best products · best performance · best protection b iological s afety c abinet b asics
TRANSCRIPT
BEST PRODUCTS · BEST PERFORMANCE · BEST PROTECTIONBEST PRODUCTS · BEST PERFORMANCE · BEST PROTECTION
BIOLOGICAL SAFETY CABINET BASICS
BIOLOGICAL SAFETY CABINET BASICS
HORIZONTAL LAMINAR FLOWCLEAN ROOM
HORIZONTAL LAMINAR FLOWCLEAN ROOM
VERTICAL LAMINAR FLOWCLEAN ROOM
VERTICAL LAMINAR FLOWCLEAN ROOM
HORIZONTAL LAMINAR FLOWCLEAN WORK STATION
HORIZONTAL LAMINAR FLOWCLEAN WORK STATION
VERTICAL LAMINAR FLOWWORK STATION
VERTICAL LAMINAR FLOWWORK STATION
BALANCED LAMINAR AIR FLOW HOODBALANCED LAMINAR AIR FLOW HOOD
NIH-03-112C CABINET(NATIONAL INSTITUTE OF HEALTH)
NIH-03-112C CABINET(NATIONAL INSTITUTE OF HEALTH)
Class II - Type A
10 inch - Inflow Supply 80 + 5 fpm
8 inch opening – Inflow Supply 90 + 5 fpm
Downflow 80 + 5 fpm with a range of 64 to 96 fpm for all readings
Class II - Type B1
8 inch opening – Inflow Supply 100 + 10 fpm
Downflow 50 + 5 fpm with a range of 45 to 60 fpm for all readings
NCI-1(NATIONAL CANCER INSTITUTE)
NCI-1(NATIONAL CANCER INSTITUTE)
June 1976
Committee composed of: NIH NCI CDC Manufactures Users
May 1993 changed from a construction specifications in favor of performance criteria
NSF-49(NATIONAL SANITATION FOUNDATION)
NSF-49(NATIONAL SANITATION FOUNDATION)
Unit Components
Unit Air flows
Unit Types Bench Top Console Vertical
HORIZONTAL LAMINAR FLOWCLEAN WORK BENCH
(PRODUCT PROTECTION ONLY)
HORIZONTAL LAMINAR FLOWCLEAN WORK BENCH
(PRODUCT PROTECTION ONLY)
NU-201 AIR FLOWNU-201 AIR FLOW
NU-301 AIR FLOWNU-301 AIR FLOW
100% Exhaust Inflow velocity 75 fpm minimum
BSL 1 –3 Usage Personnel protection only CDC/NIH recommends a glove-port
panel for use with small amounts of radionuclides when exhausted
Typical uses today: Toxic powder weighing, necropsy
Maybe thimble/air gap or hard connected to a exhaust system when proper precautions are taken
Room AirFiltered Exhaust Air
LabGard 813 Air Flow
CLASS IBIOLOGICAL SAFETY CABINET
CLASS IBIOLOGICAL SAFETY CABINET
CLASS I AIR FLOWCLASS I AIR FLOW
30% Exhaust, 70% Re-circulate
Negative pressure plenum (Changed 2007)
Inflow velocity 75 fpm minimum BSL 1 –3 Usage Personnel and Product protection Minute amounts of non-volatile toxic
chemicals and radionuclides if canopy/thimble exhausted
Typical uses today: Bacterial, Viral, Fungal, Parasitic
CLASS II – TYPE A1CLASS II – TYPE A1
Console Bench Top
70%
CLASS II – TYPE A1CLASS II – TYPE A1
30% Exhaust, 70% Re-circulate
Negative pressure plenum
Inflow velocity 100 fpm minimum BSL 1 –3 Usage Personnel and Product protection Minute amounts of volatile toxic
chemicals and radionuclides if canopy/thimble exhausted
Typical uses today: Bacterial, Viral, Fungal, Parasitic, Arbor-viruses
CLASS II – TYPE A2CLASS II – TYPE A2
Console Bench Top
70%
CLASS II – TYPE A2CLASS II – TYPE A2
70% Exhaust, 30% Re-circulate
Negative pressure plenum Inflow velocity 100 fpm minimum
BSL 1 –3 UsagePersonnel and Product protectionMinute amounts of volatile toxic chemicals
and radionuclidesMust be hard connected with typical exhaust
requirement being 300-500 CFM at 1.0” w.g.Must have interlocked internal blower with
audible and visual alarm for exhaust failureTypical uses today: Bacterial, Viral, Fungal,
Parasitic, Arbor-viruses
CLASS II – TYPE B1CLASS II – TYPE B1
CLASS II – TYPE B1CLASS II – TYPE B1
100% Exhaust
Negative pressure plenum Inflow velocity 100 fpm minimum
BSL 1 –3 Usage Personnel and Product protection Small amounts of volatile toxic chemicals
and radionuclides Must be hard connected with typical
exhaust requirement being 700-1,200 CFM at 2.0” w.g.
Must have interlocked internal blower with audible and visual alarm for exhaust failure
Typical uses today: Bacterial, Viral, Fungal, Parasitic, Arbor-viruses, Prion, Cytotoxics
CLASS II – TYPE B2CLASS II – TYPE B2
CLASS II – TYPE B2CLASS II – TYPE B2
10’ Above roof line
BlowerContactor
Damper(Automated or Manual)
Cabinet
StackMake-up
Air Supply
ONE-ON-ONE EXHAUST SYSTEMONE-ON-ONE EXHAUST SYSTEM
Stack
Blower
Duct
CAV
Damper (Manual)
Cabinet
Make-up Air Supply
Ceiling Ceiling
Contactor
GANGED EXHAUST SYSTEMGANGED EXHAUST SYSTEM
CLASS III – “GLOVE BOX”CLASS III – “GLOVE BOX”
100% Exhaust Glove Box Negative Pressure at 0.5” w.g. minimum
Double HEPA Filter ExhaustBSL 4Personnel and Product ProtectionSmall amounts of volatile toxic chemicals
and radionuclidesMust be hard connected with typical
exhaust requirement being 50-100 CFM at 0.5 w.g.
Must have negative pressure alarm for cabinet or exhaust failure
Typical uses today: Toxic Powders, BSL 4 Agents
Class I: Personnel Protection Only100% exhaust Inflow velocity 75 fpm minimum
Class II: Personnel and Product ProtectionType A1 - 30% exhaust, 70% re-circulateNegative Pressure Plenum (Changed 2008) Inflow velocity 75 fpm minimum
Type A2 - 30% exhaust, 70% re-circulateNegative Pressure Plenum Inflow velocity 100 fpm minimum
BIOLOGICAL SAFETY CABINETCLASS / TYPES
BIOLOGICAL SAFETY CABINETCLASS / TYPES
Class II: Personnel and Product ProtectionType B1 - 70% exhaust, 30% re-circulate Negative Pressure Plenum Inflow velocity 100 fpm minimum
Type B2 - 100% exhaust Negative Pressure Plenum Inflow velocity 100 fpm minimum
Class III: Personnel and Product Protection 100% exhaust Negative Pressure at 0.5” w.g. minimum
BIOLOGICAL SAFETY CABINETCLASS / TYPES
BIOLOGICAL SAFETY CABINETCLASS / TYPES
1. Minute Amount
2. Small Amount
3. In no instance should the chemical concentration approach the lower explosion limits of the compound.
4. Type A2 cabinets used for work with minute quantities of volatile toxic chemicals and tracer amounts of radionuclides required as an adjunct to microbiological studies must be exhausted through properly functioning exhaust canopies.
BSCCLASS
BSL LEVEL OFAGENT USED
NON-VOLITILE TOXIC CHEMICALS &
RADIONUCLIDES
VOLITILE TOXIC CHEMICALS &
RADIONUCLIDES
I
II – TYPE A1
II – TYPE A2
II – TYPE B1
II – TYPE B2
III
I - 3
I - 3
I - 3
I - 3
I - 3
4
YES
YES (1)
YES
YES
YES
YES
YES (1, 3)
NO
YES (4)
YES (1, 3)
YES (2)
YES (2)
RISK ASSESSMENTRISK ASSESSMENT
AIRFLOW BALANCE
OPTIMIZATION
AIRFLOW BALANCE
OPTIMIZATION
Optimized through airflow distribution verified through Biological Standard Range Tolerance Testing (NSF/ANSI 49) Biological Wide Range Tolerance Testing
BIOLOGICAL TESTING FOROPTIMAL AIRFLOW BALANCE
BIOLOGICAL TESTING FOROPTIMAL AIRFLOW BALANCE
PERSONAL PROTECTIONPERSONAL PROTECTION
PRODUCT PROTECTIONPRODUCT PROTECTION
CROSS CONTAMINATIONCROSS CONTAMINATION
BIOLOGICAL WIDE RANGEPERFORMANCE TESTING
BIOLOGICAL WIDE RANGEPERFORMANCE TESTING
Canopy / Thimble is strongly recommended Low Exhaust Alarm Use of flex duct for adjustability
Exhaust volume equals BSC exhaust volume plus air gapvolume at 0.3” w.g.
Provide adequate make up air
EXHAUST CONNECTIONS FORCLASS II, TYPE A2 BSC’S
EXHAUST CONNECTIONS FORCLASS II, TYPE A2 BSC’S
Direct hard connection is required
Provide gas-tight exhaust damper for decontamination process
Evaluate connection restrictions based on BSC requirements (i.e. exhaust sensor type used)
Provide adequate make-up air for laboratory pressure requirements
Use Concurrent Balance Value from manufacturer to design and balance BSC
EXHAUST CONNECTIONS FORCLASS II, TYPE B1/B2 BSC’SEXHAUST CONNECTIONS FORCLASS II, TYPE B1/B2 BSC’S
CBV DEFINITIONCBV DEFINITION
Concurrent Balance Value (CBV) is determined by a duct traverse measurement method as specified in ASHRAE Standard 111 – 2008, a minimum of 7.5 duct diameters downstream of a direct connected BSC at its nominal setpoint calibrated using the primary DIM method. The static pressure is measured approximately 2 duct diameters above the BSC. Appropriate filter load and tolerance values are added to accommodate filter loading. The resulting values may be used for design and balance exhaust/supply HVAC Requirements.
Since the use of the DIM in the early 90’s, differences in measurement results have been noted between duct traverse and BSC face measurement methods
ASHRAE Study Results (1212 – RP) BSC face measurement is consistent and repeatable Lack of correlation between methods makes BSC face
measurement method suspect for mechanical system design and air balancers
NSF 49 Joint Committee Reviewed ASHRAE study results and voted to incorporate the
CBV into the listing
BREIF HISTORYBREIF HISTORY
BSC FACILITY ASSESSMENTBSC FACILITY ASSESSMENT
Ceiling Height / Door Width and Height -must accommodate the needs of the user within the constraints of the facility
Personnel movements / Door movements / pass-thru’s / and flow patterns in the facility must be analyzed
Design criteria; BSL 1, 2, 3 or 4
HVAC - Facility air handling system
FACILITY DESIGNFACILITY DESIGN
Location Isolate the BSC Reduce traffic flow Diffuse room air Move away from airflow ducts Move away from windows and doors
HVAC BSC’s if exhausted require a constant volume (+/- 5%) Laboratory balance positive or negative Laboratory ventilation rates Class II, Type B cabinets should never be the dedicated exhaust
for the Lab. Spatial and temporal uniform distribution of room air Review system dynamics, personnel movement, door movement,
pass-thrus, etc.
National, Local Code Conformity
FACILITY DESIGNFACILITY DESIGN
Process Plan Analysis Applicable Automation
Applicable facility SOP’s
cGMP Requirement
PROCESS ASSESSMENTPROCESS ASSESSMENT
EXAMPLE OF DATAPROVIDED BY MANUFACTURER
EXAMPLE OF DATAPROVIDED BY MANUFACTURER
NU-430 / 435-400 NU-430 / 435-600
Concurrent Balance Value
(CFM / CMH): 829 / 1409 1221 / 2075
Certification Exhaust Value
(CFM / CMH): 754 / 1281 1100 / 1869
Plant Duct Static Pressure
(ENG / Metric): 1.7”w.g. / 43 mm w.g. 2.0” w.g. / 51 mm w.g.
Note: The Exhaust System must be designed to provide the static pressure and required concurrent balance value at the location indicated [A] above.
ASHRAE STD. 111:2008ASHRAE STD. 111:2008
NU-430 / 435-400 NU-430 / 435-600
Concurrent Balance Value (CBV) 829 1221
Certification Exhaust Value (CEV) 754 1100
Ak Factor 1.10 1.11
Ak factor = Measured Airflow Rate divided by the velocityReading of a particular instrument used in its prescribed manner
Existing DuctworkSilicone or Neoprene Sleeve(NuAire Part #NU-940-001 or Equivalent)Band ClampBand Clamp
Butterfly Valve Assembly
Apply Silicone on Inside Edge ofButterfly Valve Assembly
HEPA Filter
Hood
Directionof Air flow
1in (25mm)Minimum
1in (25mm)Minimum
TYPE B1/B2DUCT CONNECTION
TYPE B1/B2DUCT CONNECTION
Contacts outputs Fan Relay Alarm Relay
Contact input from BAS Night Setback Remote Override
CABINET / BAS CONNECTIONS FORCLASS II, TYPE B1/B2 BSC’S
CABINET / BAS CONNECTIONS FORCLASS II, TYPE B1/B2 BSC’S
BSC TESTING
AND CERTIFICATION TO
NSF/ANSI 49 ANNEX F
BSC TESTING
AND CERTIFICATION TO
NSF/ANSI 49 ANNEX F
PRIMARY TESTSPRIMARY TESTS
HEPA Filter Leak Test
PRIMARY TESTSPRIMARY TESTS
Downflow Velocity Profile Test
PRIMARY TESTSPRIMARY TESTS
Inflow Volume / Calculated Velocity Test
Airflow Smoke Pattern Test
PRIMARY TESTSPRIMARY TESTS
Site Installation Assessment Test Alarm Functions Blower interlock, Type B1/B2 Exhaust System Performance
Canopy connection. Type A2 Room Influences
PRIMARY TESTSPRIMARY TESTS
Lighting Vibration Noise
SECONDARY TESTSSECONDARY TESTS
www.hc-sc.gc.ca/pphb-dgspsp/ols-bsl
www.cdc.gov/od/ohs
www.absa.org
www.absa-canada.org
www.ebsa.be
www.inspection.gc.ca
www.who.int
www.biosafety.be
www.hse.gov.uk
www.nsf.org
www.nuaire.com
INFORMATIONAL WEBSITESINFORMATIONAL WEBSITES
BSC ENERGY IMPROVEMENTSBSC ENERGY IMPROVEMENTS
BSC Energy Consumption
Conventional BSC Energy Consumption
Considerations for Improvement of BSC Energy Consumption
Additional Cost of Ownership Considerations
Night Setback BSC’s
NuAire’s Energy Saver (ES Series)
BSC Energy ConsumptionClass II, Type A2
BSC Energy ConsumptionClass II, Type A2
Fan Air / Rejected Heat
Outlet / Process Use
Power In
Conditioned Air Out plus Rejected Heat
Fan Control / Rejected Heat
Light / Rejected Heat
Conditioned Air In
CONVENTIONAL BSCENERGY CONSUMPTIONCONVENTIONAL BSC
ENERGY CONSUMPTION
Lighting Fan / Motor Fan Control
Pre 1995: T12 Lamp with magnetic ballast .7 to 1.0 Amp (80 to 120 watts)
1995 – 2008: T8 Lamp with electronic ballast .2 to .35 Amp (20 to 40 watts)
CONVENTIONAL BSCENERGY CONSUMPTION LIGHTING
CONVENTIONAL BSCENERGY CONSUMPTION LIGHTING
Forward Curved
Backward Curved
CONVENTIONAL BSCENERGY CONSUMPTION FAN
CONVENTIONAL BSCENERGY CONSUMPTION FAN
AC PSC (35% to 60% efficiency) 4 to 10 Amps (460 to 1150 watts) 9 inch diameter fan / 1100 to 1625 RPM
Fan Control TRIAC – .5 Amp (60 watts)
CONVENTIONAL BSCENERGY CONSUMPTION FAN
CONVENTIONAL BSCENERGY CONSUMPTION FAN
%
Eff
icie
ncy
.80
.70
.60
.50
.40
.30
.20
.10
0.0
600 800 1000 1200 1400RPM
AC PSC Motor - Conventional
FAN MOTOR EFFICIENCYFAN MOTOR EFFICIENCY
4 Foot Type A2 BSC used 8 hours per day5 day a week, 50 weeks per year (2000 hours per year)
AC PSC (conventional)
Watts 564
KW .564
KW-HR 1128
*Multiply times .09 per KWH
Annual Energy Cost to run 4ft. BSC $101.52
*U.S. DOE Average Cost, Plus the energy required to control the laboratory ventilation by adding 1693 BTU’s / HR of rejected heat
ENERGY COSTENERGY COST
4 Foot Type A2 BSC that runs 24/7*(8736 hours per year)
Plus the energy required to control the laboratory ventilation by adding 1693 BTU’s / HR of rejected heat
AC PSC (conventional)
Watts 564
KW .564
KW-HR 4927
Multiply times .09 per KWH
Annual Energy Cost to run 4ft. BSC $443.43
ENERGY COSTENERGY COST
CONSIDERATIONS FOR IMPROVEMENTOF BSC ENERGY CONSUMPTION
CONSIDERATIONS FOR IMPROVEMENTOF BSC ENERGY CONSUMPTION
Lighting Fan / Motor Fan Control
T8 Lamp (3500 Lumens) with electronic ballast .2 to .35 Amp (20 to 40 watts)
T5 Lamp (3300 Lumens) with electronic ballast .2 to .33 Amp (20 to 35 watts)
LED (3000 Lumens) no ballast .05 to .2 Amp (5 to 20 watts)
LIGHTING SYSTEMS AVAILABLEFOR BSC IMPROVEMENT
LIGHTING SYSTEMS AVAILABLEFOR BSC IMPROVEMENT
LED LIGHTINGLED LIGHTING
AC – 3 Phase
DC
DC – ECM
FAN / MOTOR AVAILABLEFOR BSC IMPROVEMENTFAN / MOTOR AVAILABLEFOR BSC IMPROVEMENT
Forward Curved Fan (10-inch Diameter Wheel)
Extended RPM Range (800 to 1400 RPM)
Frequency Drive Controller (constant volume)
Minimal Motor noise (frequency)
AC – 3 PHASEAC – 3 PHASE
Backward Inclined / Small Forward Curved Fan
High RPM Range (1400 – 2200 RPM)
Regulated Power Supply (48 VDC) with Potentiometer Control
No Motor noise
DCDC
Forward Curved Fan (10-inch Diameter Wheel)
Extended RPM Range (800 to 1400 RPM)
Built in power supply with PWM Control (constant volume)
No Motor noise
DC – ECMDC – ECM
%
Eff
icie
ncy
.80
.70
.60
.50
.40
.30
.20
.10
0.0600 800 1000 1200 1400
RPM
DC MotorDC ECM Motor
AC PSC Motor - Conventional
AC 3-Phase
FAN MOTOR EFFICIENCYFAN MOTOR EFFICIENCY
4 Foot Type A2 BSC used 8 hours per day5 day a week, 50 weeks per year (2000 hours per year)
AC PSC
(conv)DC ECM DC AC/3-Ph
Watts 564 299 163 414
KW .564 .299 .163 .414
KW-HR 1128 598 326 828
Multiply times .09 per KWH
Annual Energy Cost to run 4ft. BSC $101.52 $53.82 $29.34 $74.52
Plus the energy required to control the laboratory ventilation by adding the rejected heat
ENERGY COSTENERGY COST
4 Foot Type A2 BSC that runs 24/7*(8736 hours per year)
Plus the energy required to control the laboratory ventilation by adding the rejected heat
AC PSC
(conv)DC ECM DC AC/3-Ph
Watts 564 299 163 414
KW .564 .299 .163 .414
KW-HR 4927 2516 1424 3617
Multiply times .09 per KWH
Annual Energy Cost to run 4ft. BSC $443.43 $226.44 $128.16 $325.53
ENERGY COSTENERGY COST
Lighting availability and cost
Filter capacity
Noise and vibration
Reliability
Replacement availability and cost
ADDITIONAL COST OF OWNERSHIP CONSIDERATIONS
ADDITIONAL COST OF OWNERSHIP CONSIDERATIONS
T8 T5 *LED
Availability Widely Available Limited Availability Limited Availability
Cost/Bulb $4 $16 $75
Life (hours) 20,000 20,000 100,000
*No Ballast
LIGHTING AVAILABILITY & COSTLIGHTING AVAILABILITY & COST
Filter Size (amount of media)
Motor/Fan Function
Typically expressed in percent increase of total load capacity. On average, percent increase of total load capacity equals the following filter life in years.
50% - 3 Years (NSF Requirement)
100% - 5 Years
200% - 8 Years
FILTER CAPACITYFILTER CAPACITY
AC PSC Motor allowed for a 180% increase of total load capacity
1400
1200
1000
800
600.4 .5 .6 .7 .8 .9 1.0 1.1 1.2 1.3 1.4 1.5
NSF Load Requirement
NominalSetpoint
50% NSF Load Requirement
Below AcceptableAirflow Limit
TYPICAL AC PSC MOTORFILTER LOAD CAPACITY
(WITH USE OF SPEED CONTROL)
TYPICAL AC PSC MOTORFILTER LOAD CAPACITY
(WITH USE OF SPEED CONTROL)
AC 3-Phase Motor allowed for a 250% increase of total load capacity
1400
1200
1000
800
600
NSF Load RequirementBelow AcceptableAirflow Limit
NominalSetpoint 50% NSF Load Requirement
.4 .5 .6 .7 .8 .9 1.0 1.1 1.2 1.3 1.4 1.5
TYPICAL AC 3 – PHASE MOTORFILTER LOAD CAPACITY(CONSTANT AIR VOLUME)
TYPICAL AC 3 – PHASE MOTORFILTER LOAD CAPACITY(CONSTANT AIR VOLUME)
1400
1200
1000
800
600
NSF Load RequirementBelow AcceptableAirflow Limit
NominalSetpoint 50% NSF Load Requirement
.4 .5 .6 .7 .8 .9 1.0 1.1 1.2 1.3 1.4 1.5
DC Motor allowed for a 85% increase of total load capacity
TYPICAL DC MOTORFILTER LOAD CAPACITY
(CONTROL SYSTEMS)
TYPICAL DC MOTORFILTER LOAD CAPACITY
(CONTROL SYSTEMS)
DC ECM Motor allowed for a 250% increase of total load capacity
1400
1200
1000
800
600
NSF Load RequirementBelow AcceptableAirflow Limit
NominalSetpoint 50% NSF Load Requirement
.4 .5 .6 .7 .8 .9 1.0 1.1 1.2 1.3 1.4 1.5
TYPICAL DC ECM MOTORFILTER LOAD CAPACITY(CONSTANT AIR VOLUME)
TYPICAL DC ECM MOTORFILTER LOAD CAPACITY(CONSTANT AIR VOLUME)
Filter Size (amount of media)
Motor / Fan Function
Percent increase in total load capacity
50% - (NSF requirement) (3 Years)
85% - DC (4 Years)
180% - AC PSC (7 Years)
250% - DC ECM/AC 3Phase (10 Years)
FILTER CAPACITY SUMMARYFILTER CAPACITY SUMMARY
NOISE AC PSC DC ECM DC AC 3-Phase
Airflow (Design) N/C N/C N/C N/C
Fan (RPM) 1100-1700 800-1400 1400-2200 800-1400
Motor (Harmonics) Yes No No No
VIBRATION AC PSC DC ECM DC AC 3-Phase
Airflow (Design) N/C N/C N/C N/C
Fan (RPM) Higher Lower Higher Lower
NOISE & VIBRATIONNOISE & VIBRATION
Proper Design
Bearing Life (temperature)
Electronics / Power Supply
AC PSC AC 3-Phase DC ECM DC
Years >10 >10 >10 <10
RELIABILITYRELIABILITY
Availability
AC PSC
(distributor/ manufacturer)
DC ECM
(distributor/ manufacturer)
DC
(distributor/ manufacturer)
AC/3-Ph
(distributor/ manufacturer)
Motor $175.00 $350.00 N/A $250.00
Fan $100.00 $100.00 N/A $100.00
Supply Combo $275.00 $450.00 $633.00 $350.00
Exhaust Combo N/A N/A $400.00 N/A
Power Supply N/A N/A $239.00 N/A
Fan Control $175.00 $200 / NA N/A $375.00
MOTOR REPLACEMENT COSTSMOTOR REPLACEMENT COSTS
Application Driven
Type A2 BSC’s – reduce fan / motor speed & close window
Type B1/B2 BSC’s – reduce exhaust volume and/or fan / motor and close window BSC / HVAC interface
NIGHT SETBACKNIGHT SETBACK