applying the 2010 asce 7 wind and ice requirements to

12
Applying the 2010 ASCE 7 Wind and Ice Requirements to Transmission Line Design Adam J. Beyer, EIT, A.M.ASCE 1 1 Engineer, American Transmission Company, LLC, 2 Fen Oak Ct., Madison, WI 53718; email: [email protected] ABSTRACT ASCE/SEI 7-10 - Minimum Design Loads for Buildings and Other Structures introduced wind maps and a new way to evaluate wind loading compared to its predecessors (e.g. ASCE/SEI 7-05, ASCE/SEI 7-02, etc.). The changes will present challenges to current codes and manuals which utilize the previous maps and methodologies, specifically the National Electric Safety Code (NESC) and ASCE Manual No. 74. The purpose of this paper will be to show a comparison of the extreme wind loading and combined ice and wind for ASCE 7-10 to the ASCE 7-05 values as they apply to Transmission Lines. To begin that discussion, the author will look back on work previously done by others. The intention of this paper is to begin a public discussion of possible directions the NESC and ASCE Manual No. 74 should consider. 1 INTRODUCTION The ASCE-7 committee made the decision that it was better to assume a higher wind speed (longer return period) in their loads and reduce the load factor from 1.6 to 1.0 in the latest revision of Minimum Design Loads for Buildings and Other Structures (ASCE 7-10). NESC adopted the ASCE 7-05 maps except set all load factors at 1.0. As a result, the NESC loading requirements were below those in ASCE 7-05. If ASCE Manual No. 74 and the NESC decide to adopt the wind maps with the higher return period in their next revisions the wind pressures will increase by a ratio governed by the velocities squared for both structures and wires. This will certainly have an impact on the Extreme Wind load case. Not only did the Extreme Wind maps change, but the Extreme Ice with Concurrent Wind maps changed as well. This change will also have an impact on the Extreme Ice with Concurrent Wind case. The NESC and ASCE Manual No. 74 have a few courses of action: Use a factor to reduce the wind speed on ASCE 7-10 maps o How does an engineer justify the validity of using a factor to reduce or modify the wind pressures to their previous values? Adopt the new maps with increased wind speed and ice thicknesses. o Does experience (failures) justify an increase in design loads? Reference the 50-year occurrence wind map in the appendix. o Can NESC justify using the 50-year occurrence ASCE maps? 427 ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

Upload: others

Post on 20-Mar-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Applying the 2010 ASCE 7 Wind and Ice Requirements to Transmission Line Design

Adam J. Beyer, EIT, A.M.ASCE1

1Engineer, American Transmission Company, LLC, 2 Fen Oak Ct., Madison, WI 53718; email: [email protected] ABSTRACT ASCE/SEI 7-10 - Minimum Design Loads for Buildings and Other Structures introduced wind maps and a new way to evaluate wind loading compared to its predecessors (e.g. ASCE/SEI 7-05, ASCE/SEI 7-02, etc.). The changes will present challenges to current codes and manuals which utilize the previous maps and methodologies, specifically the National Electric Safety Code (NESC) and ASCE Manual No. 74. The purpose of this paper will be to show a comparison of the extreme wind loading and combined ice and wind for ASCE 7-10 to the ASCE 7-05 values as they apply to Transmission Lines. To begin that discussion, the author will look back on work previously done by others. The intention of this paper is to begin a public discussion of possible directions the NESC and ASCE Manual No. 74 should consider. 1 INTRODUCTION The ASCE-7 committee made the decision that it was better to assume a higher wind speed (longer return period) in their loads and reduce the load factor from 1.6 to 1.0 in the latest revision of Minimum Design Loads for Buildings and Other Structures (ASCE 7-10). NESC adopted the ASCE 7-05 maps except set all load factors at 1.0. As a result, the NESC loading requirements were below those in ASCE 7-05. If ASCE Manual No. 74 and the NESC decide to adopt the wind maps with the higher return period in their next revisions the wind pressures will increase by a ratio governed by the velocities squared for both structures and wires. This will certainly have an impact on the Extreme Wind load case. Not only did the Extreme Wind maps change, but the Extreme Ice with Concurrent Wind maps changed as well. This change will also have an impact on the Extreme Ice with Concurrent Wind case. The NESC and ASCE Manual No. 74 have a few courses of action:

• Use a factor to reduce the wind speed on ASCE 7-10 maps o How does an engineer justify the validity of using a factor to reduce or

modify the wind pressures to their previous values? • Adopt the new maps with increased wind speed and ice thicknesses.

o Does experience (failures) justify an increase in design loads? • Reference the 50-year occurrence wind map in the appendix.

o Can NESC justify using the 50-year occurrence ASCE maps?

427ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

The following examples will use structures and span configurations that will be included in the appendix. All hand calculations were performed using Microsoft Excel and all structural analysis calculations were performed using Powerline Systems’ PLS-CADD/POLE software. 2 EXTREME WIND LOADING REQUIREMENTS 2.1 Converting ASCE 7-05 to ASCE 7-10 Extreme Wind Speeds The values in the table below were tabulated using the Applied Technology Council’s “Wind Speed by Location” tool. This tool is used by entering the location of the building site (latitude-longitude) or manually clicking the location of the building site on the map. The results that are provided include the ASCE 7-05 and ASCE 7-10 wind speeds. Table 1 ASCE 7-05 (50 Year MRI) and ASCE 7-10 (700 Year MRI) Extreme Wind Speed Values

Area of Interest Latitude Longitude ASCE 7-05 (m/s)

ASCE 7-10 (m/s) Ratio

Eureka, CA 40.81 -124.17 38.0 49.2 1.675 Portland, OR 45.94 -122.71 38.0 49.2 1.675

Anchorage, AK 61.23 -149.82 46.0 59.0 1.642 American Samoa - - 55.9 71.5 1.638 Las Vegas, NV 36.10 -115.22 40.2 51.4 1.633 Madison, WI 43.06 -89.42 40.2 51.4 1.633

San Antonio, TX 29.51 -98.49 40.2 51.4 1.633 US Virgin Islands - - 58.1 73.8 1.611

Houston, TX 29.76 -95.40 48.3 60.4 1.563 Hawaii - - 46.9 58.1 1.533 Alaska 54.68 -164.15 58.1 71.5 1.515

Boston, MS 42.40 -71.40 46.9 57.2 1.486 Key West, FL 24.56 -81.79 67.1 80.5 1.440

Alaska 68.56 -166.26 55.9 66.6 1.421 Alaska 71.30 -156.68 53.6 63.0 1.381

Puerto Rico - - 64.8 76.0 1.375 Miami, FL 25.80 -80.23 64.4 75.1 1.361

Corpus Christi, TX 27.78 -97.40 55.9 64.4 1.327 Guam - - 76.0 87.2 1.316

The ratio column in the table above shows: =

Where: = 7 − 10 = 7 − 05 This ratio serves as a conversion between the ASCE Standards because the velocities of the wind are the only change in the wind speed pressure equation. The largest ratio from the tabulated values is 1.675 which is from Eureka, CA and Portland, OR. The ratio from Madison, WI is 1.633. All three areas will be examined because each area represents an NESC Loading District (Light, Medium, and Heavy respectively).

428ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

Themapare

F 2.2

TabGuibasslig ForwilAloThethe EH

ese three areps were adopnot governe

Figure 1 Extre

Results o

GoBody/Gu

ASAS

NESC ASCE M

ble 2 above side, or Stand

sed on the strghtly modifie

r the purposel be looked a

ong with the e first will beother will b

HS).

eas would alspted. One ined by areas o

me Wind Spe

of Load Cal

Tab

overning uide/StandardSCE 7-10 SCE 7-05 – Rule 250C

Manual No. 74

shows what dard. The Gructure heighed.

es of this papat with 336.4different sp

e a double cie a 90° dead

so see the mnteresting thof high wind

ed Map (ASC

culations

ble 2 Wind PrEurek

(NESC

d Wind

(P14888

the differentGRF and KZ fa

ht and span l

per a span of4 kcmil “Linan lengths, tircuit tangen

d-end single

ost drastic ching to note id speed but in

CE 7-10) mph-

essures for Exka, CAC Light) (Nd Load Pa) 480

890 890 890

t wind pressuactors will mlength so the

f 122 m (Shonnet” and 10two differentnt pole with tcircuit struc

hange to desis that the larnstead areas

(m/s) (MRI =

xtreme WindPortland, OR

NESC MediumWind Load

(Pa) 1480 890 890 890

ures are for modify the bae numbers in

ort Span) an033.5 kcmil “t structure tytwo shield w

cture with on

sign if the Arger values o of lower wi

700 Years, Ca

Rm)

Madiso(NESC

Wind (P16999999

each Governase wind pren Table 2 wi

d 274 m (Lo“Curlew” coypes will be wires (3/8” Ene shield wir

ASCE 7-10 of this ratio ind speed.

ategory II)

on, WI Heavy) Load

Pa) 20 90 90 90

ning Body, essures ill be

ong Span) onductor. looked at.

EHS) and re (3/8”

429ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

2.3 PLS-CADD Analysis NESC District Load cases will be evaluated as well to compare against the wind loading.

Table 3 PLS-CADD Analysis of Different Loading Scenarios for Tangent Example Ground-Line Reaction (N-m)

Load Case Wind (m/s)

Load Factor(s)

Short Span (122 m) Long Span (274 m) Linnet Curlew Linnet Curlew

NESC Heavy1 17.9

(1.27 cm ice)

NESC 475 580 1020 1300

Extreme Wind - 20051

40.2 1.0 390 550 680 1020

Extreme Wind - 20101

51.4 1.0 640 900 1100 1660

NESC Medium2 17.9

(0.64 cm ice)

NESC 340 440 710 960

Extreme Wind - 20052

38.0 1.0 350 495 600 910

Extreme Wind - 20102

49.2 1.0 590 830 1010 1520

NESC Light3 26.8 NESC 490 700 930 1440

Extreme Wind - 20053

38.0 1.0 350 500 600 910

Extreme Wind - 20103

49.2 1.0 590 830 1010 1520

Notes: 1 Stringing Condition is NESC Heavy at 40% of ultimate tension (Creep) 2 Stringing Condition is NESC Medium at 40% of ultimate tension (Creep) 3 Stringing Condition is NESC Light at 40% of ultimate tension (Creep) The analysis in table 3 shows that the only change was the wind speed and removal of the load factor. It should be noted that table 3 shows the ASCE 7-2010 Extreme Wind Loads do govern when compared to the NESC District Loads.

430ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

Table 4 PLS-CADD Analysis of Different Loading Scenarios for Dead-End (90°) Example Ground-Line Reaction (N-m)

Load Case Wind (m/s)

Load Factor(s)

Short Span (122 m) Long Span (274 m) Linnet Curlew Linnet Curlew

NESC Heavy1 17.9

(1.27 cm ice)

NESC 4240 8480 4410 8730

Extreme Wind - 20051

40.2 1.0 1920 4300 2000 4430

Extreme Wind - 20101

51.4 1.0 1590 5000 2600 5210

NESC Medium2 17.9

(0.64 cm ice)

NESC 4320 8930 4440 9120

Extreme Wind - 20052

38.0 1.0 2320 5090 2390 5220

Extreme Wind - 20102 49.2 1.0 2790 5610 2910 5810

NESC Light3 26.8 NESC 4570 9390 4690 9600

Extreme Wind - 20053

38.0 1.0 2620 5670 2690 5800

Extreme Wind - 20103 49.2 1.0 3030 6100 3150 6300

Notes: 1 Stringing Condition is NESC Heavy at 40% of ultimate tension (Creep) 2 Stringing Condition is NESC Medium at 40% of ultimate tension (Creep) 3 Stringing Condition is NESC Light at 40% of ultimate tension (Creep) Table 4 above for the 90° dead-end case shows even with the increased wind speed on a dead-end type structure the NESC district loads (Heavy, Medium, and Light) will still govern the design of the pole. This is true for other angles in the dead-end case. It is important to note that large angle and dead-end structures are typically the most expensive structures on a transmission line and would not be affected if the ASCE 7-10 maps were adopted by ASCE Manual No. 74 and the NESC. 2.4 Turning the 700-year Mean Recurrence Interval (MRI) map into a 50-year

MRI map Turning the 700-year MRI map values into lower MRI values is necessary since Transmission Lines are traditionally designed for a 50 year life. An equation similar to C26.5-2 in the ASCE 7-10 commentary can be derived from known values. Take for example the Midwestern United States in Table 5 below:

431ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

Table 5 Return Period Values for the Midwestern United States

Midwestern United StatesReturn Period, T

(yrs) Wind Velocity, VT

(m/s) VT/V700

50 40.2 0.783 100 42.9 0.835 300 46.9 0.913 700 51.4 1.000

1700 53.6 1.043

Figure 2 Graph of Return Period vs. Velocity Ratio

The equation below can be used to determine the velocity of wind based on a desired return period. In the case of Transmission Line Design, 50 years is often the desired value. = × (0.484 + 0.0763 ( )) It should be noted that a 50-year MRI map is published in the ASCE 7-10 standard however it is not exactly the same as the 50-year MRI map from ASCE 7-05 (the ASCE 7-10 50-year MRI map is intended to be used for serviceability analysis). The reason for the difference is that the ASCE 7-05 maps were actually a 700-year MRI map divided by √1.6 (1.6 was the wind load factor). The commentary of ASCE 7-10 states “The task committee (Wind Load Subcommittee) reasoned that the annual probability of exceeding the strength design wind load in the hurricane and non-hurricane regions of the United States should be the same” (p. 509). In table C6-7 (p. 318) of ASCE 7-05 there is a footnote that states in reference to hurricane velocities, “For the MRI = 50 as shown, the actual return period, as represented by the design wind speed map in Fig. 6-1, varies from 50 to approximately 90 years.” The result was that the ASCE 7-05 maps resulted in a true 50-year event for non-hurricane regions, but in hurricane regions the event was slightly larger than a 50-year event. This means that current transmission line designs involving extreme wind events are not designed based on a consistent recurrence

y = 0.0763ln(x) + 0.4841

0.50

0.60

0.70

0.80

0.90

1.00

1.10

0 500 1000 1500 2000

V T/V 70

0

Return Period, T (yrs)

Return Period vs. Velocity Ratio

432ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

interval because the ASCE 74 and the NESC reference the ASCE 7-05 maps without the load factor. This adds to the complexity of the decision for the ASCE 74 and the NESC committees. If ASCE 74 and the NESC want to continue using the same variable recurrence interval then they will need to continue using the ASCE 7-05 maps, however trying to justify this approach may not agree with good engineering practice. The author believes the most logical choice is to specify a minimum recurrence interval and use the appropriate map from ASCE 7-10. The MRI maps available in ASCE 7-10 are 10, 25, 50, 100, 300, 700, and 1700. Depending on which map is chosen to be referenced the committees could choose to include a formula based on that map to adjust the wind speed to a desired recurrence interval. 2.5 Conclusion of Extreme Wind It is at this point that the author would like to propose a change (in bold) to the wind pressure formula so that the ASCE 7-10 maps could be adopted into ASCE Manual No. 74 and eventually the NESC. : = 0.613 × × × × × : = 0.613 × × × × × ℎ : = = = − = = = ℎ : = = (700 ) = = × (0.484 + 0.0763 ( )) : 50 700 : = 51.4 / × (0.484 + 0.0763 (50))~40.2 / By introducing the VRI term the new ASCE 7-10 maps will be able to be used by ASCE Manual No. 74 and the NESC. With these changes, the NESC for example would be able to dictate what minimum recurrence interval Transmission Lines should be designed to. Currently a minimum of 50 years for most of the United States is the recurrence interval in the NESC. If the ASCE 7-10 700-year MRI maps are adopted as is then the increased wind loads would govern the design of the tangent structures. It is possible that ASCE Manual No. 74 could adopt the ASCE 7-10 maps and methodology with modifications after benchmarking across the United States. The NESC would then be encouraged to follow as their maps are traditionally adopted from ASCE 7. By using the modified

433ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

winperremmet 3

3.1

TheExt

W

M

TheASWincasice bot(chSup

Fig

nd pressure fiod/reliabilit

main at 1.0 anthodology w

EXTREMREQUIRE

CompariWind

e values in thtreme Ice an

Table 6 AS

Area of Interest

Northern Wisconsin

Eastern Montana

Lake Superior,

Minnesota Northern Missouri

e new ExtremCE 7-10 alsond loading ces will use thon the wiresh. Four areaanged wind perior area in

gure 3 Extrem

formula, desty need of thnd this woul

with the ASC

ME ICE WITEMENTS

ison of ASC

he table belod Concurren

SCE 7-05 and A

NESC Zone

Heavy

Medium

Heavy

Medium

me Ice and Co introduced

condition. The new temps while otheras have beenspeed), East

n Minnesota

me Ice and Conin

igners may bhe line more ld align the A

CE 7-10 stand

TH CONCU

CE 7-05 to A

ow were tabunt Wind map

ASCE 7-10 Ex

ASCE 7-0

Ice (cm)

W(m

1.27 1

0.64 2

3.18 2

2.54 1

Concurrent Wd a temperatu

The ASCE 7-perature maprs have adju

n chosen for tern Montan

a (changed bo

ncurrent Windterest for this

be encouragso than befo

ASCE Manudard (use a c

URRENT W

ASCE 7-10 E

ulated using ps.

xtreme Ice an

05

Wind m/s)

Ic(cm

7.9 1.2

22.4 1.2

26.8 1.9

3.4 2.5

Wind Speed ure map for -05 cases wilp. Some arested the winanalysis wh

na (changed aoth), and No

d Map (ASCEpaper (MRI =

ed to think aore. The oveual No. 74 anconsistent re

WIND LOAD

Extreme Ice

the ASCE 7

d Concurrent

ASC

ce m)

Wind(m/s)

27 22.4

27 22.4

91 22.4

54 13.4

maps have cthe Extremell use -9.4°C

eas have incrnd speed andhich are Nortamount of raorthern Miss

E 7-10); Figure= 50 Years)

about the reterload factornd the NESCecurrence int

DING

e and Concu

7-05 and AS

t Wind Speed

CE 7-10

d )

Tempe(°C

4 -20

4 -26

4 -20

4 -15

changed slige Ice and CoC and the ASreased the amd some have thern Wisconadial ice), Lasouri (no cha

e 10-3 of ASCE

turn rs could C terval).

urrent

CE 7-10

Values

erature C)

0.6

6.1

0.6

5.0

ghtly. ncurrent

SCE 7-10 mount of adjusted nsin ake ange).

E 7 is also of

434ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

3.2 PLS-CADD Analysis NESC District Load cases will be evaluated as well to compare against the Extreme Ice and Concurrent Wind loading.

Table 7 PLS-CADD Analysis of Different Loading Scenarios for Tangent Example Ground-Line Reaction (N-m)

Load Case Wind (m/s)

Ice (cm)

Load Factor(s)

Short Span (122 m) Long Span (274 m) Linnet Curlew Linnet Curlew

NESC Heavy1 17.9 1.27 NESC 475 580 1020 1300

Extreme Ice and Wind – Wisconsin – 2005 1

17.9 1.27 1.0 190 230 400 500

Extreme Ice and Wind – Wisconsin – 2010 1

22.4 1.27 1.0 290 350 620 770

NESC Heavy1 17.9 1.27 NESC 475 580 1020 1300

Extreme Ice and Wind – Lake Superior – 2005 1

26.8 3.18 1.0 790 890 1820 2130

Extreme Ice and Wind – Lake Superior – 2010 1

22.4 1.91 1.0 370 440 820 990

NESC Medium2 17.9 0.64 NESC 340 440 710 960

Extreme Ice and Wind – Montana – 2005 2

22.4 0.64 1.0 210 270 430 580

Extreme Ice and Wind – Montana – 2010 2

22.4 1.27 1.0 290 350 620 770

NESC Medium2 17.9 0.64 NESC 340 440 710 960

Extreme Ice and Wind – Missouri – 2005 2

13.4 2.54 1.0 160 190 370 440

Extreme Ice and Wind – Missouri – 2010 2

13.4 2.54 1.0 160 190 370 440

Notes: 1 Stringing Condition is NESC Heavy at 40% of ultimate tension (Creep RS) 2 Stringing Condition is NESC Medium at 40% of ultimate tension (Creep RS) In table 6 above, the calculations show that the 2010 Extreme Ice and Wind ground-line reactions increased from the 2005 Extreme Ice and Wind in Wisconsin and Montana, but the NESC District Loads still continue to govern the design. However, one area of interest is the Lake Superior region where the loads actually decreased along some parts of the lake. There was no change in ground-line moment for the region in Northern Missouri.

435ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

Table 8 PLS-CADD Analysis of Different Loading Scenarios for Dead-End (90°) Example Ground-Line Reaction (N-m)

Load Case Wind (m/s)

Ice (cm)

Load Factor(s)

Short Span (122 m) Long Span (274 m) Linnet Curlew Linnet Curlew

NESC Heavy1 17.9 1.27 NESC 3130 6260 3250 6440

Extreme Ice and Wind – Wisconsin – 2005 1 17.9 1.27 1.0 1660 3650 1710 3730

Extreme Ice and Wind – Wisconsin – 2010 1 22.4 1.27 1.0 1840 3910 1920 4020

NESC Heavy1 17.9 1.27 NESC 3130 6260 3250 6440

Extreme Ice and Wind – Lake Superior – 2005 1

26.8 3.18 1.0 3140 5210 3390 5520

Extreme Ice and Wind – Lake Superior – 2010 1

22.4 1.91 1.0 2210 4280 2310 4810

NESC Medium2 17.9 0.64 NESC 3370 6930 3460 7080

Extreme Ice and Wind – Montana – 2005 2

22.4 0.64 1.0 1850 4110 1900 4190

Extreme Ice and Wind – Montana – 2010 2

22.4 1.27 1.0 2220 4580 2300 4700

NESC Medium2 17.9 0.64 NESC 3370 6930 3460 7080

Extreme Ice and Wind – Missouri – 2005 2

13.4 2.54 1.0 3530 6560 3630 6740

Extreme Ice and Wind – Missouri – 2010 2

13.4 2.54 1.0 3560 6640 3660 6820

Notes: 1 Stringing Condition is NESC Heavy at 40% of ultimate tension (Creep RS) 2 Stringing Condition is NESC Medium at 40% of ultimate tension (Creep RS) Table 7 above for the 90° dead-end case shows that even with the increased ice and wind speed on a dead-end type structure the district loads will still govern the design of the pole except in Missouri for small conductor sizes. 3.3 Conclusion of Extreme Ice and Concurrent Wind The analysis for Extreme Ice and Concurrent Wind shows that even though the loadings for some cases have increased, the NESC District loads still govern (a few special areas will still dictate the design but there was no increase in ice and wind loads in those areas). ASCE Manual No. 74 and the NESC can adopt the Extreme Ice and Concurrent Wind loading maps without a drastic change to current design practice. The temperature maps from ASCE 7-10 do not necessarily need to be

436ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

adopted by ASCE Manual No. 74 and the NESC because the calculations show the differences to be negligible – Less than 1.5% increase in the analysis for Missouri. 4 CONCLUSIONS Currently, there is a lot of dialogue in the construction industry to create infrastructure that is more sustainable and exhibits a longer life. Transmission lines are no exception and are just as important as a road or a building is to our everyday lives. As mentioned in this paper, the NESC (2007 and 2012) currently requires a 50 year return period (minimum) on extreme events in most areas of the United States. The author is aware of several transmission lines that have been in service for well over 50 years, so maybe it is time to examine increasing the return period on extreme events if we intend to keep these lines in service for longer periods. The author believes that overall the ASCE 7-10 maps could be adopted by ASCE Manual No. 74 and eventually the NESC if modifications are implemented to use a more applicable return period for transmission line design. In some areas the loadings have increased and structures may need to be designed to be more robust. Since the data shows that the loading conditions for different areas of the United States have changed, or we have refined our methods, then we as engineers should not be hesitant to adjust either. In the end, ensuring our electric grid is more structurally reliable based on new data as it becomes available is a step in the right direction. REFERENCES

1. ASCE/SEI 7-05. (2006). Minimum Design Loads for Buildings and Other Structures Wind Loads.

2. ASCE/SEI 7-10. (2011). Minimum Design Loads for Buildings and Other Structures Wind Loads.

3. National Electric Safety Code. (2012). Section 25 – Loadings for Grades B and C.

4. ASCE Manual No. 74 (3rd Edition). Guidelines for Electrical Transmission Line Structural Loading, Reston, VA, USA, 2006.

5. PLS-CADD, A Computer Program for the Analysis and Design of Overhead Electric Lines. Power Line Systems, Madison, WI, USA.

6. Microsoft Excel 2010. Microsoft Corp. 7. Applied Technology Council. (2011). Windspeed by Location. Retrieved

from http://www.atcouncil.org/windspeed/

437ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013

AP TanStruandRulMinMaWinShiShiCon336103Lin1SaDis2SaDis3SaLoa

PPENDIX

ngent Examucture Descrd self-supporling Span – 2n Span – 122

ax Span – 27nd to Weighield Wire 1 –ield Wire 2 –nductor 6.4 kcmil “L33.5 kcmil “Cne Angle – 0ag Conditionstrict Loads (ag Conditionstrict Loads (ag Conditionads (40% UB

mple: ription – Dourting 213 m 2 m 4 m

ht Span – 1.0– 3/8” EHS – 3/8” EHS

Linnet” ACSRCurlew” AC°

n – NESC He(40% UBS)

n – NESC Me(40% UBS)

n – NESC LigBS)

uble circuit

0

R and CSR

eavy

edium

ght District

DeaStruand RuliMinMaxWinShieCon336.1033Line1SagDist2SagDist3SagLoad

ad-End Examucture Descri

self-supporting Span – 2

n Span – 122x Span – 274nd to Weighteld Wire – 3/nductor .4 kcmil “Li3.5 kcmil “Ce Angle – 90g Condition –trict Loads (4g Condition –trict Loads (4g Condition –ds (40% UB

mple: iption – Singting 213 m 2 m 4 m t Span – 1.0 /8” EHS

innet” ACSRCurlew” ACS0° – NESC He40% UBS) – NESC Me40% UBS) – NESC Lig

BS)

gle circuit

R and SR

avy

edium

ght District

438ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2012 © ASCE 2013