COLD STORAGE AND LABORATORIES

ROSLIN OLD TO NEW AND MAKING THE BEST OF WHAT YOU

HAVE.

Old Roslin

OLD Roslin Now

Roslin New

Shared lab space and open plan office

Roslin Office and Lab cooling

Natural Ventilation

Dolly

Old Roslin Site

Freezer Management 2001

• Freezers in various locations.• Not all alarmed.• Call-out procedures unclear.• No regular maintenance.• No emergency decant space.• No clear sample management.

Change

• Freezer locations centralised + alarmed• Dedicated freezer team appointed• Standard Operating Procedures introduced• Daily temperature monitoring• Regular defrosts• Quality Assurance Management input-sample

tracking--easy to use sample tracking encourages uptake of use!

IMPACT

• Efficient use of lab space- equipment and cooling .

• Efficient use of internal Freezer Space.• Easier to identify available freezer space.• Reduction in number of freezers. • Increased sample security. • Risk Register level reduced.

Roslin Freezer Room

Freezer Park Roof Location

Roslin 3rd Floor Freezer Park

Roslin Freezer Measurements

Average KWhr used per Temperature (3 freezers)

8

9

10

11

12

13

14

15

70 75 80

Temperature (C)

Av

g. K

Wh

r

Freezers were all U-725 New Brunswicks, all relatively full. Meters were checked against each other. All over 24 hr period, with 24 hrs allowed between each measurement.

Freezer Temp Setting (C) KWhr

(-20) sm. Beko (A+) -20 0.2

(-20) lg. Ocean Frost Free -20 1.5

(-20) Chest freezer -20 1.6

(+4) Cryotechnics Lab fridge 4 2.01

(+4) Proline (food fridge) 4 0.74

(-80) NB U725 - efficient*(empty) -80 14.4

(-80) Panasonic Sanyo VIP -75 10.3

(-70) Assab (15-20 years old) -70 18

Temperature Real Costs Savings from -80 (£ )

-70 354.78 114.975

-75 427.05 42.705

-80 469.755 0

-70 328.5 105.12

-75 341.64 91.98

-80 433.62 0

-70 308.79 154.395

-75 390.915 72.27

-80 463.185 0

Roslin Freezer Measurements

Costed Savings for Temp increases from -80 per Annum* Further Various Freezer Readings

*At .09 pounds per KWhr

Steps to improvement

• Replace inefficient fridges and freezers. • Encourage sharing-making user cost aware!• Utilise climate to help cool Freezer rooms.• Manage sample tracking –user friendly.• Maintain Freezers and Alarms. 2 visits/year.• Consider -20 walk-in rooms over multiple -20

chest freezers. (20% saving )• Encourage temperatures at -70 over -80

To Do List

• Metering of cooling within freezer rooms- raise cost awareness.

• True archive freezers removed to a secure and efficiently designed building(Freezer Farm)-this would release prime space within buildings to allow either expansion or consolidation!

• Questions?

top related