apresentação - switchsync f236
DESCRIPTION
Envíenos sus comentariosMake it easier for other people to find your content by providing more information about it.AGREGAR MÁS ARCHIVOSArrastre los archivos de su equipo hasta esta área.Archivo 1 de 2 |Apresentação - Switchsync F236.pdf|Cargando...85%Cargando...Puntaje de detección1/5Nombre de archivo: Apresentação - Switchsync F236.pdf*Título: (Campo requerido)*Descripción:(Campo requerido)TRANSCRIPT
-
SWG/BTA 2000-03-27 Switchsync.PPT
SWITCHSYNCTM
Strategies and Function
for
CONTROLLED SWITCHING
-
SWG/BTA 2000-03-27 Switchsync.PPT
PROBLEM
SWITCHING INTRODUCES TRANSIENTS.
SWITCHINGINSTANT
-
SWG/BTA 2000-03-27 Switchsync.PPT
Cap. bank energising at voltage peak
TRANSIENT AT HV SIDE TRANSIENT AT 220 V OUTLET
-
SWG/BTA 2000-03-27 Switchsync.PPT
Cap. Bank energising at voltage zero
HV SIDE 220 V OUTLET
-
SWG/BTA 2000-03-27 Switchsync.PPT
PROBLEMS WITH TRANSIENTS AND HOW TO REDUCE THEM
PROBLEM:These transients may cause:- dielectric stresses in the network- electromechanical stresses on equipment- disturbances
SOLUTION:Instead of treating the symptoms by means of pre-insertion resistors, damping reactors, upgraded insulation or surge arresters controlled switching treats the root of the problem by controlling the switching instants.
The transients are to a large extentdepending on the switching instant. POSSIBILITIES:
-
SWG/BTA 2000-03-27 Switchsync.PPT
REFERENCE FOR CONTROLLED SWITCHING
Signal from a bus bar voltage transformer in one (any) phase(R-0, S-0, T-0 or R-S, S-T, T-R or any voltage with known phase shift)
Bus bar voltage
Reference point:u = 0
du/dt >0
-
SWG/BTA 2000-03-27 Switchsync.PPT
BASIC PRINCIPLE FOR CONTROLLED SWITCHING
TOTALLY COMPENSATED SYSTEM
CONTROLLED SWITCHING OF REACTORS, CAP. BANKS AND TRANSFORMERS IN ADAPTIVE MODE ANDWITH EXTERNAL COMPENSATIONS
SWITCHSYNCrelay
Sensor fortemperature
Sensor foraux. voltage
Trip or closecommand
(SENSORS OPTIONAL)
Delayed trip or close
command, after TF + TV
TB (TOPEN or TCLOSE)
+ TARC or TPREARC
CBcharacteristics
TB vs temp.
CBcharacteristics
TB vs aux. volt.
Feed-back foradaptivity
Referenceinformation
NETWORKCircuit-breaker
BusVT
CT orVT
-
SWG/BTA 2000-03-27 Switchsync.PPT
REQUIREMENTS ON CIRCUIT-BREAKERS
What circuit-breaker properties/conditions must be fulfilled to make it work?
1) RDDS, Rate of Decrease of Dielectric Strength at closing2) RRDS, Rate of Rise of Dielectric Strength at opening
Circuit-breaker with relatively constant mechanical functioning times, from time to time and with known variation with respect to:
1) dependence on auxiliary voltage variation2) dependence on ambient temperature variation3) dependence on idle time (inactivity)
Dynamic voltage withstand properties in the contact gap must be known and suitable so to match the characteristics of the applied and/or recovery voltage across the contact gap:
-
SWG/BTA 2000-03-27 Switchsync.PPT
FUNDAMENTAL REQUIREMENT
SYSTEMCONDITIONS:
- du/dt- APPLICATION
CIRCUIT-BREAKER
PROPERTIES:- RDDS/RRDS- STABILITY
- TARC- TPREARC
HAS TOMATCH
EACH OTHER
-
SWG/BTA 2000-03-27 Switchsync.PPT
RRDS Rate of Rise of Dielectric Strength at opening
Voltage withstand as a function of contact gap at opening, RRDS, versus recovery voltage at inductive load interruption (reactor de-energising)
Typical: TARCMIN 4 ms(Shorter arcing times will result in re-ignition)
RRDS at min. arcing time
SAFE contact parting area
-
SWG/BTA 2000-03-27 Switchsync.PPT
RRDS Rate of Rise of Dielectric Strength at opening
Voltage withstand as a function of contact gap at opening, RRDS, versus recovery voltage at interruption of capacitive current (de-energising of capacitive load)
TARCMIN = 0 ms(re-ignition and re-strike free for any arcing time)
RRDS at min. arcing time
RRDS at average arcing time
Smallest margin for re-strike free performance
-
SWG/BTA 2000-03-27 Switchsync.PPT
RDDS FOR TARGET AT VOLTAGE ZERO
Range ofacceptable
RDDS
-
SWG/BTA 2000-03-27 Switchsync.PPT
RDDS FOR TARGET AT VOLTAGE ZERO
Mechanicalscatter
Pre-strikingvoltage
-
SWG/BTA 2000-03-27 Switchsync.PPT
RDDS FOR TARGET AT VOLTAGE ZERO
Dielectric andmechanical
scatter
Pre-strikingvoltage
-
SWG/BTA 2000-03-27 Switchsync.PPT
RDDS FOR TARGET AT VOLTAGE ZERO
Dielectric andmechanical
scatter
Max. pre-strikingvoltage at delayed
target
-
SWG/BTA 2000-03-27 Switchsync.PPT
RDDS Rate of Decrease of Dielectric Strength at closing
Voltage withstand as a function of contact gap at closing, RDDS, versus the applied voltage at energising of capacitive load (aimed for making at voltage zero)
Mechanical spread
Statistical RDDS spread
Max. pre-striking voltage,taking spread into account
Target UO, takingspread into account
-
SWG/BTA 2000-03-27 Switchsync.PPT
HOW DOES IT WORK?
The relay is programmed with known circuit-breaker parameters (for example closing time, pre-arc) and preferred ideal switching instantdepending on actual load case
This is what the SWITCHSYNC does:
Analyses, during time TF, and finds reference
Adapts a waiting time, TV, from accepted referenceTV + TOPEN from reference means programmed contact parting
TV + TCLOSE TPREARC means current start in pre-determined point
Gives command at the end of the waiting time, TV
-
SWG/BTA 2000-03-27 Switchsync.PPT
SCHEMATIC DESCRIPTION
STARTINPUT
CHECK INPUT40 ms
CHECK VOLTAGE ZEROS
-
SWG/BTA 2000-03-27 Switchsync.PPT
SINGLE-PHASE CAPACITOR BANK ENERGISING
For making at voltage zero TF = Time to detect reference (signal frombus VT). Rapid or Secure mode
TV = Waiting time from first accepted
reference voltage zero (internally created in SWITCHSYNC)
TM = Make time = TB TPREARC (in SWITCHSYNC called switching time)
TB = Circuit-breaker closing time
TD3 = Pre-arcing time, green, mechanical
target red line
(TV adopted so that TV + TM matches the
time between reference point and
electrical target blue line)
REFERENCEVOLTAGE
ZERO
TM = TB - TD3TVTF
TD3Voltage
time
OUTPUT
COMMANDINPUT
COMMAND
Pre-programmedEL. TARGET POINTbased on reference
CONTACTTOUCH
-
SWG/BTA 2000-03-27 Switchsync.PPT
THREE-PHASE CAPACITOR BANK ENERGISING
MAKETIMES:
TMRTMSTMT
WAITINGTIMES:
TVRTVSTVT
GROUNDED CAPACITOR BANK, REFERENCE VOLTAGE: PHASE R 0
PHASE VOLTAGES R 0, S 0 AND T 0 = GAP VOLTAGES
T MRTVR
TVS TM S
TM TT VT
-
SWG/BTA 2000-03-27 Switchsync.PPT
SEQUENCE OF ZERO GAP VOLTAGES IN GROUNDED AND UNGROUNDED SYSTEMS
TR S
Ungrounded bankRed voltage = Yellow voltageBlue voltage = zero (90o later)
Grounded bankEach pole closes atphase voltage zero
60o between the poles
-
SWG/BTA 2000-03-27 Switchsync.PPT
SINGLE-PHASE REACTOR BANK DE-ENERGISING
For breaking with safe arcing time TF = Time to detect reference (signal frombus VT). Rapid or Secure mode
TV = Waiting time from first accepted
reference voltage zero (created internally in SWITCHSYNC)
TB = Circuit-breaker opening time
TA = Arcing time, blue (not evaluated bySWITCHSYNC)
(TM = TB + TA, break time)
(TV Adopted so that TV + TB matches the
time between reference point and
mechanical target, red line)
REFERENCEVOLTAGE
ZERO
time
TBTVTFTA
CurrentVoltage TM
Pre-programmedTARGET POINT
based on reference(Contact separation)
OUTPUT
COMMANDINPUT
COMMAND INTERRUPTION
-
SWG/BTA 2000-03-27 Switchsync.PPT
DELAY TIMES: TD1, TD2 AND TD3 FOR ENERGISING
Example of delay times for single-phase capacitor bank energising at voltage zero. TD1 = defines the Phase shift, TD2 = defines Electrical target, TD3 = defines Mechanical target (touch). TD3 = Pre-arcing time.
time
Voltagesignal
TD2
TD1
TD3
-
SWG/BTA 2000-03-27 Switchsync.PPT
THREE-PHASE CAPACITOR BANK ENERGISING
TD1 = Time to each voltage zero from closest reference voltage zero, here phase R
TD2 = Security delay taking mechanical spread into account
TD3 = Pre-arcing time
Example of delay times for ener-gising a grounded Y-connected capacitor bank:
Energising slightly after voltage zeroReferences to ua (phase R)ug = applied voltageubd = voltage withstand capability
-
SWG/BTA 2000-03-27 Switchsync.PPT
THREE-PHASE UN-GROUNDED CAPACITOR BANK ENERGISING
DELAY TIMES, TD1,FOR PHASE SHIFT
DEFINITION:
TD1 = TD1TD1
UN-GROUNDED CAPACITOR BANK, REFERENCE VOLTAGE: PHASE R 0
PHASE VOLTAGES R 0, S 0 AND T 0
TD1 for T
TD1 for R and S
Voltagesignal
Phase R
-
SWG/BTA 2000-03-27 Switchsync.PPT
DELAY TIMES: TD1 AND TD2 FOR DE-ENERGISING
Example of delay times for single-phase reactor de-energisingTD1 = defines the Phase shift, TD2 = defines Mechanical target, contactseparation, TD3 = 0. Arcing time for re-ignition free interruption
time
Voltagesignal
TD2
TD1
Current
-
SWG/BTA 2000-03-27 Switchsync.PPT
THREE-PHASE REACTOR BANK DE-ENERGISING
TD1 = Time to each current zero from closest reference voltage zero, here phase Rdifference in TD1 can be mechanically build-in
TD2 = Security delay taking mechanical spread into account
Example of delay times for de-energising of grounded reactor bank:
Arcing times, set long enough for re-ignition free interruption (for 50 Hz 7 ms) in every phase
References to ua = uref (phase R)
ug = recovery voltage
ubd = voltage withstand capability
-
SWG/BTA 2000-03-27 Switchsync.PPT
THREE-PHASE GROUNDED REACTOR BANK DE-ENERGISING
DELAY TIMES, TD1,FOR PHASE SHIFT
DEFINITION:
TD1TD1TD1
GROUNDED REACTOR BANK, REFERENCE VOLTAGE: PHASE R 0
time
Phase-to-ground voltages
Currents inductive case
TD1 for RTD1 for T
TD1 for S
PHASE CURRENTS R, S AND T
PHASE VOLTAGES R - 0, S - 0 AND T - 0
-
SWG/BTA 2000-03-27 Switchsync.PPT
WHAT APPLICATIONS ARE SUITABLE?
CE, Capacitor bank Energising. Making at zero voltage across contacts.
CD, Capacitor bank De-energising. Contact separation far before currentzero.
RE, Reactor Energising. Making at steady-state flux level.
RD, Reactor De-energising (50 MVAr). Contact separation far beforecurrent zero. (Chopping over-voltages increases with smaller reactors andreduces the re-ignition free window).
TE, Transformer Energising. Making at steady-state flux level.
(TD, Transformer De-energising. Lock remnant flux.)
STRATEGIES: Frequent planned switchings like:
-
SWG/BTA 2000-03-27 Switchsync.PPT
WHAT IS ACHIEVED?
CE, Smooth energising with low transients and reduced over-voltages
CD, Safe re-strike-free interruption lowers the risk for re-strikes
RE, Low inrush currents
RD, Minimised over-voltages by safe re-ignition-free interruption
TE, Low inrush currents
TD, Well defined interruption with fixed remnant flux (needed only to fix theconditions before next energising)
In general: Extended life of circuit-breakers and other equipment because of reduced wear and less stresses.Increased power quality by reduction of voltage transients and inrush currents.
-
SWG/BTA 2000-03-27 Switchsync.PPT
WHAT ARE THE SOURCES FOR ERRORS?
For the relay: Inaccuracy, from detection of reference to output command
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMPENSATIONS
What are the compensations for CB variations?
In addition to the adaptation control the client can order:
Temperature compensation (external, optional)
Operating voltage compensation (external, optional)
The external compensations are mainly meant for opening without adaptation
Adaptation control (internal)- Controls the performed switching and measures the switching time, TM- Adjusts waiting time TV, if necessary, for next switching and expects a next
switching time, TG- Takes care of systematic but not random variations (wear)- Is used for closing where making instant easily can be detected- For opening it is difficult to detect arcing time
-
SWG/BTA 2000-03-27 Switchsync.PPT
FUNCTIONING PRINCIPLE OF ADAPTATION CONTROL
In the network existing current- or voltage transformers are used to detect executed operation. For three-pole operation, the CT feed-back ought to be from the first closing pole (to eliminate risk for cross-talking)
The SWITCHSYNC checks in adaptive mode the switching timeafter each operation:
The waiting time for next adaptive operation is given by:
TGNEW = (TGOLD + TM)/2 where:
TGNEW = expected next switching time
TGOLD = expected last switching time
TM = measured last switching time
-
SWG/BTA 2000-03-27 Switchsync.PPT
FUNCTIONING PRINCIPLE OF ADAPTATION CONTROL
TV: Waiting timeTB: Operating time of CBE: ErrorTV - E/2: New automatic setting of controller
First time all the error is adjusted
-
SWG/BTA 2000-03-27 Switchsync.PPT
CB VARIATIONS
5657585960616263
80 90 100 110
Coil voltage U (%)
Clo
sin
g t
ime
(ms)
-50 C
+20 C
+70 C
Variations in closing and opening times as a function of coil voltage and temperature (tests on a single-pole operated 245 kV circuit-breaker with spring drive):
1515,5
1616,5
1717,5
1818,5
19
70 80 90 100 110
Coil voltage U (%)
Ope
ning
tim
e (m
s)
-50 C
+20 C
+70 C
-
SWG/BTA 2000-03-27 Switchsync.PPT
CB VARIATIONS
Variations in closing and opening times as a function of idle time:
Closing time vs idle time
59,9
60
60,1
60,2
60,3
60,4
60,5
0 5 10 15 20 25 30 35 40 45 50 55 60 65
Idle time (days)
Clo
sing
tim
e (m
s)
Closing time
Opening time vs idle time
16,3
16,35
16,4
16,45
16,5
16,55
16,6
16,65
0 5 10 15 20 25 30 35 40 45 50 55 60 65
Idle time (days)
Ope
ning
tim
e (m
s)
Opening time
BLG, spring-drive(0.4 ms spread during 65 days) (0.2 ms spread during 65 days)
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMPENSATIONS OF NETWORK PARAMETERS
Frequency control:
- The relay controls the frequency by measuring the time between 3consecutive voltage zeros with positive derivative (3 cycles) beforecommand is given (in Secure mode)(in Rapid mode (for 16,7 Hz) command is given after first detectedvoltage zero)
Select Secure mode!
- If necessary the waiting time will be corrected and adopted to theactual cycle time T, (frequency 15 to 66 Hz)
-
SWG/BTA 2000-03-27 Switchsync.PPT
WHAT OTHER COMPENSATIONS MAY BE NEEDED?
Detection delay (TD2 ):Delay of current onset detection, subtract detection delay from pre-arcing time. When to compensate?
Detection delay (depends on the current) = 3.2 x arccos(1-0.1/ipeak) msthe angle to be expressed in radiansipeak = secondary current from CT expressed in Ampere
Compensation is done for:reactor energising and forenergising of capacitor bankswith damping reactor (when thecurrent starts smooth andsinusoidal with the systemfrequency).
Detected start
Real start
Current onsetsignal
TD2
-
SWG/BTA 2000-03-27 Switchsync.PPT
STAGGERED CIRCUIT-BREAKERS
Staggered circuit-breakers, mechanically coupled three-pole operated circuit-breakers are most often adopted for controlled closing. The staggering corresponds to the phase shift expressed by TD1
HPL: Closing speed is about 60 % of the opening speedThis means that the non-simultaneity at opening is acceptablefor non-controlled de-energising of ungrounded capacitor banks
LTB-D: Closing- and opening speeds are about the same which meansthat controlled opening most often is required for ungroundedcapacitor banks (the critical phase is then given an arcing timeof about 5 ms).
Reversed phase order is used to minimise the mechanical time spread needed.
Example for controlled making of grounded capacitor bank:- One pole is given fast start (slow finish) of the motion- One pole remains standard- One pole is given slow start (fast finish) of the motion
-
SWG/BTA 2000-03-27 Switchsync.PPT
STAGGERED CIRCUIT-BREAKERS
HPL
LTB-D
STANDARDFAST START
INNER ARMCLOSED POS.
OUTER ARMOPEN POS.
CLOSING
OPENING
CONTACTTOUCH
OPEN POSITION
CONTACTSEP.
-
SWG/BTA 2000-03-27 Switchsync.PPT
MONITORING
Which information does the SWITCHSYNC give?
- F-model stores the switching times, TM, (max. 545 operations)- It always stores the 10 first (as a reference)- Monitoring function, trend in TM is shown
F-model has PC-connection possibilities (via modem or directly)for programming or de-loading
WARNING: If time deviation versus target >2 ms and 3.5 ms
-
SWG/BTA 2000-03-27 Switchsync.PPT
SWITCHSYNCTM Model F236
DISPLAY
INTERNAL JUMPERS TO BE CHECKED(depending on type of detection)
MODEM connectionon backside
RESET button
ALARM SIGNAL
SELECT POSITIONon display
ON/OFF(position off when
programming)
PC-connection
ENTER button(press after eachcomplete input)
SELECT VALUE
-
SWG/BTA 2000-03-27 Switchsync.PPT
TYPE OF CONTROLLERS
Name interpretation of controllers:
SWITCHSYNCTM Axyz
A = Generation letter E or Fx = Number of input commandsy = Number of adaptive inputsz = Number of output commands
F model has, in addition to the E model, following possibilities:
External parameter compensation: For temperature and auxiliary voltagevariation by means of sensors
Data storage: Maximum 545 operations
PC communication: For programming and data transfer
-
SWG/BTA 2000-03-27 Switchsync.PPT
E113
1 input command1 independent adaptive input for first making pole (2 dependent)
3 output commands
Suitable for:controlled opening of single- or three-pole operated circuit-breakers or controlled closing of three-pole operated circuit-breakers.
Or controlled closing of single-pole operated circuit-breakers if dependence of contact wear on closing time can be judged equal for all poles.
-
SWG/BTA 2000-03-27 Switchsync.PPT
F236
2 input commands
3 independent adaptive inputs
6 output commands
Suitable for:controlled opening and closing of single-pole operated circuit-breakers and with individual adaptation for every pole (at closing).
-
SWG/BTA 2000-03-27 Switchsync.PPT
SWITCH2X
Software for F-model
Password from factory: LUDVIG MENU
LUDVIG
-
SWG/BTA 2000-03-27 Switchsync.PPT
CONNECTIONS AND TECHNICAL DATA FOR SWITCHSYNC
Supply voltage: 48 - 250 V a.c./d.c.
Operating command: 48 - 250 V d.c., duration 0.15 - 1 s
Reference voltage: 35 - 150 V a.c., 15 - 66 Hz
Current start detection: 0.5 - 5 A a.c.
Voltage start detection: 48 - 250 V a.c./d.c.
Output relays: 10 A interrupting capability at 250 V d.c. t = 40 ms20 ms closing time
Ambient temperature: -5 to +55 oC (normally installed indoor)
-
SWG/BTA 2000-03-27 Switchsync.PPT
CONNECTION OF SWITCHSYNC E113
For closing or opening of three-pole operated circuit-breakers
CONTROLLED CLOSING WITH E113
1 SWITCHSYNC relay E113
2 Reference voltage from any phase
3 CT for detection of current start (1)
4 Closing order (1 input command)
5 Delayed output from SWITCHSYNC(1 adaptive output command, 3possible outputs)
6 Three-pole operated circuit-breaker
7 Mechanical lagging
E113
1
-
SWG/BTA 2000-03-27 Switchsync.PPT
CONNECTION OF SWITCHSYNC F236
For closing and opening of single-pole operated circuit-breakers
CONTROLLED CLOSING AND OPENING WITH F236
1 SWITCHSYNC relay F236
2 - 3 Input commands, close and open (2)
4 Reference voltage from any phase
5 - 7 Adaptive output commands (3, 3)
8 - 10 Non-adaptive output commands (3)
11 - 13 Current onset signals from CT (3)
14 - 16 Voltage onset detector signals
17 - 18 External parameter sensor inputs
19 Application control input (for changed
load connection)
20 Alarm output
21 Local PC connection
22 Modem PC connection
23 Power supply
24 Circuit-breaker (single-pole operated)
F236
Single-poleoperated CB
1
-
SWG/BTA 2000-03-27 Switchsync.PPT
REFERENCES SINCE 1984
Totally in service more than 1000 units
Intended for:
Capacitor bank switching 60 %
Reactor switching 25 %
Transformer switching 15 %
Line re-closing Some few
-
SWG/BTA 2000-03-27 Switchsync.PPT
FUTURE
ABB Switchgears new L-model (L183) for line re-closing, replaces pre-insertion resistors. The working principle is that the polarity and amplitude of the line voltage is given as a feed-back to the SWITCHSYNC before next closing. Making will then, at auto re-closing, occur at an instant minimising the voltage transients at the far end of the line. If the time to closing is long the SWITCHSYNC will set the target for making at voltage zero (unloaded line), time condition. The model detects when the d.c. level of the trapped charge begins.
New T-model (T183) is available for transformer energising. Reads the remnant flux by integration of the load side voltage and adapts the making instant based on that.
CIGRE has started looking at synchronised short-circuit interruption, to optimise the circuit-breaker life time
-
SWG/BTA 2000-03-27 Switchsync.PPT
NON-COUPLED PHASES
No magnetic coupling
Transformer banks, reactor banks and five-limbedreactors/transformers:- no common magnetic flux since voltage in one phase does notcause flux in other phases
No electrical coupling
Grounded, Y-connected loads since neutral point fixed Loads without delta-connection
For these cases all phases can be programmed independent of each other
-
SWG/BTA 2000-03-27 Switchsync.PPT
COUPLED PHASES
Magnetic coupling
Three-limbed reactors/transformers:- the phases are not independent of each other due to commonmagnetic flux
Electrical coupling
Ungrounded loads due to floating neutral ?-connected loads since the sum of the voltages must be zero Transformers with at least one delta-winding:
- electrical coupling that causes magnetic coupling
The phases are not independent of each other which has to be taken into account when programming
-
SWG/BTA 2000-03-27 Switchsync.PPT
TO BE AWARE OF:
Pre-insertion resistors and controlled closing does normally not match:- the RDDS characteristics of the resistor contact gap most often too bad- either one or the other, not both together
Disturbances:- High secondary currents from CT, in non-shielded or non-twisted cables, may give false feed-back of
current onset for the last closing poles due to cross-talking
Current change detection:- Detection threshold may sometimes need be adjusted
(too low means detection already before making, too high means no detection at all)
Voltage start detection:- Induced voltage may be enough for detection = ALREADY ON
Mechanically staggered circuit-breakers:- Make sure that the pole order (A-B-C) fits the phase sequence
Check the connections and the load conditions:- The client does not always know the type of load
Check the phase sequence:- FURNAS sequence is C-B-A
Check the connections:- Does the phase order fit the pole order?
-
SWG/BTA 2000-03-27 Switchsync.PPT
FACTORY TESTING:
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS:
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS:
Computer
SWITCHSYNC
TM1600
Voltage dividers
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS, CLOSING (3-POLE OP.):
REFERENCEVOLTAGE
MAKINGCURRENTS
OUTPUTCOMMAND FROM
CONTROLLER
MAKING OF GROUNDED DOUBLE Y-CONNECTED CAPACITOR BANK
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS, OPENING (3-POLE OP.):
AT COMMISSIONING FOLLOWING TRACES SHOULD BE RECORDED:- ALL BUS VOLTAGES (OR AT LEAST THE REFERENCE VOLTAGE)- ALL PHASE CURRENTS (FOR MAKING AND/OR BREAKING)- OUTPUT COMMAND FROM THE CONTROLLER
BUS VOLTAGES
BREAKING CURRENTS
OUTPUT COMMANDFROM E113
OUTPUT COMMAND
CONTACT PARTING, FIRST POLE TO OPENRESULTING ARCING TIMES FOR THE OTHERPOLES GIVEN BY MECHANICAL STAGGERING
INTERRUPTION FIRST POLE
INTERRUPTION OF 3-LIMBEDIRON CORE REACTOR
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS, CLOSING (1-POLE OP.):
FOR REACTOR ENERGISING: CHECK THE ASYMMETRY OF THE CURRENT
MAKING OF GROUNDED Y-CONNECTED 5-LIMBED IRON CORE REACTOR
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS, OPENING (1-POLE OP.):
CHECK THE ARCING TIMES
CONTACT PARTING, POLE A RESULTING ARCING TIME, POLE A
OUTPUT TO POLE A
INTERRUPTION, POLE A
KNOWN OPENING TIME, POLE A
INTERRUPTION OF GROUNDED Y-CONNECTED 5-LIMBED IRON CORE REACTOR
-
SWG/BTA 2000-03-27 Switchsync.PPT
COMMISSIONING TESTS, OPENING (1-POLE OP.):
CHECK THE ARCING TIMESCONTACT PARTING, POLE A
OPENING TIME FROM NO-LOAD TEST, POLE A
INTERRUPTION OF GROUNDED Y-CONNECTED 5-LIMBED IRON CORE REACTOR