DURING THIS COURSE WE WILL TRY TO COVER THE FOLLOWING TOPICS:• GENERAL OVERVIEW OF DELTA-V SYSTEM
• HARDWARE INSTALLATION
• SOFTWARE CONFIGURATION
• OPERATOR BASICS AND GRAPHICS CONFIGURATION
• SYSTEM ADMINISTRATION & MAINTENANCE
• DATABASE ADMINISTRATOR
THE DELTA-V SYSTEM
DELTA-V SYSTEM CONSISTS OF THE FOLLOWING COMPONENTS:
• I/O SUBSYSTEM
• CONTROLLER
• POWER SUPPLIES
• WORKSTATION
• CONTROL NETWORK
SYSTEM ARCHITECTURE (MULTIPLE NODES)
THE ABOVE FIGURE ILLUSTRATES A DELTA-V CONTROL NETWORK WITH EIGHT NODES
MAXIMUMS:
120 --- NODES100 --- CONTROLLERS / SIMPLEX OR REDUNDANT PAIRS 60 --- WORKSTATIONS
I/O SUBSYSTEM(CARRIER SPECIFICATIONS)
DELTA-V SYSTEM CONTAINS FOLLOWING TYPES OF CARRIERS:• HORIZONTAL CARRIER
2-Wide Horizontal Power/Controller Carrier 2-Wide Horizontal Power Carrier 8-Wide Horizontal I/O Interface Carrier 1-Wide Horizontal Carrier Extenders and
• VERTICALPLUS CARRIERS 4-Wide VerticalPLUS Power/Controller Carrier 4-Wide VerticalPLUS Power Carrier 8-Wide VerticalPLUS I/O Interface Carriers 1-Wide VerticalPLUS Carrier Extenders
I/O SUBSYSTEM(I/O CARDS)
A VARIETY OF I/O CARDS ARE AVAILABLE IN SERIES 2 e.g.• AI, 8-CHANNEL, 4-20 MA (SERIES 2 SIMPLEX)• AI, 4-20 MA, HART (SERIES 2 SIMPLEX AND REDUNDANT; 2
AND 4 WIRE)• AI, 16, CHANNEL, 4-20 MA, HART (SERIES 2 SIMPLEX)• AO, 8-CHANNEL, 4-20 MA, HART (SERIES 2 SIMPLEX AND
REDUNDANT)• DI, 8-CHANNEL, 24 VDC, DRY CONTACT (SERIES 2 SIMPLEX
AND REDUNDANT)• DI, 8-CHANNEL, 24 VDC, ISOLATED (SERIES 2 SIMPLEX)
I/O SUBSYSTEM(MASS TERMINATION BLOCKS)
THE DELTA-V SYSTEM CAN USE FOLLOWING TYPES OF MASS TERMINATION BLOCKS:
• 10-Pin Mass Termination Block
• 16-Pin Mass Termination Block
• 24-Pin Mass Termination Block
• 40-Pin Mass Termination Block
I/O SUBSYSTEM(I/O INTERFACE KEYING)
THERE ARE TWO KEYS ON I/O CARD & TWO KEYS ON THE I/O TERMINAL BLOCK
THE KEYS ON THE I/O CARD ARE SET AT THE FACTORY, BUT KEYS ON THE I/O TERMINAL BLOCK CAN BE CHANGED
CONTROLLER SPECIFICATIONSITEM MD/MD PLUS MX
Power requirement (supplied bysystem power supply through 2-widepower/controller carrier)
+5 VDC at 1.4 A maximum
+5 VDC at 1.4 A maximum
Fuse protection 3.0 A, non-replaceable fuses
3.0 A, non-replaceable fuses
Power dissipation 5.0 W typical7.0 W maximum
5.0 W typical7.0 W maximum
Mounting On right slot of power/controllerCarrier
On right slot of power/controllercarrier
SYSTEM POWER SUPPLY SPECIFICATIONS
IN DELTA-V SYSTEM THERE ARE FOLLOWING THREE POWER SUPPLIES:
• SYSTEM POWER SUPPLY (AC/DC)
• SYSTEM POWER SUPPLY (DUAL DC/DC)
• INTRINSICALLY SAFE SYSTEM POWER SUPPLY
WORKSTATION
EMERSON HAVE CLASSIFIED DIFFERENT WORKSTATIONS IN TERMS OF THEIR FUNCTIONALITY:• PROFESSIONAL PLUS• PROFESSIONAL PLUS AS REMOTE CLIENT SERVER• LOCAL PROFESSIONAL OPERATOR BASE MAINTENANCE• OPERATOR STATION AS REMOTE CLIENT SERVER• LOCAL APPLICATION STATION• REMOTE PROFESSIONAL OPERATOR BASE• REMOTE APPLIOCATION STATION (SATELLITE CONNECTION
ONLY)• SIMULATE FOR STAND ALONE WORKSTATION
CONTROL NETWORK
• THE CONTROL NETWORK IS AN ISOLATED ETHERNET LOCAL AREA NETWORK (LAN) THAT PROVIDES COMMUNICATION BETWEEN THE CONTROLLERS AND WORKSTATIONS
• THE CONTROL NETWORK IS DEDICATED TO THE DELTA-V SYSTEM. A SEPARATE ETHERNET INTERFACE IS PROVIDED VIA THE DELTA-V PROFESSIONAL PLUS AND APPLICATION STATION TO CONNECT THE DELTA-V SYSTEM TO A PLANT-WIDE LAN
SYSTEM CAPACITY
SYSTEM SIZING• 30,000 DSTS• UNLIMITED SCADA TAGS• 15,000 ADVANCED UNIT MANAGEMENT DSTS• 1 MAX. PROFESSIONAL PLUS STATION• 10 MAX. PROFESSIONAL STATIONS• 10 MAX. APPLICATION STATIONS• 59 MAX. OPERATOR STATIONS• 60 MAX. WORKSTATIONS OF ANY KIND• 5 MAX. REMOTE DATA SERVERS• 100 MAX. SIMPLEX CONTROLLERS
SYSTEM CAPACITY (CONT.)
SYSTEM SIZING• 100 MAX. REDUNDANT CONTROLLERS• 120 MAX. NODES EXCLUDING REDUNDANT NODES• 42 MAX. REMOTE WORKSTATIONS• 250 MAX PLANT AREAS (INCLUDING REMOTE ZONE AREAS)• 255 MODULES PER UNIT• 250 ALARM TYPES (CAN BE ADDED IF DESIRED)• 200 DELTA-V USER ACCOUNTS
DEVICE SIGNAL TAG (DST) LICENSING
DST licensing is based on the number of inputs and outputs as follows:• Analog Output • Analog Input • Discrete Output• Discrete Input
Generally speaking each instrument wired into a set of screw terminals will require 1 DST. When identifying the required DST licensing start with the P&ID and count the number and type of instruments.
DELTA-V SIMULATE SUITE
Delta-V Simulate lets you use all Delta-V software for training and development without purchasing duplicate system hardware.
• Allows you to configure the Delta-V software suite on a single PC or in a multi-node system.
• Allows you to test and execute your system configuration and OPC interfaces, execute batch and continuous control
• Allows you to easily coordinate and initialize control simulation and set control execution to be faster or slower than real time.
ASSET MANAGEMENT SOLUTION (AMS)The Delta-V / Asset Management Solution (AMS) provide the capability to configure, calibrate, monitor and troubleshoot intelligent field devices.The system provides the following capability: • Complete capturing of all current device data• Comparison/reconciliation• Device alert monitoring• Device template creation• Device signal tag and device tag search capability• Conventional I/O, HART and Fieldbus-based support• On-line help• Diagnostic add-on capability
ALARMS & EVENTSTHERE ARE FOUR ALARMS PRIORITIES AVAILABLE IN DELTA-V BUT NEW ALARM PRIORITY CAN BE ADDED.
• CRITICAL• WARNING• ADVISORY• LOG
NOTE: ALARMS WITH LOG PRIORITY WILL GENERATE AN EVENT IN THE EVENT SUMMARY RATHER THAN ALARM.
BUSSED FIELD POWER CONNECTOR
• DELTA-V I/O CARRIER IS INSTALLED ONTYPE T-DIN RAIL USING THE LATCHING SWITCH
• ON 2-WIDE POWER / CONTROLLERCARRIER 4 TERMINALS ARE PROVIDED FOR INPUT POWER i.e. FOR 12VDC & 24VDC
• ON EACH 8-WIDE I/O CARRIER TWOBUSSED FIELD POWER CONNECTORSARE PROVIDED FOR POWERING THE FIELD DEVICES
BEVELED KEYS
• BEVELED KEYS ARE SUPPLIEDWITH THE TWO-PART CONNECTOR ON THE HORIZONTAL AND VERTICAL CARRIER TO PREVENT DAMAGETO THE CARDS
BEVELED KEYS (CONT.)
• YOU CAN SETUP ANY STANDARD FOR THE KEYING SCHEME. A SAMPLE KEYING SCHEME IS SHOWN BELOW
DIN RAIL SPACING
SUGGESTED SPACING FOR DIN RAIL INSTALLATION ON MOUNTING SURFACE IS AS FOLLOWS:
• AN AREA 1.3 CM (0.5 IN.) WIDE, CENTERED 4.5 CM (1.75 IN.) FROM THE LEFT SIDE OF A 2 WIDE POWER/CONTROLLER CARRIER
• AN AREA 1.3 CM (0.5 IN.) WIDE, CENTERED 8.3 CM (3.25 IN.) FROM EITHER SIDE OF AN 8-WIDE I/O INTERFACE CARRIER
WINDOWS VERSION REQUIREMENT FOR DELTA-V
DELTA-V VERSION OPERATING SYSTEMV6 Windows NT Server 4.0 with SP6a
Windows NT Workstation 4.0 with SP6a
v7.1 Windows NT Server 4.0 with SP6a
Windows NT Workstation 4.0 with SP6a
v7.2 Windows Server 2003
Windows XP Professional SP1
v7.3 Windows Server 2003
Windows XP Professional SP1
WINDOWS VERSION REQUIREMENT FOR DELTA-V (CONT.)
DELTA-V VERSION OPERATING SYSTEMv7.4, v7.4.1 Windows Server 2003
Windows XP Professional SP1
v7.4.2 Windows Server 2003 SP1
Windows XP Professional SP2
v8.3 Windows Server 2003
Windows XP Professional SP2
v8.4.x Windows Server 2003
Windows XP Professional SP2
WINDOWS VERSION REQUIREMENT FOR DELTA-V (CONT.)
DELTA-V VERSION OPERATING SYSTEMv9.3 Windows Server 2003 SP1
Windows XP Professional SP2
v9.3.1 Windows Server 2003 SP2
Windows XP Professional SP2
v10.3 Windows Server 2003 Standard Edition with SP2 (32-bit)
Windows XP Professional with SP3 (32-bit) & Windows Vista Business Edition with SP1 (32-bit)
WINDOWS VERSION REQUIREMENT FOR DELTA-V (CONT.)
DELTA-V VERSION OPERATING SYSTEMv10.3.1 Windows Server 2003 Standard Edition
with SP2 (32-bit)
Windows XP Professional with SP3 (32-bit)Windows Vista Business Edition with SP2(32-bit) & Windows Vista Ultimate Edition with SP2 (32-bit)
V11.3 Windows Server 2008
Windows 7 (32-bit)
DELTA-V INSTALLATION
• INSERT THE DELTA-V SOFTWARE CD-ROM #1 IN TO THE CD-ROM DRIVE
• SELECT INSTALL DELTA-V V9.3 FROM THE SPLASH SCREEN OR OPEN WINDOWS EXPLORER, SELECT THE CD DRIVE AND BROWSE FOR SETUP.EXE ON THE ROOT DIRECTORY OF THE CD AND DOUBLE CLICK IT.
DELTA-V INSTALLATION (CONT.)
• SELECT OK WHEN PROMPTED TO INSTALL THE .NET FRAMEWORK 1.1. AFTER THE REBOOT LOG BACK ON AND CONTINUE WITH THE DELTA-V INSTALLATION
DELTA-V INSTALLATION (CONT.)
• SELECT NEXT FROM THE WELCOME BANNER• SELECT YES FROM THE LICENSE AGREEMENT DIALOG BOX• SELECT THE APPROPRIATE WORKSTATION TYPE FROM THE
LIST
DELTA-V INSTALLATION (CONT.)
• VERSION CONTROL IS ONLY SUPPORTED ON SERVER 2003 OPERATING SYSTEM BECAUSE OF SQL REQUIREMENT. SELECT YES TO PROCEED WITH THE INSTALLATION
DELTA-V WORKSTATION CONFIGURATION
• ONCE THE WORKSTATION IS REBOOTED THE DELTA-V WORKSTATION CONFIGURATION WILL AUTOMATICALLY START
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• AFTER REGALL/REGISTRY COMPLETES , DELTA-V WORKSTATION CONFIGURATION WILL START AUTOMATICALLY, SELECT NEXT TO BEGIN
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• A MESSAGE BOX ALLOWING YOU TO CONFIGURE SYSTEM PREFERENCES AT THIS TIME WILL APPEAR. CLICK YES
DELTA-V WORKSTATION CONFIGURATION (CONT)
• IN THE SYSTEMPREFERENCE DIALOGUESELECT THE OPTIONSYOU WANT TO ACCESS INYOU DELTA-V PROFESSIONAL PLUS
DELTA-V WORKSTATION CONFIGURATION (CONT.)
Important: When the configuration banner re-appears, the Workstation’s name will be filled in with the Node name entered during the Windows NT software installation. The PC’s node name should be changed from this screen and this screen only.Do not use the Delta-V Explorer or the network icon from the control panel to change the PC’s node name!
ProfessionalPLUS Workstation Name:EDCTRxImportant: DO NOT CHANGE the Workstation or Node name at this time.
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• SELECT REDUNDANT FOR THE NETWORK REDUNDANCY
• SELECT NEXT TO CONTINUE
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• THE FOLLOWING INFORMATION APPEARS
PRIMARY NETWORK INTERFACE:INTERFACE NAME DELTAV PIMARYDELTA-V IP ADDRESS 10.4.0.1
SECONDARY NETWORK INTERFACE:INTERFACE NAME DELTAV PIMARYDELTA-V IP ADDRESS 10.4.0.1• CLICK NEXT TO CONTINUE
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• AS THE WORKSTATION CONFIGURATION EXECUTES, THE PROGRESS LIST UPDATES. WHEN PROMPTED CLICK OK TO LOG OFF
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• LOG BACK AS AN ADMINISTRATOR. WORKSTATIONCONFIGURATION WILL CONTINUE
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• LOG BACK AS ANADMINISTRATOR. AFTER ENTERING A VALID USERNAME &PASSWORD THE DELTA-VSERVICES WILL START AND YOUWILL BE PROMPTED WITH THEDELTA-V LOGON & FLEX LOCK.
DELTA-V WORKSTATION CONFIGURATION (CONT.)
• LOG BACK AS ANADMINISTRATOR. AFTER ENTERING A VALID USERNAME &PASSWORD THE DELTA-VSERVICES WILL START AND YOUWILL BE PROMPTED WITH THEDELTA-V LOGON & FLEX LOCK.
DELTA-V OPERATE
THE DELTA-V OPERATE FUNCTIONS IN TWO MODES:
• CONFIGURE MODE: USED BY ENGINEERS TO CREATE PICTURES
• RUN MODE: USED BY ENGINEERS TO TEST THE PICTURES THEY HAVE CREATED AND BY OPERATORSTO RUN PICTURES IN THE DELTA-V OPERATE APPLICATION
DELTA-V OPERATE DESKTOP
DELTA-V OPERATE DESKTOP IS MADE UPOF THREE WINDOWS:• TOOLBAR WINDOW• MAIN WINDOW• ALARM BANNER WINDOW
RESPONDING TO ALARMS
DELTA-V OPERATE INCLUDES THE FOLLOWING FOUR STANDARD BUTTONS RELATED TO ALARM:
• ACKNOWLEDGE ALARM• ALARM FILTER• ALARM LIST• ALARM SUPPRESS
ALARM PRIORITESEACH ALARM HAS A PRIORITY ASSIGNED TO IT. THERE ARE THREE ALARM PRIORITIES (CRITICAL, WARNING, AND ADVISORY) AND A SPECIAL LOG EVENT THAT IS RECORDED IN THE EVENT CHRONICLE BUT DOES NOT SHOW UP ON THE ALARM BANNER, ALARM LIST, OR THE GRAPHICAL DISPLAYS.
ALARM PRIORITY ALARM COLOR (DEFAULT SETTING)CRITICAL RED
WARNING YELLOW
ADVISORY PURPLE
LOG BLUE
THE ALARM BANNERALARMS ARE MOST VISIBLE ON THE ALARM BANNER THAT APPEARS AT THE BOTTOM OF THE OPERATE DESKTOP. HERE IS AN EXAMPLE OF AN ALARM BANNER
ALARMS ON FACEPLATEFACEPLATES CAN BE OPENED FROM THE OBJECT DATALINK OR FROM THE TOOLBAR.
ACTIVE/UNACK—BLANK FIELDACTIVE/ACKED—CHECKMARKINACTIVE/UNACKED—EMPTY BOX
DELTA-V GROUPS
GROUPS ALLOWS YOU TO DEFINE A SET OF KEYS TO DELTA-V LOCKS THAT CAN BE EASILY ASSIGNED TO A NUMBER OF USERS. THE DEFAULT DELTA-V GROUPS ARE:• MAINTENANCE• OPERATE• SIS ENGINEERING• SIS OPERATE• SIS SUPERVISOR• SUPERVISOR• TUNE
USER ACCOUNTSTHE FOLLOWING TABLE SHOWS THE DEFAULT USER ACCOUNTS:
USER NAME WINDOWS GROUPS DELTA-V GROUPSADMINSTRATOR ADMINISTRATOR, DELTA-V,
DELTA-V ADMINS---
CONFIGURE DELTA-V SUPERVISE
MAINTAINER DELTA-V MAINTENANCE
OPERATOR DELTA-V OPERATE
SIS_CONFIGURE DELTA-V SIS ENGINEERING
SOFTPHASEUSER DELTA-V ---
SUPERVISOR DELTA-V SUPERVISE
BACKING UP SUPPORTING DATATHE DELTA-V SYSTEM CONTAINS IMPORTANT DATA THAT IS NOT BACKED UP BY ANY OF THE DELTA-V BACKUP APPLICATIONS OR COMMANDS. FOLLOWING TABLE LISTS THE MAJOR SUBDIRECTORIES AND FILES IN THE DELTA-V DIRECTORY AND WHAT INFORMATION THEY NEED.
DIRECTORY CONTENTSDeltaV\DVData\amsdevices Directory containing fieldbus device files.
DeltaV\DVData\amshartdevices Directory containing HART device files.
DeltaV\DVData\Bulkedit Directory containing the template, sample format specification files, and sample .txt files for bulk edit
BACKING UP SUPPORTING DATA (CONT.)DIRECTORY CONTENTS
DeltaV\DVData\Charts Directory containing saved Process History View charts
DeltaV\DVData\Charts\Lib Directory containing predefined E+Chart files for module and faceplate parameters. For example, AI_fp.phve contains a chart of the PV parameter of the Analog Input function block and an event log for the module. Process History View opens these files when an operator presses the E+Chart button on the module or function block's faceplate
DeltaV\DVData\Databases Directory containing the active configuration database and any backup databases
BACKING UP SUPPORTING DATA (CONT.)DIRECTORY CONTENTS
DeltaV\DVData\download Directory containing the download scripts for the last downloaded configuration
DeltaV\DVData\Expressions Directory containing expressions created in Control Studio
DeltaV\DVData\Graphics-IFIX Directory containing operator displays and historical data files
DeltaV\DVData\Graphics-iFIX\Pic
Directory containing pre-existing graphics as well as user-created pictures that are used in operator displays
DeltaV\DVData\Import-Export Directory containing files that have data exported from the configuration database
BACKING UP SUPPORTING DATA (CONT.)DIRECTORY CONTENTS
DeltaV\DVData\POWERUP Directory containing download files.
DeltaV\DVData\sound Directory containing *.wav files for audible alarms