ashida numerical single pole ef protection relay (preliminary)

15
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com Ref.: ADR211E Issue: 06 15.01.08 Page 1/6 Type: ADR211E (ADITYA Series) (Preliminary) Features: Single Element EF IDMT with instant trip. Back - lit LCD display for settings. Display of fault current / Load current. Selection of Curve: Six selectable curves (Normal Inverse 1 (C1), Normal Inverse 2 (C2), Very Inverse (C3), Extremely Inverse (C4), Long Time Inverse (C5) & Definite Time (C6). Design using DSP technology. Latching of fault current up-to last 5 fault. Password protection for setting. Site selectable CT secondary (For Model AM00x02/x03) Relay can be made either IDMT or Define time. Programmable operating time in instantaneous element Suitable For REF Protection SCADA Compatibility (RS232 and RS485 Communication For model ADR211E) General: The ADR211E is member of Ashida Numerical Relay family (Aditya Series) design to meet demand of low and medium switchgear control. The ADR211E is single pole EF relay with instantaneous high set and programmable output to simplify feeder protection wiring. The ADR211E continuously monitors earth current, through CT connections. The high-speed micro-controller samples this current through a 12-bit A/D converter. The micro-controller performs powerful Digital Algorithms to find out Amplitude of current signal, and then this value is use for protection and metering function. All measurement is tuned to fundamental frequency. Each input current is also displayed on 16 x 2 LCD display for metering. The Relay is having main three functions 1) Protection 2) Self- Supervision 3) Measurement 1. Protection Functions: The ADR211E give maximum benefit/cost ratio. The ADR211E give all the advantage of numerical relay at affordable cost. Following is summery of different protection functions provided by relay. ANSI IEC Protection Functions 50N I E >> Instantaneous Earth Fault Protection. 51N I E >t, I EP Time Over current Protection. ASHIDA Numerical Single Pole EF Protection Relay ASHIDA ADR211E

Upload: others

Post on 18-Dec-2021

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR211EIssue: 06 15.01.08

Page 1/6

Type: ADR211E(ADITYA Series)

(Preliminary)

Features:• Single Element EF IDMT with instant trip.

• Back - lit LCD display for settings.

• Display of fault current / Load current.

• Selection of Curve: Six selectable curves(Normal Inverse 1 (C1), Normal Inverse 2(C2), Very Inverse (C3), Extremely Inverse(C4), Long Time Inverse (C5) & DefiniteTime (C6).

• Design using DSP technology.

• Latching of fault current up-to last 5 fault.

• Password protection for setting.

• Site selectable CT secondary (For ModelAM00x02/x03)

• Relay can be made either IDMT orDefine time.

• Programmable operating time ininstantaneous element

• Suitable For REF Protection

• SCADA Compatibility (RS232 and RS485 Communication For model ADR211E)

General:The ADR211E is member of Ashida Numerical Relay family (Aditya Series) design to meet demandof low and medium switchgear control. The ADR211E is single pole EF relay with instantaneous highset and programmable output to simplify feeder protection wiring. The ADR211E continuouslymonitors earth current, through CT connections. The high-speed micro-controller samples thiscurrent through a 12-bit A/D converter. The micro-controller performs powerful Digital Algorithmsto find out Amplitude of current signal, and then this value is use for protection and meteringfunction. All measurement is tuned to fundamental frequency. Each input current is also displayedon 16 x 2 LCD display for metering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3) Measurement

1. Protection Functions:

The ADR211E give maximum benefit/cost ratio. The ADR211E give all the advantage of numericalrelay at affordable cost. Following is summery of different protection functions provided by relay.

ANSI IEC Protection Functions

50N IE>> Instantaneous Earth Fault Protection.

51N IE>t, IEP Time Over current Protection.

ASHIDA Numerical Single Pole EFProtection Relay

ASHIDA

ADR211E

Page 2: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR211EIssue: 06 15.01.08

Page 2/6

Type: ADR211E(ADITYA Series)

(Preliminary)

1.1. Protection Function:

The ADR211E has single element (EF). The tripping current can be set in dual stage from3% to 80% in steps of 1% by Keys switch provided on front panel. The unit has selectionof IDMT characteristic of International IEC standard, Very inverse / Extremely Inverse /Long Inverse and Standard Inverse (3.0 sec, 1.3sec, 1.5 Sec, 0.8 sec & 13.3 sec at 10times). The unit also has Time Multiplier Setting (TMS) from x0.01 to x1.0 for IDMT delaymultiplication. The instantaneous tripping function is having range of 100% - 1200% insteps of 100%. The high speed CPU continuously monitors the current input andcompares with IDMT as well as instantaneous setting. If current is above instantaneoussetting the relay provides immediate trip command bypassing IDMT delay. If is inputcurrent is less than instantaneous setting but more than IDMT setting, CPU calculateIDMT delay as per selected IDMT characteristic multiply it with TMS setting and providetrip command if fault is persist even after this time delay.

All the settings are password protected to prevent unauthorised change.The relay is available in verity of model for different application

2.0 Supervision Function: -2.1 Self-supervision: -

The continuously keeping track on its internal hardware and the movement it detect any failureof any component, it give message on LCD display, This feature is very useful to give preinformation to avoid any mall - operation. In such situation it uses some default setting andremains in protection mode.

3.0 Measurement Function:In normal condition this display shows all settings. Via keyboard the display can be program toshow the actual current flowing through the relay. If current excesses set value the relay givestrip command. The type of fault is displayed on LCD display.During the fault condition the relay measure the fault current and store in non-volatilememory. The fault current can be read via keyboard on LCD display Last 5 fault valuesalong with tripping counter can be view via key-board. All settings are save in Electricallyerasable read only memory and remain.

Page 3: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR211EIssue: 06 15.01.08

Page 3/6

Type: ADR211E(ADITYA Series)

(Preliminary)

4.0 Ordering Information:While Ordering Specify the fol lowing Information for ADR211E Relay

Ordering information:

A D R 1 1 1 A - A M - X X X - X X - X - X - X X - X

ExampleADR211E – AM-001-01-3-0-02-0Type: ADR211EBack Terminal Layout : Relay with selectable CT.Cabinet Type : CSA-150 non DrawoutAuxi l iary Supply: 77-250Vdc CT sec: 1/5 Amp.

PT Secondary0

Auxiliary Supply01 = 18 – 52 V dc02 = 77 – 250 V dc03 = 110 VAC04 = 230 VAC05 = 60 VDC

Reserved for Future Use

CT Secondary1 = 1 Amp.2 = 5 Amp.3 = 1 Amp. / 5 Amp. Selectable

D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s

A M X X X – X X – X – X – X X – X

AM XXX XX Description X

EF Relays

002 01 Relay with site selectable CT. 2 NO trip & 4 NOAnn. Duty contacts.

CSA – 150 3

02 Relay with site selectable CT. 2 NO trip & 2 NOAnn. Duty contacts.

CSA – 150D Drawout 3

Page 4: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR211EIssue: 06 15.01.08

Page 4/6

Type: ADR211E(ADITYA Series)

(Preliminary)

5.0 Technical Specifications:

Sr.No.

Specification Particulars

I. Inputs : ModelAM00101xxxxx &AM00102xxxxx

Site selatctable CT 1 or 5 Amp.

: Setting For EF 3% - 80%: Operating Time Normal Inverse 1 (C1)

Normal Inverse 2 (C2)Very Inverse (C3)Extremely Inverse (C4)Long Time Inverse (C5)Definite Tme (C6) 00(Inst) – 99.9Sec

: Inst. Setting 100% - 1200% or bypass

Protection RelaySetting Range

: Inst Operating Time 0.05 – 1.00SecOutput contacts : Model AM00101 2 NO Trip duty and 4 NO Ann. Duty contact.

: Model AM00102 2 NO Trip duty and 2 NO Ann. Duty contact.

II. Pickup Current : Within 1.1 times of set current value.

III. Resetting Current : Within 90% of set value.

IV. Time Accuracy : Within class 2.5 As per IS: 3231.

V. Burden on CT : Less than 0.2VA.

VI. Aux. Supply : 18 - 52VDC or 77 - 250VDC. To be specified while ordering.

VII. Burden on Aux.Supply

: Less than 10VA on any supply.

VIII. Contact Rating TripDuty

: Make and carry for 3sec. – 7500VA with max. 30A & 660VAC/DC: Make and carry for continuous - 1250VA with max. 5A & 660VAC/DC: Break AC - 1250 VA DC - 100 W resistive 50W inductive.

IX. Operational Indicators (Flags)ON : Green LED indicates Relay OK

: In case of following condition led become OFF1. Problems in relay Hardware.2. Auxiliary supply is not sufficient for relay operation.

FAULT : Red LED’s indicates the relay trip, Hand Reset (HR) Type.PKP : Red LED indicates relay Pickup.TRIP : Indicates that Trip pulse is being executed. When BYPASS P.B. is

pressed, actual trip is not executed.

X. Thermal WithstandCapacity

: 40 times the normal current for 3sec.

: 2 times Continuous

XI. High Voltage Test : IEC 60255-5: Except DC Voltage – 2.0 kV (RMS), 50Hz: Only DC voltage – 2.8 kV DC: Between Open contact of TRIP / CLOSE 1.5kV (RSM) 50Hz

Page 5: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR211EIssue: 06 15.01.08

Page 5/6

Type: ADR211E(ADITYA Series)

(Preliminary)

: Between Open contact of ALARM – 1kV (RSM) 50Hz

XII. Impulse VoltageTest (all circuit class– III)

: IEC60255-5: 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative impulse atinterval of 5 sec

XIII. High Frequency test : IEC 60255-22-1, Class III: 2.5 kV (peak) 1MHz , τ = 15µs 400 surges / s duration 2 s

XIV. Electro staticDischarge

: IEC 60255-22-2 Class III and IEC 61000-4-2 class III: 4kV/6kV contact discharge, 8kV air discharge, both polarities 150pF, Ri330 Ω

XV. Irradiation with radiofrequency field,pulse-modulated,

: IEC 60255-22-3 and IEC 61000-4-2 class III: 10V/m; 80 to 1000MHz; 80%; 1kHz AM

XVI. Fast transientinterference/bursts

: IEC 60255-22-3 and IEC 61000-4-3, class III: 4kV; 5/50ns; 5kHz burst duration = 15ms;: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.

XVII. Shock Test : IEC 60255-21-2 class 1: Semi-Sinusoidal: 5g acceleration, duration 11ms,: Each 3 shocks in both direction of the 3 axes

XVIII. Vibration Test : IEC 60255-21-1 class 1 / IEC 60068-2-6: Sinusoidal 10 to 60Hz ±0.035 mm: Amplitude, 60 to 150Hz, 0.5g acceleration: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal

Drawing References : For Cabinet Type CSA -150 - MAC00101: For Operating C1 - APR02201 Characteristics C2 - APR01801

C3 - APR05101C4 - APR05201C5 - APR05301

XIX.

: For Electrical Connection Model : AM00x01xxxxx - APR07403 Model : AM00x02 - APR07404

: For Stabilizing Resister - ACAGRxxxx

• Datasheet Change Log for ADR211EIssue No.(Revision)

Date Description /Changes

01 15.01.08 Original Revision

Page 6: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 7: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 8: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 9: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 10: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 11: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 12: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 13: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 14: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Page 15: ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)