blackout avoidance & undervoltage load shedding
TRANSCRIPT
BLACKOUT AVOIDANCE &
UNDERVOLTAGE LOAD SHEDDING
BLACKOUT AVOIDANCE &
UNDERVOLTAGE LOAD SHEDDING
Chuck MozinaConsultant
Beckwith Electric
Chuck MozinaConsultant
Beckwith Electric
BLACKOUTSHow and why they occur
Why voltage rather than frequency is the leading edge indicator of system collapse
How blackout conditions effect generators and generator protection
Undervoltage load shedding
Blackout Avoidance
RECENT BLACKOUTS
2003 - East Coast Blackout2003 - Italian Blackout2002 - Swedish Blackout1997 - PJM Disturbance1996 - West Coast Blackout1995 - PECO Disturbance1987 - City of Memphis
Blackout Avoidance
Root Cause of Recent Blackouts
VOLTAGE COLLAPSE – WHY?
Today, major generation sources are remote from load centers. This was NOT the case 35 years ago.
This makes the power system very reliant on transmission system to transport power to load centers.
Blackout Avoidance
VOLTAGE COLLAPSE – WHY?
Purchase power from remote sources to save $$$.
New generation built remotely from load centers.
Little new transmission being built.
Utility loads are increasingly made up of air conditioning motors susceptible to stall conditions due to transmission system faults.
Root Cause of Recent Blackouts
Blackout Avoidance
As lines trip between remote generation and load center, the reactance increases.
This increases the reactive (VAR) losses-reducing the voltage at the load center.
The voltage phase angle between thegenerators at the load center andremote generators also increase.
REMOTEGENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
How Voltage Collapses Occur
Blackout Avoidance
POWER TRANSFEREXAMPLE
POWER TRANSFEREXAMPLE
Blackout Avoidance
Real Power (MW) Flow Example
SYSTEMA
SYSTEMB SYSTEM
C
Eg O
Es O
POWERFLOW
Blackout Avoidance
Pe = Eg Es Sin ( 0g- 0s ) X
Where: Eg = Voltage at the Load Center Generation Es = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0g = Votage Angle and Local Generation
0s = Voltage Angle at Remote Generation
POWER TRANSFER EQUATION
Where: Es = Voltage at the Load Center
Eg = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and Remote Generation
0s = Voltage Angle and Local Generation
0g = Voltage Angle at Remote Generation
Pe = Eg Es Sin ( 0g- 0s ) X
Where: Eg = Voltage at the Load Center Generation Es = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0g = Voltage Angle and Local Generation
0s = Voltage Angle at Remote Generation
POWER TRANSFER EQUATION
SYSTEMA
Load = 5000 MWGEN. =5000 MW
SYSTEMB
Load = 5000 MWGen. = 5000 MW
SYSTEMC
Load = 5000 MWGen. = 5000 MW
Eg O
Es O
POWERFLOW - 0 MWTRANSFER
Real Power (MW) Flow Example
Blackout Avoidance
Where: Es = Voltage at the Load Center
Eg = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and Remote Generation
0s = Voltage Angle and Local Generation
0g = Voltage Angle at Remote Generation
Pe = Eg Es Sin ( 0g- 0s ) X
Where: Eg = Voltage at the Load Center Generation Es = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0g = Voltage Angle and Local Generation
0s = Voltage Angle at Remote Generation
POWER TRANSFER EQUATION
Real Power (MW) Flow Example
SYSTEMA
Load = 5000 MWGEN. = 7000 MW
SYSTEMB
Load = 5000 MWGen. = 5000 MW
SYSTEMC
Load = 5000 MWGen. = 3000 MW
Eg O
Es O
POWERFLOW - 2000 MW
TRANSFER
Blackout Avoidance
Where: Es = Voltage at the Load Center
Eg = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and Remote Generation
0s = Voltage Angle and Local Generation
0g = Voltage Angle at Remote Generation
SYSTEMA
SYSTEMB SYSTEM
C
Eg O
Es O
REACTIVEPOWER
FLOW SMALL
1. To make reactive power flowyou need to have a differencein voltage magnitude betweenEg and Es.
2. Voltage on a power systemcan only be varied +/- 5%which is not enough differenceto result in a significant VARSflow.
3. Thus VARS cannot betransmitted over longdistances and must begenerated locally near theload.
Reactive Power (Mvars) Flow
Blackout Avoidance
VAr Support must be provided at the load center.
Two major sources of VAr support:
Capacitor Banks – Double-Edge Sword. Vars go down with the square of voltage.
Generators/ Synch. Condensers – A dynamic source of Vars. Can adjust VAr output rapidly during contingencies.
Sources of Reactive (Var) Support
Blackout Avoidance
LOAD RESPONSE TO
LOW VOLTAGE
LOAD RESPONSE TO
LOW VOLTAGE
Blackout Avoidance
How Load Responds to Low VoltageBasic Power System
RemoteGeneration
Transmission System Load Center
ResistiveLoad
MotorLoad
VARSupport
LocalGeneration
Ps PL
QLVL
Blackout Avoidance
Resistive load current decreases as voltage goes down Helping the system.
Motor loads are constant KVA devices and increase their load current as voltage decreases-Hurts the system.
During “Heat Storm” conditions, most load is motor load making blackout more likely.
How Load Responds to Low Voltage
Blackout Avoidance
Example of Voltage Recovery From a Transmission Fault- Rapid Voltage Collapse
R e s id e n tia l V o lta g e R e co ve ry fo r P h o e n ix A re a In c id e n t o n Ju ly 2 9 , 1 9 9 5
Blackout Avoidance
RECENT BLACKOUTS REVISITED
2003 - East Coast Blackout2003 - Italian Blackout2002 - Swedish Blackout1997 - PJM Disturbance*1996 - West Coast Blackout1995 - PECO Disturbance*1987 - City of Memphis*
* Rapid Voltage Collapse
Blackout Avoidance
POWER SYSTEM INSTABILITY
POWER SYSTEM INSTABILITY
Blackout Avoidance
POWER SYSTEM INSTABILITIES
Four Types of Instability:Voltage* Steady State *Transient Dynamic
*Involved in Recent Blackouts
Blackout Avoidance
REMOTEGENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
Eg O Es O
POWER FLOW
Voltage Collapse Scenario
Blackout Avoidance
REMOTEGENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
Eg O Es O
POWER FLOW
Voltage Collapse Scenario
Blackout Avoidance
0 1800
Max.Power
TransferAll Lines in Service
Line 1Tripped
Line 2Tripped
Pe
Pmax = Eg Es X
0g - 0s90o0 1800
Max.Power
TransferAll Lines in Service
Line 1Tripped
Line 2Tripped
Pe
Pmax = Eg Es X
0g - 0s90o
Pe = Eg Es Sin ( 0g- 0s ) X
POWER TRANSFER EQUATION REMOTEGENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
Eg Og Es Os
POWER FLOW
0 1800
Max.Power
TransferAll Lines in Service
Line 1Tripped
Line 2Tripped
Pe
Pmax = Eg Es X
0g - 0s90o
Steady State Instability
Blackout Avoidance
Generator
G
GSU SystemReactance
VXd XT
XS
V2 __ 1____ + 1 2 XT + XS Xd
Per Unit MW
Per UnitMVAR
V2 ___1___ 12 XT + XS Xd
a) MW - MVAR PER UNIT PLOT
X
R
Xd + XT + XS 2
XT + XS
Xd - XT + XS 2
b) R-X DIAGRAM PLOT
Xd
Steady State Instability
Blackout Avoidance
GENERATOR RESPONDSTO BLACKOUTCONDITIONS
GENERATOR RESPONDSTO BLACKOUTCONDITIONS
Blackout Avoidance
Gen.
AVR ExcitationTransformer
Generator Step-upTransformer
CT VTGenerator
Field
StaticExciter
Generator Excitation & AVR Control
Blackout Avoidance
The Generator AVR (Automatic Voltage Regulator) Controls Field Current into the Rotor Which in Turn Controls Terminal Voltage and VAr Output/Input.
G
Reactive Powerinto System
Reactive Powerinto Generator
Real Powerinto System
+MVAR
Overexcited
Underexcited
0
-MVAR
G
UnderExcitation
Limiter(URL)
+ MW
MW
MVARS
OverexcitationLimiter (OEL)
RotorWindingLimited
StatorWindingLimited
Stator EndIron Limited
MW
MVARSystem
SystemNormal OverexcitedOperation
UnderexcitedOperation
How Generators Provide Vars to the System
Blackout Avoidance
DEPENDS ON THE MANUFACTURER:
Some Limiters Change as the Square of the Voltage – 90% Voltage Results in 81% of Setting
Some Proportional to Voltage – 90% Voltage result in 90% Setting
Some Do Not Change with Voltage at all
AVR Limiters Response During Low Voltage
Blackout Avoidance
0 1800
Max.Power
TransferAll Lines in Service
Breakers 1 and 2Tripped
PM = Pe
Pmax = Eg Es X
0g - 0s90o
A2
0C
A1
Transient Instability
Blackout Avoidance
Typical Out-of-Step Impedance LOCI
Blackout Avoidance
Occurs when fast acting AVR control amplifies rather than damps small MW oscillations.
Occurs when generators are remote from load
Solution is AVR Power System Stabilizers(PSS) – Low Freq. Filter
Required by WECC in the Western USA for generators larger than 30 MVA
Dynamic Instability
Blackout Avoidance
GENERATOR PROTECTION RESPOND TO BLACKOUT
CONDITIONS
GENERATOR PROTECTION RESPOND TO BLACKOUT
CONDITIONS
Blackout Avoidance
Loss of Field (40)
Overexcitation (24)
Overexcitation (24) System Backup (21 & 51V)
Under Frequency (81)
Out of Step Protection (78)
Key Generator Protection Functions Effected by Major System Disturbances
Blackout Avoidance
Generator Protection Effected by Major System Disturbances
Loss of Field (40) – Must be Coordinated with AVR Control, Steady State Stability Limit and Secure Under Low Voltage.
Overexcitation (24) - Coordinated with AVR Control.
System Backup (21 & 51V) – Secure on Stable Power Swings and System Low Voltage. Must be Coordinated with TransmissionProtection.
Blackout Avoidance
Under Frequency (81) – Coordinated with System Load Shedding.
Out of Step Protection (78) – Set to trip the Generator if it Losses Synchronism.
Generator Protection Effected by Major System Disturbances
Blackout Avoidance
+X
-X
+R-R
- Xd’ 2
Xd
GeneratorCapability
Under ExcitationLimiter (UEL)
Heavy Load Light Load
Impedance LocusDuring Loss of Field
1.0 pu
Steady StateStability Limit
Zone 1
Zone 2
Loss of Field (40) – Must be Coordinated with AVR Control, Steady State Stability Limit and Secure Under Low Voltage.
Blackout Avoidance
Transformation From Mw-Mvar to R-X Plot
Blackout Avoidance
G
Reactive Powerinto System
Reactive Powerinto Generator
Real Powerinto System
+MVAR
Overexcited
Underexcited
0
-MVAR
G
UnderExcitation
Limiter(URL)
+ MW
MW
MVARS
OverexcitationLimiter (OEL)
RotorWindingLimited
StatorWindingLimited
Stator EndIron Limited
Steady StateStability Limit
MW
MVARSystem
SystemNormal OverexcitedOperation
UnderexcitedOperation
Overexcitation (24)-Coordinated with AVR Control
Blackout Avoidance
Generator (IEEE/ANSI C-50.12 &13)1.05pu V/Hz on Gen. Base
Transformers (IEEE/ANSI C-57.12 )1.05pu V/Hz loaded at output1.10pu V/Hz unloaded
Overexcitation Gen./Trans. Capability
Blackout Avoidance
Figure #4C
Overexcitation Operating Limits
Blackout Avoidance
Dual Set-point Definite Time1.18pu V/Hz – 2-6 Sec. Delay1.10 pu V/Hz – 45-60 Sec. Delay
Inverse Time Curve1.10pu V/Hz Pickup with CurveSelection to Match Gen./Trans V/Hz Capability Curve
Typical V/Hz 24 Relay Settings
Blackout Avoidance
J X
R
Z2
Z1
RPFA
Max.TorqueAngle
GeneratorCapability
Curve
Z2 Reach at 50 to 67% ofGenerator Capability Curve
Z2 Reach 120% of Longest Line butMust be Less than 80 to 90%
of Capability Curve
System Backup (21 & 51V) – Secure on Stable Power Swings and System Low Voltage. Must be Coordinated with Transmission Protection.
Blackout Avoidance
J X
R
Z2
Z1
Max.TorqueAngle
GeneratorCapability
Curve
Z2 Reach at 50 to 67% ofGenerator Capability Curve
Z2 Reach 120% of Longest Line butMust be Less than 80 to 90%
of Capability Curve
Z3 out of step blocking
Load EncroachmentBlocking
RPFA
Z3
Security Enhancements for Generator Distance Backup Protection
Blackout Avoidance
Voltage Controlled Overcurrent Relays- Voltage control set below emergency system
operating voltage.- Current pickup set at 30-40% of full load (Xd).- Time delay set to coordinate with transmission
backup.
Voltage Restrained Overcurrent Relays- Current pickup varies proportional to voltage and set
150% of gen. Rating at gen. Rated voltage.- Time delay set to coordinate with transmission
backup.
Generator Voltage Overcurrent (51V) Backup
Blackout Avoidance
Coordinate Under Frequency Tripping of Generator With North American Electric Reliability Council (NERC) System Load Shedding Regions – WECC, ECAR, ERCOT, PJM, Others.
Hydro Generators not affected by Under Frequency
Gas Turbines Controls Run Back Mw Output When Frequency Drops
Under Frequency (81) – Coordinated with System Load Shedding
Blackout Avoidance
Out of Step Protection (78) – Set to trip the Generator if it Losses Synchronism
Blackout Avoidance
Undervoltage Condition Not Itself Harmful To Synchronous Generators – V/Hz is a Low Limit.
Auxiliary System is Effected By Low Voltage –Auxiliary Motor Tripping Can Shut Down Gens.
U.S. Nuclear Plants Have Second Level Voltage Separation Relays on Auxiliary System.
Automatic Generator Control (AGC) can Cause Problems when the Power System Breaks-up into Islands.
Undervoltage Power Plant Trippings Brought About By System Var Deficits
Blackout Avoidance
SYSTEM UNDERVOLTAGE LOAD SHEDDING
(UVLS)
SYSTEM UNDERVOLTAGE LOAD SHEDDING
(UVLS)
Blackout Avoidance
Utility Undervoltage Load Shedding (UVLS)
ATTEMPT TO BALANCE MVAR LOAD WITH MVAR SOURCES BY SHEDDING LOAD.
TWO TYPES OF UVLS SCHEMES:
Decentralized - Relays Measure Voltage at load to be shed.
Centralized – Relays Measure Voltage at Key locations. Voltage transmitted to Central Location and combined with other System Information. Schemes Called SPS or Wide Area Protection.
Blackout Avoidance
Status Of Utility Undervoltage Load Shedding (UVLS)
NERC- UVLS Not Mandatory- Recognized as a Cost-effective Method to Address
Voltage Collapse.- Allowed Region to Establish Policy
WECC- Most Aggressive in UVLS- Established UVLS Guidelines
Blackout Avoidance
North American Electric Reliability Council (NERC) Regional Areas
Blackout Avoidance
UVLS AT Utilities
Centralized Decentralized- BC Hydro - Puget Sound- Hydro Quebec - First Energy- Entergy - TXU- Public Service of NewMexico
- PG&E
Blackout Avoidance
Blackout Avoidance
DESIGNING A SECURE UVLS
SCHEME
DESIGNING A SECURE UVLS
SCHEME
Selection of Voltage Relays for UVLS
Measure all Three Voltage or Positive Sequence Voltage.
Use Low Voltage Cutoff.
Consider Negative Sequence Blocking.
Start Timer only if Voltage is Within Window.
Use Relay with High Reset Ratio.
Digital Voltage Relays are ideal for This Application.
Blackout Avoidance
Three-Phase UVLS Logic
27
27B
47B
Va ≤Vb
Vc
Setpoint #1
≤≤
Setpoint #1
Setpoint #1
AND
AdjustableTimer
UndervoltageTrip
AND
SINGLE PHASEUNDERVOLTAGE
Va ≤VbVc
Setpoint #2
≤≤
Setpoint #2
Setpoint #2
OR xUNDERVOLTAGE
BOCK
V2 Setpoint #3≥ xNEGATIVE
SEQUENCEOVERVOLTAGE
BLOCK
Blackout Avoidance
Positive Sequence UVLS LogicV1 = 1/3 ( Va + aVb +a2Vc )
Where: Va,Vb,Vc are line-to-neutral voltages
a = 1l120o
a2 = 1l240o
Balanced Conditions:V1=Va=Vb=Vc.
27
27B
47B
V1 ≤Setpoint #1
AdjustableTimer
UndervoltageTrip
AND
POSITIVESEQUENCE
UNDERVOLTAGE
Va≤VbVc
Setpoint #2
≤≤
Setpoint #2
Setpoint #2
OR xUNDERVOLTAGE
BOCK
V2 Setpoint #3≥ xNEGATIVESEQUENCE
OVERVOLTAGEBLOCK
Blackout Avoidance
Point of Voltage Measurement
UTILITY TRANSMISSIONSYSTEM
27
81
A C
Trip Selected Circuits(A-D)
Typical DistributionSubstation Transformer with
LTC
B D
27 = Undervoltage Relay81= Underfrequency Relay
Blackout Avoidance
UVLS SETTING CONSIDERATIONS
UVLS SETTING CONSIDERATIONS
Blackout Avoidance
UVLS Setting Considerations
Relay Engineers Must Work Closely With System Planning Engineers to Design UVLS.
Planning Engineers Have the Load Flow Data Required to Determine the Voltage Measurement Locations and Amount of Load to Shed.
They also develop the P-V (Nose Curve) that will determine the Voltage Relay Pickup Setting.
Time Delay for UVLS are Typically in the 2-10 Sec. Range – not in Cycles Range for UFLS.
Blackout Avoidance
Undervoltage Relay Pickup
MW LOAD
VOLTAGE
VcollapseSetting Margin
Relay and VT Accuracy Band
V settingAllowableOperating Area
Operating Margin
Blackout Avoidance
Coordinating UVLS Relay Pickup
Blackout Avoidance
NEW M-3401 BECKWITH LOAD SHEDDING RELAY
NEW M-3401 BECKWITH LOAD SHEDDING RELAY
Blackout Avoidance
NEW M-3401 RELAY
Blackout Avoidance
Blackout Avoidance
NEW M-3401 RELAY
M-3401 Protective Functions
Blackout Avoidance
4-Step Phase Undervoltage (27) Protection, single-phase and positive sequence
4-Step Phase Undervoltage, selectable as single phase or positive sequence responding, with Negative sequence overvoltage and single phase undervoltage supervision
Phase Overvoltage (59) Protection
Four-Step Over/Under Frequency (81) protection
Rate of Change of Frequency (81R) protection
IPSlogicTM takes the contact INPUT status and function status and generates OUTPUTS by employing (OR, AND, and NOT) boolean Logic and a timer
Three-Phase UVLS Logic
27
27B
47B
Va ≤Vb
Vc
Setpoint #1
≤≤
Setpoint #1
Setpoint #1
AND
AdjustableTimer
UndervoltageTrip
AND
SINGLE PHASEUNDERVOLTAGE
Va ≤VbVc
Setpoint #2
≤≤
Setpoint #2
Setpoint #2
OR xUNDERVOLTAGE
BOCK
V2 Setpoint #3≥ xNEGATIVE
SEQUENCEOVERVOLTAGE
BLOCK
Blackout Avoidance
Positive Sequence UVLS LogicV1 = 1/3 ( Va + aVb +a2Vc )
Where: Va,Vb,Vc are line-to-neutral voltages
a = 1l120o
a2 = 1l240o
Balanced Conditions:V1=Va=Vb=Vc.
27
27B
47B
V1 ≤Setpoint #1
AdjustableTimer
UndervoltageTrip
AND
POSITIVESEQUENCE
UNDERVOLTAGE
Va≤VbVc
Setpoint #2
≤≤
Setpoint #2
Setpoint #2
OR xUNDERVOLTAGE
BOCK
V2 Setpoint #3≥ xNEGATIVESEQUENCE
OVERVOLTAGEBLOCK
Blackout Avoidance
Blackout Avoidance
5 Programmable Outputs, 2 programmable inputs, and 1 self-test outputOscillographic Recording (COMTRADE file format)Time-Stamped Sequence of Events (SOE) recording for 32 eventsMetering of Voltage and FrequencyPorts – one RS-232 port (COM1) on front and one RS-232 and 485 port (COM2) on rearSetting Software – M-3812 IPScom® For WindowsTM Communica-tions SoftwareModbus ProtocolRelay Voltage Inputs Can Be Directly Connected (no VT required) for voltages < 480 V acContinuous Self-Diagnostics
M-3401 Standard Features
CONCLUSIONS
Voltage Collapse is the Major Cause of Blackouts in US Power Systems.
UVLS is a Viable Method of Providing Protection to Avoid Slow Voltage Collapse Situations.
UVLS May be too Slow to respond to Rapid Fault Induced Voltage Collapses.
UVLS Requires close Cooperation Between Planners and Relay Engs.
UVLS Schemes are More Difficult to Design and Set than UFLS.
Blackout Avoidance
Generator Protection Needs to be Made More Secure During Low Voltage Conditions and be Coordinated with Generator Controls.
Methods to do this are Scattered in Various Text Books and Manufactures Literature.
My Paper Provides a Single Document with this Information.
My Paper Highlights the Important Role the AVR Plays During Major Disturbances.
CONCLUSIONS
Blackout Avoidance
BLACKOUT AVOIDANCE &
UNDERVOLTAGE LOAD SHEDDING
BLACKOUT AVOIDANCE &
UNDERVOLTAGE LOAD SHEDDING
THE END
Questions ?
THE END
Questions ?
Blackout Avoidance
©2008 Beckwith Electric Co., Inc.