April 2011. ANSI/ASHRAE/IES Standard 90.1-2010 HVAC. April 2011 – PNNL-SA-80143. HVAC Compliance. Building System. Compliance Options. Prescriptive Option. Envelope. Mandatory Provisions (required for most compliance options). Energy Code Compliance. HVAC. Trade Off Option. SWH. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

1

BUILDING ENERGY CODES UNIVERSITY

ANSI/ASHRAE/IESStandard 90.1-2010 HVAC

April 2011April 2011 – PNNL-SA-80143

Page 2: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

2

HVAC Compliance

Mandatory Mandatory ProvisionsProvisions

(required for most compliance

options)

Building SystemBuilding System Compliance OptionsCompliance Options

Energy Code Energy Code ComplianceCompliance

Prescriptive Prescriptive OptionOption

Energy Cost Energy Cost BudgetBudget

Trade Off OptionTrade Off Option

SimplifiedSimplified

Envelope

HVAC

Lighting

SWH

Power

Other

Page 3: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

3

New Buildings Additions to Existing Buildings Alterations in Existing Buildings

Section 6 – 6.1.1HVAC Scope

Page 4: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

4

Equipment– New equipment shall meet the minimum efficiency requirements

Cooling systems – New cooling systems installed to serve previously uncooled spaces

shall comply with this section– Alterations to existing cooling systems shall not decrease economizer

capacity (unless economizer tradeoff is used) Ductwork

– New and replacement ductwork shall comply with applicable requirements

Piping– New and replacement piping shall comply with applicable requirements

Section 6 – 6.1.1.3HVAC Alterations Scope

Page 5: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

5

Alterations to the building HVAC system shall comply with the requirements of Section 6

Exceptions that are allowed:– Equipment being modified or repaired (not replaced)

• provided such modifications will not result in an increase in the annual energy consumption

– Equipment being replaced or altered which requires extensive revisions to other systems and such replaced or altered equipment is a like-for-like replacement

– Refrigerant change of existing equipment– Relocation of existing equipment– Ducts and pipes where there is insufficient space or access to meet

these requirements

Section 6 – 6.1.1.3HVAC Alterations

Page 6: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

6

You have to follow Sections – 6.1 General, – 6.7 Submittals, and – 6.8 Minimum Equipment Efficiency

And then you can follow either – Section 6.3 Simplified Approach OR– Sections 6.4 Mandatory Provisions and 6.5 Prescriptive Path

Alternatively, you can follow Section 11 (ECB), in which case Section 6.4 is mandatory

Section 6 – 6.2 HVAC Compliance Paths

Page 7: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

7

The simplified approach is an optional path for compliance when the following are met:

Buildings with 1 or 2 stories Buildings with gross floor area < 25,000 ft2

System serving single HVAC zone Unitary packaged or split air conditioners (air-cooled or

evaporatively cooled)

Section 6 – 6.3Simplified Approach Option

Page 8: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

8

a. Single HVAC zoneb. Single zone VAV controls (6.4.3.10)c. Cooling equipment efficiency (6.8.1)d. Air economizers (6.5.1)e. Heating equipment efficiency (6.8.1)f. Exhaust air energy recovery (6.5.6.1)g. Dual setpoint thermostat or manual changeoverh. Heat pump auxiliary heat controli. No reheat or simultaneous cooling and heating for humidity controlj. Off-hour shutoff and temperature setback/setupk. Piping insulation (Tables 6.8.3A and 6.8.3B)l. Ductwork insulation and sealing (6.4.4.2.1)m. Air balancing of ducted systemn. Outdoor air intake and exhaust systems (6.4.3.4)o. Zone thermostatic controls to prevent simultaneous heating and coolingp. Optimum start controlsq. Demand control ventilation (6.4.3.9)

Section 6 – 6.3 Simplified Approach Criteria

Page 9: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

9

Supply fans controlled by two-speed motors or variable-speed drives– Air-handling and fan coil units with chilled-water cooling coils– Supply fans with motors ≥ 5 hp

At cooling demands ≤ 50%, supply fan controls able to reduce airflow to no greater than the LARGER of

– ½ of the full fan speed OR– volume of outdoor air required to meet Standard 62.1

On and after January 1, 2012Supply fans controlled by two-speed motors or variable speed drives

– all AC equipment and air-handling units with direct expansion cooling and cooling capacity at AHRI conditions ≥ 110,000 Btu/h serving single zones

At control demands– 2/3 of the full fan speed OR– volume of outdoor air required to meet Standard 62.1

Section 6 – 6.4.3.10 (6.3.2b)Single Zone VAV Controls

Page 10: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

10

Section 6 – 6.4.3.10Single Zone VAV Controls (cont’d)

Page 11: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

11

Section 6 – 6.8.1A (6.3.2c) Equipment Efficiency

Reference Tables 6.8.1A, 6.81B and 6.8.1.D in 90.1-2010

Page 12: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

12

Section 6 – 6.3.2Economizers

The system shall have an economizer, unless the economizer Trade-off Option is used

Limited to unitary systems

Requires higher minimum cooling efficiency (EER)

Trade-off EER by

– System size

– Climate zone

Page 13: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

13

Section 6 – 6.3.2Economizers

Reference Table 6.3.2 on page 40 in 90.1-2010

Page 14: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

14

Climate and size dependent (Tables 6.5.1A and B)

There are LOTS of exceptions Can use air economizers

– 100% of design supply air– Sequenced with mechanical cooling equipment– High limit shutoff– Dampers

Section 6 – 6.5.1 (6.3.2d)Economizers

Page 15: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

15

Exceptions Systems with gas phase air cleaning per Standard 62.1 Where >75% of the air must be humidified >35°Fdp Systems with condenser heat recovery per 6.5.6.2.2a or

6.5.6.2.2b Residential systems <5X limits in Table 6.5.1A Systems with a balance point <=60°F Systems expected to operate < 20hrs/wk Systems serving zones with refrigerated casework Where comfort cooling efficiency meets or exceeds Table 6.3.2 Systems serving computer rooms under certain conditions

Section 6 – 6.5.1Economizer Exceptions

Page 16: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

16

Manual changeover or dual set-point thermostat Heat pump supplementary control No reheat or simultaneous heating and cooling for

humidity control Time clocks (except hotel/motel guest rooms and

systems requiring continuous operation)

Section 6 – 6.3Simplified Approach Option (cont’d)

Page 17: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

17

Balancing of ducted systems Outdoor air intake and exhaust systems Interlocked thermostats for separate heating and cooling System > 10,000 cfm:

– optimum start controls Demand control ventilation

Section 6 – 6.3Simplified Approach Option (cont’d)

Page 18: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

18

Piping and ductwork/plenum insulated

Section 6 – 6.3Simplified Approach Option (cont’d)

Page 19: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

19

Section 6 – 6.8.2B Duct Insulation

Reference Tables 6.8.2A and B on page 68 in 90.1-2010

Page 20: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

20

Tables 6.8.3A and 6.8.3B

Exceptions Factory-installed Piping conveying fluids

– design operating temperature range between 60°F-105°F, inclusive– that haven’t been heated or cooled through the use of fossil fuels or

electricity or where heat gain or heat loss will not increase energy usage

Hot water piping between shut off valve and coil, not > 4 ft in length, when located in conditioned spaces

Piping ≤ 1 in.– No insulation required for strainers, control values, and balancing

values

Section 6 – 6.4.4.1.3 (6.3.2k)Piping Insulation

Page 21: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

21

Section 6 – 6.8.3Piping Insulation

Reference Tables 6.8.3A and B on page 69 in 90.1-2010

Page 22: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

22

Required if: Supply air capacity ≥ value listed in Table 6.5.6.1

– Values are based on climate zone and % of outdoor air flow rate at design conditions

Recovery system effectiveness ≥ 50%

Section 6 – 6.5.6.1 (6.3.2f)Exhaust Air Energy Recovery

Page 23: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

23

Lab systems meeting 6.5.7.2 Systems serving uncooled spaces that are heated to < 60°F Systems exhausting toxic, flammable, paint or corrosive fumes

or dust Commercial kitchen hoods used for collecting grease or smoke Where > 60% of outdoor heating energy is provided from site-

recovered or site solar energy Heating energy recovery in climate zones 1 and 2 Cooling energy recovery in climate zones 3c, 4c, 5b, 5c, 6b, 7,

and 8 Where largest exhaust source is < 75% of the design outdoor

airflow Systems requiring dehumidification that employ energy

recovery in series with the cooling coil Systems operating < 20 hrs/week at outdoor air % in Table

6.5.6.1

Section 6 – 6.5.6.1 (6.3.2f) Exhaust Air Energy Recovery Exceptions

Page 24: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

24

Section 6 – 6.8.2B (6.3.2l)Duct & Plenum Insulation

Reference Table 6.8.2B on page 68 in 90.1-2010

Page 25: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

25

DCV must be provided for each zone with a area > 500 ft² and the design occupancy > 40 people/1000 ft² where the HVAC system has:

An air-side economizer, Automatic modulating control of the OSA dampers, or A design outdoor airflow > 3,000 cfm

Section 6 – 6.4.3.9 (6.3.2q)Demand Control Ventilation

Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less

than design occupancy.

Page 26: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

26

HVAC Compliance

Mandatory Mandatory ProvisionsProvisions

(required for most compliance

options)

Building SystemBuilding System Compliance OptionsCompliance Options

Energy Code Energy Code ComplianceCompliance

Prescriptive Prescriptive OptionOption

Energy Cost Energy Cost BudgetBudget

Trade Off OptionTrade Off Option

SimplifiedSimplified

Envelope

HVAC

Lighting

SWH

Power

Other

Page 27: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

27

Minimum Equipment Efficiency (Section 6.4.1)

Calculations (Section 6.4.2)

Controls (Section 6.4.3)

HVAC System Construction and Insulation (Section 6.4.4)

Section 6 – 6.4HVAC Mandatory Provisions

Page 28: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

28

HVAC Equipment Covered Air conditioners and condensing units Heat pumps (air, water, and ground source) Water-chilling packages (chillers) Packaged terminal and room air conditioners and heat pumps Furnaces, duct furnaces and unit heaters Boilers Heat rejection equipment (cooling towers) Heat transfer equipment (heat exchangers) Variable refrigerant flow (VRF) air conditioners VRF air-to-air and applied heat pumps Air conditioners serving computer rooms

Section 6 – 6.4.1.1 Minimum Equipment Efficiency

Page 29: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

29

Equipment efficiency information from manufacturers verified as followsEPACT equipment – to comply with DOE certification requirements

If certification program exists for covered product and includes provisions for verification and challenge of equipment efficiency ratings, product listed in program OR

If product not listed in program, ratings verified by an independent laboratory test report OR

If no certification program exists, equipment efficiency ratings supported by data furnished by manufacturer OR

Where components from different manufacturers are used, system designer specifies components whose combined efficiency meets Section 6.4.1

Requirements for plate type liquid-to-liquid heat exchangers listed in Table 6.8.1H

Section 6 – 6.4.1.4Verification of Equipment Efficiencies

Page 30: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

30

Mechanical equipment (6.4.1.5.1) – equipment not covered by NAECA to have a permanent label stating equipment complies with 90.1

Packaged terminal air conditioners (6.4.1.5.2) – packaged terminal air conditioners and heat pumps with sleeve sizes < 16 in. high and 42 in. wide with a cross-sectional area < 670 in2 to be factory labeled as follows:

Manufactured for nonstandard size applications only: not to be installed in new construction projects

Section 6 – 6.4.1.5Labeling

Page 31: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

31

Section 6 – 6.4.2.1Load Calculations

Must calculate heating and cooling system design loads

Must determine calculations with ANSI/ASHRAE/ACCA Standard 183-2007

Page 32: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

32

Section 6 – 6.4.2.2Pump Head

• When sizing pumps, head to be determined in accordance with generally accepted engineering standards/handbooks

• Method must be approved by the authority having jurisdiction

• Must calculate the pressure drop through each device and pipe segment in the critical circuit at design conditions

Page 33: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

33

Required for each zone Perimeter can be treated differently

Dead band controls Thermostats must have at least a 5°F dead band Exceptions

– Thermostats that require manual changeover between heating and cooling modes

– Special occupancy or applications where wide temperature ranges aren’t acceptable (e.g., retirement homes) and approved by adopting authority

Section 6 – 6.4.3.1Controls – Zone Thermostatic & Dead Band

Page 34: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

34

If limit switches, mechanical stops, or software programming for DDC systems are used

means will be provided to prevent the heating setpoint from exceeding the cooling setpoint minus any applicable proportional band

Section 6 – 6.4.3.2Controls – Setpoint Overlap Restriction

Page 35: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

35

Temperature Control off-hour requirementsAutomatic shutdownSetback controlsOptimum startZone isolationExceptions, HVAC systems

– with heating/cooling capacity < 15,000 Btu/h– intended to operate continuously

Section 6 – 6.4.3.3Controls – Off-Hour

Page 36: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

36

Automatic 7-day/week time clock with 10-hour battery backup

Exception: 2-day/week thermostat for residential applications

Each control to have Occupant sensor, OR Manually-operated timer with maximum two hour duration, OR Security system interlock

Exception Residential occupancies allowed to operate with only 2 different

time schedules/wk

Section 6 – 6.4.3.3.1Controls - Automatic Shutdown

Page 37: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

37

Climate Zones 2-8 Lower heating setpoint to 55ºF or less

Climate Zones 1b, 2b, 3b (hot/dry) Automatically restart, temporarily operate

– Raise cooling setpoint to 90ºF or higher OR

– Prevent high space humidity levels

Section 6 – 6.4.3.3.2Controls - Setback

Page 38: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

38

Individual heating and cooling air distribution systems with

Total design supply air capacity > 10,000 cfm Served by one or more supply fans

Control algorithm to at least be a function of Difference between space temperature and

occupied setpoint and amount of time prior to scheduled occupancy

Section 6 – 6.4.3.3.3Controls - Optimum Start

Page 39: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

39

Applies to Each floor in a multistory building Maximum 25,000 ft2 zone on one floor

Requirements Isolation devices to shut off outdoor and exhaust airflow when >

5,000 cfm Central systems shall be capable of stable operation with one

isolation zone Capable of separate time schedules for each isolation zone

Section 6 – 6.4.3.3.4Controls - Zone Isolation

Figure 6-EIsolation Methods for a Central VAV System(User’s Manual – 90.1.-2007)

Page 40: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

40

Stair and Shaft Vent dampers (6.4.3.4.1)Automatically closed during normal building operationInterlocked to open as required by fire and smoke detection systems

Shutoff Damper Controls (6.4.3.4.2) All outdoor air intake and exhaust systems require motorized damper Ventilation outdoor air and exhaust/relief dampers capable of automatically

shutting off during – Preoccupancy building warm-up, cool down, and setback

(Except when ventilation reduces energy costs or when ventilation must be supplied due to code requirements)

Exceptions: Backdraft gravity dampers okay

– For exhaust and relief in buildings < 3 stories in height above grade– Of any height in climate zones 1 - 3

Ventilation systems serving unconditioned spaces– 300 CFM

Page 41: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

41

Table 6.4.3.4.3 provides maximum leakage rates for outdoor air supply and exhaust dampers

Where OA supply and exhaust air dampers are required by Section 6.4.3.4

They shall have a maximum leakage rate when tested in accordance with AMCA Standard 500 as indicated in Table 6.4.3.4.3

Section 6 – 6.4.3.4.3Controls - Damper Leakage

Page 42: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

42

Section 6 – 6.4.3.4.3Controls - Damper Leakage

Reference Table 6.4.3.4.3 on page 43 in 90.1-2010

Page 43: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

43

Fans with motors > 0.75 hp shall have automatic controls complying with Section 6.4.3.3.1 that are capable of shutting off fans when not required

Exception HVAC systems intended to operate continuously

Section 6 – 6.4.3.4.4Ventilation Fan Controls

Page 44: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

44

Ventilation systems in enclosed parking garagesautomatically detect contaminant levels and stage fans ormodulate fan airflow rates to ≤ 50%, provided acceptable contaminant levels are maintained

Exception Garages < 30,000 ft2 with ventilation systems that use

mechanical cooling or heating Garages with a garage area to ventilation system motor

nameplate hp ratio > 1500 ft2/hp and don’t use mechanical cooling or heating

Where permitted by AHJ

Section 6 – 6.4.3.4.5Enclosed Parking Garage Ventilation

Page 45: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

45

Controls to prevent supplementary heat when heat pump can handle the load

ExceptionHeat pumps

– With minimum efficiency regulated by NAECA

– With HSPF rating meeting Table 6.8.1B (Includes all usage of internal electric resistance heating)

Section 6 – 6.4.3.5Heat Pump Auxiliary Heat Control

Page 46: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

46

Automatic valve to shut off preheat when humidification isn’t required

Section 6 – 6.4.3.6Controls - Humidifier Preheat

Page 47: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

47

Provide means to prevent simultaneous operation of humidification and dehumidification equipment

Limit switches, mechanical stops, or software programming (DDC systems)

Exceptions Zones served by desiccant systems, used

with direct evaporative cooling in series Systems serving zones where specific

humidity levels are required and approved by jurisdiction

– Museums and hospitals

Section 6 – 6.4.3.7Controls - Humidification and Dehumidification

Page 48: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

48

Automatic controls for Freeze protection systems

– outside air temperatures > 40°F or when conditions of protected fluid will prevent freezing

Snow- and ice-melting systems– pavement temperature > 50°F and no precipitation is falling and

outdoor temperature > 40°F

Section 6 – 6.4.3.8Controls - Freeze Protection and Snow/Ice

Page 49: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

49

Insulation installed in accordance with industry-accepted standards

Insulation protection Duct and plenum insulation Piping insulation Sensible heating panel insulation Radiant floor heating Duct sealing Duct leakage tests

Section 6 – 6.4.4HVAC System Construction and Insulation

Page 50: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

50

Insulation installed in accordance with industry-accepted standards

Insulation Protected from damage due to sunlight, moisture, equipment

maintenance, and wind Exposed to weather to be suitable for outdoor service Covering chilled water piping, refrigerant suction piping, or

cooling ducts located outside the conditioned space to include a vapor retardant located outside the insulation, all penetrations and joints of which to be sealed

Section 6 – 6.4.4.1.1General

Page 51: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

51

All supply and return ducts and plenums to be insulated per Tables 6.8.2A and 6.8.2B

Exceptions Factory-installed plenums, casings, or ductwork furnished as part of

HVAC equipment Ducts located in heated, semiheated, or cooled spaces For runouts < 10 ft in length to air terminals or air outlets, the R-value

need not exceed R-3.5 Backs of air outlets and outlet plenums exposed to unconditioned or

indirectly conditioned spaces with face areas > 5 ft2 need not exceed R-2; those ≤ 5 ft2 need not be insulated

Section 6 – 6.4.4.1.2Duct and Plenum Insulation

Page 52: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

52

Section 6 – 6.4.4.2.2 Duct Leakage Tests

Designed > 3 in. w.c. Leak tested Representative sections ≥ 25%

of the total installed duct area shall be tested

Ratings > 3 in. w.c. to be identified on drawings

Maximum permitted duct leakage

– Lmax = CLP0.65

• Where Lmax = maximum permitted leakage in cfm/100 ft2 duct surface area

Page 53: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

53

HVAC Compliance - Prescriptive

Mandatory Mandatory ProvisionsProvisions

(required for most compliance

options)

Building SystemBuilding System Compliance OptionsCompliance Options

Energy Code Energy Code ComplianceCompliance

Prescriptive Prescriptive OptionOption

Energy Cost Energy Cost BudgetBudget

Trade Off OptionTrade Off Option

SimplifiedSimplified

Envelope

HVAC

Lighting

SWH

Power

Other

Page 54: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

54

Economizers (Section 6.5.1) Simultaneous Heating and Cooling Limitation

(Section 6.5.2) Air System Design and Control (Section 6.5.3) Hydronic System Design and Control (Section 6.5.4) Heat Rejection Equipment (Section 6.5.5) Energy Recovery (Section 6.5.6) Exhaust Systems (Section 6.5.7) Radiant Heating Systems (Section 6.5.8) Hot Gas Bypass Limitation (Section 6.5.9)

Section 6 – 6.5HVAC Prescriptive Path

Page 55: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

55

Dampers capable of being sequenced with the mechanical cooling equipment and shall not be controlled by only mixed air temperature

Exception Systems controlled from space temperature (such as single-

zone systems)

Section 6 – 6.5.1.1.2Control Signal

Page 56: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

56

Automatically reduce outdoor air intake to minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage

Control types for specific climates from Table 6.5.1.1.3A Settings from Table 6.5.1.1.3B

Section 6 – 6.5.1.1.3High Limit Shutoff

Page 57: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

57

Section 6 – 6.5.1.1.3AHigh-limit Shutoff Control Options

Reference Table 6.5.1.1.3A on page 47 in 90.1-2010

Page 58: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

58

Section 6 – 6.5.1.1.3BHigh-limit Shutoff Control Settings

Reference Table 6.5.1.1.3B on page 47 in 90.1-2010

Page 59: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

59

Return, exhaust/relief and outdoor air dampers to meet the requirements in 6.4.3

Section 6 – 6.5.1.1.4Dampers

Page 60: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

60

Means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building

Outlet located to avoid recirculation into the building

Section 6 – 6.5.1.1.5Relief of Excess Outdoor Air

Page 61: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

61

System capable of cooling supply air by indirect evaporation and providing up to 100% of expected system cooling load at outside air temperatures of 50°F dry bulb/45°F wet bulb and below

Exception Systems primarily serving computer rooms

– Where 100% of expected system cooling load at 40°F dry bulb/35°F wet bulb is met with evaporative water economizers

– With dry cooler water economizers that satisfy 100% of expected system cooling load at 35°F dry bulb

You can also meet this requirement if your design can meet 100% of expected cooling load at 45°F dry bulb/40°F wet bulb with evaporative water economizers

Section 6 – 6.5.1.2.1Design Capacity – Water Economizers

Page 62: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

62

Precooling coils and water-to-water heat exchangers to have either

Water-side pressure drop of < 15 ft of water OR

Bypassed when not in use

Section 6 – 6.5.1.2.2Maximum Pressure Drop - Water Economizers

C o nde nse r

C h ille r

E va po ra to r

O ut

O ut

In

In

C o o lin gTow e r

C W P

P rim a ryC H W P Secondary

C HW PW ith

VariableSpeed D rive

H e adP ressu reC o ntro lVa lve

E co no m ize r C W P

H e atE xch an ge r

C H W S C H W R

Typ ica lC o o lin gC o il

C o o lin gC o ilW ithTer tia ryP um p

Va lveC lo sesInE co no m ize rM o de

2-W ayVa lve

Figure 6-O from90.1 User’s Manual

Page 63: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

63

Economizers must be integrated with mechanical cooling systems and be capable of providing partial cooling even when additional mechanical cooling is required

Section 6 – 6.5.1.3Integrated Economizer Control

Page 64: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

64

Designed so economizer operation doesn’t increase the building heating energy use during normal operation

Exception Economizers on VAV systems that

cause zone level heating to increase due to a reduction in supply air temperature

Section 6 – 6.5.1.4Economizer Heating System Impact

Page 65: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

65

Capable of operating in sequence the supply of heating and cooling energy to the zone

Controls prevent Reheating Recooling Mixing or simultaneously supplying air previously heated or

cooled Other simultaneous operation of heating and cooling systems to

the same zone

Section 6 – 6.5.2.1Zone Thermostatic Controls

Page 66: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

66

Zones for which volume of air that is reheated, recooled, or mixed is less than the larger of the following

30% of zone design peak supply Outside air flow rate to meet 6.2 of Standard 62.1 for the zone Any higher rate that can be demonstrated to jurisdiction to reduce overall system annual

energy usage Air flow rate required to meet applicable codes or accreditation standards (pressure

relationships or minimum air change rates)

Zones that comply with all of these Air flow rate in dead band that doesn’t exceed larger of these

• 20% of zone design peak supply• Outdoor air flow rate to meet 6.2 of Standard 62.1 for the zone• Any higher rate that can be demonstrated to jurisdiction to reduce overall system annual energy

usage Air flow rate that’s reheated, recooled, or mixed in peak heating demand < 50% of zone

design peak supply Air flow between dead band and full heating or full cooling to be modulated Lab exhaust systems complying with 6.5.7.2 Zones where ≥ 75% of energy for reheating or providing warm air in mixing systems is from

site-recovered or site-solar source

Section 6 – 6.5.2.1Zone Thermostatic Controls – Exceptions

Page 67: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

67

Zones with both supply and return/exhaust air openings > 6 ft above floor to not supply heating air > 20°F above space temperature

Applies in other parts of the Standard where reheating is allowed

ExceptionsLaboratory exhaust systems complying with 6.5.7.2During preoccupancy building warm-up and setback

Section 6 – 6.5.2.1.1Supply Air Temperature Reheat Limit

Page 68: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

68

To prevent the simultaneous heating and cooling in hydronic systems

Section 6 – 6.5.2.2Hydronic System Controls

Page 69: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

69

No common return system for both hot and chilled water

Section 6 – 6.5.2.2.1Three-Pipe System

Page 70: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

70

Two-pipe changeover system is allowed if it meets the following requirements:

Dead band from one mode to another is ≥ 15°F outdoor air temperature

Controls to allow operation of ≥ 4 hours in one mode before changing to another mode

Reset controls so heating and cooling supply temperatures at changeover point no more than 30°F apart

Section 6 – 6.5.2.2.2Two-Pipe Changeover System

Diagram Courtesy of Ken Baker

Page 71: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

71

Controls to provide heat pump water supply temperature deadband of at least 20°F between initiation of heat rejection and heat addition by central devices

Cooling tower bypass or cooling tower isolation dampers

A two-position valve at each hydronic heat pump for hydronic systems having a total pump systempower > 10 hp

Exception If system loop temperature

optimization controller is used, deadband < 20°F is allowed

Section 6 – 6.5.2.2.3Hydronic (Water Loop) Heat Pump Systems

Diagram Courtesy of Ken Baker

Page 72: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

72

Humidistatic controls to prevent Reheating Mixing of hot and cold air streams Heating and cooling of same air stream

Section 6 – 6.5.2.3Dehumidification

Page 73: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

73

Systems capable of reducing supply air flow to 50%, or to minimum ventilation

Systems under 80,000 BTU/h that can unload at least 50% Systems smaller than 40,000 BTU/h Process applications (exception does NOT apply to

computer rooms) 75% of reheat or re-cool energy is recovered or solar

Section 6 – 6.5.2.3Dehumidification Exceptions

Page 74: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

74

Section 6 – 6.5.2.4Humidification

Systems with hydronic cooling and humidification systems designed to maintain inside humidity at > 35°F dewpoint

temperature shall use a water economizer if required by 6.5.1

C o nde nse r

C h ille r

E va po ra to r

O ut

O ut

In

In

C o o lin gTow e r

C W P

P rim a ryC H W P Secondary

C HW PW ith

VariableSpeed D rive

H e adP ressu reC o ntro lVa lve

E co no m ize r C W P

H e atE xch an ge r

C H W S C H W R

Typ ica lC o o lin gC o il

C o o lin gC o ilW ithTer tia ryP um p

Va lveC lo sesInE co no m ize rM o de

2-W ayVa lve

Page 75: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

75

Each HVAC system with total fan system power > 5 hp to meet 6.5.3.1 through 6.5.3.2

Fan Power Limitation VAV Fan Control

– Part Load Fan Power Limitation

– Static Pressure Sensor location

– Set Point Reset

Section 6 – 6.5.3Air System Design and Control

Page 76: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

76

Table 6.5.3.1.1ATwo options:

nameplate hp (Option 1) fan system bhp (Option 2)

ExceptionsHospital, vivarium, and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control may use variable-volume fan power limitationIndividual exhaust fans with motor nameplate hp ≤ 1 hp

Section 6 – 6.5.3.1Fan Power Limitation

Page 77: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

77

Section 6 – 6.5.3.1Fan Power Limitation

Reference Table 6.5.3.1.1A on page 50 in 90.1-2010

Page 78: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

78

Section 6 – 6.5.3.1Fan Power Limitation

Reference Table 6.5.3.1.1B on page 50 in 90.1-2010

Page 79: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

79

Selected fan motor to be no larger than first available motor size greater than bhp

Fan bhp on design documents

Exceptions Fans < 6 bhp, where first available motor larger than bhp has

nameplate rating within 50% of bhp, next larger nameplate motor size may be selected

Fans ≥ 6 bhp, where first available motor larger than bhp has nameplate rating within 30% of bhp, next larger nameplate motor size may be selected

Section 6 – 6.5.3.1.2 Motor Nameplate Horsepower

Page 80: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

80

Individual VAV fans with motors ≥ 10 hp Must have either:

– Variable Speed Drive

– Vane axial fan with variable-pitch fan blades

– Other controls and devices to result in fan motor demand ≤ 30% of design wattage at 50% of design air volume when static pressure set point = 1/3 of total design static pressure, based on manufacturer’s certified fan data

Section 6 – 6.5.3.2.1 Part-Load Fan Power Limitation

Page 81: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

81

Placed so controller set point is ≤ 1/3 the total design fan static pressure

Except for digital control systems with zone reset capabilities where it may be at the fan discharge

Install multiple sensors in each major branch if sensor would be located downstream of a major duct split

Section 6 – 6.5.3.2.2 Static Pressure Sensor Location

Page 82: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

82

For systems with direct digital control of individual zone boxes reporting to the central control panel

Static pressure set point reset based on zone requiring the most pressure

Section 6 – 6.5.3.2.3Setpoint Reset

Page 83: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

83

In multiple-zone VAV systems with DDC of individual zone boxes reporting to central control panel

Include means to automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency as per Standard 62.1, Appendix A

Exceptions VAV systems with zonal transfer fans that recirculate air from

other zones without directly mixing it with outdoor air, dual-duct dual-fan VAV systems, and VAV systems with fan-powered terminal units

Systems required to have exhaust air energy recovery complying with 6.5.6.1

Systems where total design exhaust airflow is > 70% of total outdoor air intake flow requirements

Section 6 – 6.5.3.3Multiple-zone VAV System Ventilation Optimization Control

Page 84: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

84

Multiple zone HVAC systems to have controls to automatically reset supply-air temperature in response to building loads or outdoor air temperature

Controls to be capable of resetting supply air temperature at least 25% of difference between design supply-air temperature and design room air temperature

Controls that adjust the reset based on zone humidity are okay

Zones expected to experience relatively constant loads to be designed for fully reset supply temperature

Exceptions Climate zones 1a, 2a, and 3a Systems that prevent reheating, recooling or mixing of heated and cooled

supply air 75% of energy for reheating is from site-recovered or site solar energy

sources

Section 6 – 6.5.3.4Supply-air Temperature Reset Controls

Page 85: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

85

HVAC hydronic systems with total pump system power > 10 hp to meet 6.5.4.1 – 6.5.4.4

Hydronic Variable Flow Systems Pump Isolation Chilled and Hot Water Temperature Reset Hydronic (water-loop) Heat Pumps and Water-Cooled Unitary

Air-Conditioners Pipe Sizing

Section 6 – 6.5.4Hydronic System Design and Control

Page 86: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

86

HVAC pumping systems to include control valves Designed to modulate or step open and close as a function of load Designed for variable fluid flow Capable of reducing flow rates to ≤ 50% of design flow rate

Individual pumps serving variable flow systems with a motor > 5 hp

Have controls and/or devices resulting in pump motor demand ≤ 30% of design wattage at 50% of design water flow

Differential pressure setpoint to be ≤ 110% of that required to achieve design flow through the heat exchanger

If differential pressure control and DDC controls are used Reset setpoint downward based on valve positions until one valve

is nearly wide open

Section 6 – 6.5.4.1Hydronic Variable Flow

Page 87: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

87

Exceptions Systems where

– Minimum flow is < minimum flow required by equipment manufacturer for proper operation of equipment served by the system

– Total pump system power ≤ 75 hp

Systems that include ≤ 3 control valves

Section 6 – 6.5.4.1Hydronic Variable Flow

Page 88: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

88

If chilled water plant has more than one chiller or boiler plant has more than one boiler

Provide for flow reduction when chiller or boiler is shut down

Section 6 – 6.5.4.2 Pump Isolation

Page 89: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

89

Affects systems with design capacity > 300,000 Btu/h To include controls to automatically reset supply water

temperatures by representative building loads (including return water temperature) or by outside air temperature

Exceptions If controls would result in improper operation Hydronic systems with variable flow

Section 6 – 6.5.4.3Chilled and Hot Water Temperature Reset Controls

Page 90: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

90

Two-position valves at each hydronic heat pump must be provided and interlocked to shut off water flow to the heat pump when the compressor is off

Exceptions Units using water economizers

For hydronic heat pumps and water-cooled unitary ACs with total pump power > 5 hp Controls or devices must be provided to have pump motor demand ≤

30% of design wattage at 50% of design water flowThis basically converts the system into a variable flow system. As

such, these systems must also comply with 6.5.4.1

Section 6 – 6.5.4.4Hydronic Heat Pumps and Water-Cooled Unitary Air-Conditioners

Page 91: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

91

Chilled-water and condenser-water piping so design flow rate in each segment doesn’t exceed values in Table 6.5.4.5.

This table presents the maximum allowed flow rates per section of pipe as a function of the following three criteria:

– Pipe size– Annual hours of operation– System flow and control

ExceptionsRates exceeding the Table are allowed if the specific section of pipe in question isn’t in the critical circuit > 30% of operating hoursPiping systems with equivalent or lower total pressure drop than the same system with standard weight steel pipe with piping and fittings sized per the Table

Section 6 – 6.5.4.5Pipe Sizing

Page 92: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

92

Applies to heat rejection equipment used in comfort cooling systems such as

Air-cooled condensers Open cooling towers Closed-circuit cooling towers Evaporative condensers

Exceptions Heat rejection devices included as an integral part of equipment

listed devices whose energy usage is included in Tables 6.8.1A-6.8.1D

Section 6 – 6.5.5Heat Rejection Equipment

Page 93: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

93

Fan Speed Control Each fan powered by a motor ≥ 7.5 hp

– Have capability to operate fan at ≤ 2/3 full speed

– Have controls to automatically change the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat rejection device

Exceptions– Condenser fans serving multiple refrigerant circuits or flooded

condensers

– Installations in climates zones 1 and 2

– Up to 1/3 of the fans on a multiple fan application speed controlled

Section 6 – 6.5.5.2Fan Speed Control

Page 94: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

94

Section 6 – 6.5.5.3Limitation on Centrifugal Fan Open-Circuit Cooling Towers

• If towers have a combined rated capacity ≥ 1100 gpm at 95°F condenser water return, 85°F condenser water supply, and 75°F outdoor air wet-bulb temperature – Must meet requirement for axial fan open-circuit cooling towers

in Table 6.8.1G

Exceptions– Ducted (inlet or discharge)– Require external sound attenuation

Page 95: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

95

Condenser recovery required if 24 hrs per day and Heat rejection > 6,000,000 Btu/h and SWH load > 1,000,000 Btu/h

The required heat recovery system shall have the capacity to provide the smaller of

60% of the peak heat rejection load at design conditions or preheat of the peak service hot water draw to 85°F.

ExceptionsIf condenser heat recovery is used for space heating with a heat recover design > 30% of peak water-cooled condenser load at design conditionsIf 60% of service water heating is provided from site-solar or site-recovered energy or other sources

Section 6 – 6.5.6.2Heat Recovery for Service Water Heating

Page 96: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

96

Section 6 – 6.5.7.1 Kitchen Exhaust Systems

• Replacement air introduced directly into hood cavity to be ≤ 10% of hood exhaust airflow rate

• Conditioned supply air to not exceed the greater of– Supply flow required to meet space heating or cooling load– Hood exhaust flow minus available transfer air from adjacent spaces

• If kitchen/dining facility has total kitchen hood exhaust airflow rate > 5,000 cfm, each hood’s exhaust rate must comply with Table 6.5.7.1.3– If a single hood or hood section is over appliances with different

duty ratings, then the max. airflow rate for that can’t exceed the Table values for highest appliance duty rating under that hood or hood section

Exception• If at least 75% of all replacement air is transfer air that would

otherwise be exhausted

Page 97: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

97

Section 6 – 6.5.7.1 Kitchen Exhaust Systems, con’t

Kitchens/dining facilities with total kitchen hood exhaust airflow rate > 5,000 cfm must have one of these:– At least 50% of all replacement air is transfer air that would

otherwise be exhausted– Demand ventilation systems on at least 75% of exhaust air

(capable of at least 50% reduction in exhaust and replacement air system airflow rates)

– Listed energy recovery devices with sensible heat recover effectiveness of not less than 40% on at least 50% of the total exhaust airflow

Page 98: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

98

Section 6 – 6.5.7.1 Kitchen Exhaust Systems, con’t

Performance testing must be done using an approved field test method If demand control ventilation systems are used, additional testing

is required

Page 99: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

99

Section 6 – 6.5.7.2 Laboratory Exhaust Systems

Laboratory exhaust systems with total exhaust rate > 5,000 cfm to have one of the following VAV lab exhaust and room supply system capable of reducing

exhaust and makeup air flow rates and/or incorporate a heat recovery system

VAV lab exhaust and room supply systems required to have minimum circulation rates to comply with code to be capable of reducing zone exhaust and makeup air flow rates to the regulated minimum circulation values or minimum required to maintain pressurization relationship requirements

Non-regulated zones capable of reducing exhaust and makeup air flow rates to 50% of zone design values or minimum required to maintain pressurization relationship requirements

Direct makeup air supply to equal at least 75% of exhaust air flow rate, heated no warmer than 2°F below room setpoint, cooled to no cooler than 3°F above room setpoint, no humidification added, and no simultaneous heating and cooling used for dehumidification control

Page 100: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

100

Required for unenclosed spaces exception: loading docks with air curtains

“Radiant heating systems that are used as primary or supplemental enclosed space heating must be in conformance with the governing provisions of the standard”

Radiant hydronic ceiling or floor panels

Combination or hybrid systems with radiant heating (or cooling) panels

Radiant heating (or cooling) panels used in conjunction with other systems such as VAV or thermal storage systems

Section 6 – 6.5.8Radiant Heating Systems

Page 101: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

101

Applied in systems with stepped or continuous unloading

Limitation also pertains to chillers

Exception: Packaged unitary systems≤ 90,000 Btu/h (7.5 tons)

Section 6 – 6.5.9Hot Gas Bypass Limitation

Maximum HGBP capacity,% of total capacity

Rated capacityof system

≤ 240,000 Btu/h 50%

> 240,000 Btu/h 25%

Page 102: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

102

Section 6 – 6.7 Submittals

Record drawings Operating and maintenance manuals System balancing System commissioning

Page 103: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

103

Section 6 – 6.7.2.1Drawings

Record drawings of actual installation to building owner within 90 days of system acceptance and include, as a minimum

Location and performance data on each piece of equipment General configuration of duct and pipe distribution system

including sizes Terminal air or water design flow rates

Page 104: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

104

Operating and maintenance manuals to building owner within 90 days of system acceptance and include several items

Section 6 – 6.7.2.2Manuals

Page 105: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

105

Systems shall be balanced in accordance with accepted engineering standards

Written report for conditioned spaces > 5000 ft2

Minimize throttling losses For fans with system power > 1 hp

– Adjust fan speed to meet design flow conditions

Section 6 - 6.7.2.3 System Balancing

Page 106: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

106

Proportionately balanced to minimize throttling losses

Pump impeller trimmed or pump speed adjusted to meet design flow conditions

Each system to have either the ability to measure differential pressure increase across the pump or have test ports at each side of the pump

Exceptions Pumps with pump motors ≤ 10 hp When throttling results in < 5% of the nameplate hp draw, or 3 hp, whichever is

greater, above that required if the impeller was trimmed

Section 6 – 6.7.2.3.3Hydronic System Balancing

Page 107: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

107

Control elements are calibrated, adjusted, and in proper working condition

> 50,000 ft2 conditioned area Except warehouses and semiheated spaces Requires commissioning instructions

Section 6 – 6.7.2.4System Commissioning

Page 108: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

108

ComplianceService Water Heating (SWH)

Mandatory Mandatory ProvisionsProvisions

(required for most compliance

options)

Building SystemBuilding System Compliance OptionsCompliance Options

Energy Code Energy Code ComplianceCompliance

Prescriptive Prescriptive OptionOption

Energy Cost Energy Cost BudgetBudget

Trade Off OptionTrade Off Option

SimplifiedSimplified

Envelope

HVAC

Lighting

SWH

Power

Other

Page 109: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

109

Section 7.2 You have to follow Sections

– 7.1, – 7.4, – 7.5, – 7.7, and – 7.8

Alternatively, you can follow Section 11 (ECB), in which case Section 7.4 is mandatory

Section 7 SWH Compliance Paths

Page 110: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

110

Section 7 Service Water Heating

General (Section 7.1) Compliance Path(s) (Section 7.2) Mandatory Provisions (Section 7.4)

– Load calculations– Equipment efficiency– Service hot water piping insulation– System controls– Pools– Heat traps

Prescriptive Path (Section 7.5)– Space heating and water heating– Service water heating equipment

Submittals (Section 7.7)

Page 111: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

111

New buildings Additions to existing buildings Alterations to existing buildings

Section 7 – 7.1.1SWH Scope

Page 112: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

112

SWH equipment installed as a direct replacement shall meet these requirements

EXCEPTION:Not sufficient space or access to meet requirements

Section 7 – 7.1.1.3SWH Alterations

Page 113: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

113

In accordance with manufacturer’s published sizing guidelines or generally accepted engineering standards and handbooks

Section 7 – 7.4.1Load Calculations

Page 114: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

114

Section 7.4.2 refers to Table 7.8 for equipment efficiencies

Equipment not listed in Table 7.8 has no minimum performance requirements

Exception Water heaters and hot water supply boilers > 140 gal storage

capacity don’t have to meet standby loss requirements when– Tank surface is thermally insulated to R-12.5, and– A standing pilot light isn’t installed, and– Gas- or oil-fired water heaters have a flue damper or fan-assisted combustion

Section 7 – 7.4.2Equipment Efficiency

Page 115: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

115

Section 7 – 7.8Equipment Efficiency

Reference Table 7.8 on page 57 in 90.1-2007

Page 116: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

116

Table 6.8.3, Section 6 Circulating water heater

– Recirculating system piping, including supply and return piping

Nonrecirculating storage system– First 8 ft of outlet piping– Inlet pipe between storage tank and

heat trap

Externally-heated pipes (heat trace or impedance heating)

Section 7 – 7.4.3Service Hot Water Piping Insulation

Page 117: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

117

Section 7 – Table 6.8.3Piping Insulation

Reference Table 6.8.3 on page 54 in 90.1-2007

Page 118: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

118

Temperature Controls Temperature Maintenance Controls Outlet Temperature Controls Circulating Pump Controls

Section 7 – 7.4.4Service Water Heating System Controls

Page 119: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

119

To allow for storage temperature adjustment from 120°F or lower to a maximum temperature compatible with the intended use

Exception If manufacturer’s installation instructions specify a higher

minimum thermostat setting to minimize condensation and resulting corrosion

Section 7 – 7.4.4.1Temperature Controls

Page 120: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

120

Automatic time switches or other controls Set to switch off usage temperature maintenance system

during extended periods when hot water is not required

Section 7 – 7.4.4.2Temperature Maintenance Controls

Page 121: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

121

Controls provided To limit maximum temperature of water delivered from lavatory

faucets in public facility restrooms to 110°F

Section 7 – 7.4.4.3Outlet Temperature Controls

Page 122: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

122

To limit operation to a period from the start of the heating cycle to a maximum of five minutes after the end of the heating cycle

Section 7 – 7.4.4.4Circulating Pump Controls

Page 123: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

123

Section 7 – 7.4.5Pools

Pool heaters to have readily accessible on-off switch Pool heaters fired by natural gas can NOT have

continuously burning pilot lights Vapor retardant pool covers required (unless recovered

or solar heat) Time switches required

Page 124: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

124

Noncirculating systems to have heat traps on both the inlet and outlet piping as close as practical to storage tank (if no integral heat traps)

Section 7 – 7.4.6Heat Traps

Either a device specifically designed for this purpose or

Arrangement of tubing that forms a loop of 360° or piping that from the point of connection to the water heater includes a length of piping directed downward before connection to the vertical piping of the supply water or hot water distribution system, as applicable

Page 125: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

125

Gas- or oil-fired space heating boiler system (complying with Section 6) is allowed to provide total space heating and water heating when ONE of the following conditions is met

Single boiler or component that is heating the service water has a standby loss in Btu/h not exceeding

– (13.3 x pmd + 400) / n; where pmd is probable maximum demand in gal/h and n is the fraction of the year when outdoor daily mean temperature is > 64.9°F

Jurisdiction agrees use of a single heat source will consume less energy than separate units

Energy input of the combined boiler and water heater system is < 150,000 Btu/h

Instructions for determining standby loss are included in this Section

Section 7 – 7.5.1Space Heating and Water Heating

Page 126: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

126

Equipment used to provide the additional function of space heating as part of a combination (integrated) system shall satisfy all requirements for service water heating equipment

Section 7 – 7.5.2Service Water Heating Equipment

Page 127: ANSI/ASHRAE/IES Standard 90.1-2010 HVAC

BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU

127

Authority having jurisdiction may require submittal of compliance documentation and supplemental information in accord with Section 4.2.2 of this standard

Section 7 – 7.7Service Water Heating Submittals