algorex - cs1140 operators manual (ep5)

44
Cerberus® CS1140 Fire detection system control unit with control console Operating instructions Fire & Security Products Siemens Building Technologies Group Related to software ”Standard international” (EP5)

Upload: mohammedrezaee

Post on 19-Jan-2016

1.255 views

Category:

Documents


158 download

DESCRIPTION

CS1140

TRANSCRIPT

Cerberus® CS1140Fire detection system control unit withcontrol console

Operating instructions

Fire & Security ProductsSiemens Building Technologies Group

Related to software ”Standard international” (EP5)

Data and design subject to change

without notice. / Supply subject to

availability.

� Copyright by

Siemens Building Technologies AG

Wir behalten uns alle Rechte an

diesem Dokument und an dem in ihm

dargestellten Gegenstand vor. Der

Empfänger anerkennt diese Rechte

und wird dieses Dokument nicht ohne

unsere vorgängige schriftliche

Ermächtigung ganz oder teilweise

Dritten zugänglich machen oder

ausserhalb des Zweckes verwenden,

zu dem es ihm übergeben worden ist.

We reserve all rights in this document

and in the subject thereof. By

acceptance of the document the

recipient acknowledges these rights

and undertakes not to publish the

document nor the subject thereof in

full or in part, nor to make them

available to any third party without our

prior express written authorization,

nor to use it for any purpose other

than for which it was delivered to him.

Nous nous réservons tous les droits

sur ce document, ainsi que sur l’objet

y figurant. La partie recevant ce

document reconnaît ces droits et elle

s’engage à ne pas le rendre

accessible à des tiers, même

partiellement, sans notre autorisation

écrite préalable et à ne pas

l’employer à des fins autres que

celles pour lesquelles il lui a été

remis.

Ci riserviamo ogni diritto relativo al

presente documento e sull’oggetto

illustrato in esso. La parte che riceve

il documento si impegna a non

renderlo accessibile a terzi, né per

intero né in parte, senza la nostra

previa autorizzazione scritta ed a non

usarlo per altri scopi di quello per il

quale è stato rilasciato.

10.1999

I

Fire & Security Products

Siemens Building Technologies Group

Content

Quick reference instructions 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Control console layout 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating access 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Message categories 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Terminology ’Area’, ’Section’and ’Zone’ 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Normal operation 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating states ’Present’ and ’Absent’ 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Alarm 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Detector zone, temporary isolation 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Isolation of detectors 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fault 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

’Detector test’ mode 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

’Installation test’ mode 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

’Renovation’ mode 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote transmission OFF/ON 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Alarm devices OFF/ON 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Printer OFF/ON 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Printer: Paper replenishing 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Lamp test 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Alarm counter 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Event memory 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Set clock and date 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Overview operating menus 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10.1999

II

Fire & Security Products

Siemens Building Technologies Group

e1033e10.1999

1

Fire & Security Products

Siemens Building Technologies Group

Quick reference instructions

Alarm, what to do ?

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

Acknowledge

Reset

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetectoron faultofftest mode

This display can show 2 messages spontaneously.

=> Upper section shows 1st message

=> Lower section shows 2nd message

If more than 2 messages have been reported,scrolling becomes necessary in order to show allreported messages in the ’upper section’ (one afterthe other).

=> Scrolling is done by pressing key ’scroll’ or with the arrow keys

1st message+ «scroll box»

last message

FIRE BRIGADE REQUESTED Total: 201 AUTOM.FIRE ALARM

Main building / 1st floorroom 104

02 AUTOM.FIRE ALARMMain building / 1st floorroom 104

select MESSAGE CATEGORY F1:function

uppersection

lowersection

C A

B

C

ALARM

select MESSAGE CATEGORY F1:function

FIRE BRIGADE REQUESTED Total: 1

Main building / 1st floor01 AUTOM.FIRE ALARM

1. Press the ’acknowledge’ key

2. Read top line of display

FIRE BRIGADE in 2:35 Total: 1

01 AUTOM.FIRE ALARMMain building / 1st floorroom 104

select MESSAGE CATEGORY F1:function

CALL fire brigade: TEL.118 Total: 101 AUTOM.FIRE ALARM

Main building / 1st floorroom 104

select MESSAGE CATEGORY F1:function

=> 3 different messages possible

⇒ Alarm message to fire brigade already transmitted

⇒ Alarm message to fire brigade will be sent in ..min ..sec

– remaining time shown as ’countdown’

No transmission to fire brigade⇒ call fire brigade by telephone

either; if– remote transmission isolated– remote transmission device blocked or defective– not connected to fire brigade

3. Read fire location on the display

4. Go to indicated fire location

if fire brigade is already informed: => try to stop the fire brigade

if time count down runs: => immediately press key ’reset’

if no transmission to fire brigade: => press key ’reset’

5. Decide on ’emergency’ or ’minor incident’

Emergency: if fire brigade is already informed: => save people, guide fire brigade, fight the fire

if time count down runs: => immediately actuate nearest call point

if no transmission to fire brigade: => call fire brigade by telephone

Minor incident:

room 104

A

B

B

Alarm reset:

Alarm reset is only possible via access password (see page 6)As long as a detector still detects a fire phenomena (smoke, heat) the alarm cannot be reset. In order to remove suchan alarm the corresponding detector zone has to be isolated (see page 8)

e1033e10.1999

2

Fire & Security Products

Siemens Building Technologies Group

Quick reference instructions

How to start operating ?

Acknowledge

Reset

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetectoron faultofftest mode

INFORMATION Total: 101 present

Main building

select MESSAGE CATEGORY F1:function

WED 21-FEB-1996 13:23

password:- or TURN the key switch

0..9, del:password ok:enter c:end

password:CORRECT

authorized access level: 2.1

1. Press key

2. Enter password and press key or turn key switch (if equipped)

F1

ok

3. Select function in ’MAIN MENU’ with arrow keysthen press key ok

� option selected is shown inverse

Function ’FIRE detection’� to navigate to a fire detection SECTION or ZONE or

ELEMENT (= detector) in order to– isolate or reactivate a detector zone(s)– set a detector zone (s) on mode ’detector test’ or to terminate ’detector test’ , etc.

Function ’Extinguishing section’� to navigate to an extinguishing SECTION in order to

– isolate detector zones related to the selected extinguishing section– set detectors related to the selected extinguishing section on mode ’detector test’ or to terminate– test the extinguishing ’alarm horn’ or ’warning panel’ , etc.

Function ’CONTROL in-/ outputs’� to select a control SECTION or ZONE in order to

– isolate or reactivate a fire control function (e.g. air-conditioning shut down, etc.)– initiate manually or deactivate a fire control function, etc.

Function ’GEOGRAPHICAL location’� to select any SECTION or ZONE in order to

– isolate or reactivate a zone, etc.

Function ’DEVICE level’� to initiate a specific function such as

– lamp test– printer test, also to enable or disable the printer, etc.

Function ’LOGICAL address (CSX. no.)’� to jump directly to a known logical location

– the complete address (AREA no./ SECTION no./ ZONE no./ELEMENT no.) must be known

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

ALARM

e1033e10.1999

3

Fire & Security Products

Siemens Building Technologies Group

Introduction

This Cerberus fire detection installation consists of the following components:

System components Equipped

Type of operating console ?

Type ’AlgoPilot’

Type ’CI1145’

Series of fire detectors ? Interactive detectors

Includes also extinguishing SECTIONS ?CO2

waterN2

..........

Printer connected ?

Remote transmission connected ?

Location

Cerberus Alarm Concept activated ?

–> operating ’present’ / ’absent’ used ?

Multi area installation ?

Duration of emergency power operation ?

..............................

..............................

..........hours

�� yes no

�� yes no

�� yes no

Addressable detectors

Collective detectors

�� yes no

This table to be filled in by the commissioning engineer.

Make sure that all system operators of the fire detection installation are sufficiently instructed. If there is any doubtabout any function or measures to be taken call the local service organization for assistance.

e1033e10.1999

4

Fire & Security Products

Siemens Building Technologies Group

Control console layout

Typ ’AlgoPilot’User interface to operate the fire detection system.

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

AlgoPilot CT11

Acknowledge

Reset

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

ALARM

4

5

6

8

1a

1b

1c

7

FIRE detectionEXTINGUISHING sections

GEOGRAPHICAL location

Logical address (CSX.no.)DEVICE level

v/^ok:selection F1:function

MAIN MENU

CONTROL in- / outputs

12

3

1 Text display with red and yellow illumination: red for danger messages («Alarm») yellow for status changes or during operator actions (automatically switched off when not operated) dark, if no danger message («Alarm») is pending and no operator activity is in progress

Example: Main menu

1a Typ of menu list

1b Selected operating function

1c Instruction bar

2 Warning panel ’ALARM’ lights up when an alarm signal is pending

3 Display fields, partially with command keys : display the operating states of the fire detection system

4 Acknowledge key to confirm that the operator has received a message message not acknowledged � yellow LED is flashing

5 Reset key to reset (cancel) all currently reported alarms message acknowledged, but not reset � yellow LED is flashing

6 Function key pad for menu operation and password input: The function of F1 and F2 depends on the selected menu ok key to select or execute a command and keys move the line marking (cursor bar with inverted colors) up or down C (clear) key for cancelling the input (del) key deletes the character on the left of the cursor

7 Keylock switch, optional device for access control

8 Key ’multi alarms’, with version ’nordic’ only, to scroll the alarm messages

e1033e10.1999

5

Fire & Security Products

Siemens Building Technologies Group

Control console layout

Typ ’CI1145’User interface to operate the fire detection system.

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

Acknowledge

Reset

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

4

5

6

8

12

1a

1b

1c

7

FIRE detectionEXTINGUISHING sections

GEOGRAPHICAL location

Logical address (CSX.no.)DEVICE level

v/^ok:selection F1:function

MAIN MENU

CONTROL in- / outputs

ALARM

3

1 Text display with yellow illumination: dark, if no danger message («Alarm») is pending and no operator activity is in progress.

Example: Main menu

1a Typ of menu list

1b Selected operating function

1c Instruction bar

2 LED bar ’ALARM’ lights up when an alarm signal is pending

3 Display fields, partially with command keys : display the operating states of the fire detection system

4 Acknowledge key message not acknowledged � yellow LED is flashing to confirm that the operator has received a message

5 Reset key to reset (cancel) all currently reported alarms message acknowledged, but not reset � yellow LED is flashing

6 Function key pad for menu operation and password input: The function of F1 and F2 depends on the selected menu ok key to select or execute a command and keys move the line marking (cursor bar with inverted colors) up or down C (clear) key for cancelling the input (del) key deletes the character on the left of the cursor

7 Keylock switch, optional device for access control

8 Key ’multi alarms’ to scroll the alarm messages

e1033e10.1999

6

Fire & Security Products

Siemens Building Technologies Group

Operating access

There are the following access levels:Access level 1 Everybody � for «Acknowledge» and «Scroll» functionsAccess level 2.1 Operator 1 � with limited privileges (e.g. janitor)Access level 2.2 Operator 2 � with limited privileges (e.g. security officer)Access level 3 Service � with full privileges (for service engineer)

How to get operating access:

Enter the password via the keypad 1 and/or turn the keylock switch 2 (if equipped).

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C 2

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

1

Operator access via keylock switchInsert the key and turn it to the horizontal position.� The operating access (level 2.2) remains while the key is left in the horizontal position

Operator access via passwordThe operator has to enter:– a password (3...8 digits).� password with a particular access level is defined and released by the service engineer

(system configuration)

Note:

The main menu is only visible after entering a password (default: access level 2.1):

Log in

4. Press F1 key� an entering box is displayed

5. Enter the password and press the ok key

� The confirmation «password CORRECT» or«password INCORRECT» is displayed

To cancel keying errors press the keyC

6. start operation

Log out

Is not required because operating is automatically inhibited if nokey is pressed within a certain time (time–out 2...10 minutes; setby the service engineer).

WED 28-OCT-1997 13:23

password:- or TURN the key switch

0..9, del:password ok:enter c:end

password:CORRECT

authorized access level: 2.1

MAIN MENU

FIRE sectionEXTINGUISHING sectionCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)^/v ok:select F1:function

e1033e10.1999

7

Fire & Security Products

Siemens Building Technologies Group

Message categories

There are the following message categories:

Alarms � danger messages acquired by the system Priority 1

Faults � messages that require an immediate response Priority 2

Isolation � system components out of service Priority 3

Information � messages that do not require an immediate response Priority 4

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

1

Acknowledge

Reset

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

FAULTS Total: 101 detector

Main building / 1stfloorroom 104

select MESSAGE CATEGORY F1:function

01 detector zone OFFMain building / 1stfloorroom 104

select MESSAGE CATEGORY F1:function

01 absentMain building

select MESSAGE CATEGORY F1:function

ISOLATION Total: 1

INFORMATION Total: 1

2 3 4 5 6 7 8

01 AUTOM.FIRE ALARMmain building / 1st floorroom 104

select MESSAGE CATEGORY F1:function

FIRE BRIGADE REQUESTED Total: 1ALARM

1 Information display field

Press key 2 to display the information list.– Certain information messages are displayed spontaneously (for example warnings) if no message with a higher priority is pending.

3 Isolation display field

Press key 4 to display the list of disabled system components.– This message type is displayed spontaneously if no message with a higher priority is pending.

5 Alarms display field

Press key 6 to display the list of alarms.– This message type is always displayed spontaneously and overwrites all other message categories

7 Faults display field

Press key 8 to display the list of existing faults.– This message type is displayed spontaneously if no message with a higher priority is pending.

Note

Switching from one message category to another is always possible by pressing the corresponding selection key. If alower priority is selected, the system always goes back, to that message category with the highest priority after ashort time-out.

e1033e10.1999

8

Fire & Security Products

Siemens Building Technologies Group

Terminology ’Area’, ’Section’ and ’Zone’

What is an «Area»?It normally covers a whole building or part of a building and represents also the operating level.This is the logical designation for several, usually adjacent sections

AREA01 main building02 factory

Area ’Main building’

ok:section F2:main menu F1:function

What is a «Section»?It normally covers a floor or part of a floor in a building.This is the logical designation for several, usually adjacent zones

Section «1st floor»

01 ground floor

SECTION ’fire’

02 first floor03 second floor

ok:zone F2:area F1:function

What is a «Zone»?It normally comprises one room of a building (with collective detectors => several rooms)It is the logical designation of a detector group containing at least one detectorAutomatic fire detectors, manual call points and control outputs are always assigned to different ZONES

For this reason we have zones comprising automatic fire detectors zones comprising manual call points zones comprising control outputs

Zone «room 104»

01 room 103ZONES’fire’

02 room 10403 room 105

ok:element F2:section F1:function

e1033e10.1999

9

Fire & Security Products

Siemens Building Technologies Group

Normal operation

What is «Normal operation»?

The system is ready for receiving danger messages

No danger messages (Alarms) and no fault messages are pending and no part of the system is isolated

The green indicator 1 in the display field «System on» is ON

The system can either be in state «Present» or «Absent» (present / absent see page 10)� The operating states «Present» / «Absent» are information messages which means that there is always one

information message pending 2

select MESSAGE CATEGORY F1:function

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C1

2

Acknowledge

Reset

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

01 presentmain building

select MESSAGE CATEGORY F1:function

INFORMATION Total: 1ALARM

e1033e10.1999

10

Fire & Security Products

Siemens Building Technologies Group

Operating states ’manned’ and ’unmanned’

Is the Cerberus Alarm Concept activated? � Yes� No

Basic rulesThe operating states «Present» and «Absent» are only relevant for systems in which the signals for automatic firedetectors and manual call points are processed differently, that means, the Cerberus Alarm Concept is activated.The switchover is possible manually or automatically.

Operating state «manned» (=present)

Means: The operating person responsible for «Alarm» investigation is on site.

Indicator 1 in the display field «Premises manned» is ON.

Operating state «unmanned» (=absent)

Means: The responsible operating person is not on site.

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

1

2 3

Manual switch over from «manned» (present) to «unmanned» (absent) or vice versa(Requires corresponding operator access level)

Note:

For several areas, this function works only, if all areas are in the same state (absent or present).With this function you switch over all areas from presentto absent or vice versa.

1. Switch over by pressing key 2

� Confirmation prompt is displayed

2. Confirm the switchover by pressing the ok key 3

� The new operating state is shown in the display

� In the «Present mode» the state indicator 1 is ON

Note:

The switchover from «Present» to «Absent» (or vice versa) is also possible via the menu.If several organizationally autonomous systems are operated via a common multi-area terminal (areas with presentstate, other areas with absent state) the state can only be changed via the menu, the «Present» state indicator 1 isflashing.

Automatic switchover

From «Absent» to «Present»: � No � Yes, time = . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

From «Present» to «Absent»: � No � Yes, time = . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

actual state: present

switch over ?

INFORMATION Total: 201 present

building A02 present

building B

select MESSAGE CATEGORY F1:function

switched over !

actual state: absent

ok:switch over C:cancel

e1033e10.1999

11

Fire & Security Products

Siemens Building Technologies Group

Alarm

How are alarm messages shown in the text display field?

Room

Room

Corridor

Zone «Room 104»

1st alarmmessage

2nd alarmmessage

Zone «Room 102»

1st message+ «scroll box»

last message

103

102

Room103

Room104

� up to 2 messages can be displayed simultaneously

01 AUTOM.FIRE ALARMmain building / 1stfloorroom 104

02 AUTOM.FIRE ALARMmain building / 1stfloorroom 102

select MESSAGE CATEGORY F1:function

FIRE BRIGADE REQUESTED Total: 2

total amount ofpending messages

bottom line =instruction bar

Supplementary information(if programmed)

How can an intervention text beread out?

1. Press the «Alarms» key and select thedesired message by pressing the key, if necessary (the selected mes-sage is displayed in inverted colors)

2. Press F2 key (message category’Alarms’ selected or acknowledged� The intervention text is displayed

(if programmed)

01 AUTOM.FIRE ALARM plan:063main building / 1st floor 01/01/004room 104

02 AUTOM.FIRE ALARM plan:064Main building / 1st floor 01/01/006room 102

select MESSAGE CATEGORY F1:function

FIRE BRIGADE REQUESTED Total: 2

01 AUTOM.FIRE ALARMmain building / 1st floorroom 104

main building / 1stfloor

FIRE BRIGADE REQUESTED Total: 2

ALM,^/v:scroll F2:interv.text F1:funct.room 102

02 AUTOM.FIRE ALARM

DANGER: hazardeous materials !!-> alert emergency squad

F1:function F2:message C:end

FIRE BRIGADE REQUESTED Total: 2

site plan referencenumber

logical address ofthe alarming zone

intervention text

e1033e10.1999

12

Fire & Security Products

Siemens Building Technologies Group

Alarm cont.

What to do on ALARM ?

� ’FIRE BRIGADE in 4:31 (min)’ ?

� Alarm will be transmitted in the time indicated� yellow LED in the key ’acknowledge’ is flashing

1. Press the Acknowledge key (yellow flashing LED)

� before time is 0:00

2. Read the fire location of the 1st alarm in the upper half of the text display field

3. Go to the fire location

4. Decide on «Emergency» or «Minor incident»:Emergency: immediately actuate manual call point or the key. . . . . . . ’Alarm delay off’. . . . .

� the alarm message is transmitted. . . . . . . . . . . . . . . . . . .

Minor incident: immediately press the Reset key (flashing yellow LED). . . .

� the yellow LED becomes dark, the system reverts to normal operation. . . . . . . . . . . . . . . . . . .

2

1

3

� ’FIRE BRIGADE REQUESTED’ ?

� Alarm is already transmitted� yellow LED in the key ’acknowledge’ is flashing

1. Press the Acknowledge key (yellow flashing LED)

2. Read the fire location of the 1st alarm in the upper half of the text display field

3. Go to the fire location

4. Decide on «Emergency» or «Minor incident»:Emergency: save people, fight the fire. . . . . . .

Minor incident: immediately try to stop the fire brigade, press the Reset key. . . .

� the system reverts to normal operation. . . . . . . . . . . . . . . . . . .

1

3

3

� ’CALL fire brigade: TEL. 118’ ?

� yellow LED in the key ’acknowledge’ is flashing

1. Press the Acknowledge key (yellow flashing LED)

�LED in the Acknowledge key becomes dark. . . . . . . . . . . . . . . . . . . . .

2. Read the fire location of the 1st alarm in the upper half of the text display field

3. Go to the fire location

4. Decide on «Emergency» or «Minor incident»:Emergency: immediately Call the fire brigade (e.g. 118). . . . . . .

� the alarm message is transmitted. . . . . . . . . . . . . . . . . . . .

Minor incident: immediately press the Reset key (flashing yellow LED). . . .

� the yellow LED becomes dark, the system reverts to normal operation. . . . . . . . . . . . . . . . . . .

1

3

Top line on display reports status of remote transmission

FIRE BRIGADE REQUESTED ? ............

’FIRE BRIGADE in .... ’ ? ............

’CALL fire brigade: TEL.118’ ? ............

1

ALARM

2

e1033e10.1999

13

Fire & Security Products

Siemens Building Technologies Group

Alarm cont.

How does the Cerberus Alarm Concept function?When the system operates in «Present» mode, manual call points and automatic fire detectors trigger different ac-tions in the event of an alarm.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Danger message ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Operating mode «Present» ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁOperating mode «Absent»

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Manual call point actuated ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Fire brigade is summoned immediately. ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Fire brigade is summonedimmediately.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Autom. fire detector respondedÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Fire brigade is summoned only after the pre-programmed time.

Alarm response procedure:1. Confirm the alarm within the alarm ac-

knowledgment time (V1) and immediatelygo to the fire location.

2. At the fire location decide on whether this isan emergency or a minor incident.

3. In case of emergency immediately actuatethe nearest manual call point or press theAlarm delay off key on the console.

4. In case of a minor incident immediatelyreset the system, that is, before expirationof the alarm investigation time (V2).

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ

Fire brigade is summonedimmediately.

Alarm acknowledgement time «V1»

This is a countdown time that is active for automatic detectors when thesystem operates in «Present» mode. Checks whether someone acknowledges the danger alarm message withinthe preprogrammed time. On expiration of this time the alarm is transmitted to the fire department. The remaining time is displayed in minutes and seconds.

Alarm investigation time «V2»

This is a countdown time that is active for automatic detectors when thesystem operates in «Present» mode. Limits the time for investigating the fire location to an individually programmed time. On expiration of this time the alarm is transmitted to the fire department. The remaining time is displayed in minutes and seconds. In case of minor incidents, an alarm must be reset before V2 expires.

What to do, if an alarm message cannot be reset ?If this message is displayed on the terminal, you can isolate thecorresponding detector zone by pressing the ok key.If you don’t want to isolate the zone, press the C key or wait untilthis message disappears.As soon as conditions have returned to normal, ISOLATEDZONES must be immediately switched on again.

V1 = minutes. . . . . . . . . . . . . . .

V2 = minutes. . . . . . . . . . . . . . .

** ALARM-RESET currently NOT POSSIBLE***** detector ZONE(S) still in alarm***

NO isolation -> press key ’C’

in order to ISOLATE corresp.ZONE(S) -> press key ’ok’

e1033e10.1999

14

Fire & Security Products

Siemens Building Technologies Group

Detector zone, temporary isolation

When does a ZONE have to be isolated?ZONES equipped with automatic fire detectors or manual call points can be temporarily switched off (isolated). Thisis only necessary in exceptional situations, for example, while major construction is in progress:– ZONE with smoke detectors � if smoke or dust is produced by unusual work– ZONE heat detectors � if heat or steam is produced by unusual work– ZONE with manual call point � if there is a possibility of inadvertent actuation

As soon as conditions have returned to normal, ISOLATED ZONES must be immediately switched on again.

NoteAn isolated zone does not generate any alarm-, warning- or fault messages.

ZONE isolation procedure (Example ZONE ’fire’)

1. Press F1 key� Enter password� The MAIN MENU overview is displayed

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press ok key� The SECTIONS overview is displayedPress the key to select the desired SECTION

4. Press ok key� The ZONES overview is displayedPress the key to select the desired ZONE

5. Press F1 key� The FUNCTION LIST ’zone’ is displayedSelect the function ’set zone –> OFF,Press ok key to confirm

� The selected ZONE is isolated� displayed spontaneously (if no messages of higher

priority are pending). ISOLATION Total: 1

01 detector zone OFF main building/1st floor conference room

ok:execute F1:zones C:end

ok:section F2:main menu F1:function

ok:section F2:main menu F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)^/v ok:select F1:function

AREAS01 main building02 factory

SECTION ’fire’01 main building02 factory

ok:element F2:section F1:function

ZONES’fire’01 room 10102 room 10203 storage room04 conference room05 corridor

FUNCTION LIST ’zone’ : set zone -> OFFset zone -> ONset zone -> TESTset zone -> TEST OFFset zone -> RENOVATIONset zone -> RENOVATION OFF

select MESSAGE CATEGORY F1:function

e1033e10.1999

15

Fire & Security Products

Siemens Building Technologies Group

Detector zone, temporary isolation cont.

ZONE reactivation procedure

1. Select the message category by pressing the Isolation keyThe message is displayed in inverted colors

2. Press F1 key� The FUNCTION LIST ’zone’ is displayedPress the key to select the function«set zone –> ON» and press the ok key

� The ZONE is reactivated, that is, the isolation is cancelled

ISOLATION Total: 1

01 detector zone OFF main building/1st floor

ok:execute F1:zones C:end

FUNCTION LIST ’zone’ : set zone -> OFFset zone -> ONset zone -> TESTset zone -> TEST OFFDISCONNECT all elements within zoneCONNECT all elements within zone

ISL,^/v:scroll F1:function

conference room

e1033e10.1999

16

Fire & Security Products

Siemens Building Technologies Group

Isolation of individual detectors

When does a detector have to be isolated ?Only when it is damaged or defective until it is replaced.

NoteAn isolated (element OFF) detector cannot generate any messages.The isolation of detectors only makes sense if the corresponding ZONE is in position ’on’

Isolate a detector via the menuSteps 1 to 4 are identical to «Zone isolation» as described above

5. Press ok key� The ELEMENTS summary is displayedPress the key to select the desired ELEMENT

6. Press F1 key� The FUNCTION LIST ’element’ is displayedPress the key to select the function «set element–>OFF»and press the ok key

� The selected detector is isolated and displayed sponta-neously if no messages of higher priority are pending.

Note

If all elements of a ZONE are OFF, the corresponding zone is automatically isolated and all element isolationmessages are cancelled.The reactivation is only on the level ’ZONE’ possible.

Reactivate a detector (element)

1. Select the message category by pressing the Isolation key.The message is displayed in inverted colors.

2. Press F1 key� The FUNCTION LIST ’element’ is displayedPress the key to select the function «set element–> ON»and press the ok key

� The detector is reactivated

Isolate a detector when a fault message is pending

1. Select the message category by pressing the Faults key, thenselect the desired message by scrolling with the key, if nec-essary. The selected message is displayed in inverted colors.

2. Press F1 key� The FUNCTION LIST ’element’ is displayedPress the key to select the function «set element–>OFF»and press the ok key to confirm

� The detector is reactivated

ELEMENTS ’fire’01 conference room

F2:zone F1:function

02 conference room03 conference room04 conference room

FUNCTION LIST ’element’:poll INFORMATION ’element’

ok:execute F1:element C:end

set element -> OFFset element -> ONACTIVATE elementDEACTIVATE element

ISOLATION Total: 101 detector OFF

select MESSAGE CATEGORY F1:function

main building / 1st floor conference room

FUNCTION LIST ’element’poll INFORMATION ’element’

ok:execute F1:element C:end

set element -> OFFset element -> ONACTIVATE elementDEACTIVATE element

FAULTS

01 detector

FLT,^/v:scroll F1:function

main building / 1st floor room 102

FUNCTION LIST ’element’

poll INFORMATION ’element’

ok:execute F1:element C:end

set element -> OFFset element -> ONACTIVATE elementDEACTIVATE element

ISOLATION Total: 101 detector OFF

select MESSAGE CATEGORY F1:function

main building / 1st floor conference room

e1033e10.1999

17

Fire & Security Products

Siemens Building Technologies Group

Fault

Wath to do in case of reported fault messages?

1. Confirm the message by pressing the Acknowledge key

2. Read the fault location on the display

3. Go to the fault location

4. If the fault cannot be removed call the Cerberus service organization

What remedies are available to the user?

Defective automatic detector

Go to the location of the defective detector,

if the detector is missing:� reinsert the detector

if the detector is defective:� replace it with a spare detector

Important: only replace a defective detector with aunit of the same type.

Defective manual call point

Go the location of the defective call point,

if the glass pane is broken:� replace the glass pane

if there is any other defect:� call the Cerberus service organization

Printer out of paper

Go to the printer,� insert a new paper roll,

see section «Printer: Paper replenishing», page 27

Mains supply failure

Mains failure in the public supply network:� no action required

the emergency power battery supplies the system forat least 12 hours (depending on the user’s specifica-tion up to 72 hours)

Mains supply ok:� check the power fuse (main distribution panel of the building)

and replace the fuse, if it is blown.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁFor all other faults call the Cerberus service organization

FAULTS Total: 1

01 detector

select MESSAGE CATEGORY F1:function

main building / 1st floor room 102

FAULTS Total: 1

01 call point GLASS BROKEN

select MESSAGE CATEGORY F1:function

main building / 2ND floor CORRIDOR

FAULTS Total: 1

01 printer terminal PAPER END

select MESSAGE CATEGORY F1:function

main building / 1st floor conference room

FAULTS Total: 1

01 mains failure

select MESSAGE CATEGORY F1:function

control unit, basement

e1033e10.1999

18

Fire & Security Products

Siemens Building Technologies Group

Mode ’Detector test’

What is the «Detector test» mode for?The mode «Detector test» allows individual on-site function testing of automatic fire detectors and manual call pointswithout generating an alarm message.

Automatic fire detectors

Are actuated with a special detector tester.Interactive detectors are set to the special parameter set ’Test’ in order to achieve a fast activation with the detectortester.

Manual call points are activated depending on the type:– From externally without breaking the glass pane or opening the housing.– Simply by opening the door of the manual call point.

Test alarmIs the active state of automatic fire detectors or manual call points in «Detector test» mode. A test alarm does notgenerate a danger message in the control console. That means that neither acoustical alarm devices nor remotetransmission or any other control functions are activated.

Test alarms are recorded in the event memory and logged spontaneously, if a printer is connected.

How to set detectors or manual call points to mode «Detector test»? This is normally done on the section level, but also possible on the zone level.

It is not possible to set an individual fire detector or manual call point (element) to «Detector test».

Zones or sections set to «Detector test» are displayed spontaneously as a message in the category ’Isolation’

Set all detector zones within a SECTION to «Detector test»

1. Press F1 key� Enter the password� Display: Main MenuPress the key to select the desired menu item.

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press ok key� The SECTIONS overview is displayedPress the key to select the desired SECTION

4. Press F1 key� The FUNCTION LIST ’section’ is displayedWith the key select the function «set all DETECTOR zones–> TEST» and press the ok key (automatic detectors only).

� All zones of automatic detectors that belong to this sectionare set to «Detector test»Indicator «Detector test mode» is onSame procedure for manual call points

ok:execute F1:sections C:end

ok:zone F2:area F1:function

ok:section F2:main menu F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

AREAS01 main building02 factory

SECTIONS01 ground floor02 1st floor

FUNCTION LIST ’section’ : set all DETECTOR zones -> OFFset all DETECTOR zones -> ONset all CALL POINT zones -> OFFset all CALL POINT zones -> ONset all DETECTOR zones -> TESTterminate TEST of all DETECTOR zones

03 lift shaft04 2nd floor

e1033e10.1999

19

Fire & Security Products

Siemens Building Technologies Group

Mode ’Detector test’ cont.

Recommendations for detector test Perform the function test periodically. The interval of this test is determined by the service engineer. Switch only the fire detectors of one SECTION at a time to «Detector test», never the entire building. For manual call points the function test needs to be performed only based on a spot-check. Test automatic fire detectors and manual call points of the same room always separately. Do not set them to «Detector test» simultaneously. After the test work has been completed immediately cancel the mode «Detector test».

Testing of automatic AlgoRex detectors

1. Set the SECTION (or zone) to «Detector test» mode.

2. Place the detector tester on the detector.Observe the marking!� For smoke detectors and multisensor smoke detectors the

detector exchanger and tester DZ1193 is needed:� For heat detectors the detector tester RE6T is required:

The temperature rise is simulated with a hot-air blower

3. Wait until the response indicator on the detector flashes.

4. Remove the detector tester.

� The function test is completed. Go to next detector

NoteSmoke detectors, multisensor smoke detectors and heat detec-tors have different housings (see illustration).

Testing of manual call points

Manual call points DM1101, DM1151 (type KAC)

1. Set the manual call point ZONE to «Detector test» mode.

2. Insert the test key into the opening� «Test alarm» is simulated.

3. Wait until the response indicator of the manual call pointflashes.

4. Remove the test key.

� The function test is completed

Heat detector

Detector testerRE6T

Detector exchangerand tester DZ1193

Neural smoke detector

Smoke detector

Test key

e1033e10.1999

20

Fire & Security Products

Siemens Building Technologies Group

Mode ’Detector test’ cont.

Manual call point (type Cerberus ’indirect operation’)

1. Set the manual call point ZONE to «Detector test» mode.

2. Open the door of the manual call point with the key.

3. Press in the button � «Test alarm» is simulated.

4. Wait until the response indicator of the manual call pointflashes.

5. Close the door.

� The function test is completed

Manual call point (type Cerberus ’direct operation’)

1. Set the manual call point ZONE to «Detector test» mode.

2. Open the door of the manual call point with the key

� «Test alarm» is simulated.

3. Wait until the response indicator of the manual call pointflashes.

4. Close the door.

� The function test is completed

Terminate «Detector test» for all detector zones within a SECTION

1. Press F1 key� The MAIN MENU overview is displayed

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press ok key� The SECTIONS overview is displayedPress the key to select the SECTION that is on ’detectortest’

4. Press F1 key� The FUNCTION LIST ’section’ is displayedWith the key select the function «terminate TEST of allDETECTOR zones» and press the ok key

� The «Detector test» is now cancelled for all detectorzones of this section

key

set all DETECTOR zones -> TEST

ok:execute F1:sections C:end

ok:zone F2:area F1:function

ok:section F2:main menu F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)^/v ok:select F1:function

AREAS01 main building

SECTIONS01 ground floor02 1st floor

FUNCTION LIST ’section’ : set all DETECTOR zones -> OFFset all DETECTOR zones -> ONset all CALL POINT zones -> OFFset all CALL POINT zones -> ON

terminate TEST of all DETECTOR zones

03 lift shaft04 2nd floor

e1033e10.1999

21

Fire & Security Products

Siemens Building Technologies Group

Mode ’Detector test’ cont.

Poll ’test alarms’ in the event memory

1. Press F1 key� Enter the password� Display: Main MenuPress the key to select DEVICE level

2. Press ok key� The STATIONS overview is displayedPress the key to select the desired STATION

3. Press F1 key� The function list Control unit is displayedPress the key to select ’poll EVENT MEMORY’

4. Press ok key� The function list Event Memory is displayedPress the key to select ’poll all TEST ALARM’messages

� The TEST Alarms are displayeduse the ^/v to poll the test alarms

ok:function unit F1:function

poll all INFORMATION messages

ok:execute F1:station F2:->date/time

ok:zone F2:area F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)^/v ok:select F1:function

STATIONS01 CC1142 CBUS no1

FUNCTION LIST ’control unit’:poll INFORMATION ’control unit’poll EVENT MEMORY (’control unit’)

FUNCTION LIST ’event memory’: poll all messagespoll all DANGER messages

poll all DISCONNECTION messages

poll all TEST-ALARM messages

set PRINTERset PRINTER (’control unit’)-> OFF

02 CI1142 CBUS no205 CT1142 CBUS no5

set PRINTER (’control unit’)-> ON

^/v:scroll F1:print F2:->date/time

EVENT MEMORY**** TO OF LIST ****03-SEPT-1997 16:15:52 INFORMATION +detector TEST ACTIVATION main building / 1st floor room 10204-SEPT-1997 09:00:59 INFORMATION

poll all FAULT messages

e1033e10.1999

22

Fire & Security Products

Siemens Building Technologies Group

Mode ’Installation test’

What is the mode «Installation test» for?The mode «Installation test» allows to test the correct function of the whole fire detection system including fire con-trols, acoustical alarm devices, etc. All functions remain enabled.Make sure that the remote transmission is switched off or the fire department is informed about the test activities.

In the mode ’Installation test’ interactive detectors become more sensitive and respond faster (response behavioras in mode «Detector test»).

The mode ’Installation test’ shall be carried out only by security staff and serves basically to test the alarmorganization and fire controls.

After the test work has been completed immediately cancel the mode «Installation test».

Mode «Installation test» is normaly enabled and disabled on the level ’ZONE’ but also possible on the level ’SEC-TION’

Setting a zone to mode «Installation test»

1. Press F1 key� The MAIN MENU is displayed

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press ok key� The SECTIONS overview is displayedPress the key to select the desired SECTION

4. Press ok key� The ZONES overview is displayedPress the key to select the desired ZONE

5. Press F1 key� The FUNCTION LIST ’zone’ is displayedWith the key scroll to the function «set zone–> INSTALLATION TEST» and press ok key

� The ZONE is set to mode «Installation test»

Termination of mode «Installation test» of a zone

1. Press the Information key and select the desired message bypressing the key, if necessary. The selected message is dis-played in inverted colors.

2. Press F1 key� The FUNCTION LIST ’zone’ is displayedWith the key scroll to the function «set zone–> INSTALLATION TEST OFF» and press the ok key

� The ZONE is set to normal operation mode

ok:element F2:section F1:function

ok:zone F2:area F1:function

ok:section F2:main menu F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

AREAS01 main building

SECTIONS01 ground floor02 1st floor

ZONES ’fire’01 room 101

03 lift shaft04 2nd floor

’fire’

02 1st floor03 storage room04 conference room05 corridor

ok:execute F1:zones C:end

FUNCTION LIST ’zone’ : set zone -> TEST OFFset zone -> RENOVATIONset zone -> RENOVATION OFFACTIVATE zone

set zone -> INSTALLATION TEST OFFset zone -> INSTALLATION TEST

INF,^/v:scroll F2:detail F1:function

INFORMATION Total: 101 detector zone INSTALL. TEST

ok:execute F1:zones C:end

FUNCTION LIST ’zone’: set zone -> TEST OFFset zone -> RENOVATIONset zone -> RENOVATION OFFACTIVATE zone

set zone -> INSTALLATION TEST OFFset zone -> INSTALLATION TEST

main building / 1st floor conference room

e1033e10.1999

23

Fire & Security Products

Siemens Building Technologies Group

Mode ’Renovation’

What is the «Renovation» mode for?In «Renovation» mode, automatic detectors are much less sensitive. This may be required while unusual work is inprogress (e.g. during renovation of a building).The fire detection system remains working, the remote transmission of alarm and fault messages is enabled. Manualcall points work as in normal operation mode.

Detectors in the mode ’Renovation’ are from the insurance and approval point of view out of order. This is why the’isolation’ message is generated. Mode ’Renovation’ is enabled and disabled on the level ’ZONE’ only.Mode ’Renovation’ is enabled and disabled on the level ’ZONE’ only.

Setting a zone to mode «Renovation»

1. Press F1 key� The MAIN MENU is displayed

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press ok key� The SECTIONS overview is displayedPress the key to select the desired SECTION

4. Press «ok» key� The ZONES overview is displayedPress the key to select the desired ZONE

5. Press F1 key� The FUNCTION LIST ’zone’ is displayedWith the key scroll to the function «set zone–> RENOVATION» and press ok key

� The ZONE is set to mode «Renovation»

Termination of mode «Renovation» of a zone

1. Press the Isolation key and select the desired message bypressing the key, if necessary. The selected message isdisplayed in inverted colors.

2. Press F1 key� The FUNCTION LIST ’zone’ is displayedWith the key scroll to the function «set zone–> RENOVATION OFF» and press the ok key

� The ZONE is set to normal operation mode

ok:element F2:section F1:function

ok:zone F2:area F1:function

ok:section F2:main menu F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

AREAS01 main building

SECTIONS01 ground floor02 1st floor

ZONES ’fire’01 room 101

03 lift shaft04 2nd floor

’fire’

02 1st floor03 storage room04 conference room05 corridor

ok:execute F1:zones C:end

FUNCTION LIST ’zone’: set zone -> TEST OFFset zone -> RENOVATIONset zone -> RENOVATION OFFACTIVATE zone

set zone -> INSTALLATION TEST OFFset zone -> INSTALLATION TEST

ISL,^/v:scroll F1:function

ISOLATION Total: 101 detector zone RENOVATION

ok:execute F1:zones C:end

FUNCTION LIST ’zone’: set zone -> TEST OFFset zone -> RENOVATIONset zone -> RENOVATION OFFACTIVATE zone

set zone -> INSTALLATION TEST OFFset zone -> INSTALLATION TEST

main building / 1st floor conference room

e1033e10.1999

24

Fire & Security Products

Siemens Building Technologies Group

Remote transmission OFF/ON

This system is equipped with a remote transmission facility

for FIRE ALARM � Yes, destination: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

� No

for FAULT � Yes, destination: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

� No

What is «Remote transmission»?Remote transmission establishes a transmission path to the fire department in the event of a FIRE ALARM.For FAULT there is normally a separate path established.

When is the remote transmission switched off?Normally the remote transmission operates in active stand-by, it is only switched off in special cases, for example, fortesting the control functions. For this test the Remote alarm off key 1 on the control console is pressed. The«OFF» state is signalled by the indicator 2 .

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

12

Switching the remote transmission OFFPress key 1

(Requires corresponding operator access levels)

� The corresponding isolation message is displayed� Indicator 2 turns on

� The FIRE ALARM remote transmission is switched off

Switching the remote transmission ONPress key 1

� Indicator 2 turns off

� The FIRE ALARM remote transmission is switched to standby

Note

The remote transmission can also be switched OFF and ON via the menu, separately for «Alarm» and «Fault».The remote transmission must be periodically checked by activating a manual call point. The fire department must benotified before the test is initiated.

ISOLATION Total: 201 remote transmission ’fire’ OFF

select MESSAGE CATEGORY F1:function

main building 01 remote transmission channel FIRE02 remote transmission ’fire’ OFF factory 01 remote transmission channel FIRE

e1033e10.1999

25

Fire & Security Products

Siemens Building Technologies Group

Alarm devices OFF/ON

When do alarm devices (horns, sirens, etc.) have to be switched OFF?Normally the alarm devices operate in active stand-by. They are only switched off in special cases, for example, fortesting the control functions.

1 2 3

4 5 6

7 8 9

ok

F2

F1

0 C

Alarms FaultsIsolationInformation

Alarm device Alarm deviceAlarm devicePremisesactive faultoffmanned

Remote alarm Remote transmissionRemote alarmAlarm delayactive faultoffoff

System SystemControl functionDetector on faultofftest mode

12

Switching the alarm devices OFFPress key 1

� The corresponding isolation message is displayed� Indicator 2 turns on

� The alarm device is switched OFF

Switching the alarm devices ONPress key 1

� Indicator 2 turns on

� The alarm device is switched to stand-by

Note

The alarm devices can also be switched OFF and ON via the menu.

ISOLATION Total: 801 external horn OFF

select MESSAGE CATEGORY F1:function

main building external horn (horn II)02 internal horn OFF main building internal horn (horn I)

e1033e10.1999

26

Fire & Security Products

Siemens Building Technologies Group

Printer OFF/ON

This system is equipped with a printer � Yes Level of operating access:� control unit� terminal

� No

When does the printer have to be switched OFF?Normally the printer (if installed) operates in active stand-by. It is only switched off in special cases (for example tochange the paper). The printer can be switched OFF and ON via the menu. The «OFF» state is shown on the display.

Switching the printer OFF

1. Press F1 key� The MAIN MENU is displayedWith the key choose the function «DEVICE level»

2. Press ok key� The STATIONS overview is displayedPress the key, if necessary, to select the desired station(control unit or terminal)

3. Press F1 key� The FUNCTION LIST ’control unit’ is displayedPress the key to select «set PRINTER –> OFF» andpress the ok key

� The printer is switched OFF

Switching the printer ON

1. Press the Isolation key and select the desired message bypressing the key, if necessary. The selected message isdisplayed in inverted colors.

2. Press F1 key� The FUNCTION LIST ’control unit’ is displayedWith the key select the function «set PRINTER –> ON»and press the ok key

� The printer is switched ON

ok:execute F1:stations C:end

ok:function unit F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

STATIONS01 control unit CC1140 ground floor

FUNCTION LIST ’control unit’:poll INFORMATION ’control unit’

ISL,^/v:scroll F1:function

ISOLATION Total: 1

01 printer control unit OFF control unit CC1140 ground floor

02 terminal CT11 corridor 1st floor

poll EVENT MEMORY (control unit)set printer (control unit) -> OFFset printer (control unit) -> ONinitiate PRINTER TEST (control unit)

ok:execute F1:stations C:end

FUNCTION LIST ’control unit’:poll INFORMATION ’control unit’poll EVENT MEMORY (control unit)set printer (control unit) -> OFFset printer (control unit) -> ONinitiate PRINTER TEST (control unit)

e1033e10.1999

27

Fire & Security Products

Siemens Building Technologies Group

Printer B2Q191: Paper replenishing

Valid for this system � Yes, system equipped with printer B2Q191� No printer of this type installed

1 Switch off printer firstSwing out printer unit

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

2 Remove the usedpaper roll

3 Lift the paper flap and andslide a new paper roll overthe spindle

4 Press the leading edge of the paperlightly against the flap and feed it into theprinter through the slot.Push down the release lever A to insertthe paper.

A

5The paper can betransported by means ofthe knurled wheel

6 Thread the leading edgeof the paper around thetake-up roller and fix itwith the clamp

7 Press the winding up keySwitch on printer again

Spare paper rollsCerberus part no. 379 977 (= 4 pcs.)or – JUJU TP 50KS-A

– HONSHU PS 65 B1– MITSUBISHI F-200 U7X

Print intensityIf the print intensity is too low, call the Cerberus service organization.

e1033e10.1999

28

Fire & Security Products

Siemens Building Technologies Group

Lamp test

What is the «Lamp test» used for?For testing the correct functioning of all indicators (LEDs), the display, and the alarm buzzer.All visual and audible devices of the control console are activated for a few seconds.

Initiate lamp test

1. Press F1 key� The MAIN MENU is displayedWith the key choose the function «DEVICE level»

2. Press ok key� The STATIONS overview is displayedPress the key to select the desired station (terminal)

3. Press F1 key� The FUNCTION LIST ’terminal’ is displayedPress the key to select «initiate LAMP TEST» and pressthe ok key

� The lamp test is initiated ok:execute F1:stations C:end

ok:function unit F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

STATIONS01 control unit CC1140 ground floor

FUNCTION LIST ’terminal’:poll INFORMATION ’terminal’

02 terminal CT11 corridor 1st floor

set contrast of DISPLAYinitiate LAMP TEST

set sound level of BUZZERpoll EVENT MEMORY (terminal)set PRINTER (terminal) -> OFF

e1033e10.1999

29

Fire & Security Products

Siemens Building Technologies Group

Alarm counter

What is the purpose of polling the alarm counter?The alarm counter shows the number of past alarm events.

Polling alarm counter

1. Press F1 key� The MAIN MENU is displayed

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press F1 key� The FUNCTION LIST ’area’ is displayedPress the key to select «poll COUNTER ’fire alarms’» or«poll COUNTER ’remote alarms’» and press the ok key

� The number of alarms is displayed ok:execute F1:areas C:end

ok:section F2:main menu F1:function

MAIN MENU

DEVICE level

EXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL location

FIRE detection

logical address (CSX.no.)^/v ok:select F1:function

AREAS

FUNCTION LIST ’area’:switching PRESENT/ABSENT

01 main building

reset COUNTER ’fire alarms’poll COUNTER ’fire alarms’

poll COUNTER ’remote alarms’external HORN -> ONexternal HORN -> OFF

COUNTER ’fire alarms’ : 4

e1033e10.1999

30

Fire & Security Products

Siemens Building Technologies Group

Event memory

Polling event memory of an ’AREA’

1. Press F1 key� The MAIN MENU is displayed

2. Press ok key� The AREAS overview is displayedPress the key to select the desired AREA

3. Press F1 key� The FUNCTION LIST ’area’ is displayedPress the key to select «poll EVENT MEMORY»

4. Press ok key� The FUNCTION LIST ’event memory’ is displayedPress the key, if necessary, to select the desired function and press the ok key

� The display now shows the desired list.Either the latest entry is visible completely, older entries(if existing) can be scrolled by pressing the key

Note

with the key F2 :–>date/time a entry of a particular date/time can be selected and displayed.

Printing selected entries of the event memorySteps 1..4 are identical to «Polling event memory of an area» as described above

5. Press F1 key� The ’printout EVENT MEMORY’ menu is displayedPress the F2 key to print all entries or select desired range of date and time to printout particular events.

Use the and keys to set date and time and pressthe F1 key to select the next field. Press the ok key to print out selected entries.

� During the print out procedure on the bottom line a flashing”printing” in inverted coulors is displayed.

Note

The event memory can only be printed out, if the printer is connected to the operated terminal.

ok:execute F1:areas C:end

ok:section F2:main menu F1:function

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

AREAS01 main building

FUNCTION LIST ’area’:REMOTE transm. ’fire’ -> OFF

^/v:scroll F1:print F2:->date/time

EVENT MEMORY machine building

ok:set F1:nest field F2:print all

printout EVENT MEMORY

... printing ...

printout EVENT MEMORY

VV

02 machine building03 warehouse building

poll EVENT MEMORY

REMOTE transm. ’others’ -> ONREMOTE transm. ’others’ -> OFFREMOTE transm. ’fault’ -> ONREMOTE transm. ’fault’ -> OFF

ok:execute F1:areas F2:->date/time

FUNCTION LIST ’event memory’:

poll all TEST-ALARM messages

poll all messagespoll all DANGER messagespoll all FAULT messagespoll all DISCONNECTION messagespoll all INFORMATION messages

engine room21-FEB-1996 11:26:43 INFORMATION -detector zone INSTALL. TEST machine building compressor room

Printout starts at: 08:00 21-FEB-1996

Printout stops at: 08:00 21-FEB-1996

e1033e10.1999

31

Fire & Security Products

Siemens Building Technologies Group

Set clock and date

Normally the date and time do not have to be corrected!The date and time are set by the service engineer when installing the system.– The summer/winter time changeover is performed automatically.� Time and date are always displayed when the password is entered.

Setting the clock1. Press F1 key

� The MAIN MENU is displayed

2. Press F1 key� The FUNCTION LIST ’installation’ is displayed

3. Press ok key� An input prompt is displayedEnter the current time and press the ok key(2 digits each for hours / minutes / seconds)

� The new time is read in and loaded

Setting the date

1. Press F1 key� The MAIN MENU is displayed

2. Press F1 key� The FUNCTION LIST ’installation’ is displayedPress the key to select the function «set DATE»

3. Press ok key� An input prompt is displayedEnter the current date and press the ok key(2 digits each for day / month / year)

� The new date is read in and loaded

0..9,del:edit ok:set C:end

ok:execute F1:main menu C:end

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

FUNCTION LIST ’installation’:

re-configuration C-bus

SET CLOCK

ok:execute F1:zones C:end

FUNCTION LIST ’installation’:set CLOCK

set CLOCKset DATE

HHMMSS

MAIN MENUFIRE sectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

set DATEre-configuration C-bus

0..9,del:edit ok:set C:end

SET DATE

DDMMYY

e1033e10.1999

32

Fire & Security Products

Siemens Building Technologies Group

Overview operating menus

FUNCTION LIST ’area’switching PRESENT/ABSENT – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’fire alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . reset COUNTER ’fire alarms’ – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’remote alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> START – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> STOP – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate TEST alarm HORN – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll EVENT MEMORY – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’section’set all DETECTOR zones –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR zones –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all CALL POINT zones –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all CALL POINT zones –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all ZONES –> OFF – (�) (�) (�). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all ZONES –> ON – (�) (�) (�). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR zones –> TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate TEST of all DETECTOR zones – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all CALL POINT zones –> TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate TEST of all CALL POINT zones – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR ZONES –> INSTALL. TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate INSTALL.TEST of all DET.zones – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’zone’set zone –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> TEST OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> RENOVATION – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> RENOVATION OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTIVATE zone – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> INSTALLATION TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> INSTALLATION TEST OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’element’poll INFORMATION ’element’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set element –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set element ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTIVATE element – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEACTIVATE element – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHANGE parameter set – – (�) (�). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . parameter set -> DEFAULT – – (�) (�). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AREAS...

ZONES...

ELEMENTS...

ok

ok

ok

ok

F1

F1

F1

F1

F1

Note:F1 = press key ok = press key

FUNCTION LIST ’installation’set CLOCK – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set DATE – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . re-configuration C-bus – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 2.1 2.2 3

Access level

� � � �

FUNCTION LIST ’event memory’poll all messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all DANGER messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all FAULT messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all DISCONNECTION messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all INFORMATION messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all TEST-ALARM messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ok

F1

ok

SECTIONS...

select FIRE section

see appendix 2

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

e1033e10.1999

33

Fire & Security Products

Siemens Building Technologies Group

Overview operating menus cont.

FUNCTION LIST ’area’switching PRESENT/ABSENT – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’fire alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . reset COUNTER ’fire alarms’ – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’remote alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> START – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> STOP – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate TEST alarm HORN – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll EVENT MEMORY – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’section’BLOCKING autom.extinguishing – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ENABLING autom.extinguishing – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BLOCKING autom.& man. extinguishing release – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . ENABLING autom.& man. extinguishing release – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR zones –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR zones –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR zones –> TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate TEST of all DETECTOR zones – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all DETECTOR zones –>INSTALL: TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate INSTALL.TEST of all DET. zones – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set extinguishing control –> REVISION – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate REVISION – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set extinguishing control –> TEST – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminate TEST of exting. control – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate TEST ”horn” – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate TEST ”warning panel” – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’zone’set zone –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> TEST OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> RENOVATION – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> RENOVATION OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTIVATE zone – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> INSTALLATION TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> INSTALLATION TEST OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AREAS...

ZONES...

ok

ok

ok

ok

F1

F1

F1

F1

Note:F1 = press key ok = press key

FUNCTION LIST ’installation’set CLOCK – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set DATE – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . re-configuration C-bus – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 2.1 2.2 3

Access level

� � � �

FUNCTION LIST ’event memory’poll all messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all DANGER messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all FAULT messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all DISCONNECTION messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all INFORMATION messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all TEST-ALARM messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ok

F1

ok

SECTIONS...

EXTINGUISHING sections (details see App endix 1)

FUNCTION LIST ’element’poll INFORMATION ’element’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set element –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set element OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTIVATE element – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEACTIVATE element – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHANGE parameter set – – (�) (�). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . parameter set -> DEFAULT – – (�) (�). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ELEMENTS... F1

see appendix 2

MAIN MENUFIRE sectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

see appendix 1

e1033e10.1999

34

Fire & Security Products

Siemens Building Technologies Group

Overview operating menus cont.

FUNCTION LIST ’area’switching PRESENT/ABSENT – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’fire alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . reset COUNTER ’fire alarms’ – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’remote alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> START – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> STOP – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate TEST alarm HORN – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll EVENT MEMORY – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’section’set all ZONES –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set all ZONES–> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’zone’set zone –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set zone –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTIVATE zone – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEACTIVATE zone – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’element’poll INFORMATION ’element’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DISCONNECT element – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CONNECT element – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACTIVATE element – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEACTIVATE element – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AREAS...

ZONES...

ELEMENTS...

ok

ok

ok

ok

F1

F1

F1

F1

F1

Note:F1 = press key ok = press key

FUNCTION LIST ’installation’set CLOCK – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set DATE – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . re-configuration C-bus – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 2.1 2.2 3

Access level

� � � �

FUNCTION LIST ’event memory’poll all messagespoll all DANGER messagespoll all FAULT messagespoll all DISCONNECTION messagespoll all INFORMATION messagespoll all TEST-ALARM messages

ok

F1

ok

SECTIONS...

control in–/outputs

Note:

for time channels no function available

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

e1033e10.1999

35

Fire & Security Products

Siemens Building Technologies Group

Overview operating menus cont.

FUNCTION LIST ’area’switching PRESENT/ABSENT – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’fire alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . reset COUNTER ’fire alarms’ – – – �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll COUNTER ’remote alarms’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> START – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm HORN –> STOP – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate TEST alarm HORN – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fire’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’others’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> ON – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REMOTE transm. ’fault’ –> OFF – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll EVENT MEMORY – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’section’same as under– FIRE detection– EXTINGUISHING sections– CONTROL in-/outputsbut includes all types of sections

AREAS...

ok

ok

F1

F1

F1

Note:F1 = press key ok = press key

FUNCTION LIST ’installation’set CLOCK – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set DATE – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . re-configuration C-bus – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 2.1 2.2 3

Access level

� � � �

FUNCTION LIST ’event memory’poll all messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all DANGER messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all FAULT messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all DISCONNECTION messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all INFORMATION messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll all TEST-ALARM messages – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ok

F1

ok

SECTIONS...

select GEOGRAPHICAL location

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

e1033e10.1999

36

Fire & Security Products

Siemens Building Technologies Group

Overview operating menus cont.

FUNCTION LIST ’control unit’poll INFORMATION control unit – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll EVENT MEMORY (control unit) – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set PRINTER (control unit) –> OFF – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set PRINTER (control unit) –> ON – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate PRINTER-TEST (control unit) – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’terminal’poll INFORMATION ’terminal’ – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate LAMP TEST – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set contrast of DISPLAY – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set sound level of BUZZER – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . poll EVENT MEMORY (terminal) – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set PRINTER (terminal) –> OFF – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . set PRINTER (terminal) –> ON – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate PRINTER-TEST (terminal) – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate BATTERY LOAD TEST – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUNCTION LIST ’device’poll INFORMATION ’device’ – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DEVICE level

power supply supervision

I�/�O’s of terminal unit B3Q460/80

keys and indicators of CT11 panel

terminal CT11 (CI11)

control unit CC11

ok

F1

F1

F1

F1

F1

F1

ok

ok

ok

okI/O’s of control unit E3X100

(device)

FUNCTION LIST ’event memory’poll all messagespoll all DANGER messagespoll all FAULT messagespoll all DISCONNECTION messagespoll all INFORMATION messagespoll all TEST-ALARM messages

ok

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FBA panel F1

FUNCTION LIST ’event memory’poll all messagespoll all DANGER messagespoll all FAULT messagespoll all DISCONNECTION messagespoll all INFORMATION messagespoll all TEST-ALARM messages

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . initiate BATTERY LOAD TEST – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

power supply supervision F1

FUNCTION LIST ’function unit’poll INFORMATION ’function unit’ – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

FUNCTION LIST ’device’poll INFORMATION ’device’ – – � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

F1

F1

ok(function unit)

(device)

1 2.1 2.2 3

Access level

� � � �

Note:F1 = press key ok = press key

F1

ok

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

e1033e10.1999

37

Fire & Security Products

Siemens Building Technologies Group

Overview operating menus cont.

Note:ok = press key

logical address (CSX. no.)

ok

1 2.1 2.2 3

Access level

� � � �

area / section / zone / element – � � �. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ok

MAIN MENUFIRE detectionEXTINGUISHING sectionsCONTROL in- /outputsGEOGRAPHICAL locationDEVICE levellogical address (CSX.no.)

^/v ok:select F1:function

e1033e10.1999

38

Fire & Security Products

Siemens Building Technologies Group

Notes

e1033e10.1999

39

Fire & Security Products

Siemens Building Technologies Group

Notes

Back10.1999

40

Fire & Security Products

Siemens Building Technologies Group

Document no.

Edition

e1033e

10.1999

Siemens Building Technologies AG

CH�8708 Männedorf

Alte Landstrasse 411

Tel.

Fax

www.cerberus.ch

+41 1 − 922 61 11

+41 1 − 922 64 50

Manual CS11.2

Section 7