atex ex-proof chart

2
AT mosphères  E X plosibles  CETOP is: • the communication platform for uid power in Europe • an international umbrella organisation for 17 national uid power associations with • more than 1,000 member companies all over Europe CETOP General Secretariat • Lyoner Strasse 18 • 60528 Frankfurt/Main • Germany • e-mail: [email protected] • www.cetop.org November 2008 This poster is not intended to be exhaustive. It is based on the information supplied by national CETOP member associations. We cannot assume responsibility for the correctness of this. All information is subject to change. A TEX/IECEx: Certication standards identical for electrical equipment. For IECEx and ATEX equipment, possibility to deliver the certicates based on the same standards. Audit of the quality system for IECEx and ATEX based on common requirements. General requirements Flameproof enclosure Pressurised apparatus Powder lling Oil immersion Increased safety Intrinsic safety Encapsulation 60079-0 61241-0 61241-1 - - d tD px/py/pz pD q - o - e - ia/ib/ic iaD/ibD nA nL nR nC - ma/mb maD/mbD Concept TYPE OF PROTECTION FOR ELECTRICAL EQUIPMENT Code Gas Dust Gas Dust IEC/EN standards 61241-4 - - - 61241-11 - 61241-18 60079-1 60079-2 60079-5 60079-6 60079-7 60079-11 60079-15 60079-18 Non sparking Energy-limited Restricted-breathing Sealed devices ZONES/EQUIPMENT CATE GORIES Gas Dust (dened in application of 1999/92/EC Directive) Zones Equipment category 1D 2D or 1D 3D, 2D or 1D 20: Permanent presence 21: Occasional presence 23: Rare presence 0: Permanent presence 1: Occasional presence 2: Rare presence 1G 2G or 1G 3G, 2G or 1G Methane Propane Ethylene Hydrogen/Acetylene IIA IIB IIC I Mines Area Group Gas reference Surface EXPLOSION GROUPS Certication Construction Fluid Power Application Control Testing Certicate of conformity Notied Body Zones – Temperature Customer – End user Standards – Test Report Notied Body and/or Manufacturer Declaration of conformity Manufacturer Quality Assurance Manufacturer Directives – Standards ATEX General requirements Flow restricting enclosure Flameproofenclosure Constructional safety Control of ignition sources Liquid immersion 13463-1 13463-2 - fr d c b k 13463-3 13463-5 13463-6 13463-8 Gas/ Dust Gas/ Dust TYPE OF PROTECTION FOR NON-ELECTRICAL EQUIPMENT EN standards Code Concept Paper bre (16 mm) Aluminium (< 10 mm) Corn starch (< 10 mm) Wheat (37 mm) Wood (60 mm) Sugar (30 mm) Polyethylene (72 mm) 570 560 335 430 460 300 310 480 No ignition (fusion) 530 510 500 490 440 cloud 5 mm layer DUST IGNITION TEMPERATURES Ignition temperatures (°C) Material Fluid Power SA Belgium, Brussels Type: …/0123456D U=230 VAC; P=2.5 W Ex d mb IIC T4 Ex tD A21 IP67 T 135°C Tamb. –40°C; +65°C  0081 II 2 G D LCIE 02 ATEX 6024 X XX.XX.XXXX Type of equipment Date of production Gas marking Dust marking ATEX marking MARKING Name of manufacturer Electrical parameters Temperature parameters ATEX certicate no. Non-protected Non-protected Protected against vertically falling water drops Protected against vertically falling water drops when enclosure tilted up to 15° Protected against spraying water when up to 60° from vertical Protected against splashing water from any direction Protected against jets of water from any direction Protected against powerful jets of water from any direction Protected against immersion Protected against continuous immersion Second gure indicates protection against water penetration First gure indicates protection against dangerous access and solid foreign objects According to IEC/EN 60529 0 0 Protected against solid object Ø 50 mm or more 1 1 Protected against solid object Ø 12,5 mm or more 2 2 Protected against solid object Ø 2,5 mm or more 3 3 Protected against solid object Ø 1 mm or more 4 4 Dust protected 5 5 Dust-tight 6 6 7 8 DEGREE OF PROTECTION BY ENCLOSURE IP Europäisches Komitee Ölhydrau lik & Pneumatik · European Oil Hydraulic & Pneumatic Committee · Comité Européen des Transmissions Oléohydrau liques & Pneumatiques For protection systems: category 1 or M1 Category Electrical equipment Mechanical/pneumatic/ hydraulic equipment EUROPEAN SCHEME OF CERTIFICATION (94/9/EC) EC type examination (Annex III) Production quality assurance (Annex IV or Annex V) EC type examination (Annex III) Product quality assurance (Annex VII or Annex VI) EC type examination (Annex III) Production quality assurance (Annex IV or Annex V) Internal control (Annex VIII) Communicate the le to a notied body Internal control of production (Annex VIII) Unit verication (Annex IX) Internal control of production (Annex VIII) 1 or M1 2 or M2 3 1 or 2 or 3 or T1 T2 T3 T4 T5 T6 T1 T1 T2 T2 T3 T4 T6    T   e   m   p   e   r   a    t   u   r   e   c    l   a   s   s Typical substances    M   a   x    i   m   u   m   s   u   r    f   a   c   e    t   e   m   p   e   r   a    t   u   r   e GAS TEMPERATURE CLASSES 300 450 100 85 560°C – Hydrogen 537°C – Methane 425°C – Ethylene 305°C – Acetylene 210°C – Kerosene 160°C – Ethyl ether 95°C – Carbon disulphide 200 135 °C 600 500 400 300 200 100

Upload: yoon-ng

Post on 07-Apr-2018

239 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ATEX Ex-Proof Chart

8/3/2019 ATEX Ex-Proof Chart

http://slidepdf.com/reader/full/atex-ex-proof-chart 1/1

AT mosphères EX plosibles 

CETOP is: 

• the communication platform for fluid power in Europe 

• an international umbrella organisation for 17 national fluid power associations with 

• more than 1,000 member companies all over Europe 

CETOP General Secretariat • Lyoner Strasse 18 • 60528 Frankfurt/Main • Germany • e-mail: [email protected] • www.cetop.org  November 2008 

This poster is not intended to be exhaustive. It is based on the information supplied by national CETOP member associations. We cannot assume responsibility for the correctness of this. All information is subject to change.

ATEX/IECEx: Certification standards identical for electrical equipment. For IECEx and ATEX equipment, possibility to 

deliver the certificates based on the same standards. Audit of the quality system for IECEx and ATEX based on common requirements.

General requirements

Flameproof enclosure

Pressurised apparatus

Powder filling

Oil immersion

Increased safety

Intrinsic safety

Encapsulation

60079-0 61241-0

61241-1

- -

d tD

px/py/pz pD

q -

o -

e -

ia/ib/ic iaD/ibD

nA

nL

nR

nC

-

ma/mb maD/mbD

Concept

TYPE OF PROTECTION FOR ELECTRICAL EQUIPMENT

Code

Gas Dust Gas Dust

IEC/EN standards

61241-4

-

-

-

61241-11

-

61241-18

60079-1

60079-2

60079-5

60079-6

60079-7

60079-11

60079-15

60079-18

Non sparking

Energy-limited

Restricted-breathing

Sealed devices

ZONES/EQUIPMENT CATEGORIES

Gas

Dust

(defined in application of 1999/92/EC Directive)

Zones Equipmentcategory

1D

2D or 1D

3D, 2D or 1D

20: Permanent presence

21: Occasional presence

23: Rare presence

0: Permanent presence

1: Occasional presence

2: Rare presence

1G

2G or 1G

3G, 2G or 1G

Methane

Propane

Ethylene

Hydrogen/Acetylene

IIA

IIB

IIC

IMines

Area Group Gas reference

Surface

EXPLOSION GROUPS

Certification Construction

Fluid PowerApplication

ControlTesting

Certificate of conformityNotified Body

Zones – TemperatureCustomer – End user

Standards – Test ReportNotified Body and/or Manufacturer

Declaration of conformityManufacturer

Quality AssuranceManufacturer

Directives – Standards

ATEX

General requirements

Flow restricting enclosure

Flameproof enclosure

Constructional safety

Control of ignition sources

Liquid immersion

13463-1

13463-2

-

fr

d

c

b

k

13463-3

13463-5

13463-6

13463-8

Gas /Dust Gas /Dust

TYPE OF PROTECTION FOR NON-ELECTRICAL EQUIPMENT

EN standards CodeConcept

Paper fibre (16 mm)

Aluminium (< 10 mm)

Corn starch (< 10 mm)

Wheat (37 mm)

Wood (60 mm)

Sugar (30 mm)

Polyethylene (72 mm)

570

560

335

430

460

300

310

480

No ignition(fusion)

530

510

500

490

440

cloud 5 mm layer

DUST IGNITION TEMPERATURES

Ignition temperatures (°C)Material

Fluid Power SA

Belgium, Brussels

Type: …/0123456D

U=230 VAC; P=2.5 W

Ex d mb IIC T4

Ex tD A21 IP67 T 135°C

Tamb. –40°C; +65°C

 0081 II 2 G D

LCIE 02 ATEX 6024 X

XX.XX.XXXX

Type of equipment

Date of production

Gas marking

Dust marking

ATEX marking

MARKING

Name of manufacturer

Electrical parameters

Temperature parameters

ATEX certificate no.

Non-protected Non-protected

Protected against vertically falling water

drops

Protected against vertically falling water

drops when enclosure tilted up to 15°

Protected against spraying water

when up to 60° from vertical

Protected against splashing water

from any direction

Protected against jets of water from any

direction

Protected against powerful jets of water

from any direction

Protected against immersion

Protected against continuous immersion

Second figure indicates protection against

water penetration

First figure indicates protection against

dangerous access and solid foreign objects

According to IEC/EN 60529

0 0

Protected against solid object

Ø 50 mm or more1 1

Protected against solid object

Ø 12,5 mm or more2 2

Protected against solid object

Ø 2,5 mm or more3 3

Protected against solid object

Ø 1 mm or more4 4

Dust protected 5 5

Dust-tight 6 6

7

8

DEGREE OF PROTECTION BY ENCLOSURE

IP

Europäisches Komitee Ölhydraulik & Pneumatik · European Oil Hydraulic & Pneumatic Committee · Comité Européen des Transmissions Oléohydrauliques & Pneumatiques 

For protection systems: category 1 or M1

Category Electrical e quipment Mechanical/pneumatic/hydraulic equipment

EUROPEAN SCHEME OF CERTIFICATION (94/9/EC)

EC type examination (Annex III)

Production quality assurance(Annex IV or Annex V)

EC type examination (Annex III)

Product quality assurance(Annex VII or Annex VI)

EC type examination (Annex III)

Production quality assurance(Annex IV or Annex V)

Internal control (Annex VIII)

Communicate the file to anotified body

Internal control of production(Annex VIII)

Unit verification (Annex IX)

Internal control of production(Annex VIII)

1 or

M1

2 or

M2

3

1 or

2 or 3

or

T1

T2

T3

T4

T5

T6

T1

T1

T2

T2

T3

T4

T6

   T  e  m  p  e  r  a   t  u  r  e  c   l  a  s  s

Typical substances

   M  a  x   i  m  u  m

  s  u  r   f  a  c  e   t  e  m  p  e  r  a   t  u  r  e

GAS TEMPERATURE CLASSES

300

450

100

85

560°C – Hydrogen

537°C – Methane

425°C – Ethylene

305°C – Acetylene

210°C – Kerosene

160°C – Ethyl ether

95°C – Carbon disulphide

200

135

°C

600

500

400

300

200

100