general fa-m3 specifications fa-m3 value, value ii · function to communicate with a higher-level...
Post on 12-Mar-2020
5 Views
Preview:
TRANSCRIPT
<<Contents>> <<Index>>
General Specifications
FA-M3 FA-M3 Value, Value II (including base, power supply, sequence CPU and DI/O modules)
CONTENTS
F3SC21-1N FA-M3 Value ...................................................... 3
F3SC22- , F3SC23- FA-M3 Value II ................................................... 9
GS 34M06C81-01E©Copyright Oct. 20107th Edition: Oct. 2010Yokogawa Electric Corporation
Blank Page
<<Content>> <<Index>> 3
General Specifications
F3SC21-1N FA-M3 Value (including base, power supply, sequence CPU and DI/O modules)
General The F3SC21-1N (FA-M3 Value) is a compact programmable controller consisting of the following modules: F3BU04-0N base module (with 4 slots) F3SP05-0P sequence CPU module (with power supply and
memory) F3WD64-3N I/O module (with 32 inputs and 32 outputs) The F3SP05-0P double-slot sequence CPU module is installed in the leftmost slot of the F3BU04-0N 4-slot base module and the F3WD64-3N I/O module in slot 2. You can install any FA-M3 I/O modules in slots 3 and 4.
Features Its compact size greatly reduces installation space. The sequence CPU module has a 100-240 VAC universal power
supply so that the user doesn't have to worry about the power supply environment when using the F3SC21-1N.
The high-speed instruction processing capability of the F3SC21-1N makes it ideal for applications that require high speed response.
The use of a structured ladder programming language facilitates programming and maintenance of ladder programs.
The sequence CPU module has the personal computer link function to communicate with a higher-level computer or display. The user needs no personal computer link module (F3LC11-1N) for this purpose.
Programs and data can be saved on an optional ROM pack.
DC I/OWD64-3N
1234
5678
9101112
13141516
17181920
21222324
25262728
29303132
DISPLAY
CN3
1 2
CPU
RDYRUN
PROGRAMMER
SP05-0P
RDY
CN4
ASSY
S92
6 B
K-0
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
<< Content >> <<Index>> 4
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Specifications
Item Specification
Number of slots 4
Number of free I/O slots 2 (as the sequence CPU and 64-point I/O modules occupy two slots) Base module (F3BU04-0N)
Weight 140 g
Supply voltage 100-240 V AC, single phase, 50/60 Hz
Supply voltage fluctuation range 85-264 V AC, 50/60 Hz ±3 Hz
Power consumption 35 VA
Inrush current 20 A max. (120 V AC, Ta=25 ºC) 45 A max. (240 V AC, Ta=25 ºC)
Rated output voltage 5 V DC
Rated output current 2.0 A
Insulation resistance 5 MΩ or greater at 500 V DC (between external AC terminals and FG terminal)
Dielectric strength 1500 V AC for 1 minute (between external AC terminals and FG terminal)
FAIL-signal contact output Provided on the front terminal block on the power supply block; contact rating: 24 V DC, 0.3 A (both normally-open and normally-closed terminals available)
Allowable common-mode voltage of FAIL-signal contact
120 V max. AC or DC (between FAIL OUTPUT COM terminal and FG terminal)
Leakage current 0.5 mA max. Allowable momentary power failure time 20 ms
Pow
er s
uppl
y bl
ock
Noise immunity Immune to noise of up to 1500 Vp-p with 1-s pulse width and 1-ns rise time at 25-60 Hz (as measured with a noise simulator).
Control mode Stored program, cyclic execution
I/O control mode Refreshing method/direct I/O instructions
Programming language Structured ladder language, mnemonic language
Basic instructions 25 types Number of instructions Application
instructions 227 types
Basic instructions 0.18-0.36 μs/instruction Instruction processing speed
Application instructions 0.36 μs min./instruction
Program size 5K steps (can be stored in ROM)
Number of I/O points 2048 points max.
Number of program blocks 32 max.
Sampling trace No
Link to personal computer Yes
Monitoring of scan time 10-200 ms variable
Internal relay I: 4096 points max.
Shared relay —
Extended shared relay —
Link relay L: 2048 points
Special relay M: 2048 points
Timer T: 512 points max. (total of internal and external timers and counters)
Counter C: 512 points max. (total of internal and external timers and counters)
Data register D: 5120 points max.
File register —
Link register W: 2048 points
Special register Z: 512 points
Index register V: 32 points
Shared register —
Dev
ices
Extended shared register —
Sequence CPU module*1 (F3SP05-0P)
Sequ
ence
CPU
blo
ck
Self-diagnostics Memory error, CPU error, input/output error, syntax check, etc.
<< Content >> <<Index>> 5
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Item Specification
Other features
Configuration function (device capacity, data lock-up range at power failure, output when CPU stops, etc.) Constant scan function (1 ms to 190 ms) Debugging functions (forced SET/RESET, online edit, scan operation, etc.) Error history function (64 records) Date/clock function (year/month/day/hour/minute/second/day of week) Program protection functions ROM programming and data storage Personal computer link function
Sequ
ence
C
PU b
lock
Current consumption 350 mA (5 V DC)*2
External dimensions 58 (W) X 100 (H) X 83.2 (D) mm
Weight 320 g
UL UL508 approved, File No.E188707 (Overvoltage Category*4 II, Pollution Degree*5 2)
CE EMC Directive
EN 61326-1 Class A, Table 2 (For use in industrial locations) EN 61326-2-3*6 EN 55011 Class A, Group 1 EN 61000-6-2, EN 61000-3-2, EN 61000-3-3 compliance
Sequence CPU module*1 (F3SP05-0P)
Com
mon
Compliance with safety and EMC standards*3
C-Tick EMC Framework EN 55011 Class A, Group 1 compliance
Input type DC voltage
Number of points 32
Number of points/common 8 points/common
Isolation method Photocoupler isolation
Rated input voltage 24 V DC
Operating voltage 20.4-26.4 V DC
Rated input current 4.1 mA/point (24 V DC)
ON 6.0 V DC min., 3.2 mA min. Operating voltage/current OFF 5.8 V DC max., 0.9 mA max.
OFF→ON 1.0 ms max. Input
ON→OFF 2.5 ms max.
Inpu
t Blo
ck
Interrupt No
Output type Transistor contact (sink type)
Number of points 32
Number of points/common 8 points/common
Isolation method Photocoupler isolation
Rated load voltage 24 V DC
Maximum load current 0.1 A/point, 0.4 A/common
OFF→ON 1.0 ms max. Output Response ON→OFF 1.0 ms max.
Off-time leakage current 0.1 mA max.
Surge protector Zener diode
Out
put B
lock
External power supply 24 V DC, 60 mA
Input/output status indicator Lit when on (indicates either input or output status by using the selector switch)
Current consumption 200 mA (5 V DC)
External connection Two 40-pin connectors
Input/Output module (F3WD64-3N)
Com
mon
Weight 160 g
*1: When a sequence CPU module is to be used, use the Ladder Diagram Support Program M3, Rev. 2.02 or later. *2: The total current dissipated by the modules in slots 3 and 4 must be less than 1400 mA. *3: For details on conforming modules, see “UL-approved, CE marking and C-Tick mark-compliant Modules” (GS 34M06C11-21E) general specification
brochure. *4: The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four categories.
Overvoltage Category II applies to systems with rated voltage of 220/230/240V and applies to electrical appliances, portable devices, etc. *5: The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a reduction of dielectric
strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by condensation is to be expected.
*6: EN 61326-2-3 is applicable only to F3CU04-0S and F3CU04-1S
<< Content >> <<Index>> 6
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Base Module
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3BU04 -0N · · · · · · · · · · · · 4 slots (excluding slot for power supply)
External Dimensions
4 slots (F3BU04-0N)
O5 mounting hole
9.6
4.5 7.5
85 100
10.588.5
138147
(When mounted on module surface)
(for M4 mounting screw)
Unit: mm
<< Content >> <<Index>> 7
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Sequence CPU Module
Components and Functions
FAIL1
COM
FAIL2
N
L
FAIL OUTPUT
SP05-0P
RDY
CPU
Between FAIL1 and COM
Between FAIL2 and COM
Open
Short
Short
Open
During Normal operation
During System and Power Failures
Fail-signal contact outputContact ratings: 24 V DC, 0.3 A
Subject to grounding resistance of 100Ω max independently (JIS class D grounding, previously class 3 grounding)
Connect to FG and grounded
100-240 VAC
Lit when power supply is normal
FG
LG
FG (Frame Ground)
LG (Line filter Ground)
Power supply
RDY LED (green)
FB020301.VSD
INPUT 100-240VAC
RDYRUNALMERR
CPU modulemaintenace LEDs
PROGRAMMER
Programming tool interface connector
Terminal Dimensions
Unit: mm
8.2 mm7.1 mm
M3.5
Examples of Applicable Solderless Terminals
Vender Model Applicable Conductor
Applicable Crimping Torque
Japan Solderless Terminal Mfg. Co., Ltd. V1.25-M3
Nippon Tanshi Co., Ltd. RAV1.25-3.5
AWG22 to 18 (0.33 to 0.82 mm2) (Copper wire)
Japan Solderless Terminal Mfg. Co., Ltd. V1.25-M4
Japan Solderless Terminal Mfg. Co., Ltd. V2-M4
AWG16 to 14 (1.25 to 2.0 mm2) (Copper wire)
0.8 N • m
CPU Error Processing Different levels of errors are identified by different LEDs on the front panel of the CPU module.
LED Meaning
RDY (READY) Green Major failure (when off): The core hardware cannot run. Example: CPU error
Memory error RUN (RUN) Green When lit: The user program is running.
ALM (ALARM) Yellow
Minor failure (when lit): The user program can still run in spite of a failure. Example: Power failure
Communication error
ERR (ERROR) Red
Moderate failure (when lit): The user program cannot start or continue execution. Example: Program error*
I/O comparison error* I/O module error* Memory error Sequence processor error Instruction processing error* Scan timeout*
*: Minor or moderate failure can be defined in the configuration settings.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3SC21 -1N · · · · · · · · · · · · FA-M3 Value (with base, power supply, sequence CPU, and DI/O modules)
F3SP05 -0P · · · · · · · · · · · · Sequence CPU module (with power supply and memory) Memory: 5K steps
External Dimensions
<< Content >> <<Index>> 8
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3WD64-3N)
Internal Circuit Diagram
8
10
9
_
+
+
_
+89
Bus interface
Display selector OUT
IN
1
COM
L
L
COM
~
1
~
Inte
rnal
bus
External Connection Diagram
+
24V
COM46463626160595857
COM24847464544434241
+
COM35655545352515049
COM14039383736353433
2019181716151413121110987654321
2019181716151413121110987654321
B A
LLLLLLLL
24V
LLLLLLLL
+
+
24V
LLLLLLLL
LLLLLLLL
24V
CN2 (Output block)
COM43231302928272625
COM216151413121110 9
–+
+–
+–
–+
COM32423222120191817
COM1 8 7 6 5 4 3 2 1
–+
+–
+–
–+
2019181716151413121110987654321
2019181716151413121110987654321
B ACN1 (Input block)
Note: Viewed from the front of the module.
External Connections Connector Type
Wire connection method Soldered
Applicable wire size AWG23 max. (0.26 mm2 max.)
Applicable External Connectors Connection Method Applicable Connector
Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover
Solderless type Fujitsu FCN-363J040 housing
FCN-363J-AU contact FCN-360C040-B connector cover
Solderless type Fujitsu FCN-367J040-AU / F
Operating Environment There is no restriction on the type of CPU modules that can be used with this module.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3WD64 -3N · · · · · · · · · · · · 24 V DC input/output
Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.
External Dimensions F3WD64-3N
Unit: mm
<<Content>> <<Index>> 9
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
General The F3SC22- or the F3SC23- (FA-M3 Value II) is a compact programmable controller consisting of the following modules: F3SC22-1F F3BU04-0N (4-slot base module) F3SP08-0P (sequence CPU module) F3WD32-3F (32-point I/O module) F3SC22-2F F3BU04-0N (4-slot base module) F3SP08-0P (sequence CPU module) F3WD64-3F (64-point I/O module) F3SC22-1A F3BU04-0N (4-slot base module) F3SP08-0P (sequence CPU module) F3XD16-3F (16-point input module) F3YD14-5A (14-point output module) F3SC23-1F F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3WD32-3F (32-point I/O module) F3SC23-2F F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3WD64-3F (64-point I/O module) F3SC23-1A F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3XD16-3F (16-point input module) F3YD14-5A (14-point output module) F3SC23-2P F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3WD64-3P (64-point I/O module) F3SC23-6P F3BU04-0N (4-slot base module) F3SP08-SP (Sequence CPU module) F3WD64-4P (64-point I/O module, 12 V) Install the F3SP08-P sequence CPU module in the leftmost slot of the F3BU04-0N base module and the other I/O module(s) in slot 2 (or slots 2 and 3). The remaining slot(s) is available for a variety of FA-M3 I/O modules.
DC I/OWD32-3F
1234
5678
9101112
13141516
17181920
21222324
25262728
29303132
CN3
CPU
RDYRUN
PROGRAMMER
SP08-0P
RDY
CN4
ASSY
S92
6 B
K-0
Features Its compact size greatly reduces installation space. The sequence CPU module has a 100-240 VAC universal power
supply so that the user doesn't have to worry about the power supply environment.
The high-speed instruction processing capability makes it ideal for applications that require high speed response.
The use of a structured ladder programming language facilitates programming and maintenance of ladder programs.
The sequence CPU module has the personal computer link function to communicate with a higher-level computer or display. The user needs no personal computer link module (F3LC11-1N) for this purpose.
Programs and data can be saved on an optional ROM pack.
General Specifications
F3SC22-, F3SC23- FA-M3 Value II (including base, power supply, sequence CPU and DI/O modules)
<<Content>> <<Index>> 10
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Specifications
Common Specifications for F3SC22 and F3SC23 Item Specification
Number of slots 4 2 (for F3SC22-1F, F3SC22-2F, F3SC23-1F, F3SC23-2F, F3SC23-2P, and F3SC23-6P) Number of free I/O slots 1 (for F3SC22-1A and F3SC23-1A)
Base module (F3BU04-0N)
Weight 140 g Supply voltage 100-240 V AC, single phase, 50/60 Hz Supply voltage fluctuation range 85-264 V AC 50/60 Hz 3 Hz
Power consumption 35 VA
Inrush current 20 A max. (120 V AC, Ta=25 C) 45 A max. (240 V AC, Ta=25 C)
Rated output voltage 5 V DC Rated output current 2.0 A Insulation resistance 5 M or greater at 500 V DC (between external AC terminals and FG terminal) Dielectric strength 1500 V AC for 1 minute (between external AC terminals and FG terminal)
FAIL-signal contact output Provided on the front terminal block on the power supply block; contact rating: 24 V DC, 0.3 A (both normally-open and normally-closed terminals available)
Allowable common-mode voltage of FAIL-signal contact
120 V max. AC or DC (between FAIL OUTPUT COM terminal and FG terminal)
Leakage current 0.5 mA max. Allowable momentary power failure time 20 ms
Pow
er S
uppl
y B
lock
Noise immunity Immune to noise of up to 1500 Vp-p with 1-s pulse width and 1-ns rise time at 25-60 Hz (as measured with a noise simulator).
Control mode Stored program, cyclic execution I/O control mode Refreshing method/direct I/O instructions Programming language Structured ladder language, mnemonic language
Basic instructions 25 types Number of
instructions Application instructions 227 types
Basic instructions 0.18-0.36 s/instruction Instruction
Processing speed Application
instructions 0.36 s min./instruction
Program size 10K steps (can be stored in ROM) Number of I/O points 2048 points max. Number of program blocks 32 max. Sampling trace No Link to personal computer Yes Monitoring of scan time 10-200 ms variable
Internal relay I: 4096 points max. Shared relay — Extended shared relay —
Link relay L: 2048 points Special relay M: 2048 points Timer T: 512 points max. (total of internal and external timers and counters) Counter C: 512 points max. (total of internal and external timers and counters) Data register D: 5120 points max. File register — Link register W: 2048 points Special register Z: 512 points Index register V: 32 points Shared register —
Dev
ice
Extended shared register —
Sequence CPU module*1 (F3SP08-0P, F3SP08-SP)*3
Sequ
ence
CPU
Blo
ck
Self-diagnostics Memory error, CPU error, input/output error, syntax check, etc.
<<Content>> <<Index>> 11
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Item Specification
Other features
Configuration function (device capacity, data lock-up range at power failure, output when CPU stops, etc.) Constant scan function (1 ms to 190 ms) Debugging functions (forced SET/RESET, online edit, scan operation, etc.) Error history function (64 records) Date/clock function (year/month/day/hour/minute/second/day of week) Program protect functions ROM programming and data storage Personal computer link function
Sequ
ence
CPU
Blo
ck
Current consumption 350 mA (5 V DC)*2 External dimensions 58 (W) 100 (H) 83.2 (D) mm Weight 320 g
UL UL508 approved, File No.E188707 (Overvoltage Category*5 II, Pollution Degree*6 2)
EMC Directive
EN 61326-1 Class A, Table 2 (For use in industrial locations) EN 61326-2-3*7 EN 55011 Class A, Group 1 EN 61000-6-2, EN 61000-3-2, EN 61000-3-3 compliance CE
Low Voltage Directive
EN 61010-1 compliance (only for F3SC23-) (Overvoltage Category*5 II, Pollution Degree*6 2)
Sequence CPU module*1 (F3SP08-0P, F3SP08-SP)*3
Com
mon
Compli- ance with safety and EMC stan- dards*4
C-Tick EMC Frame-work EN 55011 Class A, Group 1 compliance
*1: When a sequence CPU module is to be used, use the FA-M3 programming Tool WideField Rev. 2.06 or later. *2: The total current dissipated by the modules in slots 2 to 4 must be less than 1600 mA. *3: F3SP08-0P and F3SP08-SP have exactly the same dimensions, internal circuitry and other characteristics, except that F3SP08-0P uses
M3.5-screw terminals while F3SP08-SP uses M4-screw terminals. F3SP08-SP is compliant to IEC61010-1 and EN61010-1, but F3SP08-0P is not.
*4 For details on conforming modules, see “UL-approved, CE marking and C-Tick mark-compliant Modules” (GS 34M06C11-21E) general specification brochure.
*5: The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four categories. Overvoltage Category II applies to systems with rated voltage of 220/230/240V and applies to electrical appliances, portable devices, etc.
*6: The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a reduction of dielectric strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by condensation is to be expected.
*7: EN 61326-2-3 is applicable only to F3CU04-0S and F3CU04-1S
F3SC22-1F, F3SC23-1F Operating Voltage/
Current Input Response Time Model Input Type Number of Points
Isolation Method
Rated Input Voltage
Rated Input Current
ON OFF OFF→ON ON→OFF
External Connection
Number of Points/
Common
DC Voltage 16 24V DC 4.1mA/point 16V DC min. 3.2mA min.
5.8V DC max.
0.9mA max.
Configu -rable as
2.0ms max. or 17ms
Configu -rable as
3.5ms max. or 18.5ms
40-pin connector
8 points/ common
Output Response Time Output Type
Number of Points
Rated Load Voltage
Maximum Load Current
OFF→ON OFF→ON Surge
Protector External Power Supply
External Connection
Number of Points/
Common
HOLD/REST Output When
Program Stops
F3WD32-3F
Transistor contact
(sink type) 16
Photocoupler isolation
24V DC 0.1A/point 0.8A/common 1ms max. 1ms max. Zener
diode 24V DC 30mA
40-pin connector
8 points/ common
Default: RESET Configurable on module basis.*
* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).
F3SC22-2F, F3SC23-2F Operating Voltage/
Current Input Response Time Model Input Type Number of Points
Isolation Method
Rated Input Voltage
Rated Input Current
ON OFF OFF→ON ON→OFF
External Connection
Number of Points/
Common
DC Voltage 32 24V DC 4.1mA/point 16V DC min. 3.2mA min.
5.8V DC max.
0.9mA max. 1.0ms max. 2.5ms max. 40-pin
connector 8 points/ common
Output Response Time Output Type Number of Points
Rated Load Voltage
Maximum Load Current
OFF→ON OFF→ON
Surge Protector
External Power Supply
External Connection
Number of Points/
Common
HOLD/REST Output When
Program Stops F3WD64-3F
Transistor contact
(sink type) 32
Photocoupler isolation
24V DC 0.1A/point 0.4A/common 1ms max 1ms max Zener
diode 24V DC 60mA
40-pin connector
8 points/ common
Default: RESET Configurable on module basis.*
* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).
<<Content>> <<Index>> 12
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
F3SC22-1A, F3SC23-1A Operating Voltage/
Current Input Response Time Model Input Type Number of Points
Isolation Method
Rated Input Voltage
Rated Input Current
ON OFF OFF→ON ON→OFF External
Connection Number of Points/ Common
F3XD16-3F DC Voltage (sink/source
type) 16 Photocoupler
isolation 24V DC 4.1mA/ point 24V DC
16V DC min. 3.2mA min.
5.8V DC max.
0.9mA max.
Configu -rable as
2.0ms max. or 17ms
Configu -rable as
3.5ms max. or 18.5ms
18-point terminal
block M3.5 screw
8 points/ Common
Output Response Time Model Output Type
Number of Points
Isolation Method
Rated Input Voltage
Maximum Load
Current OFF→ON ON→OFF
Surge Protector
External Power Supply
External Connection
Number of Points/
Common
HOLD/REST Output When
Program Stops)
F3YD14-5A Transistor Contact
(sink type) 14 Photocoupler
isolation 12-24V DC 0.5A/point 2A/common 1ms max. 1ms max. Zener
diode
18-point terminal
block M3.5 screw
12-24V DC 20mA
8 points/ common 6 points/ common
Default: RESET Configurable on module basis.*
* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).
F3SC23-2P, F3SC23-6P Operating Voltage/
Current Input Response Time Model Input Type Number of Points
Isolation Method
Rated Input Voltage
Rated Input Current ON OFF OFF→ON ON→OFF
External Connection
Number of Points/
Common
DC Voltage 32 24 V DC 4.1mA/point 16VDC min.
3.2mA min. 5.8VDC max.,
0.9mA max. 1.0ms max. 2.5ms max. 40-pin
connector 8 points/ common
Output Response Time Output Type
Number of Points
Rated Load Voltage
Maximum Load Current OFF→ON OFF→ON
Surge Protector
External Power Supply
External Connection
Number of Points/
Common
HOLD/REST Output When
Program Stops) F3WD64-3P
Transistor contact
(sink type) 32
Photocoupler isolation
24 V DC 0.1A/point 0.4A/common 1ms max. 1ms max. Active
clamp 24V DC 55mA
40-pin Connector
8 points/ common
Default: RESET Configurable on module basis.*
Operating Voltage/
Current Input Response Time Model Input Type Number of Points
Isolation Method
Rated Input Voltage
Rated Input Current ON OFF OFF→ON ON→OFF
External Connection
Number of Points/
Common
DC Voltage 32 12 V DC 4.1mA/point 8V DC min.
2.6mA min. 3.4V DC
max., 1.0mA max.
1.0ms max. 2.5ms max. 40-pin connector
8 points/ common
Output Response Time Output Type
Number of Points
Rated Load Voltage
Maximum Load Current OFF→ON OFF→ON
Surge Protector
External Power Supply
External Connection
Number of Points/
Common
HOLD/REST Output When
Program Stops) F3WD64-4P
Transistor contact
(sink type) 32
Photocoupler isolation
12 V DC 0.1A/point 0.4A/common 1ms max. 1ms max. Active
clamp 12V DC 55mA
40-pin Connector
8 points/ common
Default: RESET Configurable on module basis.*
* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).
Base Module Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3BU04 -0N · · · · · · · · · · · · 4 slots (excluding slots for power supply)
External Dimensions
4 slots (F3BU04-0N)
O5 mounting hole
9.6
4.5 7.5
85 100
10.588.5
138147
(When mounted on module surface)
(for M4 mountingscrew)
Unit: mm
<<Content>> <<Index>> 13
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Sequence CPU Module
Components and Functions
Between FAIL1 and COMBetween FAIL2 and COM
OpenShort
ShortOpen
During Normal operation
During System and Power Failures
Fail-signal contact outputContact ratings: 24 V DC, 0.3 A
Subject to JIS class 3 grounding independently.
Subject to JIS class 3 grounding independently for increased noise immunity.
100-240 VAC
Lit when the power supply is normal.
FG
LG
Power supply
CPU module maintenance LEDs
Programming tool interface connector
FAIL1
COM
FAIL2
FG
LG
N
L
FAILOUTPUT
INPUT 100-240 V AC
RDY
SP05-0P CPU
RDYRUNALMERR
PROGRAMMER
Terminal Dimensions F3SP08-0P
8.2 mm7.1 mm
M3.5
Unit: mmF3SP08-SP
8.2 mm7.1 mm
M4
Examples of Applicable Solderless Terminals Applicable
Crimping Torque Vender Model Applicable Conductor
F3SP08-0P F3SP08-SP Japan Solderless Terminal Mfg. Co., Ltd.
V1.25-M3
Nippon Tanshi Co., Ltd. RAV1.25-3.5
Not available
Japan Solderless Terminal Mfg. Co., Ltd.
V1.25-M4
AWG22 to 18 (0.33 to 0.82mm2) (Copper wire)
Japan Solderless Terminal Mfg. Co., Ltd.
V2-M4 AWG16 to 14 (1.25 to 2.0mm2) (Copper wire)
0.8 N • m
1.2 N • m
CPU Error Processing Different levels of errors are identified by different LEDs on the front panel of the CPU module.
LED Meaning
RDY (READY) Green
Major failure (when off): The core hardware cannot run. Example: CPU error Memory error
RUN (RUN) Green When lit: The user program is running.
ALM (ALARM) Yellow
Minor failure (when lit): The user program can still run in spite of a failure. Example: Power failure Communication error
ERR (ERROR) Red
Moderate failure (when lit): The user program cannot start or continue execution. Example: Program error* I/O comparison error* I/O module error* Memory error Sequence processor error Instruction processing error* Scan timeout*
*: Minor or moderate error can be selected in the configuration settings.
<<Content>> <<Index>> 14
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
-1F · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M3.5 screws), sequence CPU, and DI/O (F3WD32-3F) modules)
-2F · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M3.5 screws), sequence CPU, and DI/O (F3WD64-3F) modules)
F3SC22
-1A · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M3.5 screws), sequence CPU, and DI/O (F3XD16-3F, F3YD14-5A) modules)
F3SP08 -0P · · · · · · · · · · · · Sequence CPU Module (with power supply (M3.5 screws) and memory), memory: 10K steps
External Dimensions
83.2 582
100
Unit: mm
Model Suffix Code
Style Code
Option Code Description
-1F · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD32-3F) modules)
-2F · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD64-3F) modules)
-1A · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3XD16-3F, F3YD14-5A) modules)
-2P · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD64-3P) modules)
F3SC23
-6P · · · · · · · · · · · ·
FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD64-4P) modules)
F3SP08 SP · · · · · · · · · · · · Sequence CPU Module (with power supply (M4 screws) and memory), memory: 10K steps
<<Content>> <<Index>> 15
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3XD16-3F)
Internal Circuit Diagram F3XD16-3F (DC input module)
Businterface
Inte
rnal
bus
1
8
9
~
COM
+
+
External Connection Diagram
1
3
5
7
9
11
13
15
17
12345678
COM1
2
4
6
8
10
12
14
16
18
+
+
910111213141516
COM2
+
+
F3XD16-3F (DC input module)
Note: Viewed from the front of the module.
External Connections Terminal Block
Applicable conductor 0.33 to 0.82 mm2
Method of connection Solderless
Temperature rating 75°C min.
Material Copper Solderless terminal For 3.5 mm screws
Crimping torque 0.8 N • m
Solderless terminal
Applicable solderless terminal
e.g.: Japan Solderless Terminal Mfg.Co.,Ltd. V1.25-M3 V1.25-M4 V2-M4 Nippon Tanshi Co., Ltd RAV1.25-3.5
Operating Environment There is no restriction on the type of CPU modules that can be used with this module.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3XD16 -3F · · · · · · · · · · · · DC input (sink/source type) 24 V DC, 16 points
External Dimensions
Unit:
F3XD16-3F
mm
<<Content>> <<Index>> 16
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3YD14-5A)
Internal Circuit Diagram
1
8
10
9 COM
F3YD14-5A (Transistor Output Module)
~
L
L+
Businterface
Inte
rnal
bus
External Connection Diagram
F3YD14-5A (Transistor Output Module)
1
3
5
7
9
11
13
15
17
12345678
COM11224V
2
4
6
8
10
12
14
16
18
+
LLLLLLLL
91011121314
COM21224V
+
LLLLLL
Note: Viewed from the front of the module.
External Connections Terminal Block
Applicable conductor 0.33 to 0.82 mm2
Method of connection Solderless
Temperatule rating 75°C min.
Material Copper Solderless terminal For 3.5 mm screws
Crimping torque 0.8 N·m
Solderless terminal
Applicable solderless terminal
ex: Japan Solderless Terminal Mfg.Co.,Ltd. V1.25-M3 V1.25-M4 V2-M4 Nippon Tanshi Co., Ltd RAV1.25-3.5
Operating Environment There is no restriction on the type of CPU modules that can be used with this module.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3YD14 -5A · · · · · · · · · · · · TR output sink type 12-24 V DC, 0.5A, 14 points
External Dimensions
Unit:
F3YD14-5A
mm
<<Content>> <<Index>> 17
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3WD32-3F)
Internal Circuit Diagram
External Connection Diagram
+
LLLLLLLL
24V
+
24V
LLLLLLLL
COM43231302928272625
COM216151413121110 9
COM32423222120191817
COM1 8 7 6 5 4 3 2 1
-
+
+
-
+
-
-
+
2019181716151413121110987654321
2019181716151413121110987654321
B A
Note: Viewed from the front of the module.
External Connections Connector Type
Wire connection method Soldered
Applicable wire size AWG23 max. (0.26 mm2 max.)
Applicable External Connectors Connection Method Applicable Connector
Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover
Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover
Solderless type Fujitsu FCN-367J040-AU / F
Operating Environment This module can be used with the following CPU modules: F3SP08-0P and F3SP08-SP
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3WD32 -3F · · · · · · · · · · · · 24 V DC input/output
Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.
External Dimensions F3WD32-3F
Unit: mm
<<Content>> <<Index>> 18
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3WD64-3F)
Internal Circuit Diagram
8
10
9
_
+
+
_
+89
Bus interface
Display selector OUT
IN
1
COM
L
L
COM
~
1
~
Inte
rnal
bus
External Connection Diagram
+
24V
COM46463626160595857
COM24847464544434241
+
COM35655545352515049
COM14039383736353433
2019181716151413121110987654321
2019181716151413121110987654321
B A
LLLLLLLL
24V
LLLLLLLL
+
+
24V
LLLLLLLL
LLLLLLLL
24V
CN2 (Output block)
COM43231302928272625
COM216151413121110 9
+
+
+
+
COM32423222120191817
COM1 8 7 6 5 4 3 2 1
+
+
+
+
2019181716151413121110987654321
2019181716151413121110987654321
B ACN1 (Input block)
Note: Viewed from the front of the module.
External Connections Connector Type
Wire connection method Soldered
Applicable wire size AWG23 max. (0.26 mm2 max.)
Applicable External Connectors Connection Method Applicable Connector
Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover
Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover
Solderless type Fujitsu FCN-367J040-AU / F
Operating Environment There is no restriction on the type of CPU modules that can be used with this module.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3WD64 -3F · · · · · · · · · · · · 24 V DC input/output
Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.
External Dimensions F3WD64-3F
Unit: mm
<<Content>> <<Index>> 19
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3WD64-3P)
Internal Circuit Diagram
Inte
rnal
bus ~
~
External Connection Diagram
COM4
32
31
30
29
28
27
26
25
COM2
16
15
14
13
12
11
10
9
-
+
+
-
COM3
24
23
22
21
20
19
18
17
COM1
8
7
6
5
4
3
2
1
-
+
+
-
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
B ACN1 (Input block)
+
24V
COM8
64
63
62
61
60
59
58
57
COM6
48
47
46
45
44
43
42
41
+
COM7
56
55
54
53
52
51
50
49
COM5
40
39
38
37
36
35
34
33
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
B A
L L L L L L L L
24V
L L L L L L L L
+
+
24V
L L L L L L L L
L L L L L L L L
24V
CN2 (Output block)
Note: Viewed from the front of the module.
External Connections Connector Type
Wire connection method Soldered
Applicable wire size AWG23 max. (0.26 mm2 max.)
Applicable External Connectors Connection Method Applicable Connector
Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover
Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover
Solderless type Fujitsu FCN-367J040-AU / F
Operating Environment There is no restriction on the type of CPU modules that can be used with this module.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3WD64 -3P · · · · · · · · · · · · 24 V DC input/output (with short-circuit protector)
Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.
External Dimensions F3WD64-3P
Unit: mm
<<Content>> <<Index>> 20
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00
I/O Module (F3WD64-4P)
Internal Circuit Diagram
8
10
9 COM
COM
-
+ -+
89
OUT
IN
1 L
L
1
Overheat protectorOvercurrent protector
Constantvoltage circuit
BusInterface
Displayselector
-
+
External Connection Diagram
COM4
32
31
30
29
28
27
26
25
COM2
16
15
14
13
12
11
10
9
COM3
24
23
22
21
20
19
18
17
COM1
8
7
6
5
4
3
2
1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
B ACN1 (Input block)
12V
COM8
64
63
62
61
60
59
58
57
COM6
48
47
46
45
44
43
42
41
COM7
56
55
54
53
52
51
50
49
COM5
40
39
38
37
36
35
34
33
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
B A
L L L L L L L L
12V
L L L L L L L L
12V
L L L L L L L L
L L L L L L L L
12V
CN2 (Output block)
Note: Viewed from the front of the module.
External Connections Connector Type
Wire connection method Soldered
Applicable wire size AWG23 max. (0.26 mm2 max.)
Applicable External Connectors Connection Method Applicable Connector
Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover
Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover
Solderless type Fujitsu FCN-367J040-AU / F
Operating Environment There is no restriction on the type of CPU modules that can be used with this module.
Model and Suffix Codes
Model Suffix Code
Style Code
Option Code Description
F3WD64 -4P · · · · · · · · · · · · 12 V DC input/output (with short-circuit protector)
Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.
External Dimensions F3WD64-4P
Unit: mm
top related