aneesh draft final

Upload: shelton-s-s-shelton

Post on 05-Apr-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Aneesh Draft Final

    1/13

    Dept of electrical and electronics Page 1

    OPTIMAL DISTRIBUTION VOLTAGE CONTROL AND

    CO-ORDINATION WITH DISTRIBUTED GENERATION

    BY

    ANEESH K G

    E7 A 7706

    Guided by,

    Dr K Bijuna Kunju

    Dept. of electrical and electronics

  • 7/31/2019 Aneesh Draft Final

    2/13

    Dept of electrical and electronics Page 2

    ABSTRCT

    Distributed generation is becoming a common practice nowadays because of its

    utilization of natural energy, high reliability and low transmission losses. But since the

    output power generated from natural energy, like wind power, photovoltaics etc. are

    influenced by meteorological conditions, the voltage at each node becomes a problem.

    Here in this work, the optimal control of distribution voltage with coordination of

    distributed installations, such as the load ratio control transformer, step voltage

    regulator (SVR), shunt capacitor, shunt reactor, and static var compensator are

    presented. The communication infrastructure Is assumed to be widespread. In order to

    confirm the validity of the proposed method simulations are done for a distributed

    network with distributed generation.

  • 7/31/2019 Aneesh Draft Final

    3/13

    Dept of electrical and electronics Page 3

    INTRODUCTION

    The increasing demand of electrical energy cannot be supplied with theconventional energy sources like hydro, thermal and nuclear power plants with

    centralized power generation. So some new and renewable energy sources such as

    photovoltaic, wind mills etc. are connected with the existing power system at points

    where they are available. This process by which the generation of power is

    decentralized and is made near to the load centers is termed as distributed generation

    (DG). A high stability ,clean energy system with less transmission loss can be

    implemented using distributed generation. But since the natural power generation

    sources are influenced by the climatic conditions, the voltage at each node becomes a

    problem. So proper control methods should be adopted for the optimal control of the

    distribution voltage.

    Here, In this work the optimal control of the distribution system is

    done with installations such as load ratio control transformer (LRT), static var

    compensator (SVC), shunt reactor (ShR), shunt capacitor (SC), step voltage regulator

    (SVR) etc. The co-ordinate control of each of the equipments makes the voltage

    stability. A wide spread communication channel such as optical cable is necessary to

    control all the equipments with co- ordination.

  • 7/31/2019 Aneesh Draft Final

    4/13

    Dept of electrical and electronics Page 4

    WHAT IS DISTRIBUTED GENERATION?

    GROUP OF GENERATORS CONNECTED TO VARIOUS POINTS OF THE POWER SYSTEM

    The decentralization of the electricity generation near to the load centers

    where natural and renewable sources of energy is available is termed as distributed

    generation.

    The advantages of DG are ,

    Transmission losses are minimum. Clean and natural energy with high thermal efficiency. Close to demand. Reliability of services. Economical energy production. Less vulnerable to outages.

    The problems with DG are,

    Since the o/p of natural energy sources depends on meteorological conditions,distributed generators connected to the downstream may produce backward

    flow. So uni-directional flow of power gets affected.

    Co-generators are more expensive/watts.

    As distributed generation increases , the voltage at each node becomes a

    problem.

  • 7/31/2019 Aneesh Draft Final

    5/13

    Dept of electrical and electronics Page 5

    OPTIMAL CONTROL OF VOLTAGE USING DISTRIBUTED INSTALLATIONS

    Modern electric power utilities are facing many challenges due to over

    increasing complexity in their operation and structure. One of the main problem is

    voltage instability. The main cause of voltage instability is the inability to meet the exact

    demand of REACTIVE power. The voltage at the consumer should be maintained within

    the range. The co-ordinate operation of some distributed installations is used for the

    optimal voltage control of DG.

    The distribution installations includes,

    o Load ratio control transformer

    o Static var compensator

    o Shunt capacitors

    o Shunt reactors

    o

    Step voltage regulator

  • 7/31/2019 Aneesh Draft Final

    6/13

    Dept of electrical and electronics Page 6

    LOAD RATIO CONTROL TRANSFORMER ( LVR )

    The transformation ratio of LVR can be changed at the time of load.

    Ratio control methods Equivalent model of LRT

    Multi point selector switch along with some crank shaft and cam

    arrangements causes it to slide on the tapings. The self end information such as voltage,

    current are measured and is compared with the target value which is determined

    beforehand. The transformer tap location is adjusted so that the voltage is maintained

    at the desired level. But the problems like non uniformity of load distribution, reversed

    power flow may cause deviations from operating standard voltage at other points such

    as end portion, etc. These problems can be minimized using centralized control.

    STEP VOLTAGE REGULATOR (SVR)

    step voltage regulator is simply a step up or step down transformer which is

    connected in distribution feeder lines. It provides increments or steps of voltage change.

    It either oppose or aid their respective voltages.

    step voltage transformer(boost) step voltage transformer(buck)

    http://1.bp.blogspot.com/-Hfuu2RLws4Q/TbEe9TdN4UI/AAAAAAAAAG0/qTY7kQ8gI1o/s1600/Step-down+Autotransformer.jpghttp://4.bp.blogspot.com/-eZBfWXJ8LTs/TbEet1ihi2I/AAAAAAAAAGw/bRTmUrcOlU4/s1600/Step-up+Autotransformer.jpghttp://1.bp.blogspot.com/-Hfuu2RLws4Q/TbEe9TdN4UI/AAAAAAAAAG0/qTY7kQ8gI1o/s1600/Step-down+Autotransformer.jpghttp://4.bp.blogspot.com/-eZBfWXJ8LTs/TbEet1ihi2I/AAAAAAAAAGw/bRTmUrcOlU4/s1600/Step-up+Autotransformer.jpghttp://1.bp.blogspot.com/-Hfuu2RLws4Q/TbEe9TdN4UI/AAAAAAAAAG0/qTY7kQ8gI1o/s1600/Step-down+Autotransformer.jpghttp://4.bp.blogspot.com/-eZBfWXJ8LTs/TbEet1ihi2I/AAAAAAAAAGw/bRTmUrcOlU4/s1600/Step-up+Autotransformer.jpghttp://1.bp.blogspot.com/-Hfuu2RLws4Q/TbEe9TdN4UI/AAAAAAAAAG0/qTY7kQ8gI1o/s1600/Step-down+Autotransformer.jpghttp://4.bp.blogspot.com/-eZBfWXJ8LTs/TbEet1ihi2I/AAAAAAAAAGw/bRTmUrcOlU4/s1600/Step-up+Autotransformer.jpg
  • 7/31/2019 Aneesh Draft Final

    7/13

    Dept of electrical and electronics Page 7

    For example, if the transformer has a turns ratio of 10:1 with 1000 V

    applied in the primary, then, the secondary voltage will be 100 V. Adding or subtracting

    by using the connection mentioned above - the output voltage would be 1100 V or 900

    V, respectively. Thus, the transformer becomes an autotransformer with the capability

    to boost (raise/step-up) or buck (lower/step-down) the system voltage by 10%. The self

    end information such as current and voltage is calculated by the tap position of SVR.

    This information is compared with the desired values and controls the tap location of

    LRT to settle the voltage at a desired value.

    SHUNT CAPACITANCE

    A capacitor or a group of capacitors which are placed across the

    electrical lines to provide a voltage increase or to improve the power factor of the

    circuit. They are less expensive to install and maintain. A switchable shunt can be

    disconnected from the circuit when conditions are satisfactory. The SC must be switched

    on / off according to the system reactive power demand. The shunt capacitors supply

    necessary VAR to the system, thereby increasing the voltage level. Also whenever

    inductive load is connected to the transmission line, power factor lags because of

    lagging load current. To compensate, a shunt capacitance is connected, which draws

    current leading the voltage. The net result is improvement of power factor.

  • 7/31/2019 Aneesh Draft Final

    8/13

    Dept of electrical and electronics Page 8

    The on/off time and switching is done through centralized control,

    by comparing the self end information with the target value. Online SC control and co-

    ordinate control of SC and LRT are the common practices

    SHUNT REACTANCE

    Shunt reactors are inductors connected across the power lines to

    provide reduction in overvoltage and for power factor correction. These reactors

    consume the VAR of the system. They are also used at the end of the transmission line

    to compensate for the reactive power generated by line capacitance. In case of long

    transmission lines unloaded the receiving end voltages often goes higher than the

    sending end voltage. This effect is Ferranti effect. The shunt reactor consumes this

    reactive power and reduces the voltage level. Also the leading power factor can be

    avoided by the action of shunt reactance.

    Equivalent diagram of transmission line with line inductance, line capacitance and shunt reactor (g)

    STATIC VAR COMPENSATOR ( SVC )

    SVC is equipment that compensate for reactive power at high speed by controlling the

    current of a capacitor by the thyristor. SVC not only regulates the system voltage by

    reactive power correction, but for power factor control also. These are used near to the

    places where the loads are varying rapidly.

  • 7/31/2019 Aneesh Draft Final

    9/13

    Dept of electrical and electronics Page 9

    If the power system is capacitive (leading), the SVC will use reactors

    to consume VAR from the system, lowering the system voltage. And if it is inductive,

    capacitor banks are automatically switched in, thus providing a higher system voltage. In

    static system of VAR compensation, instead of mechanical switches controllable

    switches called thyristors are used for high reliability. The thyristors are controlled by

    signal from the control system via optical cables. The reliability can be increased by the

    controlled switching of the capacitors also with thyristors (thyristor switched capacitor)

  • 7/31/2019 Aneesh Draft Final

    10/13

    Dept of electrical and electronics Page 10

    SIMULATION

    The result of simulation done to check the validity of the proposed project is

    as follows..

    Consider a residential distribution network as shown with a photovoltaic equipment at

    node 33.

    RESIDENTIAL DISTRIBUTION NETWORK

    The load curve of residential area and capacity factor of photovoltaic generation varies

    as shown.

    Load curve of residential area capacity factor of photovoltaic generation

  • 7/31/2019 Aneesh Draft Final

    11/13

    Dept of electrical and electronics Page 11

    The voltage profile at various nodes with different control strategies at time 12.00 is as

    shown. The four different control strategies are, uncontrolled, tap control of a

    transformer, the tap of a transformer and the tap of SC and ShR, the tap of transformer,

    as well as the tap of SC and ShR and SVC control.

    At time 12.00 the photovoltaic generation is maximum. With no control on

    the installations the voltage variation is maximum. And with the co-ordinate and

    centralised control of all the installations the voltage at each node can be maintained at

    the desired value.

  • 7/31/2019 Aneesh Draft Final

    12/13

    Dept of electrical and electronics Page 12

    CONCLUSIONS

    To meet for the increasing demands of electricity, distributed generation should beEncouraged.

    The main problem with distributed generation is the voltage instability.

    Distributed installations such as Step voltage regulator, Load ratio transformer,Static VAR compensator, Shunt capacitor, Shunt reactor etc. are used for optimal

    control of voltage.

    Reliable central co-ordination of voltage regulation is done using optical fibercables.

    The co-ordinate and centralized control of all the equipments provides desiredvoltage regulation.

    REFERENCES

    K. Kabemura, K. Yonekura, T. Tsukamoto, K. Hashimoto, and M.

    Hara, Application of dispersed autonomous voltage control system to

    a real high voltage distribution network, Elect. Eng. Jpn., vol. 146, no.

    1, pp. 2736, 2004.

    N. I. Santoso and O. T. Tan, Neural-net based real-time control of

    capacitors installed on distribution systems, IEEE Trans. Power Del.,

    vol. 5, no. 1, pp. 266273, Jan. 1990. J. C.Wang, H. D. Chiang, K. N. Miu, and G. Darling, Capacitor placement

    and real time control in large-scale unbalanced distribution systems:

    Loss reduction formula, problem formulation, solution methodology

    and mathematical justification, IEEE Trans. Power Del., vol. 12,

    no. 2, pp. 953958, Apr. 1997.

    www.wikipedia.org

    www.ieeeexplore.ieee.org

    www.cleanenergyauthority.com

    R. H. Liang and C. K. Cheng, Dispatch of main transformer ULTC

    and capacitors in a distribution system, IEEE Trans. Power Del., vol.16, no. 4, pp. 625630, Oct. 2001.

    R. H. Liang and Y. S.Wang, Fuzzy-based reactive power and voltage

    control in a distribution system, IEEE Trans. Power Del., vol. 18, no.

    2, pp. 610618, Apr. 2003.

    http://www.wikipedia.org/http://www.wikipedia.org/http://www.ieeeexplore.ieee.org/http://www.ieeeexplore.ieee.org/http://www.cleanenergyauthority.com/http://www.cleanenergyauthority.com/http://www.cleanenergyauthority.com/http://www.ieeeexplore.ieee.org/http://www.wikipedia.org/
  • 7/31/2019 Aneesh Draft Final

    13/13

    Dept of electrical and electronics Page 13