13. LIGHTING
13.1 BACKGROUND
The major objectives of energy audit in lighting system include:
Measurement and comparison of illumination levels at various locations
Measurement of total power consumption of all lighting feeders
Calculate the installed load efficacy in terms of lux/watt/m (existing vs design) for
general lighting installation.
Compare calculated value with the norms for specific types of interior installations for
assessing improvement options.
To suggest ways and means to optimize the illumination levels and to optimize the
power consumption at different locations.
To identify energy saving measures and quantifies the energy and cost savings.
13.2 STEPS INVOLVED IN CONDUCTING THE ENERGY AUDIT
The steps involved in conducting energy audit of lighting plant are:
Data collection
Observations, measurement and Analysis
Exploration for energy conservation measures with detailed techno-economic
calculations
Report preparation
13.3 DATA COLLECTION
Collect the single line diagram of electrical drawing pertaining to lighting
Obtain the lighting fixture details for each section
Typical format for data collection of lighting details is given Table 13-1
-
7/28/2019 Bab 13 - Lighting
2/6
Berbagi dan Menyebarkan Ilmu Pengetahuan Serta Nilai-Nilai Perusahaan 2
PT. PLN (PERSERO)
PUSAT PENDIDIKAN DAN PELATIHAN LIGHTING
Table 13-1: Typical Data parameters
Section/Department
FixtureType &ballast type
Wattageof eachfitting
No offixtures
Totalconnectedwattage
Feederdetails
Other energyConsumerdetails
Roomdimensions
Illuminesrequired
Remarks
In case if the details are not available it is suggested to conduct a survey and obtain the above
details. In the above table under other energy consumers column provide the details of fans,
air conditioners, computers, photocopiers, etc which are connected to lighting circuit to be given.
For illumination level required refer Annexure-13.1, where recommended illumination values as
per IS: 3646 (Part-1) 1992 for various areas in power stations are provided.
If the plant has separate transformers for lighting circuit, provide the details of
transformer
Details of energy saving retrofits installed in the plant (such as voltage controllers,
sensors, controllers, timers, etc)
Details of on & off mechanism of lighting circuits
Details of energy meters provided in the lighting circuit and sections served by these
meters
Details of energy consumption monitoring of lighting systems
Energy consumption of lighting circuit
13.4 Instrument Required
The following instruments are required for conducting the energy audit of lighting system
Power Analyzer: Used for measuring electrical parameters such as
kW, kVA, pf, V, A and Hz of class 0.5 accuracy
Lux meters
Measuring tape
On line energy meter instruments (calibrated)
-
7/28/2019 Bab 13 - Lighting
3/6
Berbagi dan Menyebarkan Ilmu Pengetahuan Serta Nilai-Nilai Perusahaan 3
PT. PLN (PERSERO)
PUSAT PENDIDIKAN DAN PELATIHAN LIGHTING
13.5 Measurements & Observation to Be Made
While conducting the audit carryout a detailed survey for the following
Monitor the condition of lighting fixtures
Lux measurements at various places (Number of measurement to be carried out is given
in the following sections)
Measurement of power parameters kW, kVA, Current, Voltage, power factor, harmonics,
frequency of all feeders
Room dimensions
Counting of installed fixtures Vs number of fixtures in operation
Maintenance practices for cleaning, replacement, etc
13.6 Observations And Analysis
13.6.1 System familiarization and operational details
Detailed interactions with the plant personnel have to be carried out to get familiarization forsystem detail and operational details. Pre visit to the plant can be made to get familiarization of
lighting system
13.6.2 Measurements & Evaluation
The summary of lighting measurements and calculations are shown Table 13-2.
Table 13-2: Summary of lighting measurements and calculations
Location/Room No
Type of lampsMeasured Average
Lux levelStandard Lux level(as per I S 3646)
MeasuredPower (kW)
-
7/28/2019 Bab 13 - Lighting
4/6
Berbagi dan Menyebarkan Ilmu Pengetahuan Serta Nilai-Nilai Perusahaan 4
PT. PLN (PERSERO)
PUSAT PENDIDIKAN DAN PELATIHAN LIGHTING
Observations on housekeeping and maintenance practices Interactions and surveys to be
carried out on
House keeping measures in up keeping of luminaries
Failure rate of lamps and ballasts
Replacement procedure of failed lamps
Procurement options
Maintenance practices
Operational practices (on / off controls)
If any energy saving retrofits are installed in the plant then the operational status of the
retrofits can be assessed Identify the areas where poor illumination and excess illumination is provided
Assess the various alternate lamps / luminaries applicable for various sections
Type of panel lamps or sign lamps used to explore possibility of using LED lamps
Observations on other loads which are connected to the lighting circuit and their energy
consumption
13.6.3 Exploration of energy conservation possibilities
While conducting the energy audit explore for various energy conservation measures such as
Look for natural lighting opportunities through windows and other openings. Derive way
to improve natural lighting during the day time
In the case of industrial lighting, explore the scope for introducing translucent sheets
Use of energy efficient lighting methods / products / equipment / retrofits
Maximize sunlight use through use of transparent roof sheets, north light roof, etc.
Examine scope for replacements of lamps by more energy efficient lamps, with due
consideration to luminaries, color rendering index, lux level as well as expected life
comparison. Replace conventional magnetic ballasts by more energy efficient ballasts, with due
consideration to life and power factor apart from watt loss.
Select interior colours for light reflection.
Assess scope for delamping
Assess scope for re-arrangement of lighting fixtures
Modify layout for optimum lighting.
Providing individual / group controls for lighting for energy efficiency such as:
On / off type voltage regulation type (for illuminance control)
Group control switches / units
-
7/28/2019 Bab 13 - Lighting
5/6
Berbagi dan Menyebarkan Ilmu Pengetahuan Serta Nilai-Nilai Perusahaan 5
PT. PLN (PERSERO)
PUSAT PENDIDIKAN DAN PELATIHAN LIGHTING
Occupancy sensors
Photocell controls
Timer operated controls
Modify switches / electrical circuit
Install input voltage regulators / controllers for energy efficiency as well as longer life
expectancy for lamps where higher voltages, fluctuations are expected.
Replace energy efficient displays like LED's in place of lamp type displays in control
panels / instrumentation areas, etc.
Opt for better reflector in lighting
Cleaning of reflector at regular interval
In power plant, locations like HT/LT switchgear rooms, cable galleries etc which sites /
locations are rarely visited, lighting circuits may be modified in such a way that keeping
25% to 30% lights always ON and remaining lights controlled by simple ON /OFF
switch provided at the entrance of the room / hall
Opportunities to reduce the power consumption/ improve the energy efficiency of other
loads which are connected to the lighting circuit
Some good practices in lighting are:
Installation of energy efficient fluorescent lamps in place of "Conventional" fluorescent
lamps.
Installation of Compact Fluorescent Lamps (CFL's) in place of incandescent lamps.
Installation of metal halide lamps in place of mercury / sodium vapour lamps.
Installation of High Pressure Sodium Vapour (HPSV) lamps for applications where
colour rendering is not critical
Installation of LED panel indicator lamps in place of filament lamps.
Light Control
Grouping of lighting system, to provide greater flexibility in lighting control
Installation of microprocessor based controllers
Optimum usage of day lighting
Installation of "exclusive" transformer for lighting
Installation of servo stabilizer for lighting feeder
Installation of high frequency (HF) electronic ballasts in place of conventional ballasts
-
7/28/2019 Bab 13 - Lighting
6/6
Berbagi dan Menyebarkan Ilmu Pengetahuan Serta Nilai-Nilai Perusahaan 6
PT. PLN (PERSERO)
PUSAT PENDIDIKAN DAN PELATIHAN LIGHTING
13.6.4 Recommendations
Each energy conservation measure should discuss
The back ground
Analysis and suggestion
Energy savings evaluation (Estimated before and after)
Impact on energy consumption after implementation
Economic feasibility
Investment required and payback period
Monitoring and verification of energy savings after implementation Efforts and resources required for sustainability of energy savings
The vendors/ suppliers/ manufactures details