b c a - d. t. s. access compliance report...proposal achieves the spatial requirements to provide...

16
A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077 [email protected] B C A - D. T. S. ACCESS COMPLIANCE REPORT LOT 2

Upload: others

Post on 08-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

B C A - D. T. S. ACCESS COMPLIANCE REPORT

LOT 2

Page 2: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

ARCHIDROME 25, Montview Pde,

Hornsby Heights,

NSW 2077

Nominated Architect

Tarun Chadha

NSW Registration Number 8777

COPYRIGHT

All rights reserved

© Archidrome

This document is copyrighted and may only be

used by Council for purposes associated with

the subject site to which it relates to the extent

authorised under Clause 57 of the

Environmental Planning and Assessment

Regulation 2000 as amended, for the express

purposes of the project, subject of the

Statement of Environmental Effects, and may

not be otherwise copied, reproduced,

distributed or used without the written

permission of the authorised

authors/publishers.

Page 3: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Access Compliance Report Development Application

This report is for a proposed New Building, the development being a building with classification as detailed below;

▪ Class 2 (building containing more than 2 SOUs i.e. sole-occupancy units) ▪ Class 7a (car park)

This report is based on the relevant components of;

▪ Building Code of Australia (BCA) 2016, Volume 1- Performance requirements of DP1, DP2, DP8, DP9,

▪ AS1428.1-2009 Part 1: General requirements for access, including any amendments ▪ AS1428.2-1992 Part 2: Enhanced and additional requirements- Building and facilities ▪ AS1428.4.1-2009 Part 4.1: TGSIs (Tactile ground surface indicators), including any amendments ▪ AS2890.6-2009 Part 6: Off-street parking for people with disabilities. ▪ AS4299-1995 Adaptable Housing ▪ Disability (Access to Premises-Building) Standards 2010 (henceforth referred to as APS) ▪ AS1735 Lifts types included in the BCA including Part 12: Facilities for persons with disabilities ▪ Livable Housing Australia’s Livable Housing Design Guidelines- Third Edition

▪ State Environmental Planning Policy 65 (SEPP 65), Objective 4Q1, relating to requirements of the provision of Livable Housing Australia’s Silver Level Apartments

The assessment of the proposed development has been undertaken to the extent necessary to issue DA (Development application) consent under the Environmental Planning and Assessment Act. The proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed requirements such as assessment of internal fit-out, details of stairs, ramps and other features will occur at CC (Construction Certificate) stage. By compliance with the recommendation in this report, the development complies with the requirements of Access Code of Disability (Access to Premises-Building) Standards 2010, the Disability Access relevant sections of Building Code of Australia 2016, the requirements of SEPP 65 related to Objective 4Q1 – Livable Housing and the essential criteria of AS4299-Adaptable Housing.

Page 4: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Summary • Equitable access: Wheelchair access is available to all areas where general access is available, which includes letter boxes, common areas including community spaces, roof tops, on- ground & basement parking, waste disposal rooms etc. This is achieved through complying lifts, walkways and ramps

• Parking: Compliance is achievable. Refer TEF Report.

• Adaptable Units: Over 10% of the total units are adaptable, which complies and exceeds with the council’s criterions.

Buildings LOT 2 S No. Level Total

Units Adaptable Unit

No. Total Adaptable

Units % of

Adaptable Units

Building A 61 5 1. Ground floor E7 1

2. Level 1 E7, W7 2

3. Level 2 E7 1

4. Level 3 E7 1

Building B 62 8 1. Ground floor W1A, E8 2

2. Level 1 W1A, E8 2

3. Level 2 W1A, E8 2

4. Level 3 W1A, E8 2

TOTAL UNITS 123 13 10.57%

NOTE: All the adaptable units are also livable.

• Livable Units: Over 17% of the total units are adaptable, which complies and exceeds with the council’s criterions.

Buildings LOT 2 Sno. Level Total

Units Livable Unit No. Total Livable

Units % of Livable

Units

Building A 61 12 1. Ground floor W3, E3, E6 3

2. Level 1 W3, E3, E6 3

Page 5: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

3. Level 2 W3, E3, E6 3

4. Level 3 W3, E3, E6 3

Building B 62 10 1. Ground floor E5 1

2. Level 1 W4, E4, E5 3

3. Level 2 W4, E4, E5 3

4. Level 3 W4, E4, E5 3

TOTAL UNITS 123 22 17.88%

Page 6: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Compliance assessment with Access related requirements of BCA and Disability (Access to Premises-Building) Standards 2010 (APS)

BCA Part D3 Access for People with a Disability BCA D3.1 General building Access requirements SOU refers to a Sole Occupancy Unit

Requirement

For residential use components, access is required: - From a required accessible pedestrian entrance to at least 1 floor with SOUs and till the entry of doors of each SOU on that level. - To and within 1 of each type of room or space in common use. - Where floor is accessed by an AS1428.1 ramp or lift, all SOUs on that level till their entry doors and to and within all common use areas on that level. - Covered car park- to and within any level containing accessible carparking spaces

Compliance Comments

Capable of compliance - Access has been provided from the main pedestrian entry doorway to the entry doors of all SOUs on all levels by means of accessible pathways and lifts. - Equitable access is available from street to open garbage disposal, letter boxes by means of a ramp or lift. - Equitable access is available from street to all open community areas on ground level and roof level, including pool

BCA Part D3.2 Access to buildings

Requirement

Accessway is required from; - Main pedestrian entry at the site boundary for new buildings. - Main pedestrian entry door for existing buildings (as per APS). - Any other accessible building connected by a pedestrian link. - Accessible car parking spaces.

Compliance Comments

Capable of compliance - Level Access to be provided from the main pedestrian entry at the site boundary. OR Access by means of walkways / ramps to be provided from the main pedestrian entry at the site boundary. - External Walkway / Pedestrian Access as per requirements of AS1428-2009 - Details to be verified at CC stage of works. - All pedestrian entries have been designed to be accessible- Further detailing to be undertaken at CC stage of works The basement plan indicates a path of access which is at grade, for people to move between lifts.

Page 7: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

BCA Part D3.3 Parts of buildings required to be accessible

Requirement

Every Ramp with grades steeper than 1:20 and less than or equal to 1:14 (excluding fire isolated ramp) is to be compliant with : - AS1428.1-2009 (including but not limited to - maximum grade of 1:14 with appropriate landings at a maximum of 9M of a flight of ramp). - Handrails and kerbs to be provided on both sides with appropriate handrails extensions. - 1M clear width to be provided between handrails / kerb / kerbrails. - Every Fire-isolated Stairway is to be compliant with AS1428 - Slip resistance of ramp and landings to comply with BCA as per AS4299

Compliance Comments

Capable of Compliance There are ramps in landscape areas with a 1:14 Gradient. These comply with AS1428.1, and will need to be further detailed at CC stage. - Access to lobbies, parking, waste disposal areas, letter box, community space, entry to each unit achieved through walkways & ramps as noted on plans. This is a DTS solution. - No step ramp, kerb ramp have been identified in the development. - Every Stairway, Fire-isolated Stairway, Slip resistance requirements as per AS4299, turning spaces requirement, carpet specifications are capable of compliance. Details to be verified at CC stage of works.

Page 8: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

BCA Part D3.4 Exemption

Requirement Access is not required to be provided in the following areas : - Where access would be inappropriate because of the use of the area - Where area would pose a health and safety risk - Any path which exclusively provides access to an exempted area

Compliance Comments

Areas such as lift machine rooms, fire services room, mechanical rooms etc. in the development are exempted from providing access under this clause due to WHS concerns.

BCA Part D3.5 Accessible Carparking

Requirement There are no Accessible carparking requirements for a Class 2 under the BCA. If adaptable housing has been mandated by the Council, carparking spaces will be required under the requirements of AS4299- Adaptable housing.

Compliance Comments

Capable of compliance Blacktown Council requires provision of 10% Adaptable units in the development. Complies with AS4299, refer traffic engineering report. Note that visitors and commercial spaces are also allocated as accessible in recommendation of Council guidelines as marked on basement plans.

AS2890.6-2009 requirements for Accessible car parking space

Requirement - Dedicated space, slip resistant flooring surface, central Bollard, pavement marking in dedicated space, minimum headroom at entrances.

Compliance Comments

Capable of compliance. Parking has a shared zone and meets minimum width length and height requirements. Detailed review has been undertaken by TEF (Traffic engineer’s Report)

BCA Part D3.6 Signage

Requirement

Braille and Tactile signage is required to identify Accessible Sanitary facilities, Hearing Augmentation, a Fire exit door.

Compliance Comments

- Capable of compliance. - Signages provided at sanitary facilities, fire exit doors etc - Details of selected signage to be verified at CC stage of works.

Page 9: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

BCA Part D3.8 Tactile indicators (TGSIs)

Requirement TGSIs are required when approaching: - Stairways other than fire-isolated stairways. - Escalators / passenger conveyor / moving walk. - Ramp (other than fire-isolated ramps / kerb or step or swimming pool ramps). - Under an overhead obstruction of <2M if no barrier is provided. - When accessway meets a vehicular way adjacent to a pedestrian entry (if no kerb / kerb ramp provided at the location). Compliance is required with AS1428.4.1 including Luminance contrast and slip resistance requirements for all TGSIs.

Compliance Comments

Capable of compliance. TGSI selections generally take place at CC stage of works. Selection of TGSIs as specified will lead to compliance and these selection details are to be verified at CC stage of works.

BCA Part D3.11 Limitations on Ramps

Requirement On an accessway: - A series of connected ramps must not have a combined vertical rise of more than 3.6M; - a landing for a step ramp must not overlap a landing for another step ramp or ramp.

Compliance Comments

Complies. No such instances are noted on plans.

BCA Part D3.12 Glazing on Accessways

Requirement Glazing strips requirements: Where any glazing capable of being mistaken for a doorway or opening are required to have a glazing strip as per requirements of AS1428.1

Compliance Comments

Capable of compliance Glazing strip selections generally take place at CC stage of works. Selection of glazing strips as specified above will lead to compliance and these selection details are to be verified at CC stage of works.

BCA Part F Accessible Sanitary Facilities

BCA F2.4 Accessible sanitary facilities

Requirement Accessible unisex toilet is to be provided in accessible part of building such that; - It can be entered without crossing an area reserved for 1 sex only - Where male and female sanitary facilities are provided at different locations, Accessible unisex toilet is only required at one of the locations - Even distribution of LH and RH facilities - An accessible facility is not required on a level with no lift / ramp access.

Page 10: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Compliance Comments

- Capable of Compliance - Provision has been made in basement for an accessible toilet for general

use. - In adaptable units, toilets are designed to be adaptable. - In commercial units, the plan notes that an accessible toilet will be installed

in each commercial unit, which complies with the requirements for commercial spaces.

- Details to be verified at CC stage of works.

BCA Part E Lift Installations

BCA E3.2 Stretcher facility in lifts

Requirement A Stretcher lift is to be provided if a passenger lift is installed to serve any storey Confirm this requirement with your BCA consultant.

Compliance Comments

Design dimensions of all lifts comply with the requirements to provide stretcher lifts. Details to be verified at CC stage of works.

BCA E3.6 Passenger lift

Requirement In an accessible building, Every Passenger Lift (excluding electric passenger lift, electrohydraulic passenger lift, inclined lift) must be subject to limitations on use and must comply with Tables E3.6a and E3.6b

Compliance Comments

Capable of compliance. Provide a certificate of compliance from the lift supplier, stating that the proposed lift complies with the requirements of BCA Part E3- Lift installations.

Page 11: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

AS4299.1995- Adaptable Housing

AS4299.1995 - Class C – Essential requirements.

Siting Continuous accessible path of travel is required from street frontage and vehicle parking to entry doorway of the Adaptable unit.

Access is provided from street by means of an AS1428.1 compliant ramp / walkway. Details to be verified at the CC stage

Letter boxes Letterboxes to be on hard standing area connected to accessible pathway

Capable of compliance. Plan notes letterbox is located on flat surface connected to accessible path of travel from street to lobby. Details to be verified at the CC stage

Parking Car parking space or garage of minimum height or a hard surfaced level outside is to be provided as a sheltered car park or can be provided in the future

Capable of compliance. Sections indicate a height of 3000 mm slab to slab, in basement is available. This is sufficient to achieve the 2500 clear height at accessible parking spaces and shared zones. Refer TEF report. Details to be verified at the CC stage

TYPE 1: 2-Bed TYPE 2: 2-Bed

TYPE 3: 3-Bed

Page 12: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Accessible Entry

Door circulation requirements of S1428.1 with approach directions shown with arrows below. Accessible entry to be provided with, - An accessible door threshold - 1550mm diameter landing - 850mm clear opening door with clearances, door

Capable of compliance. Adaptable layout detail plan indicates a 1550 diameter circle at entry doors. Over 1550 x 1550 is available at all unit entry doors All unit entry doors are 900 wide leaf Details to be verified at the CC stage

Interior: General

Internal doors to have minimum clearance with provision for compliance with AS1428.1 for door approaches and minimum corridors width of 1M - Door hardware operable with one hand and located 900-1100mm above floor

Capable of compliance. Provide an 1200X 1200mm clear opening in front of doors to the adaptable bathroom and 1 main bedroom. Adaptable layout detail plan indicates a 1550 diameter circle at entry of main bedroom door Details to be verified at the CC stage

Main bedroom

At least one bedroom of area sufficient to accommodate a queen size bed and wardrobe and circulation space requirements of AS1428.2

Adaptable layout detail plan indicates a 1550 diameter circle in front of robe. A queen bed is drawn, with required 1m spaces available on all 3 sides of the bed. Complies Refer detailed plans. Details to be verified at the CC stage.

Page 13: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Main Adaptable bathroom

Provision for bathroom area with Circulation spaces of Shower and WC (including fixtures) to comply with AS1428.1.

Complies Refer Post adaptable plan A bathroom with minimum req. space is noted on plans. Refer plans.

Laundry Provision for adequate circulation space in front of or besides appliances (minimum 1550mm depth) - Circulation at doors to comply with AS1428.1 - Provision for automatic washing machine

Capable of compliance. All Laundries have over 1550 space in front of them. Details to be verified at the CC stage

Other General requirements

All surfaces to be Slip resistant to AS3661 and AS 4586 - All GPOs and Lighting/ lux requirements as per AS4299 - All waterproofing as per AS4730

Capable of compliance. Details to be verified at the CC stage

Page 14: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

SEPP 65 – Part 4Q1- Livable Housing

Compliance assessment with Objective 4Q1 that requires 20% of the units to incorporate the features of the Livable Housing Guidelines Silver level

Essential requirements. Dwelling Access

(a) Provide a safe and continuous pathway from: (i) front site boundary or (ii) associated carparking space, if provided, which may include the driveway on the site, to a step-free entrance (b) The path to be 1M clear, step-free, even, firm, slip-resistant with a crossfall of not more than 1:40.

Complies. The design complies with these requirements.

(c) Step ramp can be provided for max height of 190mm, max grade of 1:10, min width of 1M and max length of 1900mm.

NA

Dwelling entry

(a) Dwelling Entry should provide an entrance door with (i) min clear opening width of door to be 820mm (ii) Step free threshold of max 5mm with rounded or bevelled lip (iii) Sheltered (b) Level landing of 1200x1200mm at step-free entrance door (c) Entrance to be connected to a pathway

Complies. All unit entry doors feature a 900 wide leaf. Detail further at CC

(d) Max permissible threshold is 56mm where provided with Capable of

Page 15: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

a threshold ramp. compliance To be further detailed at CC

Car parking (a) Where the parking forms part of the dwelling access, the space to be (i) Min 3.2m wide and 5.4m long (ii) even, firm and a slip resistant surface and (iii) level with 1:40 max gradient (1:33 for bitumen)

NA

Internal doors and corridors

(a) Doors to rooms on the entry level used for living, dining, bedroom, bathroom, kitchen, laundry and bathroom to be (i) 820mm clear opening and (ii) provided with a level threshold of max 5mm between abutting surfaces with rounded or bevelled lip (b) Internal corridors and passageways to doorway to be min 1M clear

Capable of compliance. To be further

detailed at CC

Toilet (a) Toilet to be provided on the ground or entry level with (i) Min 900mm between walls if located in separate room (ii) Min 1200mm clear space in front of the WC pan exclusive of door swing. (b) If toilet is located in bathroom, toilet pan should be located in corner of the room to enable installation of grabrails.

Capable of compliance. One toilet in each unit has 1200 x 900 clear in front of WC as shown in the detailed Livable unit plans. Verify at CC

Shower (a) One bathroom to have a slip resistant, step free shower. Shower screens are permitted as long as they can be easily removed. (b) Shower to be located in the corner of the room

Capable of compliance. To be further detailed at CC

Page 16: B C A - D. T. S. ACCESS COMPLIANCE REPORT...proposal achieves the spatial requirements to provide access for people with a disability and it is assumed that assessment of the detailed

A R C H I D R O M E 25 MONTVIEW PDE HORNSBY HEIGHTS NSW 2077

[email protected]

Reinforcement of toilet & bathroom walls

(a) Bathroom walls shall be constructed of masonry or provided with wall reinforcement to allow the later fixing of grabrails around the shower, bath (if provided) and toilet. (b) The fastenings, wall reinforcement and grabrails combined must be able to withstand at least 1100N of force applied in any position and in any direction. Builder to photograph the wall before the sheeting. (c), (d) and (e) The walls around toilet / bath and shower to be via: (i) Noggins with a thickness of at least 25mm (ii) Sheeting with a thickness of at least 12mm

Capable of compliance. To be further detailed at CC

Internal Stairways

(a) Where an internal stair rises more than 1M, a continuous handrail must be provided on 1 side.

N/A No internal stairway in units.

Disability Discrimination Act The Federal Disability Discrimination Act 1992 (DDA) provides protection for everyone in Australia against discrimination based on disability. Note that further access consultancy would be required at CC stage to not only ensure compliance with the building, but also with the furniture such as lobby furniture, BBQ area furniture etc.

About the author Tarun Chadha is a registered architect in NSW #8777, and has provided access solutions for various projects over the past 5 years such as RFBs, Childcare centres and fitouts.