTURAL DRAWINGS ARE FOR GRAPHIC PURPOSES ONLY. REFER TOMPE DOCUMENTS FOR SPECIFIC INFORMATION. SYMBOLS THAT REPRESENT STRUCTURAL ITEMS ON ARCHITECTURALDRAWINGS ARE FOR GRAPHIC PURPOSES ONLY.

G14 ALL WOOD BLOCKING, NAILERS, SILL PLATES, ETC. IN CONTACT WITH SLABS-ON-GRADE OR CONCRETE SHALL BEPRESSURE-PRESERVATIVE TREATED (P.T.). REFER TO THE DRAWINGS FOR OTHER LOCATIONS WHERE P.T. WOOD ISREQUIRED.

G15 ALL P.T. WOOD COMPONENTS SHALL BE SEPARATED FROM CONTACT WITH ADJACENT METALS WITH PERMANENTLYAFFIXED NO. 15 FELT, SELF-ADHERING ELASTOMERIC MEMBRANE, OR OTHER SUCH PERMANENT NON-CORROSIVESEPARATION MATERIAL.

G16 ALL ANCHORS, FASTENERS, ETC. IN CONTACT WITH P.T. WOOD COMPONENTS SHALL BE STAINLESS STEEL OR G-90 (MIN.)HOT-DIPPED GALVANIZED.

GENERAL NOTES

P3CENTERLINE OF STRUCTURAL STEEL, UNLESS NOTED OTHERWISE.

P4UNLESS NOTED OTHERWISE. REFER TO ROOM FINISH GROUPS.

P5

P6

CONNECTION AND ATTACHMENT/ BRACING OF NON-LOAD BEARING

INTERIOR PARTITION WALL TO STRUCTURE/ DECK ABOVE.

P7WATER RESISTANT GYPSUM BOARD TO BE INSTALLED.

P8BRACED TO UNDERSIDE OF ROOF FRAMING AT 8'-0" O.C. MAX. U.N.O.

ALL DIMENSIONS ARE TO FACE OF STUDS OR TO

INTERIOR GYPSUM BOARD EXPOSED TO VIEW SHALL BE PAINTED

REFER TO ROOM FINISH GROUPS FOR BASE CONDITION.

REFER TO PARTITION DETAILS ON SHEET A1.2 FOR SPECIFIC

WHERE GYPSUM ASSEMBLIES ARE SPECIFIED AT WET WALL LOCATIONS,

METAL STUD FRAMED PARTITIONS, SOFFITS, ETC. TO BE LATERALLY

0'-0"

INDICATES HEIGHT A.F.F. OF SCHEDULED WALL

PARTITION TYPE, REFER TO SCHEDULE, THIS SHEET. ALL WALLS TO BE EXTENDEDFULL HEIGHT TO UNDERSIDE OF EXISTING ROOF INSULATION ABOVE, U.N.O. REFERTO TYPICAL DETAIL 11/A1.2.

P1

P2

FIBER REINFORCED GYPSUM BOARD TO A HEIGHT OF 8'-0" A.F.F.

WITH REGULAR 5/8" GYP. BD. ABOVE. FIBER REINFORCED GYPSUM BOARD MAYBE USED FULL HEIGHT AT CONTRACTOR'S OPTION.

ALL INTERIOR GYPSUM PARTITIONS SHALL HAVE 5/8"

PARTITION TYPEGENERAL NOTES

WALL PARTITION SCHEDULE

5/8" GYPSUM BOARD /3 5/8" METAL STUDS @ 16" O.C. /1 1/2" MINERAL WOOL BATTINSULATION /1/2" GYPSUM BOARD /1/2" GYPSUM BOARD /

1STC 50

5/8" GYPSUM BOARD /3 5/8" METAL STUDS @ 16" O.C. /3" MINERAL WOOL BATTINSULATION /5/8" GYPSUM BOARD /

2STC 45

2A SAME AS TYPE 2OMIT INSULATION

5/8" GYPSUM BOARD /1 1/2" FURRING CHANNELS @24" O.C. VERT. /

3 ADJACENT WALLSUBSTRATE

3A5/8" GYPSUM BOARD /9 GAUGE EXPANDED METALREINFORCING /INSTALL SUPPLEMENTAL3 5/8" METAL FRAMING ASREQUIRED TO ATTACH TOEXISTING METAL BUILDINGGIRT SYSTEM. MIN. 24" O.C.

8" METAL STUDS @ 16" O.C. /8" MINERAL WOOL BATTINSULATION WITH CROSS TIESTO HOLD INSULATION /EXTERIOR METAL FINSH PANEL

43B5/8" GYPSUM BOARD /INSTALL SUPPLEMENTAL3 5/8" METAL FRAMING ASREQUIRED TO ATTACH TOEXISTING METAL BUILDINGGIRT SYSTEM. MIN. 24" O.C.

1A SAME AS TYPE 1 W/ 9 GAUGEEXPANDED METAL REINFORCINGBEHIND THE 5/8" GYPSUM BOARD

ROOM FINISH GROUPS

1 ANTI-STATIC RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENT COVE BASEGYPSUM BOARD CEILING (PAINT) ON SUSPENDED METALFRAMING WITH 9 GAUGE EXPANDED METAL REINFORCING

FLOOR:WALLS:BASE:CEILING:

2 RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENT COVE BASEGYPSUM BOARD CEILING (PAINT) ON SUSPENDED METALFRAMING (PROVIDE 9 GAUGE EXPANDED METALREINFORCING AT DETENTION CORRIDOR 103)

FLOOR:WALLS:BASE:CEILING:

3 RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENT COVE BASESUSPENDED ACOUSTIC TILE

FLOOR:WALLS:BASE:CEILING:

4 ANTI-STATIC RESILIENT TILEGYPSUM BOARD (PAINT)4” RESILIENTSUSPENDED ACOUSTICAL TILE

FLOOR:WALLS:BASE:CEILING:

5 EPOXY RESINGYPSUM BOARD (PAINT)4” EPOXY RESINGYPSUM BOARD CEILING (PAINT) ON SUSPENDEDMETAL FRAMING WITH 9 GAUGE METAL REINFORCING

FLOOR:WALLS:BASE:CEILING:

6 CARPET TILEGYPSUM BOARD (PAINT)4” RESILIENT BASESUSPENDED ACOUSTICAL TILE

FLOOR:WALLS:BASE:CEILING:

7 EPOXY RESINGYPSUM BOARD (PAINT)4” EPOXY RESINSUSPENDED ACOUSTICAL TILE

FLOOR:WALLS:BASE:CEILING:

8 CARPET TILEGYPSUM BOARD (PAINT)4" RESILIENT BASEGYPSUM BOARD CEILING (PAINT)ON SUSPENDED METAL FRAMING WITH 9 GAUGEEXPANDED METAL REINFORCING

FLOOR:WALLS:BASE:CEILING:

GENERAL NOTES:

1. WHERE MORE THAN ONE FINISH IS LISTED REFER TO PLANS, SECTIONS, AND DETAILS.2. REFER TO TYPICAL BASE DETAIL, THIS SHEET.3. REFER TO TYPICAL FLOOR TRANSITION / THRESHOLD DETAILS, SHEET A1.2.4. REFER TO REFLECTED CEILING PLAN, SHEETS A1.2 FOR CEILING INFORMATION.5. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION AT CEILINGS.

EPOXY RESIN FLOORAND INTEGRAL BASE

REFER TOPLANS

1/2"

4"

SCHLUTER SCHIENE AE 80 STRIP

TILE WHERE APPLICABLE

WALL BASE, REFER TOROOM FINISH GROUPS

(CL

OF

HA

ND

LE)

4'-0

" A

FF

SEMI-RECESSED FIREEXTINGUISHER CABINET(FEC) REFER TO SPECS

5

N0.1

(CL

OF

HA

ND

LE)

4'-0

" A

FF

2x WOOD BLOCKINGAS REQ'D

SEMI-RECESSEDFIRE EXTINGUISHERCABINET (FEC)

CONT SEALANT ATPERIMETER OF CABINET

STANDARDCABINETEXTERIOR TRIM

ALL WORK PERTAINING TOFIRE EXTINGUISHERS SHALLBE DONE IN ACCORDANCEWITH NFPA 10

* REFER TO FLOOR PLAN

GENERAL

CODE: KENTUCKY BUILDING CODE 2013 4TH EDITION

USE GROUP: UNSEPARATED MIXED USE - EXISTING S-1 (STORAGE) AND EXISTING B (OFFICE SUITE)

CONSTRUCTION TYPE: EXISTING 2B

FIRE PROTECTION: EXISTING UNSPRINKLERED

ALLOWABLE BUILDING HEIGHT AND AREA (EXISTING)

S-1 IS MOST RESTRICTIVE

ALLOWABLE AREA (TABLE 503): 17,500 GROSS SF

EXISTING AREA (S-1 STORAGE): 8,537 GROSS SF

EXPANDED AREA (B OFFICE SUITE): 2,266 GROSS SF

TOTAL EXISTING AREA: 10,803 GROSS SF

CALCULATED OCCUPANT LOAD: 2,266 GROSS SF / 100 SF PER OCC. (B OCCUPANCY) = 23 OCCUPANTS

ALLOWABLE HEIGHT: 2 STORIES - 55'-0"

EXISTING HEIGHT: 1 STORY - 19'-0"±

CODE INFORMATION

CODE KEY PLAN

EXISTING STORAGEBUILDING(S-1) 8,537 SFNO WORK

CA

NO

PY

CA

NO

PY

EXISTING OFFICESUITE (B) 1,143 SF

OFFICE SUITEEXPANSION (B) 1,123 SF

TOTA

L A

RE

A O

FIM

PA

CT

(B) 2

,266

SF

INSTALL CONSTRUCTIONFENCE

PROVIDE 6" THICK REDSTRIPED BOX WITH 6" ARIELLETTERING AS INDICATED

CBP SecurityArea

CBP SecurityArea

CB

P S

ecur

ityA

rea

CB

P S

ecurityA

rea

EXISTING CONCRETEAIRFIELD APRON

104' - 4"

108'

- 8"

43' - 5"

10'-0" ±

30'-1

" ±

EXISTING BUILDING

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

10/1

8/2

017 2

:46:2

6 P

M

N0.1

MM

10/20/2017

1508

JSS, BKL

AB

BR

EV

IAT

ION

S, S

YM

BO

LL

EG

EN

D, G

EN

ER

AL

NO

TE

S,

PA

RT

ITIO

N T

YP

ES

AN

D C

OD

EIN

FO

RM

AT

ION

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NLE

XIN

GT

ON

, K

EN

TU

CK

Y

1508

BLU

E G

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

3" = 1'-0"2

TYP. RESIN BASE DETAIL

1 1/2" = 1'-0"3

TYP. BASE DETAIL

3/4" = 1'-0"4

TYP. FEC ELEVATION

3/4" = 1'-0"5

FEC SECTION

1" = 20'-0"1

SITE PLAN TRUENORTH

PLANNORTH

No. Description Date

DN

DN

NEW WORK KEYNOTESX

SYMBOLS LEGEND

WALL TYPE(SHEET N0.1)

NEW WORK KEY NOTES(SHEET A1.1)

ROOM FINISH GROUPS(SHEET N0.1)

ROOM NUMBER

#

#

RFG101

Name

EXISTING WALL / CONSTRUCTIONTO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED -SEE SELECTIVE DEMOLITION NOTES

DEMOLITION KEY NOTE(SHEET A1.1)

#

NEW CONSTRUCTION

SIGN TYPE(SHEET A1.3)

CEILING KEY NOTE(SHEET A1.2)# #

RFG108A

PRE-PROCESSINGPASSENGER

WAITING

3

RFG110

PROCESSING

4

RFG101

CBP GENERALOFFICE

6

RFG105

INTERVIEW

8

RFG104

SEARCH

5

RFG112

EXISTING MENSTOILET

2

113

EXISTINGWOMENS TOILET

115

EXISTING JANITOR

114

EXIST.ELECTRICAL

RFG103

DETENTIONCORRIDOR

2

RFG101A

CLOSET

6

7

3 5/

8"20

'-10

1/8"

3 5/

8"

3 5/8" 11'-7" ± 3 5/8" 11'-6" 3 5/8" 7'-9 1/8" 3 5/8" 13'-2" 3 5/8" 8'-6" 3 5/8" 8'-5 3/8" 3 5/8"

10'-0

"

3 5/

8"

4'-1

0 3/

8"

3 5/

8"

15'-6

" ±

1A

3A

1A

4

1A

1A

1

3

4

3B

3B

3B

INFILL1A

1A

3A

INFILL

2

2

RFG107

STORAGE

2

RFG106

LAN/TELCO

12A

2A

3

3B

2A

4

INFILL

1A

7'-0

"3

5/8"

1'-4

5/8

"

TO FIN.1'-3"

RFG109

TOILET

7

3B 2A

EXIST.SAFE

2

3 3

9

5

6

2'-1

"3 3/4" 7'-9"

4'-6 3/4" 1'-10"

1'-3 5/8"

3 5/8" 10'-0" 2'-10" 3'-0" 10'-0"8

CHASE

COPIER

9

9

2A

4'-4 9/16"

3 5/8"

12'-4"

4'-8

"

INFILL

4

RFG111

EXIT VESTIBULE

3

2

2A

109

107 106

103

105 104

101

101A

110

111

108

2

2

1

11 3

/4"

1'-0

"3

5/8"

4"

10'-4"

10'-4" 3

10'-4"3B3B3B

10'-4"

10'-4"

10'-4"

4

9'-4"3A3A9'-4"

3A9'-4"

10'-4"

3A3B 10'-4"

10'-4"

10 10 10 10

3A3A9'-4"

3A

9 9

10'-4"

10

10

2'-0"

1'-3

"

9'-4"

9

2A 10'-4"

2'-3

3/8

"

30X34X24

B2522

FOR REF

OPEN BLW.

30X24X14

W2052

W30X24X14

W9330WALL

BASE

REF BLW.(N.I.C.)

FILLER FOR 25"OPENING FORUNDERCOUNTER REF.

4'-8 3/16" 5'-2"

2'-3 3/16" 2'-5"

1'-0" 3'-4"4'-6"

1'-0" 3'-4"

1'-8 1/2"

R.O.

4'-4" 1'-8 1/2"

4'-6

"3'

-4"

R.O

. - F

.V.

3'-4

"

R.O

. - F

.V.

3'-4

"

R.O

. - F

.V.

8'-0

"

R.O

. - F

.V.

8'-0

"

7'-0

"

3'-4" 1'-2"

8" 3'-4"

A

1'-7" TO FIN.

C

X

ABOVEDOOR F

HUNGFROMCEILINGABOVE

D

HUNG FROMCEILING ABOVE

E

L

G H

HUNGFROMCEILINGABOVE

O

I

WK

N

M

Q

P S T

R

11

109A

12

12

12

11

X

V

V

U

RFG108B

POST-PROCESSINGPASSENGER

WAITING

3

3B10'-4"

EQ

EQ

16

18

12

12

12

12

D

HUNG FROMCEILING ABOVE

12

16

3A9'-4"

9

20

20

20

20

1717

13

1717

EQ EQ

FEC

15

15

15

14

13

13

1

1

1

1717

17

2A

16

4

A1.1

3B 9'-4"

17

17

9'-4"

9'-4"

1 23

4

5

6

7

8

9

19

9'-4"

2'-0" 1'-7 1/4"

2'-1

5/8

"1'

-2"

3B

3B3B 3B3B

3B

3'-0"

10

DEMOLISH WALL TO MINIMUM 4"BELOW EXISTING SLAB. INFILLSLAB WITH NEW CONCRETE FLUSHWITH ADJACENT SLABS. PREPARETO RECEIVE NEW FLOOR FINISHES.

DEMOLISH EXISTING WALLFINISHES AS REQUIREDFOR INSTALLATION OFNEW FEC.

10'-4"

TYP.TYP.

9

TYP.

9

TYP.

17

21

A1.28

A1.29

@METAL

@BRICK

TYP. @INFILL

1

ABV. &BLW.

21

14

J

RETURN GYPSUMBOARD TO FRAME.

JKQ

23

ADA

2

2

1

2

2

4

4

1

2

2

2

2

4

4

5

3

7

5

4

3

8

1010

7

4

3

3

9

9

44

7

5

7

53

3

9

7

5

6

3 3

2

2

1

2

2

4

4

1

2

22

3

7'-2" R.O.

47

3

15

12

12

12 12

11

5

5

11

14141414

16

14

2

3

16 16 16 16 16

3

14

16

7

17

5

18

13

17

17

17

18

18

19

7

7

12

3

13

20

SELECTIVE DEMOLITIONKEYNOTES

GENERAL NEW WORKNOTES

1. REFER TO MECH./ELEC. DRAWINGS FOR SPECIFIC NOTES REGARDING MECH/ELECITEMS NOT SHOWN ON THIS SHEET.

2. REFER TO SHEET N0.1 FOR GENERAL NOTES AND PARTITION TYPES.

CASEWORK NOTES

TYPICAL WALL AND BASE CASEWORK MODELNUMBERS SHOWN ARE TMI SYSTEMSDESIGN CORP. (PHONE NO. 1-800-456-6716)AND REPRESENT THE LEVEL OF QUALITYREQUIRED AND SHALL BE USED AS THEBASIS FOR EQUAL PRODUCTS. HEIGHTINDICATED IS TO TOP OF COUNTERTOP.

MODEL #

## - ## - ##WIDTH DEPTH

HEIGHT

TMI LEGEND:

1. MOUNT ALL CASEWORK PER ADA GUIDELINES.

2. PROVIDE FINISHED END PANELS AT ALL EXPOSED LOCATIONS.

3. PROVIDE 4" BACK AND SIDE SPLASH AT ALL WALL LOCATIONS.

4. ALL CABINETS AND BASES SHALL HAVE LOCKS ON DOORS AND DRAWERS.

5. ALL BASE CABINETS AND DRAWER CABINETS SHALL HAVE COUNTER TOPS.

6. PROVIDE INFILL PANELS AS REQUIRED TO CONCEAL VOIDS AT ALL CABINETS.

7. MOUNT TOP OF WALL CABINETS AT 7'-0" A.F.F., UNLESS NOTED OTHERWISE.

8. PROVIDE CONT. WD. BLOCKING AT WALL LOCATIONS FOR MOUNTING OF CASEWORK.

9. PROVIDE WD. BLOCKING AS NEEDED TO SUPPORT COUNTER TOP. COORD. W/ UNDERCOUNTER EQUIPMENT.

10. PLUMBING PIPES TO RUN BELOW CASEWORK AS SHOWN ON MECH DWGS.

XXXXX

GENERAL DEMOLITIONNOTES

REFER TO N0.1 FOR HAZARDOUS MATERIALNOTES AND GENERAL DEMOLITION NOTES.

PROJECTIONS

ADA WATER CLOSETREQUIREMENTS.

(SEE FIGURES 604.7PER ICC/ANSI

A117.1-2009 FORFURTHER

INFORMATION)

5

1'-0" 3'-6"

MAX MIN

6

7

3'-4"℄

1'-6

"3'

-4"

CL

2'-1

0"

9"

MAX

1'-3

" M

IN

CL

CLCL

CL

CL

GENERAL TOILET ACCESSORY NOTES:

TOILET ACCESSORY SCHEDULE

SANITARY NAPKIN DISPOSAL

18"L S.S. GRAB BAR (VERTICAL)

42"L S.S. GRAB BAR

26" A.F.F. TO TOP

34" A.F.F. TO CENTER

39" A.F.F. TO BOTTOM

36"L S.S. GRAB BAR 34" A.F.F. TO CENTER

DOUBLE ROLL TOILET TISSUE HOLDER 19" A.F.F. TO CENTER

MTG. HT.ACCESSORY

WALL PLATE MIRROR (24" WIDE) 40" A.F.F. TO BOTTOM.

HEAVY DUTY COAT HOOK 48" A.F.F. TO CENTER

SOAP DISPENSER (WALL MOUNTED) 48" A.F.F. TO OPERATOR

MODEL

REFER TO SPEC (REFER TO 4/A1.2)

BOBRICK B-2116

BOBRICK B-2111

BOBRICK B-270

BOBRICK B-2840

1. PROVIDE SOLID WOOD BLOCKING AS REQUIRED FOR SUPPORT OF ALL ACCESSORIES REGARDLESS IF GENERAL CONTRACTOR OR OWNER PROVIDED.

2. UNLESS NOTED OTHERWISE, MODEL NUMBERS IN SPECIFICATIONS DENOTE TOILET ACCESSORY PRODUCTS OFFERED BYBOBRICK WASHROOM EQUIPMENT, INC. AND REPRESENT THE LEVEL OF QUALITY REQUIRED.

3. ALL ACCESSORIES (EXCEPT #7) SHALL BE LOCATED HORIZONTALLY AND MOUNTED TO SPECIFIC POINTS A.F.F. IN ACCORDANCE WITH ALL APPLICABLEREQUIREMENTS OF THE "AMERICANS WITH DISABILITIES ACT" (A.D.A.). ITEM #7 IS TO BE MOUNTED VERTICALLY (REFER TO 3/A1.1 FOR TYPICAL GRABBAR MOUNTING LAYOUT AT TOILETS).

4. REFER TO MECHANICAL, PLUMBING, ELECTRICAL DRAWINGS, AND SPECIFICATIONS FOR PLUMBING FIXTURES AND CONTROLS. ALL EXPOSED PIPING ATHANDICAPPED LAVATORIES MUST BE INSULATED AND COVERED WITH RIGID JACKET.

5. COORDINATE FINAL PLACEMENT OF ACCESSORIES WITH ADJACENT CONSTRUCTION OR OTHER ACCESSORIES TO CONFIRM MOUNTING HEIGHTS.

6. WHERE ADJACENT TO WALLS, CENTERLINES OF ALL TOILETS ARE 1'-6" FROM FINISH FACE OF ADJACENT WALLS.

7. GRAB BARS ARE TO BE DETENTION GRADE CONSTRUCTION WITH TAMPER PROOF FASTENERS. REFER TO DETENTION FURNITURE SPEC.

-

1

2

3

4

5

6

7

8

9 PAPER TOWEL DISPENSER/TRASH RECEPTACLE 48" A.F.F. TO SLOT GEORGIA-PACIFIC 59466/59491 (RECESSED)

REFER TO SPEC (REFER TO 4/A1.2)

REFER TO SPEC (REFER TO 4/A1.2)

BOBRICK B-290 2436

10 FOLDING CHANGING STATION (SURFACE MOUNTED) 34"TO TOP (WHEN FOLDED) AMERA PRODUCTS, INC MODEL 100-SS-SM

FOR WALL TYPE SEEFLOOR PLAN.

INTEGRAL COVED P. LAM.BACKSPLASH, SEALANTCONT. WHERE MEETSWALL (SIDE SPLASH, ENDS)

PLAS. LAM. ON 3/4"PLYWD W/ CHAMFEREDEDGES ON CON'T. 2x4WD. FRAMING FRONTAND BACK

KICKERS AND CLEATS -PLAS. LAM. ON 3/4"PLYWOOD (NOT ONCASEWORK)

NOTE: BRACKET SUPPORTS,SPACED AS REQ'D. TOSUPPORT COUNTER TOPWITHOUT SAG, 42" MAX. O.C.

CLEARANCEPER ANSI/ADASTANDARDS

BASE - REFER TO ROOMFINISH GROUPS

BACKSPLASH TO MATCHADJACENT CASEWORK INHEIGHT AND COLOR

1 1/

2"1

1/2"

1 1/

2"1'

-7 1

/2"

7"

-

GROMMET@ 36" O.C.

2 1/2" Ø CUTOUT ATALL INTERMEDIATESUPPORTS.

REFER TO PLANS

2'-7

"

2'-0" U.N.O.

4"

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

FIN

AL D

OC

UM

EN

TS

10/1

8/2

017 2

:46:1

9 P

M

A1.1

MM

10/20/2017

1508

JSS, BKL

DE

MO

LIT

ION

AN

D N

EW

WO

RK

FL

OO

R P

LA

NS

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NLE

XIN

GT

ON

, K

EN

TU

CK

Y

1508

BLU

E G

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

1 (4 POST) 18" DEEP BY 48" LONG HEAVY DUTY ADJUSTABLE METAL SHELVING UNITS.REFER TO SPECS.

2 INTERVIEW TABLE SECURED TO CONCRETE SLAB W/ DURESS BUTTON. REFER TO SPECS.

3 SLED BASE SIDE CHAIR SECURED TO CONCRETE SLAB. REFER TO SPECS.

4 PROCESSING PODIUM. REFER TO DETAILS ON SHEET A1.3.

5 STEEL BENCH SECURED TO CONCRETE SLAB. REFER TO SPECS.

6 EXAMINATION TABLE SECURED TO CONCRETE SLAB. REFER TO SPECS.

7 PUBLIC TRANSACTION WINDOW/TRAY. REFER TO SPECS.

8 VINYL COATED SHELF WITH INTEGRAL CLOTHES HANGER ROD @ 8'-0". REFER TO SPECS.

9 FURNITURE BY OWNER. (N.I.C.)

10 EXISTING STEEL COLUMN TO REMAIN. PREP FOR NEW WORK.

11 WINDOW TO RECEIVE HORIZONTAL MINI BLIND. REFER TO SPECS.

12 DOOR TO RECEIVE CARD READER. REFER TO HARDWARE SPECIFICATIONS AND MEPDRAWINGS.

13 LINE OF FLOORING TRANSITION.

14 WATER FOUNTAIN. REFER TO MEP DRAWINGS.

15 DASHED LINE INDICATES PAINTED 3/4" FIRE RATED PLYWOOD FULL HEIGHT TO BOTTOMOF CEILING OVER GYPSUM BOARD.

16 DURESS BUTTON. REFER TO MEP DOCUMENTS.

17 PROVIDE WALL CORNER GUARD. REFER TO SPECS.

18 BAGGAGE EXAMINATION TABLE. REFER TO SPECS.

19 PISTOL LOCKER. FINALIZE LOCATION IN FIELD WITH OWNER. REFER TO SPEC.

20 EXISTING DOOR TO REMAIN.

21 EYEWASH. REFER TO MEP DRAWINGS.

22 REINSTALL SALVAGED RESTROOM SIGN.

23 PROVIDE DOOR RELEASE CARD READERS FOR DOORS 108 AND 110. REFER TO MEP ANDHARDWARE SPECS.

TRUENORTH

PLANNORTH

1/4" = 1'-0"2

NEW WORK FLOOR PLAN

1/4" = 1'-0"1

DEMOLITION FLOOR PLAN

1 SALVAGE EXISTING OVERHEAD DOORS IN THEIR ENTIRITY INCLUDING TRACKS,MOTORS, CONTROLS, ETC. TURN OVER TO OWNER.

2 DEMOLISH EXISTING BOLLARD IN ITS ENTIRETY. PATCH INTERIOR/EXTERIOR SLABWITH MATCHING FINISH.

3 DEMOLISH EXISTING WALL FULL HEIGHT. U.N.O. PREPARE SUBSTRATE FOR NEWWORK.

4 DEMOLISH EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY, INCLUDINGELECTRIFIED HARDWARE. PREPARE FOR NEW WORK.

5 DEMOLISH EXISTING FLOOR AND BASE FINISHES IN THEIR ENTIRETY INCLUDINGADHESIVES. PREPARE SUBSTRATE FOR NEW WORK.

6 DEMOLISH 8'-0"± HIGH PLYWOOD AROUND PERIMETER OF ROOM.

7 DEMOLISH EXISTING SUSPENDED CEILING AND SOFFITS IN THEIR ENTIRETY.

8 DEMOLISH CABINETS AND SINK/REFRIGERATOR.

9 SALVAGE EXISTING OFFICE PARTITION AND DESK. TURN OVER TO OWNER.

10 SALVAGE EXISTING STAINLESS STEEL BENCH AND TABLE. TURN OVER TO OWNER.

11 EXISTING TOILET PARTITION TO REMAIN. REMOVE AND REINSTALL AS REQUIREDFOR INSTALLATION OF NEW WORK.

12 EXISTING PLUMBING FIXTURES TO REMAIN.

13 REMOVE AND REINSTALL WALL MOUNTED TOILET ACCESSORIES. RELOCATE ASREQUIRED FOR NEW CONSTRUCTION.

14 EXISTING COLUMN AND BASE PAD TO REMAIN.

15 RELOCATE EXISTING WATER FOUNTAIN TO ACCOMMODATE NEW WORK. REFER TOMEP.

16 DEMOLISH EXISTING GYPSUM BOARD FINISH FULL HEIGHT ON EXTERIOR / PARTYWALL. FRAMING TO REMAIN.

17 EXISTING DOOR AND FRAME TO REMAIN.

18 NO ARCHITECTURAL WORK REQUIRED.

19 DEMOLISH FLOOR TILE TO EXTENTS SHOWN.

20 SALVAGE EXISTING RESTROOM SIGNAGE FOR REINSTALL

1/2" = 1'-0"3

TYP. ADA GRAB BAR LAYOUT

1" = 1'-0"4

ADA COUNTER

No. Description Date

GENERAL NOTES:1. REFER TO TYPICAL HEAD AND JAMB DETAILS ON SHEETS A1.2 AND ALUM. FRAME

ELEVATIONS ON A1.2.

2. INSTALL 2x BLOCKING BETWEEN STUDS FOR WALL MOUNTED DOOR STOPS IN STUD PARTITIONS.

3. ALL HOLLOW METAL DOORS AND FRAMES SHALL BE PAINTED PER THE SPECIFICATIONS.

HOLLOW METAL FRAME NOTES:1. PROVIDE REINFORCING 12 GA. CHANNEL IN FRAME HEAD AT ALL

H.M. FRAMES WHERE TOTAL FRAME WIDTH IS GREATER THAN 4'-0".

2. PROVIDE 11 - GA x 2" WIDE STRAPS AT 8" O.C. IN H.M. FRAME HEADS GREATER THAN 2" IN HEIGHT, TYPICAL.

3. LINTEL BEAM LENGTH SHALL BE M.O. PLUS 16" LONG (MIN 8" BEARING AT EACH END UNLESS NOTEDOTHERWISE). LINTEL PLATE LENGTH SHALL BE M.O. LESS 1/4" LONG (1/8" AT EACH END MAX.). REFER TOSTRUCTURAL DRAWINGS FOR LINTEL INFORMATION.

4. WHERE GLAZING IS SHOWN, THE FRAME FABRICATOR SHALL PRE-DRILL STOPS AND FRAME TO RECEIVEMOUNTING SCREWS. VERIFY LOCATIONS AND DEPTH OF GLAZING MATERIAL,EQUAL SPACE SCREWS.

5. UNLESS NOTED OTHERWISE, THE HINGE SIDE OF H.M. FRAME AT GYP. AND MTL. STUD WALLS SHALL BE INSTALLED 4" FROM ADJ. WALLS.

6. ALL EXTERIOR HOLLOW METAL FRAMES SHALL BE GALVANIZED, 14 GA.

7. CUT HOLE IN FRAME IN EXISTING OPENING TO GROUT FRAME SOLID. WELD IN NEW FILLERPLATE FLUSH. GRIND SMOOTH AND PREP FOR PAINTING.

DOOR AND FRAME NOTES:

DOOR NOTES:1. UNDERCUT AT NON-RATED S.C. WOOD DOORS 1/2" FROM BOTTOM OF DOOR TO SCHEDULED FLOOR FINISH.

2. UNDERCUT AT EXTERIOR DOORS 1/8" MAX. FROM BOTTOM OF DOOR TO TOP OFTHRESHOLD, WEATHER STRIP MUST CLOSE TIGHTLY AGAINST THRESHOLD.

3. ALL EXTERIOR HOLLOW METAL DOORS BE GALVANIZED AND HAVE FLUSH CLOSURECAPS16 GA. WELD CONT. TOP AND BOTTOM.

4. PROVIDE THRESHOLDS AS REQUIRED AT DOORS. SEE THIS SHEET TYPICALTHRESHOLD DETAILS AND FLOOR FINISHES.

GLASS AND GLAZING NOTES:1. PROVIDE FULLY TEMPERED (FT) GLASS WHERE INDICATED ON SCHEDULE AND/OR

SHOWN ON DOOR AND FRAME TYPES, OR AS REQ'D BY CODE.

2. ALL GLAZING AND GLAZING STOPS IN H.M. FRAMES ARE TO BE INSTALLED AT SECURESIDE OF INTERIOR FRAMES AND INTERIOR SIDE OF ALL EXTERIOR FRAMES.

HARDWARE NOTES:1. PROVIDE AND INSTALL ALL HARDWARE IN ACCORDANCE WITH ANSI A117.1 - 2009.

REMARKS:1. CARD READER. REFER TO HARDWARE SPECIFICATIONS AND MEP DRAWINGS.

2. PROVIDE TINTED GLASS IN DOOR AND FRAME.

3. PROVIDE LAMINATED GLASS IN DOOR FRAME.

4. FIELD VERIFY EXISTING OPENING SIZE. FABRICATE DOOR AND FRAME TO FIT.

5. DELAYED EGRESS HARDWARE. REFER TO SPECIFICATIONS.

6. PROVIDE DOOR RELEASE CARD READER AT BAGGAGE PODIUM. COORDINATE WITH MEP ANDDOOR HARDWARE.

3

9'-0"

3

9'-0"

3

9'-0"

3

9'-0"

2

9'-0"

1

10'-0"

1

9'-0"

1

10'-0"

1

9'-0"

5

8

5 5

5

5

4

8'-8"

F.V.

2'-6"

MODIFY EXISTINGSUSPEDED CEILINGFOR NEW WORK

7

6

6

6

1

9'-0"

6

12

A1.2

REFLECTED CEILINGPLAN KEY NOTES

GENERAL CEILING NOTES

2' x 2' SUSPENDED ACOUSTICAL CEILING.NO ACOUSTICAL TILE SLIVERS LESS THAN 6".

INTERIOR SUSPENDED GYP. BD.SOFFITS OR CEILINGS, PAINT U.N.O.REFER TO REFERENCED DETAILS.

1. = KEYNOTES

2. SEE M/E/P DRAWINGS FOR LIGHTING FIXTURE TYPE, SIZE, AND OTHER REQUIREMENTS.

3. REFER TO FLOOR PLANS AND PARTITION NOTES FOR LOCATIONS OF FULL HEIGHTWALLS.

4. GYPSUM CEILING BOARD SHALL BE USED AT ALL GYPSUM APPLICATIONS.

REFLECTED CEILING LEGEND

#

#

1. SUSPENDED ACOUSTICAL 2'X2' CEILING TILE.

2. SUSPENDED GYP. BOARD CEILING (PAINT) ON SUSPENSION SYSTEM. PROVIDE SEALANTSOFT JOINT AT PERIMETER OF ROOM.

3. SUSPENDED GYP. BOARD CEILING (PAINT) ON SUSPENSION SYSTEM WITH 9 GAUGE METALREINFORCING. PROVIDE SEALANT SOFT JOINT AT PERIMETER OF ROOM.

4. GYP. BOARD SOFFIT, REFER TO SOFFIT DETAILS. (PAINT)

5. NO WORK. EXISTING TO REMAIN. U.N.O.

6. CEILING MOUNTED SIGN. REFER TO SIGNAGE INFORMATION

7. NO ARCHITECTURAL WORK REQUIRED.

8. PAINT EXISTING GYPSUM CEILING BOARD TO REMAIN.

GLASS (AS SCHEDULED)

GLASS STOP, REFER TO SCHED.FOR GLAZING LOCATIONS

PAINTED H.M. DRYWALLFRAME, PROVIDE ADJUSTABLECOMPRESSION ANCHOR ATEACH JAMB

CONT. SEALANT AROUNDFRAME, TYP. AT BOTH SIDES

PROVIDE DOUBLE STUDSAT EACH JAMB (TYP.)

REFER TO PLANS

2"

*

1/2"

1/2"

5 7/

8" T

YP

.6

1/4"

FO

R W

ALL

TY

PE

"1"

U.N.O.

4" MIN.

ADJACENT WALL WHEREAPPLICABLE

H.M. FRAME (PAINT)

SEALANT CONT. AROUND FRAME,TYP. AT BOTH SIDES

GLASS, REFER TO FRAMEELEVATIONS

GLASS STOP CONT. ONSECURE SIDE OF FRAME

REFER TO ROOM FINISH GROUPSFOR BASE AND FLOOR FINISH

10"

TYPE "1"

5 7/8" TYP.6 1/4" WALL

EXIST. CONC.FLOOR SLAB

GLASS (AS SCHEDULED)

GLASS STOP, REFER TO SCHED.FOR GLAZING LOCATIONS

H.M. DRYWALL FRAME (PAINT)

CONT. SEALANT AROUNDFRAME, TYP. AT BOTH SIDES

PROVIDE 6" STUD BOXBEAM AT HEAD, TYP.

REFER TOPLANS

2"

*

1/2"1/2"

5 7/8" TYP.6 1/4" FOR WALL TYPE "1"

3"

FIE

LD V

ER

IFY

1'-0

5/8

"

BACKER ROD AND SEALANT,CONT. (BOTH SIDES)

ALUM. STOREFRONT SYSTEM. REFERTO ALUM. FRAME ELEVATIONS ANDPLANS (PROVIDE SHIMS AS REQ'D.)

'LC' TRIM AND SEALANT, CONT. METAL CORNER BEAD, CONT.

NEW PRE-FIN. S.M. PERIMETERTRIM AROUND EXIST. OPENING.FASTEN TO EXIST. CONSTRUCTION

EXIST. CONST. TO REMAIN(SHOWN SHADED)

3B

EXIST. METAL PANEL SYSTEM

FILL SHIM VOIDS WITH LOWEXPANSION SPRAY FOAM.PROVIDE RIGID INSULATIONINSERTS IN FRAME ATPERIMETER.

BACKER ROD AND SEALANT,CONT. (BOTH SIDES)

ALUM. STOREFRONT SYSTEM.REFER TO ALUM. FRAMEELEVATIONS AND PLANS(PROVIDE SHIMS AS REQ'D.)

'LC' TRIM AND SEALANT, CONT.

METAL CORNER BEAD, CONT.

NEW PRE-FIN. S.M. PERIMETERTRIM AROUND EXIST. OPENING.FASTEN TO EXIST. CONSTRUCTION

EXIST. CONST. TO REMAIN(SHOWN SHADED)

EXISTING THIN BRICK SYSTEM

PROVIDE SUPPLEMENTAL FRAMING TOSUPPORT SHEATHING AS REQUIRED

3B

FILL SHIM VOIDS WITH LOWEXPANSION SPRAY FOAM.PROVIDE RIGID INSULATIONINSERTS IN FRAME ATPERIMETER.

NEW PRE-FIN. S.M. ANCHOR TO NEW ANDEXIST. METAL STUDS AND METAL PANELS.PROVIDE BACKER ROD AND SEALANT AT JOINT EXIST. CONST. TO REMAIN

(SHOWN SHADED)

4 INFILL

3B3B

GYPSUM CONTROL JOINT

NEW PRE-FIN. S.M. TRIM BELOW.MATCH EXISTING IS SHAPE ANDCOLOR

EXIST. S.M. TRIM BELOW

EXIST. CONST. TO REMAIN(SHOWN SHADED)

SELF-ADHERED GRANULAR UNDERLAYMENTOVER 5/8" EXTERIOR GRADE GYPSUMSHEATHING. FIELD VERIFY TO MATCHEXISTING. PROVIDE SUPPLEMENTAL FRAMINGTO SUPPORT SHEATHING AS REQUIRED

NEW PRE-FIN. S.M. ANCHOR TO NEW ANDEXIST. METAL STUDS AND METAL PANELS.PROVIDE BACKER ROD AND SEALANT AT JOINT

THIN BRICK TO MATCH EXIST. FACE BRICK OVERLOXON METAL REINFORCED PANEL OR EQ.(EXTEND FASTENERS INTO METAL FRAMING)

4INFILL

3B3B

EXISTING THIN BRICK SYSTEM

GYPSUM CONTROL JOINT

RE

FER

TO

SC

HE

DU

LE

TYP

.

3'-4

"

SCHEDULE

REFER TO

PANICHARDWAREWHEREAPPLICABLE,TYP.

F

RE

FER

TO

SC

HE

DU

LE

SCHEDULE

REFER TO

5" 5"

7"

10"

2'-3

"6"

FG

LINE OF

FINISH FLOOR

LINE OF

FINISH FLOOR

2"

3'-0" ±2"

10"

1' -

10"

2"4'

- 2"

±2"

3'-4" ±

10"

1' -

10"

2"4'

- 2"

±2"

2' -

8"2"

8'-0" ±

2

2"

2'-5"

2"

2'-6" ±

2"

2'-5"

2"

1

7'-2

" ±

10'-0

" ±

6

A1.2

7

A1.2

MTL. PANELMATCH EXIST.

THIN BRICKMATCH EXIST.

5

A1.2

6

A1.2

7

A1.2

MTL. PANELMATCH EXIST.

THIN BRICKMATCH EXIST.

5

A1.2

10

A1.2

10

A1.2

2"

SCHEDULE

REFER TO 2"

RE

FER

TO

SC

HE

DU

LE2"

LINE OF

FINISH FLOOR1

2"

SCHEDULE

REFER TO

2"

1'-0"2"

10"

1' -

10"

2"4'

- 2"

2"

4'-6"

2"

SCHEDULE

REFER TO

2"

1'-8"2"1'-8"2"

10"

1' -

10"

2"4'

- 2"

2"

7'-0"

2 34

A1.2

4

A1.2

B.O

. CLN

GS

EE

CLN

G P

LAN

B.O

. SO

FFIT

SE

E C

LG P

LAN

B.O

. CLN

GS

EE

CLN

G P

LAN

MTL. CORNER BEAD.TYP. BOTH SIDES

5/8" GYP. CLG. BD. (PAINT)ON 3 5/8" MTL. STUDS @16" O.C. CONT. ANCHOR TOSTRUCT. ABOVE

SUSP. ACOUST. CLG.

SUSP. ACOUST. CLG.

REFER TO CLG. PLAN

TYP

.

6"

LINE OF EXISTING ROOFINSULATION

BRACE PARTITIONS BACKTO ROOF STRUCTURE AT8' O.C. MIN.

EXISTING ROOF STRUCT

6" MTL. STUDS MIN. @ 16"O.C. CONT. ANCHOR TOEXIST. ROOF STRUCT.PROVIDE SIZE AND GUAGEAS REQUIRED TO SUPPORTSOFFIT AND SPAN BETWEENROOF STRUCTURALMEMBERS.

AT ROOF BATT INSULATION, FILL VOIDS SOLIDW/ BATT INSUL. BACKER ROD AND SEALANTBOTH SIDES

GYP. BD. EACH FACE ONMTL. STUDS @ 16" O.C. NOFINISH REQ'D. ON GYP. BD.ABOVE FIN. CLG. SEAL ANDTAPE JOINTS

SOUND BATT INSUL.

HOLD PARTITION 1/2"BELOW EXISTING ROOFINSULATION

LINE OF EXISTING ROOFINSULATION

REFER TOPLANS

1/2"

BRACE PARTITIONS BACKTO ROOF STRUCTURE AT8' O.C. MIN.

EXISTING ROOF STRUCT

EL.: 112'-9"± MIN.

EL.: 113'-3"± MAX.

B.O. STRUCTURE

1/8"

MA

X

EQ.EQ.

EQ.EQ.

EQ.EQ.

TYP. TRANSITION/ THRESHOLDDETAIL CONDITIONS

TYPICAL EXTERIOR DOOR

1/2

"

SEALANT

MAX.1/2" HT.

SCHEDULED FLOOR

SCHEDULED DOOR

FINISH

21

43

CONCRETE

RESILIENT REDUCER STRIP

DOOR

DOOR

CARPET

GENERAL NOTES:

1. REFER TO ROOM FINISH GROUPS AND FLOOR PLANS FOR FINISHES. IT IS THE CONTRACTOR'S RESPONSIBILITY TO MAKE SURE THE PROPER THRESHOLD IS USED.

2. PROVIDE RESILIENT TRANSITION STRIPS OR REDUCERS BETWEEN ALL DIFFERING FLOOR FINISH MATERIALS IE CARPET TO TILE.

3. PROVIDE STRIP OR REDUCER PROFILE AS RECOMMENDED BY MANUFACTURER FOR APPLICATION.

RESILIENT TILE

METAL THRESHOLD INSTALL INCONT. BED OF SEALANT

RESILIENT TILE ORTERRAZO, REFER TO R.F.G.

ALUMINUM REDUCER STRIP

DOOR

EPOXY RESINRESILIENT TILE

RESILIENT TRANSITIONSTRIP CARPETREDUCER STRIP

3"

FIELD VERIFY

1'-0 5/8"

3B

BACKER ROD AND SEALANT,CONT. (BOTH SIDES)

NEW PRE-FIN. S.M.PERIMETER TRIM AROUNDEXIST. OPENING. FASTENTO EXIST. CONSTRUCTION

EXIST. CONST. TO REMAIN(SHOWN SHADED)

EXIST. METALPANEL SYSTEM

ALUM. STOREFRONT SYSTEM.REFER TO ALUM. FRAMEELEVATIONS AND PLANS(PROVIDE SHIMS AS REQ'D.)

'LC' TRIM AND SEALANT, CONT.

METAL CORNER BEAD, CONT.

NEW PRE-FIN. S.M. FLASHINGWITH DRIP EDGE. EXTENDUNDER FRAME HEAD

FILL SHIM VOIDS WITH LOWEXPANSION SPRAY FOAM.PROVIDE RIGID INSULATIONINSERTS IN FRAME AT PERIMETER.

FILL FRAME W/ RIGIDINSUL. INSERTS

EXISTING FLOOR SLAB

CONT. SEALANT AROUNDFRAME, TYP. AT BOTH SIDES

PRE-FIN ALUM. STOREFRONTSYSTEM, REFER TO ALUM. FRAMEELEVATIONS AND PLANS. PROVIDEWD. SHIM AS REQUIRED

FACE OF WALL BEYOND

PROVIDE PRE-FIN.EXTRUDED ALUM. FLUSHINFILL TO MATCH FRAME

FINISH FLOOR, REFER TOROOM FINISH GROUPSAND FLOOR PLANS

10"

3" 4 1/2"

PRE-FIN. ALUM. SUB SILL,SET IN BED OF SEALANT.FINISH TO MATCH FRAME (@EXTERIOR LOCATIONS)

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

FIN

AL D

OC

UM

EN

TS

10/1

8/2

017 2

:46:2

2 P

M

A1.2

MM

10/20/2017

1508

JSS, BKL

DO

OR

SC

HE

DU

LE

, D

OO

R A

ND

FR

AM

E E

LE

VA

TIO

NS

, C

EIL

ING

PL

AN

AN

D D

ET

AIL

S

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NLE

XIN

GT

ON

, K

EN

TU

CK

Y

1508

BLU

E G

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

DOOR SCHEDULE

NO.

DOOR FRAME

HE

AD

JA

MB

FIR

E R

AT

ING

CLO

SE

R D

EG

.

RemarksNO

. LE

AV

ES

LE

AF

WID

TH

HT

.

MA

TL.

TY

PE

GLA

ZIN

G

MA

TL.

TYPE GLA

ZIN

G

101 1 3'-0" 7'-0" SCWD FG 1/4" H.M. 2 1/4" 2/A1.2 3/A1.2 - 105° 1, 2

101A 1 3'-0" 7'-0" SCWD. F - H.M. 1 - 2/A1.2 3/A1.2 - -

103 1 3'-0" 7'-0" SCWD. F - H.M. 1 - 2/A1.2 3/A1.2 - 90° 1, 3

104 1 3'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - -

105 1 3'-0" 7'-0" SCWD F - H.M. 3 1/4" 2/A1.2 3/A1.2 - - 3

106 1 3'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - 90° 1

107 1 4'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - 105°

108 1 3'-0" 7'-0" H.M. FG 1" INSUL. H.M. 1 - 5/A1.2 SIM. 6&7/A1.2SIM.

- 105° 1, 4, 6

109 1 3'-0" 7'-0" SCWD F - H.M. 1 - 2/A1.2 3/A1.2 - -

109A 1 1'-0" 7'-0" H.M. F H.M. 1 - 2/A1.2 3/A1.2 - -

110 1 3'-0" 7'-0" H.M. FG 1/4" H.M. 1 - 2/A1.2 SIM. 3/A1.2 SIM. - 90° 1, 5, 6

111 1 3'-0" 7'-0" H.M. F - H.M. 1 - 2/A1.2 3/A1.2 - 105°

1/4" = 1'-0"1

NEW WORK CEILING PLAN

1 1/2" = 1'-0"3

TYPICAL H.M. JAMB @ MTL. STUD

1 1/2" = 1'-0"4

TYPICAL H.M. SILL DETAIL

1 1/2" = 1'-0"2

TYPICAL H.M. HEAD @ MTL. STUD

1 1/2" = 1'-0"6

ALUM. JAMB @ EXIST. EXT. OPENINGAT MTL. PANEL (H.M. SIM.)

1 1/2" = 1'-0"7

ALUM. JAMB @ EXIST. EXT.OPENING AT BRICK (H.M. SIM.)

1 1/2" = 1'-0"8

METAL PANEL INFILL @ EXIST.EXT. OPENING

1 1/2" = 1'-0"9

INFILL @ EXIST. EXT. OPENING

DOOR TYPES1/4" = 1'-0"

HOLLOW METAL FRAME TYPES1/4" = 1'-0"

ALUMINUM STORE FRONT FRAME TYPES1/4" = 1'-0"

DOOR DIMENSIONS: DIMENSIONS NOTED ARE MINIMUM SIZES TOFACILITATE AND/OR CONCEAL PROJECT SPECIFIC HARDWARE, MFR.STANDARD DIMENSIONS WHICH NOMINALLY EXCEED THE MINIMUMS AREACCEPTABLE SUBJECT TO ARCHITECT REVIEW.GLAZING NOTE: DIMENSIONS TO GLAZING EDGE NOTED ARE TO OUTMOSTEDGE AND DO NOT INCLUDE GLAZING TRIM.DENOTES TEMPERED GLASS

ALL EXTERIOR GLAZING SHALL BE 1" INSULATED U.N.O.DENOTES TEMPERED GLASS

ALL EXTERIOR GLAZING SHALL BE 1" INSULATED U.N.O.DENOTES TEMPERED GLASS

1 1/2" = 1'-0"12

TYP. SOFFIT DETAIL

1 1/2" = 1'-0"11

TYPICAL TOP OF WALL DETAIL

1 1/2" = 1'-0"5

ALUM. HEAD @ EXIST. EXT. OPENINGAT MTL. PANEL (H.M. SIM.)

1 1/2" = 1'-0"10

ALUM SILL DETAIL

No. Description Date

CBP FORMS COUNTER

ROOM NAMEFUNCTION/LOCATION

NOT USED

RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY (ON EXTERIOR OF DOOR 108)

PASSENGER WAITING AREA (ON WALL OR HUNG FROM CEILING)

1 FULL SET OF AIRPORT STATUTORY SIGNS (TOTAL 10 SIGNS) (ON EAST WALL OF ROOM 108A)

AT ENTRY TO WAITING - HUNG FROM CEILING : WELCOME SIGN

DHS SEAL FOR PROCESSING PODIUM

CBP PROCESSING AREA (HUNG ABOVE PODIUM WITH IMMIGRATION AND BAGGAGE AIGA ICONS)

1 FULL SET OF STATUTORY SIGNS (TOTAL 10 SIGNS) (ON NORTH WALL OF ROOM 110)

EXIT FROM PROCESSING - "THANK YOU FOR YOUR COOPERATION" (ON WALL AT DOORS 108 & 110)

RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY (ON EXTERIOR OF DOORS 110 & 106)

UNISEX RESTROOM (ON WALL AT DOOR 109); BRAILLE REQUIRED

AUTHORIZED PERSONNEL ONLY (ON DOOR 101)

CBP OFFICE (ON WALL AT DOOR 101); BRAILLE REQUIRED

STORAGE ROOM (ON WALL AT DOOR 107); BRAILLE REQUIRED

LAN ROOM (ON WALL AT DOOR 106); BRAILLE REQUIRED

AUTHORIZED PERSONNEL ONLY (ON DOORS 103 & 107)

108A

ROOMNO.X

TYPE

-

108A

108A/108B

108A

110

110

110

108A/110

106/111

109

101

107

106

103/107

101

SELECTED STATUTORY SIGNS (ON WALL IN DETENTION SUITE)103

INTERVIEW ROOM (ON WALL AT DOOR 105); BRAILLE REQUIRED105

SEARCH ROOM (ON WALL AT DOOR 104); BRAILLE REQUIRED104

EXTERIOR IDENTITY SIGNAGE - ON WALL AT ENTRANCE TO GAF - AT BOTH LANDSIDE AND AIRSIDE ENTRANCES12" DIA. SEAL WITH 4" TALL LETTERS - PANEL SIGN STYLE

A

B

C

D

E

F

G

H

I

J

K

L

M

O

P

Q

N

R

S

T

X

8" X 11.5"

SIZEREQUIRED

-

6" X 36"

12" X 36"

15" DIAMETER

CBP FORMS COUNTER

GENERAL COMMENTSFINISH - TEXT - DESCRIPTION

-

RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY

PASSENGER WAITING AREA

1 FULL SET OF AIRPORT STATUTORY SIGNS (TOTAL 10 SIGNS)

WELCOME TO THE UNITED STATES. PLEASE HAVE YOUR DOCUMENTS READY TO PRESENT TO A CBP OFFICER

CBP PROCESSING AREA - 1 DHS SEAL ON FACE OF PROCESSING PODIUM

CBP PROCESSING AREA

CBP PROCESSING AREA - 1 FULL SET OF STATUTORY SIGNS (TOTAL 10 SIGNS)

THANK YOU FOR YOUR COOPERATION

RESTRICTED AREA - AUTHORIZED PERSONNEL ONLY

TOILET

AUTHORIZED PERSONNEL ONLY

101 CBP OFFICE

107 STORAGE

106 LAN ROOM

AUTHORIZED PERSONNEL ONLY

SELECTED STATUTORY SIGNS: (1) ASSAULTING AN OFFICER OR EMPLOYEE OF THE UNITED STATES; (2) SEARCHAND DETENTION OF PERSONS, MERCHANDISE AND CONVEYANCES; (3) EXPLOSIVES, FIREARMS AND WEAPONSARE PROHIBITED; (4) ILLEGAL DRUGS; (5) CURRENCY AND MONETARY INSTRUMENTS; (TOTAL 5 SIGNS)

105 INTERVIEW ROOM

104 SEARCH ROOM

DHS SEAL: U.S. CUSTOMS ANDBORDER PROTECTION-------------------------------------BLUE GRASS AIRPORT

PROVIDEDBY

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

CONTRACTOR

-

CBP

CBP

CBP

CBP

CBP

CBP

CBP

CBP

1

QUANTITYREQUIRED

-

1

2

1

1

1 FULL SETS

1

1 FULL SET

2

2

1

1

1

1

1

1

1 EACH

1

1

2

11" X 17"

11" X 17"

11" X 17"

11" X 17"

11" X 17"

11" X 17"

11" X 17"

6" X 36"

SIGNAGE SCHEDULE

8" X 11.5"

8" X 11.5"

8" X 11.5"

8" X 11.5"

8" X 11.5"

8" X 11.5"

8" X 11.5"

UNISEX RESTROOM (ON WALL AT DOOR 109); BRAILLE REQUIRED109

SEE PLAN; BRAILLE REQUIREDSEE PLAN

U

V

BABY CHANGING STATION

EXIT

CONTRACTOR

CONTRACTOR

1

1

8" X 11.5"

8" X 8"

108A/108B

2.06' H X 7.89' L

15 SECOND DELAYED EGRESS (ON WALL AT DOOR 110); BRAILLE REQUIRED110W 1 8" X 11.5" CARD REQUIRED FOR EXIT OR ALARMED EXIT. PUSH BAR UNTIL THE ALARM SOUNDS. DOOR CAN BE OPENED IN15 SECONDS.

CONTRACTOR

EXIT

VSIGN DETAIL3" = 1'-0" D

LSIGN DETAIL3" = 1'-0"

6" P

ICTO

GR

AM

FIE

LD (T

YP

.)

PICTOGRAM LOCATION(RAISED 1/32" FROMSURFACE OF SIGN)

RAISED LETTERS ONSIGN FACE

GRADE 2 BRAILLE

11 1

/2"

U

BABY CHANGING STATION

6" P

ICTO

GR

AM

FIE

LD (T

YP

.)

RAISED LETTERS ONSIGN FACE

GRADE 2 BRAILLE

11 1

/2"

SIGN DETAIL3" = 1'-0"

Message

100*

NSIGN DETAIL3" = 1'-0"

RAISED LETTERS ONSIGN FACE

RAISED NUMBERSON SIGN FACE

GRADE 2 BRAILLE

RAISED LETTERS ONSIGN FACE

GRADE 2 BRAILLE

ACRYLIC SIGN PANELACRYLIC SIGN PANELACRYLIC SIGN PANEL

ACRYLIC SIGN PANEL

SIGN DETAIL3" = 1'-0"

ACRYLIC SIGN PANEL

TOILET

8" 8"

Message

ASIGN DETAIL3" = 1'-0"

RAISED LETTERS ONSIGN FACE

GRADE 2 BRAILLE

ACRYLIC SIGN PANEL

J

Message 3" FLUSH LETTERSON SIGN FACE

8"

11 1

/2"

8"

11 1

/2"

REFER TO SIGNAGE SCHED.

RE

FER

TO

SIG

NA

GE

SC

HE

D.

F H

O P S T

8"

8"

W

HANG FROM CEILING GRID WITH STAINLESS STEEL AIRCRAFT CABLE SYSTEM

SIGNAGE GENERAL NOTES1. WHERE ROOM SIGNS ARE AT GLASS WALL PROVIDE SOLID PANEL ON OPPOSITE SIDE OF

SIGN ON GLASS.

2. CHARACTERS SHOWN ON THIS SHEET ARE COMPUTER GENERATED. SPACING OFCHARACTERS IS NOT ACCURATE. CORRECT "VISUAL" SPACING IS THE RESPONSIBILITYOF THE MFR.

3. PICTOGRAMS ARE SHOWN HEREIN FOR INFORMATION AND INTENT ONLY. MECHANICAL,CAMERA - READY ARTWORK SHALL BE SUPPLIED BY THE SIGNAGE CONTRACTOR.

4. COLORS OF PANEL SIGNS TO BE SELECTED BY ARCHITECT.

5. UNLESS OTHERWISE NOTED, ALL SIGNS TO BE MOUNTED BESIDE DOORS AT 4'-0" A.F.F.TO BOTTOM OF SIGN AND 2" FROM EDGE OF DOOR FRAME ON THE LATCH SIDE. WHERETHERE IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR, INCLUDING AT DOUBLELEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. MOUNTINGLOCATION FOR SUCH SIGNAGE SHALL BE SO THAT A PERSON MAY APPROACH WITHIN 3IN OF SIGNAGE WITHOUT ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHINTHE SWING OF A DOOR. THE ARCHITECT SHALL BE CONSULTED BEFORE PLACEMENT OFSIGNAGE FOR LEFTHAND AND RIGHTHAND ORIENTATION OF SIGNS.

6. * = THREE CHARACTER NUMBER TO BE SUPPLIED BY ARCHITECT/OWNER.

7. ALL SIGNAGE SHALL MEET REQUIREMENTS OF ADAAG OF THE AMERICANS WITHDISABILITIES ACT (ADA) AND ICC (ANSI) A117.1-2009.

8. MESSAGE (COPY) TO BE DETERMINED BY ARCHITECT/OWNER.

9. SIGNAGE INDICATED TO BE PROVIDED BY CBP IS TO BE PURCHASED BY CONTRACTORTHROUGH U.S. CUSTOMS AND BOARDER PATROL AND INSTALLED BY CONTRACTOR.SIGNAGE INDICATED TO BE PROVIDED BY CONTRACOTR IS TO BE FABRICATED, SUPPLIEDAND INSTALLED BY CONTRACTOR AS INDICATED IN SPEC. AND DRAWINGS.

10. "CBP" REFERS TO UNITED STATES CUSTOMS AND BORDER PROTECTION AGENCY.

11. "GAF" REFERS TO THIS PROJECT / GENERAL AVIATION FACILITY

3"3"

3'-0

"4"

3'-1

0"

4'-0" 3'-0"

3/4"

3/4" 3/4"

DHS SEAL - REFER TOSIGNAGE SCHEDULE

FINGERPRINT READER (N.I.C.)

PLASTIC LAMINATE COLOR A

PLASTIC LAMINATE COLOR B

PLASTIC LAMINATE COLOR C

PLASTIC LAMINATE COLOR B

2'-1

0"

2 1/4" 3/4"

3" 1'-4 1/2" 1'-4 1/2" 3" 1'-9" 1'-9" 3"

4'-0"

1'-0

"2'

-10"

3'-1

0"

3/4" 3/4"

6

A1.3

5

A1.3

FINGERPRINT READER (N.I.C.)

DURRESS ALARM. TETHERTO FLOOR OUTLET

CYLINDERLOCKS

RECESSEDSTAINLESS STEELPULLS

PLASTIC LAMINATE COLOR A

PLASTIC LAMINATECOLOR B

PLASTIC LAMINATECOLOR A

NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.

INTERCOM CABINET WITHPIVOT SLIDING DOOR

PLASTIC LAMINATECOLOR C

CYLINDERLOCKS

RECESSEDSTAINLESS STEELPULLS

3/4" 2 1/4"

3'-0"

7

A1.3

3" 3"

4"

3"

1"3"

10 1/4"

1'-0"

2'-1

0"1'

-0"

OUTLET SWITCH. TETHERTO FLOOR OUTLET

PROVIDE CPUEXHAUST FAN

PLASTIC LAMINATEDRAWERS, ERFER TO SPEC.

8"

DATA/POWER OUTLETS. CONCEALEDFLEX CONDUIT FROM FLOOR. TETHERTO FLOOR OUTLETS

PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF

PLASTIC LAMINATE ON 3/4"PLYWOOD VENTED DOOR

NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.

PLASTIC LAMINATE 3/4"PLYWOOD FRAME

PLASTIC LAMINATE 3/4" PLYWOODTOE KICKS ON 2X WOOD BLOCKING

PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A) WITH RADIUSSEDEGDE ON 1X WOOD FRAMING

PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A)

PLASTIC LAMINATECOLOR B

PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF

1 1/

2"

1/8"

4 1/

4"

1/4"

4 1/

4"

1/4"

1'-7

3/8

"

1'-0"

1'-8"

GROMMET TOLOW COUNTER

4"

1'-0

"2'

-10"

3"3"

1'-3"

2'-9"

3"3"

3" 3"

PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF

PLASTIC LAMINATE ON3/4" PLYWOOD NON-VENTED DOOR

PLASTIC LAMINATE 3/4"PLYWOOD DIVIDER PANELBEYOND

TASK LIGHT, COORDINATEPOWER CONNECTIONWITH ELECTRICAL.

INTERCOM CABINET WITHPIVOT SLIDING DOOR

NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.

PLASTIC LAMINATE 3/4"PLYWOOD FRAME

PLASTIC LAMINATE 3/4" PLYWOODTOE KICKS ON 2X WOOD BLOCKING

SEALANT, CONT.

PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A) WITH RADIUSSEDEGDE ON 1X WOOD FRAMING

PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A)

PLASTIC LAMINATECOLOR B

1 1/

2"8"

1'-8

1/2

"

4 3/4"

1'-8"

4"

2'-1

0"

3" 3"

PLASTIC LAMINATE ON 3/4"PLYWOOD ADJUSTABLE SHELF

PLASTIC LAMINATE ON3/4" PLYWOOD NON-VENTED DOOR

PLASTIC LAMINATE 3/4"PLYWOOD DIVIDER PANELBEYOND

NOTE:ALL PLASTICLAMINATE TO BECOLOR C, U.N.O.

PLASTIC LAMINATE 3/4"PLYWOOD FRAME

PLASTIC LAMINATE 3/4" PLYWOODTOE KICKS ON 2X WOOD BLOCKING

SEALANT, CONT.

PLASTIC LAMINATE 3/4"PLYWOOD COUNTERTOP(COLOR A) WITH RADIUSSEDEGDE ON 1X WOOD FRAMING

1/8"

2'-4

3/8

"

1'-8"

2'-9"

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

10/1

8/2

017 2

:46:2

4 P

M

A1.3

MM

10/20/2017

1508

JSS, BKL

SIG

NA

GE

SC

HE

DU

LE

AN

DE

LE

VA

TIO

NS

AN

D C

AS

EW

OR

KD

ET

AIL

S

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NLE

XIN

GT

ON

, K

EN

TU

CK

Y

1508

BLU

E G

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

1 1/2" = 1'-0"3

PROCESSING PODIUM ELEVATION - FRONT

1 1/2" = 1'-0"4

PROCESSING PODIUM ELEVATION - BACK

1 1/2" = 1'-0"5

PROCESSING PODIUM SECTION

1 1/2" = 1'-0"6

PROCESSING PODIUM SECTION

1 1/2" = 1'-0"7

PROCESSING PODIUM SECTION

No. Description Date

VT

E(NAME)

ABAN(NAME)

FD-#

P-#

SAN

BALANCING VALVE

BALL VALVE

CHECK VALVE

THERMOMETER

DOUBLE CHECK VALVE ASSEMBLY

PIPING UNION

PETE'S PLUG

POINT OF CONNECTION

LIMIT OF DEMOLITION

PIPE ELBOW TURNING UP/TURNING DOWN

PIPE TEE TURNING UP/TURNING DOWN

ABOVE FINISHED FLOOR

ABOVE FINISHED ROOFAFR

AFF

DOMESTIC COLD WATERCW

FREEZE PROOF WALL HYDRANTFPWH

HOSE BIBBHB

DOMESTIC HOT WATERHW

INSIDE DIMENSIONID

IN ACCORDANCE WITHIAW

INVERT ELEVATIONIE

NOT TO SCALENTS

NOT IN CONTRACTNIC

NORMALLY OPENNO

NORMALLY CLOSEDNC

OUTSIDE DIMENSIONOD

OPEN RECEPTACLEOR

TOP ELEVATIONTE

TYPICALTYP

UNLESS OTHERWISE NOTEDUON

VENT PIPING

EXISTING PIPING (THIN LINE)

ABANDONED EXISTING PIPING (THIN LINE)

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER SUPPLY

DOMESTIC RECIRCULATING HOT WATER

CLEANOUT IN CEILING SPACE

FLOOR CLEANOUT

EXTERIOR CLEANOUT

SYMBOLS & ABBREVIATIONS

CAST IRONC.I.

DOWNDN

OVERFLOW ROOF LEADERORL

POUNDS PER SQUARE INCHPSI

DOMESTIC RECIRCULATING HOT WATERRHW

SANITARY RISERSR

THRUST BLOCKTB

TRAP PRIMERTP

VENT THRU ROOFVTR

OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI

OWNER FURNISHED, OWNER INSTALLEDOFOI

CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI

CO

CO

ECO

FLOOR DRAIN DESIGNATOR

PLUMBING FIXTURE DESIGNATOR

XXX

XEQUIPMENT TAG DESIGNATOR

STRAINER

X TAGGED NOTE DESIGNATOR

X REVISION DESIGNATOR

SAFETY RELIEF VALVE

SAFETY RELIEF VALVE

TS

TEMPERATURE SENSOR

HOSE BIB

SANITARY WASTE PIPING

4" SAN

P2

4" E(SAN)

2" SAN

2" VT

4" VT

4"

VT

4"

VT

4" SAN

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:2

5 P

M

P1.0

KRM

09/25/2017

1508/XACO16

CMR

PL

UM

BIN

G L

EG

EN

D

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

PLUMBING GENERAL NOTES• COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, ETC., WITH ALL

CASEWORK EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC., PRIORTO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALLBE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THECONTRACTOR.

• THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE COURSE OFTHEIR WORK SO AS TO INSURE THAT THEY DO NOT INTERRUPT ANYEXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULARATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS ANDELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC., OF EACHUNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BEPERFORMED IN ACCORD WITH ALL FEDERAL, STATE AND/OR LOCALRULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE APPLICABLEMUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THEMOST STRINGENT REQUIREMENT SHALL APPLY.

• WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER ORGYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE RESPONSIBLEFOR REMOVAL AND REINSTALLATION (OR REPLACEMENT, IF DAMAGED)OF ALL CEILING OR TILE AND GRID MEMBERS NECESSARY TO PERFORMHIS WORK. NEW TILE AND GRID SHALL MATCH THE SURROUNDINGAREAS. ALL PATCHING WORK SHALL MATCH ADJACENT SURFACES.

• ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM THEWORK OF OTHER TRADES, WHETHER EXISTING OR NEW.

• PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR (TOOWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC., THAT ARE TOREMAIN IF DAMAGED DURING CONSTRUCTION. REPAIRS SHALL MATCHADJACENT SURFACES TO THE SATISFACTION OF THE ARCHITECT ANDOWNER.

• OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAYAPPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL,FEDERAL, MUNICIPALITY, UTILITY COMPANY, COMMONWEALTH OFKENTUCKY, ETC.)

• CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING WORK DURINGDEMOLITION. IF ITEMS ARE UNCOVERED DURING DEMOLITION THENFIELD VERIFY THE USE OF THE ITEMS AND PLAN AN ALTERNATE ROUTETO RUN THESE ITEMS. THEN CONTACT THE ENGINEERS TO REVIEW THEROUTING.

• WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE ALLEXISTING CONDUITS, WATER, HYDRONIC, ETC. SHALL BE LOWERED TOBE BELOW FULL THICKNESS OF FIRE PROOFING WITH NO INTERFERENCE.

• ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES SHALL BEAPPROPRIATELY FIRE STOPPED PER AN APPROVED U.L. LISTEDSTANDARD. CONTRACTOR SHALL PAY PARTICULAR ATTENTION TOINSULATED PIPING PENETRATIONS.

• ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE BUILDING SHALLBE SCHEDULED 2 WEEKS IN ADVANCE, AND SHALL COMPLY WITHINTERIM LIFE SAFETY MEASURES.

• ALL PIPING IN ROOMS WITH CEILINGS SHALL BE ABOVE CEILING EXCEPTAS NOTED.

• IN ACCORDANCE WITH K.R.S. ALL PLUMBING WORK SHALL BECONSTRUCTED IN COMPLIANCE WITH PLANS APPROVED BY ANDBEARING THE APPROVAL STAMP OF THE KENTUCKY DIVISION OFPLUMBING AND/OR THE DIVISION OF WATER. THE CONTRACTOR SHALLNOT BEGIN WORK UNTIL HE HAS RECEIVED SUCH APPROVED PLANS.

• LOCATIONS OF PIPING AND EQUIPMENT ARE APPROXIMATE ANDSUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT SCALE THEDRAWINGS.

• ALL OFFSETS IN PIPING ARE NOT NECESSARILY SHOWN. PROVIDEADDITIONAL OFFSETS WHERE NECESSARY.

• THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES OROTHER COSTS THAT ANY UTILITY COMPANY MAY REQUIRE TO COMPLETETHEIR WORK. (GAS, SEWER, WATER, ETC.).

• INSTALL ALL PIPING AND EQUIPMENT IN STRICT ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTION. IF IN CONFLICT WITHTHE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THEENGINEERS PRIOR TO INSTALLATION FOR CLARIFICATION. PROVIDERECOMMENDED ACCESS AND SERVICE CLEARANCES FOR ALLEQUIPMENT.

• SEAL AIRTIGHT AROUND ALL PIPING PENETRATIONS THROUGH WALLS,FLOORS AND ROOF. PROVIDE FIRE STOPPING IN FIRE PARTITION.

• THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTINGEQUIPMENT APPURTENANCES, ETC., THAT CONFLICT WITH NEW WORK.

• WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICTWITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEERS BEFOREINSTALLATION. REFER ALSO TO ARCHITECTURAL WALL INTERIOR ANDEXTERIOR WALL ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OFTHESE DOCUMENTS.

• ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCINGEQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN ANAPPROVED MANNER. NOISY OR STRUCTURALLY DAMAGINGINSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED ATTHE INSTALLING CONTRACTOR'S EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BETHAT OF THE ENGINEER.

• DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOREQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE THERESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANYPROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHERAPPROVED BY THE ENGINEERS OR NOT, SHALL BE THE RESPONSIBILITYOF THE PURCHASER.

• VALVES, BALANCING DAMPERS OR ANY MECHANICAL/ELECTRICAL ITEMREQUIRING ACCESS SHALL NOT BE LOCATED ABOVE A HARD CEILING. IFTHIS IS NOT POSSIBLE, THEN AN APPROPRIATELY SIZED ACCESS DOORSHALL BE PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE ANDADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE LOCATEDAN UNREASONABLE DISTANCE ABOVE THE CEILINGS. IN GENERAL ALLSUCH ITEMS UNLESS INDICATED OTHERWISE SHALL BE MOUNTED SIX TOTWELVE INCHES ABOVE THE CEILING. IF IN DOUBT, CONTACT ENGINEERPRIOR TO INSTALLING.

• ALL MANHOLES, VAULTS AND SIMILAR UNDERGROUND STRUCTURESSHALL HAVE THE TOP ELEVATION SET FLUSH WITH FINISHED GRADEUNLESS SPECIFICALLY NOTED OTHERWISE.

• WHEN RUNNING ANY TYPE OF PIPING BELOW A FOOTER, OR IN THE ZONEOF INFLUENCE THE PIPING SHALL BE BACKFILLED WITH CEMENTITIOUSFLOWABLE FILL PER SPECIFICATIONS. WHENEVER POSSIBLE, LOCATEPIPING OUTSIDE OF THE ZONE OF INFLUENCE. THE ZONE OF INFLUENCEIS THE AREA UNDER THE FOOTER WITHIN A 45 DEGREE ANGLEPROJECTING DOWN FROM THE BOTTOM EDGE OF THE FOOTER OF ALLSIDES OF THE FOOTER. ADDITIONALLY, GREASE TRAPS, MANHOLES,VAULTS AND OTHER UNDERGROUND STRUCTURES SHALL BE HELD AWAYFROM BUILDING WALLS FAR ENOUGH TO BE OUTSIDE OF THE ZONE OFINFLUENCE.

• THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND 2009 IECC.

• WORK IN CONFINED AREAS SHALL BE IN ACCORDANCE WITH THEOWNER'S SAFETY POLICY REQUIREMENTS.

PLUMBING FIXTURE SCHEDULE

FIXTURE TAG DESCRIPTION CW HW VENT WASTE

P-1 WATER CLOSET - FLOOR MOUNTED - MANUAL FLUSH VALVE - ADA COMPLIANT : VITREOUS CHINA, 18" HIGHELONGATED BOWL, SIPHON JET, 11/2" TOP SPUD INLET, CHINA BOLT CAPS AND WHITE OPEN FRONT PLASTIC SEATWITH SELF-SUSTAINING CHECK HINGES. PROVIDE MANUAL 1.6 GPF FLUSH VALVE WITH HANDLE AT A MAXIMUM OF31" AFF.

1-1/2" - 2" 4"

P-2 LAVATORY - WALL HUNG W/ SINGLE LEVER FAUCET - ADA COMPLIANT : VITREOUS CHINA, 20"X18" WALL HUNGLAVATORY WITH 4" FAUCET CENTERS, CONCEALED ARMS AND 4" HIGH BACKSPLASH. PROVIDE WITH A 0.5 GPMSINGLE LEVER FAUCET, CHROME PLATED 3/8" SUPPLIES WITH STOPS, GRID DRAIN, A KENTUCKY CODE P-TRAP,TAILPIECE AND ESCUTCHEONS. MOUNT LAVATORY AT A HEIGHT LEAVING A CLEARANCE OF AT LEAST 29" FROMTHE FLOOR TO THE APRON AND THE RIM AT A MAXIMUM OF 34" AFF. PROVIDE ON THE EXPOSED WASTE PIPE ANDWATER SUPPLY LINES A TRAP-WRAP INSULATION KIT WITH A VINYL AND PLASTIC COVERING.

1/2" 1/2" 2" 2"

P-3 SINGLE COMPARTMENT SINK : SINGLE COMPARTMENT STAINLESS STEEL SINK, 19"X21" O.D., 14"X18" I.D., 61/2"DEEP, 18 GAUGE, WITH 8" CENTERS. PROVIDE WITH 8" RIGID SPOUT GOOSENECK FAUCET WITH 4" WRIST BLADECONTROL HANDLES, REAR CENTERED CRUMB CUP STRAINER DRAIN, 3/8" ANGLE SUPPLIES WITH STOPS,KENTUCKY CODE P-TRAP, TAILPIECE AND ESCUTCHEONS.

1/2 1/2" 2" 2"

P-4 ELECTRIC WATER COOLER - BI LEVEL - ADA COMPLIANT : BI-LEVEL BARRIER FREE WATER COOLER WITH SINGLECOMPRESSOR, WATER SUPPLY, DRAIN AND ELECTRICAL CONNECTION. 8.0 GPH OF 50°F WATER AT 90°F AMBIENTAND 80°F INLET WATER, 18.8 GAUGE STAINLESS STEEL BASIN, 1/5 HP COMPRESSOR, 115V/1PH, SURFACEMOUNTED TO THE WALL WITH CHILLER BELOW BOWL AND SIDE AND FRONT PUSH BAR OPERATORS. MOUNT SOTHE BOTTOM OF THE LOWER COOLER IS AT 9" MINIMUM AFF WITH A CLEARANCE OF 27" MINIMUM FROM THEBOTTOM OF THE APRON OF THE BOWL TO THE FINISHED FLOOR. THE DIMENSION TO THE CENTERLINE OF THELOWER COOLER BUBBLER SHALL BE 35".

1/2" - 2" 2"

P-5 EMERGENCY EYE/FACE WASH STATION : GUARDIAN G1724 OR EQUAL EYE/FACE WASH WITH FOUR GS PLUS SPRAYHEADS, STAINLESS STEEL BOWL AND STAY-OPEN BALL VALVE. EACH SPRAY HEAD SHALL HAVE A REMOVABLE ABSPLASTIC SPRAY COVER, RETICULATED POLYURETHANE FILTER, SELF-REGULATING FLOW CONTROL AND INTEGRAL"FLIP-TOP" DUST COVER.PROVIDE WITH LEONARD TA-300-STSTL-REC OR EQUAL EMERGENCY MIXING VALVE TO PROVIDE TEPID WATER TOEYE/FACE WASH UNIT. ASSEMBLY SHALL INCLUDE 1/2" INLETS CHECK AND STOP VALVES AND 1/2" OUTLET. MIXINGVALVE SHALL BE MOUNTED IN A RECESSED STAINLESS STEEL CABINET WITH LOCKING DOOR.

1/2" 1/2" - -

PLUMBING DEMOLITION NOTES• THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR

AREAS IN WHICH THE CEILING IS REMAINING. THE CONTRACTOR ISRESPONSIBLE FOR REMOVING THE EXISTING CEILING AS REQUIRED ANDREINSTALLATION. TEMPORARILY SUPPORT LIGHTS, DIFFUSERS, CEILINGETC. REPLACE BROKEN CEILING TILES WITH NEW AT NO ADDITIONALCOST TO OWNER. FIELED VERIFY EXACT REQUIREMENTS.

• ALL OUTAGES SHALL BE SCHEDULED THROUGH THE PROJECTREPRESENTATIVE FOR PROPER COORDINATION. A REQUEST FOR ANOUTAGE SHALL BE SUBMITTED IN WRITING A MINIMUM OF TWO WEEKS INADVANCE.

• ALL WALLS AND FLOOR SLABS SHALL BE REPAIRED TO MATCH EXISTINGAND TO A LIKE NEW CONDITION. ALL RATED WALLS AND FLOOR SLABSSHALL BE PATCHED AND REPAIRED TO MAINTAIN RATING.

• ALL EXISTING BUILDING FINISHES SHALL BE PROTECTED DURING THEDEMOLITION PHASE.

• HEAVY DASHED LINES INDICATE ITEMS FOR REMOVAL (U.O.N) AND LIGHTSOLID LINES INDICATE EXISTING ITEMS TO REMAIN.

• COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATEDFOR DEMOLITION) WITH THE OWNER.

PHASING NOTES• THIS PROJECT INTERFACES EXTENSIVELY WITH EXISTING BUILDING

SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOCOORDINATE AND PHASE ALL TIE-INS AND INTERRUPTIONS OF EXISTINGSERVICES TO MINIMIZE OR ELIMINATE DOWNTIME. AS AN EXAMPLE,MAIN GAS SERVICE, WATER SERVICE, ELECTRICAL SERVICE, HVACSERVICES, ETC., WILL BE AFFECTED AND REPLACED OR MOVED DURINGTHIS PROJECT. THE CONTRACTOR SHALL INSTALL ALL NEW SERVICESAND EQUIPMENT AND HAVE THEM TESTED AND FULLY AND RELIABLYFUNCTIONAL PRIOR TO INTERRUPTING, RELOCATING OR REMOVING ANYEXISTING SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITYTO BARE ANY AND ALL COSTS ASSOCIATED WITH THIS PHASING,INCLUDING TEMPORARY SERVICES, TEMPORARY RELOCATION, PREMIUMTIME WORK, ETC. CONTRACTOR SHALL COORDINATE ALL SAID WORKWITH THE OWNER AND APPLICABLE UTILITIES PER THE CONTRACTDOCUMENTS.

1SANITARY WASTE AND VENT RISER

ECO

P-2

P-4

P-5

P-3

TAGGED NOTES

P2 4" VENT THRU ROOF. SEAL ROOF PENETRATION WATER TIGHT.

P-1

No. Description Date

DN

DN

P1

E(WH)

3/4" E(HW)

1 1/2" E(CW)

2" E(SAN)

1 1/2" E(CW)

3/4" E(HW)

P5

P-1

P-2

P-5

P-4

P-3

4" SAN

3/4

" C

W

3/4

" H

W

2" VT

4"

VT

P2

ECO

3/4

" C

W

3/4" HW

1 1/2" CW

1 1

/2"

CW

3/4

" H

W

E(WH)

3/4" E(HW)

1 1/2" E(CW)

4"

E(S

AN

)

4"

SA

N

4"

SA

N

P4

P4

P6

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:2

7 P

M

P2.0

KRM

09/25/2017

1508/XACO16

CMR

PL

UM

BIN

G -

FIR

ST

FL

OO

R

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

1/4" = 1'-0"1

DEMO - PLUMBING - FIRST FLOOR

1/4" = 1'-0"2

PLUMBING - FIRST FLOOR

TAGGED NOTES

P1 DEMO EXISTING SINK AND UNDER COUNTER PUMP.

P2 4" VENT THRU ROOF. SEAL ROOF PENETRATION WATER TIGHT.

P4 PATCH AND REPAIR ASPHALT AND CONCRETE PER ARCHITECTURAL REQUIREMENTS.

P5 SALVAGE EXISTING DRINKING FOUNTAIN.

P6 RELOCATE EXISTING DRINKING FOUNTAIN. CONNECT TO EXISTING WATER AND WASTESUPPLY LINES.

TRUENORTH

PLANNORTH

No. Description Date

EA

EA

RA

SA

EA

OA

TA

CD

FD

SD

FSD

E(NAME)

ABAN(NAME)

RF

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

EA AIR DUCT TURNING UP

EA AIR DUCT TURNING DOWN

FLEXIBLE DUCT

SUPPLY AIR DUCT

RETURN AIR DUCT

EXHAUST AIR DUCT

OUTSIDE AIR DUCT

TRANSFER AIR DUCT

CONDENSATE DRAIN

FIRE DAMPER

SMOKE DAMPER

COMBINATION FIRE/SMOKE DAMPER

POINT OF CONNECTION

LIMIT OF DEMOLITION

VOLUME DAMPER

PIPE ELBOW TURNING UP/TURNING DOWN

PIPE TEE TURNING UP/TURNING DOWN

ABOVE FINISHED FLOOR

ABOVE FINISHED ROOFAFR

AFF

CONDENSATE DRAINCD

CAST IRONC.I.

DOWNDN

FIRE DAMPERFD

INSIDE DIMENSIONID

NORMALLY CLOSEDNC

NORMALLY OPENNO

NORMALLY OPENNO

NOT IN CONTRACTNIC

NOT TO SCALENTS

OUTSIDE DIMENSIONOD

CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI

OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI

OWNER FURNISHED, OWNER INSTALLEDOFOI

OPEN RECEPTACLEOR

POUNDS PER SQUARE INCHPSI

SMOKE DAMPERSD

THRUST BLOCKTB

TOP ELEVATIONTE

TYPICALTYP

UNLESS NOTED OTHERWISEUNO

VARIABLE FREQUENCY DRIVEVFD

REFRIGERANT PIPING

SYMBOLS & ABBREVIATIONS

XXX

XEQUIPMENT TAG DESIGNATOR

X TAGGED NOTE DESIGNATOR

X REVISION DESIGNATOR

EXISTING PIPING (THIN LINE)

ABANDONED EXISTING PIPING (THIN LINE)

EXISTING DUCT OR PIPING TO BE REMOVED

CEILING

NOTES:

1. SUPPORT DUCTWORK, DIFFUSERS, ETC. INDEPENDANTLY OFCEILING SYSTEM

2. PROVIDE VOLUME DAMPERS IN ALL BRANCH DUCTS TO GRILLES,REGISTERS, AND DIFFUSERS, INCLUDING RECTANGULAR BRANCHDUCTS.

EXTERNAL INSULATION(WHERE REQUIRED-SEESPECIFICATIONS)

2'' EXTENSION ANDLOCKING QUADRANTOPERATOR

REFER TO SPECS FOR DUCTSEALANT REQUIREMENTS ATFITTING, JOINTS, ETC.

PROVIDE TRANSITION WHEREREQUIRED. PAINT ALL SHEETMETAL (VISIBLE THROUGHGRILLE) PER SPECIFICATIONS.

THE MAX. LENGTH OFFLEX DUCTWORK SHALLNOT EXCEED 6'-0".

CONNECT WITH A MIN. OF THREESCREWS SPACED A MAX. OF 6'' APART.DUCT SHALL BE SECURED WITH PANDUITTYPE STRIP AND A MIN. OF 2 COMPLETEWRAPS OF DUCT TAPE.

RIGID ROUND DUCT. (LENGTH AS REQUIRED)

ROUND VOLUME DAMPER. (REFER TOSPECS) DO NOT PROVIDE VOLUME DAMPERABOVE HARD CEILINGS.

FLEXMASTER OREQUAL BELLMOUTHSPIN-IN COLLARFITTING.

RECTANGULAR MAINDUCT. (SEE SPECFOR INSULATION)

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:2

2 P

M

M1.0

KRM

09/25/2017

1508/XACO16

CMR

ME

CH

AN

ICA

L L

EG

EN

D

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

MECHANICAL GENERAL NOTES• COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, ETC., WITH ALL

CASEWORK EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC., PRIORTO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALLBE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THECONTRACTOR.

• THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE COURSE OFTHEIR WORK SO AS TO INSURE THAT THEY DO NOT INTERRUPT ANYEXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULARATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS ANDELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC., OF EACHUNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BEPERFORMED IN ACCORD WITH ALL FEDERAL, STATE AND/OR LOCALRULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE APPLICABLEMUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THEMOST STRINGENT REQUIREMENT SHALL APPLY.

• WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER ORGYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE RESPONSIBLEFOR REMOVAL AND REINSTALLATION (OR REPLACEMENT, IF DAMAGED)OF ALL CEILING OR TILE AND GRID MEMBERS NECESSARY TO PERFORMHIS WORK. NEW TILE AND GRID SHALL MATCH THE SURROUNDINGAREAS. ALL PATCHING WORK SHALL MATCH ADJACENT SURFACES.

• ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM THEWORK OF OTHER TRADES, WHETHER EXISTING OR NEW.

• PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR (TOOWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC., THAT ARE TOREMAIN IF DAMAGED DURING CONSTRUCTION. REPAIRS SHALL MATCHADJACENT SURFACES TO THE SATISFACTION OF THE ARCHITECT ANDOWNER.

• OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAYAPPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL,FEDERAL, MUNICIPALITY, UTILITY COMPANY, COMMONWEALTH OFKENTUCKY, ETC.)

• CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING, HVAC ANDELECTRICAL WORK DURING DEMOLITION. IF ITEMS ARE UNCOVEREDDURING DEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS ANDPLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THEN CONTACT THEENGINEERS TO REVIEW THE ROUTING.

• WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE ALLEXISTING CONDUITS, WATER, HYDRONIC, ETC. SHALL BE LOWERED TOBE BELOW FULL THICKNESS OF FIRE PROOFING WITH NO INTERFERENCE.

• ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES SHALL BEAPPROPRIATELY FIRE STOPPED PER AN APPROVED U.L. LISTEDSTANDARD. CONTRACTOR SHALL PAY PARTICULAR ATTENTION TOINSULATED PIPING PENETRATIONS.

• ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE BUILDING SHALLBE SCHEDULED 2 WEEKS IN ADVANCE, AND SHALL COMPLY WITHINTERIM LIFE SAFETY MEASURES.

• ALL DUCTWORK, PIPING, CONDUITS, ETC. IN ROOMS WITH CEILINGSSHALL BE ABOVE CEILING EXCEPT AS NOTED.

• LOCATIONS OF PIPING, DUCTS AND EQUIPMENT ARE APPROXIMATE ANDSUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT SCALE THEDRAWINGS.

• ALL OFFSETS IN DUCTS AND PIPING ARE NOT NECESSARILY SHOWN.PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.

• COORDINATE ALL HVAC WORK WITH ELECTRICAL, PLUMBING AND OTHERTRADES TO AVOID INTERFERENCE WITH PIPING, DUCTS, CONDUIT ANDOTHER EQUIPMENT.

• INSTALL ALL PIPING, DUCTWORK AND EQUIPMENT IN STRICTACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTION. IF INCONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS,ADVISE THE ENGINEERS PRIOR TO INSTALLATION FOR CLARIFICATION.PROVIDE RECOMMENDED ACCESS AND SERVICE CLEARANCES FOR ALLEQUIPMENT.

• SEAL AIRTIGHT AROUND ALL DUCTS AND PIPING PENETRATIONSTHROUGH WALLS, FLOORS AND ROOF. PROVIDE FIRE STOPPING IN FIREPARTITION.

• SEAL ALL NEW DUCTWORK JOINTS WITH UNITED MCGILL, IRONGRIP 6O1OR EQUAL WATER BASED SEALANT.

• ALL MOTOR DRIVEN EQUIPMENT SHALL BE INSTALLED WITH FLEXIBLECONNECTIONS TO DUCTWORK, PIPING, ETC., UNLESS OTHERWISENOTED.

• THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTINGEQUIPMENT APPURTENANCES, ETC., THAT CONFLICT WITH NEW WORK.

• WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICTWITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEERS BEFOREINSTALLATION. REFER ALSO TO ARCHITECTURAL WALL INTERIOR ANDEXTERIOR WALL ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OFTHESE DOCUMENTS.

• DOUBLE WIDTH TURNING VANES SHALL BE INSTALLED IN ALL SUPPLY,RETURN, AND EXHAUST DUCTWORK ELBOWS.

• ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCINGEQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN ANAPPROVED MANNER. NOISY OR STRUCTURALLY DAMAGINGINSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED ATTHE INSTALLING CONTRACTOR'S EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BETHAT OF THE ENGINEER.

• DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOREQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE THERESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANYPROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHERAPPROVED BY THE ENGINEERS OR NOT, SHALL BE THE RESPONSIBILITYOF THE PURCHASER.

• VALVES, BALANCING DAMPERS OR ANY MECHANICAL/ELECTRICAL ITEMREQUIRING ACCESS SHALL NOT BE LOCATED ABOVE A HARD CEILING. IFTHIS IS NOT POSSIBLE, THEN AN APPROPRIATELY SIZED ACCESS DOORSHALL BE PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE ANDADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE LOCATEDAN UNREASONABLE DISTANCE ABOVE THE CEILINGS. IN GENERAL ALLSUCH ITEMS UNLESS INDICATED OTHERWISE SHALL BE MOUNTED SIX TOTWELVE INCHES ABOVE THE CEILING. IF IN DOUBT, CONTACT ENGINEERPRIOR TO INSTALLING.

• ALL MANHOLES, VAULTS AND SIMILAR UNDERGROUND STRUCTURESSHALL HAVE THE TOP ELEVATION SET FLUSH WITH FINISHED GRADEUNLESS SPECIFICALLY NOTED OTHERWISE.

• WHEN RUNNING ANY TYPE OF PIPING BELOW A FOOTER, OR IN THE ZONEOF INFLUENCE THE PIPING SHALL BE BACKFILLED WITH CEMENTITIOUSFLOWABLE FILL PER SPECIFICATIONS. WHENEVER POSSIBLE, LOCATEPIPING OUTSIDE OF THE ZONE OF INFLUENCE. THE ZONE OF INFLUENCEIS THE AREA UNDER THE FOOTER WITHIN A 45 DEGREE ANGLEPROJECTING DOWN FROM THE BOTTOM EDGE OF THE FOOTER OF ALLSIDES OF THE FOOTER. ADDITIONALLY, GREASE TRAPS, MANHOLES,VAULTS AND OTHER UNDERGROUND STRUCTURES SHALL BE HELD AWAYFROM BUILDING WALLS FAR ENOUGH TO BE OUTSIDE OF THE ZONE OFINFLUENCE.

• THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND 2009 IECC.

• WORK IN CONFINED AREAS SHALL BE IN ACCORDANCE WITH THEOWNER'S SAFETY POLICY REQUIREMENTS.

PHASING NOTES• THIS PROJECT INTERFACES EXTENSIVELY WITH EXISTING BUILDING

SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TOCOORDINATE AND PHASE ALL TIE-INS AND INTERRUPTIONS OF EXISTINGSERVICES TO MINIMIZE OR ELIMINATE DOWNTIME. AS AN EXAMPLE,MAIN GAS SERVICE, WATER SERVICE, ELECTRICAL SERVICE, HVACSERVICES, ETC., WILL BE AFFECTED AND REPLACED OR MOVED DURINGTHIS PROJECT. THE CONTRACTOR SHALL INSTALL ALL NEW SERVICESAND EQUIPMENT AND HAVE THEM TESTED AND FULLY AND RELIABLYFUNCTIONAL PRIOR TO INTERRUPTING, RELOCATING OR REMOVING ANYEXISTING SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITYTO BARE ANY AND ALL COSTS ASSOCIATED WITH THIS PHASING,INCLUDING TEMPORARY SERVICES, TEMPORARY RELOCATION, PREMIUMTIME WORK, ETC. CONTRACTOR SHALL COORDINATE ALL SAID WORKWITH THE OWNER AND APPLICABLE UTILITIES PER THE CONTRACTDOCUMENTS.

MECHANICAL DEMOLITION NOTES• THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR

AREAS IN WHICH THE CEILING IS REMAINING. THE CONTRACTOR ISRESPONSIBLE FOR REMOVING THE EXISTING CEILING AS REQUIRED ANDREINSTALLATION. TEMPORARILY SUPPORT LIGHTS, DIFFUSERS, CEILINGETC. REPLACE BROKEN CEILING TILES WITH NEW AT NO ADDITIONALCOST TO OWNER. FIELED VERIFY EXACT REQUIREMENTS.

• ALL OUTAGES SHALL BE SCHEDULED THROUGH THE PROJECTREPRESENTATIVE FOR PROPER COORDINATION. A REQUEST FOR ANOUTAGE SHALL BE SUBMITTED IN WRITING A MINIMUM OF TWO WEEKS INADVANCE.

• ALL WALLS AND FLOOR SLABS SHALL BE REPAIRED TO MATCH EXISTINGAND TO A LIKE NEW CONDITION. ALL RATED WALLS AND FLOOR SLABSSHALL BE PATCHED AND REPAIRED TO MAINTAIN RATING.

• ALL EXISTING BUILDING FINISHES SHALL BE PROTECTED DURING THEDEMOLITION PHASE.

• HEAVY DASHED LINES INDICATE ITEMS FOR REMOVAL (U.O.N) AND LIGHTSOLID LINES INDICATE EXISTING ITEMS TO REMAIN.

• COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATEDFOR DEMOLITION) WITH THE OWNER.

SPLIT SYSTEM INDOOR UNIT SCHEDULE

MARK MANUF. MODEL #

DIMENSIONS (IN.) WEIGHT(LBS)

AIRFLOW(CFM)

ELECTRICAL

REMARKS LENGTH WIDTH HEIGHT VOLTAGE PHASE

SS-1 DAIKIN FTX09 2'-7" 9" 1'-0" 18 300 208 V 1 1,2,3,4,5,6

SPLIT SYSTEM OUTDOOR UNIT SCHEDULE

MARK MANUF. MODEL #

DIMENSIONS (IN.)

WEIGHT(LBS)

TOTALCOOLING

(MBH)

SENSIBLECOOLING

(MBH)

HEATINGCAPACITY

(MBH)MINIMUM

SEER

ELECTRICAL

REMARKS LENGTH WIDTH HEIGHT MCAMOC

P VOLTAGE PHASE

CU-1 DAIKIN RX09 2'-3" 1'-0" 1'-10" 60 9.0 9.0 10.0 19 12 A 15 208 V 1 1,2,3,4,5,6,7

EXHAUST FAN SCHEDULE

MARK MANUFACTURER MODEL # SERVICE TYPE CFME.S.P.("WG) RPM HP VOLTAGE PHASE STARTER DRIVE DISCONNECT

MAXSONES MAX DBA WEIGHT REMARKS

EF-1 GREENHECK SQ-90 DETENTIONAREA

INLINE 260 0.50 1725 0.1 120 V 1 YES DIRECT YES 8.8 57 60 1,2

EF-2 GREENHECK SQ-97 RESTROOMEXHAUST

INLINE 100 0.50 1725 0.25 120 V 1 YES DIRECT YES 8.6 56 60 1,2

REGISTERS, GRILLES, AND DIFFUSERS SCHEDULE

MARK MANUFACTURER MODEL TYPE GRILLE SIZE PANEL SIZEINLET DUCT

SIZEBRANCH DUCT

SIZE CFM P.D.NOISE

CRITERIATHROW

PATTERN REMARKS

350FL ALUMININUM SIDEWALL GRILLE 10"X8" - 10"X8" 10"x8" 0-200 .05 25 - 1,2

E-1 TITUS 50F ALUMINUM 1/2" EGG CRATE 12"x12" 12"x12" - 6" DIA. 0-100 .05 25 - 1,2

E-2 TITUS SG-PRA ALUMINUM SECURITY GRILLE 12"x12" 12"x12" - 6" DIA. 0-100 .05 25 - 1,2,4

L-2

R-1 TITUS 50F ALUMINUM 1/2" EGG CRATE 22"x22" 24"x24" - 8" DIA. 101-225 .05 25 - 1,2

R-2 TITUS 50F ALUMINUM 1/2" EGG CRATE 22"x22" 24"x24" - 12" DIA 401-600 .05 25 - 1,2

S-1 TITUS OMNI-AA ALUMINUM ADJUSTABLE SQUARE DIFFUSER 12"x12" 12"x12" 6" DIA. 6" DIA. 0-100 .05 25 4-WAY 1,2,3

S-2 TITUS OMNI-AA ALUMINUM ADJUSTABLE SQUARE DIFFUSER 15"x15" 24"x24" 8" DIA. 8" DIA. 101-225 .05 25 4-WAY 1,2,3

S-3 TITUS OMNI-AA ALUMINUM ADJUSTABLE SQUARE DIFFUSER 18"x18" 24"x24" 10" DIA. 10" DIA. 226-400 .05 25 4-WAY 1,2,3

S-4 TITUS SG-PRA ALUMINUM SECURITY GRILLE 12"x12" 12"x12" 6" DIA. 6" DIA. 0-100 .05 25 4-WAY 1,2,3,4,5

REMARKS:

1. MAINTAIN MANUFACTURER'S CLEARANCES.2. PROVIDE INTERNAL CONDENSATE PUMP.3. SIZE ALL REFRIGERANT PIPING PER MANUFACTURER'S INSTRUCTIONS. REVIEW PIPING RUNS WITH MANUFACTURER.PROVIDE ALL COMPONENETS NECESSARY FOR PROPER OPERATION. R-410 REFRISGERANT.4. ELECTRICAL CONNECTION SHALL BE PROVIDED WITH OUTDOOR UNIT.5. PROVIDE WITH WIRED THERMOSTAT.6. ACCEPTABLE MANUFACTURERS INCLUDE DAIKIN, PANASONIC, OR LG.

REMARKS:

1. MAINTAIN MANUFACTURER'S CLEARANCES.2. HEAT CAPACITY IS BASED ON 70 DB INDOOR AIR TEMPERATURE. COOLING CAPACITY IS BASED ON 80 DB/67 WB INDOOR AIR TEMPERATURE AND95 DB AMBIENT.3. PROVIDE SINGLE POINT ELECTRICAL CONNECTION FOR INDOOR AND OUTDOOR UNIT.4. PROVIDE LOW AMBIENT COOLING TO 0 DEGREES.5. SIZE ALL REFRIGERANT PIPING PER MANUFACTURER'S INSTRUCTIONS. REVIEW PIPING RUNS WITH MANUFACTURER. PROVIDE ALL COMPONENTSNECESSARY FOR PROPER OPERATION. R-410 REFRIGERANT.6. ACCEPTABLE MANUFACTURERS INCLUDE DAIKIN, PANASONIC, OR LG.

LOUVER SCHEDULE

MARK MANUFACTURER MODEL # SERVICE CFMLENGTH

(IN)HEIGHT

(IN) FREE AREAVELOCITY

(FPM)APD (IN.

WG.) REMARKS

L-1 RUSKIN ELF375DX RESTROOMEXHAUST

100 10 8 0.20 SF 500 FPM 0.10 1,2,3

L-2 RUSKIN ELF375DX DETENTIONAREA

260 12 12 0.33 SF 680 FPM 0.10 1,2,3

REMARKS:

1. PROVIDE WITH BIRDSCREEN.2. COLOR TO BE SELECTED BY ARCHITECT.3. ACCEPTABLE MANUFACTURERS INCLUDE RUSKIN, PENN, OR GREENHECK.

REMARKS:

1. PROVIDE FACTORY MOUNTED DISCONNECT.2. ACCEPTABLE MANUFACTURERS INCLUDE TWIN CITY, CAPTIVEAIRE, OR GREENHECK.

REMARKS:

1. COLOR TO BE SELECTED BY ARCHITECT.2. COORDINATE MOUNTING TYPE (LAY-IN, GYP BOARD, ETC.) WITH ARCHITECTURAL DRAWINGS.3. PROVIDE AIR ADJUSTER FLAPS/AIR PATTERN DEFLECTORS.4. PROVIDE WITH TAMPER PROOF SCREWS.5. PROVIDE WITH FACE OPERATED DAMPER ACCESSORY.

1/8" = 1'-0"1

TYPICAL ROUND SUPPLY BRANCH DUCTDETAIL

No. Description Date

DN

DN

E(AHU)

E(AHU)

E(SA)

E(SA) E(SA)

A1

A1 A1

A1 A1

A1 A1 A1 A1

A2

A2

E(OA)

E(CU-2) E(CU-2) E(CU-2) E(CU-2)

G

RF

RF

RF

OA

E(SA)

A13

A13

A5 A5 A5

A5

A5

A5

A5

A2 A2 A2 A2

A15

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:2

3 P

M

M2.0

KRM

09/25/2017

1508/XACO16

CMR

DE

MO

- F

IRS

T F

LO

OR

AIR

DIS

TR

IBU

TIO

N

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

1/4" = 1'-0"1

DEMOLITION MECHANICAL FLOOR PLAN

TAGGED NOTES

A1 REMOVE EXISTING DIFFUSER AND BRANCH DUCT. CAP AND PATCH MAIN DUCT SHEETMETAL AND INSULATION.

A2 EXISTING EQUIPMENT TO REMAIN.

A5 REMOVE EXISTING GRILLE.

A13 EXISTING INTAKE LOUVER TO REMAIN.

A15 SALVAGE EXISTING GRILLES AND DUCTWORK IN THIS AREA.

TRUENORTH

PLANNORTH

No. Description Date

DN

DN

PROCESSING

110

PRE-PROCESSING PASSENGERWAITING

108

TOILET

109

STORAGE

107

LAN/TELCO

106

INTERVIEW

105

SEARCH

104

EXIT VESTIBULE

111

EXISTING STAFF TOILET

-

EXISTING STAFF TOILET

-

EXISTING PUBLIC TOILET

-

EXIST. ELECTRICAL

-

EXISTING JANITOR

-

CBP GENERAL OFFICE

101

DETENTION CORRIDOR

103

E-2

75

E-2

100

S-4

75

S-4

75

E(CU-2) E(CU-2) E(CU-2) E(CU-2)

E(AHU)

E(AHU)

S-4

50

10"x8" EA

S-1

35

S-2

200

S-2

200

S-2

200

S-2

175

S-3

275

S-3

275

S-2

200SS-1

E(SA)

24 30 24 60

E(OA)

G

RF

3/4" CDRF

R-2

600

R-2

550

R-1

200

R-1

200

E-2

50

T

TT

CU-1

E(OA)

12"x12" RA

E(SA)

A4

A4A4

A4 A4

A4

A4

A4

A4

A4

A4

E(SA)E(SA) 12"x

14"

RA

A10

A9

A8

A6

A11

EF-2

L-1

E-1

7510"x8" EA

10"x8" EA

10"x

8"

EA

L-2

10'-0"

A14

A16

3/4" CDRF

10"x8" EA

EF-1

POST-PROCESSING PASSENGERWAITING

113

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:2

4 P

M

M3.0

KRM

09/25/2017

1508/XACO16

CMR

AIR

DIS

TR

IBU

TIO

N -

FIR

ST

FL

OO

R

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

TAGGED NOTES

A4 CONNECT TO EXISTING DUCT.

A6 EXTEND CONCRETE PAD FOR CONDENSING UNIT.

A8 SPILL CONDENSATE TO GRADE. PIPE SHALLPENETRATE EXTERIOR WALL AT 1'-0'' ABOVEFINISHED GRADE AND ELBOW DOWN. SEALPENETRATION WALL PENETRATION AIRTIGHT.

A9 SIZE REFRIGERANT PIPING PER MANUFACTURERSREQUIREMENTS.

A10 BALANCE TO 100 CFM OA.

A11 BALANCE TO 150 CFM OA.

A14 EXHAUST LOUVER SHALL BE A MINIMUM OF 10'-0"FROM INTAKE LOUVER.

A16 REINSTALL AND RECONNECT SALVAGED GRILLES INTHIS AREA.

DIFFUSER RUNOUT SCHEDULEMARK BRANCH DUCT SIZE

E-1 6" DIA.

E-2 6" DIA.

R-1 8" DIA.

R-2 12" DIA

S-1 6" DIA.

S-2 8" DIA.

S-3 10" DIA.

S-4 6" DIA.

TRUENORTH

PLANNORTH

No. Description Date

C

SD

SD

BL

P

UON

E, EM

CFOI

OFOI

CFCI

OFCI

T

C/S

J

DESCRIPTION

DP

S

S

X

S

S 3

S D

S K

PC

S

S 4

S

U

SL

N

OS

OS

S PL

IL

GROUND FAULT PROTECTED DUPLEX WITHWEATHER-PROOF "WHILE IN USE" TYPE DIE-CASTMETAL COVERPLATE WITH LOCKABLE ENCLOSUREAT OUTLET - SEE SPECIFICATIONS

WP

ER

DUPLEX FOR ELECTRIC WATER COOLER: PROVIDEREMOTE, READILY ACCESSIBLE GFI DEVICE AT 48"ADJACENT TO WATER COOLER, COORDINATE EXACTLOCATION WITH PLUMBING CONTRACTOR TO CONCEALOUTLET BEHIND COOLER

EWC

AUDIO/VIDEO INTERCOM STATION: MASTER WITHSELECTIVE DOOR CONTROLS, POWER SUPPLIES & DOORRELAY CONTACTS AS REQUIRED FOR OPERATION OF ANYDOOR IN THE SYSTEM AND VIEWING OF ANY AUDIO/VIDEOINTERCOM REMOTE ON THE SYSTEM. AIPHONE#AX-MVW/DESK STAND - COLOR BY ARCHITECT.

SAME AS ''IM'' EXCEPT WALL MOUNTED W

DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATORSTATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR''EMERGENCY RELEASE'' OPERATOR STATIONS ASREQUIRED.

DOOR RELEASE CARD READER STATION. PROVIDE ANYADDITIONAL ROUGH-IN FOR ''EMERGENCY RELEASE''OPERATOR STATIONS AS REQUIRED.

AUTOMATIC DOOR CONNECTION (MAY ALSO HAVEELECTRIC STRIKE/MAG-LOCK/ELECTRIFIED PANICCONNECTION - SEE ARCHITECTURAL HARDWARESPECIFICATIONS)

FLOORBOX, COMBINATION POWER AND LOWVOLTAGE, REFER TO FLOORBOX SCHEDULE

B

SS

KEYED, LOCKED PULL STATION : DOUBLE ACTION.STATION SHALL ONLY BE OPERABLE VIA KEY INPOSSESSION OF STAFF.

CDCARBON MONOXIDE DUCT DETECTOR

POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES

SAME AS ''CR'' EXCEPT MULLION MOUNT M

SLASH THROUGH ANY DEVICE INDICATES MOUNTINGABOVE COUNTERTOP 4" ABOVE BACKSPLASH

OVERHEAD PROJECTOR: PROVIDE DUPLEXRECEPTACLE, ONE DATA, HDMI, 3.5mm AUDIO, ANDVGA OUTLET ON (3) PLATES

CCTV CAMERA: CEILING MOUNT DOME

WP

''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE WITHONE DUPLEX RECEPTACLE ON BOTH SIDES

AUDIO/VIDEO INTERCOM STATION: REMOTE WITHFLUSH-MTD S.S. ENCLOSURE. AIPHONE #AX-DVF.

S VS

VS

LV

PILOT LIGHT SWITCH (ILLUMINATED WHEN LOAD IS ON)

ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATEDWHEN LOAD IS OFF)

EMERGENCY AUTOMATIC TRANSFER SWITCH FORLIGHTING CONTROLS (REFER TO DETAIL)

FILLED CENTER BAR INDICATES INTEGRAL GROUNDFAULT PROTECTION (GFCI)

GANG RECEPTACLE IN COMBINATION WITH SWITCH(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

FLUSH MOUNTED REMOTE ALARM INDICATINGSTATION/TEST SWITCH

CONNECTION TO SPRINKLER TAMPER SWITCHWITH ADDRESSABLE MODULE

CONNECTION TO SPRINKLER FLOWSWITCH WITH ADDRESSABLE MODULE

PHOTO-ELECTRIC SMOKE DETECTOR FORPATIENT ROOM MONITORING (SEE RISER)

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING UNIT (CPU)

DOOR ALARM/POSITION SWITCH

DOOR POWER SUPPLY

DOOR DELAYED EGRESS/ELECTRIFIED PANIC MECHANISM

TELEVISION SYSTEM OUTLET WITH DUPLEX RECEPTACLE,COORDINATE LOCATION WITH WALL BRACKET WHEREAPPLICABLE

SURGICAL LIGHT INTENSITY CONTROL

LIGHT SWITCH: LOW VOLTAGE

AS NOTED

AS NOTED

LIGHT SWITCH FOR UNDER-CABINET LIGHTS

6'-6'' TOTOP

48" TOLEVER

48" TOLEVER

PULL STATION : DOUBLE ACTION

AUDIO-ONLY NOTIFICATION APPLIANCE

VISUAL-ONLY NOTIFICATION APPLIANCE

AUDIO/VISUAL NOTIFICATION APPLIANCE

BELL / LIGHT

BELL ONLY

HEAT DETECTOR

CARBON MONOXIDE ALARM: SINGLE STATIONW/SOUNDER BASE

CARBON MONOXIDE AUDIO/VISUAL NOTIFICATIONAPPLIANCE

DOOR HOLDER : WALL TYPE

DOOR HOLDER : CLOSURE TYPE

DUCT SMOKE DETECTOR

PRESSURE SWITCH

REMOTE L.C.D. FIRE ALARM ANNUNCIATOR

POST INDICATOR VALVE

ISOLATION MODULE

H.V.A.C. SMOKE DAMPER CONNECTION

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

SURFACE PLUG-MOLD

SPECIAL OUTLETS

HD

ABV CLG

CM

F

DH

ABV DOOR DH

ABV CLG DD

FS

TS

PS

4'-0''

I

ZONE ADDRESSABLE MODULE Z

SM

ABBREVIATIONS

DESCRIPTION

XLSL

, ,

STRIP FIXTURE

CROSS-HATCHING INDICATES LIGHT IS POWEREDFROM THE EMERGENCY-CRITICAL BRANCH

PARALLEL-HATCHING INDICATES LIGHT ISPOWERED FROM THE EMERGENCY-LIFE SAFETYBRANCH

PANEL FURNITURE

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE-SAFETY TYPE, TAMPER-RESISTANT

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)

EXAM LIGHT SWITCH

NIGHT LIGHT SWITCH WITH CONSTANTLY ILLUMINATEDHANDLE

LINE VOLTAGE DIMMER SWITCH

LINE VOLTAGE THREE-WAY SWITCH

LINE VOLTAGE FOUR-WAY SWITCH

KEYED SWITCH

OCCUPANCY OR VACANCY SENSOR SWITCH

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT

LOW VOLTAGE MOMENTARY SWITCH

PHOTO-CELL AS NOTED

SURGICAL/EXAM LIGHT

EXIT LIGHT (CEILING, END, WALL MOUNT)

LIGHTING

REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURESPECIFICATIONS, MOUNTING HEIGHTS, ETC.

SPECIAL VIDEO SYSTEM SIGNAL INPUT

SECURITY PANIC ALARM

SECURITY INTERCOM

SECURITY ACCESS CONTROL

SECURITY CCTV VIDEO SURVEILLANCE

PANIC ALARM BUTTON

PANIC ALARM ANNUNCIATOR

PANIC ALARM POWER SUPPLY CABINET

DOOR RELEASE KEYSWITCH STATION

DOOR RELEASE KEYPAD STATION

MOTION SENSOR DOOR CONTROL

REMOTE DOOR RELEASE PUSH-BUTTON

CCTV CAMERA: WALL MOUNT DOME

CCTV POWER SUPPLIES/CONTROL PANEL 4'-0''

4'-0''

DOORFRAME

ABV DOOR

8" ACT

DESCRIPTION

WALL, CLG

80"

CLG

CLG

CLG

WALL

54"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

4'-0"

1'-6"

1'-6"

1'-6"

1'-6"

4'-0"

1'-6"

1'-6"

ON CNTR.

2'-2"

CLG

AS NOTED

4'-0''

4'-0''

18''

4'-0''

4'-0''

CLG

4'-0''

6'-0''

4'-0''

4'-0''

CEIL.

CLG

7'-0"

S

CLG

S

FLOOR

S

S

S M

TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION

TELEVISION

4'-0" TV-HE

DR

AW

ING

SY

MB

OL

AMBER STROBE 80''

,

SURFACE OR SUSPENDED CEILING FIXTURE (SLASHINDICATES RECESSED)

POLE MOUNTED AREA LIGHT

, ,

,

,

EMERGENCY BATTERY WALL-PACK

WALL MOUNT FIXTURE ,

FLOODLIGHT

V

A

F

F K

F

GRAPHICS DISPLAY TERMINAL

RI

INDICATES VANDAL-PROOF POLYCARBONATE COVER,VANDAL PROOF COVERS SHALL BE UL LISTED FOR USEWITH THE SPECIFIC DEVICE THEY ARE PROTECTING

PC

80"

CLG

WALL

WALL

7'-6''

FIREMAN'S PHONE JACK FP

ADDRESSABLE RELAY MODULE R

WALL

ACCESS CONTROL POWER SUPPLIES/CONTROL PANEL 4'-0''

4'-0''

ABV CLG

ELECTRIC STRIKE AT LATCH

MAGNETIC LOCK(S) ABV DOOR

INDICATES EXTERIOR CAMERA RATED FORCONDITIONS, WET LOCATION LISTED, WITHAUXILLARY HEATER

PTZINDICATES CAMERA WITH PAN/TILT/ZOOM FUNCTION

FLOORBOX, POWER ONLY, AS SCHEDULED FLOOR

FIRE RATED POKE THOUGH FLOOR BOX, COORDINATEEXACT COVER REQUIREMENTS WITH ARCHITECTURALFINISHES, DEVICES AS SCHEDULED

DESCRIPTION

K

DB

DB

WP

DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETEWITH TRANSFORMER (MOUNT ABOVE CEILING INCORRIDOR NEAR PUSH-BUTTON) AND ALL ACCESSORIES,POWER FROM NEAREST AVAILABLE 120V NORMAL POWERGENERAL RECEPTACLE CIRCUIT, NUTONE OR EQUAL

DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDECONNECTION TO PUSHBUTTON STATION IN AREA.COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER, ETC.)DESIRED WITH OwNER/ARCHITECT, NUTONE OR EQUAL

PLUMBING FIXTURE ELECTRIC EYE TRANSFORMERCONNECTION. TRANSFORMER SHALL BE 120V-24V.MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAMETYPE AS/IF NEEDED

PROVIDE CONNECTION TO HAND DRYER (SEEARCHITECTURAL SPECIFICATIONS)

VERIFY WITHARCHITECT

WGWIREGUARD - PROVIDE MANUFACTURER'S SPECIFICGUARD FOR DEVICE NOTED

BOX ON ANY DEVICE INDICATES SURFACE MOUNTEDBACKBOX/WIREMOLD

CONDUIT CONCEALED IN WALLS OR IN CEILINGSPACE: ARROW(S) INDICATE(S) HOME RUN & # OFCIRCUITS: HASHMARKS INDICATE # OFCONDUCTORS. DASHED LINE INDICATESCONDUIT BELOW FLOOR.

WIREWAY WITH REMOVABLE COVER (SIZE AS NOTED)

PANELBOARD, SURFACE OR FLUSH MOUNTED,HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

MECHANICAL EQUIPMENT DESIGNATOR(SEE MECH. SCHEDULES)

EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)

KITCHEN EQUIPMENT OUTLET COUPLING CONNECTION(SEE DETAIL)

AS SHOWN

AS SHOWN

AS NOTED

AS SHOWN

MISCELLANEOUS

DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC COMBINATION STARTER

ENCLOSED FLUSH MTD. CIRCUIT BREAKER

WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOROUTDOORS.

TRENCH DUCT (SIZE AS NOTED)

PUSHBUTTON STATION

FLEXIBLE CONDUIT

TRANSFORMER

TAGGED NOTE

REVISION TAG

WIRE BASKET CABLE TRAY, SIZE AS NOTED

LOW VOLTAGE CABLE PATH

5'-0"

5'-0"

5'-0"

5'-0"

4'-0"

4'-0''

7'-6''

6'-6'' TO TOP

XPEXPLOSION PROOF - PROVIDE WIRING METHODS,ENCLOSURES, RATINGS, ETC. AS SUITABLE FORHAZARDOUS LOCATION.

SURGE PROTECTION DEVICE

GENERATOR ANNUNCIATOR PANEL - SEE SPECIFICATIONS 4'-0''

THERMOSTAT PROVIDED BY MECHANICAL CONTRACTOR,ELECTRICAL CONTRACTOR SHALL PROVIDE BACK-BOXCONDUIT STUB-UP, REFER TO MECHANICAL DRAWINGSFOR LOCATIONS

PANEL FURNITURE DUPLEX RECEPTACLE. PROVIDE ALLWIRING AS REQUIRED, COORDINATE EXACTINSTALLATION REQUIREMENTS AND LOCATIONS WITHOWNER'S PANEL FURNITURE VENDOR

PANEL FURNITURE DATA/VOICE OUTLET. PROVIDE ALLWIRING AS REQUIRED, COORDINATE EXACTINSTALLATION REQUIREMENTS AND LOCATIONS WITHOWNER'S PANEL FURNITURE VENDOR

POWER CONNECTION TO PANEL FURNITURE,PROVIDE SEAL-TIGHT CONDUIT CONNECTION FROMRECESSED WALL BOX TO PANEL FURNITURE,PROVIDE FINAL CONNECTIONS TO PANEL FURNITUREAS REQUIRED BY PANEL FURNITURE VENDOR

1'-6"

COMBINATION POWER AND LOW VOLTAGE CONNECTIONTO PANEL FURNITURE, PROVIDE SEAL-TIGHT CONDUITCONNECTION FROM RECESSED WALL BOX TO PANELFURNITURE, PROVIDE FINAL CONNECTIONS TO PANELFURNITURE AS REQUIRED BY PANEL FURNITUREVENDOR

PPPOWER POLE AS NOTED

,

SECURITY INTRUSION DETECTION

MOTION DETECTOR CLG

MOTION DETECTOR KEYPAD CONTROLLER 4'-0''

SECURITY SYSTEM HEAD END 4'-0''

LIGHTING CONTROL SWITCHES

MOMENTARY CONTACT SWITCH

HAND-OFF-AUTO 3-POSTION SWITCH

TIMER SWITCH

S MC

S HOA

S T

4'-0"

4'-0"

4'-0"

M

SV

S

S

V

1'-6''

4'-0''PAGING SYSTEM AMPLIFIER/TUNER CABINET

PAGING MICROPHONE

WALL VOLUME CONTROL

PAGING SPEAKER: WALL

PAGING SPEAKER W/ VOLUME CONTROL

PAGING SPEAKER: CEILING CLG

CLG

8'-0"

4'-0"

OVERHEAD PAGING

VANDAL PROOF / WEATHERPROOF WALL MOUNTEDPAGING SPEAKER. QUAM VP1

EXTERIOR VANDAL PROOF / WEATHERPROOF WALLMOUNTED PAGING SPEAKER, SHALL BE PAINTEDCOLOR SELECTED BY ARCHITECT/OWNER. QUAM VP6

RECESSED WALL MOUNTED PAGING SPEAKERDUKANE 5A606 SPEAKER. ATLAS 417-8WD

WALL MOUNTED PAGING HORN

CALL INITIATION STATION

LCD WALL DISPLAY

8'-0"

9'-0"

SEEFLOORPLANS

SEEFLOORPLANS

44"

S

H

S

S

C

LD

R

EXT.

FIRE ALARM

WP

PUSH-TO-EXIT BUTTON 4'-0''

SURFACE WIRE-MOLD

PE

PA

MK

MD

SEC-M

GEN-A

SPD

J

J

ML

ES

SEC-A

GDT

AS

NAC

CC

CC

CR

RR

DP

DA

IM

KP

IR

KS

MS

PP

CR

DS

AD

IM

PIV

FAA

FACP

SEC-P

PA

PB

SEC-C

J

T

FP

DR

AW

ING

SY

MB

OL

DR

AW

ING

SY

MB

OL

MO

UN

TIN

GH

EIG

HT

(T

OC

EN

TE

R O

FB

OX

)

DR

AW

ING

SY

MB

OL

AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYESENSOR CONNECTION. COORDINATE EXACTCONNECTION REQUIREMENTS WITH MANUFACTURER.

GROUND

NEUTRAL

PHASE

FIREMAN'S KNOX BOX CONNECTION KB

REMOTE FIRE ALARM ANNUNCIATOR W/ MICROPHONE 54" FAAM

WALL, CLG

WALL, CLG V

A

F,

,

,

CM

INDICATES CHIME AUDIBLE NOTIFACTION CH

DEVICE USED FOR ELEVATOR CONTROL EL

FIRE ALARM CONTROL EXTENDER EXT

4'-6''

TRANSPONDER CABINET 4'-0'' TRAN

BE , BRPROJECTED BEAM SMOKE DETECTOR; EMITTER(BE) AND RECEIVER (BR)

FLOOR

AV

AUDIO/VISUAL SYSTEM OUTLET WITH DUPLEXRECEPTACLE, REFER TO ASSOCIATED DETAIL FORADDITIONAL INFORMATION

1'-6"

COMBINATION POWER AND DATA OUTLET LOCATION,REFER TO ASSOCIATED DETAIL FOR ADDITIONALINFORMATION

1'-6"

COMBINATION POWER AND DATA OUTLET LOCATION,GFCI DUPLEX RECEPTACLE, REFER TO ASSOCIATEDDETAIL FOR ADDITIONAL INFORMATION

1'-6"

1'-6"FF

,

,

DEAD FRONT GFCI DEVICE, LABEL AND INSTALL INREADILY ACCESSIBLE LOCATION

FILLED OUTER BARS INDICATES INTEGRAL INTEGRALUSB OUTLETS IN ADDITION TO POWER RECEPTACLES

1'-6"

, J

VARIABLE FREQUENCY DRIVE 5'-0"

CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROMSTUB UP CONDUIT

MOTOR CONNECTION, REFER TO EQUIPMENTCONNECTION SCHEDULE

DUPLEX RECEPTACLE, CEILING MOUNTED CLG

CONDUIT UP

CONDUIT DOWN

GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''

WIREGUARD - PROVIDE MANUFACTURER'S SPECIFICGUARD FOR DEVICE NOTED

PAY

#D/#V

#D

INTERMEDIATE DISTRIBUTION FRAME - REFERENCEDATA SYSTEM SCHEMATICS AND DETAILS FORADDITIONAL REQUIREMENTS

MAIN DISTRIBUTION FRAME - REFERENCE DATA SYSTEMSCHEMATICS AND DETAILS FOR ADDITIONALREQUIREMENTS

WIRELESS ACCESS POINT OUTLET WITH PROVISIONSFOR (1 DATA OUTLET FOR ANTENNA. PROVIDE ACOMPLETE DATA OUTLET WITH FACEPLATE ABOVECEILING, MOUNTED AT AN ACCESSIBLE HEIGHT NO MORETHAN 24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A20' COIL OF CABLE AHEAD OF THE OUTLET FORADJUSTMENT OF FINAL OUTLET LOCATION. THECONTRACTOR SHALL COORDINATE EXACT LOCATIONSWITH THE OWNER AND ADJUST OUTLET LOCATIONS ATSUBSTANTIAL COMPLETION TO ACCOMMODATE OWNER'SWAP LOCATIONS.

TELECOMMUNICATIONS SYSTEM BACKBOARD. PROVIDE96''H x 3/4''D FIRE-RETARDENT PLYWOOD BACKBOARDWITH TWO (2) COATS OF NON-C0NDUCTIVE, FIRE-RETARDANT LIGHT GRAY PAINT, #3/0 TO GROUND BAR ATMAIN SERVICE SWITCHBOARD, 30-PT GROUND BAR AND A6'-0'', #3 AWG PIGTAIL AT BACKBOARD. INSTALL BOARD AT2' AFF. (LENGTH OF BOARD AS INDICATED ON FLOORPLAN)

WAP

DATA OUTLET : NUMBER BESIDE OUTLET INDICATESNUMBER OF DATA JACKS

VOICE OUTLET : NUMBER BESIDE OUTLET INDICATESNUMBER OF VOICE JACKS

COMBINATION OUTLET : NUMBER BESIDE OUTLETINDICATES NUMBER OF DATA/VOICE JACKS

TELEMETRY ANTENNA

RF TRACKER ANTENNA

DATA / VOICE

AS REQ'D.OUTLET (VOICE ONLY) : PAYPHONE TYPE

1'-6"

1'-6"

1'-6"

CLG

CLG

#V

MDF

IDF

TEL

SLASH THROUGH ANY DEVICE INDICATES MOUNTINGABOVE COUNTERTOP 4" ABOVE BACKSPLASH

,

#D

,

#V

,

#D/#V

S 1LINE VOLTAGE SWITCH 4'-0"

CLG

MO

UN

TIN

GH

EIG

HT

(T

OC

EN

TE

R O

FB

OX

)

MO

UN

TIN

GH

EIG

HT

(T

OC

EN

TE

R O

FB

OX

)

MO

UN

TIN

GH

EIG

HT

(T

OC

EN

TE

R O

FB

OX

)

DESCRIPTION

CA

BL

ING

/CO

ND

UC

TO

RS

- O

F O

I

CA

BL

ING

/CO

ND

UC

TO

RS

- O

F C

I

CA

BLIN

G/C

ON

DU

CT

OR

S -

C F

C I

ITE

M U

SE

D O

N P

RO

JE

CT

DE

VIC

ES

- O

F C

I

DE

VIC

ES

- C

F C

I

SYSTEM DE

VIC

ES

- O

F O

I

SECURITY: PANIC ALARM (VENDOR ALLOWANCE)

SECURITY: ACCESS CONTROL (VENDOR ALLOWANCE)

SECURITY: INTERCOM (VENDOR ALLOWANCE)

SECURITY: CCTV (VENDOR ALLOWANCE)

SYSTEMRESPONSIBILITYMATRIX

FIRE ALARM

TELEVISION

DATA PROCESSING

TELEPHONE

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TOVENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGSSHALL BE INCLUDED BY THE CONTRACTOR.

B. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESSCONTROL DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.

C. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACTINSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OFALL SYSTEMS PRIOR TO CONSTRUCTION.

D. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS,CONTRACTOR SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TOCABLE PATHS AS REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS ATCABINETS/ON BACKBOARDS AS REQUIRED. COORDINATE EXACTREQUIREMENTS WITH APPROPRIATE VENDORS PRIOR TO CONSTRUCTION.

E. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALLSYSTEMS INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION,GROUNDING, TESTING, LABELING, ETC.

F. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEMCOMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THECONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TOBID. ALL SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BEFULLY COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORSSHALL COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR TOBID. NEW COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMSWHERE POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BECOORDINATED WITH THE OWNER PRIOR TO ORDERING. ALL PROGRAMMINGSHALL BE INCLUDED AS REQUIRED BY THE OWNER. PROVIDE 4 HOURS OFTRAINING FOR EACH SYSTEM.

SECURITY: PANIC ALARM

SECURITY: ACCESSCONTROL

SECURITY: INTERCOM

SECURITY: CCTV

FIRE ALARM

SYSTEM COMPANY CONTACT

SIMPLEX

MATRIX SYSTEMSINC.

MATRIX SYSTEMSINC.

MATRIX SYSTEMSINC.

MATRIX SYSTEMSINC.

DANNY CALIA859-294-7233

JEFF STOUT844-593-6879

JEFF STOUT844-593-6879

JEFF STOUT844-593-6879

JEFF STOUT844-593-6879

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:1

6 P

M

E1.0

AKP

09/25/2017

1508/XACO16

WRS

EL

EC

TR

ICA

L L

EG

EN

D

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

ELECTRICAL GENERAL NOTES• EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO

THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITHSPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT WITH ANY OTHER BUILDINGSSYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.

• ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THECONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE UNDERSTANDING OF THEPROJECT REQUIREMENTS.

• WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES. INCLUDINGBUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.

• CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATEAND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TOELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.

• ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED.ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

• INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THECOLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

• ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOWCLARIFICATION BY WRITTEN ADDENDUM.

• WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENTREQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.

• DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND MUST BESUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.

• OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT.(CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).

• MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO.MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.

• INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS ANDDIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER PRIOR TOINSTALLATION FOR CLARIFICATION.

• DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE RATING. NOINSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.

• THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE,FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

• ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOTMEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THEACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER

• ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATEOF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY PERIODS FOREQUIPMENT ARE SPECIFIED.

• UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OREXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENTSURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.

• WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKESUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY.COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND ARCHITECT.

• THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THEUTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).

• COORDINATE WITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEWORK DETAILS FOR LOCATION OF ADDITIONALRECEPTACLES, UTILITY OUTLETS, ELECTRICAL DEVICES, ETC.

• CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2'DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.

• ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROMSURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BESATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE ENGINEER.

• CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.

• PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT

• DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THERESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION,WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.

• THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THISCONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORKOF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANYSUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.

• WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THEENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS,CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.

• WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD ORPRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TOMAINTAIN CEILING RATINGS.

• COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHENEQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATEDSHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE CONTRACTOR(S).

• ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OROTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOTACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE ENGINEER IN WRITING.

• ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE ORMULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.

• NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E.VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.

• ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DONOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THISPRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACHUNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATEAND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED INACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOSTSTRINGENT REQUIREMENT SHALL APPLY.

• ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE.DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN PERMISSION FROM THEENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.

• WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLECONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.

• REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETSAND EQUIPMENT. IF IN DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.

• FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONSPROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER PRIOR TOROUGHING-IN ANY WORK.

• AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FORSEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARYCONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE.

• THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTINGAND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.

• ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF INDOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.

• INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITYCOMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. ASCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TOAVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANYANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGERNOTIFICATION PERIOD, SO PROVIDE.

• WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAMEWALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND TRANSMISSION FROMROOM TO ROOM.

• JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL.LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH SPECIFICATIONS, WHICHEVERIS MORE STRINGENT.

• ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONALELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OFLOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVINGJURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT SHALL APPLY.

• DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONEDDRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.

• NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTERHOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.

• ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THEOWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.

• REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. WORK SHALL BE COMPLETED IN PHASES PER THEPHASING PLAN AND AS COORDINATED WITH OWNER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTALINSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS REQUIRED BY OWNER TO ACCOMPLISH THEPHASING PLAN.

12" = 1'-0"1

ELECTRICAL LEGENDNo. Description Date

DN

DN

J

J

FF

F

F

FF J

J J J J

CR

F

S

S

KP

KP

CR

KP

KP

.

GFI

.

GFI

.

GFI

.

3

.

3

.

GFI

.

MC

.

MC

.

EPB

.

EPB

.

MC

X4

X4

X4

X6

X5

X7

X8

X16

X3

X16

X13

X3

X3

X15X15X15X15

X3

X3

X9

X9

X11

X12

X10

X2

X17

X17

X3

X3X2 X1

X17

X17

X14

X14

X14

X15

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:1

7 P

M

E2.0

AKP

09/25/2017

1508/XACO16

WRS

DE

MO

- F

IRS

T F

LO

OR

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

GENERAL NOTES (DEMOLITION):

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINESINDICATE EXISTING ITEMS TO REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITSTHAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHENDEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THEDRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OREQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON THE CIRCUITS SHALLREMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUITBREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BELABELED AS SPARES IN THEIR PANELS. PROVIDE NEW TYPEWRITTENDIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THISDRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY AREDIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTINGCONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL.THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATEDHEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTIONTHAT THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HEPROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FORDEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH ANDREPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES ARESHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW FINISHES -SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FORDEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO OWNER ATTHEIR OPTION.

F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/ORRELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATEDWITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTIONBARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGSAS REQUIRED WHERE DEVICES ARE BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLECEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NECREQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALLBE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENTSHOWN ON PLANS.

K. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OFBUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT ANDAS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BERESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTENINSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER ASREQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL ANDENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.

L. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORKPLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEWLOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.

M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALLBE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND INSERTSLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES ORNUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE DETAILEDAND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL ROOMNUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSEDBREAKERS SHALL BE IN OFF POSITION.

TAGGED NOTES

X1 EXISTING PANEL PP5. PANEL TO BE REMOVED AND RELOCATED . SALVAGEEXISTING FEEDER. PANEL IS 120/240 VOLT, RATED AT 100 AMPS.

X2 EXISTING MATRIX SYSTEM ACCESS CONTROL PANEL TO TO BE SALVAGED ANDREINSTALLED AT NEW LOCATION.

X3 EXISTING FIRE ALARM DEVICE TO BE SALVAGED AND REUSED IN EXPANDEDSIMPLEX SYSTEM.

X4 MOMENTARY CONTACT SWITCH TO BE REMOVED.

X5 EXISTING PANEL PP2 TO REMAIN.

X6 EXISTING PANEL PP3 TO REMAIN.

X7 EXISTING TELECOMMUNICATION BACKBOARD AND SERVICE ENTRANCE.SERVICE TO REMAIN.

X8 EXISTING SIMPLEX FIRE ALARM CONTROL PANEL (FACP) 4010 TO BE EXPANDEDAS NEEDED FOR AREA OFRENOVATION.

X9 EXISTING EMERGENCY PUSH BUTTON TO BE SALVAGED AND REUSED.

X10 EXISTING PANELS TO BE REMOVED AND RELOCATED. SALVAGE EXISTINGFEEDER. PANEL IS 120/240 VOLT, RATED AT 100 AMPS.

X11 EXISTING IT SERVER TO BE RELOCATED. PROVIDE NETWORK CONNECTIONS TONEW LAN/TELCO ROOM.

X12 EXISTING EIGHT (8) CAT 5E NETWORK CONNECTIONS. CABLES TO BE REMOVED.

X13 EXISTING WATER HEATER WITH ELECTRICAL CONNECTIONS TO REMAIN. REFEEDAS NEEDED.

X14 EXISTING EMERGENCY EGRESS REMOTE HEAD TO REMAIN AND REFEED VIANEW INVERTER POWER SUPPLY

X15 EXISTING MECHANICAL UNIT TO REMAIN. MAINTAIN POWER AS NEEDED.

X16 EXISTING FIRE ALARM DEVICE EXISTING TO REMAIN. MAINTAIN OPERATION.

X17 EXISTING ACCESS CONTROL READER/KEYPAD TO BE REMOVED. REVISE ACCESSCONTROL PROGRAMMING TO REFLECT REMOVAL OF DEVICES.

1/4" = 1'-0"1

DEMO - FIRST FLOOR

TRUENORTH

PLANNORTH

No. Description Date

LR

LR

LR

LR OS

OSOSOS

LR

PROCESSING

110

CBP GENERAL OFFICE

101

EXIT VESTIBULE

111

EXISTING PUBLIC TOILET

-

EXISTING STAFF TOILET

-

EXIST. ELECTRICAL

-

EXISTING JANITOR

-

DETENTION CORRIDOR

103

SEARCH

104

INTERVIEW

105

LAN/TELCO

106

STORAGE

107

PRE-PROCESSING PASSENGERWAITING

108

TOILET

109

R1 R1 R1

R1R1R1 R1

R1

R1E

R1 R1

S1E S1

S1S1

VR2E

VR2

VR1E

VR1

R1 R1

R1

R1R1

R1E

R1

R1E

R2R2E

.OS

.OS

R1 R1 R1 R1

.OS

R1

X1

.3

.OS

X2

L2

X1

L1

L1

.LVD

.LVD

.LVD3

.LVD3

a a a a

a

aa

aa

aa

a

bb

b

b

a

b

R1

S2

U1

L5

R1

b

-16PP2

L3 L3

L4

.LVD3

L7

L7

L1

L7

L6

.LVD3

.LVD3.LVD3a b

L4

PP2PP5

L4

L2

-18PP2

U1

U1

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:1

8 P

M

E3.0

AKP

09/25/2017

1508/XACO16

WRS

LIG

HT

ING

- F

IRS

T F

LO

OR

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

1/4" = 1'-0"1

LIGHTING - FIRST FLOOR

GENERAL NOTES (LIGHTING):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL ANDCEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, ASINDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCHCIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDEDWITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRALCONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IFADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSEINDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYINGCONDUCTORS PER N.E.C. #310.15(B)(3), AND UPSIZE CONDUIT ASREQUIRED PER N.E.C. #300.17 AND ANNEX C. MULTIWIRE BRANCHCIRCUITS AS DEFINED IN N.E.C #100 / 210.4 (CIRCUITS SHARING A COMMONNEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVELABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVEEMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. ALSO,MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.

D. LOCATE CHAIN-HUNG INDUSTRIAL FIXTURES IN MECHANICAL ROOMS TOAVOID DUCTWORK AND PIPING, TO MAXIMIZE AVAILABLE LIGHT. SPACEAROUND EQUIPMENT, AIR HANDLERS, ETC. TO PROVIDE ADEQUATELIGHTING TO ALL AREAS OF ROOM. PROVIDE ADDITIONAL FIXTURES OFSAME TYPE AS NEEDED TO FULFILL THIS REQUIREMENT.

E. LOCATE EXIT SIGNS FOR MAXIMUM VIEWING AREA TO IDENTIFY EGRESSPATHS AS INDICATED ON PLANS. COORDINATE LOCATIONS SUCH THATARCHITECTURAL FEATURES OR EQUIPMENT FROM OTHER TRADES DONOT OBSTRUCT VIEW.

F. WHERE EXIT SIGNS OR EMERGENCY BATTERY PACKS ARE PROVIDED,THEY SHALL BE CONNECTED TO AN UNSWITCHED LINE.

G. LUMINAIRES INDICATED WITH MULTI-LEVEL SWITCHING SHALL HAVESIMILAR LAMPS CONTROLLED TOGETHER, I.E. INBOARD AND OUTBOARDLAMPS OR RIGHT AND LEFT HAND LAMPS.

H. ALL LIGHTING FIXTURE LENSES, PARABOLIC LOUVERS, DOWNLIGHTINGALZAK CONES AND "PARACUBE" LOUVERS SHALL BE HANDLED WITHCOTTON GLOVES DURING INSTALLATION AND LAMPING TO AVOIDFINGERPRINTS OR DIRT DEPOSITS. IT IS PREFERRED THAT FIXTURES BESHIPPED AND INSTALLED WITH CLEAR PLASTIC BAGS TO PROTECTLOUVERS. AT CLOSE OF PROJECT, AND AFTER CONSTRUCTION AIRFILTERS ARE CHANGED, REMOVE BAGS. ANY LOUVER OR CONE SHOWINGDIRT OR FINGER PRINTS SHALL BE CLEANED WITH SOLVENTRECOMMENDED BY THE MANUFACTURER, OR REPLACED AS NECESSARYIN ORDER TO TURN OVER TO THE OWNER NEW FIXTURES AT OCCUPANCY.

I. RECESSED LUMINAIRES SHALL BE SECURED SUCH THAT THE FORCEREQUIRED INSERTING LAMPS, TRIMS, LENSES, LOUVERS, OR DOORFRAMES DOES NOT SHIFT HOUSING. ALL TRIMS SHALL BE COMPLETELYFLUSH WITH FINISHED CEILINGS AT COMPLETION OF CONSTRUCTION.

J. CONTRACTOR SHALL PROVIDE UNSWITCHED CONDUCTOR TO ALL EXITSIGNS, EMERGENCY INVERTER BATTERY PACKS, AND NIGHT LIGHTS ASREQUIRED.

TAGGED NOTES

L1 EXISTING ROOM LIGHT FIXTURES AND CONTROLS REMAIN AND RECIRCUITED.

L2 LIGHTING CONTROL RELAY WITH NETWORK INTERFACE. RELAYS TO PROVIDEAUTOMATIC LIGHTING CONTROL VIA PROGRAMMABLE TIMECLOCK SCHEDULE.

L3 LIGHT CONTROL SWITCH TO BE VANDAL PROOF (INSTITUTION GRADE).

L4 LIGHTING CONTROL RELAY FOR LOCAL LIGHTING CONTROL(SWITCH/OCCUPANCY SENSOR).

L5 PROVIDE WALL MOUNTED "IN USE" LIGHT TO ILLUMINATE UPON LIGHT CONTROLON STATUS IN ROOMS 103, 104, AND 105. LIGHT TO BE LASERMET SLIM JIM THINPROFILE LED "ROOM IN USE" SIGN OR EQUAL.

L6 REPLACE EXISTING EXIT SIGN WITH TYPE X1.

L7 NEW LIGHTING CONTROL SWITCH. CIRCUIT TO EXISTING FIXTURES.

TRUENORTH

PLANNORTH

No. Description Date

DN

DN

J

J

J

J

PROCESSING

110

CBP GENERAL OFFICE

101

EXIT VESTIBULE

111

EXISTING PUBLIC TOILET

-

EXISTING STAFF TOILET

-

EXIST. ELECTRICAL

-

EXISTING JANITOR

-

DETENTION CORRIDOR

103

SEARCH

104

INTERVIEW

105

LAN/TELCO

106

STORAGE

107

TOILET

109

.

GFI

.

GFI

.

GFI .

GFI

.

GFI

E2

NEMA 14-20

.

GFI

.

GFI.

M

E1

E1

.

M

E5

.

PRE-PROCESSING PASSENGERWAITING

108

PP2

-17PP2

.

GFI

-4PP2

-3PP2

-2PP2

E6

EF-2

SS-1

.

M

-1PP5

-7PP2

-8PP2

-11PP2

-10PP2

-12PP2

-13PP2

-14PP2

-2PP5

-1PP2

.

GFI

.

MCU-1-4,6PP5

.

MEF-1

-3PP5

PP5

-5PP2

E3E4

E7

E7

-6PP2

-15PP2

E1

E8

E5

-9PP2

E9

E9

-19PP2

S18S19

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:1

9 P

M

E4.0

AKP

09/25/2017

1508/XACO16

WRS

PO

WE

R -

FIR

ST

FL

OO

R

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

1/4" = 1'-0"1

POWER - FIRST FLOOR

GENERAL NOTES (POWER):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL ANDCEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, ASINDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3)BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BEPROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATEDNEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING.IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITHTHOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENTCARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT ASREQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITSAS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A COMMON NEUTRALCONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEARADHESIVE LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES,ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CAREAREAS. MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUITNUMBER.

D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCHAS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM SHALL BEMARKED IN ACCORDANCE WITH NEC 406.3(E).

E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTSSHALL BE COORDINATED WITH MECHANICAL AND PLUMBINGCONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE ISMAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIREDCLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESEAREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENTNAMEPLATES OR ACCESS PANELS OR THROUGHACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHERTRADES.

TAGGED NOTES

E1 EXISTING ROOM TO REMAIN. MAINTAIN POWER TO EQUIPMENT LOCATED ATTHESE LOCATIONS.

E2 DISCONNECT TO BE PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATEINSTALLATION WITH MECHANICAL CONTRACTOR.

E3 RELOCATED PANEL PP2. REWORK FEEDER TO LOCATION SHOWN.

E4 RELOCATED PANEL PP5. REWORK FEEDER TO LOCATION SHOWN.

E5 PROVIDE NEW RECESSED FLOOR BOX WITH QUAD RECEPTACLE AT PODIUM.

E6 RECEPTACLE DEDICATED FOR MICROWAVE ONLY.

E7 RECEPTACLES AT LOCATIONS SHOWN ARE TO BE TAMPER PROOF(INSTITUTIONAL) TYPE.

E8 POWER FOR TRANSACTION WINDOW.

E9 POWER CONNECT PROVIDED WITH OUTDOOR UNIT.

S18 ALL CCTV SIGNALS TO HOMERUN TO LAN/TELCO ROOM. SECURITY VENDOR TOPROVIDE NETWORK VIDEO RECORDER WITH 45 DAY BACKUP. CBP OFFICE TOHAVE SELECT REVIEW/MONITOR PERMISSIONS AND CBP TO HAVEADMINISTRATIVE PERMISSIONS.

S19 PROVIDE LOCAL VIDEO MONITORING AND CONTROL STATION. COORDINATEWITH SECURITY VENDOR AND CBP.

TRUENORTH

PLANNORTH

No. Description Date

DN

DN

F

S

CC

CC

CR

CC

CC

CC CC

PB

PB

F

F

F

V

V

V

SD

SD

SD

SD

F

SD

SD

WAP

SD

SD

S

SD

SD

WAP

SD

SD

FF

CC

CR

CC

CC

CC

CC

CR

PB

CR PB

MD

MD

MD

MK

MD

ES

M

MK

MD

DA

DA

DA

A

CR

RR

RR

CR

ES

CC

MDMD

MDMD

M

PA PA

IM

MD

PA

M

CR

IR

MD

ES

ES

CR

CR

KP

PE

CR

ES

CBP GENERAL OFFICE

101

PROCESSING

110

STORAGE

107

LAN/TELCO

106 INTERVIEW

105

SEARCH

104

TOILET

109

PRE-PROCESSING PASSENGERWAITING

108

EXISTING PUBLIC TOILET

-

EXIT VESTIBULE

111

EXIST. ELECTRICAL

-

EXISTING JANITOR

-

EXISTING STAFF TOILET

-

.

2D

S1

.

LCD

S3

S2

DETENTION CORRIDOR

103

.

2D

.

2D

S4

.

2D

.

2D

.

2D

S5

S9

S4

S2

S8

S11

4D

S10

S7

S6

m

m

.

2D

.

2D

m

S14

S16

S19

S12

S17

S13

.

2D

S16

S7

S20

S21

ACPS22

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:1

9 P

M

E5.0

AKP

09/25/2017

1508/XACO16

WRS

SY

ST

EM

S -

FIR

ST

FL

OO

R

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S

1/4" = 1'-0"1

SYSTEMS - FIRST FLOOR

GENERAL NOTES (SYSTEMS):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, ANDCASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILINGMOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATEDON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITSPER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH ADEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORSSHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORSARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTORSHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C.MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITSSHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVELABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVEEMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARKINSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.

D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND SHEET)AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF EACH SYSTEM.

E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO THENEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS). REFER TOCABLING PATH INSTALLATION DETAIL FOR ADDITIONAL REQUIREMENTS.

F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT BLUEFOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH. PROVIDE PULLSTRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM CABLING INSTALLATION.

TAGGED NOTES

S1 FIXED CCTV INTERVIEW CAMERA WITH WIDE-ANGLE LENS. HOMERUN NETWORKCABLE TO LAN/TELCO ROOM 106 RACK. CAMERA TO INCLUDE MICROPHONE WITHAUDIO RECORDING.

S2 RECESSED DURESS ALARM BUTTON CONCEALED UNDER TABLE. CONNECT TOCCC AND/OR OTHER DBP DESIGNATED LOCATION

S3 INTERVIEW CAMERA MONITOR.

S4 SMOKE DETECTOR IN SEARCH AND INTERVIEW ROOM TO HAVE INSTITUTIONALRATED COVER (SHROUD).

S5 LAN/TELCO ROOM IS TO BE SHIELDED. COORDINATE ROOM PENETRATION ANDPROVIDE UNIQUE GROUND.

S6 PROVIDE AUDIO/VISUAL DURESS ALARM INDICATOR OVER DOOR.

S7 DETENTION GRADE MICROPHONE, CEILING MOUNTED TO BE PROVIDED BYSECURITY VENDOR. PROVIDE SINGLE GANG BACKBOX WITH 3/4" CONDUIT TOSECURITY HEADEND. AUDIO/VIDEO TO BE RECORDED VIA NETWORKED VIDEORECORDER.

S8 NEW RECESS FLOOR BOX TO INCLUDE (4) DATA CONNECTIONS ANDMICROPHONE AND CAMERA SYSTEM CABLING WITH INTERFACE TO SECURITYSYSTEM.

S9 REUSE EXISTING ACCESS CONTROL KEYPAD AT LOCATION SHOWN.

S10 DOOR TO HAVE REMOTE RELEASE FROM PROCESSING 110 PODIUM. SEE NOTES11.

S11 PROVIDE REMOTE RELEASE CARD READER FOR EXIT VESTIBULE 111 DOOR.

S12 ACCESS CONTROL SYSTEM IS TO BE EXPANSION OF EXISTING FACILITY SYSTEM.ACCESS CONTROL TO BE BY SECURITY VENDOR (MATRIX SYSTEMS).COORDINATE ALL RACEWAY, POWER, CABLING INSTALLATION, AND OPERATIONWITH VENDOR.

S13 KEYPAD TO DISABLE LAN/TELCO INTRUSION DEVICES ONLY. CODE ENTEREDSHUTS OFF MOTION DETECTION AND DOOR ALARMS WITHIN A 60 SECONDWINDOW.

S14 SECURITY SYSTEM IS TO BE MONITORED BY AIRPORT SECURITY. COORDINATEMONITORING METHOD WITH CBP AND SEGREGATE ALARMS AND DEVICESACCORDINGLY.

S16 REMOTE INTERCOM STATION WITH NETWORK CONNECTION. CONNECT TOMASTER INTERCOM LOCATED IN CBP GENERAL OFFICE 101.

S17 INTERCOM MASTER STATION TO BE LOCATED NEAR TRANSACTION WINDOW.

S19 PROVIDE LOCAL VIDEO MONITORING AND CONTROL STATION. COORDINATEWITH SECURITY VENDOR AND CBP.

S20 PROVIDE REMOTE RELEASE CARD READER FOR DOOR 108.

S21 WIRE MESH NEEDS TO ALSO BE PLACED ON THE CEILING IN THE SEARCH ROOM.

S22 ACCESS CONTROL PANEL

TRUENORTH

PLANNORTH

No. Description Date

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION MODEL LUMENS WATTAGE VOLTAGE

FIXTURE DESCRIPTION MANUFACTURER AND SERIES MODELTRUE LUMEN

OUTPUTTOTAL WATTAGE VOLTAGE MOUNT ORDERING INFORMATION

R1

RECESSED 2' X 4' LED VOLUMETRIC TROFFER WITH CURVED, LINEAR LENS.2-3/8” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL

REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACTRESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR WITH POLYMER

LIGHT DIFFUSING FILM, INTEGRAL 89% EFFICIENT LOW INRUSH MULTI-VOLT0-10V DIMMABLE DRIVER, 4000 KELVIN 82 CRI LED ARRAY PRODUCING 4800

DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS

LITHONIA 2BLT4 OR EQUAL 5,117 45 120V CEIL. 2BLT4-48L-ADSM-LP840

R1E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2BLT4 OR EQUAL 5,117 45 120V CEIL. 2BLT4-48L-ADSM-LP840

R2

RECESSED 2' X 4' LED VOLUMETRIC TROFFER WITH CURVED, LINEAR LENS.2-3/8” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL

REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACTRESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR WITH POLYMER

LIGHT DIFFUSING FILM, INTEGRAL 89% EFFICIENT LOW INRUSH MULTI-VOLT0-10V DIMMABLE DRIVER, 4000 KELVIN 82 CRI LED ARRAY PRODUCING 6000

DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS

LITHONIA 2BLT4 OR EQUAL 6,163.60 52.95 120V CEIL. 2BLT4-60L-ADSM-LP840

R2E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2BLT4 OR EQUAL 6,163.60 52.95 120V CEIL. 2BLT4-60L-ADSM-LP840

VR1

SURFACE MOUNTED 2' X 4' LED VANDAL RESISTANT, DAMP LOCATION LEDTROFFER. 20-GAUGE COLD ROLLED STEEL DOOR FRAME,

TAMPER-RESISTANT FASTNERS AND POLYCARBONATE LENS. 18 GUAGESWING ARMS. UNPAINTED GALVANIZED STEEL. 4000KELVIN, 80 CRI WITH 5000DELIEVERED LUMENS. LONG LIFE LED'S, HIGH-EFFICIENCY DRIVERS. LUMEN

MAINTENANCE OF L80/60,000 HOURS, L70 RATED LIFE OF 100,000 HOURS.

LITHONIA 2VRTL OR EQUAL 4,388.60 38.70 120V CEIL. 2VRTL-XX-L48-5000LM-APFL-40K-XX-APFL-XX-40K-80CRI

VR1E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2VRTL OR EQUAL 4,388.60 38.70 120V CEIL. 2VRTL-XX-L48-5000LM-APFL-40K-XX-APFL-XX-40K-80CRI

VR2

SURFACE MOUNTED 2' X 4' LED VANDAL RESISTANT, DAMP LOCATION LEDTROFFER. 20-GAUGE COLD ROLLED STEEL DOOR FRAME,

TAMPER-RESISTANT FASTNERS AND POLYCARBONATE LENS. 18 GUAGESWING ARMS. UNPAINTED GALVANIZED STEEL. 4000 KELVIN, 80 CRI WITH 7000

DELIVERED LUMENS. LONG LIFE LED'S, HIGH-EFFICIENCY DRIVERS. LUMENMAINTENANCE OF L80/60,000 HOURS, L70 RATED LIFE OF 100,000 HOURS.

LITHONIA 2VRTL OR EQUAL 6,449.30 58.50 120V CEIL. 2VRTL-XX-L48-7000LM-APFL-40K-XX-APFL-XX-40K-80CRI

VR2E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA 2VRTL OR EQUAL 6,449.30 58.50 120V CEIL. 2VRTL-XX-L48-7000LM-APFL-40K-XX-APFL-XX-40K-80CRI

I1

SUSPENDED MOUNTED LED STRIP LIGHT WITH 20 GAUGE STEEL HOUSING,HIGH GLOSS BAKED WHITE ENAMEL FINISH, REPLACEABLE MEDIUM DIFFUSE

ACRYLIC LENS, HIGH OUTPUT LEDS ON TWO LAYER CIRCUIT BOARD,ELECTRONIC LED DRIVER. 5000 KELVIN, 90 CRI WITH 2000 DELIVERED

LUMENS, 80 CRI, 85% OUTPUT AT 44,000 HOURS, CSA LISTED FOR DAMPLOCATIONS.

LITHONIA ZL2N OR EQUAL 2,000.00 32.40 120V STRIP ZL2N L48 2000LM MDD MVOLT 40K 90CRI WH

I1E SAME AS PARENT TYPE. INCLUDE BATTERY PACK FOR EMERGENCY LIGHTING. LITHONIA ZL2N OR EQUAL 2,000.00 32.40 120V STRIP ZL2N L48 2000LM MDD MVOLT 40K 90CRI WH

I2

SUSPENDED MOUNTED LED STRIP LIGHT WITH 20 GAUGE STEEL HOUSING,HIGH GLOSS BAKED WHITE ENAMEL FINISH, REPLACEABLE MEDIUM DIFFUSE

ACRYLIC LENS, HIGH OUTPUT LEDS ON TWO LAYER CIRCUIT BOARD,ELECTRONIC LED DRIVER. 5000 KELVIN, 90 CRI WITH 3000 DELIVERED

LUMENS, 80 CRI, 85% OUTPUT AT 44,000 HOURS, CSA LISTED FOR DAMPLOCATIONS.

LITHONIA ZL2N OR EQUAL 2,894.80 33.20 120V STRIP ZL2N L48 3000LM MDD MVOLT 40K 90CRI WH

X1

CEILING MOUNTED, TWIN HEAD, INTERIOR EGREESS LIGHT. CONSTRUCTEDOF UV-STABILIZED THERMOPLASTIC WHICH IS CORROSION-RESISTANT WITHA UL94V-0 FLAME RATING. 12 SERIES PARALLEL WHITE LED'S PER HEAD WITH

A 10 YEAR LED LAMP LIFE.

LITHONIA ECR LED M6 OR EQUALOSHA LUMENSTANDARD

1.50 277V CEIL. ECR-LED-HO-M6-78423184561

X2

CEILING MOUNTED VANDAL RESISTANT EXIST SIGN. CONTRUCTED OF CASTALUMINUM - RUGGED, LOW-PROFILE HOUSING IS .250" TO .525" THICK.

CONTAINS UC-STABLE POLY CARBONATE COVER THAT IS .130" THICK. COVERIS SECURED WITH FOUR STAINLESS STEEL, TORX T20 TAMPERPROOF SCREW

WITH CENTER PIN. 10 YEAR LED LAMP LIFE.

LITHONIA LV OR EQUALOSHA LUMENSTANDARD

2.30 277V CEIL. LV-S-W-1-R-120/277

U1THIN PROFILE BACKLIT LED SIGN. IT MEASURES 11mm THICK AND REQUIRESNO ADDITIONAL POWER SUPPLY OR TRANSFORMER AND FITS TO EXISTING

MAINS POWER SINGLE OR TWIN SOCKET BACKBOXES.LASERMET SLIM JIM OR EQUAL

OSHA LUMENSTANDARD

4.60 277V WALL LEDS-SJ-R-RIU

NOTES:1. LAMP AND BALLAST COMBINATION TO HAVE FIVE YEAR WARRANTY FROM THE FIXTURE MANUFACTURER. FURNISH WITH WARRANTY CERTIFICATES.

2. FIXTURE TO BE CIRCUITED TO NEAREST UNSWITCHED EMERGENCY POWER CIRCUIT.* ALL FIXTURES SHALL BE PRE-LAMPED FROM THE

MANUFACTURER** POINT-BY-POINT CALCULATIONS FOR THE CLASSROOMS, MEDIA CENTER, CAFETERIA, GYMNASIUM AND SITE ARE REQUIRED. MANUFACTURERS WISHING TO BID THIS PROJECT MUST SUBMIT ORIGINAL FIXTURE BROCHURES, AND ELECTRONIC FILE (VISUAL OR AGI32) POINT-BY-POINT

CALCULATIONS, TEN (10) DAYS PRIOR TO BID FOR WRITTEN APPROVAL.

COPYRIGHT © 2017SHERMAN CARTER BARNHARTARCHITECTS, PLLC

JOB NO.

DATE

DRAWN

CHECKED

REVISIONS

SHEET

LE

XIN

GT

ON

, K

Y

10/1

9/2

017 2

:39:2

0 P

M

E6.0

AKP

09/25/2017

1508/XACO16

WRS

PA

NE

L/F

IXT

UR

E S

CH

ED

UL

ES

BL

UE

GR

AS

S A

IRP

OR

TC

US

TO

MS

FA

CIL

ITY

RE

NO

VA

TIO

NS

1508/X

AC

O16

BLU

EG

RA

SS

AIR

PO

RT

CU

ST

OM

S F

AC

ILIT

Y R

EN

OV

AT

ION

S No. Description Date

CIRCUIT #15 TO BE A GFI BREAKER.

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

TOTAL ESTIMATED DEMAND CURRENT: 29 A

REC 8820 VA 100.00% 8820 VA TOTAL CONNECTED CURRENT: 29 A

LTNG 1512 VA 100.00% 1512 VA TOTAL ESTIMATED DEMAND: 10532 VA

EQUIP 200 VA 100.00% 200 VA TOTAL CONNECTED LOAD: 10532 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 37 A 28 A 24 A

TOTAL LOAD (kVA): 4.3 kVA 3.3 kVA 2.9 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

REC PROCESSING FLOOR BOX 12 12 3/4" 20 1 19 0.4 20

REC 109, DRINKING FOUNTAINS 12 12 3/4" 20 1 17 0.5 0.5 18 1 20 3/4" 12 12 LTNG 101, 103, 104, 105

GFI BREAKER 12 12 3/4" 20 1 15 0.5 1.0 16 1 20 3/4" 12 12 LTNG 106, 107, 108, 109, 110

REC CBP GEN OFFICE 101 12 12 3/4" 20 1 13 0.7 0.7 14 1 20 3/4" 12 12 REC 101, 111

REC LAN/TELCO 106 12 12 3/4" 20 1 11 0.7 0.4 12 1 20 3/4" 12 12 REC 103, 105

REC 107, 108 12 12 3/4" 20 1 9 0.9 0.5 10 1 20 3/4" 12 12 REC LAN/TELCO 106

REC PROCESSING 110 12 12 3/4" 20 1 7 0.7 0.5 8 1 20 3/4" 12 12 REC PROCESSING 110

REC PROCESSING FLOOR BOX 12 12 3/4" 20 1 5 0.4 0.4 6 1 20 3/4" 12 12 REC DED TV 101

REC CBP GEN OFFICE 101 12 12 3/4" 20 1 3 0.2 0.2 4 1 20 3/4" 12 12 REC DED MICROWAVE 101

REC PRE-PROCESSING 108 12 12 3/4" 20 1 1 1.1 0.2 2 1 20 3/4" 12 12 REC 101

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM:

VOLTAGE: 208Y/120V,3P,4W SPD: LOCATION: STORAGE 107

PANEL: PP2 MAINS TYPE: AIC RATING:

PANELBOARD AND WIRING SCHEDULE kAIC VALUE:

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

TOTAL ESTIMATED DEMAND CURRENT: 8 A

TOTAL CONNECTED CURRENT: 8 A

TOTAL ESTIMATED DEMAND: 3000 VA

EQUIP 3000 VA 100.00% 3000 VA TOTAL CONNECTED LOAD: 3000 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 13 A 9 A 4 A

TOTAL LOAD (kVA): 1.5 kVA 1.0 kVA 0.5 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 0.5 6

EQUIP EF-1 108 12 12 3/4" 20 1 3 0.5 0.5 42 15 3/4" 12 12 EQUIP CU-1

EQUIP EF-2 RM 109 12 12 3/4" 20 1 1 0.5 1.0 2 1 20 3/4" 12 12 EQUIP DISPOSAL 101

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM:

VOLTAGE: 208Y/120V,3P,4W SPD: LOCATION: STORAGE 107

PANEL: PP5 MAINS TYPE: AIC RATING:

PANELBOARD AND WIRING SCHEDULE kAIC VALUE: