application of controls

30
Application of Controls Application of Controls CAV with Humidity Control CAV with Humidity Control

Upload: saddam

Post on 01-Feb-2016

56 views

Category:

Documents


0 download

DESCRIPTION

Application of Controls. CAV with Humidity Control. Application of Controls. CAV with Humidity Control CAV AHU dedicated to a special area: clean room textile factory hospital operating theatre computer equipment room - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Application of Controls

Application of ControlsApplication of Controls

CAV with Humidity ControlCAV with Humidity Control

Page 2: Application of Controls

Application of ControlsApplication of Controls

CAV with Humidity ControlCAV with Humidity ControlCAV AHU dedicated to a special area:CAV AHU dedicated to a special area:

clean roomclean room textile factorytextile factory hospital operating theatrehospital operating theatre computer equipment roomcomputer equipment room

Environment requires humidity control Environment requires humidity control as well as temperature control - as well as temperature control -

energy efficiency is not as importantenergy efficiency is not as important

Page 3: Application of Controls

Application of ControlsApplication of Controls

Return AirReturn Air

OutdoorOutdoorAirAir

Cooling CoilCooling Coil

Chilled WaterChilled WaterValveValve

FanFan Heater ElementsHeater Elements

CAV with Humidity ControlCAV with Humidity ControlTT

HH

Temperature sensor in spaceTemperature sensor in space

Humidity sensor in spaceHumidity sensor in space

Temperature and humidity Temperature and humidity sensors may alternatively be sensors may alternatively be

placed in return air ductplaced in return air duct

Page 4: Application of Controls

Application of ControlsApplication of Controls

CAV with Humidity ControlCAV with Humidity ControlThe valve is controlled by the humidity The valve is controlled by the humidity sensor to achieve the humidity setpoint.sensor to achieve the humidity setpoint.

The heating elements are controlled by The heating elements are controlled by the temperature sensor to reheat the air the temperature sensor to reheat the air

to achieve the temperate setpoint.to achieve the temperate setpoint.

This works if outdoor air is used; if pre-This works if outdoor air is used; if pre-treated air is used, cooling request may treated air is used, cooling request may

be greater than dehumidification be greater than dehumidification request and valve is controlled by request and valve is controlled by

temperature sensor.temperature sensor.

Page 5: Application of Controls

Application of ControlsApplication of Controls

HumidityHumidity TemperatureTemperatureCAV with Humidity ControlCAV with Humidity Control

HH

TT

S.P.S.P.

D.B.D.B.

P.B.P.B.

Cooling CoilCooling CoilCommandCommand

HeatingHeatingCommandCommand

S.P.S.P.

D.B.D.B.

P.B.P.B.

Page 6: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical Controls

Page 7: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical ControlsFCU ControlFCU Control

A temperature A temperature switch in the return switch in the return

air controls the 2 air controls the 2 position valveposition valve

A separate 3 speed A separate 3 speed switch is connected switch is connected

to the fanto the fan

Page 8: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical ControlsFCU ControlFCU Control

A temperature A temperature switch in the switch in the room controls room controls the 2 position the 2 position

valvevalve

The integral 3 The integral 3 speed switch is speed switch is

connected to the connected to the fanfan

Page 9: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical ControlsCondenser FanCondenser Fan

As the condenser As the condenser pressure pressure

increases, a fan increases, a fan is startedis started

As the pressure As the pressure continues to continues to

rise, a second rise, a second fan is startedfan is started

FromFromEvaporatorEvaporator

ToToCompressorCompressor

Page 10: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical ControlsCooling Tower FanCooling Tower Fan

As the As the temperature temperature

increases, the increases, the low speed low speed winding is winding is engagedengaged

As the As the temperature temperature continues to continues to rise, the high rise, the high

speed winding is speed winding is engagedengaged

Page 11: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical ControlsCold RoomCold Room

As the As the temperature temperature

increases, the increases, the compressors are compressors are

brought on in brought on in sequencesequence

Condenser fans Condenser fans controlled based controlled based

on pressureon pressure

C1C1 C2C2 C3C3 C4C4

EvaporatorEvaporator

ColdColdRoomRoom

CondenserCondenser

Page 12: Application of Controls

Application of ControlsApplication of Controls

Mechanical ControlsMechanical ControlsCompressor Compressor

SafetiesSafeties

If the condenser If the condenser pressure is too pressure is too high or too low, high or too low, the compressor the compressor

will be shut will be shut downdown

If the lube oil If the lube oil pressure is too pressure is too

low, the low, the compressor will compressor will be shut downbe shut down

Page 13: Application of Controls

Application of ControlsApplication of Controls

Chiller Plant IntegrationChiller Plant Integration

Page 14: Application of Controls

Application of ControlsApplication of Controls

Chiller Plant IntegrationChiller Plant Integration Single seat user interfaceSingle seat user interface

Consolidation of informationConsolidation of information

Facility wide strategiesFacility wide strategies

Simplify operations / trainingSimplify operations / training

Page 15: Application of Controls

Application of ControlsApplication of Controls

DataportIntegrator

DDCRS232

Local Area Network

Operator Workstation (PC)

NCU

Carrier Comfort Network

Chiller Plant IntegrationChiller Plant Integration

Page 16: Application of Controls

Application of ControlsApplication of Controls

Chiller Plant IntegrationChiller Plant Integration Chilled Water Setpoint / Control PointChilled Water Setpoint / Control Point

Entering/Leaving Chilled Water Temp.Entering/Leaving Chilled Water Temp.

Entering/Leaving Condenser Water Entering/Leaving Condenser Water Temp.Temp.

Evaporator Refrigerant Temperature Evaporator Refrigerant Temperature and Pressureand Pressure

Condenser Refrigerant Temperature Condenser Refrigerant Temperature and Pressureand Pressure

Page 17: Application of Controls

Application of ControlsApplication of Controls

Chiller IntegrationChiller IntegrationDischarge TemperatureDischarge Temperature

Bearing TemperatureBearing Temperature

Motor Winding TemperatureMotor Winding Temperature

Oil Sump TemperatureOil Sump Temperature

Oil Pressure TransducerOil Pressure Transducer

etc....etc....

In brief, anything visible from Control In brief, anything visible from Control Panel.Panel.

Page 18: Application of Controls

Application of ControlsApplication of Controls

Chiller SequencingChiller Sequencing

Page 19: Application of Controls

Application of ControlsApplication of Controls

0

50

100

150

200

250

TONS

1 x 300 TR Chiller

Chiller SequencingChiller Sequencing

Page 20: Application of Controls

Application of ControlsApplication of Controls

0

100

200

300

400

500

600

700

800

TONS

3 x 300 TR Chiller

1 Chiller on

2 Chillers on

3 Chillers on

Chiller SequencingChiller Sequencing

Page 21: Application of Controls

Application of ControlsApplication of Controls

0

100

200

300

400

500

600

700

800

TONS

3 x 300 TR Chiller +30 HP associatedpumps/fans each

1 Chiller on

2 Chillers on

3 Chillers on

Chiller SequencingChiller Sequencing

Page 22: Application of Controls

Application of ControlsApplication of Controls

0

100

200

300

400

500

600

700

800

TONS

3 x 300 TR Chiller +30 HP associatedpumps/fans each

Run 1 ChillerRun 2

Chillers Run 3 Chillers

Chiller SequencingChiller Sequencing

Page 23: Application of Controls

Application of ControlsApplication of Controls

IncreasingLoad

DecreasingLoad

Differential to preventshort cycling

Chiller SequencingChiller Sequencing

Page 24: Application of Controls

Application of ControlsApplication of Controls

Chiller SequencingChiller Sequencing1. Plot curves for all combinations of 1. Plot curves for all combinations of

chillerschillers including pumps and cooling towers including pumps and cooling towers

2. Take switchover points from graph2. Take switchover points from graph

3. Program switchover points with 3. Program switchover points with differentialdifferential

4. Use run time to choose lead and lag 4. Use run time to choose lead and lag chillers chillers

Page 25: Application of Controls

Application of ControlsApplication of Controls

Chilled Water ResetChilled Water Reset

Page 26: Application of Controls

AHU 1

AHU 3

AHU 2

60%

75%

70%

Valve

6 Degrees

1000 Tons723 kW

Application of ControlsApplication of Controls

Chilled Water ResetChilled Water Reset

Page 27: Application of Controls

Application of ControlsApplication of Controls

AHU 1

AHU 3

AHU 2

60%

75%

70%

Valve

6 Degrees

1000 Tons723 kW

7 Degrees

68%

80%

76%658 kW

Chilled Water ResetChilled Water Reset

Page 28: Application of Controls

Application of ControlsApplication of Controls

56

58

60

62

64

66

68

Time

Chilled Water ResetChilled Water Reset

Page 29: Application of Controls

Application of ControlsApplication of Controls

RatioRatio Max. Reset*Max. Reset*

AHU 1AHU 1 8%/Deg8%/Deg 9.1 Deg 9.1 Deg

AHU 2AHU 2 6%/Deg6%/Deg 8.5 Deg 8.5 Deg

AHU 3AHU 3 5%/Deg5%/Deg 8.0 Deg 8.0 Deg* Assuming maximum valve position allowed is 85%

Chilled Water ResetChilled Water Reset

Page 30: Application of Controls

Application of ControlsApplication of Controls

Chilled Water ResetChilled Water Reset1. Record step response of valve position 1. Record step response of valve position

forfor each AHU to measure system delay and each AHU to measure system delay and calculate ratio (%/Degree) calculate ratio (%/Degree)

2. Automatically reset chilled water 2. Automatically reset chilled water temperature temperature

3. Look for opportunities to add localized 3. Look for opportunities to add localized cooling to increase chiller savings cooling to increase chiller savings