ee4503 electrical systems design

Post on 22-Feb-2016

68 Views

Category:

Documents

1 Downloads

Preview:

Click to see full reader

DESCRIPTION

EE4503 Electrical Systems Design. Branch circuit and Feeder (Lighting and Appliances). Topics. Characteristics of Loads Circuits Design Branch Circuit Feeder Circuit Load Schedule. Characteristics of Loads. Continuous Load - PowerPoint PPT Presentation

TRANSCRIPT

Assumption University Thailand

EE4503Electrical Systems Design

Branch circuit and Feeder (Lighting and Appliances)

1

Assumption University Thailand

Topics

• Characteristics of Loads

• Circuits Design

• Branch Circuit

• Feeder Circuit

• Load Schedule

2

Assumption University Thailand

Characteristics of Loads

3

• Continuous Load– More than 3 hrs. of continuous usage e.g.

lighting, air condition

• Non-continuous Load:– Less than 3 hrs. of continuous usage e.g.

electric oven, microwave

When not sure, add 25% more

Assumption University Thailand

Characteristics of LoadsDefinition

4

• Total Connected Load: total kVA or MVA listed

• Maximum Demand: the maximum kVA or MVA used at the same time

Assumption University Thailand

Characteristics of LoadsDefinition

5

• Demand Factor (D.F.): ratio of “Maximum Demand” to “Total Connected Load” ()

• Diversity Factor: summation of every branched circuits’ maximum demand to the system’s maximum demand (always greater than or equal to 1.0)

Assumption University Thailand

Characteristics of LoadsDefinition

6

• Peak Load (P): the maximum kVA or MVA at the given periond (e.g. 15 min)

• Load Factor (L.F.): ratio of “Average Load” to the “Peak Load” (). is total energy for period of time

Assumption University Thailand

Characteristics of LoadsCommon Load

7

• Lighting: about 20-50% of total load or 20-100VA/m2

• Receptacle: if no specific information, 180-200VA/set (1, 2 or 3 outlets)

• HVAC: 1TR (12,000 BTU) is about 1.5-1.8kVA

• Motor

• Escalator: manufacturer’s specification

Assumption University Thailand

GroundingCommon Load - Lighting

8

http://www.g-w.com/pdf/sampchap/9781605255880_ch12.pdf

Assumption University Thailand

GroundingCommon Load - Escalator

9

http://www.elevatorbooks.com/Content/Site108/ProductContent/April2012Articl_00000012203.pdf

Assumption University Thailand

Circuit Design

10

• Branch Circuit

• Feeder Circuit

• Main Circuit

Assumption University Thailand

Branch Circuit

11

• Connect from a distribution panel to load or receptacle

• Lighting or Appliance Branch Circuit– Lighting Branch Circuit

– Receptacle Branch Circuit

– Lighting & Receptacle Branch Circuit

– Individual Branch Circuit

Assumption University Thailand

Branch CircuitCalculation

12

• Load of a branch circuit (BC) at least the total load connected to that branch.

• Conductor Sizing Current Rating of CB

• Current Rating of CB Maximum Load

• Size of a BC goes by the current rating of CB: 15(16)A, 20A, 25A, 30(32)A, 40A, 50A, 63A

Assumption University Thailand

Branch CircuitDesign Procedure

13

• Find “Load”

• Calculate “Circuit Breaker” (% of BC)

• Calculate “Cable”

• Verify “Voltage Drop”: 1-2% of rated voltage

?? safety factor ??

Assumption University Thailand

Branch CircuitDesign Recommendations

14

• Lighting Circuit: continuous load– 50-70% of BC (no more than 80%) or

allowance of 10-30%

• Individual Branch Circuit: load is known– Should be no more than 80% of BC

Assumption University Thailand

Branch CircuitDesign Recommendations

15

• Receptacles Circuit: single, duplex, triplex– 180VA per set (200VA for ease)

• Individual Circuit with ELCB: heater, Jacuzzi

• Receptacles Circuit with ELCB: toilet, kitchen, basement, outdoor, < 1.5m from water

?? Some recommendations can be relaxed ??

Assumption University Thailand

Branch CircuitDesign Recommendations

16

• Separate the type of load: lighting on one BC

• Future Load:– 20% spare at least

– 40% if continuous load

• Cable size is no smaller than 2.5mm2

• BC for receptacles contains less than 10 sets

Assumption University Thailand

Branch CircuitDrawing

17

• # of hash marks is # of cables

• No hash mark means 2 cables

• One hash mark + number is the number of cables

• Arrow + Lx is connected to circuit breaker (phase) #x

Assumption University Thailand

Branch CircuitPanelboard

18

• No more than 42 circuit

• No longer than 50 m

• Easy to access (no higher than 1.8m)

• Rated is more than the rated of the cable

• At least one panel board per floor

• Must have protection equipment (CB)

Assumption University Thailand

Branch CircuitPanelboard

19

• Should be in the center: balance the voltage drop

• Should be close to the incoming: shortest feeder

• Three types– Active Branch Circuit (60-80%)

– Spare Branch Circuit with CB (10-20%)

– Spare Branch Circuit (10-20%)

Assumption University Thailand

Branch CircuitFeeder

20

• Rated current of feeder is the total load deducted by the “demand factor”

• Feeder Cable Rating of CB

• Rating of CB Feeder’s Rated Current

Assumption University Thailand

Branch CircuitFeeder – Demand Factor

21

• Demand Factor is the ratio of the maximum usage power at any certain time to the total connected load.

• There are tables for the demand factor, e.g. receptacles in kitchen, lighting. If not specify, 0.8 is a good number

Assumption University Thailand

Branch CircuitFeeder – Neutral

22

• In single phase system, neutral cable will be the same size and line cable.

• In three phase, neutral cable can be reduced.– Less than 200A, use the phase current

– More than 300A• Without Harmonics, • With Harmonics, use the phase current

Assumption University Thailand

Branch CircuitFeeder - Design Procedure

23

• Sum up total BCs’ load

• Calculate “Circuit Breaker”

• Calculate “Cable”: Phase then Neutral

• Verify “Voltage Drop”: 1-2% of rated voltage

Assumption University Thailand

Branch CircuitLoad Schedule

24

• List of connected load

• CB number start from 1(A), 3(B), 5(C), 2(A), 4(B), 6(C) then 7(A), 9(B), 11(C), 8(A), 10(B), 12(C)

• Consider the balance of load in all phases (less than 20% is recommended)

Assumption University Thailand

Branch CircuitLoad Schedule – Design Recommendation

25

• Load Calculation– Non-continuous Load, no multiplier

– Continuous Load, 1.25 multiplier (or more in case of future expansion)

– If not sure, treat as continuous load.

• Then choose the circuit breaker

• Then choose the cable

Assumption University Thailand

Branch Circuit & FeederDesign Procedure

26

• Make the Load Schedule– Design Branch Circuit

• Design Feeder (from the load schedule)

Assumption University Thailand

Branch Circuit & FeederDesign Examples

27

Assumption University Thailand

Branch Circuit & FeederDesign Examples

28

Assumption University Thailand

Branch Circuit & Feeder!! 25% margin !!

29

• If we are not sure of the load value, add extra 25%.

• After the load, when we choose the CB, add extra 25% (for the case there are some change in voltage/load/etc.)

Assumption University Thailand

Branch Circuit & Feeder!! CB for “motor” load !!

30

• CB is 250% bigger in rated.

• Cable is 125% bigger in rated.

Assumption University Thailand

• Electrical Systems Design: ประสทิธิ ์พทิยพฒัน์

Reference

31

top related