ee4503 electrical systems design

31
Assumption University Thailand EE4503 Electrical Systems Design Branch circuit and Feeder (Lighting and Appliances) 1

Upload: dennis

Post on 22-Feb-2016

67 views

Category:

Documents


1 download

DESCRIPTION

EE4503 Electrical Systems Design. Branch circuit and Feeder (Lighting and Appliances). Topics. Characteristics of Loads Circuits Design Branch Circuit Feeder Circuit Load Schedule. Characteristics of Loads. Continuous Load - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: EE4503 Electrical Systems Design

Assumption University Thailand

EE4503Electrical Systems Design

Branch circuit and Feeder (Lighting and Appliances)

1

Page 2: EE4503 Electrical Systems Design

Assumption University Thailand

Topics

• Characteristics of Loads

• Circuits Design

• Branch Circuit

• Feeder Circuit

• Load Schedule

2

Page 3: EE4503 Electrical Systems Design

Assumption University Thailand

Characteristics of Loads

3

• Continuous Load– More than 3 hrs. of continuous usage e.g.

lighting, air condition

• Non-continuous Load:– Less than 3 hrs. of continuous usage e.g.

electric oven, microwave

When not sure, add 25% more

Page 4: EE4503 Electrical Systems Design

Assumption University Thailand

Characteristics of LoadsDefinition

4

• Total Connected Load: total kVA or MVA listed

• Maximum Demand: the maximum kVA or MVA used at the same time

Page 5: EE4503 Electrical Systems Design

Assumption University Thailand

Characteristics of LoadsDefinition

5

• Demand Factor (D.F.): ratio of “Maximum Demand” to “Total Connected Load” ()

• Diversity Factor: summation of every branched circuits’ maximum demand to the system’s maximum demand (always greater than or equal to 1.0)

Page 6: EE4503 Electrical Systems Design

Assumption University Thailand

Characteristics of LoadsDefinition

6

• Peak Load (P): the maximum kVA or MVA at the given periond (e.g. 15 min)

• Load Factor (L.F.): ratio of “Average Load” to the “Peak Load” (). is total energy for period of time

Page 7: EE4503 Electrical Systems Design

Assumption University Thailand

Characteristics of LoadsCommon Load

7

• Lighting: about 20-50% of total load or 20-100VA/m2

• Receptacle: if no specific information, 180-200VA/set (1, 2 or 3 outlets)

• HVAC: 1TR (12,000 BTU) is about 1.5-1.8kVA

• Motor

• Escalator: manufacturer’s specification

Page 8: EE4503 Electrical Systems Design

Assumption University Thailand

GroundingCommon Load - Lighting

8

http://www.g-w.com/pdf/sampchap/9781605255880_ch12.pdf

Page 9: EE4503 Electrical Systems Design

Assumption University Thailand

GroundingCommon Load - Escalator

9

http://www.elevatorbooks.com/Content/Site108/ProductContent/April2012Articl_00000012203.pdf

Page 10: EE4503 Electrical Systems Design

Assumption University Thailand

Circuit Design

10

• Branch Circuit

• Feeder Circuit

• Main Circuit

Page 11: EE4503 Electrical Systems Design

Assumption University Thailand

Branch Circuit

11

• Connect from a distribution panel to load or receptacle

• Lighting or Appliance Branch Circuit– Lighting Branch Circuit

– Receptacle Branch Circuit

– Lighting & Receptacle Branch Circuit

– Individual Branch Circuit

Page 12: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitCalculation

12

• Load of a branch circuit (BC) at least the total load connected to that branch.

• Conductor Sizing Current Rating of CB

• Current Rating of CB Maximum Load

• Size of a BC goes by the current rating of CB: 15(16)A, 20A, 25A, 30(32)A, 40A, 50A, 63A

Page 13: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitDesign Procedure

13

• Find “Load”

• Calculate “Circuit Breaker” (% of BC)

• Calculate “Cable”

• Verify “Voltage Drop”: 1-2% of rated voltage

?? safety factor ??

Page 14: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitDesign Recommendations

14

• Lighting Circuit: continuous load– 50-70% of BC (no more than 80%) or

allowance of 10-30%

• Individual Branch Circuit: load is known– Should be no more than 80% of BC

Page 15: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitDesign Recommendations

15

• Receptacles Circuit: single, duplex, triplex– 180VA per set (200VA for ease)

• Individual Circuit with ELCB: heater, Jacuzzi

• Receptacles Circuit with ELCB: toilet, kitchen, basement, outdoor, < 1.5m from water

?? Some recommendations can be relaxed ??

Page 16: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitDesign Recommendations

16

• Separate the type of load: lighting on one BC

• Future Load:– 20% spare at least

– 40% if continuous load

• Cable size is no smaller than 2.5mm2

• BC for receptacles contains less than 10 sets

Page 17: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitDrawing

17

• # of hash marks is # of cables

• No hash mark means 2 cables

• One hash mark + number is the number of cables

• Arrow + Lx is connected to circuit breaker (phase) #x

Page 18: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitPanelboard

18

• No more than 42 circuit

• No longer than 50 m

• Easy to access (no higher than 1.8m)

• Rated is more than the rated of the cable

• At least one panel board per floor

• Must have protection equipment (CB)

Page 19: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitPanelboard

19

• Should be in the center: balance the voltage drop

• Should be close to the incoming: shortest feeder

• Three types– Active Branch Circuit (60-80%)

– Spare Branch Circuit with CB (10-20%)

– Spare Branch Circuit (10-20%)

Page 20: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitFeeder

20

• Rated current of feeder is the total load deducted by the “demand factor”

• Feeder Cable Rating of CB

• Rating of CB Feeder’s Rated Current

Page 21: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitFeeder – Demand Factor

21

• Demand Factor is the ratio of the maximum usage power at any certain time to the total connected load.

• There are tables for the demand factor, e.g. receptacles in kitchen, lighting. If not specify, 0.8 is a good number

Page 22: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitFeeder – Neutral

22

• In single phase system, neutral cable will be the same size and line cable.

• In three phase, neutral cable can be reduced.– Less than 200A, use the phase current

– More than 300A• Without Harmonics, • With Harmonics, use the phase current

Page 23: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitFeeder - Design Procedure

23

• Sum up total BCs’ load

• Calculate “Circuit Breaker”

• Calculate “Cable”: Phase then Neutral

• Verify “Voltage Drop”: 1-2% of rated voltage

Page 24: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitLoad Schedule

24

• List of connected load

• CB number start from 1(A), 3(B), 5(C), 2(A), 4(B), 6(C) then 7(A), 9(B), 11(C), 8(A), 10(B), 12(C)

• Consider the balance of load in all phases (less than 20% is recommended)

Page 25: EE4503 Electrical Systems Design

Assumption University Thailand

Branch CircuitLoad Schedule – Design Recommendation

25

• Load Calculation– Non-continuous Load, no multiplier

– Continuous Load, 1.25 multiplier (or more in case of future expansion)

– If not sure, treat as continuous load.

• Then choose the circuit breaker

• Then choose the cable

Page 26: EE4503 Electrical Systems Design

Assumption University Thailand

Branch Circuit & FeederDesign Procedure

26

• Make the Load Schedule– Design Branch Circuit

• Design Feeder (from the load schedule)

Page 27: EE4503 Electrical Systems Design

Assumption University Thailand

Branch Circuit & FeederDesign Examples

27

Page 28: EE4503 Electrical Systems Design

Assumption University Thailand

Branch Circuit & FeederDesign Examples

28

Page 29: EE4503 Electrical Systems Design

Assumption University Thailand

Branch Circuit & Feeder!! 25% margin !!

29

• If we are not sure of the load value, add extra 25%.

• After the load, when we choose the CB, add extra 25% (for the case there are some change in voltage/load/etc.)

Page 30: EE4503 Electrical Systems Design

Assumption University Thailand

Branch Circuit & Feeder!! CB for “motor” load !!

30

• CB is 250% bigger in rated.

• Cable is 125% bigger in rated.

Page 31: EE4503 Electrical Systems Design

Assumption University Thailand

• Electrical Systems Design: ประสทิธิ ์พทิยพฒัน์

Reference

31