barc

125
1 A REPORT ON STUDY OF ELECTRICAL POWER SYSTEM OF TAPS-3&4 AND IT’S PROTECTION AT TARAPUR ATOMIC POWER STATION- 3&4(NPCIL), MAHARASHTRA Done under the guidance of Shri A.N. THAKUR SME (E) TAPP- 3&4 BY: - SIDDHARTH JAIN (0801EE101060) Shri G. S. Institute of Tech. & Science, Indore (M.P.) JUNE, 2013

Upload: siddharth-jain

Post on 09-Aug-2015

92 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: BARC

1

A REPORT ON

STUDY OF ELECTRICAL POWER SYSTEM OF TAPS-3&4

AND IT’S PROTECTION

AT

TARAPUR ATOMIC POWER STATION- 3&4(NPCIL), MAHARASHTRA

Done under the guidance of

Shri A.N. THAKUR

SME (E)

TAPP- 3&4

BY: -

SIDDHARTH JAIN

(0801EE101060)

Shri G. S. Institute of Tech. & Science,

Indore (M.P.) JUNE, 2013

Page 2: BARC

2

Page 3: BARC

3

ACKNOWLEDGEMENT

A comprehensive report always requires the goodwill, encouragement and support of many

people. The all-round aspect thinking that an engineer has to have can hardly be gained through

books and classes. The exposure to industries, learning and fulfilling their requirements make me

feel more confident about my knowledge, and such learning process is very motivating make me

feel more confident about my knowledge, and such learning process is very motivating to keep

learning more. Right from the design aspects, protection schemes, calibration and maintenance to

troubleshooting are part of our knowledge.

All this was possible with great support and guidance of employees at TAPS- 3&4, the love and

tenderness that these people have shared with me is invaluable. I am wholeheartedly indebted to

them. I dedicate this project to the employees and friends at electrical maintenance unit (EMU),

TAPS-3&4.

I would like to extend my gratitude to

Shri R.K. Gargye, SD TMS

Shri R.P. Tomar, SD TAPS-3&4

Shri A.N. Thakur, SME (E)

ShriAshwin Kumar Yadav, SO/E

Shri Tapas Kumar Dey, SO/E

ShriNishantDhimole, SO/E

ShriSanjay Panday, SO/D

ShriNayan Shah, SO/D

I would also like to extend my special gratitude to Shri H.T. Gayiker,Shri Rahul Sapkale SA/D

and Shri M.M. Raut TM/D for their support and cooperation.

Page 4: BARC

4

TABLE OF CONTENTS

1) Introduction to TAPS-3&4 and India’s nuclear programme

1.1) How a Nuclear Reactor Works

1.2) Importance of the Project

1.3) About the Project

1.3.1) Plant Layout

1.3.2) Unique Features of This 540 MWe Plant

1.4) India’s Nuclear Programme

1.4.1) Pressurized Heavy Water Reactor (PHWR)

1.4.2) Nuclear Fuel Cycle

2) Electrical system

2.1) General Description of Electrical System:

2.2) Objectives of Electrical System

2.3) Classification of Electrical System

2.4) Description of Station Auxiliary Power Supply System

2.4.1) Class IV Power Supply System

2.4.1.1) 6.6 KV System

2.4.1.2) 415V System

2.4.2) Class III Power Supply System

2.4.3) Class II Power Supply System

2.4.4) Class I Power Supply System

2.5) Unit Auxiliary System Voltage Levels

2.6) Nomenclature Adopted For Taps-3&4 Electrical Systems

2.7) Redundancy

2.8) System operation

2.8.1) Normal operation

2.8.2) Shut down condition

2.8.2.1) Unit shut down condition

Page 5: BARC

5

2.8.3) Operation Under Off Normal Condition

2.8.3.1) Shut down of one UT

2.8.3.2) Shut down of two UTs

2.8.3.3) Shut down of SUT

2.8.3.4) Fault on any of the 6.6kV buses C41 to C44

2.8.3.5) Fault on any of the 415V buses D41 to D46

2.8.3.6) Tripping of any one of the auxiliary transformers

2.8.4) Operational transients

2.8.4.1) 6.6kV auto/ manual transfer operations

2.8.4.2) Manual transfer

2.8.5) Auto-Transfer scheme

2.8.5.1) Automatic fast transfer (SUT to UTs)

2.8.5.2) Automatic fast transfer (UT to SUT)

2.8.5.3) Automatic slow transfer

2.8.5.4) Emergency transfer scheme

2.8.5.4. A) 6.6 kV class-III, 415v class-III bus supply and

feeder restoration

2.8.5.4. B) EMTR initiation for 415 V class-III buses

2.8.5.4. C) EMTR initiation for 415 v class-II buses

2.8.5.4. D) Emergency transfer panel

3) Power ups system

3.1) General description

3.2) Components of system

3.3) Operations

3.4) Design basis

3.5) Technical particulars of power ups

4) Gas insulated switchyard

4.1) TAPP-3&4 Grid

4.1.1) 400 KV Switchyard

Page 6: BARC

6

4.1.2) 220 KV Switchyard

4.2) Details of electrical equipment

4.2.1) Capacitive voltage transformer

4.2.2) SF6 gas circuit breaker

4.2.3) Lighting arrestor

4.2.4) Current transformer

4.2.5) Electromagnetic potential transformer

4.2.6) Disconnecting switches/Earthing switches

4.3) Switching Scheme Adopted

4.4) Operation Principle

4.5) SF6 Monitoring

4.6) Ratings OF 220 KV & 400 KV GIS

4.7) Hot line washing system for insulators

4.8) Why GIS housed indoor switchyard is selected for tapp-3 & tapp-4?

5) Electrical protection

5.1) Purpose of Electrical Protection

5.2) Essential Qualities of Electrical Protections

5.3) Types of Protective Relays

5.3.1) Electromagnetic relays

5.3.2) Static relays

5.3.3) Digital relays

5.3.4) Numerical relays

6) Transformers and its protection

6.1) Transformer Faults

6.2) Transformer Protection

6.2.1) Transformer Instantaneous Over-Current Protection

6.2.2) Transformer Differential Protection

6.2.2.1) Principle of Transformer Differential Protection.

6.2.2.2) Basic Considerations for Transformer Differential protection

Page 7: BARC

7

relay settings.

6.2.3) Transformer gas (Buchholz) relay

6.2.3.1) Generation of Gas Due to Faults

6.2.3.2) Operation of a Transformer Gas Relay

6.2.4) WTI and OTI Protection

6.2.4.1) OTI and WTI at TAPS

6.2.5) Overfluxing Protection:

6.2.6) Transformer Ground Fault Protection

6.2.6.1) Residually Connected Earthfault Protection

6.2.6.2) Neutral Connected Earthfault Protection

6.2.6.3) Restricted Earthfault Protection

6.3) Characteristic Transformer Faults

6.4) Condition monitoring of transformers

6.5) Choice of Transformers at TAPS-3&4

6.5.1) Why such GT is chosen?

6.5.2) Why such Unit-transformer is chosen?

6.5.3) Why such type of SUT is chosen?

6.6) Protection of transformer at TAPS-3&4

6.6.1) Protection of GT (Generator Transformer)

6.6.2) Protection for UT

6.6.3) Protection for SUT

7) Generator and generator protection

7.1) Requirement and Functions

7.2) Description

7.2.1) Overall System Layout

7.2.2) Layout of Individual System

7.3) Design Features

7.4) Protections of Generator

7.4.1) Nature of faults in generators and their protection

7.4.1.1) Stator winding faults & protection

Page 8: BARC

8

7.4.1.2) Overcurrent protection

7.4.1.3) Overvoltage protection

7.4.1.4) Undervoltage protection

7.4.1.5) Rotor Earth Fault protection:

7.4.1.6) Loss of Excitation (Field Failure):

7.4.1.7) U/O Frequency:

7.4.1.8) Unbalance Loading:

7.4.1.9) Prime mover failure - Reverse power protection:

7.4.1.10) Overspeed Protection:

7.4.1.11) Protection against inadvertent energisation:-

7.4.1.12) Overfluxing

7.5) Generator Circuit Breaker

7.5.1) General Construction Features:

7.5.2) Capabilities of the GCB

7.5.3) Contacts

7.5.4) GCB Specifications:

7.5.5) Air blast type Generator Circuit Breakers

7.5.5.1) Operating Mechanism

7.5.6) Importance and Advantages of using GCB in TAPS-3&4 systems

7.6) Generator protection scheme at TAPS-3&4

7.7) Replacement of REF protection scheme at TAPS-3&4

7.7.1) New relay scheme

7.7.1.1) Installation

7.7.1.2) Testing for REF

8) Motor protection

8.1) General description

8.2) Motor Faults and settings

8.2.1) Thermal Overload Protection (49)

8.2.2) Short circuit Protection (50/51)

8.2.3) Start Protection

Page 9: BARC

9

8.2.3.1) Excess long Start Protection (48)

8.2.4) Stalling Protection

8.2.5) Negative Phase sequence Protection

8.2.6) Earth fault Protection

9) Vacuum circuit breaker

9.1) Dielectric strength of Vacuum

9.2) Electric arcing in Vacuum

9.3) Phenomena associated with breaking at current zero

9.4) Practical design of vacuum interrupters

9.5) Suitability of Vacuum CB for MV

9.6) Vacuum CB at TAPS- 3&4

9.6.1) CB control

9.6.2) Circuit Breaker Positions

9.6.3) Operating Mechanism

9.6.3.1) Anti-pumping:

9.6.3.2) Trip-free

9.6.3.3) Spring charging & breaker closing mechanism

9.6.4) VCB Particulars

10) Distance protection

10.1) General description

10.2) Factors influencing distance protection

10.3) Principles of distance relays

10.4) Relay performance

11) Conclusions

12) Appendix

13) Bibliography

Page 10: BARC

10

1) INTRODUCTION TO TAPS-3&4 AND INDIA’S NUCLEAR

PROGRAMME

Tarapur Atomic Power Project, Unit-3&4 is the first twin unit module of 540 MWe capacity

each in India. These units are from pressurized Heavy Water Reactor family. These reactors

are indigenously developed and designed. The twin unit module design has been chosen based

upon the overall techno-economic considerations. Its operation will be supported by supply of

heavy water from the heavy water plants and fuel from the Nuclear Fuel Complex, both under

the Department of Atomic Energy.

Tarapur Atomic Power Project-3&4 is located on the West Coast of the Arabian Sea. The site is

located near the existing Tarapur Atomic Power Station-1&2. The nearest railway station is

Boisar at a distance of 12 Km from the site, which is on the main trunk railway line from

Mumbai-Delhi. The site is well connected by road and is around 30 Km away from the Bombay-

Ahmedabad National Highway.

1.1) HOW A NUCLEAR REACTOR WORKS:

A Nuclear Reactor is a source of heat, which is produced by self-sustained and controlled chain

reaction within the reactor core. The geometrical boundaries within which the nuclear fuel,

moderator, coolant and control rods are arranged to facilitate production and control of the

nuclear reaction to provide heat energy at desired rate is called the reactor core.

The natural uranium is used as a fuel in our Pressured Heavy Water Reactors. Uranium has a

natural property to emanate radio-active particles. This element has 3 isotopes i.e. U-238, U-235

and U-234. Only the isotope U-235 which is around 0.7% in the natural uranium is important for

energy production. When thermal neutron strikes the atom of U-235, fission of U-235 atom

Page 11: BARC

11

takes place breaking it up into two or more fragments. During this process enormous heat

energy is generated along with production of two to three fast moving neutrons.

These fast moving neutrons are slowed down in the presence of moderator (heavy water) and its

probability to cause further fission with uranium atom increases. This process continues and

self-sustained chain reaction is maintained. This provides the constant heat energy source. The

energy produced in this process is proportional to the neutron density in the reactor core. Thus

the reactor power is regulated by controlling the absorption of the excess neutrons in the core.

The heat produced in the reactor is used to generate light water steam at high pressure, which

drives the turbo-generator to produce electrical energy.

1.2) IMPORTANCE OF THE ATOMIC PROJECT:

The states in the western zone are located at considerable distances from the coal fields and coal

linkages and transport bottlenecks are becoming difficult day by day. Potential for the

development of hydro-electric power is also limited and is further vitiated by ecological

problems in setting up of the hydro-electric projects. It is in the light of these circumstances that

the addition of 1080 MWe to the western grid from nuclear power is to be viewed. It has been

visualized that there is going to be a magnificent industrial growth in western zone and addition

of 1080 MWe electric power generated by TAPP-3&4 will meet demand as a base load station in

western zone of India.

1.3) ABOUT THE PROJECT:

1.3.1) Plant layout:

a) The Principle features of the layout are:

b) The layout is based on the concept of independent operation of each unit with some of the

common facilities for the reason of economy.

c) All safety related systems and components are placed in separate buildings/structures of

appropriate design including seismic considerations.

Page 12: BARC

12

d) All safety related systems and components are protected from low trajectory missiles

emanating from turbine. This has resulted in locating the turbine building at an angle

with reference to reactor building axis.

e) A common fuelling machine head calibration and maintenance facility between the two

reactor units is provided, communicating via fuelling machine air lock and passage

leading to each RB. This facility has been located in service building, which is common

for both units. This facility would reduce the down time of the plant.

f) Reactor Auxiliary Building is located very near to Reactor Building to avoid long piping

lengths.

g) A separate Control Building has been provided as a common facility.

h) A separate emergency control room has been provided for each unit in service buildings

as a back up.

i) Emergency power systems have been provided in two station auxiliary buildings for each

unit for higher reliability.

j) Space around the reactor buildings has also been considered for erection facility for

heavy equipments.

1.3.2) Unique features of this 540 MWE plant:

a) 220 KV & 400 KV gas insulated indoor switchyards (GIS) 400 KV used for power

evacuation system.

b) Introduction of generator CB between generator and GT System divided in two

independent divisions one fed by UT and other fed by SUT

c) Totally independent EMTR for both divisions.

d) 4 DG sets/unit

e) Safety related systems of each division housed in separate buildings qualified for SS

1.4) INDIA’S NUCLEAR PROGRAMME:

To utilize large uranium and thorium reserves in the country for electricity generation, India has

been following a three-stage nuclear power programme, which aims at the development of

Page 13: BARC

13

a) Pressurized Heavy Water Reactors, (PHWR) based on natural uranium.

b) Fast breeder reactors utilizing plutonium-uranium fuel cycle, and

c) Breeder Reactors for utilization of thorium.

1.4.1) Pressurized heavy water reactor (PHWR)

In the PHWR based nuclear power programme, India has attained commercial maturity. The

design of 220 MWe PHWR has been standardized and scaled up to 540 MWe. This has been

further scaled up to 700 MWe. Self-reliance has been achieved in the whole ambit of PHWR

technology, and associated fuel cycle, starting from mining and ore processing, fuel fabrication,

fuel reprocessing and waste management, including heavy water production.

Table-1: Nuclear Power Stations in Operation

Unit – Location Reactor Type Capacity (MWe)

Tarapur Atomic Power Station-1&2 BWR 2×160

Tarapur Atomic Power Station-3&4 PHWR 2×540

Rajasthan Atomic Power Station-1&2 PHWR 100, 200

Rajasthan Atomic Power Station-3&4 PHWR 2×220

Madras Atomic Power Station-1&2 PHWR 2×220

Narora Atomic Power Station-1&2 PHWR 2×220

Kakrapar Atomic Power Station-1&2 PHWR 2×220

Kaiga Generating Station-1&2 PHWR 2×220

Total 3900

With a total capacity of 3900 MWe, 16 atomic power reactors (table-1) are in operation in the

country. Currently, 7 nuclear power reactors with a total capacity of 3380 MWe are under

construction. These include, two 220 MWe PHWRs each at Rawatbhatta and Kaiga, two 100

MWe pressurized water reactors at Kundakulam (Tamil Nadu), and one 50 MWe fast breeder

reactor at Kalpakam and two newest 700MWe reactors at Kakrapar, Gujarat. The current share

of nuclear power generation as a percentage of total electricity generation in the country is 3 %.

Page 14: BARC

14

1.4.2) Nuclear fuel cycle

India has acquired comprehensive capability in the PHWR design, construction and operation of

associated plants/facilities covering the entire nuclear fuel cycle of the nuclear power programme

based on PHWRs.

Nuclear fuel fabrication for power and research is done at Nuclear Fuel Complex, Hyderabad

and BARC respectively.

There are 7 heavy water plants in the country that are based on ammonia-hydrogen exchange and

hydrogen sulphide-water exchange technologies. The latter has been developed indigenously.

Through continuing research, BARC has developed heavy water upgrading technology on

commercial scale. Based on this technology, at present 23 upgrading/final enrichment towers are

in operation at various sites.

The Indian nuclear power generation programme is based on closed cycle approach that involves

reprocessing of spent fuel and recycle of plutonium and uranium-233 for power generation. The

development of fuel reprocessing technology had commenced from inception of DAE’s nuclear

power programme. DAE has a pilot plant for fuel reprocessing at Trombay and industrial scale

plants at Tarapur and Kalpakam. BARC has successfully developed technology for vitrification

for radioactive waste.

Page 15: BARC

15

Page 16: BARC

16

2) ELECTRICAL SYSTEM

2.1) GENERAL DESCRIPTION OF ELECTRICAL SYSTEM:

The electrical system of this project is divided mainly into two sub systems. Main power output

system and station auxiliary power supply system. Main power output system transmits the

power generated by 500 MWe generators at 21 KV from generator terminals to the switchyard

through generator transformer, which steps up voltage upto 400 KV before evacuation to grid.

Station auxiliary power supply system provides power supply for various station loads required

for start up operation, safe shutdown and maintaining the unit. The main sources of power supply

are from startup transformer interconnected with 220 KV grid and unit transformers (2 No.)

connected with output terminals of main generator. Station auxiliary power supply is also

divided into various classes namely CL-IV, CL-III, CL-II, and CL-I, depending upon

requirement of availability / reliability of power supply for various loads. Diesel generators and

battery banks are provided as backup power supplies.

2.2) OBJECTIVES OF ELECTRICAL SYSTEM

The electrical power system for TAPP-3&4 is designed to provide for

The following objectives:

a) To evacuate the power generated from the turbo generators to the off site grid connected

to the station at 400 KV switchyard.

b) To provide required quality of power to the station axillaries through start-up transformer

(SUT) and/ or GT/UT combination and in case of emergency on site diesel generator sets

and uninterruptible power supply systems.

Page 17: BARC

17

c) To provide emergency electric power supply to safety system of the station during

simultaneous occurrence of postulated initiating events and single failure of any

active/passive electric component/system.

d) To provide station emergency electric power system with reliable off site power from at

least two transmission lines preferably connected to two generating stating stations.

e) To provide fast transfer systems, emergency transfer systems and load shedding schemes

so that electrical power supply is restored within the interruption time permitted by the

connected loads.

f) To provide operational flexibility.

g) To provide necessary isolations, alarms and indications for safe operation maintenance of

electrical equipment.

h) To provide fire protection and safety.

i) To provide earthing of electrical system and equipment for personnel and system safety

and isolation of defective system.

j) To provide surge suppression, lighting protection.

k) To provide adequate lighting during plant operation and during emergency.

2.3) CLASSIFICATION OF ELECTRICAL SYSTEM

Power supply system for Nuclear power station is classified into four categories depending

upon the requirement of continuity of power supply to the loads.

a) Class-IV Power Supply:

Alternating current power supply to auxiliaries, which can tolerate prolonged interrupt

without affecting safety of reactor, is classified as class-IV. This supply is the normal

power supply drawn from switchyard through SUT and or GT/UT combination.

b) Class-III Power Supply:

Alternating current power supply to auxiliaries, which can tolerate short interruptions (up

to one minute), is classified as class-III power supply. Under normal conditions this

Page 18: BARC

18

power supply is derived from class-IV and on loss of class-IV power supply, on-site

standby diesel generators provide the back up.

c) Class-II Power Supply:

Alternating current power supply to auxiliaries, which require un-interrupted power

supply, is called class-II power supply. Under normal conditions electrical power is

derived from class-III buses through AC/DC rectifier together with DC to AC inverter. A

battery bank provides direct back up power so that class-II power is available even when

supply to class-III or rectifier is not available.

d) Class-I Power Supply (Dc Supply):

Dc power supply to loads which require uninterruptible direct current power supply.

Normally direct current power is derived through a AC to DC rectifier connected to class-

III. Battery backup is provided so that direct current power supply continues to be

available even when class-III or rectifier fails.

2.4) DESCRIPTION OF STATION AUXILIARY POWER SUPPLY

SYSTEM:

Station auxiliary power supply system (SAPSS) Provides power supply to various station

auxiliary loads required for start-up, shut down and running operations of the unit. The class IV

SAPSS has been divided into two divisions, one division (Division I) supplied from unit

transformers (UTs) and the other division (Division II) supplied from start up transformer (SUT).

Interconnections are provided between Division-I and Division II at all voltage levels except

415V CL.III and CI.IV to feed the loads belonging to the other division in case of total or partial

loss of power to that division. The buses, transformers and MCCs in Division-I are given odd

numbers and Division-II even numbers. Supply sources in each division can independently meet

the entire station demand under normal and abnormal conditions of one unit operation.

Page 19: BARC

19

2.4.1) Class IV Power Supply System

Under normal condition of operation, the power to all the auxiliary loads is fed from class IV

power supply system. Class IV Power supply system for each unit derives its power from UTs

(two Nos.) and SUT (one No.). UTs are two winding transformers of 21 KV/6.9 KV, 35 MVA

rating each, connected to Generator terminals through a Generator Circuit Breaker (GCB). SUT

is a three winding transformer (70/35/35 MVA, 220/6.9/6.9 KV and unloaded delta for

suppression of harmonic currents), which is connected to 220 KV grid and supplies power to

class IV system at 6.6KV.

The class IV power supply has two levels of voltages supplying power at:

a) 6.6 KV, 3-phase for motors of rating 200KWand above.

b) 415 V, 3-phase for motors 200 KW rating.

2.4.1.1) 6.6 KV System

This system consists of four numbers of buses with each switchgear bus fed from UTs or SUT

directly. The startup/auxiliary power of the unit will be derived through GT/UT and/or SUT.

Major loads connected on this system are Primary Coolant pumps; Boiler feed pumps,

Condensate pumps, CW pumps, Chillers etc. One 6.6 KV feeder will be provided for supplying

loads in waste management plant and D20 & Upgrading plant from unit-4.

2.4.1.2) 415 V System

This system consists of six numbers (6Nos.) of buses supplied through six 6.6 KV/433V, 2 MVA

transformers for feeding power to auxiliary loads. 415V loads in service building, CW pump

house and DM plant will be supplied from 415V; Class IV local MCCs. MCCs located in DM

plant will be supplied from Unit-4. To maintain the continuity of the supply with minimum time

of interruption when any one of the six transformers fails, a hot standby transformer is provided

to supply the load of the affected bus, which will be switched in manually.

Page 20: BARC

20

2.4.2) Class III Power Supply System

This system derives its power from class IV, 6.6 KV system under normal condition of

operation. This system consists of four numbers (4 Nos.) of 6.6kV buses, each backed up by a

DG set, and four numbers (4 Nos.) of 415 V buses.

2.4.3) Class II Power Supply System:

Class II, 415V, emergency power supply system provides uninterrupted A.C. power to the loads

connected to this system. This system consists of 2 Nos. of 415V buses which derive power from

power UPS.

2.4.4) Class I Power Supply System:

This system provides 220V DC uninterrupted power to the DC loads. This is further divided into:

a) 220V DC power supply

b) 220V DC control supply

2.5) Unit Auxiliary System Voltage Levels:

Following voltage levels have been adopted for TAPP-3&4 Electrical systems.

21KV (AC) : Input to unit Auxiliary transformer/ Unit

generation voltage.

6.6 KV (AC) : Unit main power buses, DG sets,

motors above 200KW rating &

auxiliary transformers

415V (AC) : Distribution buses, motors below 200

KW rating

240V (AC) : Single-phase loads like, control power

supplies, recorders, lighting, space

heaters, receptacles.

220V (DC) : Control power to circuit breaker, DG

controls, emergency lighting etc.

24V (DC) : Controls, annunciations, indications

Involving main control room control

logic, remote operation etc.

Page 21: BARC

21

Figure1-class III power supply system

Page 22: BARC

22

2.6) NOMENCLATURE ADOPTED FOR TAPP-3&4 ELECTRICAL

SYSTEM

A) Capital Alphabets have been used to designate various voltage levels. Following is the list of

voltage designation.

Voltage level Alphabet

i. 400KV (AC) A

ii. 220KV (AC) B

iii. 6.6KV (AC) C

iv. 415KV (AC) D

v. 220V (DC) E

vi. 240V (AC) F

vii. 24V (DC) G

B) Numerical have been used to designate different classes

Class Numerical

IV 4

III 3

II 2

I 1

C) Grouping:

For designating equipments in div-1, odd numbers are used & for Div-2, even numbers are used.

Example: 52410- BU- C 4 3

3 – Bus number in division-1

4 – Class –IV

C – 6.6 kV

B – Bus

52410 – System USI

Page 23: BARC

23

2.7) REDUNDANCY:

Each division will be functioning independently irrespective of availability of other Division.

This arrangement is provided to ensure that failure of one of the equipments, does not affect the

operation of the other equipments in general, and operation of safety related equipment in

particular.

In each division there are safety related equipments and non-safety related equipments. Each

safety related equipment power supply system is provided with alternate source of feed so that

the equipment comes back into operation within the specified limit of time.

Equipments are duplicated and supplied from Div-1&2 so that when one equipment is out of

service, the stand by will be operational to ensure the system operation.

2.8) SYSTEM OPERATION

2.8.1) Normal operation

Under normal operating condition the Main generator is synchronized with the grid and the

station supply is available through UTs and SUT. Under this condition, total auxiliary load is

shared by UTs & SUT equally. Buses C41 and C43 will be fed from UT1 &UT2 respectively

and buses C42and C44 will be fed from SUT and hence the breaker between C41 & LV1 of

SUT, C43 & LV2 of SUT, C42 & UT1 and C44 & UT2 will remain open CL .IV-CL. III ties

between buses C41 & C31, C43 &C32, C42 & C32 and C44 & C34 will remain closed. 415V

buses will be energized through respective auxiliary transformers. Reserve transformer will be

on hot stand by and ties between reserve transformer and 415V CI. IV buses (D41 to D46) will

remain open.

Page 24: BARC

24

2.8.2) Shutdown condition

2.8.2.1) Unit shut down condition

Under this condition power is derived from 400kV grid through GT-UT combination and / or

from 220 KV grid through SUT.

2.8.3) Operation Under Off Normal Condition

2.8.3.1) Shutdown of one UT

Under this condition, the load taken by the running UT will not change. The load catered to by

the shut down UT will be transferred to corresponding SUT winding with the respective 6.6kV

breaker from SUT closed.

2.8.3.2) Shutdown of two UTs:

It is not envisaged that both the UTs will be on forced outage simultaneously during the unit

operation. However under this condition all the station load is supplied from SUT.

2.8.3.3) Shutdown of SUT:

Under this condition all the loads of a unit are supplied from the UTs.

2.8.3.4) Fault on any of the 6.6kV buses C41 to C44:

Consider fault on bus C41. Bus will be isolated by protection. Fast transfer will be blocked by

operation of corresponding incomer breaker lockout relay. All the motor loads on this bus will

trip on under voltage. If standby loads corresponding to running loads on this bus are available

on the other buses they will start automatically. All the feeders except feeders to MCCs, lighting

load centers and other load centers on corresponding 415V switchgears will trip on under voltage

and if standby loads corresponding to running loads are available on other buses they will be

started automatically.

Page 25: BARC

25

Loads on corresponding MCCs will also trip and interposing relays (3C) will be deenergized.

Loads will be restored manually after restoration of power supply to the bus.

2.8.3.5) Fault on any of the 415V buses D41 to D46:

Consider fault on bus D41. This bus will be isolated by protection. All the feeders except

feeders to MCCs, lighting load center and other load centers on this bus will trip on under

voltage. Loads on corresponding MCCs will trip and interposing relays (3C) will be

deenergized. Loads will be restored manually after restoration of power supply to the bus.

2.8.3.6) Tripping of any one of the auxiliary transformers:

In the event of tripping of any one of the auxiliary transformers all the feeders except feeders to

MCCs, lighting load center and other load centers on the corresponding bus will trip on under

voltage. If standby loads are available on the other buses they will start automatically. Loads on

corresponding MCC’s will trip and interposing relays (3C) will be deenergized. Hot standby

transformer will be switched in manually. Loads will have to be started manually after

restoration of supply.

2.8.4) Operational transients

2.8.4.1) 6.6kV auto/ manual transfer operations

For starting of the unit the power to the buses C41 and C43 is drawn through GT/ UTs and for

the buses C42 and C44 is drawn through SUT and the unit is synchronized with the grid by

closing GCB. For loss of supply to Class IV 6.6kV system from either SUT or UTs provision

has been made for high speed transfer of loads from one source to another (UTs to SUT or SUT

to UTs).

Page 26: BARC

26

2.8.4.2) Manual transfer:

For planned transfer of loads from one source to other (SUT to UTs and UTs to SUT), the two

sources will be momentarily paralleled by closing the incoming sources breaker and the outgoing

source breaker will be tripped automatically. If the outgoing source breaker fails to trip the

incoming source breaker will trip automatically after a preset time delay. The time for which the

buses are paralleled is very small and hence during this time the possibility of a fault is remote.

2.8.5) Auto-Transfer scheme:

The purpose of auto transfer is to achieve automatic transfer of 6.6KV, Class-IV auxiliary power

supply, in the event of failure of either of the two feeds (from unit transformer or start-up

transformer) due to faults in feeder. The auto transfer scheme shall consist of:

a) Fast transfer scheme and

b) Slow transfer scheme.

2.8.5.1) Automatic fast transfer (SUT to UTs):

Immediately after the tripping of SUT by protections, the loads fed from SUT will be transferred

to UTs by automatic fast transfer under the following conditions:

a) No fault on bus undergoing transfer i.e. Bus incomer breaker lockout relay in reset

condition.

b) Residual bus voltage is above preset value.

c) Angular difference between residual bus voltage and incoming voltage is less than preset

value. (It may be noted that the angular separation between the voltages of the buses

under normal conditions before transfer will depend on the proximity of interconnection

between the 400 kv and 220 kv systems). The above transfer is a high-speed dead

transfer with a dead to time of about 2 cycles (40 milliseconds).

Page 27: BARC

27

2.8.5.2) Automatic fast transfer (UT to SUT):

After the tripping of UTs by protection, the loads fed from UTs will be transferred to SUT. Fast

transfer is initiated only in case of faults in UT, GT and interconnecting bus duct up to GCB. In

case of unit trip GCB will be opened and the power to UT buses is maintained through GT/UTs.

Advantages of fast transfer

The fast transfer schemes proposed in above will have the following advantages:

a) All motors will reaccelerate quickly and consequently all essential services will be

available immediately.

b) The voltage dips during change over will be of momentary nature only.

c) High inrush currents in individual motors as well as in auxiliary system are reduced.

d) Since the residual bus voltage does not go down perceptibly, the 415 V motor contactors

do not drop off during the change over sequence. Thus restarting of 415V motors after

the change over can be avoided.

e) There will be no perceptible flicker in the lighting systems, and hence fluorescent and

HPMV lamps, which are susceptible to voltage dips, will remain unaffected.

2.8.5.3 ) Automatic slow transfer:

In the event of failure of fast transfer the slow transfer can be carried out after the voltage of the

bus undergoing transfer goes below 20%.In case other system conditions demand the

disconnecting of loads during Slow transfer, the to the affected bus will be restored

automatically after disconnecting the loads. Restoration of the loads will be carried out

manually thereafter

In the event of electrical faults in start-up transformer or in the zone covering generator

transformer and unit transformers, buses fed by one of these sources are automatically

transferred to healthy source by simultaneous tripping of faulty source and closing of incomer

breaker from healthy source. The fast transfer scheme receives it initiating signals from the

lockout relays of GT, UT, SUT, 400 KV bus to which GT is connected, 220KV bus to which

SUT is connected etc. Auto transfer initiation from UT to SUT takes place on energisation of

Page 28: BARC

28

relay UTX by 86A2-I, 86A2-II and 400KV BUS diff. Relay 4 along with GCB 52 X contact.

Auto-transfer initiation from SUT to UT takes place on energisation of relay SUTX by SUT

protection main and backup lockout relays, 220 KV Bus diff. Protection and LINE-1, LINE-2

protection Lock Out relays as shown in the scheme.

The scheme proposed for fast transfer shall be high-speed dead transfer with a dead time of about

2 cycles (40 milli seconds) after considering the difference between closing time and opening

time of breakers. If the above minimum bus dead time of 2 cycles is not achieved with the

available close and trip time of 6.6 KV breakers, closing of the healthy side breaker shall be

delayed accordingly. This is achieved by Timers UT-T1 and SUT-T1.

Synchronism between the faulty supply and incoming supply (represented by the 6.6 KV bus

voltages) is checked by synchronism check relay (25) and if it is permissive, the fast transfer

shall take place. The fast transfer shall be completed within a set time; otherwise it will be

blocked. This is achieved through timer UT-T2 and SUT-T2.

In case fast bus transfer fails, the change over shall be achieved by slow bus transfer scheme

provided the voltage of affected bus has fallen below 20% of rated voltage This is achieved by

energizing relays C41-27-UTX, C43-27-UTX, C42-27-UTX, C44-27-UTX (UT to SUT transfer

initiation) and C41-27-SUTX, C43-27 SYTX, C42-27-SUTX, C44-27-SUTX (SUT to UT

initiation) through 2/27-3 of respective 6.6 KV bus and 52X & 86 contacts of supply breaker.

Subsequent to fast transfer, if both healthy and faulty source breakers remain closed

simultaneously, both breakers will be tripped instantaneously. This is achieved through relays

UT-C41X, UT-C43X, UT-C42X, UT-C44C (UT to SUT transfer) and SUT-C41X, SU-C43X,

SUT-C42X and SUT-C44X (SUT to UT transfer).

Page 29: BARC

29

2.8.5.4) Emergency transfer scheme

EMTR scheme is initiated for any of the following conditions:-

a) Loss of normal class-IV supplies to any one or more number of 6.6 KV class-III buses.

b) Loss of supply to 415 class-III buses due to 6.6 KV/433 V auxiliary transformer failures.

c) Failure of ups in class-II system/ups static bypass beyond preset duration.

d) Loss of class-II supply.

Sensing of the above conditions is done either by detecting under-voltage on the bus when there

is no bus fault or directly by checking equipment failure at EMTR logic diagrams.

2.8.5.4. A) 6.6 kV class-III, 415 class-III bus supply and feeder restoration

On initiation of EMTR, all motor feeder breaker and other predefined loads are tripped and

reclosing is blocked by under-voltage lockout relay. The closing of each feeder is blocked until

the blocking feature is reset by the breaker hand switch manually or by restoration of sequence

contact of emergency transfer panel. This sequence is required after permanent supply is

available to class-III buses.

The sequence is initiated by EMTR logic. This energises number of software timers, each of

which is set at a time step of 4 seconds. This contact of each timer will give permission to close

the corresponding class-iii feeder. After the last restoration of loads is done by timer it

automatically reset EMTR scheme.

2.8.5.4. B) EMTR initiation for 415 V class-III buses

Loss of voltage on any of the 415 V class-III buses initiates emtr. EMTR is also initiated on

tripping of any one of the 6.6 KV/433 V auxiliary transformers normally supplying to a 415 V

class-III bus. EMTR restores power supply to the affected 415 class-III bus by closing the

standby transformer secondary side circuit breaker after checking for conditions such as

healthiness of the bus, availability of breaker etc. After power supply is restored to the affected

bus, EMTR restores the loads in a predetermined sequence.

Page 30: BARC

30

2.8.5.4. C) EMTR initiation for 415 v class-II buses

Loss of voltage on class-II bus initiates EMTR. EMTR closes the class-III-class-II tie breaker

and restores supply to the affected class-ii bus. Prior to closing the class-III-class-II tie breaker,

emtr will check for healthiness of the bus, availability of breaker etc. EMTR will also start DGs

of that division but the dg will be manually connected to the relevant class-III bus by operator

action.

2.8.5.4. D) Emergency transfer panel

Two emergency transfer panels are provided for each unit of TAPP-3 and TAPP-4. One

emergency transfer panel is dedicated for each division. Emergency transfer scheme for one

division is completely independent from emergency transfer scheme for the other division.

Functions of any division emergency transfer scheme are independent of other division scheme

with no communication between them. Each EMTR has two redundant PLCs running in parallel

all the time.

The output issued to the field is generated by combining the output of both the PLCs in such a

manner that n case of failure of any one plc, required function is met by the other healthy plc.

For this purpose, normally open output contacts of the two PLCs are connected in parallel and

normally closed contacts are connected in series.

Page 31: BARC

31

3) POWER UPS SYSTEM

3.1) GENERAL DESCRIPTION

The ups system provides uninterrupted ac power to the loads connected to class-II buses. Class-II

system is divided into 2 divisions (i.e. bus D21 & bus D22) which are located in SABs.

Each division in CL-II power supply system consists of one power ups set and its associated

switchgear.

Each division derives its power from the following sources:

1. From 415 V class –III power supply through ups set under normal condition.

2. Through battery & ups inverter under class-iii power failure condition or under ups

rectifier failure condition.

3. Directly from 415 V class –III power supply system when power from ups is not directly

available.

Tie-breakers, one at each end, are provided between buses D21 &D22. Similarly tie-breakers,

one at each end are provided between buses D33 and D21 and also between D32 and D22.

For each power ups system, one 400 KV DC switchgear is provided in between power ups and

its associated power battery bank. The connection between power ups and 400v dc switchgear

through dc bus duct. Similarly, connection between 400v dc switchgear and power battery are

through dc bus duct. One 500 v dc boost charger for each division is provided for off-line boost

charging of power batteries. The boost charger is connected to the battery bank through the 400v

dc switchgear.

3.2) COMPONENTS OF SYSTEM:-

The static ups system consists of 4 systems:

1. Rectifier assembly

2. Inverter assembly

3. Static-by pass switch

4. Controller for the above 3 assembly

Page 32: BARC

32

Rectifier assembly:

It is used to charge battery and provide input supply to inverter. Two six pulse fully controlled

SCR bridges are employed to provide regulated dc supply.

Inverter assembly:

Converts dc output of rectifier into ac voltage with the help of IGBT based microprocessor

controlled PWM inverters.

Static- by pass switch:

Two back-to back thyristors for each phase are provided as static by-pass switch. All six

thyristors are fired simultaneously during emergency requirement. These switches enable to and

fro transfer of load from the inverter output to bypass supply without any interruptions of supply

to load.

Power battery:

Each power battery set is rated to supply entire class-ii power supply system loads of both the

divisions for a period of 30 minutes.

3.3) OPERATIONS:

Class –II power supply system derives the power from class-III power supply through ups set.

Both the tie breaker between buses D21 and D22 are kept open. In case of tie breaker between

class-III and class-II buses of a division, the breaker at class-III end is normally closed and

breaker at class-II end is open. Each ups and switchgear is designed to meet the entire class-II

system load requirement during normal and emergency condition.

Page 33: BARC

33

3.4) DESIGN BASIS:

Power ups systems are designed considering the following criteria:

1. The ups panel can operate satisfactorily for input voltage of 415v ± 10% and frequency

of 50 Hz ±5%. Output voltage and frequency of the ups will follow the input voltage and

frequency within a specified band and will be in synchronism with the input to facilitate

the changeover to static bypass and vice-versa.

2. The transient output voltage fluctuations are within ± 5%, steady state voltage is ± 1% of

set value and steady state output frequency variation is ± 0.5 % of set value.

3. Neutral of output transformer are solidly earthed.

4. Static by-pass facility is provided.

5. For calculation of ups rating, a design margin of around 25% is considered on the

maximum base load on ups.

6. For the purpose of sizing of ups, continuous operation of steady load and starting of

biggest motor (on the class-ii 415 v) with soft starter is considered. Simultaneous starting

of 4 ECCS valve motors on the remaining loads connected to the buses are considered.

7. While feeding 100% linear load, the output filter shall limit harmonic distortion

generated by ups within 4% and any single harmonic within 3%.

8. Under normal condition ups, will feed normal load and float charge its battery. Ups set

will also be designed such that it will be able to feed normal load while equalizing

charging its battery.

3.5) TECHNICAL PARTICULARS OF POWER UPS:

Normal ratings

Capacity 650 KVA

Voltage 415 V

Current 3*904

Maximum and minimum power factor for operation 0.18 lag to .85 lag at 650 Kva

Page 34: BARC

34

4) GAS INSULATED SWITCHYARD

The main output system consists of a 400 KV switchyard for evacuation of 1080MWe power

generated from the two units. The 400 KV switchyard will serve as an additional start-up source,

as Generator Circuit Breaker is provided between Generator and Generator Transformer. The

220 KV switchyard is provided to obtain start-up power for the station Auxiliary loads through

the start-up Transformer.

The purpose of the above separate switchyards at different voltage levels is mentioned below:

400 KV Switchyard:-

a) For evacuation of generated power

b) For obtaining start-up power supply via GT-UT Transformer.

220 KV Switchyard:-

a) For obtaining power supply via start-up Transformer / Start-up.

Gas insulated switchyard is provided for both the switchyards. In this type of switchyard, all the

switchgear components (like CTs, PTs, CBs etc.) and all live connections are enclosed in

metallic enclosures filled with pressurized SF6 gas. The complete switchgear will be housed in a

building with adequate ventilation and space for maintenance. The attached single line

diagrams– 1&2 show the layout of 400 KV & 220 KV switchyards.

4.1) TAPP-3&4 Grid

Both the 400 KV & 220 KV switchyards, the transmission lines & the transformer feeders

constitute the TAPP-3&4 grid.

The transmission lines from the switchyards are connected to the grids of Maharashtra State

Electricity Board, which in turn is further connected to the Electrical Power Networks of Gujarat,

Chhattisgarh Madhya Pradesh, Goa & Union territories and forms the Western regional grid.

Four Nos. of 400 KV lines & 2 Nos. of 220 KV lines are envisaged for TAPP-3&4 grid.

Page 35: BARC

35

Two Nos. of 400 KV lines will be terminated at 400 KV PADGHE--- substation at a distance of

108 KM and another two Nos. will be terminated at 400 KV Boisar sub-station situated about 10

KM from our site.

Regarding 220 KV lines, one number will be terminated at Boisar sub-station and another as tie

line to TAPS-1&2.

Fig: 4.1 Power Evacuation (400 kV) & 220 kV System

Page 36: BARC

36

4.1.1) 400 KV Switchyard:

The configuration of 400 KV switchyard is as follows

a) No of Feeder bays 4

b) No of GT bays 2

c) Bus coupler bay 1

d) Bus PT bay 1

e) Space for future bays 2(one for ICT and one for feeder)

Electrical equipments present are:

a) Part of main bus.

b) Bay bus

c) Current transformer

d) Voltage transformer

e) Isolators

f) Lightning arrestor

g) Earth switches

h) Wave traps

i) SF6/Air

j) Bushing.

4.1.2) 220 kV Switchyard:

The configuration of 220 kV Switchyard is as follows:-

a) No of feeder Bays = 2

b) No of Transformer Bays = 2

c) Bus – coupler bay = 1 Bus PT bay = 1

d) Space for future bays = 2 (One for 1 CT & one for line feeder).

Electrical equipments are similar to those mentioned for 400 KV in section 4.1.1

Page 37: BARC

37

Fig 4.2 – 400KV SWITCHYARD

Page 38: BARC

38

Page 39: BARC

39

Fig: 4.4 Respective positions of the four types of switchgear in terms of the current to be

broken and of the number of operations to be conducted.

4.2) DETAILS OF ELECTRICAL EQUIPMENT:

4.2.1) Capacitive Voltage Transformer:

The capacitive voltage transformer consists of a consists of a capacitive potential divider and an

inductive medium voltage circuit. The inductive part is immersed in mineral oil and hermitically

sealed with an nitrogen cushion inside a steel tank. One, two or three capacitor units are mounted

on the steel tank and are used as capacitor potential divider. They consist of condenser stacks

with paper foils as dielectric under mineral oil with a nitrogen gas cushion and are hermitically

sealed.

The CVT are provided on all the three phases. Each outgoing line from the switchyard has its

own potential transformer. Line potential transformers are of capacitor type. Capacitor potential

transformers are used with power line carrier communication system (PLCC) and are suitably for

a PLCC system frequency range of 40 KHz to 500 KHz.

Page 40: BARC

40

Type of CVTs:-

This line CVTs are of single phase type and each unit is connected between respective phase and

earth. Each CVT has 3 secondary winding and winding connection will be of phase to ground.

Function:

Each CVT has 3 secondary winding and used as:

1. Core-1: metering and synchronizing.

2. Core-2: back, over current protection and CVT fail protection.

3. Core-3: earth fault directional core protection.

4. CVT is used with power line carrier communication (PLCC).

5. CVT is used for carrier inter tripping with PLCC.

Table 4.1-Technical details of CVT used in 200 kv and 400 kv switchyard

200 kv 400 kv

Make BHEL, Bhopal BHEL, Bhopal

Installation Outdoor outdoor

Frequency 50 Hz 50 Hz

No. of secondary voltage 3 3

Rated phase voltage 200/√3 v 400/√3 v

Highest system voltage 245/√3 v 420/√3 v

Rated secondary winding and the method

of connection

First winding 110/√3v (star grounded) 110/√3 v(star grounded)

Second winding 110/√3v (star grounded) 110/√3 v(star grounded)

Third winding 110/√3v (star grounded) 110/√3v (star grounded)

Highest voltage capacitor 4840 pf 4656 pf

Rated voltage factor continuous 1.2 1.2

Rated voltage factor short time 1.5 1.5

Rated voltage factor time duration 30 sec 30 sec

Intermediate voltage capacitor 48400 pf 80000 pf

Page 41: BARC

41

4.2.2) SF6 gas circuit breaker:-

200 kV GIS circuit breaker (HB9 type) and 400 kV GIS circuit breaker (HB10 type)

Each CB comprises:

1. 3 metal clad breaker poles, each pole being actuated by its operating mechanism, one

supporting frame for the three poles.

2. Each pole is provided with one single break interrupt of the single pressure puffer type

with separate contact system for carrying continuous current and for arching whereby

control erosion is reduced to a negligible level ensuring long life.

3. Simplicity of interrupt operation: the moving contact with a compression cylinder, which,

during tripping operation generates the pressurized SF6 gas, required for arc quenching

4. Only minor over voltage of switching of small inductive currents, owing to optimized

interruption process which prevents current chopping.

Properties of SF6:

1. In pure form it is inert, exhibits exceptional thermal stability and has excellent arc

quenching properties as well as exceptional high insulating properties, one of the

most stable component, non-flammable, non-toxic and odorless.

2. Its density s more than that of air and heat dissipation in it is also much more than that

in air. At the atmospheric pressure the dielectric strength is about 2.4 times that of air

at about 3 kg/cm2 it is same as that of oil.

3. There is some decomposition of gas after the long periods of arcing. However such

decomposition is very little and has no effect upon dielectric strength and interrupting

capability. The solid arc product formed by arcing is metallic fluoride which appears

in the form of fine gray powder. This powder has high dielectric strength under dry

condition as existing in the breaker. A good quality absorbent is used in the apparatus

to remove most of the gaseous decomposed by-products so the level of this gaseous

by-product is kept very low.

Page 42: BARC

42

4.2.3) Lighting arrestor

Provided in 220 kV and 400 kV transmission line and power transformer lines in switchyard and

transformer yard for suppression strokes in transmission lines. A surge monitor counter is located

on the lighting arrestors on which 3 color band are there. Each of these bands has its own

significance. The criteria for different bands are as follows:

Green- healthy

Yellow-precaution

Red- first check counter, if counter is healthy, then clean insulator and if still red then

remove arrestor.

Surge monitor is provided on all the three phases and s located on the mounting structures of

lighting arrestors.

4.2.4) Current transformer

Constructional details

The CT is of the ring type. The straight conductors passing through the cores act as a

single turn primary winding.

The secondary winding on the cores are braced inside a retaining frame and are so

inserted with the screening cylinder in the cast aluminium enclosure.

The number of cores to be accommodated in an enclosure depends upon the primary

current, the accuracy class and the required specification.

The ends of secondary winding are brought into the terminal box through a gas tight

bushing plate.

CT consists of one or more magnetic cores on which the secondary turns are wound.

The inter layer insulation is made up of synthetic film.

The phase conductors of GIS form the primary winding.

The magnetic cores are mounted on a sheath like metallic armature, which ensures a good

distribution of the electric field.

The phase bar passes through this armature.

Page 43: BARC

43

The cores are carefully sealed in order to withstand the mechanical vibrations occurring

during the transmission and when in use in GIS.

Each winding may offer several ct ratio.

The CT terminal block consists of a barrier insulator with several outlets.

4.2.5) Electromagnetic potential transformer

They are used to transform high tension line voltage to low voltage in order to supply appropriate

voltage to measuring to instruments, meters, relays and other similar apparatus. They can be used

with the voltmeters for voltage measurement or they can be used in combination with current

transformer for wattmeter or watt-hour meter measurements. They are also used to operate

protective relays and similar devices.

Other features:

1. There are one set of VT for each 220 kV bus bars. Each set consists of three single phase

VTs. Each 220 kV VTs is of electromagnetic type having 400 VA. These have the ratios

of (220 kv/√3)/110/√3, 110/√3/110√3 volts and 0.2, 3p, 3p class respectively. These VTs

are star/ star connected to ground.

2. The 400 kv EMPT are also electromagnetic type with 100 va rating 0.2 and 3p and

400kv/√3:110/√3:110/√3:110/√3.

3. The active part of the VT is formed by a rectangular core consisting of one or more

magnetic steel sheet on which the secondary turns and high voltage windings are wound.

4. Pressurized sf6 gas insulates the high voltage from the conducting parts.

5. The inter layer insulation of the primary winding is made of a synthetic film. Selected

from its dielectric properties, its thermal stability and its low moisture absorbency.

6. The windings are manufactured and the active parts assembled in an air conditioned

workshops. Considerable care is taken to avoid pollution by dust particles. In order to

eliminate moisture a vacuum is created inside the enclosure and then it is dried before

filling the gas.

Page 44: BARC

44

Application:

EMPT are connected to potential coils of directional relay associated with bus differential

protection, synchronizing check relays and other metering and recording instruments.

Secondary core allocation:

The secondary terminals are brought and terminated in a terminal box fitted to the EMPT bottom

220 KV GIS EMPT. 3 cores are provided for each EMPT in 200 kV GIS.

220 KV GIS EMPT:

1. Core1: used for synchronization, bus voltage and frequency measurement, biling and

metering.

2. Core2: bus u/v protection, fuse failure protection, o/fd fluxing protection and o/c

protection.

3. Core3: directional grounding over current protection.

400 KV GIS EMPT:

2 cores are provided for each EMPT in 400 kV GIS

1. Core1: used for synchronization, bus voltage and frequency measurement, billing and

metering.

2. Core2: fuse failure, DR, under voltage protection

4.2.6) Disconnecting switches/Earthing switches

The DS and ES are motor operated and are capable of remote operation from control room as

well as local control panel. es are provided on the line, transformer and bus, EMPT isolators.

These are electrically interlocked with the man isolators so that they are not closed to the earth

when the system is charged. These may only be operated after de-energisation and in the absence

of current.

The DS are capable of making and breaking

Magnetizing current of the EMPT

Capacitive current of the bus and short connections.

Page 45: BARC

45

General features of the disconnectors (220 KV GIS)

Depending upon the geometrical course of the current path, 3 different types are used:

In-line disconnectors

L-shaped disconnectors

T-shaped disconnectors

General features of ES (220 KV GIS)

Two types of ES are available:

1. Maintenance type (slow operating): for earthing isolated sections of switch gear for

protection of personnel during maintenance and overhauls or erection.

2. High speed type (fast closing, slow opening):

For earthing high capacities cables, overhead lines.

For interrupting capacitive and inductive currents from parallel overhead lines.

For safely earthing even line equipment, if operated inadvertently.

4.3) SWITCHING SCHEME ADOPTED

The switching scheme adopted for both the 400 KV & 220 KV switchyards is Double Bus

scheme with bus-coupler and bypass isolators for transformer feeders only.

The general features associated with this scheme are as follows:-

a) Very good operational flexibility.

b) Total shutdown of switchyard due to bus-faults is ruled out as the same are of totally

enclosed type.

c) Transformer feeder breaker can be taken out for maintenance without affecting the

circuit.

d) Any main bus can be taken out for maintenance without affecting the associated circuits.

e) Future expansions are possible without prolonged shutdowns.

f) Reliability is more as most of the switchgear components are of totally enclosed type.

Page 46: BARC

46

4.4) OPERATION PRINCIPLE:

General organization of the GIS:

The GIS consists of the electro technical power equipment, the local control and the monitoring

equipment.

The GIS equipment is made up of bays.

Each bay contains:

1. all the devices attached to the wiring diagram busbar components, circuit breaker

2. and the various disconnectors,

3. The total control monitoring cubicle for the bay devices.

4. Local bay control panel

Control cubicle:

The local bay control panel contains;

1. the single phase mimic diagram of the bay,

2. the control switches of the switching devices,

3. the position indicating lamps of the switching devices,

4. the local remote mode selector switch,

5. the alarm panel board with signaling lamps.

The alarm panel signals any disturbance on:

1. SF6 gas monitoring

2. Circuit breaker monitoring,

3. Disconnectors monitoring,

4. Auxiliary supplies.

Bay control mode:

The control mode determines the control possibilities of the devices in each bay (disconnector,

earthing switch and circuit breaker).

Page 47: BARC

47

Priority:

Priority is normally given to continuity of supply. Operation is thus designed to respect this

priority. For example if a monitoring function reveals a failure, an alarm is triggered, but bay

operation is not interrupted.

Dependability:

Dependability is ensured by the interlocking functions between bay device operations. The

interlocking functions only allow operations without risk for personnel and equipment.

4.5) SF6 MONITORING:

As gas density is not an easily measurable physical quantity, the specific mass of gas in the

compartment is replaced by pressure brought to a reference temperature of 200 C expressed in

relative value and brought to an atmospheric pressure of 0.1013 MPa. The term “pressure”

means “corrected pressure brought to a temperature of 200 C and to an atmospheric pressure of

0.1013 MPa and characterizes the specific mass of gas in the specific conditions of use. Gas

pressure in the devices and GIS substation compartments determines breaking and insulation

withstand.

Compartment pressure is normally monitored at two levels:-

1. The first level indicates an acceptable pressure drop. It is placed slightly above minimum

operating pressure, the equipment retains its properties and normal operating conditions

remain unchanged. At this stage the operator must check and top up the compartment.

2. The second level indicates the minimum operating pressure. Under this pressure the

devices dot not retain their insulation properties and the circuit breaker does not retain the

breaking properties. Appearance of the second level includes automatic change in

operating conditions, and device locking or circuit breaker tripping. Operation conditions

are then determined by the chosen priorities. At this stage operating personnel must check

the monitoring circuits and if necessary place part of the substation out of operation and

top up the compartment.

Page 48: BARC

48

Table 4.2 -Ratings OF 220 KV & 400 KV GIS:

S. No Description Values for 220 KV Values for 400 KV

1 Rated voltage 220 KV 400KV

2 Rated frequency 50Hz 50Hz

3 Rated current (In) Feeder &

busbars

1250 A 162000

4 Rated breaking capacity

current (Icc)

40KA – 3s 162000

5 Rated short time withstand

current (Ith)

40KA 40KA

6 Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO

7 Rated insulation level

8 Lightning impulse (UW) 1050KV 1425

9 Power frequency (Us) 460 KV – 1min 520

11 Filling Pressure (Pn) 0.70 0.43

12 First stage alarm pressure 0.62 0.37

13 Second stage alarm pressure 0.60 0.36

14 Auxiliary voltage services

rated values.

15 Control devices 110V DC

16 Motor 110 V DC

17 Heating and Lighting 220 V (ac) - 50 HZ.

Page 49: BARC

49

4.6) HOT LINE WASHING SYSTEM FOR INSULATORS

Many electric networks are located near sources of extreme pollution. Contaminants like salt,

dust and sand collect on insulators. The contaminants when mixed with moisture in the air can

significantly reduce the effectiveness of the power line insulators. If the pollutants are not

cleaned off of the insulators, they will form conductive bands or dry bands. These conductive

bands enable leakage (also known as creep age) current to jump across the insulator dry band to

dry band. If too much time lapses without washing, there will ultimately be a short circuit to

ground called a flashover.

Flashovers are bad. Flashovers can destroy the power company’s apparatus and will produce a

momentary electric blackout which means the customer is out of electricity until the snag can be

corrected. These faults are usually brief in nature and will vary irregularly with no noticeable

pattern. This can be extremely frustrating to everyone involved in trying to resolve the crisis.

In TAPS 3&4 hot line washing is specifically designed to meet the particular requirements for

the 400/220 KV switchyards. Each switchyard has its own special features which includes a

variety of insulators performing different tasks. These have varying shapes, sizes and power

ratings and therefore demand differing design of insulator washing. Spray-rings can take form of

circular, square or rectangular rings having a number of specially designed nozzles mounted

them on them. The numbers of nozzles depend on the size and the rating of the insulators.

Each nozzle is accurately designed to achieve the required spray pattern and the direction onto

the insulator. Each spray-ring with its associated nozzles and supporting clamps is tailor made to

each type of insulator.

The spray-rings are arranged in washing zones to enable economic pump set and pipe work

sizing. It also provides identification of particular area in which insulators are washed together.

Zoning obviously takes into account various electrical consideration and is arrange to minimize

the possibility of flashover due to over-spraying.

Page 50: BARC

50

It is important to have fast actuating valves so that nozzles form the correct pattern instantly. The

use of low conductivity water is imperative in hot line insulator washing system. Our design

includes a monitoring system, which constantly measures the conductivity of the dm water

between the storage tank and the wash pumps. The maximum conductivity permissible is pre-set

and if exceeded stops the washing sequences instantly.

Operation of HLW is carried out manually from wash control panel. The frequency of wash is

determined by the rate of pollutant build up, which in turn depend upon the location of site and

time of years.

Wash zone allocation:-

It is not practical to wash all the insulators in a substation together, as this would require a large

pumping and pipe work system. For practical purposes insulators are washed n group or zones.

The zones may be a full bay of equipment that s a feeder bay or similar equipment within the

bay, or equipment which is very close together where it is impossible to wash one item of

equipment without over spraying onto the adjacent equipment.

Washing of overhead equipment should be carried out separately from washing ground mounted

equipment to prevent water flowing back from high –level equipment and out through the

nozzles for the ground equipment at the end of washing cycle.

The allocation of wash zone is therefore dependent on various criteria such as water

requirements, relative position of equipment and relative level of equipments. For tarapur,

wormald fire system recommend a total of 46 wash zones of the 400 KV equipment and 20 wash

zones for the 220 KV equipment.

Page 51: BARC

51

4.7) WHY GIS HOUSED INDOOR SWITCHYARD IS SELECTED FOR

TAPP-3 AND TAPP-4?

Reliability:-

In case of GIS equipment failure rate is negligible; faults due to external influence and climatic

pollution are nearly zero except at the termination.

Installation:-

For GIS simple as factory assembled equipment are delivered, whereas for conventional outdoor

it is time consuming and in case of indoor it is not only time consuming but also require very

large size enclosure which are difficult to construct.

Maintenance requirement:

GIS requires negligible and normally limited to operating mechanism maintenance whereas

conventional outdoor and indoor switch yard require continuous maintenance.

Hotline washing:

For GIS it is limited to outdoor line take-off bushings and CVTs. No separate DM water plant

required. In case of conventional outdoor regular hot line washing is required throughout the

year and separate dm water plant. In case of indoor switchyard some quantity of hotline washing

is required for outdoor insulated and wall bushings.

Safety:-

GIS is almost completely safe since all parts except termination are enclosed. In case of outdoor

and indoor switchyard all part exposed, personnel safety needs continuous attention.

GIS housed indoor switchyard was finally selected, GIS because of many advantages stated

above and indoor because of plant’s close proximity to Arabian sea which can leads to heavy

salt deposition on insulator and heavy rains during the monsoon.

Page 52: BARC

52

Page 53: BARC

53

5) ELECTRICAL PROTECTION

In generating stations, all electrical circuits and machines are subject to faults. A fault is

generally caused by the breakdown of insulation between a conductor and ground or between

conductors due to a variety of reasons. The result is a flow of excess current through a relatively

low resistance resulting in severe damage unless cleared quickly. The majority of systems and

devices in our stations are three phase which can experience faults of categories:

• Phase to ground

• Phase to phase

• Three phase, with or without ground.

In this module, we will discuss the purpose and essential qualities of electrical protection

schemes, the types of faults that can be expected and various means of protecting equipment

against them.

5.1) PURPOSE OF ELECTRICAL PROTECTION:

The function of protective relaying is to ensure the prompt removal from service of a faulty

electrical system component, thereby protecting that part and the remainder of the electrical

system from damage and electrical instability.

Every item of electrical equipment must have some form of electrical protection, which will

remove electrical power from the equipment in the event of it becoming faulty or overloaded.

This is necessary to ensure that:

a) Damage is minimized on the faulty equipment and any damage is not allowed to spread

to other equipment. For example, if a fault occurs in a motor, we want to isolate the

motor before damage occurs to the bus supplying the motor.

b) Unaffected equipment remains in service. Continuing on the previous example when a

fault occurs in a motor, we only want the motor to trip (not the entire bus), while still

providing power to the unaffected equipment on that same bus.

Page 54: BARC

54

c) Equipment operating limits are maintained. Again using the motor as an example, most

motors are designed to run in an overload condition for at least a short duration without

experiencing damage. However, we must remove the electrical power when the overload

gets too great, preventing damage to the equipment.

d) Electrical system stability is maintained. As discussed in the previous module on

generators, an un-cleared or slow-clearing fault will make the electrical system unstable.

Instability will cause the break-up of the electrical system until stability is obtained.

Inevitably there is loss of generation capability and disruption to large amounts of

electrical equipment.

5.2) ESSENTIAL QUALITIES OF ELECTRICAL PROTECTIONS:

Having looked at the fundamental purpose of electrical protection, we should cover the four

main building blocks that are used to meet these requirements:

Speed:

When electrical faults or short circuits occur, the damage produced is largely dependent upon the

time the fault persists. Therefore, it is desirable that electrical faults be interrupted as quickly as

possible. High-speed fault detecting relays can now operate in as little time as 10 milliseconds

and output relaying in 2 milliseconds. The use of protection zones minimized the requirement for

time-delayed relaying.

Reliability:

The protective system must function whenever it is called upon to operate, since the

consequences of non-operation can be very severe. This is accomplished by duplicate A and B

protections and duplicate power supplies.

Security:

Protections must isolate only the faulted equipment, with no over-tripping of unaffected

equipment. This is accomplished by the use of over-lapping protection zones.

Page 55: BARC

55

Stability:

It is defined as the quality of the protection system by the virtue of which the protective system

remains inoperative & stable under certain specified condition such as system disturbance,

through fault, transients etc. Design aspects like biased differential scheme & harmonic restraint

relay add to stability of the transformer protection system.

Selectivity:

The protective relaying should select the faulty part of the system & should isolate as far as

possible only faulty part from the remaining healthy system.

Discriminating quality of protective system enables it to distinguish between normal & abnormal

condition, and abnormal condition within protective zone & abnormal condition elsewhere.

Sensitivity:

The protection must be able to distinguish between healthy and fault conditions, i.e., to detect,

operate and initiate tripping before a fault reaches a dangerous condition. On the other hand, the

protection must not be too sensitive and operate unnecessarily. Some loads take large inrush

starting currents, which must be accommodated to prevent unnecessary tripping while still

tripping for fault conditions. The ability of relaying to fulfill the sensitivity requirement is

improved by the use of protection zones.

Redundancy:

To ensure operation of the protection under fault conditions redundancy can be obtained with the

following alternative scheme listed in the order of merit for availability and to ensure tripping.

1) One out of two : Highest

2) Two out of three : 2nd Highest

3) Single relay scheme: 3rd Highest

4) Two out of two : Lowest

To achieve complete redundancy, it may be necessary to provide, for each of the redundant

scheme, separate cores of instrument transformers, DC power source and communication

Page 56: BARC

56

channel and trip relays. Further, trip contact of lockout relays and trip relays. Further, trip contact

of lockout relays and trip coils of circuit breakers may have to be duplicated for each scheme to

the extent possible.

However, considering the cost involved in providing complete redundancy the following levels

of redundancy is adopted for the different protective scheme.

400KV Line:

Two main protections operating on different principles are provided. Each scheme has dedicated

core of current transformers and dedicated core of voltage transformer. DC supply for main 1&2

will be from 2 different DC sources, Circuit breakers will have two trip coils one for each main

protection will have a separate carrier channel. This will amount to one out of two schemes.

220 KV Line:

One main protection and one back up protection with dedicated core of current transformers, and

dedicated core of voltage transformer are provided. DC supply is from two different Dc sources.

Circuit breakers have two trip coils and separate trip relays for each scheme. The main protection

will have a separate carrier channel. This approximates to one out of two schemes. However, the

speed of clearing of back up protection will be slower than the main protection.

Transformer Protection:

One main protection and one back up protection with dedicated core of current Transformer are

provided. DC supply will be separate for main and back up protection.

Generator Protection:

The protection relays of generator are divided in to two groups Groub-1 and Group-2. Each

group is provided with separate DC supply and trip relays. These trip relays will operate on

separate trip coils of 400KV and generator breakers, and common trip coils of unit transformer

and Exciter field circuit breakers.

Page 57: BARC

57

The classifications of the various protections in two groups are done in such a way to ensure that

the availability of any group would be adequate to ensure tripping of generator under any fault

condition. Thus the arrangement will approximate to one out of two schemes. Further separate

control batteries and DC will feed each group supply boards. These batteries will have inter-

connection facility to avail supply to the DC board from other battery, when the associated

battery is not available.

Bus-Bar Protection:

Bus-bar protection is with main and check zone feature with dedicated core of current

transformers. Each zone will have one main protection. Check zone protection will be common

to all the zones. Each will have DC supply from different sources.

5.3) Types of Protective Relays:

Fig. 5.1 Trip Circuit

5.3.1) Electromagnetic relays:

These relays are either of attracted armature or induction cup or induction disc versions. They

possess mechanical inertia and therefore take longer time to operate as compared to static relays.

Besides, the burden imposed by these relays on the CT and VT are substantial. These relays are

provided as back-up relays for station electrical Auxiliary Systems.

Page 58: BARC

58

5.3.2) Static relays:

These relays use solid state devices to process the input signals in analog form. The burdens

imposed on CTs by these relays are very low compare to Electromagnetic relays. It is possible to

obtain higher speed of operation with static relays. Static relays are already in use in various

power stations of the country and are gradually replacing Electro-magnetic version, which are

being taken out of manufacturing range by most of the manufacturers.

5.3.3) Digital relay:-

Digital protection relays introduced a step change in technology. Microprocessors and

microcontrollers replaced analogue circuits used in static relays to implement relay functions.

Compared to static relays, digital relays introduce A/D conversion of all measured analogue

quantities and use a microprocessor to implement the protection algorithm. The microprocessor

may use some kind of counting technique, or use the Discrete Fourier Transform (DFT) to

implement the algorithm. However, the typical

Microprocessors used have limited processing capacity and memory compared to that provided

in numerical relays. The functionality tends therefore to be limited and restricted largely to the

protection function itself.

5.3.4) Numerical relays:

These are programmable version of solid state relays based on digital signal processing by

microprocessors. The main advantage is in its modular architecture allowing the same unit to be

programmed in to different types of relays. Processing is carried out using a

Specialised microprocessor that is optimised for signal processing applications, known as a

digital signal processor or DSP for short. Digital processing of signals in real time requires a

very high power microprocessor. In addition, the continuing reduction in the cost of

microprocessors and related digital devices (memory, I/O, etc.) naturally leads to an approach

where a single item of hardware is used to provide a range of functions (‘one-box solution’

approach). By using multiple microprocessors to provide the necessary computational

Page 59: BARC

59

performance, a large number of functions previously implemented in separate items of hardware

can now be included within a single item.

Figure 5.2 typical numerical relay

Page 60: BARC

60

6) TRANSFORMERS AND ITS PROTECTION

Transformers:

For each 500 MWe unit, protections for the following transformers are considered.

A) Generator transformer (GT)

B) Unit transformer (UT)

C) Start-up transformer (SUT)

6.1) TRANSFORMER FAULTS:

Transformer faults are generally classified into following categories:

a. Winding and terminal faults

b. Core faults

c. Tank and transformer accessory faults

d. On–load tap changer faults

e. Abnormal operating conditions

f. Sustained or unclear external faults

Winding faults

A fault on a transformer winding is controlled in magnitude by the following factors:

a) source impedance

b) neutral earthing impedance

c) transformer leakage reactance

d) fault voltage

e) winding connection

Core Faults

A conducting bridge across the laminated structures of the core can permit sufficient eddy-

current to flow to cause serious overheating. The bolts that clamp the core together are always

insulated to avoid this trouble. If any portion of the core insulation becomes defective, the

resultant heating may reach a magnitude sufficient to damage the winding.

Page 61: BARC

61

Tank Faults

Loss of oil through tank leaks will ultimately produce a dangerous condition, either because of a

reduction in winding insulation or because of overheating on load due to the loss of cooling.

Overheating may also occur due to prolonged overloading, blocked cooling ducts due to oil

sludging or failure of the forced cooling system, if fitted.

6.2) TRANSFORMER PROTECTION:

Transformers, of course, are somewhat more difficult to provide electrical protection than a

section of solid electrical bus. This is such because:-

a) Transformers have high magnetizing inrush currents when energized.

b) Transformers can vary the ratio of input to output current via off-load and under-load tap-

changers.

c) The input and output current is often not the same phase relationship (sometimes has Y.∆

transformation)

d) Transformers will be affected by over-fluxing (high volts/hertz).

e) They will be affected by over-temperature.

To examine transformer protections, we will build on the similarity to bus protections just

discussed. Transformers utilize duplicate protections and the protection zone (similar to buses)

can been seen in the figure below

Figure 6.1 – Transformer protection zone

Page 62: BARC

62

6.2.1) Transformer Instantaneous Over-Current Protection:

Fuses commonly protect small distribution transformers typically up to ratings of 1MVA at

distribution voltages. In many cases no circuit breaker is provided, making fuse protection the

only available means of automatic isolation. The fuse must have a rating well above the

maximum transformer load current in order to withstand the short duration overloads that may

occur. Also, the fuses must withstand the magnetizing inrush currents drawn when power

transformers are energized. High Rupturing Capacity (HRC) fuses, although very fast in

operation with large fault currents, are extremely slow with currents of less than three times their

rated value.

Transformer ratings Fuse

KVA Full load current(A) Rated current(A) Operating time at

3*ratings (s)

100 5.25 16 3

200 10.5 25 3

315 15.8 36 10

500 26.2 50 20

1000 52.5 90 30

Table 6.1- Typical Fuse Ratings

Plain over current and earth fault protection utilizing IDMT relays are used primarily to protect

the transformer against the effects of external short circuits and excess overloads. The current

settings of the protection must be above the permitted sustained over load allowance and below

the minimum short circuit current. The ideal characteristic is the extremely inverse (CDG14) as

it is closely approximates to the thermal curve of the transformer.

The protection is located on the supply side of the transformer and is arranged to trip both the

HV and LV circuit breakers. In many cases the requirements for protecting the transformer and

maintaining discrimination with similar relays in the remainder of the power system are not

Page 63: BARC

63

compatible. In these circumstances, negative sequence filter protection or under voltage blocking

may be used to obtain the desired sensitivity.

High set overcurrent cut-Off:

On small transformers where the main protection is provided with overcurrent devices and where

the transformer is fed from one end only, a high set instantaneous relay is utilized to provide

protection against terminal and internal winding faults.

The relay is set to be above the short circuit level on the secondary (load ) side of the transformer

and below that for a terminal fault on the primary (supply)side of the transformer.

On choosing the type and setting of the high set relay, it is important to consider the magnetizing

inrush currents under normal switching, offset fault currents and starting currents of motors. The

first two problems can be overcome by using a relay sensitive only to fundamental frequency

currents, while the third is overcome by setting the relay above the maximum starting current

level.

6.2.2) TRANSFORMER DIFFERENTIAL PROTECTION:

6.2.2.1) Principle of Transformer Differential Protection:

Similar to bus protections, transformers are protected by differential relays. Inter-winding faults

(short circuits) and ground faults within power transformers can be detected by this protection

scheme. Failure to detect these faults and quickly isolate the transformer may cause serious

damage to the device.

A differential relay is basically an instantaneous over current relay that operates on the difference

of current flowing into and out of the protected zone. For transformers the differential protection

(Figure 6.2) is basically the same as that for a bus but there are certain differences that we will

look more closely at. These differences are a direct result of three characteristics or a

transformer.

Page 64: BARC

64

a) A transformer has a turns ratio so the current in is not really equal to the current out. The

current transformers are not likely exactly matched to the transformer turns ratio so there

will always be an unbalance current in the operating coil of a transformer differential

relay.

b) Transformers require magnetizing current. There will be a small current flow in the

transformer primary even if the secondary is open circuited.

c) A transformer has an inrush current. There is a time period after a transformer is

energized until the magnetic field in the core in alternating symmetrically. The size and

the length of this inrush depend on the residual field in the core and the point in the ac

cycle the transformer is re-energized. In large transformers in might be ten or twenty

times the full-load current initially and it might take several minutes to reduce to

negligible values.

Transformer differential relays have restraint coils as indicated in Figure below. The value of the

operate current has to be a certain set percentage higher than the current flowing in the restraint

coils.

Figure 6.2

The current is very high. The restraint coils also prevent relay operation due to tap changes,

where the ratio of transformer input to output current can continuously vary. One other item

included in transformer differential relays but not shown in the diagram is second harmonic

restraint.

Page 65: BARC

65

When transformers are first energized there is over-fluxing (saturation) of the core and the large

inrush energizing current has a distorted waveform. This waveform is described as having high

second harmonic content. The transformer differential relays make use of this known fact and

add in extra restraint when it detects this second harmonic. This extra feature prevents the

transformer from tripping due to magnetizing current when being energized, but does not add

any time delay.

Because the differential relay will not operate with load current or faults outside the protected

zones (through faults), it can be set to operate at a low value of current thereby giving rapid

operation when a fault occurs. There is no need to time delay the operation of the relay and

therefore a fast acting type of relay can be used.

6.2.2.2) Basic Considerations for Transformer Differential protection relay settings

a) Line current transformer primary ratings:

The rated currents of the primary and the secondary sides of a two winding transformer

will depend on the MVA rating of the transformer and will be in inverse ratio to the

corresponding voltages. For three winding transformers the rated current will depend on

the MVA rating of the relevant winding. Line current transformers should therefore have

primary ratings equal to or above the rated currents of the transformer windings to which

they are applied.

b) Current transformer connections:

The CT connections should be arranged, where necessary to compensate for phase

difference between line currents on each side of the power transformer. If the transformer

is connected in delta/star as shown in figure, balanced three phases through current

suffers a phase angle of 30 degree which must be corrected in the CT secondary leads by

appropriate connection of the CT secondary windings.

When CTs are connected in delta, their secondary ratings must be reduced to 1/ √3

times the secondary rating of star connected CTs, in order that the currents outside the

delta may balance with the secondary currents of the star connected CTs.

Page 66: BARC

66

c) Inter posing CTs (ICT’s) to compensate for mismatch of Line CTs:

Besides their use for phase compensation, interposing CTs may be used to match up

currents supplied to the differential protection from the line CTs for each winding. The

amount of CT mismatch which a relay can tolerate with out mal-operation under through

fault conditions will depend on its bias characteristic and the range over which the tap

changer can operate. If the combined mismatch due to CTs and tap changer is above the

accepted level, then interposing CTs may be used to achieve current matching at the mid

point of the tap changer range.

For the protection of two winding transformers interposing CTs should ideally match the

relay currents under through load conditions corresponding to the maximum MVA rating

of the transformer.

6.2.3) Transformer Gas (BuchHolz) Relay:

The transformer gas relay is a protective device installed on the top of oil-filled transformers. It

performs two functions. It detects the slow accumulation of gases, providing an alarm after a

given amount of gas has been collected. Also, it responds to a sudden pressure change that

accompanies a high rate of gas production (from a major internal fault), promptly initiating

disconnection of the transformer. An incipient fault or developing fault usually causes slow

formation of gas (the process of gas formation is discussed later in this section).

Examples of incipient faults are:

• Current flow through defective supporting and insulating structures;

• Defective joints at winding terminals causing heating;

• Minor tap changer troubles; and

• Core faults.

A major fault is one that results in a fast formation of a large volume of gases. Examples of such

faults are:

• Shorts between turns and windings; and

• Open circuits, which result in severe arcing.

Page 67: BARC

67

Failure to disconnect the transformer under fault conditions can result in severe equipment

damage from high gas and oil pressures and the effect of the electrical fault.

Figure-6.3 Buchholz relay mounting arrangement

6.2.3.1) Generation of Gas Due to Faults:

Internal transformer electrical faults result in the production of ionized gases. A significant

volume of gas is frequently generated in the early stages of a fault by rapid oil breakdown. The

generated gases rise through the oil to the top of the equipment and collect in the gas relay.

Once a sufficient volume of gas has accumulated, an alarm is generated by contacts within the

gas relay. In the event of a gas alarm, it is necessary to sample and analyze the gas being

generated. This analysis, together with knowledge of the rate at which gas is accumulating, will

determine the proper course of action. If a fault is thought to be developing, the device must be

removed from service. Ignoring this early warning sign can lead to severe equipment damage as

the fault progresses.

Page 68: BARC

68

6.2.3.2) Operation of a Transformer Gas Relay:

A typical transformer gas relay consists of two chambers, each performing a distinctive function.

The relay assembly consists of a gas accumulation chamber mounted directly over a pressure

chamber. The accumulation chamber collects slowly produced gases. A float located in this

partially oil-filled chamber moves as the gas volume increases. It operates an alarm switch when

the amount of gas collected reaches a specified level. An indicator coupled to the float also

provides a means to monitor the rate at which gas is being generated.

Sudden pressures, such as oil circulating pump surges, are normal operating events and the relay

must be set to ride through them. In practice, it is necessary to make sure the relay is set to

operate at about 7 KPa (1 psi) above the maximum oil circulating pump surge pressure.

Dangerously high pressure increases from major faults are relieved by an explosion vent on the

top of the transformer tank. This is basically a diaphragm sealed pipe with its open end directed

away from the transformer. A significant increase in pressure bursts the diaphragm and

discharges gases and hot oil with a possibility of resulting fire.

6.2.4) WTI and OTI Protection:

Heat is generated in a power transformer by current flow in the primary and the secondary

windings as well as internal connections due to I2R losses. At low loads, the quantity of heat

produced will be small. But, as the load increases, the amount of heat becomes significant. At

full load, the windings will be operating at or near their design temperature. The nameplate on a

transformer will provide information on the maximum allowable in-service temperature rise for

its windings and connections and will indicate what method of cooling is employed to remove

the heat generated under load. A temperature of about 105°C is considered to be the normal

maximum working value for large power transformers, based on an assumed maximum ambient

temperature of 40°C.

Page 69: BARC

69

The winding temperature is sensed and indicated by a winding temperature gauge/alarm

assembly.

6.2.4.1) OTI and WTI at TAPS:

Similar Indicators are used for oil temperature indication and winding temperature indication.

The instrument operates as OTI when its sensing bulb is mounted in an oil filled pocket located

in the hottest oil of an oil immersed transformer.

The instrument operates as WTI, when a proportionate load current of the transformer is passed

through the thermal image device; the instrument integrates the simulated temperature rise of the

thermal image device and the top oil temperature measured by the sensing bulb.

6.2.5) Overfluxing Protection:

Increase in power frequency voltage causes increase in working magnetic flux, thereby increases

the iron loss and magnetizing current. The core and core bolt get heated and the lamination

insulation is affected. Overfluxing protection is provided for generator transformer and feeder

transformer where a possibility of over fluxing due to sustained over-voltages exists. The

reduction in frequency also increases the flux density and consequently, it has the similar effects

as those due to over-voltage.

The expression for flux in a transformer is given as:

Φ α V / f

Where, Φ = flux, V = applied voltage, f = frequency

and all are p.u. values. When V/f exceeds unity, it has to be detected. Usually 10% of

Overfluxing can be allowed without damage. If V/f exceeds 1.1, overfluxing protection operates.

Overfluxing does not require high speed tripping and hence instantaneous tripping is undesirable

when momentary disturbances occur. But the transformer should be isolated in 1-2 min if over

fluxing persists. The Overfluxing setting is IDMT in general cases.

Page 70: BARC

70

6.2.6) Transformer Ground Fault Protection:

Earthfault protection of transformer can be in one or more types such as:

a) Residually connected earth fault protection.

b) Neutrally connected earth fault protection.

c) Restricted earth fault protection.

6.2.6.1) Residually Connected Earthfault Protection:

Delta windings and ungrounded star windings are best protected by zero-sequence overcurrent

relays (Earth fault relays) supplied by CTs situated at the terminals of power transformer.

Such relay can only operate for a ground fault in the transformer winding since it does not have

an earth connection through which it can supply an external fault.

The relay is usually instantaneous but must be of high impedance type if supplied with residually

connected CTs in the three phases. The high impedance relay is required to prevent wrong

operation of the relay on false residual currents during heavy external fault between phases due

to transient differences in the CT outputs. An ordinary overcurrent relay is acceptable if it is

supplied by a core-balance type CT because in this case, the magnetic conditions of the CTs are

the same for all the three phases.

6.2.6.2) Neutral Connected Earthfault Protection:

The relay is connected across the secondary of a CT whose primary is connected in the neutral to

earth connection of a star connected transformer. The fault current finds a path through the earth

and earth to neutral connection of the transformer.

The magnitude of the earth fault current is dependent on the type of earthing and the location of

the fault.

In both the above types of protection the zone of protection can not be accurately defined. The

protected area is not restricted to the transformer winding alone. The relay may sense an

earthfault beyond the transformer winding depending upon position of the source.

Page 71: BARC

71

Hence, such protection is called unrestricted earthfault protection. In residually connected

earthfault relays where the zone of protection is not restricted to transformer winding only and in

neutral connected earthfault relays, IDMTL earthfault protection co-ordinated with down stream

is to be provided.

6.2.6.3) Restricted Earthfault Protection:

When the primary winding is delta connected or star connected without neutral earthing,

earthfaults on secondary side are not reflected on the primary side as the zero sequence

impedance between the primary and secondary is infinite (i.e., open). In such cases an earthfault

relay connected in the residual circuit of 3 CTs on primary side will operate on internal faults in

primary winding only. During external ground fault the sensitivity of low impedance relay is

limited by the fact that the magnetizing current of the neutral CT is three times that of each of the

If this resistance balance does not exist, it can theoretically be remedied by adding resistance on

the neutral CT side, but this is not the practice because the balance would not hold during

transient conditions or if the neutral CT saturates. The proper solution is to use a stabilizing

resistance in series with low impedance relay or to use high impedance relay.

This protection is based on high impedance differential principle, offering stability for any type

of fault occurring outside the protected zone and satisfactory operation for faults within the zone.

Page 72: BARC

72

6.3) CHARACTERISTIC TRANSFORMER FAULTS:-

Table – 6.3 transformer faults

Type of faults Causes Effects Actuation of

Buchholz relay

Major components

of gases evolved

High energy

discharges

(arcing)

Short circuits in

the windings.

External short

circuit from parts

at potential to

earth.

Breakdown

between the

windings.

Breakdown

through the oil

between the bare

conductors

Pyrolytic

decomposition

of insulating

oil.

Formation of

oil carbon.

Decreases in

the flash point

of oil.

Suddenly

actuations

Methane, Hydrogen

& Acetylene

(Carbon monoxide if

solid insulation is

also involved.)

Continuous

sparking at

breaks

Bad contact

action of

connections to

metallic parts

with floating

potential.

Slight

decomposition

of insulating oil

Actuation after a

long period

Hydrogen,

Acetylene, Methane

is less than in (a)

Discharges

between selector

contacts

Due to surfaces

layer of foreign

materials

High energy

partial

discharges with

tracking

Poor

impregnation.

Presence of

cavities in the

insulation.

Electrical

overstressing of

the insulation.

Ionization

processes.

(Excitation and

dissociation of

hydrocarbon

molecules by

collision with

high-energy

electrons, ions,

atomic

hydrogen etc.)

Low energy

partial

Poor

impregnation or

Ionization

Methane, Hydrogen.

Page 73: BARC

73

discharges

without tracking

cavities in the

insulation

processes

Thermal faults:

Overhauling to

temperature

between 150°C

& 300°C (Hot

spot).

Excessive

magnetic

losses.

Insufficient

cooling.

Slight

decomposition

of oil.

After a long

period

Hydrogen,

Methane,

Ethylene,

(Ethylene

predominates),

No Acetylene.

Local

overheating

(300°C to

1000°C)

High circulating

currents in the

core

Decomposition

of oil with

formation of oil

carbon

After some time

Hydrogen,

Methane,

Ethylene,

(Ethylene

predominates),

No Acetylene.

Local

overheating

beyond 1000°C

Shorting links

between core

laminates

Decomposition

of oil with

formation of oil

carbon.

Destruction of

organic

insulation.

Melting spots,

Core burn,

melted

conductors and

scorching

points.

Actuation of

relay after

accumulation of

little quantities

of gases.

Hydrogen,

Methane,

Ethylene,

(Ethylene

predominates),

Considerable

amount of

Acetylene.

6.4) CONDITION MONITORING OF TRANSFORMERS

It is possible to provide transformers with measuring devices to detect early signs of degradation

in various operator can make a better judgement as to the frequency of maintenance, and detect

Page 74: BARC

74

early signs of deterioration that, if ignored, would lead to an internal fault occurring. Such

techniques are an enhancement to, but are not a replacement for, the protection applied to a

transformer. A typical condition monitoring system for an oil immersed transformer is capable of

monitoring the condition of various transformer components as shown in Table 5.3

Table 6.4- condition monitoring of transformer

Page 75: BARC

75

6.5) CHOICE OF TRANSFORMERS AT TAPS-3&4

6.5.1) why such GT is chosen?

Type: 3 Nos. of single-phase transformers

OFAF, OFAN (60%)

YNd 11,

210 MVA (1Phase rating)

Reasons for adopting three single phase units:

a) No weight and transport height constraints:

A single unit of 3 phases, 630 MVA capacity would be immense in size and weight and,

if any attempt is made to decrease the size, height has to be increased for the same flux

density of core. Further the cooling arrangement will have to be very elaborate for entire

coverage

b) Easy repair /replacement of single unit;

As amount of oil in one unit is less compared to single unit, replacement / draining of oil

will take less time and thereby reduce the total downtime. Further, with a spare single

unit available, the downtime is reduced, in case of shutdown.

c) No common failure probability:

No question of transformer phase to phase faults, as the units are physically separate.

Each unit has its own cooling arrangement. Therefore, cooling unit failure of one unit

will not lead to total outage; the total units can remain in service at reduced power.

(OFAN-80%, ONAN = 60%). Easy identification of phase to earth, inter-turn faults as

each unit has its own buchholz relay.

Page 76: BARC

76

d) Because of single unit and adoption of OFAF type of cooling these units will have a

OFAN rating (= 80 % of OFAF rating) and ONAN rating of 60%, unlike single 3 Φ units,

which has only one rating.

As large area is available for heat dissipation for each unit compared to a single unit.

Use of radiators for fanning purpose, even without fans, oil flow through the radiators

will provide 60 % cooling.

6.5.2) why such Unit-transformer is chosen?

Type: 21/ 6.9 Dy1

ONAF/ONAN;

35 MVA each

Nos. =2

Reasons for such configuration:

a) Approximate station consumption 70 MVA at full power operation Two Nos. of 35 MVA

UTs units are provided to meet station load in case of SUT outage. However, if SUT is

available, effectively one UT is enough for Div-1. Therefore, providing two Nos., we

have redundancy in case of one UT failure.

b) Cost studies indicate that there is marginal difference in price between 2 Nos. of 35 MVA

and one single unit of 70 MVA. Therefore, above redundancy is justified.

c) Above logic does not apply to SUT because of the high cost difference as one additional

GIS bay will be required.

d) UT-LVs are provided with bus-duct compared to cables provided in 220MWe plants. All

the advantages of bus-duct are available.

Page 77: BARC

77

UTs are of single secondary type and bus trunking is done and two breakers are provided. One

feeds div-1 in the normal case and Div-2 in case of SUT outage. However, the increase in fault

MVA because of decreased percentage impedance compared to a two secondary winding

transformer needs to be seen i.e. cost studies for a dual secondary transformer and a single

secondary transformer with bus-trunking and two breakers. The voltage regulation is, however,

better in the chosen design.

6.5.3) why such type of SUT is chosen?

SUT is a 3 limb design, three winding transformer (70/35/35 MVA, 220/6.9/6.9 kV and an

unloaded tertiary delta for suppression of harmonic currents).

The total maximum demand of power for auxiliary system has been worked out to be 65.2MVA

based on the load schedule and load estimation on 6.6kV and 415V plant Electrical Auxiliary

System Based on this, for each unit one three winding 70MVA/40MVA ONAF/ONAN SUT has

been selected, thereby keeping a margin of 7.34%. While selecting the start-up transformers, due

consideration is given for choosing the percentage impedance in connection with fault level and

regulation of transformer. The percentage impedance of SUTs have been selected as 13%

between primary and each of secondary windings and 26% between the two secondary windings

on 35 MVA base. The SUTs are capable of withstanding short circuit forces due to a terminal

fault on one winding with full voltage maintained on other windings.

The salient features of SUTs are as follows:

a) Double wound secondary winding to reduce the fault level on 6.6k buses.

b) Vector group (Y-yo) to maintain synchronism with unit Auxiliary Transformers to permit

Auto Transfer.

c) Unloaded tertiary winding for suppression of third harmonics.

d) The SUTs are located close to turbine building and connected to 6.6kV switchgear

through bus duct to ensure high reliability and low fire hazard.\

Page 78: BARC

78

e) The percentage impedance of SUTs have been selected as 13% between primary and

each of secondary windings and 26% between the two secondary windings on 35 MVA

base.

f) Both the windings on LV sides have more or less equal prospective loading & hence

OLTCs on HV windings can maintain 6.6 kV voltages on 6.6 kV buses effectively. The

ranges have been selected as +8.75% to –11.25% to take care of secondary voltage

variation in 16 steps of 1.25% each.

6.6) PROTECTION OF TRANSFORMER AT TAPS-3&4:

One main protection and one back up protection with dedicated core of current Transformer are

provided. DC supply will be separate for main and back up protection

6.6.1) Protection of GT (Generator Transformer):

Numerical relay is provided for main protection:

Table -6.5 protection of GT

SR.NO. NATURE OF FAULT MAIN PROTECTION BACK-UP

PROTECTION

REMARKS

1. Phase to phase fault

HV side 87T 87GT

21G and 51V

LV side 87T 87GT

21G and 51V

87GT, 87T,

21G

2 Phase-to-earth fault

HV side 87T

64GT

87GT

51N

Page 79: BARC

79

LV side 64G1

64G2

64D

3 Internal fault (Including

incipient fault)

63

Abnormal over-loads OTI

WTI

Over-fluxing protection 99G1 99G2

Fig.6 .4- Drawing showing Protection scheme of GT

Page 80: BARC

80

6.6.2) Protection for UT:

Table -6.6 Protection for UT

S.NO NATURE OF FAULT MAIN

PROTECTION

BACK-UP

PROTECTION

REMARKS

1 Phase to phase fault

HV side 87UT 51UT

87GT

LV side 87UT 51UT

87GT

2 Phase-to-earth fault

HV side 64G1*

64G2

64D

87GT

LV side 64UT 51SN

3 Internal fault (Including incipient

fault)

63 Indicates two

stages, stage-1

for alarm &

stage-2 for trip

4 Abnormal over-loads OTI

WTI

5 Over-fluxing protection 99G1 99G2*

Page 81: BARC

81

6.6.3) Protection for SUT:

Table- 6.7- Protection of SUT

S.NO NATURE OF FAULT MAIN

PROTECTION

BACK-UP

PROTECTION

REMARKS

1 Phase to phase fault

HV side 87SUT 67

LV side 87SUT 67

2 Phase-to-earth fault

HV side 87SUT 67N

64SUT (HV)

LV side 64SUT (LV) 51SN

3 Internal fault (Including incipient

fault)

63 Indicates two

stages, stage-1

for alarm &

stage-2 for trip

4 Abnormal over-loads OTI

WTI

5 Over-fluxing protection 99SUT

Page 82: BARC

82

7) GENERATOR AND GENERATOR PROTECTION

The generator serves to generate the electric power required in the power plant, converting

kinetic energy supplied by the turbine into electric energy. The efficiency lies between 98% and

99% and is thus very high. The inherent losses are dissipated by various cooling systems. The

description refers to a two-pole turbine generator driven at a speed of 50 Hz. (3000 rpm)

7.1) REQUIREMENT AND FUNCTIONS:

The generator is able to supply a rated apparent power of 659 MVA at a cosine (Φ) of 0.85 under

rated conditions. The voltage is 21 KV and is variable over a range of ±5%. The capability

curves show the operational limit of the generator. The internal losses are to be dissipated with

the aid of the two cooling systems, which use hydrogen and primary water. The shaft seals in the

stator frame end shields ensure that no hydrogen can escape when the generator is at rest or in

turning operation. Electrical and mechanical forces and all types of vibration are controlled

during operation and malfunction. These include, for example, terminal short-circuits, clearing

close-in short circuit and incorrect synchronization. A mechanical generator protection system

prevents inadmissibly high stressing of the individual components. An electrical generator

protection system is provided which is explained in detail later.

7.2) DESCRIPTION:

7.2.1) Overall System Layout:

The generator can be divided into the following circuits and systems:

a) Electro-magnetic circuit.

b) Primary water-cooling system

c) Hydrogen cooling system

d) Seal oil system

Page 83: BARC

83

The purpose of each of the above mentioned system is mentioned below:

Excitation of the generator is provided by a rotating rectifier set which is rigidly coupled to the

rotor shaft. Generator voltage regulation is performed by a THYRISTOR voltage regulator. The

rotor is supported by end-shield bearing equipped with a shaft jacking oil system.

The primary water supply system ensures that the stator winding including phase connections

and bushings can be directly cooled with primary water.

The rotor winding is directly cooled with hydrogen. The hydrogen supply system is also used to

dissipate the core losses, friction and stray losses.

The seal oil supply system prevents the escape of hydrogen from the generator frame through the

shaft glands.

7.2.2) Layout of Individual System:

Electro – Magnetic Circuit:

Excitation current is supplied to the rotor winding via two axial semicircular conductors. The

rotor winding induces the stator current in the stator winding which is led out of the generator

frame through phase connectors via 6 bushings.

Primary Water (PW) cooling System:

The DM water used for the stator windings, phase connectors and bushings is called primary

water to distinguish from the secondary –side coolant (raw water, condensate etc).

The primary water is circulated in a closed cycle and transfers the heat absorbed to the secondary

water in the primary water coolers. The pump is supplied with hot water from the water tank. It

pumps the water to the generator via the cool

Page 84: BARC

84

Hydrogen Cooling Circuit:

Hydrogen is circulated in the generator interior in a closed circuit by a multi-stage axial-flow fan

arranged on the rotor on the drive side. The fan draws hot gas from the air gap and delivers it to

the coolers where it is cooled and divided into three flow paths after each cooler section:

Flow path –I is directed to the rotor on the turbine side underneath the fan hub to cool the turbine

–side rotor half.

Flow path-II is directed from the coolers to the individual frame compartments to cool the core.

Flow path-III is directed to the exciter-side stator-end winding via cross-over ducts in the casing

to cool the exciter-side rotor half and the end sections of the core.

Having fulfilled their cooling function, the three flows are directed to the air gap where they are

mixed and returned to the fan and thus to the cooler.

The hydrogen temperatures are controlled automatically by varying the secondary cooling water

flow through H2 coolers to maintain a uniform generator temperature level at various load and

secondary cold-water temperature.

Choice of Hydrogen gas as cooling medium:

The heat dissipating capacity of Hydrogen is eight times higher than that of air. For effective

cooling, the hydrogen in the generator is pressurized. 4 bar of hydrogen pressure is maintained.

Any possible moisture in the hydrogen in the generator is removed by the gas dryer. Hydrogen

may form explosive gas mixtures, has to be handled carefully thus. It should be 99.9% v/v. The

remaining 0.1% v/v shall be free of corrosive contaminants: traces of ammonia (NH3) and

Sulphur dioxide (SO2) shall not be detectable by any analysis.

7.3) DESIGN FEATURES:

The generator described here is a two-pole generator which uses direct water cooling of the

stator winding, phase connectors and bushings and hydrogen cooling of the rotor winding. The

Page 85: BARC

85

losses in the remaining generator components, such as core, friction and stray losses are

dissipated by hydrogen. The required exciter power is supplied by an exciter set which is rigidly

coupled to the generator rotor and equipped with rotating rectifiers so there is no need for slip

rings.

Description Technical Data

A. Generator:

a) Rated output- 659 MVA

b) Power factor- 0.85

c) Rated terminal voltage- 21 kV ± 5 %

d) Rated phase current- 18.118 KA

e) Rated speed- 50s-1

f) Frequency- 50 Hz

B. Cooling media H2O and H2:

a) H2 pressure at rated output 4 bar gauge

b) Cooling of stator winding- H2O

c) Cooling of rotor winding- H2 direct

d) Cooling of stator core- H2

C. Peak Short-circuit currents:

a) 3 Phase- 27.2 kA

b) 2 Phase- 43.1 kA

7.4) PROTECTIONS OF GENERATOR:

The most important factors, which make protection necessary for a generator, are the electrical

stresses imposed on the insulation, the mechanical forces acting on the various parts of the

machine, and temperature rises.

Page 86: BARC

86

Since every generator is connected to a power system, its protection system must contain

elements which, should a fault occur in the system, will disconnect the generator in a manner

compatible with the protection system of the power system.

The number and variety of faults to which a generator may be subjected being great, several

protective systems are employed, both of the discriminative and non-discriminative type. Great

care has to be exercised in coordinating the systems used and the settings adopted, so that a

sensitive, selective and discriminative protection scheme is available.

As both the main and the unit auxiliary transformers form a part of the generator, their protection

is inevitably associated with that of the generator and its associated main and unit auxiliary

transformers against insulation failure and the other hazards.

The various forms of protection applied to generator units fall into one of the following two

categories:

I. Protective relay or device to detect faults occurring outside the generator unit.

II. Protective relay or device to detect faults occurring within the generator unit and the

associated connections.

7.4.1) Nature of faults in generators and their protection:-

7.4.1.1) Stator winding faults & protection

Failure of the stator windings or connection insulation can result in severe damage to the

windings and stator core. The extent of the damage will depend on the magnitude and duration of

the fault current. An earth fault involving the stator core results in burning of the iron at the point

of fault and welds laminations together.

Relay application for the stator earthfault is mainly influenced by the method of stator earthing.

When the stator neutral is earthed through a resistor, a C.T. is mounted in the neutral to earth

connection. Either an inverse time relay or an instantaneous relay is used across the C.T.

secondary, depending on whether the generator is directly connected to the station busbars or via

Page 87: BARC

87

a delta/star transformer. In the former case, the inverse time relay will require grading with other

fault relays in the system; but in the latter case, because the earthfault loop is restricted to the

stator and transformer primary winding, on discrimination with other earthfault relays is

necessary.

With resistor earthing, it is impossible to protected being dependent on the value of the neutral

earthing resistor and the relay setting. When the neutral is earthed through the primary winding

of a distribution transformer, earthfault protection is provided by connecting an overvoltage relay

across its secondary, as shown in figure below. The maximum earthfault current is determined by

the size of the transformer and the loading resistor R. Optimum loading is when the power

dissipated in the resistor equals the capacitive loss in the generator system. At this point the

transient overvoltages possible are at a practical minimum. Increasing the power dissipation in

the resistor beyond this point increases the energy in the fault arc and therefore the degree of

Fig. 7.1 Relay scheme for SEF protection

The amount of stator winding protected using distribution or voltage transformer earthing,

depends upon the relay setting, which is expressed as a percentage of the rated secondary output

voltage of the transformer. Thus a 10% setting would protect 90% of the winding. The time

setting should be chosen to avoid operation due to interwinding capacitance as mentioned above,

a setting of 1.5 sec. at 10x voltage setting being adequate for most applications.

Page 88: BARC

88

7.4.1.2) Overcurrent protection

Overcurrent protection of generators may take two forms. Plain overcurrent protection may be

used as the principle form of protection for small generators, and back-up protection for larger

ones where differential protection is used as the primary method of generator stator winding

protection. Voltage dependent overcurrent protection may be applied where differential

protection is not justified on larger generators, or where problems are met in applying plain

overcurrent protection.

7.4.1.3) Overvoltage protection

Overvoltages on a generator may occur due to transient surges on the network, or prolonged

power frequency overvoltages may arise from a variety of conditions.

A sustained overvoltage condition should not occur for a machine with a healthy voltage

regulator, but it may be caused by the following contingencies:

a) Defective operation of the automatic voltage regulator when the machine is in isolated

operation.

b) Operation under manual control with the voltage regulator out of service.

c) Sudden loss of load (due to tripping of outgoing feeders, leaving the set isolated or

feeding a very small load) may cause a sudden rise in terminal voltage due to the trapped

field flux and/or overspeed.

7.4.1.4) Undervoltage protection

Undervoltage protection is rarely fitted to generators. It is sometimes used as an interlock

element for another protection function or scheme, such as field failure protection or inadvertent

energisation protection, where the abnormality to be detected leads directly or indirectly to an

undervoltage condition.

Page 89: BARC

89

Where undervoltage protection is required, it should comprise an undervoltage element and an

associated time delay. Settings must be chosen to avoid maloperation during the inevitable

voltage dips during power system fault clearance or associated with motor starting.

7.4.1.5) Rotor Earth Fault protection:

A single earthfault on the field winding or in the exciter circuit of a generator is not in itself a

danger to the machine. Should a second earth fault develop, however, part of the field winding

will become short circuited resulting in magnetic unbalance of a field system with subsequent

mechanical damage to the machine bearings.

Three Methods are available to detect this type of fault. They are:

a) Potentiometer Method

b) A.C. Injection Method

c) D.C. Injection Method

Each scheme relies upon the rotor earth fault closing an electrical circuit, the protection relay

forming one branch of the circuit.

Potentiometer Method:

This scheme comprises a centre tapped resistor connected in parallel with the main field

winding. The centre point of the resistor is connected to earth through an overvoltage relay.

Thus, any earthfault on the field winding will produce a voltage across the relay terminals,

maximum voltage occurring for faults at the extreme ends of the windings, reducing to zero for

faults at the centre of the winding.

The obvious disadvantage to this scheme is that a relay blind spot exists for faults at the centre of

the field windings. To prevent an earthfault in this position remaining undetected, it is usual to

displace the centre ta of the resistor by a push button or switch. When this type of rotor earthfault

protection is employed, it is essential that station instructions are issued to ensure that the ‘blind

spot’ is checked at least once a shift.

The main advantages of the scheme are its simplicity and the fact that it does not need any

auxiliary supply.

Page 90: BARC

90

A.C. Injection Method:

This scheme comprises of auxiliary supply transformer, one side of the secondary being earthed,

the other start or finish of the main field winding. When an earthfault occurs, the relay circuit is

completed, and the current through the relay being independent of the exciter voltage and a

function only of the fault resistance

.

This scheme is free from blind spots, it can have a high degree of sensitivity consistent with the

withstand limitations of the relay and it is impervious to switching surges in the main filed

circuit. It has the great disadvantage that there is always a small leakage current circulating due

to the capacitance between the field winding earth which has injurious affects on the bearings of

the machine. Figure 6.5 shows path of the leakage current in the rotor circuit. A further

disadvantage of the scheme is that should the auxiliary A.C. supply fail, the protection becomes

inoperative.

D.C. Injection Method:

This scheme is similar in principle to the a.c. injection method, and comprises a

transformer/rectifier bridge, the positive D.C. node of the bridge being earthed, the other node

being connected via a relay and limiting resistor to be the positive end of the main field winding.

This scheme offers all the advantage of the a.c. injection scheme without the disadvantage of

leakage currents circulating through the rotor bearings it also has the advantage that should the

a.c. auxiliary supply be lost, the scheme will still remain effective over a large portion of the

field winding.

The “ALSTOM” scheme recommended for this protection is type VAEM 21 which is arranged

to operate when the insulation level falls. The relay is suitable for all exciter voltages upto 1200

volts and is provided with sufficient contacts to energize visual and audible alarm circuits and

the main and field circuit breaker trip circuits.

It should be noted that it is not usually necessary to disconnect the machine in unattended

stations as a single rotor earthfault does not constitute an immediate hazard

Page 91: BARC

91

7.4.1.6) Loss of Excitation (Field Failure):

Figure-6.2 loss of excitation

The main effects are:-

a) Causes Asynchronous running (> Sync speed).

b) Main flux provided by reactive (Stator) current supplied from system, i.e. Operation at

leading power factor.

c) AC induced in Rotor, which causes heating.

d) Stator current limit may be exceeding

Failure of the field system results in a generator operating at above synchronous speed as an

induction generator, drawing magnetizing current from the system. There is no immediate danger

to a set operating in this manner. However, overloading of the stator and over heating of the rotor

result from continued operation and therefore the machine should be disconnected and shut down

if the field cannot be restored. It is often to protect in the event of a field circuit failure. This is

often done with a DC relay set to operate when field circuit current falls to around 5% of

nominal.

A more sophisticated scheme, recommended for all large, important sets, allows for tripping the

machine in the presence of swing conditions resulting from loss of field. It initiates load

Page 92: BARC

92

shedding with subsequent tripping of the machine if the field is not restored, and initiates load

shedding with subsequent tripping of the machine if the field is not restored within a prescribed

time. The scheme comprises an offset Mho relay, type YCGF and an instantaneous undervoltage

relay, type VAG. The AC and DC connections are given in figure.7.2

Figure 7.3 shows typical machine terminal impedance characteristic on loss of excitation plotted

on an R-X diagram together with the offset Mho field failure relay characteristic. Relay

operation occurs immediately the terminal impedance locus enters the relay characteristic, in this

example approximately 5 sec. after the machine loss its field supply.

It is usual to offset the relay characteristic by an amount OA along the X axis, equal to half the

direct axis transient reactance of the machine and make the diameter of the characteristic AB

equal to the direct axis synchronous reactance. In this way operation on power swings and loss of

synchronism not accompanied by loss of field are prevented.

Figure 7.3- relay characteristics for loss of excitation

As previously stated, it is not always necessary to shut the set down immediately the ‘loss of

field relay’ operates unless there is a danger of system instability. The best indication of a

Page 93: BARC

93

system’s ability to maintain stability is the system voltage. Thus the offset mho relay is arranged

to shut the machine down instantaneously only when its operation is accompanied by a collapse

in system voltage, this condition being detected by an instantaneous undervoltage relay, set to

approx. 70% of normal volts. Should the offset mho relay operate alone, it is arranged to initiate

load shedding of the set down to a safe value and to initiate the master tripping relay after a

prescribed time delay.

7.4.1.7) U/O Frequency:

The resulting eddy currents can cause severe rotor heating possibly resulting in the rotor wedges

expanding and causing severe damage to the machine. It can be considered as back up protection

for governor failure.

7.4.1.8) Unbalance Loading:

The main effects are:

a) Gives rise to Negative Phase sequence currents in the stator, which causes contra rotating

magnetic field.

b) Stator flux cuts rotor at twice sync speed inducing double frequency current in field

system and rotor body.

c) Resulting eddy currents causes overheating.

Negative phase sequence currents in the stator, resulting from unbalanced loading, produce a

location field rotating at twice synchronous speed with respect to the rotor and hence induce

double frequency currents in the rotor. These currents are very large and result in severe over

heating of the rotor, especially in steam generators with cylindrical rotors. The ability of a

generator to withstand negative phase sequence currents depends upon the machine construction.

Cooling is also important and large power station generators use hydrogen as a coolant. The

direct cooling method involves the coolant being directed down ducts adjacent to the rotor

conductors.

Page 94: BARC

94

It is necessary to limit the time for which negative phase sequence currents can flow in a steam

generator. The time for which a generator may be allowed to operate with unbalanced stator

currents with-out danger of permanent damage is obtained from expression I2T=‘K’ where ‘K’ is

a constant depending on the type of machine and the form of cooling and I2 is the average

negative phase sequence current over time T seconds.

Internal stator faults are cleared instantaneously by the differential protection but external faults

or unbalance resulting from an open circuit may remain undetected or persist for a significant

period depending on the protection co-ordination of the system. It is therefore necessary to install

a negative phase sequence relay with a characteristic to match the withstand curve of the

machine, arranged to trip the main circuit breaker and give an alarm should the continuous

withstand be exceeded. The generator protection scheme suitable for this application employs a

type CTN relay, at TAPS-3&4.

7.4.1.9) Prime mover failure - Reverse power protection:

In such case,

a) Time delay required to prevent operation on transient power swings

b) Sensitivity required depends on prime mover

c) True power measurement is required

The effect of prime mover failure is to cause the machine to ‘motor’ by taking power from the

system. The seriousness of this condition depends on the type of drive used for the generator.

In steam turbine sets, the steam acts as coolant, maintaining the turbine blades at a constant

temperature. Failure of steam supply will therefore result in overheating, due to friction, with

subsequent distortion of the turbine blades. In condensing turbines, the rate of temperature rise is

slow and no immediate action need be taken. However with back pressure turbines, the

temperature can rise rapidly to a dangerous level because steam at back pressure density is

trapped in the turbine-casing. Prompt action should therefore be taken to prevent motoring.

Failure of the prime mover may result in severe mechanical damage and, in addition, will impose

a heavy motoring load on the generator.

Page 95: BARC

95

As there is a reversal of power when the machine motors, a directional power relay is used to

detect this condition over the full power factor range. This type of relay would also operate for

power swing conditions and when the machine is being synchronized. Therefore, to prevent

unwanted operations, it is usual in this application to introduce a time delay.

The reverse power relay is normally used for two applications viz. as a reverse power relay to

trip the generator when the machine starts motoring and as a reverse power interlock device to

prevent the possibility of a turbo-generator set overspeeding should a steam valve fail to close

completely after the generator C.B. has opened on a fault.

The reverse power relay is arranged so that its contacts close immediately the set starts to motor,

the opening of the circuit breaker will be prevented until the motoring condition sets in, giving

positive indication that the steam valves have closed and the entrenched steam has been

expended.

The more recent development is to use a low (forward) power interlock instead of the reverse

power interlock so that it is not necessary to delay the generator circuit breaker tripping till the

set has actually started motoring. When a low power interlock is used, the normally open contact

of the power relay is replaced by a normally closed contact. As soon as the power supplied by

the generator falls below 0-5% of rated power, the low power relay resets and completes the

tripping circuits to the generator circuit breaker. This low setting ensures avoidance of

overspending once the electrical side has been tripped. It also ensures reliable operation of the

relay on the motoring power taken by the set when the steam input is zero.

7.4.1.10) Overspeed Protection:

While it is the general practice to provide mechanical overspeed device on both steam and hydro

turbines, which operate directly on the steam throttle valve or main stop valves (stop valves refer

to hydro-electric sets only), it is not usual to back-up these devices by an over speed relay on

steam-driven sets. It is, however, considered good practice on hydro-electric units, as the

response of the governor is comparatively slow and the set is more prone to overspeed. The relay

Page 96: BARC

96

when fitted is usually supplied from the permanent magnet generator used for the control of

governor.

7.4.1.11) Protection against inadvertent energisation:-

Accidental energisation of a generator when it is not running may cause severe damage to it.

With the generator at standstill, closing the circuit breaker results in the generator acting as an

induction motor; the field winding (if closed) and the rotor solid iron/damper circuits acting as

rotor circuits. Very high currents are induced in these rotor components, and also occur in the

stator, with resultant rapid overheating and damage. Protection against this condition is therefore

desirable. A combination of stator undervoltage and overcurrent can be used to detect this

condition. An instantaneous overcurrent element is used, and gated with a three phase

undervoltage element (fed from a VT on the generator side of the circuit breaker) to provide the

protection.

7.4.1.12) Overfluxing

Overfluxing occurs when the ratio of voltage to frequency is too high. The iron saturates owing

to the high flux density and results in stray flux occurring in components not designed to carry it.

Overheating can then occur, resulting in damage. It is usual to provide a definite time-delayed

alarm setting and an instantaneous or inverse time-delayed trip setting, to match the withstand

characteristics of the protected generator.

7.5) GENERATOR CIRCUIT BREAKER:

The generator circuit breaker (GCB) is located indoors between the generator and the generator

transformers in the run of the main bus ducts called as isolated phase bus ducts (IPBD). During

unit trip, the GCB will isolate the generator from the system. When the requirement arises, the

generator transformers would be back-charged from 600 KV grid and used to step down the

Page 97: BARC

97

voltage for feeding unit connected loads through unit transformers with GCB kept open. Its main

purpose is to protect the generator.

7.5.1) General construction features:

The GCB comprises of three identical single pole units with an operating mechanism suitable for

3-phase operation. A common local control panel with all-necessary controls, indication and

annunciation is provided for each three pole GCB.

Each single pole unit of the GCB is suitable for connecting to the bus ducts through flexible

bolted connections on both sides. The enclosure of the GCB has provision for bolting on the

flexible connectors on either side for connection to the IPBD enclosure, thus giving a continuous

physical IPBD enclosure on both sides.

The main parts of an air-blast GCB

a) Main Contact

b) Auxiliary contact

c) Moving Contact

d) Fixed Contact

e) Insulated support

f) Blasting valve

g) Muffler

h) Terminals

i) Air (Low pressure area)

j) Blowers

k) Radiators

l) Conducting Housing

7.5.2) Capabilities of the GCB:

As the GCB is a very critical component included in the main power evacuation circuit from the

659 MVA generator, a very high degree of reliability and availability is ensured in this

equipment.

Page 98: BARC

98

The GCB is suitable for conditions and functions detailed below:

a) Operation at the rated current and voltage continuously under specified site conditions.

b) Breaking any load current up to rated current as well as to break and make the

magnetizing currents of the Generator Transformer (GT) & Unit Transformer (UT’s).

c) Connecting the generator with the system after synchronizing.

d) Making and latching, carrying for one second and interrupting the design fault currents.

e) Back charging of the GT during starting and on tripping of the GCB, when the auxiliaries

would be fed via the GT and UT. The GCB would be open under this condition.

f) Interruption of current during out-of-phase switching.

g) Interruption of current during generator pole slipping.

h) The GCB is capable of operating at the design ambient temperature and can operate

without injurious heating while executing the duties indicated above. The GCB has

features with high repeatability of closing and opening times over the applicable range of

parameters such as pneumatic pressure, control voltage etc.

i) The time between the first and the last poles to open and close does not exceed 10

milliseconds.

j) The GCB is capable of breaking 50% of the rated fault current at at rated voltage level

under out of phase conditions.

7.5.3) Contacts:

The GCB has two separate contact systems, one for load current carrying and another for

interruption. The tips of main and arcing contacts have silver facing and tungsten tipping

respectively.

Main contacts has ample area and contact pressure for carrying the rated current and the short

time rated fault current of the breaker without excessive temperature rise to avoid pitting and

welding. The maximum temperature rise of the hottest spot on the main contacts is limited to 60

C°, and the total temperature to 105 C°. Contact is adjustable to allow for wear, easily

replaceable and has a minimum number of moving parts and adjustment to accomplish these

Page 99: BARC

99

results. Main contact is the first to open and the last to close to ensure very little contact burning

and wear. Arcing contacts is the first to close and last to open and is easily accessible for

inspection and replacement.

7.5.4) GCB Specifications:

Table 7.1 GCB specification

Type of circuit breaker

Air blast, 3-phase generator circuit breaker

with 3 single pole units.

Nominal system voltage 21 kV

Rated maximum voltage 24 kV

Rated Continuous current 19.1 kA

Rated Frequency 50 Hz

Rated short-circuit current (symmetrical) 120 kA

Rated interrupting time 5 cycles

Duty cycle CO - 30 min – CO

Operating pressure 30 – 33.4 bar

Mass of tree pole circuit-breaker 5 cycles

Maximum opening time 15000 kg

7.5.5) Air blast type generator circuit breakers:

The air blast circuit breaker design uses a blast of compressed air serving as the arc-quenching

medium for the GCB. The design of the breaker is such as not to require conditioning of air in

main receiver during service. Damping resistors are thermally suitable for the specified duty

without deterioration of either resistor or resistor supports. Pressure switches are provided which

shall give an alarm and then lock out the breaker operation in case of low air pressures.

Page 100: BARC

100

The exhaust gases from both pneumatic operating mechanism and air blast breaker pole are

effectively cooled and demonized before releasing to the atmosphere. The loss of air pressure in

the breaker interruption chamber while in operation does not cause any reduction of current

carrying capacity or cause damage to the insulation.

7. 5.5.1) Operating mechanism:

The pneumatic operating mechanism is non-pumping under every method of closing and is trip

free. The capacity of local and main air receivers of air blast circuit breaker is sufficient to carry

out one (1) and two (2) Cooperation respectively with normal pressure, without replenishing the

air supply.

The GCB can be closed and opened electrically from both local as well as remote control points.

Provision is made for emergency tripping of the GCB manually without the requirement of an

electrical control supply. Provision is there to provide locking of this means of tripping.

Independently adjustable pressure switches with potential free contacts are furnished on each

circuit breaker mechanism for purpose of low and high air pressure alarm and lock out in case of

insufficient air pressure to perform a closing /opening operation. However, if the breaker is

already performing opening operation, operation shall be completed before locking out on

insufficient pressure.

It is possible to operate the breaker manually allowing for slow closing/opening of the breaker

contacts for purposes of testing and maintenance. While such provision is in operation,

movements of the contacts shall remain fully under the control of the operator at which time the

operation of the trip/ close mechanism shall have no effect. Two trip coils are provided for

greater reliability. Trip coil supervision relays suitable for monitoring of the trip coils both in the

open and close positions of the breaker are provided for each trip coil. The trip coils have

sufficient continuous rating to cater to the trip coil supervision relay current.

Page 101: BARC

101

The circuit breaker control scheme includes all necessary electrical and preferably mechanical

interlocks to preclude the single phase operating of the circuit breaker. Separate auxiliary relays

are provided for tripping and alarm.

A mechanical indicator is provided on each pole of the breaker to show open and closed

positions where it will be visible through a glass window to a man standing on the ground. An

operation counter is provided on the local control panel. The closing release operates correctly at

all values from 80% to 110% of the rated voltage. The shunt trip operates correctly under all

operating conditions of the circuit breaker and at all values of control voltage from 50% to 110%

of rated voltage.

The compressed air closing/opening mechanism is capable of closing and opening the circuit

breaker under all conditions between no-load and its rated making capacity when the air pressure

immediately before the closing/opening operation is between 85% and 105% of the rated supply

pressure. The make time at a supply pressure of 85% of the rated pressure does not exceed the

specified make time.

7.5.6) Importance and Advantages of using GCB in TAPS-3&4 system:

The GCB is a very important equipment of the whole system in operation and in protection also.

The earlier schemes used in older nuclear plants of NPCIL did not have the GCB. But later with

age they realized the importance of it and in this latest plant of NPCIL, GCB is included in the

design structure.

This is due to following main reasons:

a) During GCB tripped, only the generator will be out of active power system, so the pack

power from the 400 KV grid can be used to feed power to house loads and keep active

the electrical system through the UT’s.

b) In case of far of faults in e.g. busbar of 400KV or in transmission lines, the GT CB will

trip and detach the generator, restricting it to feed the fault. Here through GCB, the

Page 102: BARC

102

generator may continue to run on least or house loads, and need not be shut down. This

prevents generator stop and plant to get shutdown. This phenomenon of feeding the house

loads is called Ilanding.

c) Also ATS operations are minimized.

d) Brush less type of excitation system is used for TAPP-3&4 generator for rotor field and

as this has a high de-excitation time constant, any fault in the 21 KV side, if there were

no GCB, would be fed for a sufficient time by the generator because of slow decay in

rotor field even after opening of field breaker. Introduction of GCB will minimize the

fault feed and subsequent damage to the IPBD / Primaries of GT / UT.

7.6) GENERATOR PROTECTION SCHEME AT TAPS- 3&4

Table 7.2 generator protection scheme at TAPS-3&4

SR.NO Nature of fault Group 1 Group2

1. Phase faults for stator winding 87G 87GT*

2. Earth fault in stator winding 64G1(100%) 64G2 (95%)

3. Turbine failure (Reverse Power) 32G1 32G2

4. Unbalanced loading 46G1 46G2

5. Two stage rotor earth fault 64F

6. Loss of excitation 40G

7. Loss of synchronism (pole slipping) 78G

8. Over fluxing (common generator & generator

transformer)

9. Under frequency 81G1 81G2

10. Starting protection Phase-to-phase 51S

11. Back-up protection 51V 21G

12. Over voltage 59G

Page 103: BARC

103

13. Dead M/C protection 51D1 51D2

14. Main exciter protection No separate relay (covered by

rotor E/F relay)

7.7) REPLACEMENT OF REF PROTECTION SCHEME AT TAPS-3&4

The rotor earth fault relay earlier used at TAPS-3&4 proved unsatisfactory and had to be

replaced with a new relay. The old scheme used to give trip on rotor earth fault unnecessarily,

even when the system was healthy. On 14th April, we started the replacement process and

installing a new relay, Siprotec 7UM62.

7.7.1) New Relay scheme

The new relay is based on the principal of low frequency (1-3 Hz) voltage injection. Its

resistance module measures the voltage Umeas and current Ig. Ig is the current proportional to earth

current. Any earth current will result is more earth current and lesser value of resistance between

brushes.

7. 7.1.1) Installation

The new Siemens relay SIPROTEC 7UM62 is installed. The relay can be used for all types of

protections for generator, though only Under excitation and Rotor earth fault protection functions

are used from it. This is done since already a protection scheme exists for other protections of

generator.

The process followed was as below:-

a) A well-defined commissioning procedure is prepared for the replacement of scheme and

list of test procedures and expected results.

b) The Relay and its accessories are installed and all wiring required is done at the site using

ED’s.

Page 104: BARC

104

c) The relay PCB’s are taken out and the Jumper settings are done as per our requirements

d) After reinstalling the PCB’s, the relay is interfaced using a Siemens software DIGSI and

logics are designed for all binary inputs, binary outputs and for glowing LED’s on relays.

e) After logic programming other settings are also configured regarding connection of CT’s

their values and similar parameters.

f) The final settings are then downloaded into the relay. Now the relay is ready for

operation

g) Contact changeover and LED operation is checked by forced operation through the same

software, and continuity is checked for each makeover using MVM.

7. 7.1.2) Testing for REF

A practical testing of relay operation and response on faulty conditions is necessary

a) External resistance from a resistance decade box is fed to the contacts of the new relay to

check its resistance measuring accuracy. The trip and alarm signal is found OK for the

setting resistance. Also a small DC supply in series is connected, for verifying no

disturbance in measurement.

b) After satisfactory results generator brush input is directly fed to the relay. The brushes are

removed from generator in sequence and conditional results are observed. Tripping is

observed for an actual REF.

Page 105: BARC

105

8) MOTOR PROTECTION

8.1) GENERAL DESCRIPTION

There are several types and motors of different rating, utilization are used at TAPS-3&4. These

are fed from the electrical panels, given their ratings. Motors below 90 kW are fed from Motor

control Cubicle (MCC)- 415 V, motors above 90 kW and below 200 kW are fed from 415 V

switchgear panels and all motors of rating above 200 kW are fed from 6.6 kV switchgear panels.

The choices of protection are independent of the type of motor and the type of load to which they

are connected.

Motor protection relays requires of following values of the motor to be electrically protected.

The relay settings would depend on these factors.

a) Full load current

b) CT Ratio

c) Thermal withstand characteristics (hot / cold)

d) Starting current versus time characteristics.

The protections is usually provided for three-phase motors, it is generally effective against

overloads and short-circuit conditions, rarely take into full account the harmful effects of

unbalanced line currents. Even a modest unbalance can cause damage to the motor by

overheating and in the extreme instance of motor stalling due to loss of one phase, severe rotor

damage can occur within the normal starting time.

8.2) MOTOR FAULTS AND SETTINGS

8.2.1) Thermal Overload Protection (49)

The majority of winding failures are either indirectly or directly caused by overloading (either

prolonged or cyclic), operation on unbalanced supply voltage, or single phasing, which all leads

Page 106: BARC

106

through excessive heating to the deterioration of the winding insulation until an electrical fault

occurs. Furthermore, the thermal withstand capability of the motor is affected by heating in the

winding prior to a fault. It is therefore important that the relay characteristic takes account of the

extremes of zero and full-load pre-fault current known respectively as the 'Cold' and 'Hot'

conditions.

Set the pick-up of relay at 103% of the rated current = Irated x 1.03 Amps

Referred to secondary, Is = Irated x 1.03 x (CTsec/ CTpri)

Depending on the cooling factor of the motor, the thermal coefficient is set in the relay. Setting

for thermal alarm and thermal trip is specified.

8.2.2) Short circuit Protection (50/51):

This Protection takes care of the faults, which occur between Phases generally across terminals

or between phases inside. The fault current is totally depended upon the bus fault level and not

upon the motor characteristics. Here instantaneous clearance is preferred.

However if the motor is controlled by Fuse contactor, then it would be advisable if fuse blows

and clears the fault rather than forcing the contractor to open on fault. To this effect the short

circuit protection will be disabled

In this case, the setting of Motor control By CB (circuit breaker) automatically ensures that the

Short circuit protection will be enabled.

The setting of the relay will have to discriminate between fault condition and starting condition.

This can be achieved by increasing the setting more than the maximum starting current.

Instantaneous short circuit = 1.3 x Starting Current x (CTsec/ CTpri)

current setting

Set Isc at a value +5 % of the one obtained above.

Page 107: BARC

107

The relay used also has a unique feature called the doubling feature where the effective setting

gets doubled during starting process and returns back to normal condition after start sequence is

over. Therefore the setting on this relay now gets reduced by half

Hence the Short Circuit current = Isc/ 2

8.2.3) Start Protection

When a motor is started, it draws a current well in excess of full load rating throughout the

period that the motor takes to run-up to speed. While the motor starting current reduces

somewhat as motor speed increases, it is normal in protection practice to assume that the motor

current remains constant throughout the starting period. The starting current will vary depending

on the design of the motor and method of starting.

A motor may fail to accelerate from rest for a number of reasons:

a) loss of a supply phase

b) mechanical problems

c) low supply voltage

d) excessive load torque

Etc.

A large current will be drawn from the supply, and cause extremely high temperatures to be

generated within the motor. This is made worse by the fact that the motor is not rotating, and

hence no cooling due to rotation is available. Winding damage will occur very quickly – either to

the stator or rotor windings depending on the thermal limitations of the particular design (motors

are said to be stator or rotor limited in this respect).

Maximum Motor starting current

at rated voltage = 6 Times Full load Current

Maximum Motor starting current

at lower voltage of say 80% = 80% of max starting current

Page 108: BARC

108

8.2.3.1) Excess long Start Protection (48):

This protection will operate if the motor takes longer time to start. The setting will be based on

the worst case type of voltage for starting, which occurs when starting with low voltage.

Therefore Current setting will be 80% of Max current during starting at low voltage.

Time Setting will determine after how much time with this current the relay will detect it as a

prolonged start. This requires the value of the maximum starting time, which is applicable, when

the motor starts with low voltage. General value is 8-12 sec.

8.2.4.) Stalling Protection:

In the extreme instance of motor stalling due to loss of one phase, severe rotor damage can occur

within the normal starting time. The maximum stalling current works out to be 6 times the rated

current.

However we have to protect the machine as soon as it begins to stall. Therefore we consider that

the if the machine starts drawing more than twice rated current, we can reasonably assume that

stalling has begun and there fore set the relay with current setting accordingly.

Current setting = 2.00

Time setting shall be set less than the maximum stall withstands time of the relay. A general

value is 18-22 sec.

8.2.5) Negative Phase sequence Protection:

The negative phase sequence protection has to be graded with the NPS withstand levels of the

motor. In absence of this, it is recommended to provide current setting equal to rated current.

Set current setting = 1.00

Time characteristic setting may be set to definite time as we de do not have the inverse withstand

level of motor.

The definite time setting can be set to 0.1 sec.

This means that if the negative sequence setting reaches rated current, the relay will operate

instantaneously.

Page 109: BARC

109

8.2.6) Earth fault Protection:

The earth fault setting shall be based on the standing leakage currents and the method of system

earthing. If the system is resistance earthed, CBCT may be required and the required primary

operating current may be studied based on system study.

For system which is solidly earthed, standing unbalance leakage currents can be measured using

standard residual mode of connection and earth fault setting shall be made accordingly.

Generally the leakage currents shall not exceed 5 % of the rated current. Therefore the current

setting may be set to 10% of the rated current.

Current setting = 0.1 x full load Current x (CTsec/ CTpri) x1000

Time delay setting may be set to instantaneous which will be 0.1 sec (100mA). This is an

intentional delay and is used to prevent inrush currents, which last for couple of cycles from

operating the e/f element during starting.

Page 110: BARC

110

9) VACUUM CIRCUIT BREAKERS:

Vacuum CBs have been used for breaking currents in 6.6 kV switchgear panels, i.e. for all loads

above 200 kW. Vacuum CB have very low maintenance, and very high reliability.

9.1) DIELECTRIC STRENGTH OF VACUUM:

Any breaking medium must first be a good insulator for it is to stop current from flowing

through it. Vacuum is not an exception to the rule: it has interesting yet particular dielectric

properties in comparison to other insulating gases that are commonly used under pressure that is

higher than or equal to 1 bar.

At a pressure of even 10-3 bar, a 1 mm3 volume still contains 27.106 gas molecules, but their

interactions are negligible since their mean free path between two collisions is of the order of a

hundred meters: the term "vacuum" is thus appropriate since each molecule behaves as if it were

practically alone.

9.2) ELECTRIC ARCING IN VACUUM:

Even though, as described in the above section, vacuum may be an excellent dielectric, an arc

can very well "live" in the "vacuum". In fact, the arc voltages in vacuum are in general

considerably lower than those of arcs that develop in other mediums, which constitute an

advantage in regard to the energy that is dissipated in the arc. Arcs in vacuum occur, by

voluntarily simplifying, in two main forms: the diffuse mode and the constricted mode.

A diffuse mode, characteristic of the "vacuum" medium:

The diffuse mode is specific to arcing under vacuum: it shows remarkable particularities, which

clearly differentiate it from arcings in gaseous mediums. It is the mode, which a vacuum arc

naturally adopts for a current range covering a few amps to a few kA. The main characteristics of

Page 111: BARC

111

the diffuse mode is that the cathode emits into the inter-electrode gap, via one or several cathode

spots, a globally neutral plasma made up of electrons and of high speed ions whose velocity is

primarily directed perpendicularly to the surface of the cathode; and the anode, with its entire

surface immersed by this plasma, reacts as a passive charge collector.

A constricted mode similar to the one of an arc in a gaseous medium

First a contraction of the plasma column generally explained by the Hall-effect takes place. The

current is concentrated on a more limited area of the anode. Furthermore the anode attracts more

and more electrons, and the neutrality of the plasma is no longer ensured: positive ions are

lacking to balance the space charge of electrons near the anode. This leads to the formation of a

positive anode voltage drop which is needed to attract electrons despite the space charge.

The energy received by the anode increases and tends to be concentrated on a reduced area: the

anode heats up and starts to emit neutral particles that are ionized by the incident electrons. Near

the anode, secondary plasma, made up of secondary electrons and ions that are less energetic

than those emitted by the cathode spots, appears. These phenomena result in the appearance of a

luminous anode spot, considerably larger (in the region of a cm2) than the cathode spots, made

of molten metal, which spills considerable amounts of vapor, which becomes ionized in the flow

coming from the cathode, into the inter-electrode gap.

Here, we are dealing with an arc in an atmosphere of dense metallic vapors, for which operating

mechanisms now rely on the ionization of the gaseous medium.

9.3) PHENOMENA ASSOCIATED WITH BREAKING AT CURRENT

ZERO:

All medium voltage circuit-breakers take advantage of the natural passage of alternating current

through zero (twice per period, i.e. every 10 ms for a 50 Hz current) to interrupt the current.

Page 112: BARC

112

Case of vacuum switching:-

To determine the conditions for successful current interruption, it is necessary to study the

phenomena that intervene near current zero in the vacuum arc plasma.

Post-arc current: Near the end of the half-cycle, the current decreases at a rate which is

proportional to the peak current value and to network frequency (di/dt = ω Î). The vacuum arc

returns to the diffuse mode and, near current zero, only a single cathode spot remains. However,

the inter-contact gap is still filled with residual, globally neutral plasma that is made up of

electrons, ions and neutral particles which come from the preceding arc. At the time of current

zero, the last cathode spot extinguishes itself because the arc voltage disappears.

9.4) PRACTICAL DESIGN OF VACUUM INTERRUPTERS:

The preceding section highlighted the conditions that must be satisfied for successful breaking.

These conditions are almost always satisfied when an arc remains in the diffuse mode, that is to

say when currents to be interrupted do not exceed a few kA. It is the case for switches and

contactors that can therefore use very simple butt contacts.

When an arc passes into the constricted mode, the energy is dissipated onto a reduced electrode

surface, and it causes localized overheating and considerable vaporization. If this arc remains

immobile, breaking is no longer guaranteed. Two methods are used to overcome the difficulties

that are produced by the passage of an arc into the constricted mode.

a) The first consists in causing a rapid circular movement of the constricted arc so that the

energy is distributed onto a large part of the contact and overheating is limited at all

points: this is obtained through the application of a radial magnetic field Br in the arc

zone.

b) The second consists in preventing the passage into the constricted mode through the

application of an axial magnetic field: when the field reaches a sufficient value, the arc is

stabilized in a mode qualified as a diffuse column and does not concentrate itself; even

though it is immobile the arc uses most of the contacts’ surface and overheating therefore

remains limited in this case as well.

Page 113: BARC

113

9.5) SUITABILITY OF VACUUM CB FOR MV:

A high breaking capacity is required for a circuit breaker application. As with SF6, vacuum

offers for this application the advantages of an enclosed break with no external manifestations

and a maintenance free design with high electrical endurance. The very rapid dielectric recovery

of the vacuum can be an advantage in comparison with SF6 in special applications for which the

rate of rise of the TRV is faster than that required. (ex: case of a circuit-breaker directly

connected to the secondary of a high power transformer). In such cases, not very frequent for

standardized TRVs cover the great majority of applications, vacuum circuit-breakers need less

derating than SF6 circuit-breakers.

Since vacuum switching is conducted without an external energy supply, vacuum circuit-

breakers require less operating energy than SF6 circuit breakers of the puffer type. For that

which deals with SF6 circuit-breakers with rotating arc or with self-expansion, the gap is less

significant.

This advantage is however counterbalanced by the inherent disadvantages of the vacuum

technique which can only use butt contacts. These contacts need high contact pressure to prevent

repulsion and contact welding upon closing on fault: contact pressure needed per pole is in the

region of 200 daN for a 25 kA circuit-breaker and of 600 daN for a 50 kA circuit-breaker. This

requirement leads to a rise in the operating energy for closing and to reinforced pole structure

that must tolerate these permanent stresses in the closed position.

9.6) VACUUM CB AT TAPS- 3&4:

The switchgear is of M/S Siemens Ltd. and it is suitable for indoor installation. Circuit breakers

are used for motor feeders, DG set and auxiliary transformers, C1-IV bus incomers. These are

trolley-mounted type and necessary interlocks are provided for:

Page 114: BARC

114

a) Preventing breaker operation while the breaker trolley is in any intermediate position

between service and test position.

b) Preventing withdrawal of the trolley when the breaker is in closed position.

c) Preventing movement of closed breaker in service position to test position or rack out.

The main parts of the circuit breakers are chambers, spring charging and operating mechanism.

The control scheme of breaker incorporates usual safety features such as anti-pumping and other

interlocks. The breaker is trip-free as per provision of IEC-56. All the breakers are provided

with two trip coils to provide redundancy.

9.6.1) CB control:

All breakers can be operated either from local control switch in switchgear or from remote

control in the control room. There is a local / remote selector in the switchgear to ensure that

either local or remote control is effective at a time. The selector switch should be kept in remote

position under normal condition of plant operation. Operating through local control switch is

possible only when breaker is in test position. It is also possible to test the breaker when it is in

test position from control room.

Emergency trip push button is provided on the breaker for each feeder for tripping in any

emergency condition.

9.6.2) Circuit Breaker Positions:

All breakers have got three positions namely.

a) Service position (Breaker fully in)

b) Test position

c) Isolated position

a) Service Position:

This is the normal operating position of the breaker. In this position, the breaker is fully

locked in and can be controlled from remote control. In this position breaker is

connected to both, the power and control circuit. It is also possible to open breaker

Page 115: BARC

115

manually by operating emergency push button on breaker, which acts directly on the

operating mechanism during emergency conditions. Interlocks are provided to prevent

breaker withdrawal and insertion if the breaker is already in closed position. With the

breaker open only, the trolley can be moved from “Service Position”. If the breaker is in

the intermediate position between “Service and test position, it cannot be closed.

b) Test position:

This position is used to check operating of breaker from local, remote on logic testing. In

this position power circuit is disconnected but control circuit is maintained.

c) Isolated Position:

Physically position is same as test, but control circuit is also disconnected.

Interlocks are provided such that the breaker can be moved from service to test and from

test to isolate only in CB open condition.

9.6.3) Operating mechanism:

9.6.3.1) Anti-pumping:

After a close-open cycle, it is not possible to reclose the breaker as long as the closing command

is maintained. This feature known as anti-pumping, is assured mechanically, both in local and

remote control operations. For reclosing the breaker, the permanent closing command should be

momentarily interrupted.

9.6.3.2) Trip-free:

The moving contacts of the breaker return & remain in open position, when the opening

operation is initiated after initiation of closing command. In this case, the closing command is

overruled by the tripping command.

Check the availability of local indications for

Breaker OFF - Green-glowing

Page 116: BARC

116

CB close - Red not glowing

Lockout relay operated - Amber not glowing

CB in service - Yellow-glowing

Relay unhealthy - Red not glowing

Trip check Healthy - White-glowing by pushing yellow PB

9.6.3.3) spring charging & breaker closing mechanism:

Electrically operated breakers incorporate electrical motor operated spring charge (stored energy

type) mechanism. The ACB operates in the following sequence:

a) Motor charges the closing mechanism spring. The supply to motor gets disconnected by a

limit switch at the end of the charging operation.

b) The closing electromagnet, when actuated, discharges the spring and closes the breaker.

c) After the VCB closes, the spring gets automatically charged for the next closing

operation.

d) Position of the breaker main contacts is indicated by an indicator visible through a

transparent window on the breaker front fascia.

9.6.4) VCB Particulars:

1 Circuit Breaker Type : Vacuum

2 Rated voltage, Frequency & NO. of phases : 7.2 KV, 50 Hz. 3 ph

3 Rated Operating Duty : O3 min-CO -3 min- CO

4 Rated Current at site and ambient temperature : 1250A for 6000 kW motor

within enclosure 630 A for others

5 Rated Breaking Capacity (symm.) : 44 KA (rms)

6 Rated Making Current : 110 KA (Peak)

7 Short Time Current withstand for a sec. duration : 44 KA (rms)

8 Asymmetrical A.C Breaking Current Component

(% DC component at time in m. sec). : 46.88 KA (rms)

Page 117: BARC

117

: (26% at time

t = 60 m. sec.)

9 Total Break time : 4 Cycles (max.)

10 Total make time : 6 Cycles (max.)

11 (a) Operating mechanism

(i) Type : Motor charged spring with

mechanical trip facility

(ii) Spring charging motor : 220 V DC, Operable at voltage

range at 80% to 110%, Class-B or

better insulated.

(b) Trip free and antipumping : Yes

12 Minimum no. of Auxiliary contacts : 6 No+ 6 NC for

13 Withstand test One Minute : Powercircuit: 28KV (rms)

power frequency : Control circuit: 2KV (rms)

1.2/50 micro sec. impulse : 75 KV (Peak)

14 Auxiliary Control Voltage

a) For Closing/Tripping coil/protection circuits : 220 V DC

b) For spring charging motor : 220 V DC

c) For space heaters and lighting : 270 V AC, 1 ph

d) Inter posing relay circuit : 24 V DC

Page 118: BARC

118

10) DISTANCE PROTECTION

10.1) GENERAL DESCRIPTION

Transmission lines are a vital part of the electrical distribution system, as they provide the path to

transfer power between generation and load. Transmission lines operate at voltage levels from

69kV to 765kV, and are ideally tightly interconnected for reliable operation.

Factors like de-regulated market environment, economics, right of- way clearance and

environmental requirements have pushed utilities to operate transmission lines close to their

operating limits. Any fault, if not detected and isolated quickly will cascade into a system wide

disturbance causing widespread outages for a tightly interconnected system operating close to its

limits.

Transmission protection systems are designed to identify the location of faults and isolate only

the faulted section. The key challenge to the transmission line protection lies in reliably detecting

and isolating faults compromising the security of the system.

Distance protection is a non-unit protection that can be applied to overhead lines and cables.

Distance protection discriminates between faults occurring in different parts of the system by

measurement of impedance and so requires to be connected to CTs and VTs associated with the

protected circuit.

10.2) FACTORS INFLUENCING DISTANCE PROTECTION

The high level factors influencing distance protection include the criticality of the line (in terms

of load transfer and system stability), fault clearing time requirements for system stability, line

length, the system feeding the line, the configuration of the line (the number of terminals, the

physical construction of the line, the presence of parallel lines), the line loading, the types of

communications available, and failure modes of various protection equipment.

Page 119: BARC

119

The more detailed factors for transmission line protection directly address dependability and

security for a specific application. The protection system selected should provide redundancy to

limit the impact of device failure, and backup protection to ensure dependability. Reclosing may

be applied to keep the line in service for temporary faults, such as lightning strikes. The

maximum load current level will impact the sensitivity of protection functions, and may require

adjustment to protection functions settings during certain operating circumstances. Single-pole

tripping applications impact the performance requirements of distance elements, differential

elements, and communications schemes.

The physical construction of the transmission line is also a factor in protection system

application. The type of conductor, the size of conductor, and spacing of conductors determines

the impedance of the line, and the physical response to short circuit conditions, as well as line

charging current. In addition, the number of line terminals determines load and fault current

flow, which must be accounted for by the protection system. Parallel lines also impact relaying,

as mutual coupling influences the ground current measured by protective relays. The presence of

tapped transformers on a line, or reactive compensation devices such as series capacitor banks or

shunt reactors, also influences the choice of protection system, and the actual protection device

settings.

10.3) PRINCIPLES OF DISTANCE RELAYS

Since the impedance of a transmission line is proportional to its length, for distance measurement

it is appropriate to use a relay capable of measuring the impedance of a line up to a

predetermined point (the reach point). Such a relay is described as a distance relay and is

designed to operate only for faults occurring between the relay location and the selected reach

point, thus giving discrimination for faults that may occur in different line sections. The basic

principle of distance protection involves the division of the voltage at the relaying point by the

measured current. The apparent impedance so calculated is compared with the reach point

impedance. If the measured impedance is less than the reach point impedance, it is assumed that

a fault exists on the line between the relay and the reach point.

Page 120: BARC

120

The reach point of a relay is the point along the line impedance locus that is intersected by the

boundary characteristic of the relay. Since this is dependent on the ratio of voltage and current

and the phase angle between them, it may be plotted on an R/X diagram. The loci of power

system impedances as seen by the relay during faults, power swings and load variations may be

plotted on the same diagram and in this manner the performance of the relay in the presence of

system faults and disturbances may be studied.

10.4) RELAY PERFORMANCE

Distance relay performance is defined in terms of reach accuracy and operating time. Reach

accuracy is a comparison of the actual ohmic reach of the relay under practical conditions with

the relay setting value in ohms. Reach accuracy particularly depends on the level of voltage

presented to the relay under fault conditions. The impedance measuring techniques employed in

particular relay designs also have an impact. Operating times can vary with fault current, with

fault position relative to the relay setting, and with the point on the voltage wave at which the

fault occurs.

Depending on the measuring techniques employed in a particular relay design, measuring signal

transient errors, such as those produced by Capacitor Voltage Transformers or saturating CT’s,

can also adversely delay relay operation for faults close to the reach point. It is usual for

electromechanical and static distance relays to claim both maximum and minimum operating

times. However, for modern digital or numerical distance relays, the variation between these is

small over a wide range of system operating conditions and fault positions.

Micom P442 a numerical relay is used at taps- 3&4 for transmission line protection (distance

protection), earth-fault and overcurrent protection.

Page 121: BARC

121

11) CONCLUSIONS

1) Electrical systems and equipments are required to operate plant auxiliaries during start-

up, smooth plant operation and emergency conditions.

2) Classification of electrical power supply is done keeping in view the requirement of

running the plant auxiliaries of different systems under different plant operating

conditions.

3) Configuration of power supplies to auxiliary loads is done in such a way to ensure

minimum system outage and common mode failure.

4) Standardized power & control supply voltage levels are used for running and control of

plant auxiliaries.

5) Nomenclature adopted for identification of electrical system / equipments is based on

alphabets and numerical.

6) The 400 KV & 220 KV switchyards are provided to connect TAPP-3&4 units to part of

western grid.

7) 400 KV Switchyard will be used for power evacuation and as an alternate source of

station auxiliary power in case of SUT or 220KV switchyard outage.

8) 220 KV switchyard will be used for supplying power for running station auxiliary loads.

9) GIS (Gas Insulated Switchgear) has been adopted for both the switchyards to mitigate the

effects of saline atmosphere.

10) Electrical systems being one of the most critical system for TAPP -3&4, all possible

safety measures related directly or indirectly to electrical faults have been taken care off.

Some of the numerical relays used in TAPP- 3 & 4 for various type of protection are:

Micom P343

a) Generator main protection

b) Dead machine protection

c) Over-voltage protection

d) Over-current protection

e) Earth-fault protection

f) Over-frequency protection

g) Loss of excitation

Page 122: BARC

122

h) Under-frequency protection

i) Differentiate protection

j) Under-voltage protection

Micom P122

Primary circulating water differential protection

Micom P123

a) Tie feeder pump protection

b) Auxiliary transfer feeder protection (Over- current and earth-fault)

Micom P127

a) Directional over current protection

b) Directional earth-fault protection (incomer class-III 6.6 kV)

Micom P442

Transmission line protection

Micom P220

a) Motor protection

b) Thermal over-current protection

c) Earth-fault protection

d) Short-circuit protection

e) Unbalance protection

f) Mechanical jam protection (rotor block)

Page 123: BARC

123

12) APPENDIX

TERMINOLOGY

1. SUT : Start – up Transformer.

2. GT/UT : Generator Transformer

Unit Transformer or Unit Auxiliary Transformer (UAT)

3. SAPSS : Station Auxiliary Power Supply System.

4. Div – 1 : Electrical systems and plant auxiliaries fed by UT

during normal condition.

Div – 2 : Electrical systems and plant auxiliaries fed by SUT

during normal condition, but fed by UT during abnormal condition

5. DG : Diesel Generators

6. SWRD : Switchyard

7. CWPH : Cooling Water Pump House

8. DM : De-Mineralizing water plant

9. GIS : Gas Insulated Switchgear.

10. CT / PT : Current Transformer / Potential Transformer

11. CB : Circuit Breaker.

12. SF6 : Sulphur Hexafluoride gas.

13. AVR : Automatic Voltage Regulator

14. Back-up

Protection : A protection system intended to supplement the main

protection in case the latter should be ineffective, or to

deal with faults in those parts of the power system that

are not readily included in the operating zones of the

main protection.

15. HV : High Voltage

16. IGBT : Insulated gas bipolar transistor

A special design of transistor that is suitable for handling

Page 124: BARC

124

high voltages and currents (relative to an ordinary

transistor). Frequently used in static power control

equipment (inverters, controlled rectifiers, etc) due to the

flexibility of control of the output.

17. LV : Low Voltage

18 I.D.M.T. : Inverse time relay with definite minimum

Time.

An inverse time relay having an operating time that

tends towards a minimum value with increasing values

of the electrical characteristic quantity.

19 PLCC : Power Line Carrier Communication

A mean of transmitting information over a power

transmission line by using a carrier frequency

superimposed on the normal power frequency.

20 UPS : Uninterruptible Power Supply

Page 125: BARC

125

BIBLIOGRAPHY

[1]. Training On Power System Protection, Alstom

[2]. NPRAG, Alstom Ltd.

[3]. Fundamentals of power system protection by Y.G.Paithankar, S.R.Bhide

[4]. Relay Manuals, Alstom

[5]. IS 9001- 2008 Current transformer

[6]. O & M manual, FOR 400KV Switchyard

[7]. O & M manual, Unit transformer

[8]. O & M manual, For Start –up Transformer

[9]. Switchgear and protections, Sunil .S. Rao

[10]. Electrical training manual, NTC, NPCIL

[11]. 5-482-630En-C, GIS manual, Merlin Gerin